Bldg 7 Vol. 18-23.pdf

PDF 1 MB Posted

Attached to
Y1DA--Replace Building 7 and Building 9 Roofs Federal contract opportunity
Solicitation number
36C24620R0093
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 6

About this file

This document package includes final construction documents for replacing the roof on Building 7 at the VA Medical Center in Salem, Virginia. The documents provide specifications for demolishing the existing roof, installing a new roof system, and installing a lightning protection system. Key details include specifications for slate roofing materials and underlayment, roof insulation, flashing, roof drainage, snow retention, and 23 roofing details. The documents also include specifications for installing a Class I copper lightning protection system with air terminals, conductors, mounting hardware, connections to ground rods, bonding to rooftop equipment, and 24 lightning protection details.

The related federal contract opportunity is solicitation number 36C24620R0093 to replace the roofs on Building 7 and Building 9 at the VA Medical Center in Salem, Virginia. The opportunity was issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 6. The solicitation seeks offers to demolish the existing roofs and install new roof systems and lightning protection on both buildings in accordance with the provided specifications.

View the file

Other files for this federal contract opportunity

Other files attached to Y1DA--Replace Building 7 and Building 9 Roofs, newest first.
File Type Posted
Building 7_FINAL SPECIFICATIONS.pdf PDF
P07 Wage Determintions VA20200172 Roanoke.pdf PDF
Bldg 9 Vol. 18-23.pdf PDF
Bldg 7 Vol. 1-8.pdf PDF
Bldg 7 Vol. 9-17.pdf PDF
Bldg 9 Vol. 1-8.pdf PDF
Bldg 9 Vol. 9-17.pdf PDF
36C24620R0093_1.docx DOCX document
Building 9_FINAL SPECIFICATIONS.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FINAL CONSTRUCTION DOCUMENTS

Af fa ir s

Ve te ra ns

Quality Consulting Engineers, PLLC

6277-600 Carolina Commons Drive, #

Indian Land SC 29707 803.207.5450 djones@qualityconsultingengineers.com 23

ROOFING DETAILS

AE304

fa ir s

Ve te ra ns

Quality Consulting Engineers, PLLC

6277-600 Carolina Commons Drive, #

Indian Land SC 29707 803.207.5450 djones@qualityconsultingengineers.com 23

ROOFING DETAILS

AE305

fa ir s

Ve te ra ns

Quality Consulting Engineers, PLLC

6277-600 Carolina Commons Drive, #

Indian Land SC 29707 803.207.5450 djones@qualityconsultingengineers.com 23

ROOFING DETAILS - FLAT ROOF

AE306

3" = 1'-0"F1 RAILING/BALUSTER

3" = 1'-0"F2 CORNER PEDESTAL ELEVATION

3" = 1'-0"B1 BALUSTER

RE

G

IS

TERED ARCHITECT

NORT H CA ROL I N

AC

H

A R L OT T E , N

. C

C

HA

RL

ES WI LL IAM BEV

IN

S

(TYPICAL)

(TYPICAL)

(TYPICAL)

(TYPICAL)

DORMERS

(TYP.)

(TYPICAL)

ROUTE CONDUCTORS NEAR SNOW GUARD

BANDS AND ALONG BUILDING CONTOURS

AND OTHER ARCHITECTURAL FEATURES

WHERE POSSIBLE. (TYPICAL)

RI

DG

E

RI

DG

E

RI

DG

E

RI

DG

E

RI

DG

E

RIDGERIDGE RIDGERIDGE

RI

DG

E

VALLE

Y

HIP

VALLEY

HIP

VALLEY VALLE

Y

VALLEY VALLEY

HIP HIP

CHIMNEY

FLAT/LOW SLOPE

ROOF AREA

VALLEY

HIP

VALLE

Y

HIP

VALLE

YVALLEY

VALLEYVALLEY

HIPHIP

CHIMNEY

RI

DG

E

VALLEY VALLE

Y

HIP

VALLE

YVALLE

Y

HIPVALLEY

VALLEY

DORMERS

(TYP.)

G

GG

G

G G

G G

Approved: Associate Director

Approved: Chief of Staff

Approved: Service Chief th re e inc he s = o ne fo ot on e an d on e-ha lf i nc he s = o ne fo ot on e inc h on e fo ot th re e-qu ar te rs in ch o ne fo ot on e-ha lf i nc h on e fo ot th re e-eig ht s i nc h on e fo ot on e-qu ar te r i nc h on e fo ot on e-eig ht in ch o ne fo ot

DRAWING NO.

Dwg. Of

Project No.

Date

DrawnChecked

Location

Building Number

Project Title

Approved: Medical Center Director

Approved: Chief of Facility Management Svc.

Drawing Title

DateRevisions

Approved: Infection Control Officer

Approved: Safety Manager

Approved: GEMS Coordinator

Approved: Energy Engineer

658-16-101

01/15/2020

BUILDING 7

VA MEDICAL CENTER, SALEM, VA 24153

REPLACE ROOF AND TUCKPOINT (BUILDING 7)

102 3rd Ave., NE Hickory, NC 28601

828.315.9962 www.atriaxgroup.com

2105 Water Ridge Pkwy #450 Charlotte, NC 28217

704.535.6374 www.wmba.net

FINAL CONSTRUCTION DOCUMENTS

Quality Consulting Engineers, LLC

6277-600 Carolina Commons Drive, #350 Indian Land SC 29707

803.207.5450 djones@qualityconsultingengineers.com

QCE Project # 19010 01/15/2020

SCALE: 1/8" = 1'-0"

1.

2. ALUMINUM LIGHTNING PROTECTION SYSTEM COMPONENTS SHALL NOT BE

MOUNTED TO COPPER SURFACES. COPPER COMPONENTS SHALL BE USED

TO AVOID ELECTROLYTIC CORROSION. COPPER LIGHTNING PROTECTION

MATERIALS SHALL NOT BE PLACED ON ALUMINUM, GALVANIZED STEEL,

GALVALUME SURFACES OR ANY OTHER DISSIMILAR METAL SURFACES,

PAINTED OR NOT.

3. GROUNDED METAL BODIES WITHIN THE BONDING DISTANCE DETERMINED

BY NFPA 780 - 2017 EDITION SHALL BE BONDED TO THE SYSTEM IN

ACCORDANCE WITH THOSE REQUIREMENTS.

4. UNDERGROUND METALLIC PIPING FOR EVERY UTILITY ENTERING THE

BUILDING SHALL BE BONDED TO THE NEAREST DOWN CONDUCTOR OR

GROUND ELECTRODE. FIELD VERIFY EXACT LOCATIONS.

5. ADHESIVE USED WITH ADHESIVE AIR TERMINAL BASES AND CONDUCTOR

FASTENERS SHALL BE COMPATIBLE WITH ROOFING MEMBRANE - VERIFY

WITH ROOFING CONTRACTOR.

6. AIR TERMINALS HAVE BEEN LOCATED ON THE ROOF TOP EQUIPMENT AS

BEST DETERMINED BY THE ENGINEER. IF THE METAL THICKNESS OF AN

OBJECT IS 3/16" OR GREATER, AIR TERMINALS MAY BE ELIMINATED IF THE

OBJECT IS PROPERLY CONNECTED TO THE SYSTEM.

7. ROOF TOP METALLIC EQUIPMENT OR OBJECTS NOT SHOWN ON THIS

DRAWING SHALL BE PROTECTED AS REQUIRED TO MEET THE

REQUIREMENTS LISTED ABOVE INCLUDING THE INSTALLATION OF AIR

TERMINALS AND OR BONDING. IF THE METAL THICKNESS OF AN OBJECT IS

3/16" OR GREATER, AIR TERMINALS MAY BE ELIMINATED IF THE OBJECT IS

PROPERLY CONNECTED TO THE SYSTEM.

8. ALL ELEVATIONS ARE APPROXIMATE AND ARE TAKEN FROM AVERAGE

GRADE.

9. AIR TERMINALS SHALL BE PLACED WITHIN 24” OF THE OUTSIDE CORNER OR

EDGE OF THE OBJECT THEY ARE PROTECTING AND SHALL PROJECT A

MINIMUM OF 10" ABOVE THE PROTECTED EDGE OR OBJECT. THE SPACING

BETWEEN AIR TERMINALS ARE NOT TO EXCEED 20 FEET. AIR TERMINALS

THAT EXTEND 24" ABOVE THE PROTECTED EDGE ARE NOT TO EXCEED1 A

SPACING GREATER THAN 25', EXCEPT FOR MID-ROOF AIR TERMINALS (50'

MAX SPACING).

10. ALL LIGHTNING CONDUCTORS ARE TO MAINTAIN A HORIZONTAL OR

DOWNWARD PATH. ALL BENDS IN THE CONDUCTOR SHALL HAVE A RADIUS

BEND OF 8 INCHES OR GREATER, AND SHALL HAVE AN ANGLE BEND OF 90

DEGREES OR GREATER.

11. EACH INDIVIDUAL ITEM OF THE LIGHTNING PROTECTION SYSTEM IS NOT LABELED FOR THE SAKE OF CLARITY. ITEMS ARE INDICATED AT RANDOM LOCATIONS ONLY, BUT A COMPLETE SYSTEM SHALL BE

PROVIDED TO MEET THE REQUIREMENTS LISTED ABOVE.

LPS NOTES

1 CLASS I COPPER HORIZONTAL LIGHTNING CONDUCTOR RUN EXPOSED ON

SLATE ROOF. FASTEN EVERY 3 FEET MAXIMUM WITH COPPER CABLE

HOLDER SET IN ADHESIVE.

2 CLASS I COPPER DOWN CONDUCTOR CONNECTED TO GROUND ROD AND

INSTALLED EITHER: A) CONCEALED IN 1" PVC SCHEDULE 40 CONDUIT PER

THE DOWN CONDUCTOR DETAIL, B) EXPOSED ON EXTERIOR OF BUILDING

IF PERMITTED BY THE VA OR C) BONDED TO INTEGRAL BUILDING STEEL

AT TOP AND BOTTOM OF DOWN CONDUCTOR PENETRATION ONLY IF

STEEL IS 3/16" THICK, AN 8" SQUARE AREA OF WELDING TO STEEL IS

POSSIBLE & THE STEEL IS CONTINUOUS. COORDINATE WITH VA RESIDENT

ENGINEER AND UL INSPECTOR.

4 BOND TO COPPER GUTTER WITH COPPER BONDING LUG AND SECURE

WITH APPROPRIATE SCREW FASTENER.

3 ROUTE CONDUCTORS ALONG AND DOWN CHIMNEY TO MATCH SURFACE

CONTOURS AND ARCHITECTURAL FEATURES WHERE POSSIBLE.

PLAN NOTES

12. ROOF PADS, PAVERS, FLASHINGS OR ANY OTHER SPECIAL ROOFING

MATERIALS REQUIRED FOR THE INSTALLATION OF THE LIGHTNING

PROTECTION SYSTEM SHALL BE FURNISHED AND INSTALLED BY THE

ROOFING CONTRACTOR.

13. ACTUAL JOB SITE CONDITIONS MAY REQUIRE ITEMS SHOWN ON THE

DRAWING TO BE EITHER LOCATED IN DIFFERENT LOCATIONS OR MADE OF

DIFFERENT MATERIALS. ALL CHANGES MADE TO THE LIGHTNING

PROTECTION SYSTEM AND THE COMPLETED INSTALLATION SHALL MEET

OR EXCEED THE REQUIREMENTS LISTED ABOVE.

14. MAXIMUM HEIGHT OF BUILDING ~ 60' ABOVE FINISHED GRADE.

15. IN ORDER FOR THESE SYSTEMS TO BE COMPLETE LIGHTNING PROTECTION

SYSTEMS, THE ELECTRICAL SERVICE, WATER SERVICE AND GAS SERVICE

MUST BE BONDED TO THE NEAREST DOWN CONDUCTOR OR GROUND

ELECTRODE AS WELL AS ANY AND ALL UNDERGROUND METALLIC PIPING

ENTERING THE STRUCTURE. BOND SERVICES WITH TINNED PIPE CLAMP.

16. PROVIDE UL LETTER OF FINDINGS UPON INSPECTION TO ALLOW FOR

FUTURE UL MASTER LABEL AFTER ALL CONNECTED STRUCTURES HAVE

LIGHTNING PROTECTION SYSTEM INSTALLED.

17. BOND ALL METALLIC OBJECTS ON ROOF INCLUDING GUTTER SYSTEM AND

MECHANICAL UNITS/DUCTS/FLUES, LADDERS, HATCHES, ETC.

CLASS I ALUMINUM LIGHTNING

CONDUCTOR (24 STRANDS OF 14 AWG

WIRE - 95 LBS. PER 1000 FEET). SEE

AIR TERMINAL DETAILS FOR METHOD

OF FASTENING. SECURE TO BUILDING

EVERY THREE FEET MAXIMUM. (NOT

USED UNLESS REQUIRED FOR

BONDING TO SIMILAR METALS.)

CLASS I COPPER LIGHTNING

CONDUCTOR (29 STRANDS OF 16 AWG

WIRE - 203 LBS. PER 1000 FEET).

COPPER PARALLEL CABLE

CONNECTOR.

3/4" X 10'-0" COPPER CLAD GROUND

ROD WITH ULTRAWELD CONNECTIONS.

SEE DETAIL "G" AND "H"

ULTRAWELD CONNECTION WITH WELD

METAL. NOT USED THIS PROJECT.

G

LPS LEGEND

18. ISOLATED METAL BODIES THAT SHOW NO CONDUCTANCE TO GROUND

SHALL NOT REQUIRE BONDING. A GROUNDED METAL BODY WITHIN THE

SIX-FOOT RULE SHALL BE BONDED TO THE SYSTEM.

19. CONNECTIONS TO GROUND COUNTERPOISE SHALL BE MADE AT A POINT

NOT LESS THAN 1'-0” BELOW GRADE, AND 2'-0” AWAY FROM FOUNDATION

WALL

20. CONNECTIONS TO GROUND SHALL BE MADE AT A POINT NOT LESS THAN

1'-0” BELOW GRADE, AND 2'-0” AWAY FROM FOUNDATION WALL

21.

22. A LIGHTNING ARRESTOR, PROTECTOR, OR ANTENNA-DISCHARGE UNIT

MUST BE INSTALLED ON EACH ELECTRIC, TELEPHONE, AND TELEVISION

SERVICE ENTRANCE.

CONDUCTORS SHALL MAINTAIN A HORIZONTAL OR DOWNWARD PATH FREE

FROM “U” AND “V” POCKETS. ANY RISE IN HORIZONTAL CONDUCTOR SHALL

NOT EXCEED 8 INCHES. CONDUCTOR MAY RISE UPWARDS AT A RATE OF NO

MORE THAN 3” OF RISE PER 1'-0” RUN.

23. ALL ADHESIVE FIXTURES SHALL BE SET WITH AN ADHESIVE COMPOUND

COMPATIBLE WITH THE ROOFING MATERIAL. ADHESIVES SHALL BE

APPROVED IN ADVANCE BY THE ROOFING CONTRACTOR.

24. CONDUCTOR SHALL BE FASTENED EVERY 3'-0” ON CENTER MAXIMUM.

25. WHEN ANCHORING IN MASONRY, HOLES MADE TO RECEIVE THE BODY OF

THE ANCHOR SHALL BE MADE IN THE BRICK, STONE, OR OTHER MASONRY

UNIT RATHER THAN IN MORTAR JOINTS.

26. BOND TO METALLIC PLUMBING WASTE VENTS ON ROOF AND TO

STRUCTURAL STEEL WITHIN BUILDING.

LIGHTNING PROTECTION SYSTEM SHALL BE INSTALLED BY QUALIFIED

PERSON(S) PER THE LIGHTNING PROTECTION STANDARDS: LPI-175, NFPA

780, UL96A, VA OFFICE OF OCCUPATIONAL SAFETY AND HEALTH, AND VA

DESIGN GUIDE STANDARDS. THESE STANDARDS MUST BE FOLLOWED

DURING THE DESIGN, INSTALLATION, AND INSPECTION OF A LIGHTNING

PROTECTION SYSTEM.

27. THE ROOF LINES OF THIS BUILDING ARE NON-STANDARD AND NEED TO BE

THOROUGHLY SURVEYED. THE ROOF IS ARCHITECTURAL IN NATURE AS

WELL AND EXTRA CARE IS REQUIRED WITH REGARDS TO LPS CONDUCTOR

ROUTING .

ELECTRICAL ROOF PLAN - LPS

28. JOB CONDITIONS MAY DICTATE VARIATIONS IN AIR

TERMINAL, CONDUCTORS, AND GROUND ROD LOCATIONS AND A

THOROUGH SITE SURVEY MUST BE COMPLETED PRIOR TO SHOP DRAWING

FABRICATION.

LIGHTNING PROTECTION SYSTEMS SHALL BE INSTALLED IN A NEAT,

PROFESSIONAL MANNER.

29.

E401

1/2" X 12" GENTLY TAPERED SOLID

COPPER AIR TERMINAL WITH

UNIVERSAL BASE MOUNTED

HORIZONTALLY.

SEE DETAIL "C"

1/2" X 12" GENTLY TAPERED SOLID

COPPER AIR TERMINAL WITH RIDGE

SADDLE BASE.

SEE DETAIL "D"

XX XX

GSBDAJ

E401

ELECTRICAL - ROOF PLAN - LPS

GROUND ROD DETAIL "G"

CLASS I COPPER

LIGHTNING

CONDUCTOR

ULTRAWELD MOLD WITH

WELD METAL

3/4" X 10' COPPER

CLAD GROUND ROD

1" PVC SCH. 40

CONDUIT

TYPICAL BOND TO

BASE OF STEEL COLUMN

ULTRAWELD MOLD WITH

WELD METAL

SEE GROUND ROD

DETAIL "G" FOR

CONTINUATION

STUB OUT PVC

BELOW

FOOTING

CLASS I COPPER

LIGHTNING CONDUCTOR

HLPUL

50H2

1 BOLT PARALLEL CLAMP BONDING LUG BONDING LUG COPPER FLANGE

BONDING PLATE

TINNED

U-BOLT PIPE CLAMP

THRU ROOF DETAIL "T"

CLASS I COPPER LIGHTNING

CONDUCTOR

BIMETAL THRU-ROOF

ASSEMBLY

1" PVC SCHEDULE 40

CONDUIT

CLASS I COPPER LIGHTNING

CONDUCTOR

DOWN CONDUCTOR DETAIL

CLASS I COPPER

LIGHTNING

CONDUCTOR SECURED

EVERY 3' WITH COPPER

CABLE HOLDER SET IN

ADHESIVE

1" PVC SCH. 40

CONDUIT

BRONZE FLANGE

BONDING PLATE (TYP.

OF 2)

AIR TERMINAL DETAIL "C" AIR TERMINAL DETAIL "D"

GENTLY TAPERED AIR

TERMINAL

UNIVERSAL CONCEALED

AIR TERMINAL BASE

MOUNTED HORIZONTALLY

CABLE FASTENER

COPPER, CLASS I

LIGHTNING PROTECTION

CONDUCTOR

AIR TERMINAL ADAPTER

HORIZONTAL BASE

GENTLY TAPERED AIR

TERMINAL

RIDGE SADDLE AIR

TERMINAL BASE

CABLE FASTENER

COPPER, CLASS I

LIGHTNING PROTECTION

CONDUCTOR

RIDGE SADDLE BASE

ALL CONDUCTOR BENDS

SHALL HAVE A RADIUS

OF 8" OR GREATER AND

SHALL HAVE AN ANGLE

BEND OF 90° OR

GREATER.

CONNECT TO

GROUND ROD BELOW

GRADE. -SEE DETAIL

"G"

CLASS I COPPER

LIGHTNING

CONDUCTOR

SEE THRU

ROOF DETAIL

"T"

GROUND ROD TEST WELL DETAIL "H"

1 SCALE: NTS

ELECTRICAL - LPS - DETAILS

GROUND PLATE DETAIL "G"

ALTERNATE METHOD

24"

24"

1/4"

COPPER GROUND PLATE, TO BE USED AS AN

ALTERNATIVE INSTALLATION METHOD, WHERE ROCK

IS ENCOUNTERED LIMITING THE BURAL DEPTH;

BURY AT A MINIMUM OF 24" BFG

BASE METHOD

E801

XX XX

GSBDAJ

E801

ELECTRICAL LPS - DETAILS

Approved: Associate Director

Approved: Chief of Staff

Approved: Service Chief th re e inc he s = o ne fo ot on e an d on e-ha lf i nc he s = o ne fo ot on e inc h on e fo ot th re e-qu ar te rs inc h on e fo ot on e-ha lf i nc h on e fo ot th re e-eig ht s i nc h on e fo ot on e-qu ar te r in ch o ne fo ot on e-eig ht in ch o ne fo ot

DRAWING NO.

Dwg. Of

Project No.

Date

DrawnChecked

Location

Building Number

Project Title

Approved: Medical Center Director

Approved: Chief of Facility Management Svc.

Drawing Title

DateRevisions

Approved: Infection Control Officer

Approved: Safety Manager

Approved: GEMS Coordinator

Approved: Energy Engineer

658-16-101

01/15/2020

BUILDING 7

VA MEDICAL CENTER, SALEM, VA 24153

REPLACE ROOF AND TUCKPOINT (BUILDING 7)

102 3rd Ave., NE Hickory, NC 28601

828.315.9962 www.atriaxgroup.com

2105 Water Ridge Pkwy #450 Charlotte, NC 28217

704.535.6374 www.wmba.net

FINAL CONSTRUCTION DOCUMENTS

Quality Consulting Engineers, LLC

6277-600 Carolina Commons Drive, #350 Indian Land SC 29707

803.207.5450 djones@qualityconsultingengineers.com

QCE Project # 19010 01/15/2020 23 of 23

Building 7_FINAL CD DRAWINGS 18
Building 7_FINAL CD DRAWINGS 19
Building 7_FINAL CD DRAWINGS 20
Building 7_FINAL CD DRAWINGS 21
Building 7_FINAL CD DRAWINGS 22
Building 7_FINAL CD DRAWINGS 23