B08_Solicitatoin_Attach_5_Drawings_013125_-.pdf

PDF 3 MB Posted

Attached to
THRO LIFT STATION Construction Project Federal contract opportunity
Solicitation number
140P6325B0003
Issued by
Department of the Interior National Park Service Midwest Region

About this file

This document is a set of construction drawings for the Cottonwood Campground North Lift Station Replacement project at Theodore Roosevelt National Park in North Dakota. The comprehensive drawing set includes detailed site layouts, topographical surveys, erosion control plans, site demolition plans, sanitary sewer pipe and profile details, and electrical system diagrams. Key technical details include:

The project involves replacing the existing lift station with a new packaged lift station, installing a new sanitary sewer system with horizontally directionally drilled force main, constructing a new absorption field, and implementing associated site improvements. The drawings specify technical requirements for infrastructure components such as a 2" PVC force main, new wet well, valve vault, diversion structure, and electrical systems including utility transformers and control panels. The design incorporates erosion control measures, utility trench specifications, and precise elevation and grading details to ensure proper installation within the park's South Unit campground area.

View the file

Other files for this federal contract opportunity

Show all 13

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TITLE OF PROJECT

THEODORE ROOSEVELT NATIONAL PARK

80126

NATIONAL

SERVICE

PARK LOCATION WITH PARK

COTTONWOOD CAMPGROUND - NORTH LIFT STATION

REPLACEMENT

SOUTH UNIT

NAME OF PARK

REGION COUNTY STATE

NORTH DAKOTABILLINGSMIDWEST

SITE PLAN SYMBOLOGY GENERAL SYMBOLOGY

2250.399

FIREPIT

2255.122

FIREPIT

UE

UE

UE

UE

UE

UE

UE

UE

S

S

S S

S S

S

S

S

S

S

S

S

CONTROL POINT TABLE

Point #

Northing

482799.643

483233.769

482905.555

482974.388

483081.081

481581.948

Easting

1211099.585

1211820.485

1211472.463

1212136.923

1211768.421

1211829.063

Elevation

2253.43

2250.64

2253.25

2254.92

2252.90

2269.41

Description

AC Below Grade - CP2017-06

Iron Pin 3/4" Rod

Rim of Manhole

Iron Pin 5/8" Rebar - Red Plastic Cap

Iron Pin - PK Nail in Lid

Park Control - MCP2015-16

FIREPIT

2255.122

FIREPIT

UE

UE

UE

UE

UE

UE

UE

UE

S

S

S S

S S

S

S

S

S

S

S

S

FIREPIT

2255.122

FIREPIT

UE

UE

UE

UE

UE

UE

UE

UE

S

S

S

S

S S

S S

S S

S S

S

S

S

S

S

S

S

FIREPIT

2255.122

FIREPIT

UE

UE

UE

UE

UE

S

S

S

S

S S S S S S S S

S

S

S

S

S

2255.122

FIREPIT

UE

UE

UE

UE

UE

S

S

S

S

S S S S S S S S

S

S

S

S

ONE-LINE, POWER, AND LIGHTING SYMBOLOGY

S

XXX

J

KVA

SPD

WH

DMP

LP100

208/120V 3 , 4W

ATS

B

CDCD

CA

B

CA

7 1/2 HP

G

GFP

CB

CONDUIT RUN BETWEEN DEVICES CONCEALED IN

NON-ARCHITECTURALLY FINISHED AREAS OR UNDER

FLOOR SLAB. CONDUIT AND CONDUCTOR SIZES SHALL

BE THE SAME AS THE HOMERUN FOR THE CIRCUIT.

CURRENT TRANSFORMER (CT)

VOLTAGE TRANSFORMER (VT, PT, OR CPT)

UTILITY WATT-HOUR METER PER UTILITY REQUIREMENTS

GROUND

LIGHTNING ARRESTER

DIGITAL METERING PACKAGE

LOW VOLTAGE SURGE PROTECTIVE DEVICE

CONTROL PANEL WITH DISCONNECT SWITCH INTEGRAL OR PROVIDED

WITH ASSOCIATED EQUIPMENT

MOTOR/LOAD CONTROLLER AND SEPARATELY MOUNTED

MOTOR/LOAD CONTROLLER WITH SHORT CIRCUIT

PROTECTION AND DISCONNECT

TWO RECEPTACLES IN 2-GANG BOX UNDER COMMON COVER

PLATE

X Y

PLUG-IN RECEPTACLE STRIP, QUANTITY AND SPACING

OF RECEPTACLES AS NOTED OR SPECIFIED

SWITCHBOARD OR PANELBOARD; NAME, VOLTAGE,

PHASE, NUMBER OF WIRES WHEN INDICATED

Z

CONDUIT TAG OR CIRCUIT NUMBER - WIRE

AND CONDUIT SIZE AS SPECIFIED IN CIRCUIT

SCHEDULE ON THE SHEETS

CONDUIT STUBBED OUT AND CAPPED

CIRCUIT CONTINUATION

WALL MOUNTED LUMINAIRE, LAMP TYPE AS SPECIFIED, ALL OR PARTIAL

EMERGENCY (INTERNAL OR EXTERNAL POWER SOURCE AS INDICATED

X

YZ

NON-MOTOR LOAD WITH DESIGN KVA, KW, OR AMP

SIMPLEX RECEPTACLE

X Y

Z Y X

SEPARATELY MOUNTED COMBINATION MOTOR STARTER

OR CONTROLLER; SEE ELECTRICAL ONE - LINE DIAGRAM

OR SCHEDULE FOR DESCRIPTION

NON-FUSED SWITCH, CURRENT RATING, AND

NUMBER OF POLES AS NOTED (3 POLE UON)

GROUND ROD

GROUND CABLE

Y X

SPECIAL-PURPOSE RECEPTACLE AS DEFINED ON PLANS

DUPLEX RECEPTACLE

WALL SWITCH

Y X

Y X

Y X

SINGLE-FACED CEILING OR WALL MOUNTED EXIT LIGHT;

DIRECTIONAL ARROWS (IF REQUIRED) AS INDICATED ON PLANS

DOUBLE-FACED CEILING OR WALL MOUNTED EXIT LIGHT;

DIRECTIONAL ARROWS (IF REQUIRED) AS INDICATED ON PLANS

X Y

X Y

EMERGENCY LIGHT, REMOTE MOUNTED HEAD

X

Y EMERGENCY LIGHT, NUMBER OF ATTACHED HEADS AS SHOWN

CEILING/PENDANT MOUNTED LUMINAIRE, LAMP TYPE AS SPECIFIED, ALL OR

PARTIAL EMERGENCY (INTERNAL OR EXTERNAL POWER SOURCE AS

INDICATED

Y

XZ WALL MOUNTED LUMINAIRE, LAMP TYPE AS SPECIFIED

CEILING/PENDANT MOUNTED LUMINAIRE, LAMP TYPE AS SPECIFIED

Y X

Z

WALL MOUNTED LUMINAIRE, LAMP TYPE AS SPECIFIED

X Y

Z

CEILING/PENDANT/BOLLARD MOUNTED LUMINAIRE, LAMP TYPE AS

SPECIFIED

X Y

Z

CIRCUIT HASH MARKS (WHEN INDICATED); LONG,

SHORT, SINGLE DOT, AND DOUBLE DOT REPRESENT

PHASE, NEUTRAL, EQUIPMENT GROUND, AND ISOLATED

EQUIPMENT GROUND, RESPECTIVELY. X REPRESENTS

CONDUCTOR SIZE OTHER THAN #12 IN 3/4" CONDUIT.

GROUND FAULT PROTECTION

CIRCUIT RUN BETWEEN DEVICES EXPOSED IN

NON-ARCHITECTURALLY FINISHED AREAS; CONCEALED

IN ARCHITECTURALLY FINISHED AREAS. CONDUIT AND

CONDUCTOR SIZES SHALL BE THE SAME AS THE

HOMERUN FOR THE CIRCUIT.

HOMERUN TO SOURCE (E.G. PANELBOARD, MCC)

NUMBER IN PARENTHESES REPRESENTS CONDUCTOR SIZE OTHER THAN #12

SINGLE PHASE: 2#12, 1#12G IN 3/4"C

THREE PHASE: 3#12, 1#12G IN 3/4"C

UNLESS OTHERWISE NOTED, CONDUCTOR SIZE IS FOR ENTIRE CIRCUIT,

SOURCE TO LAST DEVICE. ALSO, SEE ONE LINE DIAGRAM FOR CIRCUIT

REQUIREMENTS

CONDUIT TURNING DOWN

CONDUIT TURNING UP

PANELBOARD (LESS THAN 250V)

PANELBOARD (250V TO 600V)

JUNCTION OR PULL BOX

CONTROL PANEL INTEGRAL OR PROVIDED WITH ASSOCIATED EQUIPMENT

IC INSTRUMENTATION / CONTROL DEVICE

PB PUSHBUTTON

SELECTOR SWITCHSS

OR

3-PHASE, 4-WIRE GROUNDED WYE CONNECTION

3-PHASE, 3-WIRE DELTA CONNECTION

TRANSFORMER

TRANSFER SWITCH, CURRENT RATING, AND

NUMBER OF POLES AS NOTED

GENERATOR

MOTOR WITH DESIGN HORSEPOWER

(WHEN INDICATED)

NON-FUSED SAFETY SWITCH, 30A, 3P, X

INDICATES AMP RATING GREATER THAN 30A

MEDIUM VOLTAGE CIRCUIT BREAKER

FUSIBLE SWITCH, CURRENT RATING, FUSE

RATING, AND QUANTITY AS NOTED (3 POLE

UON)

FUSED CUTOUT, CURRENT RATING, FUSE RATING,

AND QUANTITY AS NOTED

FUSE, RATING, AND NUMBER OF FUSES AS NOTED

OR

SEPARATELY MOUNTED CIRCUIT BREAKER; SEE

ELECTRICAL ONE - LINE DIAGRAM OR SCHEDULE

FOR DESCRIPTION

MAGNETIC MOTOR STARTER AND SEPARATELY

MOUNTED COMBINATION MAGNETIC MOTOR

STARTER

DISCONNECT OR DRAWOUT CONNECTION

X Y

ATS - AUTOMATIC

MTS - MANUAL

SUBSCRIPTS:

X - INDICATES TYPE

GFCI - GROUND FAULT CIRCUIT INTERRUPTER

IG - ISOLATED GROUND

TR - TAMPER RESISTANT

PLH - PLUG LOAD HALF CONTROLLED

PLD - PLUG LOAD DUAL CONTROLLED

USB - USB CHARGING STATION

SPD - SURGE PROTECTIVE DEVICE

Y - INDICATES CIRCUIT NUMBER FROM PANELBOARD

XXXOR

X Y

Z

X Y

Z

CEILING/PENDANT/BOLLARD MOUNTED LUMINAIRE, LAMP TYPE AS SPECIFIED,

EMERGENCY (INTERNAL OR EXTERNAL POWER SOURCE AS INDICATED)

WALL MOUNTED LUMINAIRE, LAMP TYPE AS SPECIFIED, EMERGENCY

(INTERNAL OR EXTERNAL POWER SOURCE AS INDICATED)

Y

X RECESSED FLOOR MOUNTED BOX, QUANTITY AND TYPE OF

RECEPTACLES AS INDICATED

CORD AND PLUG CONNECTION

X

ELECTRICAL EQUIPMENT ENCLOSURE: SWITCHBOARD, MOTOR

CONTROL CENTER, CONTROL PANEL, TRANSFORMER OR OTHER

EQUIPMENT AS INDICATED. ESTIMATED SIZE AS INDICATED.

WHEN USED X INDICATES EQUIPMENT TYPE.

FUSED SAFETY SWITCH, 3P, X INDICATES AMP RATING

GREATER THAN 30A, Y INDICATES FUSE SIZE

SEPARATELY MOUNTED MOTOR STARTER OR CONTROLLER;

SEE ELECTRICAL ONE-LINE DIAGRAM OR SCHEDULE FOR

DESCRIPTION.

Y

X

WALL MOUNTED FLOOD LUMINAIRE, LAMP TYPE AS SPECIFIED

POLE/STANCHION MOUNTED LUMINAIRE, LAMP TYPE AS SPECIFIED

POLE/STANCHION MOUNTED LUMINAIRE, LAMP TYPE AS SPECIFIED,

EMERGENCY (INTERNAL OR EXTERNAL POWER SOURCE AS INDICATED

POLE/STANCHION MOUNTED FLOOR LUMINAIRE, LAMP TYPE AS SPECIFIED

X Y

Z

X Y

Z

X Y

Z

X Y

Z

X 20A 3P

X

100AF

80AT

3P

PHOTOCELLPC

OSX LIGHTING CONTROL OCCUPANCY SENSOR, CEILING MOUNTED,

X INDICATES SPECIFIC TYPE AS SPECIFIED

TC TIME CLOCK

X - INDICATES TYPE

NONE

K P L

DM

MC

T

SINGLE POLE

DOUBLE POLE

THREE-WAY

FOUR-WAY

KEY SWITCH

PILOT LIGHT

LIGHTED HANDLE

DIMMING

MOMENTARY CONTACT

TIMER

Y - INDICATES CONTROLLING SWITCH (IF REQUIRED)

X - INDICATES LUMINAIRE TYPE PER LUMINAIRE SCHEDULE

Y - INDICATES CIRCUIT NUMBER FROM PANELBOARD

Z - INDICATES CONTROLLING SWITCH (IF REQUIRED)

NL - NIGHT LIGHT UNSWITCHED

SUBSCRIPTS:

LIGHTING FIXTURE SUBSCRIPTS:

MOTOR STARTER AND CONTROLLER SUBSCRIPTS:

A - MAGNETIC STARTER NEMA SIZE

B - STARTER TYPE

C - CONTROL DIAGRAM OR CONTROLS

SCHEDULE NUMBER (IF REQUIRED)

D - CONTROLLER TYPE

NONE

FVR

2S

RVAT

FULL VOLTAGE NON-REVERSING (FVNR)

FULL VOLTAGE REVERSING

TWO SPEED

REDUCED VOLTAGE AUTO TRANSFORMER

VFD

SS

CONT

VARIABLE FREQUENCY DRIVE

SOLID STATE

CONTACTOR

EQUIPMENT TYPES:

ATS

CP

MTS

MCC

UPS

VFD

SB

SG

T

AUTOMATIC TRANSFER SWITCH

CONTROL PANEL

MANUAL TRANSFER SWITCH

MOTOR CONTROL CENTER

UNINTERRUPTIBLE POWER SUPPLY

VARIABLE FREQUENCY DRIVE

SWITCHBOARD

SWITCHGEAR

TRANSFORMER

GENERAL NOTES:

MCCB

ICCB

LVP

MCP

TYPES:

MOLDED CASE

INSULATED CASE

LOW VOLTAGE POWER

MOTOR CIRCUIT

PROTECTOR

(RATING PER CONNECTED

LOAD)

LOW VOLTAGE CIRCUIT BREAKER (CB). RATING

AND NO. OF POLES AS SHOWN. WHEN SPECIFIC

TYPE, OTHER THAN MCCB, IS REQUIRED, X

INDICATES TYPE.

L S I G A

TRIP UNIT:

LONG TIME PICKUP

SHORT TIME PICKUP

INSTANTANEOUS PICKUP

GROUND FAULT PICKUP

ARC ENERGY REDUCTION

MODE

S MANUAL MOTOR STARTERX

Y

OSX LIGHTING CONTROL OCCUPANCY SENSOR, WALL MOUNTED,

X INDICATES SPECIFIC TYPE AS SPECIFIED

SOSX OR

X - INDICATES TYPE

HP

TE

FT

HORSEPOWER RATED

HORSEPOWER RATED WITH THERMAL ELEMENT

HORSEPOWER RATED WITH FUSETRON FUSE

Y - INDICATES SWITCH TYPE

SUBSCRIPTS:

NONE

R

TOGGLE SWITCH TYPE

ROTARY SWITCH TYPE

X Y

X Y

OR

X

Y

CONDUIT CONNECTION TO EQUIPMENT

X

1. THIS IS A STANDARD ELECTRICAL SYMBOLOGY SHEET. NOT

ALL SYMBOLS MAY BE USED ON THIS PROJECT.

2. SCREENING OR SHADING OF WORK IS USED TO INDICATE

EXISTING COMPONENTS OR TO DE-EMPHASIZE PROPOSED

IMPROVEMENTS TO HIGHLIGHT SELECTED TRADE WORK.

REFER TO CONTEXT OF EACH SHEET FOR USAGE.

3. SEE P&ID LEGEND SHEET FOR PROJECT SPECIFIC EQUIPMENT

SYMBOLS, EQUIPMENT ABBREVIATIONS, AND PIPING SYSTEM

ABBREVIATIONS.

X

E - ELECTRICAL

M - MECHANICAL

K - KEY

INTERLOCK: X - INDICATES TYPE

TYPES:

X ROOM/AREA LIGHTING CONTROL TYPE,

SEE LIGHTING CONTROL SCHEDULE FOR REQUIREMENTS

(#X)

(#X)

2 LOW VOLTAGE DIGITAL WALL SWITCH, NUMBER INDICATES

QUANTITY OF PUSH BUTTONS PER SINGLE GANG PLATE, LETTER

INDICATES CONTROL ZONE WHEN SHOWN

a

J OR

SV SOLENOID VALVE

FIREPIT

2255.122

FIREPIT

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

UE

S

S

S

S

S S

S S

S S

S

S

S

S

S

S

S

S

S

S

S

S

S

P

P

P C C

C

�3" M

IN

IM

U M

IC ICICIC

PAD MOUNTED

UTILITY XFMR

MFR

SPD

30A 2P

20A 1P

30A 2P

30A 2P

10KAIC

DUPLEX CONTROL PANEL

240/120V

SERVICE ENTRANCE RATED

WP IN-USE

GFCI

GNDGROUND ROD

PUMP

CABLESLEVEL SWITCH

MFR CABLES

LEVEL SWITCHES

7.2KV:120/240V

15KVA

WH

TO COMFORT

STATION

NORTH #1

TO COMFORT

STATION

NORTH #2

100A METER SOCKET

MOUNTED TO TRANSFORMER

N

PUMP 1 PUMP 2

0.50.5

IC

PER

MFR

SPD

PER

MFR

PER

MFR

PER

MFR

MFR

PER

MFR

10KAIC

CP-01 DUPLEX CONTROL PANEL

FURNISHED BY SPEC 33 32 13

INSTALLED BY DIV 26

240/120V, NEMA 4X

SERVICE ENTRANCE RATED

WP IN-USE

GFCI

GND BUS

#2

GROUND ROD

PUMP MFR SUBMERSIBLE CABLE, 2"C

ROUTE CABLES THROUGH

ELECTRICAL COUPLING IN SIDE OF

WETWELL, SEE DETAIL 1/C9

MFR 11-CORE

CABLE, 2"C

FOGROD LEVEL SENSOR

MFR

NEUT

PAD MOUNTED

UTILITY XFMR

7.2KV:120/240V

15KVA

WH

TO COMFORT

STATION

NORTH #1

TO COMFORT

STATION

NORTH #2

EXISTING 100A METER

BID ALT 1 - COORDINATE WITH ROUGHRIDER

ELECTRIC COOP TO UPGRADE TO 200A

SERVICE. PROVIDE 200A METER SOCKET.

3#1/0, #4G, 1 1/2"C

(INCREASED FOR VOLT DROP)

PUMP 1 PUMP 2

CONDUIT SEAL FITTINGS, TYP.

3#1/0, #4G, 1 1/2"C

(INCREASED FOR VOLT DROP)

PROVIDE WATERPROOF TAP IN HANDHOLE

FIELD VERIFY EXISTING SIZE.

VOLTAGE DROP CALCULATIONS

ARE BASED ON ASSUMED #10 AWG

CONDUCTOR SIZE. CONFIRM WITH

ENGINEER ANY DISCREPANCIES

FOUND FROM ASSUMED SIZE.

INTRINSICALLY

SAFE BARRIERS

#2

Sheets and Views
1 G0 COVER - Layout1
2 G1 LEGENDS - Plot
3 G2 ABBREVIATIONS - Plot
4 C1 TOPO - Plot
5 C2 LAYOUT - Plot
6 C3 EC - Plot
7 C4 DEMO - Plot
8 C5 P&P - Plot
9 C6 DETAIL - Plot
10 C7 DETAIL - Plot
11 C8 DETAIL - Plot
12 C9 DETAIL - Plot
13 E1 LEGEND - Plot
14 E2 LAYOUT - Layout1
15 E3 DETAILS - Plot
16 E4 ONE-LINE DIAGRAMS - Plot

File details come from the government source that posted it. Updated .