B08_Solicitation_Attach_7__Specifications_Septic_Flow_Calculations_102824_-_Copy.pdf
PDF 24 KB Posted
- Attached to
- THRO LIFT STATION Construction Project Federal contract opportunity
- Solicitation number
- 140P6325B0003
About this file
This document is a detailed septic flow calculations worksheet for the Theodore Roosevelt National Park - South Unit Camp Sewer Replacement project. The calculations outline specific septic system requirements, including a total daily flow of 2,725 gallons per day (GPD), derived from 25 GPPD for central comfort stations and 109 visitors based on a 4-year summer average. The septic tank sizing calculations account for 58 total fixtures across comfort station fixtures (15 each), camp tender residence fixtures (4), and future campsites (24 fixtures from 6 full hookup sites), resulting in a total required septic tank size of 3,700 gallons. The breakdown includes a 2,500-gallon tank for current requirements and a 1,200-gallon tank for a future duplex, with references to specific sewage system design guidelines (62-03.1-03-03 and 62-03.1-03-07).
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140P6325B0003_Amd_0003.pdf | ||
| B09_Solicitation_Amendment_3_Attach_1_Clarity_on_Diversion_Box_0003.pdf | ||
| B09_Solicitation_Amendment_3_Attach_2_Oldcastle_example_0003.pdf | ||
| Sol_140P6325B0003_Amd_0002.pdf | ||
| B09_Solicitation_Amendment_Attach_1_Questions_and_Answer_0001.pdf | ||
| Sol_140P6325B0003_Amd_0001.pdf | ||
| B08_Solicitation_Attach_4_Wage_Determination.pdf | ||
| B08_Solicitation_attach_6_Bid_Schedule.xlsx | XLSX spreadsheet | |
| B08_Solicitatoin_Attach_1__Specifications_013125_-.pdf | ||
| B08_Solicitation_Attach_2_Specifications_Submittal_List_013125_.xls | XLS spreadsheet | |
| Sol_140P6325B0003.pdf | ||
| B08_Solicitatoin_Attach_5_Drawings_013125_-.pdf | ||
| B08_Solicitation_Attach_3_Limitations_on_Subcontracting_Report.xlsx | XLSX spreadsheet |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
25 GPPPD
2725 GPD
2500 Gallons
1200 Gallons
3700 Gallons
Required Septic Tank Size*:
Total Required Septic Tank Size:
*Reference 62-03.1-03-07 Septic Tanks
Septic Flow Calculations
Septic Tank Calculations
Comfort Station Fixtures (15 Each):
Camp Tender Residence Fixtures:
Future Campsites (6 Full Hookup - 4 Fixtures Each):
Total Fixtures Served:
Required Septic Tank Size*:
Future Duplex:
Theodore Roosevelt National Park - South Unit Camp Sewer Replacement
Camps with Central Comfort Stations (flush toilets, no showers)*:
Visitors(Based on 4-yr Summer Average):
Total Daily Flow:
*Reference 62-03.1-03-03 Design of Individual Sewage System