B08_Attachment_2_Project_Specifications_07-15.pdf

PDF 773 KB Posted

Attached to
Fire Sprinkler System Replacements Federal contract opportunity
Solicitation number
140P1424Q0112
Issued by
Department of the Interior National Park Service Intermountain Region

About this file

This document is a detailed set of specifications for a fire sprinkler system replacement project at Glacier National Park in Montana. The key details are:

The project involves removing the existing dry pipe, water-based fire suppression system and installing new automatic dry pipe systems and associated components to ensure a fully functional fire suppression system that provides comprehensive coverage for Apartment Buildings 94 and 96. The systems must be designed and installed in compliance with all relevant codes and standards.

The contractor must have experience designing and installing water-based fire suppression systems in Montana for at least 5 years, and the design work must be performed by a registered professional fire protection engineer or NICET Level III Automatic Sprinkler System Layout Technician. The contractor must also be certified by the equipment manufacturer and licensed by the state and local jurisdictions.

The sprinkler system must be hydraulically designed to provide a minimum density of 0.15 gallons per minute per square foot over the hydraulically most remote 1500 square feet, with a 10 psi safety margin. The contractor must perform water flow testing to determine the water supply performance. The specifications provide detailed requirements for the sprinkler components, piping, valves, monitoring, and testing.

View the file

Other files for this federal contract opportunity

Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GLACIER NATIONAL PARK

MONTANA

APARTMENTS 94 & 96 FIRE SPRINKLER REPLACEMENT

PMIS #336659

SPECIFICATIONS

NATIONAL PARK SERVICE (NPS)

APARTMENT 94 & 96 FIRE SPRINKLER REPLACEMENT

07 92 00 – JOINT SEALANTS | 1 of 9

07 92 00 – JOINT SEALANTS

PART 1 - GENERAL

1.1 SUMMARY

A. This section covers interior and exterior sealant and their application, wherever required for complete installation of building materials or systems.

1.2 RELATED REFERENCES

A. Publications listed below form a part of this specification to extent referenced.

1. Publications are referenced in text by basic designation only.

B. ASTM C509-06: Elastomeric Cellular Preformed Gasket and Sealing Material C. ASTM C612-14: Mineral Fiber Block and Board Thermal Insulation D. ASTM C717-14a: Standard Terminology of Building Seals and Sealants E. ASTM C734-06(R2012): Test Method for Low-Temperature Flexibility of Latex Sealants after Artificial

Weathering F. ASTM C794-10: Test Method for Adhesion-in-Peel of Elastomeric Joint Sealants G. ASTM C919-12.: Use of Sealants in Acoustical Applications.

H. ASTM C920-14a: Elastomeric Joint Sealants.

I. ASTM C1021-08(R2014): Laboratories Engaged in Testing of Building Sealants J. ASTM C1193-13: Standard Guide for Use of Joint Sealants.

K. ASTM C1248-08(R2012): Test Method for Staining of Porous Substrate by Joint Sealants L. ASTM C1330-02(R2013): Cylindrical Sealant Backing for Use with Cold Liquid Applied Sealants M. ASTM C1521-13: Standard Practice for Evaluating Adhesion of Installed Weatherproofing Sealant Joints N. ASTM D217-10: Test Methods for Cone Penetration of Lubricating Grease O. ASTM D1056-14: Specification for Flexible Cellular Materials—Sponge or Expanded Rubber P. ASTM E84-09: Surface Burning Characteristics of Building Materials Q. 40 CFR 59(2014) - National Volatile Organic Compound Emission Standards for Consumer and Commercial

Products

1.3 QUALITY ASSURANCE

A. INSTALLER QUALIFICATIONS

1. An experienced installer with a minimum of three (3) years’ experience and who has specialized in installing joint sealants similar in material, design, and extent to those indicated for this Project and whose work has resulted in joint-sealant installations with a record of successful in-service performance. Submit qualification.

B. SOURCE LIMITATIONS

1. Obtain each type of joint sealant through one (1) source from a single manufacturer.

C. PRODUCT TESTING

1. Obtain test results from a qualified testing agency based on testing current sealant formulations within a

12-month period.

i. Testing Agency Qualifications: An independent testing agency qualified according to ASTM C1021.

ii. Test elastomeric joint sealants for compliance with requirements specified by reference to ASTM C920, and where applicable, to other standard test methods.

iii. Test elastomeric joint sealants according to SWRI’s Sealant Validation Program for compliance with requirements specified by reference to ASTM C920 for adhesion and cohesion under cyclic movement, adhesion-in peel, and indentation hardness.

07 92 00 – JOINT SEALANTS | 2 of 9

iv. Test other joint sealants for compliance with requirements indicated by referencing standard specifications and test methods.

D. LAB TESTS

1. Submit samples of materials that will be in contact or affect joint sealants to joint sealant manufacturers for tests as follows:

i. ADHESION TESTING

(a) Before installing elastomeric sealants, test their adhesion to protect joint substrates according to the method in ASTM C794 to determine if primer or other specific joint preparation techniques are required.

ii. COMPATIBILITY TESTING

(a) Before installing elastomeric sealants, determine compatibility when in contact with glazing and gasket materials.

iii. STAIN TESTING

(a) Perform testing per ASTM C1248 on interior and exterior sealants to determine if sealants or primers will stain adjacent surfaces. No sealant work is to start until results of these tests have been submitted to the COR Representative (COR) and the COR has given written approval to proceed with the work.

E. PRECONSTRUCTION FIELD-ADHESION TESTING

1. Before installing elastomeric sealants, field test their adhesion to joint substrates according to Method A, Field-Applied Sealant Joint Hand Pull Tab, in Appendix X1.1 in ASTM C1193 or Method A, Tail Procedure, in

ASTM C1521.

i. Locate test joints where indicated in construction documents or, if not indicated, as directed by COR.

ii. Conduct field tests for each application indicated below:

(a) Each type of elastomeric sealant and joint substrate indicated.

(b) Each type of non-elastomeric sealant and joint substrate indicated.

iii. Notify COR seven (7) days in advance of dates and times when test joints will be erected.

iv. Arrange for tests to take place with joint sealant manufacturer’s technical representative present.

F. MOCKUPS

1. Before installing joint sealants, apply elastomeric sealants as follows to verify selections and to demonstrate aesthetic effects and qualities of materials and execution:

i. Joints in mockups of assemblies that are indicated to receive elastomeric joint sealants.

1.4 CERTIFICATION

A. Contractor is to submit to the COR written certification that joints are of the proper size and design, that the materials supplied are compatible with adjacent materials and backing, that the materials will properly perform to provide permanent watertight, airtight or vapor tight seals (as applicable), and that materials supplied meet specified performance requirements.

1.5 SUBMITTALS

A. ACTION SUBMITTALS

1. PRODUCT DATA

i. Primers

ii. Sealing Compounds, each type, including compatibility when different sealants are in contact with each other.

07 92 00 – JOINT SEALANTS | 3 of 9

2. SUSTAINABLE DESIGN SUBMITTALS

i. Volatile organic compounds per volume as specified in PART 2 PRODUCTS.

3. SAMPLES

i. None required.

B. INFORMATIONAL SUBMITTALS

1. Installer qualifications.

2. Contractor certification.

3. Manufacturer's installation instructions for each product used.

C. CLOSEOUT SUBMITTALS

1. Manufacturer warranty.

1.6 PROJECT CONDITIONS:

A. ENVIRONMENTAL LIMITATIONS

1. Do not proceed with installation of joint sealants under following conditions:

i. When ambient and substrate temperature conditions are outside limits permitted by joint sealant manufacturer or are below 4.4 degrees C (40 degrees F).

ii. When joint substrates are wet.

B. JOINT-WIDTH CONDITIONS

1. Do not proceed with installation of joint sealants where joint widths are less than those allowed by joint sealant manufacturer for applications indicated.

C. JOINT-SUBSTRATE CONDITIONS

1. Do not proceed with installation of joint sealants until contaminants capable of interfering with adhesion are removed from joint substrates.

1.7 DELIVERY, HANDLING, AND STORAGE

A. Deliver materials in manufacturers' original unopened containers, with brand names, date of manufacture, shelf life, and material designation clearly marked thereon.

B. Carefully handle and store to prevent inclusion of foreign materials.

C. Do not subject to sustained temperatures exceeding 32 degrees C (90 degrees F) or less than 5 degrees C (40 degrees

1.8 DEFINITIONS

A. Definitions of terms in accordance with ASTM C717 and as specified.

B. Backing Rod: A type of sealant backing.

C. Bond Breakers: A type of sealant backing.

D. Filler: A sealant backing used behind a back-up rod.

1.9 WARRANTY

A. CONSTRUCTION WARRANTY:

1. Comply with FAR clause 52.246-21 "Warranty of Construction".

B. MANUFACTURER WARRANTY

1. Manufacturer shall warranty their sealant for a minimum of five (5) years from the date of installation and final acceptance by the Government.

i. Submit manufacturer warranty.

07 92 00 – JOINT SEALANTS | 4 of 9

PART 2 - PRODUCTS

2.1 SEALANTS

A. EXTERIOR SEALANTS

1. GENERAL

i. Provide location(s) of exterior sealant as follows:

(a) Joints formed where frames and subsills of windows, doors, louvers, and vents adjoin masonry, concrete, or metal frames. Provide sealant at exterior surfaces of exterior wall penetrations.

(b) Metal to metal.

(c) Masonry to masonry or stone.

(d) Stone to stone.

(e) Cast stone to cast stone.

(f) Masonry expansion and control joints.

(g) Wood to masonry.

(h) Masonry joints where shelf angles occur.

1. Voids where items penetrate exterior walls.

(i) Metal reglets, where flashing is inserted into masonry joints, and where flashing is penetrated by coping dowels.

2. VERTICAL SURFACES

i. Provide non-staining ASTM C920, Type S or M, Grade NS, Class 25

3. HORIZONTAL SURFACES

i. Provide ASTM C920, Type S or M, Grade P, Class 25

B. FLOOR JOINT SEALANT

1. ASTM C920, Type S or M, Grade P, Class 25

2. Provide location(s) of floor joint sealant as follows:

i. Seats of metal thresholds exterior doors

ii. Control and expansion joints in floors, slabs, ceramic tile, and walkways

C. INTERIOR SEALANTS

1. VOC CONTENT OF INTERIOR SEALANTS

i. Sealants and sealant primers used inside the weatherproofing system are to comply with the following limits for VOC content when calculated according to 40 CFR 59, (EPA Method 24):

(a) Architectural Sealants: 250 g/L.

(b) Sealant Primers for Nonporous Substrates: 250 g/L.

(c) Sealant Primers for Porous Substrates: 775 g/L.

2. VERTICAL AND HORIZONTAL SURFACES

i. ASTM C920, Type S or M, Grade NS, Class 25

3. FOOD SERVICE

i. Use a Vinyl Acetate Homopolymer, or other low VOC, non-toxic sealant approved for use in food preparation areas.

4. PROVIDE LOCATION(S) OF INTERIOR SEALANT AS FOLLOWS

i. Typical narrow joint 6 mm, (1/4 inch) or less at walls and adjacent components.

ii. Perimeter of doors, windows, access panels which adjoin concrete or masonry surfaces.

iii. Interior surfaces of exterior wall penetrations.

iv. Joints at masonry walls and columns, piers, concrete walls or exterior walls.

07 92 00 – JOINT SEALANTS | 5 of 9

v. Perimeter of lead faced control windows and plaster or gypsum wallboard walls.

vi. Exposed isolation joints at top of full height walls.

vii. Joints between bathtubs and ceramic tile; joints between shower receptors and ceramic tile; joints formed where nonplanar tile surfaces meet.

viii. Joints formed between tile floors and tile base cove; joints between tile and dissimilar materials; joints occurring where substrates change.

ix. Behind escutcheon plates at valve pipe penetrations and showerheads in showers.

D. ACOUSTICAL SEALANT

1. Conforming to ASTM C919; flame spread of 25 or less; and a smoke developed rating of 50 or less when tested in accordance with ASTM E84. Acoustical sealant have a consistency of 250 to 310 when tested in accordance with ASTM D217; remain flexible and adhesive after 500 hours of accelerated weathering as specified in ASTM C734; and be non-staining.

2. Provide location(s) of acoustical sealant as follows:

i. Exposed acoustical joint at sound rated partitions.

ii. Concealed acoustic joints at sound rated partitions.

iii. Joints where item pass-through sound rated partitions.

2.2 COLOR

A. Sealants used with exposed masonry are to match color of mortar joints.

B. Sealants used with unpainted concrete are to match color of adjacent concrete.

C. Color of sealants for other locations to be light gray or aluminum, unless otherwise indicated in construction documents.

2.3 JOINT SEALANT BACKING

A. GENERAL

1. Provide sealant backings of material and type that are non-staining; are compatible with joint substrates, sealants, primers, and other joint fillers; and are approved for applications indicated by sealant manufacturer based on field experience and laboratory testing.

B. CYLINDRICAL SEALANT BACKINGS

1. ASTM C1330, of type indicated below and of size and density to control sealant depth and otherwise contribute to producing optimum sealant performance:

i. Type C: Closed-cell material with a surface skin.

C. ELASTOMERIC TUBING SEALANT BACKINGS

1. Neoprene, butyl, EPDM, or silicone tubing complying with ASTM D1056 or synthetic rubber (ASTM C509), nonabsorbent to water and gas, and capable of remaining resilient at temperatures down to minus 32 degrees C (minus 26 degrees F). Provide products with low compression set and of size and shape to provide a secondary seal, to control sealant depth, and otherwise contribute to optimum sealant performance.

D. BOND-BREAKER TAPE

1. Polyethylene tape or other plastic tape recommended by sealant manufacturer for preventing sealant from adhering to rigid, inflexible joint-filler materials or joint surfaces at back of joint where such adhesion would result in sealant failure.

2. Provide self-adhesive tape where applicable.

2.4 WEEPS

A. Weep/Vent Products: Provide the following unless otherwise indicated or approved.

1. Round Plastic Tubing: Medium-density polyethylene, 10 mm (3/8-inch) OD by thickness of stone or masonry veneer.

07 92 00 – JOINT SEALANTS | 6 of 9

2.5 FILLER

A. Mineral fiberboard: ASTM C612, Class 1.

B. Thickness same as joint width.

C. Depth to fill void completely behind back-up rod.

2.6 PRIMER

A. As recommended by manufacturer of caulking or sealant material.

B. Stain free type.

2.7 CLEANERS-NON-POROUS SURFACES

A. Chemical cleaners compatible with sealant and acceptable to manufacturer of sealants and sealant backing material B. Cleaners to be free of oily residues and other substances capable of staining or harming joint substrates and adjacent non-porous surfaces and formulated to promote adhesion of sealant and substrates.

PART 3 - EXECUTION

3.1 INSPECTION

A. Inspect substrate surface for bond breaker contamination and unsound materials at adherent faces of sealant.

B. Coordinate for repair and resolution of unsound substrate materials.

C. Inspect for uniform joint widths and that dimensions are within tolerance established by sealant manufacturer.

3.2 PREPARATIONS

A. Prepare joints in accordance with manufacturer's instructions and SWRI (The Professionals’ Guide).

B. Clean surfaces of joint to receive caulking or sealants leaving joint dry to the touch, free from frost, moisture, grease, oil, wax, lacquer paint, or other foreign matter that would tend to destroy or impair adhesion.

1. Clean porous joint substrate surfaces by brushing, grinding, blast cleaning, mechanical abrading, or a combination of these methods to produce a clean, sound substrate capable of developing optimum bond with joint sealants.

2. Remove loose particles remaining from above cleaning operations by vacuuming or blowing out joints with oil-free compressed air. Porous joint surfaces include but are not limited to the following:

i. Concrete.

ii. Masonry.

iii. Unglazed surfaces of ceramic tile.

3. Remove laitance and form-release agents from concrete.

4. Clean nonporous surfaces with chemical cleaners or other means that do not stain, harm substrates, or leave residues capable of interfering with adhesion of joint sealants. Nonporous surfaces include but are not limited to the following:

i. Metal.

ii. Glass.

iii. Porcelain enamel.

iv. Glazed surfaces of ceramic tile.

C. Do not cut or damage joint edges.

D. Apply non-staining masking tape to face of surfaces adjacent to joints before applying primers, caulking, or sealing compounds.

1. Do not leave gaps between ends of sealant backings.

2. Do not stretch, twist, puncture, or tear sealant backings.

07 92 00 – JOINT SEALANTS | 7 of 9

3. Remove absorbent sealant backings that have become wet before sealant application and replace them with dry materials.

E. Apply primer to sides of joints wherever required by compound manufacturer's printed instructions or as indicated by pre-construction joint sealant substrate test.

1. Apply primer prior to installation of back-up rod or bond breaker tape.

2. Use brush or other approved means that will reach all parts of joints. Avoid application to or spillage onto adjacent substrate surfaces.

3.3 BACKING INSTALLATION

A. Install backing material, to form joints enclosed on three sides as required for specified depth of sealant.

B. Where deep joints occur, install filler to fill space behind the backing rod and position the rod at proper depth.

C. Cut fillers installed by others to proper depth for installation of backing rod and sealants.

D. Install backing rod, without puncturing the material, to a uniform depth, within plus or minus 3 mm (1/8 inch) for sealant depths specified.

E. Where space for backing rod does not exist, install bond breaker tape strip at bottom (or back) of joint so sealant bonds only to two opposing surfaces.

3.4 SEALANT DEPTHS AND GEOMETRY

A. At widths up to 6 mm (1/4 inch), sealant depth equal to width.

B. At widths over 6 mm (1/4 inch), sealant depth 1/2 of width up to 13 mm (1/2 inch) maximum depth at center of joint with sealant thickness at center of joint approximately 1/2 of depth at adhesion surface.

3.5 INSTALLATION

A. GENERAL

1. For application of sealants, follow requirements of ASTM C1193 unless specified otherwise.

i. Take all necessary steps to prevent three-sided adhesion of sealants.

2. Apply sealants and caulking only when ambient temperature is between 5 degrees C and 38 degrees C (40 degrees and 100 degrees F).

3. Do not install polysulfide base sealants where sealants may be exposed to fumes from bituminous materials, or where water vapor in continuous contact with cementitious materials may be present.

4. Do not install sealant type listed by manufacture as not suitable for use in locations specified.

5. Apply caulking and sealing compound in accordance with manufacturer's printed instructions.

6. Avoid dropping or smearing compound on adjacent surfaces.

7. Fill joints solidly with compound and finish compound smooth.

8. Tool exposed joints to form smooth and uniform beds, with slightly concave surface conforming to joint configuration per Figure 5A in ASTM C1193 unless shown or specified otherwise in construction documents.

i. Remove masking tape immediately after tooling of sealant and before sealant face starts to “skin” over.

ii. Remove any excess sealant from adjacent surfaces of joint, leaving the working in a clean finished condition.

9. Finish paving or floor joints flush unless joint is otherwise detailed.

10. Apply compounds with nozzle size to fit joint width.

11. Test sealants for compatibility with each other and substrate. Use only compatible sealant. Submit test reports.

12. Replace sealant which is damaged during construction process.

B. WEEPS

1. Place weep holes and vents in joints where moisture may accumulate, including at base of cavity walls, above shelf angles, at all flashing, and as indicated on construction documents.

07 92 00 – JOINT SEALANTS | 8 of 9

i. Use round plastic tubing to form weep holes.

ii. Space weep holes formed from plastic tubing not more than 406 mm (16 inches) o.c.

iii. Trim tubing material used in weep holes flush with exterior wall face after sealant has set.

C. INTERIOR SEALANTS

1. Where gypsum board partitions are of sound rated, fire rated, or smoke barrier construction, follow requirements of ASTM C919 only to seal all cut-outs and intersections with the adjoining construction unless specified otherwise.

i. Apply a 6 mm (1/4 inch) minimum bead of sealant each side of runners (tracks), including those used at partition intersections with dissimilar wall construction.

ii. Coordinate with application of gypsum board to install sealant immediately prior to application of gypsum board.

iii. Partition intersections: Seal edges of face layer of gypsum board abutting intersecting partitions, before taping and finishing or application of veneer plaster-joint reinforcing.

iv. Openings: Apply a 6 mm (1/4 inch) bead of sealant around all cutouts to seal openings of electrical boxes, ducts, pipes and similar penetrations. To seal electrical boxes, seal sides and backs.

v. Control Joints: Before control joints are installed, apply sealant in back of control joint to reduce flanking path for sound through control joint.

3.6 FIELD QUALITY CONTROL

A. Field-Adhesion Testing: Field-test joint-sealant adhesion to joint substrates according to Method A, Field-

Applied Sealant Joint Hand Pull Tab, in Appendix X1 in ASTM C1193 or Method A, Tail Procedure, in ASTM C1521.

1. Extent of Testing: Test completed elastomeric sealant joints as follows:

i. Perform 10 tests for first 305 m (1000 feet) of joint length for each type of elastomeric sealant and joint substrate.

ii. Perform one test for each 305 m (1000 feet) of joint length thereafter or one test per each floor per elevation.

B. Inspect joints for complete fill, for absence of voids, and for joint configuration complying with specified requirements. Record results in a field adhesion test log.

C. Inspect tested joints and report on following:

1. Whether sealants in joints connected to pulled-out portion failed to adhere to joint substrates or tore cohesively. Include data on pull distance used to test each type of product and joint substrate.

2. Compare these results to determine if adhesion passes sealant manufacturer’s field-adhesion hand-pull test criteria.

3. Whether sealants filled joint cavities and are free from voids.

4. Whether sealant dimensions and configurations comply with specified requirements.

D. Record test results in a field adhesion test log. Include dates when sealants were installed, names of persons who installed sealants, test dates, test locations, whether joints were primed, adhesion results and percent elongations, sealant fill, sealant configuration, and sealant dimensions.

E. Repair sealants pulled from test area by applying new sealants following same procedures used to originally seal joints. Ensure that original sealant surfaces are clean and new sealant contacts original sealant.

F. Evaluation of Field-Test Results: Sealants not evidencing adhesive failure from testing or noncompliance with other indicated requirements, will be considered satisfactory. Remove sealants that fail to adhere to joint substrates during testing or to comply with other requirements. Retest failed applications until test results prove sealants comply with indicated requirements.

07 92 00 – JOINT SEALANTS | 9 of 9

3.7 CLEANING

A. Fresh compound accidentally smeared on adjoining surfaces: Scrape off immediately and rub clean with a solvent as recommended by manufacturer of the adjacent material or if not otherwise indicated by the caulking or sealant manufacturer.

B. Leave adjacent surfaces in a clean and unstained condition.

END OF SECTION 07 92 00

09 91 13 – EXTERIOR PAINTING | 1 of 2

09 91 13 – EXTERIOR PAINTING

PART 1 - GENERAL

1.1 SUMMARY

A. Section includes surface preparation and the application of paint systems on exterior substrates. The following exterior substrates:

1. Steel.

2. Wood.

1.2 DEFINITIONS

A. MPI Gloss Level 4: 20 to 35 units at 60 degrees and not less than 35 units at 85 degrees, according to ASTM

D523.

1.3 SUBMITTALS

A. ACTION SUBMITTALS

1. PRODUCT DATA

i. For each type of product. Include preparation requirements and application instructions.

(a) Include printout of current "MPI Approved Products List" for each product category specified, with the proposed product highlighted.

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. PRODUCTS

1. Subject to compliance with requirements, provide product listed in the Exterior Painting Schedule for the paint category indicated.

2.2 PAINT, GENERAL

A. MPI STANDARDS

1. Products shall comply with MPI standards indicated and shall be listed in its "MPI Approved Products Lists."

2. Material Compatibility:

3. Materials for use within each paint system shall be compatible with one another and substrates indicated, under conditions of service and application as demonstrated by manufacturer, based on testing and field experience.

4. For each coat in a paint system, products shall be recommended in writing by topcoat manufacturers for use in paint system and on substrate indicated.

B. COLORS

1. Match Existing

3.1 EXAMINATION

A. Examine substrates and conditions, with Applicator present, for compliance with requirements for maximum moisture content and other conditions affecting performance of the Work.

B. Maximum Moisture Content of Substrates:

1. When measured with an electronic moisture meter as follows:

i. Wood: 15 percent.

09 91 13 – EXTERIOR PAINTING | 2 of 2

C. Verify suitability of substrates, including surface conditions and compatibility with existing finishes and primers.

D. Proceed with coating application only after unsatisfactory conditions have been corrected.

E. Application of coating indicates acceptance of surfaces and conditions.

3.2 PREPARATION

A. Comply with manufacturer's written instructions and recommendations in "MPI Architectural Painting

Specification Manual" applicable to substrates and paint systems indicated.

B. Remove hardware, covers, plates, and similar items already in place that are removable and are not to be painted. If removal is impractical or impossible because of size or weight of item, provide surface-applied protection before surface preparation and painting.

C. After completing painting operations, use workers skilled in the trades involved to reinstall items that were removed. Remove surface-applied protection.

3.3 APPLICATION

A. Apply paints according to manufacturer's written instructions and recommendations in "MPI Manual."

B. Apply paints to produce surface films without cloudiness, spotting, holidays, laps, brush marks, roller tracking, runs, sags, ropiness, or other surface imperfections. Cut in sharp lines and color breaks.

3.4 CLEANING AND PROTECTION

A. Protect work of other trades against damage from paint application. Correct damage to work of other trades by cleaning, repairing, replacing, and refinishing, as approved by the COR, and leave in an undamaged condition.

B. At completion of construction activities of other trades, touch up and restore damaged or defaced painted surfaces.

END OF SECTION 09 91 13

09 91 23 – INTERIOR PAINTING | 1 of 3

09 91 23 – INTERIOR PAINTING

PART 1 - GENERAL

1.1 SUMMARY

A. Section includes surface preparation and the application of paint systems on the following interior substrates:

1. Wood.

2. Gypsum board.

1.2 DEFINITIONS

A. MPI Gloss Level 1: Not more than five units at 60 degrees and 10 units at 85 degrees, according to ASTM D523.

B. MPI Gloss Level 2: Not more than 10 units at 60 degrees and 10 to 35 units at 85 degrees, according to ASTM

D523.

C. MPI Gloss Level 3: 10 to 25 units at 60 degrees and 10 to 35 units at 85 degrees, according to ASTM D523.

D. MPI Gloss Level 4: 20 to 35 units at 60 degrees and not less than 35 units at 85 degrees, according to ASTM

D523.

E. MPI Gloss Level 5: 35 to 70 units at 60 degrees, according to ASTM D523.

F. MPI Gloss Level 6: 70 to 85 units at 60 degrees, according to ASTM D523.

G. MPI Gloss Level 7: More than 85 units at 60 degrees, according to ASTM D523.

1.3 SUBMITTALS

A. ACTION SUBMITTALS

1. PRODUCT DATA:

i. For each type of product indicated in this section:

(a) Include preparation requirements and application instructions.

(b) Include a printout of the current "MPI Approved Products List" for each product category specified, with the proposed product highlighted.

(c) Ensure product data indicates VOC contents.

B. INFORMATIONAL SUBMITTALS

1. LABORATORY TEST REPORTS:

i. For paints and coatings:

ii. Indicate compliance with requirements for low-emitting materials.

2.1 GENERAL

A. MANUFACTURERS

1. Subject to compliance with requirements, provide products by one of the following:

i. Benjamin Moore & Co.

ii. PPG Architectural Coatings.

iii. Sherwin-Williams Company (The).

iv. Or approved equal.

B. MPI STANDARDS

1. Products shall comply with MPI standards indicated and be listed in its "MPI Approved Products Lists."

09 91 23 – INTERIOR PAINTING | 2 of 3

C. MATERIAL COMPATIBILITY

1. Materials for use within each paint system shall be compatible with one another, and substrates indicated, under conditions of service and application as demonstrated by the manufacturer, based on testing and field experience.

2. For each coat in a paint system, topcoat manufacturers shall recommend products in writing for use in paint system and on the substrate indicated.

D. VOC CONTENT

1. For field applications inside the weatherproofing system, paints and coatings shall comply with VOC content limits of authorities having jurisdiction and the following VOC content limits:

i. Flat Paints and Coatings: 50g/l

ii. Non-flat Paints and Coatings: 150 g/L

iii. Primers, Sealers, and Undercoaters: 200 g/L.

E. LOW-EMITTING MATERIALS

1. Interior paints and coatings shall comply with the testing and product requirements of the Californian

Department of Public Health’s “Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers.”

F. COLORS

1. Match Existing

3.1 EXAMINATION

A. Examine substrates and conditions, with Applicator present, for compliance with requirements for maximum moisture content and other conditions affecting the performance of the Work.

B. Maximum Moisture Content of Substrates:

C. When measured with an electronic moisture meter as follows:

1. Wood: 15 percent.

2. Gypsum Board: 12 percent.

D. Verify the suitability of substrates, including surface conditions and compatibility with existing finishes and primers.

E. Proceed with the coating application only after unsatisfactory conditions have been corrected.

F. Application of coating indicates acceptance of surfaces and conditions.

3.2 PREPARATION

A. Comply with the manufacturer's written instructions and recommendations in "MPI Architectural Painting

Specification Manual" applicable to substrates and paint systems indicated.

B. Remove hardware, covers, plates, and similar items already in place that are removable and are not to be painted.

1. If removal is impractical or impossible because of the size or weight of the item, provide surface-applied protection before surface preparation and painting.

C. After completing painting operations, use workers skilled in the trades involved to reinstall items that were removed.

1. Remove surface-applied protection, if any.

3.3 APPLICATION

A. Apply paints according to the manufacturer's written instructions

09 91 23 – INTERIOR PAINTING | 3 of 3

B. Apply paints to produce surface films without cloudiness, spotting, holidays, laps, brush marks, roller tracking, runs, sags, ropiness, or other surface imperfections. Cut in sharp lines and color breaks.

3.4 INTERIOR PAINTING SCHEDULE

A. GYPSUM BOARD SUBSTRATES

1. GENERAL

i. Institutional Low-Odor/VOC Latex System MPI INT 9.2M

2. PRIME COAT

i. Primer sealer, interior, institutional low odor/VOC, MPI #149

3. INTERMEDIATE COAT

i. Latex, interior, low institutional odor/VOC matching topcoat.

4. TOPCOAT

i. Latex, interior, institutional low odor/VOC (MPI Gloss Level 4), MPI #146.

B. WOOD SUBSTRATES

1. GENERAL

i. Institutional Low-Odor/VOC Latex System MPI INT 6.3V

2. PRIME COAT

i. Primer sealer, interior, institutional low odor/VOC, MPI #39

3. INTERMEDIATE COAT

i. Latex, interior, institutional low odor/VOC matching topcoat.

4. TOPCOAT

i. Latex, interior, institutional low odor/VOC, flat (MPI Gloss Level 1), MPI #143.

ii. Topcoat: Latex, interior, institutional low odor/VOC, (MPI Gloss Level 2), MPI #144.

iii. Topcoat: Latex, interior, institutional low odor/VOC, (MPI Gloss Level 3), MPI #145.

iv. Topcoat: Latex, interior, institutional low odor/VOC, (MPI Gloss Level 4), MPI #146.

v. Topcoat: Latex, interior, institutional low odor/VOC, semi-gloss (MPI Gloss Level 5), MPI #147.

vi. Topcoat: Latex, interior, institutional low odor/VOC, gloss (MPI Gloss Level 6), MPI #148.

END OF SECTION 09 91 23

21 00 00 – FIRE SUPRESSION | 1 of 17

21 00 00 – FIRE SUPRESSION

PART 1 - GENERAL

1.1 PROJECT DESCRIPTION

A. The project involves the removal of the current dry pipe, water-based fire suppression system, and installing new automatic dry pipe systems and associated components to ensure a fully functional fire suppression system that provides comprehensive coverage for Apartment Buildings 94 and 96. These systems must be designed and installed in compliance with all relevant codes and standards specified in this scope of work and National Park Service (NPS) Standards.

1.2 LOCATION

A. The project is located in the West Glacier Headquarters area of Glacier National Park.

1.3 SPECIAL PROCEDURES

A. All work, including but not limited to architectural, mechanical, electrical, and structural, shall be performed with extreme care to avoid damage to existing materials that remain or that need to be removed and reinstalled.

Where "hot work" (open flame, grinding, welding, brazing, smelting) is required, the Contractor shall apply for and have on-site, at all times, a valid National Park Service hot work permit.

B. The authority having jurisdiction (AHJ) is the National Park Service Intermountain Region Structural Fire Management Officer.

1.4 MINIMAL DAMAGE

A. This project intends to maintain the historic and non-historic finishes and materials with "minimal damage" due to the work. Minimal damage is defined as removal and replacement with the same removed material without discernible damage to the material or no more than one small hole that is less than two (2) inch square in any one-foot square area. Damaged materials shall be replaced with similar or in-kind materials as the Contractor Officer approves.

B. Where required, the Contractor shall provide temporary service for utilities that are disrupted by work. The Contractor shall coordinate all temporary service disruptions with the NPS and other on-site contractors. The Contractor shall notify the Contracting Officer 48 hours before any planned utility interruptions.

C. Piping offsets, fittings, and any other accessories required shall be furnished to provide a complete installation and eliminate interference with other construction. Sprinklers shall be installed over and under ducts, piping, and platforms when such equipment negatively affects or disrupts the sprinkler discharge pattern and coverage.

1.5 QUALITY ASSURANCE

A. GENERAL

1. All work shall comply with this specification's applicable requirements, the codes, standards, and entities identified in section 1.8 of this specification, and applicable state and local codes.

2. Where required by applicable NFPA codes and standards or this specification, devices and equipment shall be UL-listed or FM-approved.

B. QUALIFICATIONS:

1. DESIGNER/INSTALLER

i. Company specializing in designing and installing water-based fire suppression systems.

(a) Experience: Continuously designed and installed water-based fire suppression systems in state of Montana for five years.

(b) Designer: Registered professional fire protection engineer in state of Montana or a certified NICET Level III Automatic Sprinkler System Layout Technician.

21 00 00 – FIRE SUPRESSION | 2 of 17

(c) Contractor shall be certified by the material/equipment manufacturer as trained in, and as knowledgeable of, the manufacturer's standard practice and procedure relating to installation of sprinkler systems. The Contractor shall be certified and licensed by the state and local jurisdictions, as applicable.

(d) Contractor shall be a firm specializing in performing work of this section with a minimum of five years’ experience and must be regularly engaged in the installation of water-based fire suppression systems.

(e) Contractor shall have successfully installed automatic water-based fire suppression systems of the same type and design as specified herein. The Contractor shall provide evidence of key personnel having such qualifications. The data shall include:

1. Names

2. Locations of at least three installations where the Contractor has installed such systems.

3. The Contractor shall indicate the type and design of each system and certify each system has performed satisfactorily in the manner intended for a period of not less than 12 months.

4. The Contractor shall submit a copy of a valid state sprinkler contractor certificate and license, as applicable.

2. PERSONNEL

i. Design: All fire sprinkler plans submittals, to include shop drawings and working plans, shall be developed in accordance with codes and standards identified in this specification by a Fire Protection Engineer registered in the State of Montana, or a certified NICET Level III Automatic Sprinkler System Layout Technician.

ii. Installation Supervision: The sprinkler system installation supervisor shall be qualified and experienced in the design and installation requirements of sprinkler systems following NFPA 13 and state requirements.

iii. The Contractor shall provide workers normally employed in the field and as otherwise specified in the specification and NFPA 13.

(a) Where required by this specification or NFPA 13 equipment and components shall bear the UL and/or FM label or marking.

3. OTHER REQUIREMENTS

i. The design, equipment, materials, installation, and workmanship shall be in strict accordance with the required and advisory provisions of this specification and NFPA 13 and other applicable NFPA codes.

ii. The advisory provisions (Annexes) of the NFPA publications referred to herein shall be considered to be mandatory, as though the word "shall" has been substituted for "should" wherever it appears. If there are any conflicts between these specifications and the referenced standards and publications, the most stringent requirement shall apply.

iii. The Contractor shall coordinate with the NPS and all trades and contractors on the site to ensure that the final installation of the water-based fire suppression system meets the minimum installation requirements of NFPA 13.

1.6 REFERENCES

A. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) – CURRENT RELEASES/EDITIONS

1. NFPA 13 (Standard for the Installation of Sprinkler Systems)

2. NFPA 25 (Inspection, Testing and Maintenance of Water-Based Fire Protection Systems)

3. NFPA 70 (National Electrical Code)

4. NFPA 72 (National Fire Alarm Code)

5. NFPA 101 (Life Safety Code)

21 00 00 – FIRE SUPRESSION | 3 of 17

6. NFPA 170 (Standard for Fire Safety and Emergency Symbols)

7. NFPA 291 (Recommended Practice for Fire Flow Testing and Marking of Hydrants)

B. INTERNATIONAL CODE COUNCIL – CURRENT RELEASES/EDITIONS

1. International Building Code

2. International Fire Code

C. UNDERWRITERS LABORATORIES, INC. (UL)

1. UL-193 Alarm Valves for Fire-Protection Service

2. UL-199 Automatic Sprinklers for Fire-Protection Service

3. UL-1468 Direct Acting Pressure Reducing and Pressure Restricting Valves

D. FACTORY MUTUAL SYSTEM (FM)

1. FM Approval Guide

E. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)

1. ANSI/ASME B1.20.1 - Pipe Threads, General Purpose

2. ANSI/ASME B16.1 - Cast Iron Pipe Flanges and Flanged Fittings

3. ANSI/ASME B16.3 - Malleable Iron Threaded Fittings, Class 150 and 300

4. ANSI/ASME B16.4 - Cast Iron Threaded Fittings, Class 125 and 250

5. ANSI/ASME B16.5 - Steel Pipe Flanges and Flanged Fittings

6. ANSI/ASME B16.9 - Factory-made Wrought Steel Buttweld Fittings

7. ANSI/ASME B16.11 - Forged Steel Fittings, Socket-Welded and Threaded

8. ANSI/ASME B16.21 - Nonmetallic Flat Gaskets for Pipe Flanges

9. ANSI/ASME B16.25 - Buttwelded Ends for Pipe, Valves, Flanges, and Fittings

10. ANSI/ASME B36.10M - Wrought Steel Pipe

F. AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM)

1. ASTM A53 - Welded and Seamless Steel Pipe

2. ASTM A126 - Gray Iron Castings for Valves, Flanges, Pipe Fittings

3. ASTM A135 - Electric-Resistance-Welded Steel Pipe

4. ASTM A183 - Carbon Steel Track Bolts and Nuts

5. ASTM A193 - Alloy-Steel and Stainless Steel Bolting Materials for High Temperature Service

6. ASTM A194 - Carbon and Alloy Steel Nuts and Bolts for High Pressure and High-Temperature Service

7. ASTM A197 - Cupola Malleable Iron

8. ASTM A234 - Piping Fittings of Wrought Carbon Steel and Alloy Steel for Moderate and Elevated

Temperatures

9. ASTM A307 - Carbon Steel Bolts and Studs, 60,000 psi Tensile Strength

10. ASTM F436 - Hardened Steel Washers

11. ASTM A536 - Ductile Iron Castings

12. ASTM A795 - Black and Hot-Dipped Zinc-Coated (Galvanized) Welded and Seamless Steel Pipe for Fire

Protection Use

G. AMERICAN WELDING SOCIETY (AWS)

1. AWS D10.9 - Specification for Qualification of Welding Procedures and Welders for Piping and Tubing

H. AMERICAN WATER WORKS ASSOCIATION (AWWA)

1. AWWA C104 - Cement Mortar Lining for Ductile Iron Pipe and Fittings for Water

2. AWWA C110 - Ductile Iron and Gray Iron Fittings, 3-in. through 48-in. for Water and Other Liquids

3. AWWA C111 - Rubber Gasket Joints for Ductile Iron Pressure Pipe and Fittings

4. AWWA C115 - Flanged Ductile Iron Pipe and Threaded Flanges

21 00 00 – FIRE SUPRESSION | 4 of 17

5. AWWA C150 - Thickness Design of Ductile Iron Pipe

6. AWWA C151 - Ductile Iron Pipe Centrifugally Cast in Metal Molds or Sand-Lined Molds, for Water or Other

Liquids

7. AWWA C153 - Ductile Iron Compact Fittings, 3-in. through 12-in., for Water and Other Liquids

8. AWWA C600 - Installation of Ductile Iron Water Mains and Their Appurtenances

1.7 DEFINITIONS

A. AHJ: Authority Having Jurisdiction. The Authority Having Jurisdiction is the National Park Service Intermountain

Region Structural Fire Management Officer B. ALARM SIGNAL: Signifies a state of emergency requiring immediate action. Pertains to signals from operation of an alarm initiating device.

C. APPROVED: Acceptable to the Authority Having Jurisdiction.

D. AUTOMATIC FIRE ALARM SYSTEM: A system providing an emergency function without the necessity of human intervention and activated as a result of a predetermined temperature rise, or increase in level of products of combustion, in accordance with the minimum requirement of NFPA 72.

E. CO: Contracting Officer F. COR: Contracting Officer's Representative G. DRY PIPE SPRINKLER SYSTEM: A sprinkler system employing automatic sprinklers that are attached to a piping system containing air or nitrogen under pressure, the release of which (as from the opening of a sprinkler) permits the water pressure to open a valve known as a dry pipe valve, and the water then flows into the piping system and out the opened sprinklers.

H. FIRE PROTECTION SPRINKLER CONTRACTOR: A person or company engaged in the planning, sale, installation, repair, alteration, addition, maintenance, or inspection of fire protection sprinkler systems or water spray systems.

I. FLOW: The flow rate of the water from the source under flow conditions.

J. GRADE: Lowest point of elevation of the finished surface of ground, paving, or sidewalk with the area between the building and property line.

K. HAZARDOUS AREA/ROOM: An area in a structure of building used for the process or storage that involves highly combustible, flammable, or explosive products or other material which may present a potential danger to life, health, property through fire, explosion, etc.

L. HISTORIC STRUCTURE: A building deemed to have historical, architectural, or cultural significance by regional or national jurisdiction.

M. HYDRAULICALLY DESIGNED SYSTEM: A calculated sprinkler system in which pipe sizes are selected on a pressure loss basis to provide a prescribed water density, in gallons per minute per square foot (min), or a prescribed minimum discharge pressure or flow per sprinkler, distributed with a reasonable degree of uniformity over a specified area.

N. NICET: National Institute for Certification in Engineering Technologies O. NPS: National Park Service P. PIPE SCHEDULE SYSTEM: A sprinkler system in which the pipe sizing is selected from a schedule that is determined by the occupancy classification and in which a given number of sprinklers are allowed to be supplied from specific sizes of pipe.

Q. RESIDUAL PRESSURE: The pressure available from the source under flow conditions.

R. SPRINKLER SYSTEM: For fire protection purposes, an integrated system of underground and overhead piping designed in accordance with fire protection engineering standards. The installation includes one or more automatic water supplies. The portion of the sprinkler system aboveground is a network of specially sized or

21 00 00 – FIRE SUPRESSION | 5 of 17 hydraulically designed piping installed in a building, structure, or area, generally overhead, and to which sprinklers are attached in a systematic pattern. The valve controlling each system riser is located in the system riser or its supply piping. Each sprinkler system riser includes a device for actuating an alarm when the system is in operation. The system is usually activated by heat from a fire and discharges water over the fire area.

S. STATIC PRESSURE: The pressure available from the source when no water is flowing to the system.

T. SUPERVISORY SIGNAL: Indicates abnormal status or need for action regarding fire suppression or other protective system, such as a control valve supervisory/tamper switch.

U. TROUBLE SIGNAL: Indicates that a fault, such as an open circuit or ground, has occurred in indicating appliance circuit, initiating device circuit, or internal to FACP.

V. WATER-BASED FIRE SUPPRESSION SYSTEM (FIRE SPRINKLER): A system of W. overhead and underground piping to protect the interior or exterior of a building or structure from fire where the primary extinguishing agent is water.

X. WATERFLOW ALARM DEVICE: A mechanical device mounted on the sprinkler pipe that has a paddle internal to the sprinkler pipe to monitor the water for flow. This device is typically monitored by the building fire alarm system.

1.8 SYSTEM DESCRIPTION

A. Provide an automatic dry pipe fire sprinkler system in all areas of the building/areas indicated on the drawings, and provide complete fire protection coverage in accordance with the required and annex provisions of NFPA 13 for the uniform distribution of water.

B. The dry pipe sprinkler system shall be hydraulically designed to provide densities as described in this specification.

C. The activation of waterflow switches shall announce an alarm condition at the sprinkler monitoring panel or fire alarm control panel.

D. Valve tamper and circuit trouble conditions shall be annunciated at the sprinkler monitoring panel or fire alarm control panel as supervisory and trouble conditions, respectively.

E. Sprinkler protection shall be provided based on the hazard classifications in this specification and NFPA 13.

1.9 SYSTEM COMPONENTS COMPLIANCE

A. Performance requirements for the fire sprinkler will be determined by a review of construction submittals and by field inspection.

B. Compliance review shall be performed by the AHJ, or his/her designee.

1. Compliance review is to verify that the Contractor is providing systems, products, and/or materials that will satisfy the stated criteria.

2. This review shall not relieve the Contractor from responsibility for any errors or omissions, nor from responsibility for complying with the requirements of the project contract, this specification, or NFPA 13.

1.10 HYDRAULIC SYSTEM DESIGN PARAMETERS

A. HAZARD CLASSIFICATIONS

1. Ordinary Hazard (Group 1)

i. Provide sprinklers hydraulically designed to provide a minimum density of 0.15 gallons per minute per square foot over the hydraulically most remote 1500 square feet of floor area, for a minimum of 60 minutes where the sprinkler system is remotely electronically supervised and monitored off site (90 minutes is not remotely monitored). Water supply calculation will include 250 gpm for inside and outside hose streams.

B. HYDRAULIC DESIGN REQUIREMENTS

1. Sprinkler Discharge Area

21 00 00 – FIRE SUPRESSION | 6 of 17

i. The discharge area for each system shall be the hydraulically most remote area as defined in NFPA 13 and as stated for the occupancies referenced above.

2. Friction Losses

i. Losses in pipe shall be calculated in accordance with the Hazen-Williams formula with "C" values in accordance with NFPA 13.

3. A minimum 10 pounds per square inch safety margin over the required pressure shall be incorporated into all hydraulic calculations.

4. If the system minimum requirements cannot be met, it is the responsibility of the Contractor to identify alternative options with costs and discuss with the AHJ.

C. WATER SUPPLY

1. Contractor shall be responsible for performing waterflow test to determine the performance of the water distribution system. Flow tests shall be performed on the two fire hydrants closest to the facility in which D. Location and spacing of sprinklers in relation to the ceiling, light fixtures, ventilation equipment, storage, ceiling fans, and soffits, shall not exceed that permitted by NFPA 13 and the listing of each sprinkler. The spacing of sprinklers on the branch lines for open areas shall be uniform.

E. Drain pipes shall be 2 inch and valves shall be installed on the system to allow drainage. The system shall drain to the maximum extent possible through the main drain valve. Discharge from the drain pipe shall be to the building exterior, directed away from the building and stair. The discharge from the drain pipe shall be piped to within 8 inches of grade. Splash blocks under the drain outlet shall be provided to prevent soil erosion. Discharge to sump pumps, floor drains, sinks and waste lines, etc. is not permitted.

1.11 PIPE SCHEDULE SYSTEM DESIGN PARAMETERS

A. Pipe schedule method shall be permitted only for new installations of 5000 sq. ft. or less or for additions or modifications to existing pipe schedule systems sized according to the pipe schedules of the appropriate chapter of NFPA 13.

B. The pipe schedule method shall be permitted for use in systems exceeding 5000 sq. ft. where the flows required by the appropriate chapter of NFPA 13 are available at a minimum residual pressure of 50 psi at the highest elevation of sprinkler.

C. Pipe schedule system shall meet the minimum flow and pressure requirements of NFPA 13.

D. The number of sprinklers on each given pipe size shall meet NFPA 13 requirements.

E. Extra hazard occupancies shall be hydraulically calculated.

F. The pipe schedule method shall be permitted for additions or modifications to existing extra hazard pipe schedule systems.

1.12 SUBMITTALS

A. The COR shall review and "accept/reject" or take other appropriate action on the Contractor's submittals including shop drawings, samples, documentation, and as-built drawings. This review is to verify conformance to project specifications and design concepts expressed in the contract documents. The AHJ is allotted 20 working days to review and approve/reject each submittal.

B. SHOP DRAWINGS

1. The Contractor shall prepare and submit at least four (4) complete sets of detailed shop drawings indicating the proposed layout of equipment, mains, risers, hangers, pipes, and sprinklers.

2.

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .