B08_Attachment_10_-_Addendum_1_Apartments_94___96_Fire_Sprinkler_Systems_Replacement_0001.pdf
PDF 404 KB Posted
- Attached to
- Fire Sprinkler System Replacements Federal contract opportunity
- Solicitation number
- 140P1424Q0112
About this file
This document is an addendum to the request for a fire sprinkler system replacement project at Apartments 94 and 96 in Glacier National Park. The addendum provides details on the existing conditions of the buildings, including the total number of sprinkler heads, their locations, and access points to the attics. It notes that the joint compound in the interior walls contains asbestos, which must be addressed. The addendum is related to a federal contract opportunity issued by the Department of the Interior National Park Service Intermountain Region to replace the fire sprinkler systems at these two apartment buildings. The solicitation number is 140P1424Q0112, and the project is for the Fire Sprinkler System Replacements at Glacier National Park.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140P1424Q0112_Amd_0002.pdf | ||
| Sol_140P1424Q0112_Amd_0001.pdf | ||
| B08_Attachment_9_-_Site_Visit_Sign-in_Sheet_0001.pdf | ||
| B08_Attachment_5_HAZMAT_INSP_B96_HQ_MAY13.pdf | ||
| B08_Attachment_1_Statement_of_Work.pdf | ||
| B08_Attachment_2_Project_Specifications_07-15.pdf | ||
| Sol_140P1424Q0112.pdf | ||
| B08_Attachment_3_Wage_Determination_MT20240022_01052024.pdf | ||
| B08_Attachment_4_HAZMAT_INSP_B94_HQ_DEC20.pdf | ||
| B08_Attachment_8_Apartment_96_Floor_Plan.pdf | ||
| B08_Attachment_6_Site_Map.pdf | ||
| B08_Attachment_7_Apartment_94_Floor_Plan.pdf |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Apartments 94 and 96 Fire Sprinkler Replacement Addendum #1
08/27/2024
General information and notes:
- The contractor may cut a hole in an interior or exterior walls or remove a vent to aid in construction and demolition. All openings must be weather-proofed and patched at the end of the job. Note that the joint compound in the interior walls in each building tested positive for asbestos.
- In B#96, there are attic accesses in the storage room and units B and G. Access to inside these apartments must be coordinated with NPS.
B#94 Apartments existing conditions - 109 total sprinkler heads
- Attic access through the storage room in the front of the building
- Typical one bedroom apartments (units A, B, G & H) – 9 sprinkler heads per unit o 3 sprinkler heads in living room o 1 sprinkler head in kitchen o 1 sprinkler head in each of two hallway closets o 1 sprinkler head in bathroom o 1 sprinkler head in bedroom o 1 sprinkler head in bedroom closet o
- Typical studio apartments (units C, D, E, & F) – 6 sprinkler heads per unit o 1 sprinkler head in living room o 1 sprinkler head in kitchen o 1 sprinkler head in each of two hallway closets o 1 sprinkler head in bathroom o 1 sprinkler head in hallway o
- Laundry room (rear of building) o 1 sprinkler head in laundry room
- Storage and riser room (front of building) o 2 sprinkler heads
- Exterior o 6 exterior sprinkler heads under front porch
Apartments 94 and 96 Fire Sprinkler Replacement Addendum #1
08/27/2024 o Low point drain at east end of building
- Attic o 40 sprinkler heads (assumed)
B#96 Apartments existing conditions – 109 total sprinkler heads
- Attic access through the storage room and units B and G
- Typical one bedroom apartments (units A, B, G & H) – 9 sprinkler heads per unit o 3 sprinkler heads in living room o 1 sprinkler head in kitchen o 1 sprinkler head in each of two hallway closets o 1 sprinkler head in bathroom o 1 sprinkler head in bedroom o 1 sprinkler head in bedroom closet o
- Typical studio apartments (units C, D, E, & F) – 6 sprinkler heads per unit o 1 sprinler head in living room o 1 sprinkler head in kitchen o 1 sprinkler head in each of two hallway closets o 1 sprinkler head in bathroom o 1 sprinkler head in hallway o
- Laundry room (rear of building) o 1 sprinkler head in laundry room
- Storage and riser room (front of building) o 1 sprinkler head
- Exterior o No exterior sprinkler heads o Low point drain at east end of building
- Attic o 47 sprinkler heads (assumed)