B01 Att J02 - Construction Drawings.pdf
PDF 13 MB Posted
- Attached to
- Whiteriver Hospital Backup Generator Federal contract opportunity
- Solicitation number
- 75H70123R00024
About this file
This document provides details for a federal contract solicitation for construction services. The Indian Health Service is seeking a contractor to install a backup generator at Whiteriver Hospital in Whiteriver, Arizona under solicitation number 75H70123R00024. The work includes renovating the essential electrical system to accommodate an additional generator as a backup to the existing emergency generator, though the generator itself is not included in the scope of work. The period of performance is 180 calendar days from the notice to proceed and the total value is anticipated to be between $500,000 and $1,000,000. A site visit is scheduled for May 15, 2023 and the contract type will be firm fixed price. The response is due as a request for proposal to be evaluated using lowest price technically acceptable criteria.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| B05 Amend A00002.pdf | ||
| B05 Amend A00001.pdf | ||
| B01 Att J04 - Construction Narrative.pdf | ||
| B01 Att J01 - WD AZ20230027 Mod 1 2023.02.03.pdf | ||
| B01 RFP 75H70123R00024 Whiteriver Backup Generator Installation.pdf | ||
| B01 Att J09 - Key Personnel Resume Form.docx | DOCX document | |
| B01 Att J05a - FORMS_TPT_5000HC_11228.pdf | ||
| B01 Att J03 - Construction Specifications.pdf | ||
| B01 Att J06 - Self Performed Calculation Sheet (Construction).docx | DOCX document | |
| B01 Att J10 - Generator Price Schedule.xlsx | XLSX spreadsheet | |
| B01 Att J08 - PPQ.docx | DOCX document | |
| B01 Att J07 - Company Specialized Experience Form Construction.docx | DOCX document | |
| B01 Att J05 - 2023 Exemption Letter for a Qualifying Hospital.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A. THE CONTRACTORS SHALL COORDINATE EQUIPMENT AND
MATERIAL TRAFFIC AND STORAGE WITH OWNER.
B. ALL UTILITY WORK SHALL BE COORDINATED WITH MECHANICAL,
PLUMBING ELECTRICAL, AND FIRE PROTECTION.
C. ALL ASPECTS OF CONTRACTOR STAGING AND CONSTRUCTION
PHASING SHALL BE APPROVED BY OWNER.
D. ALL HOSPITAL ACCESS POINTS, AND ALL BUILDING EXITS, MUST
REMAIN ACCESSIBLE, CLEAR AND UNOBSTRUCTED THROUGHOUT
ALL PHASES OF DEMOLITION AND CONSTRUCTION. SHORT-TERM
CLOSURE MAY BE ACCEPTABLE AS COORDINATED WITH OWNER.
E. THE CONTRACTOR SHALL COORDINATE ALL ROOF TOP WORK AND
ROOF REPAIRS WITH THE OWNER.
GENERAL PHASING NOTES
1050 E. Southern Ave, Suite #D, Tempe, Arizona 85282, (480) 751-9542designgroup
Architecture, Engineering, and Sustainable Design
AESUS
KEY PLAN NTS NORTH
Drawing Title: Project Title:
Date
Location
Checked
Building Number:
Project Number:
Drawing Number:
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
WHITERIVER HOSPITAL BACKUP
GENERATOR INSTALL
Location:
100% Submittal - Not for Construction
NOV. 03, 2022
PH22WR03H8
WHITE RIVER INDIAN HEALTH SERVICE
200 W HOSPITAL DR. WHITERIVER, AZ 85941
AESUS
BOILER PLANT
AREA OF WORK
AESUS
G-100
COVER SHEET
DX
A3-301
X
XX
X
DETAIL FLAG NUMBER
DOOR NUMBER
AE-501
BUILDING SECTION CUT
OTHER SECTION CUT
SHEET WHERE APPEARS (TYPICAL)
AE-301
AA
SHEET WHERE APPEARS
ELEVATION NUMBER
SHEET WHERE APPEARS
x x x x
EXISTING COLUMN CENTER LINEA
X
WINDOW TAG
AE-301
AA
AE-301
AA
ELEVATION NUMBER
AE-710
4 2
DASHED LINE
AROUND
AREA DETAILED
PLAN OR DETAIL NUMBERX
EQ-X
CPT1
W-X
E
EA EACH
E EAST
EWC ELECTRIC WATER COOLER
ELEC ELECTRIC (AL)
EL ELEVATION
ELEV ELEVATOR
EMER EMERGENCY
ENGR ENGINEER
EQ EQUAL
EQUIP EQUIPMENT
EXIST EXISTING
ETR EXISTING TO REMAIN
EXP EXPANSION
EXP BT EXPANSION BOLT
EJ EXPANSION JOINT
EXP EXPOSED
EXT EXTERIOR
EIFS EXTERIOR INSULATION AND
FINISH SYSTEM
F
FWC FABRIC WALL COVERING
FT FEET, FOOT
FGL FIBERGLASS
FIN FINISH
FIN GR FINISH GRADE
FDV FIRE DEPARTMENT VALVE
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER
CABINET
FHC FIRE HOSE CABINET
FP FIREPROOF
FIXT FIXTURE
FLASH FLASHING
FLEX FLEXIBLE
FLR FLOOR
FD FLOOR DRAIN
FLUOR FLUORESCENT
FTG FOOTING
FDTN FOUNDATION
FRMG FRAMING
FURN FURNACE, FURNITURE
G
GA GAGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GL GLASS
GL BLK GLASS BLOCK
GB GRAB BAR
GR GRADE
GRAN GRANITE
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GUT GUTTER
GYP BD GYPSUM BOARD
H
HNDRL HANDRAIL
HDW HARDWARE
HDWD HARDWOOD
HD HEAD
HVAC HEATING, VENTILATING, AIR CONDITIONING
HT HEIGHT
HPT HIGH POINT
HC HOLLOW CORE
HM HOLLOW METAL
HORIZ HORIZONTAL
HB HOSE BIBB
HOSP HOSPITAL
HR HOUR
I
IN INCH
INFO INFORMATION
ID INSIDE DIAMETER
INSUL INSULATED,INSULATION
INT INTERIOR
J
JAN JANITOR
JT JOINT
K
KPL KICKPLATE
KIT KITCHEN
KB KNEE BRACE
L
LAB LABORATORY
LAM LAMINATE
LC LAUNDRY CHUTE
LV LAVATORY
LT LIGHT
LD LINEAR DIFFUSER
L CL LINEN CLOSET
LL LIVE LOAD
LLV LONG LEG VERTICAL
LPT LOW POINT
M
MACH MACHINE
MH MANHOLE
MFD MANUFACTURED
MFR MANUFACTURER
MRB MARBLE BASE
MRF MARBLE FLOOR
MKR BD MARKER BOARD
MO MASONRY OPENING
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MED MEDICAL
MC MEDICINE CABINET
MEMB MEMBRANE
MTL METAL
MIN MINIMUM, MINUTE
MISC MISCELLANEOUS
MOD MODIFIED
MLDG MOLDING
N
NAT FIN NATURAL FINISH
NOM NOMINAL
N NORTH
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NTS NOT TO SCALE
NO NUMBER
O
OFF OFFICE
OC ON CENTER
OPNG OPENING
OPP OPPOSITE
OPH OPPOSITE HAND
ORCH ORCHESTRA
ORN ORNAMENTAL
OD OUTSIDE DIAMETER
OH OVERHANG, OVERHEAD
OF/CI OWNER FURNISHED/
CONTRACTOR INSTALLED
O OXYGEN
P
P PAINT
PR PAIR
PNL PANEL
PTD PAPER TOWEL DISPENSER
PTN PARTITION
PERF PERFORATED
PC PIECE
PLAM PLASTIC LAMINATE
PLAS PLASTIC, PLASTER
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PCC PRECAST CONCRETE
PREFAB PREFABRICATE
PREFIN PREFINISH
PROD PRODUCTION
Q
QTY QUANTITY
QT QUARRY TILE
A
AFF ABOVE FINISHED FLOOR
ACST ACOUSTIC (AL)
ACT ACOUSTICAL CEILING TILE
APC ACOUSTICAL PANEL CEILING
AWP ACOUSTICAL WALL PANEL
AWT ACOUSTICAL WALL
ADJ ADJUSTABLE
A/C AIR CONDITIONING
AHU AIR HANDLING UNIT
ALT ALTERNATE
ALUM ALUMINUM
AB ANCHOR BOLT
AL ANGLE
APPROX APPROXIMATE
ARCH ARCHITECT (URAL)
ASPH ASPHALT
ASSY ASSEMBLY
AUTO AUTOMATIC
AWN AWNING
B
BALC BALCONY
BSMT BASEMENT
BM BEAM, BENCHMARK
BR BEDROOM
BLKG BLOCKING
BD BOARD
BOT BOTTOM
BRKT BRACKET
BRK BRICK
B CL BROOM CLOSET
BLDG BUILDING
BLT IN BUILT-IN
BUR BUILT-UP ROOFING
C
CAB CABINET
CPT CARPET
CSMT CASEMENT
CI CAST IRON
CB CATCH BASIN
CLG CEILING
CEM CEMENT
CL CENTER LINE
CER CERAMIC
CT CERAMIC TILE
CO CLEANOUT, CASED OPENING
CLR CLEAR, COLOR
CLO CLOSET
COL COLUMN
CMPST COMPOSITE
CONC CONCRETE
CMU CONCRETE MASONRY UNIT
CONSTR CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
COTR CONTRACTING OFFICER
CJ CONTROL JOINT
COP COPING
CU COPPER
CG CORNER GUARD
CORR CORRIDOR
CNTR COUNTER
CSK COUNTER SUNK
D
DMPF DAMPPROOFING
DL DEAD LOAD
DEMO DEMOLITION
DET DETAIL
DIA DIAMETER
DIFF DIFFUSER
DIM DIMENSION
DR DOOR, DRAIN
DH DOUBLE HUNG
DN DOWN
DS DOWNSPOUT
DWR DRAWER
DWG DRAWING
DF DRINKING FOUNTAIN
DUPL DUPLICATE
R
R RADIUS, RISER
RWD REDWOOD
REF REFERENCE, REFRIGERATOR
REINF REINFORCE
REQD REQUIRED
RB RESILIENT BASE
RF RESILIENT FLOORING
RA RETURN AIR
REV REVISION
RD ROOF DRAIN
RM ROOM
RO ROUGH OPENING
RS ROUGH SAWN
S
SCHED SCHEDULE
SECT SECTION
SHTHG SHEATHING
SHT SHEET
SHV SHELVING
SIM SIMILAR
S SOUTH
SP FIN SPECIAL FINISH
SPEC SPECIFICATION
SQ SQUARE
SF SQUARE FEET
SST STAINLESS STEEL
STD STANDARD
STL STEEL
STL JST STEEL JOIST
STOR STORAGE
STRUCT STRUCTURAL
S4S SURFACED FOUR SIDES
SUSP SUSPEND
SW SWITCH
SYMM SYMMETRICAL
T
TK BD TACKBOARD
TEL TELEPHONE
TV TELEVISION
TMPD TEMPERED
TEMP TEMPORARY
TER TERRAZZO
THK THICKNESS
TPD TOILET PAPER DISPENSER
T&G TONGUE AND GROOVE
TOS TOP OF SLAB, STEEL
T TREAD
TYP TYPICAL
U
UC UNDERCUT
UNFIN UNFINISH
UNO UNLESS NOTED OTHERWISE
V
VAC VACUUM
VR VAPOR RETARDER
VNR VENEER
VP VENEER PLASTER
VIF VERIFY IN FIELD
VERT VERTICAL
VEST VESTIBULE
VCT VINYL COMPOSITION TILE
VWC VINYL WALL COVERING
W
W CAB WALL CABINETS
WC WALL COVERING, WATER CLOSET
WP WATERPROOFING, WEATHER
PROOF, WORKING POINT
WT WEIGHT
WWF WELDED WIRE FABRIC
W WEST
WF WIDE FLANGE
WDW WINDOW
W/ WITH
W/O WITHOUT
WD WOOD
WDP WOOD PANELING
KEYED NOTE
WALL TYPE
X
X WINDOW TREATMENT TYPE
EQUIPMENT
INTERIOR FINISH TYPE
FURNITURE, FIXTURE, EQUIPMENT
CONTRACT LIMIT LINE
COLUMN CENTER LINE
NEW WALL
DEMOLITION
EXISTING WALL
NORTH
Project No: PH22WR03H8
DESIGN TEAM
ABBREVIATIONS OWNER
CODE REFERENCES
FOR THE PURPOSE OF THIS TASK WE WILL BE USING THE LATEST VERSION OF THE
NFPA AND IBC CODES.
A. BUILDING: 2021 INTERNATIONAL BUILDING CODE
B. ENERGY: 2021 INTERNATIONAL ENERGY CONSERVATION CODE
C. PLUMBING: 2021 INTERNATIONAL PLUMBING CODE
D. MECHANICAL: 2021 INTERNATIONAL MECHANICAL CODE
E. ELECTRICAL: 2020 INTERNATIONAL ELECTRICAL CODE, NFPA 70
F. FIRE: 2021 INTERNATIONAL FIRE CODE
G. NFPA 99, HEALTH CARE FACILITIES CODE
H. NFPA 110, STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS
I. ASHRAE, THE COMMISSIONING PROCESS, GUIDELINE 0
J. ASHRAE, COMMISSIONING PROCESS FOR BUILDING AND SYSTEMS, STANDARD 202
K. ENERGY CONSERVATION STANDARDS FOR NEW FEDERAL LOW RISE
RESIDENTIAL BUILDINGS 10 CFR PART 435
L. 2019 IHS ARCHITECT/ENGINEER DESIGN GUIDE.
M. CONSULT THE WHITE MOUNTAIN APACHE TRIBE AND LOCAL UTILITIES FOR ANY
LOCAL JURISDICTIONAL CODES AND STANDARDS THAT MUST BE FOLLOWED
PROJECT DESCRIPTION
FACILITY MAP
SYMBOL LEGEND
BUILDING INFORMATION
BUILDINGS INVOLVED IN PROJECT INCLUDE THE FOLLOWING:
THE WHITERIVER BOILER PLANT.
NO LIFE SAFETY WILL BE AFFECTED BY THIS PROJECT OR THE
CONSTRUCTION OPERATION.
GENERAL NOTES
VICINITY MAP
BASE BID:
A. INSTALL ALL INFRASTRUCTURE TO SUPPORT GEN 2 INSTALLATION
INCLUDING BUT NOT LIMITED TO:
a. SB-GEN DISTRIBUTION BOARD
b. INSTALLATION OF CONDUITS WITH PULL STRING TO
GENERATOR PAD FOR POWER
c. INSTALLATION CONDUITS WITH PULL STRING FOR
GENERATOR PAD FOR CONTROLS.
d. INSTALLATION OF CONDUITS AND CONDUCTORS WITHIN
ELECTRICAL ROOM FROM SB-GEN TO ATS-NED AND EDP.
e. EQUIPMENT PAD, CONCRETE, AND EARTH WORK.
BID OPTION 1:
A. GEN 2 INSTALLATION INCLUDING:
a. TESTING GEN 2 AT EXISTING SITE TO CONFIRM
FUNCTIONALITY.
b. TRANSPORTING GEN 2 FROM EXISTING SITE TO WHITERIVER
HOSPITAL.
c. INSTALLATION AND CONNECTION ON GEN 2 POWER AND
CONTROLS.
d. CONDUCTORS BETWEEN GEN 2 AND SB-GEN.
e. CONTROL WIRING BETWEEN SELECTOR SWITCH AND GEN.
f. TESTING AND COMMISSIONING OF GEN 2.
g. FENCING, GATE, AND BOLLARDS.
THE SCOPE OF WORK SHALL INSTALL A BACKUP GENERATOR ON SITE TO PROVIDE
REDUNDANCY FOR THE EXISTING WHITERIVER HOSPITAL PRIMARY GENERATOR.
THIS WORK SHALL INCLUDE BUT NOT BE LIMITED TO ARCHITECTURAL, STRUCTURAL,
MECHANICAL, & ELECTRICAL.
BID ITEMS
DESCRIPTIONSYMBOL
WHITERIVER HOSPITAL BACKUP GENERATOR INSTALL
WHITERIVER INDIAN HOSPITAL
INDIAN HEALTH SERVICE
Architect & Structual
MPE Engineers
1050 E. Southern Ave. Suite 5, Tempe, Arizona 85282
AESUS Design Group
1050 E. Southern Ave. Suite 5, Tempe, Arizona 85282
AESUS Design Group
Orlando Gonzales (ogonzales@aesusdesign.com)
480-454-2861
David Combs (dcombs@aesusdesign.com)
480-454-2861
NORTH
PROJECT AREA
PROJECT SITE
IHS Whiteriver Indian Hospital
A. ANY CHANGES MUST BE APPROVED BY OWNER BEFORE DOING ANY
ADDITIONAL WORK. WORK SCHEDULE TO BE PERFORMED DURING
REGULAR DAY SHIFT HOURS (8AM-4:30PM) ANY WORK OUTSIDE OF
REGULAR SCHEDULE REQUIRES APPROVAL FROM OWNER.
B. COORDINATE STAGING AREA WITH OWNER, AND FIND INTERIOR
COVERED STORAGE ON SITE FOR MATERIALS THAT MUST BE
PROTECTED FROM ELEMENTS - COORDINATE WITH OWNER.
C. WORK PERFORMED FOR THIS PROJECT MAY INTERRUPT SERVICE TO
ADJACENT AREAS AT TIMES BUT WILL NOT INTERRUPT OVERALL
FACILITY OPERATION. SEE ELECTRICAL FOR POWER INTERRUPTION
AND OUTAGE REQUIREMENTS.
D. CONTRACTOR TO VERIFY ALL DETAILS AGAINST EXISTING
CONDITIONS PRIOR TO PURCHASE OF EQUIPMENT AND PRIOR TO
CONSTRUCTION. CONTRACTOR IS RESPONSIBLE FOR BRINGING ANY
DISCREPANCIES IN PLANS AND EXISTING SITE CONDITIONS TO
IMMEDIATE ATTENTION OF THE OWNER
E. CONTRACTOR SHALL PERFORM ALL WORK AND PROVIDE ALL
MATERIALS IN ACCORDANCE WITH CONSTRUCTION SPECIFICATIONS.
G. NOT ALL KEYNOTES ARE ON ALL SHEETS.
200 West Hospital Drive, Whiteriver, AZ 85941
ISSUED SHEETS
Sheet Number Sheet Name
GENERAL
G-100 COVER SHEET
CIVIL
C101 GRADING PLAN
C102 DETAILS
ARCHITECTURE
AE-100 LEVEL 01 FLOOR PLAN
STRUCTURAL
S-001 GENERAL STRUCTURAL NOTES
S-002 GENERAL STRUCTURAL NOTES / ABBREVIATIONS / LEGENDS
S-101 PLANS AND DETAILS
MECHANICAL
M-001 MECHANICAL ABBREVIATIONS
M-101 MECHANICAL OVERALL PLAN
M-501 MECHANICAL DETAILS
ELECTRICAL
E-001 SYMBOLS AND ABBREVIATIONS
E-201 ELECTRICAL POWER PLAN
E-601 ELECTRICAL ONE-LINE DIAGRAM
E-401 GROUNDING DETAILS
Project Number:
75H70122F30010
SEPT. 16, 2022NOV. 03, 2022NOV 17, 2022
FINAL SUBMITTAL - 100%
CONSTRUCTION DOCUMENTS
David Combs Snapshot
-4.5%
-6 .1
-47.4%
-9 .6
-2.6%
-6.1%
-3 6.
9%
-3 0.
2% -3 3.
6%
-3 8.
9%
-3 4.
8%
-11.5%
-5 0.
7%
-3 1.
0%
-3 6.
9% -5
.0
-4 .4
-4 6.
0%
-3 4.
5%
-3.0%
-4 .1
-2 .9
-4 .4
-1 .5
T
T
5464.25 5464.14
5473.00
5473.22
5472.33
5464.16
5471.54
5470.72
5471.52
5478.16
5485.71
5480.36
5485.17
54825482
54765477
SB-GEN
PAD: 5478.25'
TOP SLAB: 5479.083'
1050 E. Southern Ave, Suite #D, Tempe, Arizona 85282, (480) 751-9542designgroup
Architecture, Engineering, and Sustainable DesignAESUS
KEY
PLAN
NTS
Drawing Title:
Project Title:
Date
Location
Checked
Building Number:
Project Number:
Drawing Number:
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Location:
1" = 10'-0"1 GRADING PLAN
NORTHNORTH
EXISTING METAL STAIRS
EXISTING UNDERGROUND
WATER STORAGE TANKS
EXISTING BLDG
PARKING AREA
C101
Office of Construction and Facilities Management
WHITERIVER HOSPITAL BACKUP
GENERATOR INSTALL
SEPT. 16, 2022
75H70122F30010
WHITE RIVER INDIAN HEALTH SERVICES
200 W HOSPITAL DR. WHITERIVER, AZ 85941
AESUS
BOILER PLANT
AREA OF WORK
AESUS
GRADING PLAN
Cut/Fill Summary Name
CUT-FILL
Totals
2d Area
613.77 Sq. Ft.
613.77 Sq. Ft.
Cut
0.00 Cu. Yd.
0.00 Cu. Yd.
Fill
10.39 Cu. Yd.
10.39 Cu. Yd.
Net
10.39 Cu. Yd.<Fill>
10.39 Cu. Yd.<Fill>
C102 A
C102 B
LEGEND
C CONCRETE
P
FL
PAVEMENT
FLOW LINE
FF FINISHED FLOOR
FOUND/SET 1/2" REBAR
CONCRETE SURFACE
TRANSFORMER
EDGE OF PAVEMENT
BLOCK/RETAINING WALL DRAINAGE FLOW DIRECTION
OUTFALL LOCATION
EXISTING ELEVATION MARKER
PROPOSED ELEVATION MARKER
RIP-RAP
GRAVEL
PAVEMENT
PAD ELEVATION: 5,478.5'
SLAB AND FOOTING DETAILS PROVIDED BY OTHERS
EXISTING BLDG
EXISTING BLDG
O2 STORAGE
CONDUIT ROUTED
ABOVE GRADE
TBM
SET 12" REBAR
ELEV: 5,485.43'
GENERAL CIVIL NOTES
1. ALL CONSTRUCTIONS SHALL CONFORM TO LATEST IHS CONSTRUCTION STANDARDS AND SPECIFICATIONS.
2. ALL QUANTITIES SHOWN ON THE PLANS ARE APPROXIMATE AND ARE FURNISHED SOLELY FOR THE
CONTRACTORS CONVENIENCE. CONTRACTOR IS RESPONSIBLE TO VERIFY QUANTITIES
3. A THOROUGH ATTEMPT HAS BEEN MADE TO SHOW THE LOCATION OF ALL UNDERGROUND UTILITIES SHOWN ON THESE PLANS. THE CONTRACTOR SHALL BE RESPONSIBLE AND SHALL NOT BE RELIEVED OF RESPONSIBILITY FOR MAKING A COMPLETE AND ACCURATE ON-SITE DETERMINATION OF LOCATIONS, MATERIAL, AND SIZE OF UTILITIES, STRUCTURES, AND FIELD CONDITIONS WHICH MAY AFFECT THE PROGRESS OF THE WORK. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGE TO STRUCTURES AND UTILITIES ENCOUNTERED DURING CONSTRUCTION AND SHALL FIELD EXPOSE EXISTING UNDERGROUND UTILITIES PRIOR TO TRENCHING IN
THEIR VICINITY.
4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR QUALITY CONTROL MEASURES SUFFICIENT TO PRODUCE
MATERIALS AND WORKMANSHIP OF ACCEPTABLE QUALITY.
5. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL COSTS OF TESTING AND INSPECTION.
6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL RE-WORK AND/OR REMOVAL AND REPLACEMENT OF
MATERIALS NEEDED BY FAILING TESTS OR SUBSTANDARD WORKMANSHIP.
7. THE CONTRACTOR SHALL IMPLEMENT BEST HOUSE-KEEPING MEASURES AND EROSION AND SEDIMENT CONTROL MEASURES TO PREVENT THE TRANSPORT OF CONSTRUCTION MATERIALS INTO DRAINAGE INLETS, MANHOLES, UTILITY STRUCTURES, OR ONTO ADJACENT STREETS AND PROPERTIES.
8. APPROVAL OF A PORTION OF THE WORK IN PROGRESS DOES NOT GUARANTEE ITS FINAL ACCEPTANCE. TESTING AND EVALUATION MAY CONTINUE UNTIL WRITTEN FINAL ACCEPTANCE OF A COMPLETE AND WORKABLE UNIT.
9. BACKFILL COMPACTION SHALL BE TYPE 1 UNLESS OTHERWISE NOTED AND MEET MIN. 95% COMPACTION.
10. AGGREGATE BASE COURSE SHALL NOT BE PLACED ON SUBGRADE UNTIL SUBGRADE REQUIREMENTS HAVE BEEN
ACHIEVED.
11. ALL ASPHALT CONCRETE PAVEMENT SHALL BE PER APPLICABLE MAG STANDARDS OR AS AMENDED BY THE GOVERNING AGENCY. ASPHALT CONCRETE MIX DESIGN SHALL BE SUBMITTED TO THE PUBLIC WORKS DIRECTOR
OR EQUIVALENT OR HIS DESIGNEE FOR APPROVAL PRIOR TO START OF CONSTRUCTION.
12. ALL UTILITY FRAMES, COVERS, VALVE BOXES, MANHOLES, ETC. SHALL BE ADJUSTED TO FINISH ASPHALT GRADE
AFTER PLACEMENT OF SURFACE COURSE BY THE CONTRACTOR PER COP STANDARD DETAILS.
13. ALL CONCRETE TO BE AT LEASE 3000 PSI CLASS A PORTLAND CEMENT CONCRETE UNLESS OTHERWISE NOTED.
14. ALL EXPANSION JOINTS TO BE SEALED WITH A 12" EXPANSION JOINT, PRE-FORMED JOINT FILLER AND SEALER IN
ACCORDANCE WITH MAG SECTION 729.
15. NO JOB WILL BE CONSIDERED COMPLETE UNTIL ALL CURBS, PAVEMENT, AND SIDEWALKS HAVE BEEN SWEPT
CLEAN OF ALL DIRT AND DEBRIS.
T
GENERAL CIVIL DEMO NOTES
1. THE CONTRACTOR SHALL INCLUDE IN THE BID THE COST OF REMOVING ANY EXISTING SITE FEATURES
AND APPURTENANCES NECESSARY TO ACCOMPLISH THE CONSTRUCTION OF THE PROPOSED SITE
IMPROVEMENTS. THE CONTRACTOR SHALL ALSO INCLUDE IN THE BID THE COST NECESSARY TO
RESTORE SUCH ITEMS IF THEY ARE SCHEDULED TO REMAIN AS PART OF THE FINAL SITE
IMPROVEMENTS. REFER TO PLANS TO DETERMINE EXCAVATION, DEMOLITION AND TO DETERMINE
THE LOCATION OF THE PROPOSED SITE IMPROVEMENTS.
2. UNLESS SPECIFICALLY NOTED TO BE SAVED / STOCKPILED (R&S) OR REUSED / RELOCATED (R&R), ALL
SITE FEATURES CALLED FOR REMOVAL (REM) SHALL BE REMOVED WITH THEIR FOOTINGS,
ATTACHMENTS, BASE MATERIAL, ETC, TRANSPORTED FROM THE SITE TO BE DISPOSED OF IN A
LAWFUL MANNER AT AN ACCEPTABLE DISPOSAL SITE AND AT NO COST TO THE OWNER.
3. ALL EXISTING SITE FEATURES TO REMAIN SHALL BE PROTECTED THROUGHOUT THE CONSTRUCTION
PERIOD. ANY FEATURES DAMAGED DURING CONSTRUCTION OPERATIONS SHALL BE REPAIRED OR
REPLACED TO THE SATISFACTION OF THE OWNER'S REPRESENTATIVE AT NO ADDITIONAL COST.
4. DURING EARTHWORK OPERATIONS, CONTRACTOR SHALL TAKE CARE TO NOT DISTURB EXISTING MATERIALS TO REMAIN, OUTSIDE THE LIMITS OF EXCAVATION AND BACKFILL AND SHALL TAKE WHATEVER MEASURES NECESSARY, AT THE CONTRACTOR'S EXPENSE, TO PREVENT ANY EXCAVATED MATERIAL FROM COLLAPSING. ALL BACKFILL MATERIALS SHALL BE PLACED AND COMPACTED AS
SPECIFIED TO THE SUBGRADE REQUIRED FOR THE INSTALLATION OF THE REMAINDER OF THE
CONTRACT WORK.
5. IT SHALL BE THE CONTRACTOR'S OPTION, WITH CONCURRENCE OF THE OWNER, TO REUSE EXISTING
GRAVEL IF IT MEETS THE REQUIREMENTS OF THE SPECIFICATIONS FOR GRAVEL BORROW.
6. ALL ITEMS CALLED FOR REMOVAL SHALL BE REMOVED TO FULL DEPTH INCLUDING ALL FOOTINGS, FOUNDATIONS, AND OTHER APPURTENANCES, EXCEPT AS SPECIFICALLY NOTED OTHERWISE.
7. 'CLEAR AND GRUB VEGETATION' SHALL INCLUDE REMOVAL OF GRASS, SHRUBS, AND UNDERBRUSH, REMOVAL OF ROOTS, ROUGH GRADING, INSTALLATION OF LOAM (IF APPLICABLE), FINE GRADING, SEEDING AND TURF ESTABLISHMENT BY THE CONTRACTOR.
8. THE STORAGE OF MATERIALS AND EQUIPMENT WILL BE PERMITTED AT LOCATIONS DESIGNATED BY OWNER OR OWNER'S REPRESENTATIVE. PROTECTION OF STORED MATERIALS AND EQUIPMENT SHALL
BE THE SOLE RESPONSIBILITY OF THE CONTRACTOR.
21'
21' 5'
19'-8"
6'
6'
28'
13'
3-31-2024
10-27 -20
Date
NOV. 03, 2022
FINAL SUBMITTAL - 100%
CONSTRUCTION DOCUMENTS
NOV 17, 2022
0+00 0+10 0+20 0+30 0+40 0+50 0+60 0+70 0+80 0+90 1+00 1+10 1+201+25
0+00 0+10 0+20 0+30 0+40 0+50 0+60 0+70 0+80 0+90 1+00 1+10 1+19
1050 E. Southern Ave, Suite #D, Tempe, Arizona 85282, (480) 751-9542designgroup
Architecture, Engineering, and Sustainable DesignAESUS
KEY
PLAN
NTS
Drawing Title:
Project Title:
Date
Location
Checked
Building Number:
Project Number:
Drawing Number:
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Location:
C102
NORTH
Office of Construction and Facilities Management
WHITERIVER HOSPITAL BACKUP
GENERATOR INSTALL
SEPT. 16, 2022
75H70122F30010
WHITE RIVER INDIAN HEALTH SERVICES
200 W HOSPITAL DR. WHITERIVER, AZ 85941
AESUS
BOILER PLANT
AREA OF WORK
AESUS
DETAILS
A SECTION A
1-1/2" = 1'-0"B SECTION B
1-1/2" = 1'-0"
FILTER FABRIC
18" DEEP D50: 6" RIP RAP
2:1 MAXFILTER FABRIC
MIN. 1' BEYOND
RIP-RAP
DEPTH: D50*3
RIP-RAP D50 FOR EROSION PROTECTION
D50=V2/(2*g*C2*(S-1))
D50 - AVERAGE DIAMETER OF 50% OF THE SPHERICAL ROCKS FOR THE RIP RAP IN FEET;
V - AVERAGE CHANNEL VELOCITY IN FEET PER SECOND;
G - ACCELERATION DUE TO GRAVITY, 32.17 FT/S²;
C - ISBASH CONSTANT WITH VALUES EQUAL TO 0.86 FOR HIGHLY TURBULENT FLOW OF WATER OR 1.20 FOR LOW
TURBULENCE WATER FLOW; AND
S - SPECIFIC GRAVITY OF THE ROCK WITH VALUES RANGING FROM AROUND 2.50 TO 3.00
D50=1.512/(2*32.17*0.862*(2.5-1)) = 0.3833 FT
COMPACTED PAD
C RIP-RAP EROSION PROTECTION DETAILS
NTS
EROSION PROTECTION
SHEET C102, DETAIL C
EROSION PROTECTION
SHEET C102, DETAIL C
PAD ELEV: 5478.25'
*SEE STRUCTURAL AND
ARCHITECTURAL DRAWINGS
SLAB AND FOOTING DETAILS
PAD ELEV: 5478.25'
*SEE STRUCTURAL AND
ARCHITECTURAL DRAWINGS
SLAB AND FOOTING DETAILS
EROSION PROTECTION
SHEET C102, DETAIL C
6' RIBBON SLAB 5' RIBBON SLAB
6' RIBBON SLAB
6' RIBBON SLAB
3-31-2024
10-27 -20
Date
NOV. 03, 2022
FINAL SUBMITTAL - 100%
NOV 17, 2022
T
EQUIPMENT
C
O V
E R
C O
V E
R
1'-0"
12"
MIN
12"
MIN
EQUIPMENT
ANCHOR BOLTS
PROVIDED AND,
INSTALLED BY GC
#6 @ 12" O.C. EA. WAY
TOP AND BOTTOM
FILTER FABRIC
GRANULAR BASE
6" SLAB W/ CONT. 6X6 WIRE MESH,
TYP. ALIGN W/ ADJ. SLAB
#4 SMOOTH DOWELS @
12" O.C. ALL AROUND
4" 4"
MIN MIN
GRADE
PAINT TO MATCH EXISTING
FACILITY STANDARD
FILL WITH GROUT
AND CROWN TOP 1"
6" DIA. STEEL POST,
SCHEDULE 40,
GALVANIZED FILLED WITH
CONCRETE
6'-0"SEE FLOOR PLAN SEE FLOOR PLAN SEE FLOOR PLAN
PROVIDE DEADMAN
ANCHORS PER MFR.
AND SPECIFICATION.
CHAIN LINK FENCING
WITH PRIVACY SLATS.
PROVIDE LOCKING HARDWARE AND
ASSOCIATED COMPONENTS,
TYPICAL.
PROVIDE DEADMAN
ANCHORS PER MFR.
AND SPECIFICATION.
CHAIN LINK FENCING
WITH PRIVACY SLATS,
MATCH EXISTING.
ELEVATION A ELEVATION B
DBL. CHAINLINK MANGATE
1. THE ARCHITECTURAL DRAWINGS SHOW PRINCIPAL AREAS AND
LIMITS OF CONSTRUCTION WHERE WORK MUST BE
ACCOMPLISHED UNDER THIS CONTRACT. WORK MUST BE
ACCOMPLISHED IN AREAS NOT SHOWN ON ARCHITECTURAL
DRAWINGS DUE TO CHANGES AFFECTING ELECTRICAL,
MECHANICAL, PLUMBING AND TECHNOLOGY ALONG WITH
OTHER SYSTEMS. THIS WORK SHALL BE PART OF THIS
CONTRACT, AND ALL TRADES SHALL INSPECT THESE AREAS,
ASCERTAIN WORK REQUIRED AND DO THE WORK IN
ACCORDANCE OF CONTRACT REQUIREMENTS AT NO
ADDITIONAL COST. SEE MECHANICAL, ELECTRICAL, PLUMBING
AND TECHNOLOGY PLANS FOR ADDITIONAL WORK.
2. CONTRACTORS SHALL VISIT THE SITE DURING BIDDING TO
BECOME FAMILIAR WITH THE EXISTING CONDITIONS. THE
GENERAL CONTRACTOR SHALL LOCATE, INSPECT AND FIELD
VERIFYALL EXISTING CONDITIONS, DIMENSIONS AND
ELEVATIONS PRIOR TO DEMOLITION AND CONSTRUCTION.
NOTIFY ARCHITECT IMMEDIATELY OF ANY DISCREPANCIES
3. DO NOT SCALE DRAWINGS. NOTIFY ARCHITECT IMMEDIATELY
OF ANY DISCREPANCIES.
4. WHEREVER OPENINGS ARE CUT THROUGH FIRE RATED
PARTITIONS, IT SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR FOR WHOM THE HOLE
IS CUT TO PATCH AND REPAIR ANY OPENING TO MAINTAIN THE
INTEGRITY OF THE FIRE RATING.
5. GENERAL CONTRACTOR TO CHECK MECHANICAL DRAWINGS
FOR EXISTING PIPES AND DUCTSFURRED IN WALLS. VERIFY
SIZE AND LOCATION WITH MECHANICAL CONTRACTOR PRIOR
TO PROCEEDING WITH REMODELING.
6. FIREPROOFING SHALL BE UNPIERCED. ANY SUBCONTRACTOR
PENETRATING THE FIREPROOFING SHALL BE REQUIRED TO
REPLACE FIREPROOFING TO THE ORIGINAL CONDITION AND
FIRE RATING, AT THE SUBCONTRACTORS EXPENSE.
7. EQUIPMENT UNIT DIMENSIONS ARE FOR PRODUCT
DESCRIPTION ONLY, VERIFY SIZE WITH MANUFACTURER.
8. ALL DIMENSIONS PERTAINING TO MECHANICAL OR ELECTRICAL
SERVICES OR EQUIPMENT SHALL BE VERIFIED WITH THE
RESPECTIVE TRADE.
9. ALL CONTRACTORS THAT PENETRATE AND/OR DISTURB ANY
AREAS AT EXISTING CONDITIONS SHALL PATCH AREA TO
MATCH EXISTING ADJACENT AREA OR SURFACE AND PREPARE
FOR SCHEDULED FINISH APPLICATION. COORDINATE WORK
WITH GENERAL CONTRACTOR PRIOR TO PROCEEDING.
10. VERIFY HEIGHTS AND LOCATIONS OF ACCESS PANELS (AP)
AND COORDINATE TYPES WITH TRADES WHICH REQUIRE
THEM.
11. PROVIDE LINTELS AND FRAMING FOR GRILLES, LOUVERS, AND
ROOF VENTS AS REQUIRED BY MECHANICAL CONTRACTOR,
VERIFY SIZE AND LOCATION.
12. STRUCTURAL, MECHANICAL, AND ELECTRICAL ABBREVIATIONS
AND SYMBOLS MAY DIFFER FROM ARCHITECTURAL. SEE
RESPECTIVE SECTIONS AND/OR DRAWINGS FOR DEFINITIONS.
13. CONTRACTOR SHALL EVALUATE INTEGRITY OF ALL PARTITIONS
WITHIN THE PROJECT SCOPE AND UPGRADE AS REQUIRED.
ALL FIRE RESISTIVE RATED WALLS SHALL BE CONSTRUCTED
OF MATERIALS / ASSEMBLIES MEETING THE EXISTING RATING
RATING, TERMINATE AT THE DECK ABOVE WITH A TESTED
HEAD OF WALL ASSEMBLY AND ALL PENETRATIONS SHALL BE
SEALED WITH A TESTED ASSEMBLY. ALL SMOKE PARTITIONS
SHALL BE CONSTRUCTED OF MATERIALS THAT RESIST THE
PASSAGE OF SMOKE, TERMINATE AT THE DECK ABOVE WITH A
JOINT SEALED WITH FIRE CAULK AND ALL PENETRATIONS
SHALL BE SEALED WITH FIRE CAULK.
GENERAL NOTES
14 15 16 17 18
A
B
C
+/- 13' - 7"
AE-100
28' - 0"
AE-1003
AE-100
3A
3B
3BAE-100 3
AE-100
33B
6' - 0"
6' - 0"
EXISTING UNDERGROUND
WATER STORAGE TANKS.
EXISTING O2 STORAGE
EXISTING STAIRSEXISTING
TRANSFORMER
25' - 8"
1050 E. Southern Ave, Suite #D, Tempe, Arizona 85282, (480) 751-9542designgroup
Architecture, Engineering, and Sustainable Design
AESUS
KEY PLAN NTS NORTH
Drawing Title: Project Title:
Date
Location
Checked
Building Number:
Project Number:
Drawing Number:
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
WHITERIVER HOSPITAL BACKUP
GENERATOR INSTALL
Location:
100% Submittal - Not for Construction
NOV. 03, 2022
PH22WR03H8
WHITE RIVER INDIAN HEALTH SERVICE
200 W HOSPITAL DR. WHITERIVER, AZ 85941
AESUS
BOILER PLANT
AREA OF WORK
AESUS
AE-100
LEVEL 01 FLOOR PLAN
1/8" = 1'-0"1
LEVEL 01 - FLOOR PLAN
KEYNOTES
1 PROPOSED GENERATOR LOCATION, SEE ELECTRICAL.
2 EXISTING BOILER ROOM TO REMAIN.
4 EXISTING RETAINING WALL TO REMAIN.
5 NEW CONCRETE EQUIPMENT PAD. VERIFY EXACT SIZE WITH MANUFACTURER AND
FINAL GENERATOR SUBMITTAL. SEE DETAIL 2 ON SHEET AE-100.
6 PROVIDE A 6'0" WIDE DOUBLE SWING GATE.
7 PROVIDE A 6" CONCRETE RIBBON SLAB WITH CONTINUOUS WELDED WIRE MESH.
8 PROVIDE A 8'-0" HIGH CHAIN LINK FENCE ENCLOSURE. INSTALL GENERATOR PRIOR
TO CONSCTRUCTION OF FENCE.
9 6" STEEL BOLLARD, TYPICAL. SEE DETAIL 4/AE-100.
3/4" = 1'-0"2
TYPICAL EQUIPMENT PAD
3/4" = 1'-0"4
STEEL BOLLARD
3/8" = 1'-0"3
CHAINLINK FENCE DETAIL
Project Number:
75H70122F30010
SEPT. 16, 2022NOV. 03, 2022NOV 17, 2022
FINAL SUBMITTAL - 100%
CONSTRUCTION DOCUMENTS
David Combs Snapshot s
CR
(18"/18")
M
VFD
JJJ
J
M M
M
K1
K1
TYPICAL OUTLET SYMBOL NOTES
-STAR SYMBOL INDICATES DEVICE IS MOUNTED 4" ABOVE COUNTER,
CASEWORK, BACKSPLASH OR 46" IF NOTHING BELOW.
-INDICATES MOUNTING HEIGHT ABOVE FINISHED FLOOR.
-ISOLATED GROUND
-WEATHER PROOF
-EXPLOSION PROOF
"+84"
"IG"
"WP"
"XP"
20A, 125V, 2 POLE, 3 WIRE GROUNDING DUPLEX RECEPTACLE
20A, 125V, 2 POLE, 3 WIRE GROUNDING DOUBLE DUPLEX RECEPTACLE
20A, 125V, 2 POLE 3 WIRE GROUNDING DUPLEX RECEPTACLE WITH (2) INTEGRAL
USB CHARGING PORTS
HALF SWITCHED RECEPTACLE - LOWER OUTLET SWITCHED VIA CONTROL ZONE
INDICATED OR NEAREST OCCUPANCY SENSOR. UPPER OUTLET IS UNSWITCHED -
ALWAYS HOT
20A, 125V, 2 POLE, 3 WIRE GROUNDING GFCI DUPLEX RECEPTACLE
20A, 125V, 2 POLE, 3 WIRE GROUNDING GFCI RECEPTACLE WITH WHILE IN USE
WEATHERPROOF ENCLOSURE.
SPECIAL OUTLET. REFER TO SCHEDULE FOR REQUIREMENTS.
CEILING MOUNTED RECEPTACLE, TYPE AS INDICATED ABOVE.
PEDESTAL MOUNTED DUPLEX OR DOUBLE DUPLEX CONVENIENCE RECEPTACLE.
FLOOR BOX - WITH DUPLEX OR DOUBLE DUPLEX RECEPTACLE
FLOOR BOX WITH POWER AND DATA FURNITURE FEED CONNECTIONS. FURNITURE
FEED CIRCUIT QUANTITY AS INDICATED ON PLANS.
ELECTRICAL POWER SWITCH
M - MOTOR RATED WITH INTEGRAL THERMAL OVERLOADS U.O.N.
SURFACE MOUNTED ENCLOSED DIVIDED RACEWAY FOR POWER AND DATA.
DUPLEX SPACING (20A, 125V, 2 POLE, 3 WIRE GROUNDING DUPLEX RECEPTACLE
U.O.N)
DATA OUTLET SPACING (PROVISINS FOR NOT LESS THAN 4 PORTS U.O.N)
POWER / TELECOM. POLE. PROVIDE JUNCTION BOX ABOVE CEILING FOR POWER
CONNECTION (CIRCUIT QUANTITY AS NOTED ON PLANS) FOR FOR TELECOM/DATA
CONNECTIONS (1 PER ASSOCATED WORKSTATION) CONNECT TO WIRING IN
POWER POLE.
EXTENSION CORD REEL.
UNISTRUT RACK
TYPICAL OUTLET SYMBOL CIRCUITING NOTES
NOTES:
1. OUTLETS LOCATED AT COUNTERS SHALL BE LOCATED 18" AFF IN KNEE SPACE IF
PROVIDED OR 4" ABOVE COUNTER OR BACK SPLASH AS APPLICABLE IF NO KNEE
SPACE IS PROVIDED UNLESS NOTED OTHERWISE.
POWER OUTLETS
IG
+30"
CIRCUIT NUMBER
ELEVATION AFF
TYPE2
D
D
M
XXX-XXX
FOOT ON DEVICE INDICATES WALL MOUNTED
MARK NUMBER FOR MECHANICAL EQUIPMENT
KEY NOTE REFERENCE SYMBOL.
XXX-XXX
GENERAL
CIRCUIT NUMBER(S)
PANEL NAME
1LN1-1,3,5
BRANCH CIRCUIT HOMERUN. PROVIDE #12 PHASE, #12
NEUTRAL AND #12 GROUND CONDUCTORS FOR EACH
INDICATED CIRCUIT UNLESS NOTED OTHERWISE. SEE
GENERAL NOTE #2 AND #3.
NO MULTI-WIRE BRANCH CIRCUITS PERMITTED. NO SHARED
NEUTRAL.
CONDUIT RUN CONCEALED IN CEILING OR WALL
CONDUIT RUN BELOW GRADE, UNDER OR CONCEALED IN
FLOOR SLAB, UNDER RAISED FLOOR
CONDUIT RISER UP
CONDUIT RISER DOWN
INDICATES CIRCUIT CONTINUATION
STUB INTO ACCESSIBLE CORRIDOR CEILING SPACE UNLESS
OTHERWISE NOTED
CAP END OF CONDUIT
CONDUIT SLEEVE
POWER CONDUIT FILL EXAMPLE
(2) 4"C, 4 #500, 1#1/0G
TOTAL QUANTITY OF IDENTICAL CONDUIT/WIRE RUNS AS SPECIFIED (AS APPLICABLE)
CONDUIT SIZE (SEE SPECIFICATIONS FOR ALLOWED TYPES)
QUANTITY OF PHASE AND NEUTRAL CONDUCTORS.
NEUTRAL CONDUCTOR MAY BE SPECIFIED SEPARATELY WITH 'N' SUFFIX
CONDUCTOR SIZE (AWG/KCMIL)
QUANTITY OF GROUND CONDUCTORS (ASSUME QTY 1 IF NOT INDICATED)
GROUND CONDUCTOR SIZE (AWG/KCMIL)
CIRCUIT DESIGNATIONS
(R)(R)
NOTES:
THE FOLLOWING SYMBOLS ARE EXAMPLES INTENDED TO SHOW METHODOLOGY FOR
DEMOLITION. THIS APPROACH IS APPLICABLE TO ALL SYMBOLS INDICATED ON THIS SHEET.
NEW - SHOWN HERE FOR REFERENCE AS A COMPARISON AGAINST
EXISTING AND DEMO ITEMS
EXISTING ELECTRICAL ITEM TO BE REMOVED (BOLD AND DASHED)
EXISTING ELECTRICAL ITEM TO BE RELOCATED. HALFTONE
(R) INDICATES NEW LOCATION
EXISTING ELECTRICAL ITEM TO REMAIN. HALFTONE.
DEMOLITION AND REMODEL
LIGHTING FIXTURE DESCRIPTIONS
RECESSED OR SURFACE MOUNTED LUMINAIRE
RECESSED OR SURFACE MOUNTED ROUND DOWNLIGHT LUMINAIRE
STRIP LIGHT, SURFACE MOUNTED (LENGTH AS SHOWN ON PLANS)
LINEAR LUMINAIRE, SURFACE OR RECESSED (SOLID) OR PENDANT (DASHED)
MOUNTED (LENGTH/TYPE AS SHOWN ON PLANS)
LINEAR LUMINAIRE, WALL MOUNTED (LENGTH AS SHOWN ON PLANS)
WALL SCONCE LUMINAIRE
SUSPENDED TRACK LIGHT, TRACK HEAD QUANTITY AS SHOWN ON PLANS
COVE LIGHT. PLACE IN ARCHITECTURAL COVE, COORDINATE EXACT
LOCATIONS WITH ARCHITECTURAL DRAWINGS.
DENOTES DIRECTION OF LIGHT DISTRIBUTION. PROVIDE DIRECTIONAL LIGHT
THROW (WALL WASH EFFECT) WHERE SHOWN.
EXIT SIGN CEILING OR WALL MOUNTED AS INDICATED
INDICATES DIRECTIONAL CHEVRON FOR EXIT SIGNS.
DENOTES LOCATION(S) OF ILLUMINATED EXIT FACE
EMERGENCY TWIN HEAD FLOOD LIGHTING 'BUG EYE' UNIT WITH INTEGRAL
BATTERY PACK
T
30A/3P
30A/3P/
20AF
30A/3P
12x3
CP
C
480/277V OR 480V PANEL 208/120V OR 120/240V PANEL
HEAVY DUTY DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
ENCLOSED CIRCUIT BREAKER
MANUAL MOTOR STARTER SWITCH WITH THERMAL OVERLOAD
PROTECTION.
CONTACTOR
VARIABLE FREQUENCY DRIVE
MOTOR - WITH DISCONNECT (WHERE SHOWN IN PLANS)
MOTOR DESIGNATION SHOWN IN BOX
CONTROL PANEL FURNISHED BY OTHERS, INSTALLED BY
DIVISION 26, UNLESS NOTED OTHERWISE
REDUCED VOLTAGE MOTOR STARTER
NUMBER REFERS TO NEMA STARTER SIZE
COMBINATION REDUCED VOLTAGE MOTOR STARTER/DISCONNECT
NUMBER REFERS TO NEMA STARTER SIZE
COMBINATION 2 SPEED MOTOR STARTER/DISCONNECT
MOTOR - WITH DISCONNECT (FUSED WHERE SHOWN IN PLANS)
MOTOR DESIGNATION SHOWN IN BOX
CONTROL PANEL FURNISHED BY OTHERS, PROVIDED AND INSTALLED
BY DIVISION 26, UNLESS NOTED OTHERWISE
PUSHBUTTON STATIONS. ONE, TWO, OR THREE AS INDICATED
EMERGENCY POWER OFF' BREAK GLASS STATION.
BUS DUCT, FEEDER OR PLUG-IN TYPE AS INDICATED
CABLE TRAY - WIDTH x HEIGHT AS INDICATED, OR KEY NOTED
UNDER FLOOR DUCT SYSTEM
JUNCTION BOX, ABOVE CEILING (NO FOOT) OR FLUSH WALL MOUNTED
(WITH FOOT)
T = JUNCTION BOX FOR VOICE/DATA
JUNCTION BOX WITH FLEXIBLE CONNECTION TO EQUIPMENT
INDICATED AND REQUIRED
LADDER STYLE CABLE TRAY
CONDUIT - SEE SPECIFICATIONS ON E002 FOR TYPE
POWER DISTRIBUTION
30A/3P
30A/3P
30A/3P
TABS INDICATE FLUSH MOUNTED PANEL
INDICATES REQUIRED
CLEARANCE
TYPICAL OUTLET SYMBOL NOTES
"*" -MOUNTED +4" ABOVE COUNTER, CASEWORK, BACKSPLASH OR 46" IF NOTHING
BELOW. COORDINATE WITH ARCHITECTURAL DETAILS AND CASEWORK CONTRACTOR.
-INDICATES MOUNTING HEIGHT TO CENTER OF OUTLET BOX ABOVE FINISHED FLOOR."+84"
NOTES:
1. OUTLETS LOCATED AT COUNTERS SHALL BE LOCATED 18" AFF IN KNEE SPACE IF
PROVIDED OR 4" ABOVE COUNTER OR BACK SPLASH AS APPLICABLE IF NO KNEE
SPACE IS PROVIDED U.O.N.
TELECOM. WIRED INFRASTRUCTURE
VOICE/DATA COMBINATION OUTLET. PROVIDE 1-1/4" CONCEALED CONDUIT TO 6"
ABOVE ACCESSIBLE CEILING ACCESSIBLE WITH 90 DEG BEND TOWARDS NEAREST
IT CLOSET OR CABLE TRAY, UNO.
DATA OUTLET. PROVIDE 1-1/4" CONCEALED CONDUIT TO 6" ABOVE ACCESSIBLE
CEILING ACCESSIBLE WITH 90 DEG BEND TOWARDS NEAREST IT CLOSET OR
CABLE TRAY, UNO.
VOICE OUTLET. PROVIDE 3/4" CONCEALED CONDUIT TO 6" ABOVE ACCESSIBLE
CEILING ACCESSIBLE WITH 90 DEG BEND TOWARDS NEAREST IT CLOSET OR
CABLE TRAY, UNO.
CEILING MOUNTED COMMUNICATIONS OUTLET, VOICE, DATA OR COMBO UNIT.
PEDESTAL/BENCH MOUNTED COMMUNICATIONS OUTLET. VOICE, DATA OR COMBO
AS INDICATED.
OUTLET MOUNTED IN CAST BOX INSTALLED UNDER RAISED FLOOR.
FLOOR OUTLET. PATHWAY PROVIDE BY ELECTRICAL CONTRACTOR. REFER TO
ELECTRICAL DRAWINGS AND SCHEDULE FOR REQUIREMENTS.
TELEVISION ANTENNA TAP-OFF OUTLET AT +84", PROVIDE 1"C TO ABOVE
ACCESSIBLE CEILING.
TELEPHONE MOUNTING BOARD. 3/4" THICK FIRE-TREATED PLYWOOD (8FT HIGH)
FOR TELEPHONE MOUNTING BOARD WITH (1) DEDICATED FOURPLEX OUTLET AND
#6 COPPER BOND TO BUILDING GROUND ELECTRODE SYSTEM. TELEPHONE
CONDUIT PER UTILITY SPECIFICATIONS. PROVIDE 2"C (OR AS SPECIFIED BY
OWNER) BACK TO BUILDING'S TELECOM POINT OF CONNECTION FOR USE BY
TELECOM INSTALLER. FIELD VERIFY TELECOM POINT OF CONNECTION LOCATION
PRIOR TO STARTING CONSTRUCTION.
NOTE:
SYMBOLS SHOWN ARE FOR REFERENCE ONLY AND DO NOT CONSTITUTE A CHECK
LIST OF DEVICES REQUIRED BY THE CONTRACT
0.0"
18"
6'-0"
3'-10"
10'-0"
6'-8"
BATTERY LIGHTING UNITS AND REMOTE WALL MOUNTED LIGHT HEADS (OR
1'-0" BELOW FINISHED CEILING AT TOP OF UNIT)
WARNING AND SIGNALING FIXTURES/SIGNS (CENTERED 6IN. ABOVE
DOOR/WINDOW)
CLOCK RECEPTACLES
BOTTOM LENS FOR WALL MOUNTED FIRE ALARM STROBES SPEAKERS,
HORNS AND COMBINATION HORN/STROBES
TOP OF FLUSH AND SURFACE MOUNTED PANELBOARDS AND TELEPHONE
CABINETS. TOP OF HIGHEST DISCONNECT SWITCHES, MAGNETIC
STARTERS, CONTACTORS, ATS.
GENERATOR REMOTE ANNUNCIATOR
WALL MOUNTED LIGHTING SWITCHES, MANUAL MOTOR STARTERS, FIRE
ALARM PULL STATIONS, WALL MOUNTED TELEPHONES.
GARAGE RECEPTACLES
ELECTRICAL RECEPTACLES, VOICE/DATA OUTLETS, DATA OUTLETS, UNO
FINISHED FLOOR
7'-0"
5'-6"
24"
MOUNTING HEIGHT NOTES: MOUNTING HEIGHTS TO FINISHED FLOOR TO CENTER OF
OUTLETS, UNLESS OTHERWISE NOTED.
MOUNTING HEIGHT NOTES
GENERAL NOTES
1. ALL DEVICE MOUNTING HEIGHTS INDICATED ON THIS LEGEND ARE FROM FINISHED FLOOR
TO CENTER OF OUTLET BOX.
2. PROVIDE #10 WIRE (FOR PHASE, NEUTRAL AND GROUND) FOR ALL 20A 120V CIRCUITS
EXCEEDING 75 FEET AND FOR 20A 277V CIRCUITS THAT EXCEED 150 FEET. PROVIDE #8
WIRE (FOR PHASE, NEUTRAL AND GROUND) FOR ALL 20A 120V CIRCUITS EXCEEDING 150
FEET AND FOR ALL 20A 277V CIRCUITS EXCEEDING 250 FEET.
3. CONTRACTOR MAY COMBINE UP TO (3) 20A (SINGLE POLE) RECEPTACLE CIRCUITS WITHIN
A SINGLE CONDUIT. CONDUIT SHALL NOT BE LESS THAN 3/4". WIRING CONFIGURATIONS
SHALL BE AS FOLLOWS: (FOLLOW WIRE UPSIZING TO ACCOMMODATE VOLTAGE DROP DUE
TO LENGTH AS INDICATED IN NOTE #2.)
• FOR 3 CIRCUITS, 20A, HOMERUNS TO PANELS SHALL BE 3#12 PHASE CONDUCTORS, 3#
12 NEUTRAL CONDUCTORS AND 1#12 GROUND. (WHEN UPSIZING FOR VOLTAGE DROP
AS INDICATED IN NOTE #2 REQUIRES 3#8 PHASE CONDUCTORS, 3#8 NEUTRAL
CONDUCTORS AND 1#8 GROUND UTILIZE 1"C IN LIEU OF 3/4"C).
• FOR 2 CIRCUITS, 20A, HOMERUNS TO PANELS SHALL BE 2#12 PHASE CONDUCTORS, 2#
12 NEUTRAL CONDUCTORS, AND 1 #12 GROUND.
• 1 CIRCUIT, 20A, HOMERUNS TO PANEL SHALL BE 1#12 PHASE CONDUCTOR, 1#12
NEUTRAL CONDUCTOR AND 1#12 GROUND.
4. VERIFY LOCATION AND CONNECTION REQUIREMENTS FOR EQUIPMENT PROVIDED BY
OTHER TRADES PRIOR TO ROUGH-IN.
5. COORDINATE CEILING MOUNTED LIGHTS AND DEVICES WITH CEILING CONTRACTOR AND
INSTALL AS SHOWN ON THE REFLECTED CEILING/LIGHTING PLANS.
6. ALL FLOOR MOUNTED ELECTRICAL EQUIPMENT (SWITCHGEAR, SWITCHBOARDS, FREE
STANDING PANELBOARDS, DISTRIBUTION BOARDS, TRANSFORMERS, ETC.) SHALL BE
INSTALLED ON 4" HIGH CONCRETE PAD. CONCRETE PAD SHALL EXTEND PAST EDGE OF
EQUIPMENT 3" ON EACH SIDE U.N.O.
7. COORDINATE ALL DIMENSIONS, ELECTRICAL POINT OF CONNECTIONS, AND WIRING
REQUIREMENTS ON ALL PRE-PURCHASED EQUIPMENT WITH FINAL APPROVED SHOP
DRAWINGS.
8. FIRE SEAL ALL CONDUIT PENETRATIONS THROUGH FIRE RATED WALLS AND SLABS. FIRE
RATING SEAL SHALL BE EQUAL TO OR GREATER THAN THE FIRE RATING OF THE WALL OR
SLAB THROUGH WHICH THE CONDUIT PASSES.
9. COORDINATE THE LOCATION AND MOUNTING HEIGHTS OF OUTLETS AND MULTI-OUTLET
ASSEMBLIES WITH ARCHITECTURAL FLOOR PLANS AND ELEVATION DRAWINGS..
10. CONTRACTOR SHALL VERIFY ALL DOOR SWINGS BEFORE INSTALLING SWITCH/LIGHTING
CONTROL BOXES. DO NOT PLACE SWITCH OR LIGHTING CONTROL DEVICE BEHIND DOOR
SWING.
11. FOR MOUNTING HEIGHT OF UNDER-SHELF/CABINET LIGHTING FIXTURES REFER TO
ARCHITECTURAL DRAWINGS.
12. COORDINATE EXACT LOCATION OF SUSPENDED LIGHTING FIXTURES IN MECHANICAL AND
STORAGE AREAS WITH OTHER TRADES. DO NOT PLACE LIGHTING FIXTURE DIRECTION
ABOVE MECHANICAL EQUIPMENT OR DUCTS.
13. RACEWAYS, SLEEVES, AND BOXES FOR IT CABLING SHALL COMPLY WITH COMMERCIAL
BUILDING STANDARD FOR TELECOMMUNICATION PATHWAYS AND SPACES,
ANSI/TIA/EIA-569-A.
14. BOND FLAMMABLE LIQUID STORAGE CABINETS WITH #10 AWG WIRE TO THE NEAREST
STEEL COLUMN. INSTALL WIRE IN CONDUIT.
SITE EXTERIOR
SITE LIGHTING FIXTURE DESCRIPTIONS
POLE LUMINAIRE - ARM QUANTITY AS INDICATED ON PLANS
POLE MOUNTED POST TOP LUMINAIRE
GROUND MOUNTED LOW LEVEL LUMINAIRE - BOLLARD
IN-GRADE UP-LIGHT LUMINAIRE
DENOTES DIRECTION OF LIGHT DISTRIBUTION. PROVIDE DIRECTIONAL LIGHT
THROW (WALL WASH EFFECT) WHERE SHOWN.
GROUND MOUNTED FLOOD LUMINAIRE, TWIN OR SINGLE AS INDICATED ON PLANS
POLE MOUNTED FLOOD LUMINAIRE, TWIN OR SINGLE AS INDICATED ON PLANS
HHMH
UNDERGROUND CONDUIT AND WIRING
EXOTHERMIC COMPRESSION CONNECTION
GROUND ROD AND SYSTEM TEST WELL
GROUND ROD CONNECTION
ELECTRICAL MANHOLE OR HANDHOLE
MH=MANHOLE, HH=HANDHOLE
SITE POWER AND TELECOMMUNICATIONS
AIR TERMINAL P = PARAPET MOUNTED, S = SCREEN WALL MOUNTED
THRU ROOF DOWN CONDUCTOR TO GROUNDING SYSTEM
MAIN CONDUCTOR BONDING CONNECTION
SECONDARY CONDUCTOR GROUND CONNECTION
COPPER GROUND ROD 3/4"DIA. X 10'-0" LONG
G
P
LIGHTNING PROTECTION
A, AMP
AF
AFC
AFF
AIC
AM
AS
ASYM
AT
ATS
AWG
BOF
B.S.C
C
CAP
CATV
CB
CCTV
cd
CL
CU
DISC
DPST
EC
EWC
ELEC
EM
EPO
EMT
FLA
GRC
GEC
GEN
GFCI
GFI
GFP
GND, G
HOA
HP
IMC
IG
JB
KAIC
KVA
KW
KWH
LED
LTG
LV
MCA
MCB
- AMPERES
- AMP FUSE OR AMP FRAME
- AVAILABLE FAULT CURRENT
(SYMMETRICAL)
- ABOVE FINISHED FLOOR
- AMPERE INTERRUPTING
CAPACITY
- AMMETER
- AMP SWITCH
- ASYMMETRICAL
- AMP TRIP
- AUTOMATIC TRANSFER SWITCH
- AMERICAN WIRE GAUGE
- BOTTOM OF FIXTURE
- BARE STRANDED COPPER
CONDUCTOR
- CONDUIT
- CAPACITY OR CAPACITOR
- COMMUNITY ANTENNA TV
- CIRCUIT BREAKER
- CLOSED CIRCUIT TELEVISION
- CANDELA
- CURRENT LIMITING
- COPPER
- DISCONNECT
- DOUBLE POLE SINGLE THROW
- ELECTRICAL CONTRACTOR
- ELECTRIC WATER COOLER
- ELECTRIC OR ELECTRICAL
- EMERGENCY
- EMERGENCY POWER OFF
- ELECTRICAL METAL TUBING
- FULL LOAD AMPERES
- GALVANIZED RIGID CONDUIT
- GROUNDING ELECTRODE
CONDUCTOR
- GENERATOR
- GROUND FAULT CIRCUIT
INTERRUPTER
- GROUND FAULT INDICATION
- GROUND FAULT PROTECTION
- GROUND
- HAND-OFF-AUTO
- HORSEPOWER
- INTERMEDIATE METAL
CONDUIT
- ISOLATED GROUND
- JUNCTION BOX
- THOUSAND AMPERE
INTERRUPTING CAPACITY
- KILOVOLT AMPERES
- KILOWATT
- KILOWATT HOUR
- LIGHT EMITTING DIODE
- LIGHTING
- LOW VOLTAGE
- MINIMUM CIRCUIT AMPS
- MAIN CIRCUIT BREAKER
ABBREVIATIONS
- MOTOR CONTROL CENTER
- MANHOLE
- MAIN LUGS ONLY
- NORMALLY CLOSED
- NATIONAL ELECTRICAL CODE
- NOT IN CONTRACT
- NOT IN SCOPE OF THIS
PROJECT
- NON FUSIBLE
- NIGHT LIGHT
- NORMALLY OPEN
- NOT TO SCALE
- OVER CURRENT
PROTECTION
- OVERLOADS
- POLE
- PULLBOX
- PHASE
- PANEL
- POINT OF CONNECTION
- POLYVINYL CHLORIDE
- POWER
- RECEPTACLE
- RIGID GALVANIZED STEEL
- SOLENOID
- SINGLE POLE DOUBLE
THROW
- SPEAKER
- SINGLE POLE SINGLE
THROW
- SWITCH
- SWITCHBOARD
- SYMMETRICAL
- TELEPHONE
- TELECOMMUNICATIONS
GROUNDING BUSBAR
- TELEPHONE MOUNTING
BOARD (PLY-WOOD)
- TELEPHONE TERMINAL
BACKBOARD
- TELEVISION
- TYPICAL
- UNDERGROUND
- UNLESS OTHERWISE NOTED
- VOLT
- VOLT AMPERES
- VOLTAGE DROP
- VOLT METER
- VOLT METER SWITCH
- WATTS OR WIRE
- WITH
- WITHOUT
- WEATHERPROOF
- TRANSFORMER
- EXPLOSION PROOF
MCC
MH
MLO
N.C.
NEC
NIC
NIS
NF
NL
N.O.
NTS
OCP
OL
P
PB
PH, Ø
PNL
POC
PVC
PWR
RCPT.
RGS
SOL
SPDT
SPKR
SPST
SW
SWBD
SYM
TEL
TGB
TMB
TTB
TV
TYP
UG
UNO/UNO
V
VA
VD
VM
VS
W
W/ W/O
WP
XFMR
XP
IN ADDITION TO ANY OTHER TESTING REQUIREMENTS, THIRD PARTY TESTING SHALL BE
REQUIRED FOR THE FOLLOWING:
GROUND FAULT PROTECTION
• SWITCHBOARDS, PANELBOARDS, MCC'S AND OTHER EQUIPMENT RATED 1000A OR MORE
OR OVER 600V
• INSULATION RESISTANCE TEST (PHASE TO PHASE, PHASE TO GROUND)
• DIELECTRIC VOLTAGE WITHSTAND TEST (PHASE TO PHASE, PHASE TO GROUND)
CONDUCTORS THAT SUPPLY EQUIPMENT RATED AT 1000 AMPERES OR MORE, OR OVER 600
VOLTS
• INSULATION RESISTANCE TEST (PHASE TO PHASE, PHASE TO GROUND)
• DC HIGH POTENTIAL TEST (PHASE TO PHASE, PHASE TO GROUND)
EMERGENCY AND STANDBY POWER SYSTEMS: SWITCHBOARDS PANELBOARDS, DISTRIBUTION
BOARDS, TRANSFER EQUIPMENT, POWER SOURCE, CONDUCTORS, FIRE PUMPS, EXHAUST
AND VENTILATION FANS.
• PHASE ROTATION TEST
• INSULATION RESISTANCE TEST ON FEEDER CONDUCTORS AND EQUIPMENT (PHASE TO
PHASE, PHASE TO GROUND)
• AUTOMATIC TRANSFER TEST
• OPERATION TEST SYSTEM UNDER LOAD CONDITIONS
TESTING AND SPECIAL INSPECTIONS
POWER ONE-LINE DIAGRAM
CIRCUIT BREAKER. AMP TRIP, FRAME AND OPTIONS AS INDICATED,
3P U.O.N.
FUSE, AMP RATING (AT) AS INDICATED. 3-POLES,
(1) FUSE PER POLE U.O.N.
DISCONNECT SWITCH. SIZE (AF) AS INDICATED. 3-POLE U.O.N.
FUSIBLE DISCONNECT SWITCH. AMP FUSE (AT) AND SWITCH RATING
(AF) AS INDICATED. 3-POLES WITH (1) FUSE PER POLE U.O.N.
AUTOMATIC TRANSFER SWITCH AMPACITY, VOLTAGE, NUMBER OF
POLES, WITHSTAND RATING AS INDICATED
LOW VOLTAGE DRAW-OUT CIRCUIT BREAKER. AMP TRIP (AT), AMP
FRAME (AF)AND OPTIONS AS INDICATED. 3-POLES U.O.N.
MEDIUM VOLTAGE DRAW-OUT CIRCUIT BREAKER. AMP TRIP, AMP
FRAME AND POLES AS INDICATED.
TRANSFORMER
PRIMARY (DELTA U.O.N) AND SECONDARY (WYE U.O.N)
VOLTAGES AS SHOWN
KVA RATING AS SHOWN
SEE TRANSFORMER SCHEDULE FOR ADDITIONAL REQUIREMENTS
480V/100A/ 4P/
25KA WCR
800AT/800AF
800AT/800AF/3P
XXX
3 LA'S
SELECTOR SWITCHES
AS - AMMETER PHASE
VS - VOLTMETER PHASE
WS - WATTMETER
DIGITAL METERING
CURRENT TRANSFORMER
POTENTIAL TRANSFORMER
KEY INTERLOCK - WITHDRAWN KEY
KEY INTERLOCK - CAPTIVE KEY
CONTROL PANEL
VARIABLE FREQUENCY DRIVE
HEAVY DUTY DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
ENCLOSED CIRCUIT BREAKER
FULL VOLTAGE MOTOR STARTER
COMBINATION FULL VOLTAGE
MOTOR STARTER / DISCONNECT
REDUCED VOLTAGE MOTOR
STARTER
COMBINATION REDUCED VOLTAGE
MOTOR STARTER/DISCONNECT
COMBINATION 2 SPEED MOTOR
STARTER/DISCONNECT
MOTOR, HP AS SHOWN
CONNECTION TO GROUND BARE #
4/0CU U.N.O
LIGHTNING
ARRESTERS
PANELBOARD/
DISTRIBUTION
BOARDS
METER WITH CURRENT TRANSFORMER
M - UTILITY OR OWNER METER
AM- A.C. AMMETER
VM- A.C. VOLTMETER
FM- FREQUENCY METER
WM- WATTMETER
SERVICE ENTRANCE SECTION OR OTHER LARGE
SWITCHBOARD OR DISTRIBUTION BOARD.
RATINGS, BREAKER QTY AND SIZE, NAMES ETC. AS
INDICATED ON PLANS
EXISTING SERVICE ENTRANCE SECTION OR OTHER
LARGE SWITCHBOARD/DISTRIBUTION BOARD. RATINGS,
BREAKER QTY AND SIZE, NAMES ETC. AS INDICATED ON
PLANS. ANY NEW WORK WITHIN EXISTING EQUIPMENT
WILL BE BOLD AND NOTATED AS NEW.
200AT/3P
200AF/3P
100AT/200AF
200AT
200AF
N.C. 100%
M
AS
DM
KEY DESIGNATION - PROVIDE ONE LESS KEY
THAN LOCKS (KIRK KEY OR EQUIVLIENT)
ELECTRICAL SHEET LIST
Sheet
Number Sheet Name DATE REVISION
E-001 SYMBOLS AND ABBREVIATIONS
E-201 ELECTRICAL POWER PLAN
E-401 GROUNDING DETAILS
E-601 ELECTRICAL ONE-LINE DIAGRAM
Grand total: 4
NFPA 13 - FIRE SPRINKLER CODE LATEST
NFPA 101 - LIFE SAFETY CODE LATEST
NFPA 72 - NATIONAL FIRE ALARM CODE LATEST
INTERNATIONAL FIRE CODE 2021
FIRE AND LIFE SAFETY CODES EDITION
INTERNATIONAL MECHANICAL CODE (IMC) 2021
INTERNATIONAL BUILDING CODE (IBC) 2021
AMERICANS WITH DISABILITIES ACT (ADA) LATEST
OWNER SPECIFICATIONS AND STANDARDS IHS
LOCAL AND STATE CODES AND AMENDMENTS WR, AZ
NATIONAL ELECTRICAL CODE (NFPA 70) 2020
GENERAL EDITION
ALL OF THE FOLLOWING ARE HEREBY MADE PART OF THESE
SPECIFICATIONS. THEY SHALL BE SATISFIED BY THE CONTRACTOR AT NO
ADDITIONAL EXPENSE TO THE OWNER
CODES AND STANDARDS
1050 E. Southern Ave, Suite #D, Tempe, Arizona 85282, (480) 751-9542designgroup
Architecture, Engineering, and Sustainable Design
AESUS
KEY PLAN NTS NORTH
Drawing Title: Project Title:
Date
Location
Checked
Building Number:
Project Number:
Drawing Number:
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management
WHITERIVER HOSPITAL BACKUP
GENERATOR INSTALL
Location:
FINAL SUBMITTAL - 100%
CONSTRUCTION DOCUMENTS
NOV 17, 2022
o n e e ig h th in c h o n e fo o t
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Dwg. of
75H70122F30010
WHITE RIVER INDIAN HEALTH SERVICES
200 W HOSPITAL DR. WHITERIVER, AZ 85941
AESUS
BOILER PLANT
AREA OF WORK
AESUS
E-001
SYMBOLS AND ABBREVIATIONS
EXPIRES 09/31/24
11 17
WP
A. REFER TO SHEET E001 SYMBOLS, ABBREVIATIONS, AND ADDITIONAL
REQUIREMENTS INCLUDING, BUT NOT LIMITED TO, CODE REQUIREMENTS,
EQUIPMENT AND MATERIAL SPECIFICATIONS AND INSTALLATION REQUIREMENTS,
DEVICE MOUNTING HEIGHTS, EQUIPMENT IDENTIFICATION, ETC.
B. REFER TO SHEET E601 FOR ELECTRICAL ONE LINE DIAGRAM.
C. ALL EQUIPMENT AND FIXTURES ARE NEW UNLESS NOTED OTHERWISE.
D. CONDUIT AND WIRE IS SHOWN DIAGRAMMATICALLY. ACTUAL ROUTING AND
REQUIRED NUMBER OF SUPPORTS SHALL BE DETERMINED BY THE CONTRACTOR.
E. UNLESS CONDUIT ROUTING CLEARLY INDICATES AS SUCH, DO NOT ROUTE
CONDUIT ON OR ABOVE ROOFTOPS WITHOUT CONSULTING ENGINEER TO
DETERMINE ANY POTENTIAL IMPACT TO RACEWAY OR CONDUCTOR SIZE DUE TO
ADDITIONAL AMBIENT DERATING FOR ROOFTOP INSTALLATION.
F. CONCEAL CONDUITS IN ALL FINISHED AREAS INCLUDING CONCEALMENT WITHIN
MASONRY WALLS WHEN PRESENT. (EXCEPTION: ELECTRICAL, MECHANICAL, AND
JANITOR ROOMS).
G. FIRE WALL PENETRATIONS MUST BE SEALED WITH AN APPROVED DESIGN TESTED
FIRE STOPPING SYSTEM APPROPRIATE TO THE PENETRATED WALL TYPE
INSTALLED IN ACCORDANCE WITH MANUFACTURER'S REQUIREMENTS. REFER TO
E500 SERIES DRAWINGS FOR FIRE PENETRATION DETAIL.
H. WHEN OVERHEAD ELECTRICAL WORK IS EXPOSED: MOUNTING OF ALL ELECTRICAL
WORK/CONDUIT SHALL RUN TIGHT WITH DECK. CONTRACTOR MAY RUN CONDUIT
UNDER FLOOR AS NECESSARY TO FACILITATE CONCEALMENT OF CONDUITS.
I. PRIOR TO ROUGH-IN AND FINAL CONNECTION, VERIFY ELECTRICAL
CHARACTERISTICS AND EXACT LOCATION OF THE EQUIPMENT.
J. INSTALL ALL CONDUITS PARALLEL PERPENDICULAR AND UNIFORM TO BUILDING
ELEMENTS
K. ALL WALL VOICE/DATA DROPS SHOWN ON TELECOM DRAWINGS SHALL HAVE A
MINIMUM 4” SQUARE JUNCTION BOX AND 1” CONDUIT WITH PULL CORD STUBBED UP
INTO CEILING SPACE OR TO THE CABLE TRAY, IF APPLICABLE.
L. NO MORE THAN 270 DEGREES OF CONDUIT BENDS ARE ALLOWED IN ANY CONDUIT
RUNS NO MORE THAN 180 DEGREE OF CONDUIT BENDS ARE ALLOWED IN ANY
INTERIOR CONDUIT RUNS.
M. IDENTIFY ALL CONDUIT RUNS WITH MARKER TAPE.
N. COORDINATE ALL TRAY AND CONDUITS FOR SPECIAL SYSTEMS, POWER AND
LIGHTING WITH ALL OTHER TRADES. REFER TO MECHANICAL DRAWINGS.
O. VERIFY ALL EQUIPMENT LOCATIONS AND DIMENSIONS IN THE FIELD PRIOR TO
INSTALLING RACEWAYS AND WIRING
P. ELECTRICAL WORK SHALL BE DONE IN CONFORMANCE WITH THE CONSTRUCTION
DOCUMENTS, ALL APPLICABLE CODES, ISSUED DRAWINGS AND SPECIFICATIONS.
Q. ALL 20A 120V RECEPTACLES WITHIN 6FT OF A SINK OR WET DAMP AREA SHALL BE
GFCI PROTECTED PER NEC 210.8(B)(5)(6)
GENERAL NOTES
METER
SES
SES-2
ATS-NED
NED
ATS-ELS
ATS-EEQ
ATS-EEC
NTDEPD(E) GEN 1
GEN 2
SB- GEN
SUPPORT CONDUITS AND ROUTE ABOVE
GRADE. GALAVANIZED RIGID STEEL CONDUIT.
TYPICAL WHERE ROUTED ON GRADE OR
SUBJECT TO PHYSICAL DAMAGE.
ROUTE CONDUITS ABOVE WALKWAY
PROPOSED GENERATOR LOCATION
ROUTE CONDUITS
OVERHEAD (TYP)
1 2
6 (TYPICAL OF 2)
12 12
(E) PANEL PM
GENERATOR 'GEN 2'
1050 E. Southern Ave, Suite #D, Tempe, Arizona 85282, (480) 751-9542designgroup
Architecture, Engineering, and Sustainable Design
AESUS
KEY PLAN NTS NORTH
Drawing Title: Project Title:
Date
Location
Checked
Building Number:
Project Number:
Drawing Number:
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management
WHITERIVER HOSPITAL BACKUP
GENERATOR INSTALL
Location:
FINAL SUBMITTAL - 100%
CONSTRUCTION DOCUMENTS
NOV 17, 2022
o n e e ig h th in c h o n e fo o t
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Dwg. of
75H70122F30010
WHITE RIVER INDIAN HEALTH SERVICES
200 W HOSPITAL DR. WHITERIVER, AZ 85941
AESUS
BOILER PLANT
AREA OF WORK
AESUS
E-201
ELECTRICAL POWER PLAN
1050 E. Southern Ave, Suite #D, Tempe, Arizona 85282, (480) 751-9542designgroup
Architecture, Engineering, and Sustainable Design
AESUS
KEY PLAN NTS NORTH
Drawing Title: Project Title:
Date
Location
Checked
Building Number:
Project Number:
Drawing Number:
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management
WHITERIVER HOSPITAL BACKUP
GENERATOR INSTALL
Location:
FINAL SUBMITTAL - 100%
CONSTRUCTION DOCUMENTS
NOV 17, 2022
o n e e ig h th in c h o n e fo o t
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Dwg. of
75H70122F30010
WHITE RIVER INDIAN HEALTH SERVICES
200 W HOSPITAL DR. WHITERIVER, AZ 85941
AESUS
BOILER PLANT
AREA OF WORK
AESUS
E-201
ELECTRICAL POWER PLAN
1/8" = 1'-0"1 ELECTRICAL POWER PLAN
1" = 40'-0"2 ELECTRICAL SITE PLAN
KEYNOTES
1. LITHONIA AFF-PEL-DDBTXD-UVOLT-LTP-SDRT-WT-CW OR
APPROVED EQUAL. PROVIDE LOCAL LIGHT SWITCH.
2. EXOTHERMIC WELD TO GENERATOR ENCLOSURE.
3. EXOTHERMIC BOND BETWEEN GROUND RING TO 5/8IN X
10FT GROUND ROD.
4. GROUND TEST WELL AND 5/8IN X 10FT GROUND ROD.
GROUND ROD
5. #4/0 BARE COPPER, DIRECT BURIED GROUND RING.
6. MOUNT AIR TERMINAL TO TOP OF GENERATOR
ENCLOSURE.
7. #4/0 CU DOWN CONDUCTOR FROM AIR TERMINAL TO
GROUND RING.
8. #4/0 CU CONDUCTOR BOND TO METALLIC FENCE.
9. #4/0 BARE CU CONDUCTOR FROM GROUND RING TO
GENERATOR ENCLOSURE.
10. STUB UP CONDUIT THROUGH EQUIPMENT PAD.
COORDINATE EXACT LOCATION WITH EXISTING
GENERATOR POINT OF CONNECTION LOCATION.
11. PROVIDE (3) 120V, 20A CIRCUITS. (1) FOR BLOCK HEATER,
(1) FOR BATTERY CHARGER, (1) FOR LIGHTING AND
RECEPTACLE. UTILIZE SPARE BREAKERS WITHIN PANEL PM
OR NEAREST AVAILABLE GENERATOR BACKED PANEL
BOARD.
12. FEED FROM PANEL 'PM' OR NEAREST AVAILABLE
GENERATOR BACKED PANEL BOARD.
13. GEN 2 ANNUNCIATOR PANEL AND GENERATOR SELECTION
CONTROLLER. LOCATE DIRECTLY ADJACENT TO GEN 1
ANNUNCIATOR.
14. PROPOSED EQUIPMENT LOCATION. LOCATE AS TO NOT
IMPEDE UPON DOOR SWINGS, EGRESS PATHS, OR
GENERATOR INTAKES. PROVIDE 6IN PAD.
15. SEAL PENETRATIONS THROUGH EXTERIOR WALL.
EXPIRES 09/31/24
11 17
CAD WELD TYPE XA WELD
301 CAD WELD TYPE XA WELD
CAD WELD
TYPE GT
WELD
GROUND ROD
CAD WELD TYPE
XA WELD 301
CAD WELD TYPE GT WELD
GROUND ROD
302 302
SECURING #2
WIRE TO CHAIN
LINK FABRIC
CAD WELD TYPE
PT WELD
TYPICAL
TYPICAL
TYPICAL OF 3
TO EQUIPMENT
CAD WELD TYPE GL WELD
MATCH BOLT HOLE
PATTERN OF CONNECTOR
TO EQUIPMENT.
OR
DETAIL NOTES:
DRILL 1/2" HOLE
IN BLANK
FERRULE ON
COPPER BRAID
TYPICAL
OR
TYPICAL OF 3
SECURING #2 WIRE TO
CHAIN LINK FABRIC
TYPICAL OF 3
TYPICAL 311
CADWELD TYPE VS POLE
#251 - CU LOOP
#150 - FLAT SURFACE BASE
TYP. MAIN CONDUCTOR
.375" THRU .625" X 12" THRU 24"
TYP. AIR TERMINAL
1'-4" MAXIMUM
(TYPICAL FOUR
CORNERS)
GREATER THAN 4'-0",
NOT TO EXCEED 20'-0"
GREATER THAN 4'-0",
NOT TO EXCEED 20'-0"
1/2 "x12" AIR TERMINAL
SECONDARY BONDING WIRE
SECONDARY
BONDING WIRE
NOTE:
WHERE THE METAL BODY IS LESS THAN 3/16 INCHES
THICK, A CONTINUOUS GROUND CONDUCTOR (NOT SHOWN
HERE) PROVIDING TWO PATHS TO GROUND SHALL BE
REQUIRED TO BOND ALL AIR TERMINALS.
1050 E. Southern Ave, Suite #D, Tempe, Arizona 85282, (480) 751-9542designgroup
Architecture, Engineering, and Sustainable Design
AESUS
KEY PLAN NTS NORTH
Drawing Title: Project Title:
Date
Location
Checked
Building Number:
Project Number:
Drawing Number:
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management
WHITERIVER HOSPITAL BACKUP
GENERATOR INSTALL
Location:
FINAL SUBMITTAL - 100%
CONSTRUCTION DOCUMENTS
NOV 17, 2022
o n e e ig h th in c h o n e fo o t
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Dwg. of
75H70122F30010
WHITE RIVER INDIAN HEALTH SERVICES
200 W HOSPITAL DR. WHITERIVER, AZ 85941
AESUS
BOILER PLANT
AREA OF WORK
AESUS
E-401
GROUNDING DETAILS
N.T.S.1 #2/0 - #2/0 B.C. CONNECTION
N.T.S.2 #2/0 - #4/0 B.C. CONNECTION
N.T.S.3…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .