This document is a Solicitation Notice for the Generator Replacement project at the Wings Neck Radar Site in Pocasset, MA, issued by the U.S. Army Corps of Engineers - New England District.

The work consists of removing and properly disposing of an existing 35 KW propane standby generator, exhaust muffler, automatic transfer switch, and components, and furnishing and installing a new 24 KW propane standby generator, automatic transfer switch, exhaust silencer/muffler, and connecting the existing louvers to function with the new generator. The new generator must be installed in the same location as the current generator, per the Statement of Work. The construction magnitude is less than $100,000, and the procurement is set-aside for small business vendors. The applicable NAICS code is 238210 with a Small Business Size Standard of $19 Million. All vendors must have an active registration in SAM.gov to be considered.

View the file

Other files

File Type Posted
Amendment W912WJ24Q0140-0002.pdf PDF
Amendment W912WJ24Q0140-0001.pdf PDF
Solicitation W912WJ24Q0140.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

WINGS NECK GENERATOR REPLACEMENT

Figure 1

Figure 1 Aerial Satellite Map – Shows location of the Site Wings Neck located at 10 Harbor

Way, Pocasset, MA 02559.

WINGS NECK GENERATOR REPLACEMENT

Informational Photos:

Photo 1

Photo 1 – Above Photo shows a view of the Wings Neck utility building located inside security fence enclosure.

Photo 2

Photo 2 – Above Photo shows a west side view of the utility building access door into the interior generator room.

Photo 3

Photo 3 – Above Photo shows the interior Onan 35KW generator set (nonfunctioning) with (2) vent louvers with motor actuators, (1) vent louver on each end of the generator.

Photo 4

Photo 4 – Above Photo shows existing muffler which shall be replaced with new generator silencer exhaust pipe. Contractor shall use the same penetration for new generator exhaust.

Photo 5

Photo 5 – Above Photo shows existing Automatic Transfer Switch (ATS). Contractor shall remove, dispose, and provide new ATS, plywood back board, and associated conduits.

Contractor shall replace all conduits and conductors from the ATS to the Louver Motor

Controllers. Existing disconnect switch and fire extinguisher shall be removed, reused, and reinstalled. The existing (2) breaker subpanel shall be removed and disposed (one breaker is unused and one breaker was serving the existing block heater).

Photo 6

Photo 6 – Above Photos shows the exterior and interior view of the vent louver with actuator motors and the existing generator exhaust pipe. There are (2) vent louvers, (1) on each side of the generator.

Photo 7

Photo 7 – Above photo shows the existing vent louver Honeywell Modutrol IV Motor to remain.

Contractor shall provide new conduits and conductors from the ATS to these motors.