ATTACHMENT D.1 SALIENT CHARACTERISTICS - PX018UA1C8 Cut Sheets.pdf

PDF 2 MB Posted

Attached to
4120--Computer Room Air Conditioner (CRAC) Unit QTY1EA
Solicitation number
36C26025Q0748
Issued by

About this file

The provided file is a technical cut sheet for the Liebert PDX Air Cooled DX Cooling Unit, specifically for the PX018 model. The document details the standard features of the precision cooling unit, which include:

Key technical specifications include a digital scroll compressor with R-410A refrigerant and variable capacity operation from 20-100%, an electronically commutated (EC) fan with backward curved blades, and a cabinet constructed of 20 gauge steel powder-coated in RAL7021 black gray matte color. The unit features a Liebert iCOM control system with a 7-inch high-definition capacitive color touchscreen that provides system information, allows parameter adjustments, and offers unit-to-unit communication capabilities. Additional features include a MERV8 filter, a unit disconnect switch, remote shutdown terminal, and comprehensive connectivity options for building management systems including Ethernet, RS-485, Modbus, BACnet, SNMP, and SMS messaging.

View the file

Other files

File Type Posted
36C26025Q0748.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REV : 5

REV DATE : 9/18

DPN003380

Page :1 /2

AIR COOLED

Fo rm

N o.

: D P

N

_R E

V

STANDARD FEATURES

LIEBERT PDX

DX COOLING COIL The evaporator coil is constructed of copper tubes and hydrophilic coated aluminum fins. A stainless steel condensate drain pan is provided.

REFRIGERATION SYSTEM Single refrigeration circuit shall include a liquid line filter drier, a refrigerant sight glass with moisture indicator, an expansion valve, pressure safety switch, and a liquid line solenoid valve.

DIGITAL SCROLL COMPRESSOR The compressor is an R-410A scroll-type with variable capacity operation from 20-100%.

Compressor solenoid valve unloads the compressor to provide variable capacity operation. The compressor has a suction gas cooled motor, EPDM vibration isolators, internal thermal overloads, automatic reset high pressure switch with lockout after three failure occurrences, RotoLock service valves, low pressure transducer and crankcase heater.

ELECTRONICALLY COMMUTATED (EC) FAN is plug type, integral direct driven fan with backward curved blades and Electronically Commutated DC motor; commonly referred to as an EC fan. The fan speed shall be variable and automatically regulated by the Liebert iCOM® control through all modes of operation. The impeller shall be made of aluminum and dynamically balanced. The fan shall be located to draw air through the coil to ensure even air distribution and maximum coil performance.

CABINET The exterior panels are 20 gauge steel and powder coated with RAL7021 black gray matte color paint to protect against corrosion. Exterior panels are insulated with ½” (sides) or 1”(front and rear), 1-1/2 lb insulation. Front and side panels have captive, 1/4 turn fasteners to allow quick panel removal. The cabinet is designed so that all components are serviceable and removable using the front and right sides of the unit.

FILTER - The filter shall be deep-pleated, 2 in (51mm) thick with a MERV8 rating efficiency based on ASHRAE 52.2-2007.

LIEBERT iCOM CONTROL SYSTEM The Liebert PDX is controlled by the iCOM Control System. A 7-inch, high definition, capacitive, color touchscreen presents system information and allows parameters to be viewed and adjusted. The controls shall be menu driven and shall display user menus for active alarms, event log, graphic data, unit view/status overview (including the monitoring of room conditions, operational status in percentage of each function, date and time), total run hours, various sensors, display setup and service contacts. It features a 3-level password protection system. Unit–to-Unit communication capability with other Liebert PDX units is included as standard.

BASE-COMMS FOR BMS CONNECTIVITY The Liebert iCOM controller provides one Ethernet Port and one RS-485 Port dedicated for BMS connectivity. Provides ground fault isolated RS-485 Modbus, BACnet IP & Modbus IP network connectivity to Building Management Systems for unit monitoring and management. Also, provides ground fault isolated 10/100 baseT Ethernet connectivity for unit monitoring and management. The supported management interfaces include: SNMP v1/v2c/v3 for Network Management Systems, HTTP for web page viewing, SMTP for e-mail, and SMS for mobile messaging. The iCOM controller can support dual IP on one network and one 485 protocol simultaneously.

UNIT DISCONNECT SWITCH A “Locking-Type” fused disconnect switch is available. The “Locking-Type” consists of a main unit switch operational from the outside of the unit. Access to the high voltage electric panel can be obtained only with the switch in the “off” position. The disconnect has main fuses within the disconnect.

65,000 AMP SHORT CIRCUIT CURRENT RATING (SCCR) The 60Hz electrical panel provides 65kA SCCR.

REMOTE SHUTDOWN TERMINAL The remote shutdown terminal shall provide the customer with a location to remotely shut down the unit, complying with the National Fire Code.

REV : 5

REV DATE : 9/18

DPN003380

Page :2 /2

AIR COOLED

Fo rm

N o.

: D P

N

_R E

V

STANDARD FEATURES

LIEBERT PDX

COMMON ALARM CONTACT The common alarm contacts shall provide the customer with a set of normally open contacts for remote indication of unit alarms. Four alarm contacts shall be provided for units without a condensate pump. Three alarm contacts shall be provided for units with a condensate pump.

SUPPLY AIR SENSOR The supply air temperature sensor shall provide real-time, direct feedback to the downflow raised floor cooling unit to provide a consistent supply air temperature by adjusting the compressor capacity or the chilled water valve accordingly to maintain set point. The supply air temperature sensor will provide real-time, monitoring of discharge air temperature on all other units.

INFRARED HUMIDIFIER High intensity infrared quartz lamps over a stainless steel humidifier pan. An automatic water supply system maintains water level in the pan and a timed flush system greatly reduces mineral precipitation, and is field adjustable to change the cycle time. A 1" (25mm) air-gap within the water supply piping assembly shall prevent backflow of the humidifier supply water.

ELECTRIC REHEAT Electric low watt density 304/304 stainless steel fin tubular electric reheat elements provide reheat to control room dry bulb temperature.

REV : 3

REV DATE : 8/18

DPN003381

Page :1 /2

AIR COOLED

F or m N o.

: D

P N

_R

E V

OPTIONAL FEATURES

LIEBERT PDX

(Refer to specification sheet for options supplied)

DUAL-FLOAT CONDENSATE PUMP has a capacity of 5 GPM (18.9 l/min) at 40ft (12.2 m) head. Pump is complete with integral primary and secondary float switches, pump, motor assembly and reservoir. The secondary float shall send a signal to the local alarm and shut down the unit upon high water condition. The condensate pump shall be factory-installed on upflow units and field-installed on downflow units.

DIGITAL SCROLL COMPRESSOR SOUND JACKET The compressor sound jacket shall reduce the level of sound emitted from the compressor. It shall consist of a 3/8 inch closed cell polymeric 4.5 - 8.5 lb/ft3 density jacket that encloses the compressor.

SMOKE SENSOR - The Smoke Sensor samples the return air and shuts down the unit upon activation and sends visual and audible alarms. Dry contacts are available for a remote customer alarm. This smoke sensor is not intended to function as or replace any room smoke detection system that may be required by local or national codes.

Adam.Lensegrav Cross-Out

Adam.Lensegrav Cross-Out

REV DATE : 8/18

DPN003381

Page :2 /2

F or m N o.

: D

P N

_R

E V

OPTIONAL FEATURES

LIEBERT PDX

AIR COOLED

UPFLOW UNIT PLENUM(S) are available in various configurations for upflow units: ducted air discharge with solid panels or 2 way, 3 way, or 4 way air discharge with grilles. Each plenum is constructed of 20 gauge steel with 1” (25.4mm), 1 1/2 Ib. (.68kg) insulation and is powder-coated with RAL7021 black gray matte color paint to protect against corrosion. The ducted air discharge plenum is available in 18

in. (457mm), 24 in. (610mm), 30 in. (762mm), 36 in. (914mm), 42 in. (1067mm), or 48 in. (1219mm), and the air discharge with grilles plenum is 18 in. (457mm) high.

LIQUI-TECT SENSOR - The water sensor is a hermetically sealed solid state device with no moving parts. When the sensor detects the presence of moisture, the alarm system is activated.

Document generated 06 April 2022 05:09 PM (EST).

Adam.Lensegrav Cross-Out

REV : 8

REV DATE : 12/17

DPN002929

Page :1 /1

AIR COOLED MODELS WITH TXV

F or m N o.

: D

P N

_R

E V

PIPING SCHEMATIC

LIEBERT PDX

Filter DrierSight Glass

SUCTION

LIQUID

COMPRESSOR

Thermal Expansion Valve

EVAPORATOR

COIL

Check Valve

CONDENSER COIL

FACTORY REFRIGERANT PIPING

FIELD PIPING

For rises over 25ft. (7.6m), trap every 20ft. (6m) or evenly divided

SERVICE / SCHRADER (ACCESS) CONNECTION NO VALVE CORE

LIQUID RETURN

HOT GAS DISCHARGE

Sensing Bulb

External Equalizer

Service Valve

Service Valve

SERVICE / SCHRADER (ACCESS) CONNECTION WITH VALVE CORE

LEE-TEMP RECEIVER

Service Valve

Relief Valve Check Valve

Head Pressure Control Valve

LIQUID RETURN

Digital Solenoid Valve

Optional Field Installed Fusible Plug

HOT GAS

DISCHARGE

LIEBERT MC CONDENSER

LIEBERT PDX UNIT

LIEBERT MC CONDENSER

WITH LEE-TEMP RECEIVER

LIQUID

LIQUID

HOT GAS DISCHARGE

Solenoid Valve

CONDENSER COIL

Includes factory provided inverted trap. No external trap required.

Includes factory provided inverted trap. No external trap required.

Notes:

1. Schematic representation shown. Do not use for specific connection locations.

2. Components are not supplied by Liebert but are required for proper circuit operation and maintenance.

3. Traps must be installed and horizontal lines pitched to ensure proper oil return and to reduce liquid floodback to compressor. Pitch horizontal hot gas piping at a minimum of 1/2" per 10 feet (42mm per 10m) so that gravity will aid in moving oil in the direction of the refrigeration flow.

4. Do not isolate any refrigerant circuits from over pressurization protection.

Trap at base of risers over 5ft. (1.5m)

INTERCONNECTING

PIPING

Pressure Transducer

Adam.Lensegrav Line

Adam.Lensegrav Line

REV : 7

REV DATE : 4/18

DPN002937

Page :1 /1

UPFLOW MODELS

Fo rm

N o.

: D P

N

_R E

V

CABINET DIMENSIONAL DATA

LIEBERT PDX & PCW

Note: Unit with front return shown. Bottom return with rear return floorstand is also available (24" height rear return floorstand is required for use with bottom return unit).

Liebert PDX Model No. PX011 PX018-023 PX029

Air Cooled 600 (272) 670 (304) 700 (317)

Air Cooled w/dual cool 700 (317) 750 (340) 790 (358)

Water/Glycol 620 (281) 690 (313) 720 (327)

GLYCOOL™ or Water/Glycol w/dual cool 720 (327) 770 (349) 810 (367)

Liebert PCW Model No. PW011 PW017 PW029

Chilled Water 575 (260) 600 (272) 650 (294)

DRY WEIGHT lb (kg) APPROXIMATE

Top View

Front View

1 1/4" 32mm

30 1/4" 768mm

Duct Flange

32 5/8" 827mm

Duct Flange

34 1/2" 876mm

77 1/2" 1970mm

3/4" 19mm

34" 864mm

24" 610mm

Shaded area indicates a recommended minimum clearance be provided for component access.

Recommended Clearance for unit installation and for servicing these components if equipped:

Reheat, Filter Clog Switch, Econ-O-Coil Valve, or Gravity Drain Connections.

5 5/8" 143mm

34 3/8" 874mm

Adam.Lensegrav Cross-Out

Adam.Lensegrav Cross-Out

Adam.Lensegrav Cross-Out

Adam.Lensegrav Cross-Out

Adam.Lensegrav Rectangle

Adam.Lensegrav Rectangle

REV : 10

REV DATE : 5/19

DPN002939

Page :1 /1

UPFLOW AIR COOLED MODELS

Fo rm

N o.

: D P

N

_R E

V

PRIMARY CONNECTION LOCATIONS

LIEBERT PDX

FRONT VIEW

PX011 PX018, PX023 PX029

L1 LIQUID LINE SYSTEM 25-5/8 (651) 3/8 1/2 5/8

G1 HOT GAS DISCHARGE 27-7/8 (708) 1/2 5/8 7/8

CD CONDENSATE DRAIN N/A 16-5/8 (422) 3-1/8 (89)

CDP CONDENSATE DRAIN WITH PUMP 3-1/4 (83) 5-7/8 (149)

HUM HUMIDIFIER SUPPLY LINE 29-1/2 (749) 26 (660)

ECS ECON-O-COIL SUPPLY 3-1/4 (83)

ECR ECON-O-COIL RETURN 8-1/4(210)

E1 ELECTRICAL CONN. (HIGH VOLT) 30 (762)

E2 ELECTRICAL CONN. (HIGH VOLT) 27-3/4 (705)

LV1 ELECTRICAL CONN. (LOW VOLT) 27-1/2 (699)

LV2 ELECTRICAL CONN. (LOW VOLT) 26-1/2 (673)

7/8, 1-3/8, 1-3/4

7/8

Z in. (mm)

N/A

N/A

1-1/8

CONNECTION SIZE in.

3/4 NPT FEMALE

1/2

1/4

POINT DESCRIPTION X in. (mm) Y in. (mm)

1-1/2 (38)

31-1/4 (794)

5-1/8 (130)

4-1/4 (108)

Notes:

1. Drawing not to scale. All dimensions from rear corner of unit including panels and have a tolerance of ± 1/2" (13mm).

2. Field pitch Condensate drain line a minimum of 1/8" (3mm) per 12" (305mm) All units contain a factory installed condensate trap. Do not trap external to the unit.

Drain line may contain boiling water. Select appropriate drain system materials The drain line must comply with local codes.

3. Supplied on Dual Cooling Systems only.

4. Unit with front return shown. Bottom return with rear return floorstand also available.

5. All refrigerant & water piping connections are O.D. Copper except as noted.

6. Concentric knockouts to be used based on field supplied conduit diameter.

LV1

ECS

LV2

X

Y

O

TOP VIEW

FRONT OF UNIT

L1

E1 E2

HUM

CDP

RIGHT SIDE VIEW

G1

ECR

ECSECR

L1G1

CD 25 5/8"

143mm

Document generated 06 April 2022 05:09 PM (EST).

Adam.Lensegrav Cross-Out

Adam.Lensegrav Cross-Out

Adam.Lensegrav Cross-Out

Adam.Lensegrav Cross-Out

Adam.Lensegrav Cross-Out

Adam.Lensegrav Cross-Out

REV : 0

REV DATE : 3/18

DPN004594

Page: 1/3

UPFLOW & DOWNFLOW MODELS

F or m N o.

: D

P N

_R

E V

ELECTRICAL FIELD CONNECTIONS

LIEBERT PDX & PCW

1. High Voltage Entrance. Supplied on top and bottom of electric box. Knockout size Ø1.75in (44.5mm).

2. Low Voltage Entrance. Ø1.375 in. (34.9mm) hole located on bottom of Electric Box.

3. Three phase Electric Service and earth ground. Field supplied.

4. Three phase connection. Electric service connection terminals on disconnect.

5. Factory installed disconnect switch. Fused disconnect switch provided on units.

6. Earth ground connection. Connection terminals for field supplied earth grounding wire.

7. Earth ground bar. Connection terminals with factory ground from each high voltage component for field supplied earth grounding wire.

8. Control and monitoring section of electric box.

9. Remote unit shutdown. Replace existing jumper between terminals 37 & 38 with normally closed switch having a minimum 75VA, 24VAC rating. Use field supplied Class 1 wiring. Two additional contact pairs available as an option (labeled as 37B & 38B, 37C & 38C). Replace existing jumper for appropriate pair as done for 37 & 38.

10. Remote Alarm Device (RAD) Connections. Alarm connections may be factory wired or field wired. See schematic, RAD1- 4, for factory wired alarms. For field wired alarms, use Class 1 wiring to connect normally open contacts between terminals 24 & 50, 24 & 51, 24 & 55, or 24 & 56. Suitable for 24VAC.

11. Smoke detector alarm connections. Field supplied Class 1 wiring to 1 Amp, 24VAC maximum remote alarm circuits.

Factory wired contacts from optional smoke detector are #91-Common, #92-NO, and #93-NC. Optional smoke detector trouble (SDT) connections #80 & # 81.

12. Common alarm connection. Field supplied Class 1 wiring to common alarm terminals 75 & 76 (and optional 94 & 95, and 96 & 97), which are factory connected to normally open contacts, 1 Amp, 24VAC maximum on common alarm relay (R3).

13. Heat rejection connection. Field supplied Class 1 wiring to heat rejection interlock terminals 70 & 71 which are factory connected to normally open compressor side switch (self contained units only) or to GLYCOOL relay K11 (GLYCOOL units only). On Dual Cool units only, connect auxilliary cooling source terminals 72 & 73 to relay K11. See indoor and outdoor electric schematic for more information.

14. Reheat and Humidifier Lockout. Optional emergency power lockout of reheat and/or humidifier: Connections #82 & #83 are provided for remote 24VAC source and Class 1 wiring by others.

15. Main Fan Auxiliary Switch. Optional main fan auxiliary side switch. Terminals located on customer connection terminal block for remote indication that the evaporator fan motor/unit is on. Field to connect 24V maximum, Class 1 wiring to connections #84 & #85.

16. Optional Condensate Alarm (Dual Float Condensate Pump only). Relay terminals located on customer connection terminal block for remote indication. Field supplied Class 1 wiring to connections #88 & #89.

17. Optional Remote Liquitect Indicator. Optional remote liquitect indicator for unit shutdown. Terminals located on customer connection terminal block. Field to connect 24V maximum, Class 1 wiring to connections #58 & #59.

18. Optional Analog Inputs #3 & #4. Customer connection to terminals 41, 42, 43, 44 for analog inputs.

19. Spare Terminals for Optional Devices. Customer connection when optional device is supplied. See unit schematic.

Document generated 06 April 2022 05:09 PM (EST).

Adam.Lensegrav Cross-Out

Adam.Lensegrav Cross-Out

DPN004594

Page: 2/3

UPFLOW & DOWNFLOW MODELS

F or m N o.

: D

P N

_R

E V

ELECTRICAL FIELD CONNECTIONS

LIEBERT PDX & PCW

20. CANbus Connector. Terminal block with terminals 49-1 (CAN-H) and 49-3 (CAN-L) + SH (shield connection).

The terminals are used to connect the CANbus communication cable (provided by others) from the indoor unit to the Liebert MC Condenser.

21. CANbus Cable. CANbus cable provided by others to connect to the outdoor condenser and optional PRE unit.

No special considerations are required when the total external cable connection between the indoor unit and outdoor unit(s) is less than 450FT (137M). For total external cable connections greater than 450FT (137M). For external cable connections greater than 450FT (137M), but less than 800FT (243M) a CANbus isolator is required (Contact Factory).

Cable must have the following specifications:

- Braided shield or foil shield with drain wire

- Shield must be wired to ground at indoor unit

- 22-18AWG stranded tinned copper

- Twisted pair (minimum 4 twists per foot)

- Low Capacitance (15pF/FT or less)

- Must be rated to meet local codes and conditions

- EXAMPLES BELDEN 89207 (PLENUM RATED), OR ALPHA WIRE 6454 CATEGORY 5, 5E, OR HIGHER

22. Do not run in same conduit, raceway, or chase as high voltage wiring.

23. For CANbus network lengths greater than 450FT (137M) call Factory.

OPTIONAL COMMUNICATION CONNECTIONS

24. Unit-To-Unit – Plug 64 is reserved for U2U communication.

25. Site and BMS – Plug 74 and terminal block 3 are reserved for Site and BMS connections. Plug 74 is an eight pin RJ45 for a Cat 5 cable. Terminal block 3 is a two position screw terminal block for use with twisted pair wires. Only one of these connections can be used at a time.

NOTE: Refer to specification sheet for total unit full load amps, wire size amps, and max overcurrent protective device size.

Document generated 06 April 2022 05:09 PM (EST).

DPN004594

Page: 3/3

UPFLOW & DOWNFLOW MODELS

F or m N o.

: D

P N

_R

E V

ELECTRICAL FIELD CONNECTIONS

LIEBERT PDX & PCW

UPFLOW UNIT

38B

38B

37B 38C

37C

37B 38C

37C S

H

S H

49-3 49-1

49-3 49-1

37 37

1 High Voltage Entrance

6 87

DOWNFLOW UNIT

Terminal Block For Customer Connection

2Low Voltage Entrance

24 25

Document generated 06 April 2022 05:09 PM (EST).

Adam.Lensegrav Line

Adam.Lensegrav Line

Adam.Lensegrav Cross-Out

Adam.Lensegrav Cross-Out

DPN004596

Page: 1/1

UPFLOW MODELS

F or m N o.

: D

P N

_R

E V

ELECTRICAL FIELD CONNECTIONS

LIEBERT PDX & PCW

1 Opening for field wiring. Suggested entry point for HV field wiring to unit.

2 Opening for field wiring. Suggested entry point for LV field wiring to unit.

3. Wire tie anchors. Use to secure customer wiring.

Notes:

1. Wire needs to be routed outside Electric Box to Low Voltage knockout on bottom of Electric Box.

REV : 2

REV DATE : 3/20

DPN004350

Page :1 /3

UNIT MOUNTED DISPLAY

Fo rm

N o.

: D P

N

_R E

V

PRODUCT INFORMATION

LIEBERT® iCOM™

The Liebert® iCOM™ display is a 7-inch capacitive, color-touchscreen display in an ergonomic, aesthetically pleasing housing. The display and housing will be viewable while the unit accent panels are open or closed.

The display can be easily detached to view while the panel is open.

Menu Layout- The menus will be broken out into two main menu screens: User screen and Service screen.

The User screen contains the menus to access parameters required for basic unit control and setup.

The Service screen is designed for service personal and provides access to advanced control setup features and diagnostic information.

Password Protection- The display will contain two unique passwords to protect against unauthorized changes.

An auto hide/show feature allows the user to see applicable information based on the login used. These four-digit passwords may be customized according to User preference.

Unit Backup and Restore- The user shall have the ability to create safety copies of important control parameters.

The display has the ability for the user to automatically backup unit configuration settings to internal memory or USB storage drive. Configuration settings may be transferred to another unit for a more streamlined unit startup.

Parameter Search- The display has search fields for efficient navigation and parameter lookup.

Parameter Download- The Liebert iCOM shall enable the user to download a report that lists parameter names, factory default settings, and the user programmed settings in .csv format for remote reference.

Parameter Directory- The Liebert iCOM shall provide a directory that lists all parameters in the control. The list shall provide Line ID numbers, parameter labels, and current parameter values.

DPN004350

Page :2 /3

UNIT MOUNTED DISPLAY

Fo rm

N o.

: D P

N

_R E

V

PRODUCT INFORMATION

LIEBERT® iCOM™

Context Sensitive Help- The display will have an onboard help database. The database will provide context sensitive help to assist with setup and navigation of the menus.

Display Setup- The user has the ability to configure the display information based on the specific user’s preference.

Language, units of measure, screen contrast, home screen layout, back light timer and the hide/show of certain readouts will be configurable through the display.

Additional Readouts- The display has the ability for the user to configure custom widgets on the main screen.

Widget options will include items such as fan speed, call for cooling, call for free cooling, maintenance status, call for hot water reheat, call for electric reheat, call for dehumidification, call for humidification, airflow, static pressure, fluid flow rate and cooling capacity.

Status LEDs- The display will provide the user with the unit’s operating status using an integrated LED.

The LED will indicate if the unit has an active alarm; if the unit has an active alarm that has been acknowledged;

or if the unit is on, off, or in a standby status.

Unit Alarms – All unit alarms are annunciated through both audio and visual cues, clearly displayed on the screen, automatically recorded in the event log, and communicated to monitoring plug connections.

Event Log – The display will automatically store the last 400 unit-only events (messages, warnings, and alarms).

Service Contact Information – The display has the ability to store the local service or sales contact information.

Upgradeable –Display and Control Board software upgrades are performed through a USB connection.

Unit-to-Unit (U2U) Communication – Communication via private Ethernet network allows for advanced control functionality (Teamwork modes, sharing sensor data, Standby Rotation, Lead-Lag, and Cascade operation).

Temperature Control- Precision temperature control is maintained while maximizing efficiency based on a user entered setpoint and tolerance.

Various Control Types- Proportional, PI (proportional-integral), or Intelligent control types can be selected for supply or return temperature. These control types have been developed to maximize component life and maintain precise environmental control.

Timers/Sleep Mode- The menus shall allow various customer settings for turning the unit On or Off.

Sensor Calibration- The menus shall allow unit sensors to be calibrated with external sensors.

Maintenance/Wellness Settings- The menus shall allow reporting of potential component problems before they occur.

DPN004350

Page :3 /3

UNIT MOUNTED DISPLAY

Fo rm

N o.

: D P

N

_R E

V

PRODUCT INFORMATION

LIEBERT® iCOM™

Options Setup- The menus shall provide operation settings for the installed components.

Auto Restart- The unit will return to its previous operating status after loss of power. Units can be stagger started to minimize system current draw.

Auxiliary Boards- The menus shall allow setup of optional expansion boards.

Various Sensors: The menus shall allow setup and display of optional custom sensors. The control shall include four customer accessible analog inputs for field-supplied sensors. The analog inputs shall accept a 4 to 20mA signal. The user shall be able to change the input to 0 to 5VDC or 0 to 10VDC. The gains for each analog input shall be programmable from the front display. The analog inputs shall be able to be monitored from the front display.

Diagnostics/Service Mode- The Liebert® iCOM™ control shall be provided with self-diagnostics to aid in troubleshooting. The microcontroller board shall be diagnosed and reported as pass/not pass. Control inputs shall be indicated as On or Off at the front display. Control outputs shall be able to be turned On or Off from the front display without using jumpers or a service terminal. Each control output shall be indicated by an LED on a circuit board.

590-1351-501B/SL-31050_REV2_6-17

LIEBERT® LIQUI-TECT® 410

POINT LEAK-DETECTION SENSOR

Product Specification/Installation Guide

The Liebert Liqui-tect 410 (LT410) provides single-point detection of leaks. The point-detection sensor has two gold-plated sensing probes to prevent corrosion and to provide accurate readings. The LT410 constantly monitors for leaks, internal faults, and power failures and warns of any abnormal conditions. Mounting brackets allow for sensor height adjustment and leveling.

The LT410 is the ideal solution for sensing leaks under a raised computer floor or air conditioning drip pans. Two independent outputs provide added flexibility with the capacity to signal both a local alarm panel and a remote building-management system or external equipment, such as motorized water shut-off valves.

LT410 APPLICATIONS

The LT410 is ideally-suited for:

• Glycol and chilled-water cooling,

• Humidification supply water piping,

• Condensate pumps and drains,

• Unit and ceiling auxillary drip pans,

• Overhead piping troughs.

LOCATIONS/PLACEMENT

The LT410 is an excellent choice for:

• Large-scale network control centers,

• Data centers,

• Server rooms and closets,

• Unattended, remote shelters,

• Mechanical equipment rooms,

• Sensitive areas with overhead piping,

• Industrial process-control rooms.

COMPONENTS OF THE

LIQUI-TECT 410 MODULE

The LT410 consists of a metal enclosure with a hinged top door that provides access to the internal wiring termination. It includes side access through a box connector for installation of the power and contact wiring. The mounting brackets attach to the enclosure with adjustable slots to allow custom setting of the height of the sensing probes.

LIEBERT® LT410 POINT LEAK-DETECTION SENSOR

Product Specification/Installation Guide

SPECIFICATIONS

Power Requirements 24 VAC 100 mA, 50/60 Hz, 3 VA (max.)

Dimensions, W x D x H 6.35 x 2.25 x 4.46 in (161.2 x 57.2 x 113.2 mm)

Weight (assembled) 2.0 lb (0.9 kg)

Metal Enclosure NEMA 1, IP 30

ENVIRONMENTAL CONDITIONS

Operating Temperature 50°F to 104°F (10°C to 40°C)

Operating Humidity 10% to 95% relative humidity (non-condensing)

Operating Altitude 0 to 10,000 ft (0 to 3,048 m)

Output Relay Contact Rating 2 Form-C; 3 A rating at 24 VAC

AGENCY LISTINGS

UL UL916

C-UL C22.2, No. 205-M1983

CE Yes

FCC Compliance 47 CFR, Part 15

TOP VIEW

FRONT VIEW SIDE VIEW5.85”

(148.5mm)

4.46” (113.2mm)

6.35” (161.2mm) 2.25”

(57.2mm)

Form-C relay outputs and power wiring

Adjustable probe height

0.0 - 0.5” (0.0 - 12.7mm)

DIMENSIONS -

TOP, FRONT AND SIDE

LIEBERT® LT410 POINT LEAK-DETECTION SENSOR

Product Specification/Installation Guide

WIRING INTERCONNECTIONS

Circuits are shown in powered, non-alarm state.

NOTE: All power and alarm connections must be Class 2 circuits.

Red Wires Orange Wires Yellow Wires

24 V, AC/DC

@ 0.10A, 50-60 Hz, DC Class 2 Circuit Only

Alarm Contact Rating

24 VAC @ 3A

Class 2 Circuit Only

Alarm Contact Rating

24 VAC @ 3A

Class 2 Circuit Only

PO

W

ER

PO

W

ER

1- N

O

1- N

C

1- C

O M

2- N

O

2- N

C

2- C

O M

Gold-plated Probes

Height adjustable 0-0.5” (0-12.7mm)

PLACEMENT ON SUBFLOOR

UNDER COOLING SUPPORT

EQUIPMENT

To a Liebert environmental unit and an optional monitoring panel

To external power supply or directly from unit (see Power Wiring on page 4)

Leak detection zone (directly beneath unit)

VertivCo.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA © 2017 Vertiv Co. All rights reserved. Vertiv and the Vertiv logo are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice.

590-1351-501B/SL-31050_REV2_6-17

LIEBERT® LT410 POINT LEAK-DETECTION SENSOR

Product Specification/Installation Guide

Liebert DS, DSE, LT410 CW, PDX or Mini-Mate2 (8 ton) Orange Wires Environmental

1-NC

Unit

1-COM 24 (24V)

1-NO 50, 51, 55 or 56

Note: Terminal 50 not available on Mini-Mate2 (8-ton)

Liebert Mini-Mate2, LT410 (1 to 5 ton) Orange Wires Environmental

1-NC

Unit

1-COM TB1-1 (24V)

1-NO TB1-2 or TB1-3

LT410 Liebert CRV Orange Wires Environmental

1-NC

Unit

1-COM 60

1-NO 61

NOTE: In iCOM, use the Service Options menu to add that the Liqui-tect is installed.

LT410 Liebert contact monitor panel Yellow Wires Alarm

2-NC

Panel

2-COM

2-NO

Liebert DS, DSE, CW, PDX, or Mini-Mate2 (8 ton) LT410

TB1 TB1

T5 (24V) Red

G5 (Ground) Red

Location of T5 (24V) connection on main controller board of Liebert unit.

Liebert Mini-Mate2 LT410 (1 to 5 ton)

TB1

From 24V Transformer Red

Red

* Requires external transformer (there are no designated terminal connections on the unit)

Liebert CRV LT410

Medium Control Board TB1

6 Red

4 Red

Transformer LT410

TB1

From 24V Transformer Red

Red

POWER WIRING

The LT410 is rated for 24 VAC, 50/60 Hz, and 0.10 A.

WIRING TO AUXILIARY ALARM PANELS

The LT410 has two Form-C dry contact alarm output contacts: orange wires (1) and yellow wires (2). Each contact is rated for 24 VAC at 3 amp.

TB1

Input Contact (N.O.)

Document generated 06 April 2022 05:09 PM (EST).

Adam.Lensegrav Rectangle

Adam.Lensegrav Rectangle

Adam.Lensegrav Cross-Out

REV : 8

REV DATE : 3/19

DPN002981

Page :1 /1

UPFLOW DISCHARGE GRILLE

Fo rm

N o.

: D P

N

_R E

V

PLENUM DIMENSIONAL DATA

LIEBERT PDX & PCW

WITH GRILLE

FRONT VIEW - UNIT WITH PLENUM

FRONT VIEWS - CHECK ONE (1):

REAR VIEWS - CHECK ONE (1):

LEFT SIDE VIEWS -

CHECK ONE (1): RIGHT SIDE VIEWS -

CHECK ONE (1):

WITH GRILLE

WITHOUT GRILLE

WITH GRILLE

WITHOUT GRILLE

WITHOUT GRILLEWITHOUT GRILLE

WITH GRILLE

SIDE VIEW - UNIT WITH PLENUM

ECS

ECR

E1

E2

LV1

LV2

L1 (PDX)

WS

G1 (PDX)

WR

CDP

HUM

Notes:

1. Two grilles minimum per plenum required.

The nominal grille size is 24" (609mm) x 14" (355mm).

2. All Plenums are shipped flat (non-assembled) and must be assembled on site.

3. Upflow bottom return units are available with required rear return floorstand with filter.

4. Units supplied with Dual Cooling systems only (4 pipe system).

5. Concentric knockouts to be used based on field supplied conduit diameter.

POINT DESCRIPTION X in. (mm) Y in. (mm) KNOCKOUT SIZE, in. (mm)

L1 LIQUID LINE SYSTEM 1

G1 HOT GAS DISCHARGE 1

CDP CONDENSATE DRAIN WITH PUMP 3-1/2 (89) 6-1/8 (155) 3/4 (19)

HUM HUMIDIFIER SUPPLY LINE 29-1/2 (748) 26 (662) 1/2 (13)

WS SUPPLY-CW/WATER/GLYCOL

WR RETURN-CW/WATER/GLYCOL/GLYCOOL™

ECS ECON-O-COIL SUPPLY / GLYCOOL™ SUPPLY 3-1/8 (80)

ECR ECON-O-COIL RETURN 8-1/4 (210)

E1 ELECTRICAL CONN. (HIGH VOLT) 29-1/8 (739) 28-5/8 (728)

E2 ELECTRICAL CONN. (HIGH VOLT) 31-1/4 (793) 27-5/8 (702)

LV1 ELECTRICAL CONN. (LOW VOLT) 32-1/4 (818)

LV2 ELECTRICAL CONN. (LOW VOLT) 30-1/2 (775)

5-1/8 (130)

4-1/4 (109)

5-1/8 (130)

1 (25)

25-5/8 (651)

25-5/8 (651)

25-5/8 (652)

7/8 (23), 1-3/8 (35), 1-3/4 (44)

2 (51)

2 (51)

31 3/4" 807mm

1 3/8" 35mm

77 1/2" 1970mm

18" 458mm

34 1/2" 876mm

REV : 4

REV DATE : 8/19

DPN002155

Page :1 /1

STANDARD & OPTIONAL FEATURES

Fo rm

N o.

: D P

N

_R E

V

PREMIUM EFFICIENCY CONTROL

LIEBERT MC CONDENSER

STANDARD FEATURES

COIL Liebert microchannel coils are all‐aluminum construction. Tubes are created by extruding small parallel refrigerant flow paths into aluminum.

Full‐depth louvered aluminum fins fill spaces between the tubes. Tubes, fins and aluminum headers are oven‐brazed to form a complete refrigerant‐to‐air heat exchange coil. Baffles are used in the headers to separate one coil slab into multiple passes as needed. Coils are factory leak tested at a minimum of 300 PSIG and dehydrated. Copper stub pipes are electric resistance welded to aluminum coils and joints are protected with polyolefin to seal joint from environmental corrosive elements. Hot gas and liquid lines are brazed to the stub pipes with spun closed ends for customer piping connections. Coil pipe assembles are filled and sealed with a nitrogen holding charge for shipment. One coil is used per fan assembly.

FAN/MOTOR ASSEMBLY The fan/motor assembly is complete with external rotor motor, fan blades and fan/finger guard. Fan blades are constructed of stamped aluminum or steel extrusion coated with PP plastic. Fan guards are heavy gauge, close meshed, steel wire, coated with a black corrosion resistant finish. Fan terminal blocks located on the top of the fan guard with IP54 protection class. Fans are factory balanced and tested before shipment.

FAN MOTORS Fan motors are specifically designed for variable speed and have ball bearings. The EC fans provide internal overload protection through the built‐in electronics. Each EC fan motor has built‐in controller and communication module, linked via RS485 communication wire to each fan and the Premium Control Board. This allows each fan to receive and respond to precise fan speed inputs from the Premium control board.

PREMIUM EFFICIENCY FAN CONTROL The Liebert premium efficiency condenser control system is complete with control board, EC fan motor(s),refrigerant‐pressure transducer(s), refrigerant‐temperature thermistor(s), ambient‐temperature thermistor, and motor overload protection in the factory wired control panel. The control board maintains EC fans on the same circuit to the same speed in order to maintain refrigerant head pressure. The control board receives a run signal from the compressor of the indoor unit via field‐supplied low voltage interlock wires and field‐supplied CANbus communication wires from the indoor unit iCOM. The control system provides refrigerant head pressure and system starting for outdoor ambient temperature as low as -30°F (‐35 °C), provided the total temperature design range (from minimum to maximum) is 125°F (70°C) or less.

HOUSING The condenser housing is constructed of bright aluminum sheet and divided into individual fan sections by full width baffles. Internal structural support members, including coil support frame, are galvanized steel for strength and corrosion resistance. Panel doors are provided on two sides of each coil/fan section to provide for coil cleaning. Aluminum legs are provided with rigging holes for hoisting the unit into position.

COMMUNICATION The Premium Efficiency Control communicates with the iCOM control of the indoor Liebert unit using field supplied CANbus wires. The communication link allows for condenser alarm condition communication to iCOM, communication of other measurable items on the condenser, and fan control features to improve efficiency, sound and wintertime operation based on iCOM programming.

UNIT DISCONNECT SWITCH Locking unit disconnect switch is factory installed and wired in attached condenser control section.

OPTIONAL FEATURES

LIEBERT LEE‐TEMP LOW AMBIENT CONTROL Lee‐Temp receiver kits can be added to achieve head pressure control down to minimum ambient temperatures of ‐30 °F (‐34 °C). The premium efficiency fan control when used with the Liebert Lee‐Temp receiver kits runs the fan(s) at lower speeds during cold temperatures saving fan energy.

575V POWER SUPPLY The factory installed condenser option will include a secondary enclosure, a 575V-to-480V, 3 phase, step down transformer, secondary fuses for the transformer, and all wiring between the main and secondary electrical enclosures. Site power connections will be made in the main electrical enclosure and the secondary enclosure will be located on the condenser end opposite of the main electrical enclosure.

E-COAT COIL PROTECTION The aluminum microchannel coil is epoxy-coated for extended coil life in corrosive environments, such as coastal areas.

Factory-applied E-coat using immersion and baking process provides a flexible epoxy-coating to all coil surfaces and ensures complete coil encapsulation. Coil color is black and a factory-applied UV topcoat protects the E-coat from solar UV ray degradation.

REV DATE : 12/16

DPN003436

Page :1 /1

1 FAN (MCS028, MCM040, MCL055)

F or m N o.

: D

P N

_R

E V

CABINET & ANCHOR DIMENSIONAL DATA

LIEBERT MC CONDENSER

With Receiver Option

Note:

1. Liebert recommends a clearance of 36” (915mm) on each side for proper operation and component access.

2. Cross Bracing required for legs longer than

18" (457.2mm). Quantity varies per model & options selected.

3. For PDX w/EEV systems & unheated refrigerant receivers, 6-1/2" (165mm) is 9-1/4" (235mm) and 15-1/4" (387) is not applicable.

A*

A

G

F

Typical all legs

18 (457) 36 (914) 48 (1219) 60 (1524)

DIM "G" 31-5/8 (803) 49-5/8 (1260) 61-5/8 (1565) 73-5/8 (1870)

DIM "H" 39-5/8 (1006) 57-5/8 (1464) 69-5/8 (1768) 81-5/8 (2073)

MCL055

DIM "G" 35-7/8 (911) 53-7/8 (1368) 65-7/8 (1673) 77-7/8 (1978)

DIM "H" 43-5/8 (1108) 61-5/8 (1565) 73-5/8 (1870) 85-5/8 (2175)

LIEBERT

MODEL

NUMBER

MCS028

MCM040

F in. (mm)

(LEG HEIGHT DIMENSIONS)

H

TOP OF

FAN GUARD

575V Option

Left Side of Unit

C D

M L K

Front View (Lee-Temp Shown)

6 1/2" 165mm Ref.

K

Entering Hot Gas and Leaving Liquid Piping

A

DETAIL A

MCS028 50-5/8 (1287) 58-7/8 (1495) 44-1/8 (1120) 42-1/2 (1080) 42-1/2 (1080) 40-7/8 (1038) 35-7/8 (910)

MCM040 57-3/16 (1453) 65-3/8 (1661) 48 (1219) 46-5/16 (1177) 46 (1168) 44-3/8 (1127) 39-5/16 (999)

MCL055 68 (1727) 77 (1956) 56 (1422) 54-3/8 (1381) 55-1/2 (1410) 53-7/8 (1368) 48-3/4 (1238)

K in (mm) L in (mm) M in (mm)D in (mm)C in (mm)

LIEBERT

MODEL

NUMBER

A in (mm) A* in (mm)

(575V ONLY)

1 7/8" 48mm Typ.

3 5/8" 93mm Typ.13/16"

21mm Typ.

7" 178mm

Typ.

1/2" (13mm) X 1" (25mm) Obround Typ.

Main Electric

Box End

575V Option

Anchor Plan

15 1/4" 387mm

Document generated 06 April 2022 05:09 PM (EST).

Adam.Lensegrav Cross-Out

Adam.Lensegrav Cross-Out

Adam.Lensegrav Cross-Out

Adam.Lensegrav Cross-Out

Adam.Lensegrav Cross-Out

Adam.Lensegrav Cross-Out

Adam.Lensegrav Line

Adam.Lensegrav Line

Adam.Lensegrav Line

Adam.Lensegrav Line

Adam.Lensegrav Line

Adam.Lensegrav Line

Adam.Lensegrav Line

Adam.Lensegrav Line

Adam.Lensegrav Rectangle

Adam.Lensegrav Rectangle

Adam.Lensegrav Rectangle

Adam.Lensegrav Cross-Out

Adam.Lensegrav Cross-Out

Adam.Lensegrav Cross-Out

Adam.Lensegrav Cross-Out

Adam.Lensegrav Cross-Out

REV DATE : 4/18

DPN003034

Page :1 /1

F or m N o.

: D

P N

_R

E V

CONDENSER AND OPTION WEIGHT DATA, lb(kg)

LIEBERT MC CONDENSER

Total weight is the sum of 'Condenser' + ('PDX-EEV Receiver' or 'Lee-Temp' or 'DSE Receiver 050/080/085' or 'DSE Receiver

125/150/165')'+'Coated Coil' + '575V Transformer'.+ 'Seismic/Wind Bracing'

MCS028 MCS056 MCM040 MCM160

1 2 1 1 2 2

18" Leg 154 ( 70) 270 ( 122) 231 ( 105) 441 ( 200) 441 ( 200) 860 ( 390)

36" Leg 286 ( 130) 419 ( 190) 363 ( 165) 590 ( 268) 590 ( 268) 1066 ( 484)

48" Leg 318 ( 144) 451 ( 205) 395 ( 179) 622 ( 282) 622 ( 282) 1114 ( 505)

60" Leg 349 ( 158) 482 ( 219) 426 ( 193) 653 ( 296) 653 ( 296) 1160 ( 526)

45 ( 20) 45 ( 20) 45 ( 20)

55 ( 25) 110 ( 50) 55 ( 25) 100 ( 45) 110 ( 50) 220 ( 100)

45 (20) 90 (41)

92 (42) 184 ( 83)

55 ( 25) 65 ( 29) 60 ( 27) 70 ( 32) 70 ( 32) 80 ( 36)

4 ( 2) 8 ( 4) 5 ( 2) 10 ( 5) 10 ( 5) 20 ( 9)

40 ( 18) 40 ( 18) 40 ( 18) 40 ( 18) 40 ( 18) 57 ( 26)

Additional Weight for Options

Refrigerant Circuits

Size Small (MCS) Medium (MCM)

MCM080Condenser Model

PDX-EEV Receiver

Condenser Dry

Weight

Lee-Temp

DSE Receiver DA050/080/085

DSE Receiver DA125/150/165

Seismic/Wind Bracing 18" legs

Coated Coil

575V Transformer

MCL055 MCL165

1 1 2 1 1 2

18" Leg 344 ( 156) 602 ( 273) 602 ( 273) 891 ( 404) 1186 ( 538) 1186 ( 538)

36" Leg 486 ( 220) 766 ( 347) 766 ( 347) 1136 ( 515) 1453 ( 659) 1453 ( 659)

48" Leg 518 ( 235) 798 ( 362) 798 ( 362) 1184 ( 537) 1501 ( 681) 1501 ( 681)

60" Leg 549 ( 249) 829 ( 376) 829 ( 376) 1230 ( 558) 1547 ( 702) 1547 ( 702)

45 ( 20)

60 ( 27) 115 ( 52) 120 ( 54) 175 ( 79) 215 ( 98) 240 ( 109)

45 ( 20) 90 ( 41) 45 (20) 45 ( 20) 90 ( 41)

94 ( 43) 94 ( 43) 94 ( 43) 188 ( 85)

67 ( 30) 77 ( 35) 77 ( 35) 118 ( 54) 118 ( 54) 118 ( 54)

8 ( 4) 16 ( 7) 16 ( 7) 24 ( 11) 32 ( 15) 32 ( 15)

40 ( 18) 40 ( 18) 41 ( 19) 57 ( 26) 57 ( 26) 57 ( 26)

575V Transformer

Coated Coil

Seismic/Wind Bracing 18" legs

Size Large (MCL)

Condenser Model MCL110 MCL220

Refrigerant Circuits

Condenser Dry weight

PDX-EEV Receiver

Lee-Temp

DSE Receiver DA050/080/085

DSE Receiver DA125/150/165

Additional Weight for Options

Document generated 06 April 2022 05:09 PM (EST).

Adam.Lensegrav Rectangle

Adam.Lensegrav Line

Line

DETAIL A

REV DATE : 12/16

DPN002166

Page :1 /1

SINGLE CIRCUIT 1 FAN, 2 FAN, 3 FAN & 4 FAN UNITS

F or m N o.

: D

P N

_R

E V

PIPING DIMENSIONAL DATA

LIEBERT MC CONDENSER

VERTICAL

HORIZONTAL

LEAVING LIQUID

LINE

ENTERING HOT

GAS LINE

OPTIONAL FUSIBLE PLUG SERVICE KIT TO BE BRAZED INTO THE LIQUID LINE(S) IN

EITHER THE VERTICAL OR HORIZONTAL POSITION. (WHERE REQUIRED)

(VERTICAL POSITION IS PREFERRED, HORIZONTAL POSITION IS OPTIONAL.)

HOT GAS LINE LIQUID LINE

MCS 028 1 1 7/8 5/8

MCM 040 1 1 7/8 5/8

MCM 080 2 1 1-1/8 7/8

MCL 055 1 1 1-1/8 7/8

MCL 110 2 1 1-3/8 1-1/8

MCL 165 3 1 1-3/8 1-1/8

MCL 220 4 1 1-5/8 1-3/8

CONDENSER

CIRCUITS

CONNECTION SIZES, OD, IN

MODEL NO.

NUMBER

OF FANS

FIELD PIPING

COVER*

* SHIPPING COVER IS NOT NECESSARY FOR PROPER CONDENSER OPERATION AND

MAY BE RECYCLED IF FIELD PIPING INTERFERES WITH PROPER REATTACHMENT.

VERTICAL

MCS028 ONLY

HORIZONTAL

LEAVING LIQUID

LINE

ENTERING HOT GAS LINE

INVERTED TRAPS

ARE FACTORY PROVIDED

INSIDE CONDENSER

Document generated 06 April 2022 05:09 PM (EST).

Adam.Lensegrav Line

Adam.Lensegrav Line

Adam.Lensegrav Line

Adam.Lensegrav Line

Adam.Lensegrav Line

Adam.Lensegrav Line

Adam.Lensegrav Cross-Out

Adam.Lensegrav Cross-Out

Adam.Lensegrav Cross-Out

Adam.Lensegrav Cross-Out

Adam.Lensegrav Rectangle

REV : 14

REV DATE : 2/20

DPN000788

Page :1 /2

Fo rm

N o.

: D

PN

_R

EV

RECOMMENDED REFRIGERANT LINE SIZES CU, OD

LIEBERT AIR COOLED SYSTEMS

Indoor Model Equivalent Length 50 ft (15m) 100 ft (30m) 150 ft (45m) 300 ft (91m) 450ft (137m) Hot Gas Line, in. 3/4 3/4 3/4 7/8 Liquid Line, in. 5/8 5/8 5/8 3/4

Hot Gas Line, in. 7/8 7/8 7/8 1-1/8 Liquid Line, in. 3/4 3/4 3/4 7/8

Hot Gas Line, in. 1/2 5/8 5/8 5/8 Liquid Line, in. 3/8 1/2 1/2 1/2

Hot Gas Line, in. 5/8 5/8 5/8 3/4 Liquid Line, in. 1/2 1/2 1/2 5/8

Hot Gas Line, in. 3/4 3/4 3/4 7/8 Liquid Line, in. 5/8 5/8 5/8 5/8

Hot Gas Line, in. 7/8 7/8 7/8 1-1/8 Liquid Line, in. 5/8 5/8 5/8 3/4

Hot Gas Line, in. 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 Liquid Line, in. 7/8 7/8 7/8 7/8 7/8

Hot Gas Line, in. 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8 Liquid Line, in. 7/8 7/8 7/8 7/8 7/8

Hot Gas Line, in. 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8 Liquid Line, in. 7/8 1-1/8 1-1/8 1-1/8 1-1/8

Hot Gas Line, in. 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8 Liquid Line, in. 7/8 1-1/8 1-1/8 1-1/8 1-1/8

Hot Gas Line, in. 1-5/8 1-5/8 1-5/8 1-5/8 Liquid Line, in. 1-3/8 1-3/8 1-3/8 1-3/8

DA165

System Fluid : R-410A

CR035RA

PX018

PX023

PX029

DA050 / DA080/

DA085

Any Compressor Type

CR019RA/ CR020RA

DA125

DA150

PX011

DA250 / DA265

LIEBERT AIR-COOLED SYSTEMS USING R-410A

Notes:

1. Consult factory for proper line sizing for runs longer than maximum equivalent length shown in table.

2. Must downsize vertical riser one trade size (1-1/8” to 7/8” or 7/8” to 3/4” or 3/4" to 5/8" or 5/8" to 1/2").

3. Consult factory when actual pipe length between condenser/Liebert EconoPhase and Liebert DSE unit will exceed 300 ft (91 m).

4. Liebert DA250-265 unit can be extended to max 200ft (61m) linear or 300ft. (91m) equivalent.

Indoor Model Equivalent Length 50 ft (15m) 75 ft (23m) 100 ft (30m) 125 ft (38m) 150 ft (45m) Suction Line, in. 7/8 7/8 7/8 7/8 7/8 Liquid Line, in. 1/2 1/2 1/2 1/2 1/2

Suction Line, in. 7/8 1-1/8 1-1/8 1-1/8 1-1/8 Liquid Line, in. 1/2 1/2 5/8 5/8 5/8

Suction Line, in. 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 Liquid Line, in. 1/2 5/8 5/8 5/8 5/8

System Fluid: R-410A Digital Scroll Models

MT060

MT048

MT036

2 2 2

2 2 2 2

Document generated 06 April 2022 05:09 PM (EST).

Adam.Lensegrav Rectangle

Adam.Lensegrav Line

Line

REV DATE : 9/19

DPN003954

Page :1/4

LIEBERT MC CONDENSER

F or m N o.

: D

P N

_R

E V

AIR COOLED PIPING SCHEMATIC

Indoor Unit

Notes:

1. Pitch horizontal hot gas piping at a minimum of 1/2" per 10 feet (42mm per 10m) so that gravity will aid in moving oil in the direction of the refrigeration flow.

2. Single circuit condenser shown.

3. Unit piping entrance varies by unit and may be through the top of the unit.

4. Indoor unit may be Liebert DS, PDX, or CRV and is shown for reference only while demonstrating proper pipe and unit/condenser height differences.

5. The bottom of the condenser coil or bottom of the receiver (if equipped) must be higher than the elevation of the TXV inside the indoor unit. The vertical height must not exceed 60 feet (18.3m).

6. Trapping must be practiced at bottom of riser with any rise over 5 feet high. If rise exceeds 25 feet (7.5m), then a trap is required in 20 foot (6 m) increments or evenly divided

Field piping

Gas

Gas

Liquid

Liquid

Gas

MC Condenser without Receiver

Liquid

Gas

CONDENSER ABOVE INDOOR UNIT

Liquid

MC Condenser with Receiver

H

60' 18.3m

Maximum Vertical Rise

7.6" 194mm

Internal TXV Height H in. (mm)

PDX Downflow 44 (1118)

PDX Upflow 20 (508)

DS035-105 Downflow/Upflow 43 (1092)

CRV - CR019 45 (1143)

CRV - CR020/CR035 27 (686)

TXV location

(Piping to Condenser & Receiver not shown for clarity)

(Piping to Condenser not shown for clarity)

Document generated 06 April 2022 05:09 PM (EST).

Adam.Lensegrav Line

Adam.Lensegrav Line

Rectangle

DPN003954

Page :3/4

LIEBERT MC CONDENSER

F or m N o.

: D

P N

_R

E V

AIR COOLED PIPING SCHEMATIC

Indoor Unit

H

TXV location

Liquid

Gas

CONDENSER AND INDOOR UNIT AT SAME LEVEL

Notes:

1. Pitch horizontal hot gas piping at a minimum of 1/2" per 10 feet (42mm per 10m) so that gravity will aid in moving oil in the direction of the refrigeration flow.

2. Single circuit condenser shown.

3. Unit piping entrance varies by unit and may be through the top of the unit.

4. Indoor unit may be Liebert DS, PDX, or CRV and is shown for reference only.

5. The bottom of the coil must be less than 15' (4.6m) below the elevation of the TXV inside the indoor unit.

Contact your Vertiv sales representative for additional information.

Field piping

Internal TXV Height H in. (mm)

PDX Downflow 44 (1118)

PDX Upflow 20 (508)

DS035-105 Downflow/Upflow 43 (1092)

CRV - CR019 45 (1143)

CRV - CR020/CR035 27 (686)

MC Condenser without Receiver

Document generated 06 April 2022 05:09 PM (EST).

DPN003954

Page :4/4

LIEBERT MC CONDENSER

F or m N o.

: D

P N

_R

E V

AIR COOLED PIPING SCHEMATIC

Notes:

1. Pitch horizontal hot gas piping at a minimum of 1/2" per 10 feet (42mm per 10m) so that gravity will aid in moving oil in the direction of the refrigeration flow.

2. Single circuit condenser shown.

3. Unit piping entrance varies by unit and may be through the top of the unit.

4. Indoor unit may be Liebert DS, PDX, or CRV and is shown for reference only while demonstrating proper pipe and unit/condenser height differences.

5. The bottom of the condenser coil must be less than 15 feet (4.6m) below the location of the TXV in the indoor unit, otherwise extended legs or a field piped subcooler needs to be utilized.

Contact your Vertiv sales representative for additional information.

6. This Configuration is not valid for Liebert MC with Lee-Temp or unheated receiver.

Indoor Unit

Field piping

Gas

Liquid

MC Condenser without receiver

CONDENSER BELOW INDOOR UNIT

Liquid

Gas

Gas

MC Condenser with Receiver 6

H

15' 4.6m

Maximum Vertical Drop

TXV location5

Internal TXV Height H in. (mm)

PDX Downflow 44 (1118)

PDX Upflow 20 (508)

DS035-105 Downflow/Upflow 43 (1092)

CRV - CR019 45 (1143)

CRV - CR020/CR035 27 (686)

Document generated 06 April 2022 05:09 PM (EST).

REV : 7

REV DATE : 12/17

DPN002188

Page :1 /1

F or m N o.

: D

P N

_R

E V

TYPICAL PIPING SCHEMATIC FOR AIR-COOLED DX SYSTEMS

LIEBERT MC CONDENSER

Field installed relief valve(s) required for 50Hz EU CE units.

Check Valve Relief Valve Service

Valve Head Pressure Control Valve

Service Valve

External Equalizer

Trap at base of risers over 5ft. (1.5m)

Check Valve

LEE-TEMP RECEIVER

HOT GAS DISCHARGE

LIQUID RETURN

EVAPORATOR

COIL

LIQUID

SUCTION

COMPRESSOR

Expansion Valve

Solenoid Valve

Sight Glass

Filter Drier LIQUID LINE

Check Valve

CONDENSER COIL

(Includes factory provided inverted trap. No external trap required)

CONDENSER COIL

(Includes factory provided inverted trap. No external trap required)

For rises over 25ft. (7.6m), trap every 20ft. (6m) or evenly divided

HOT GAS DISCHARGE

FIELD PIPING

FACTORY REFRIGERANT PIPING SERVICE/SCHRADER (ACCESS) CONNECTION NO VALVE CORE

SERVICE/SCHRADER (ACCESS) CONNECTION WITH VALVE CORE

Notes:

1. Single refrigeration circuit shown for clarity.

2. Schematic representation shown. Do not use for specific connection locations.

3. Components are not supplied by Liebert, but are required for proper operation and maintenance.

4. Traps must be installed and horizontal lines pitched to ensure proper oil return and to reduce liquid floodback to compressor. Pitch horizontal hot gas piping at a minimum of 1/2" per 10 feet (42mm per 10m) so that gravity will aid in moving oil in the direction of the refrigeration flow.

5. Do not islolate any refrigeration circuits from over pressurization protection.

Service Valve

Sensing Bulb

LIEBERT MC CONDENSER

LIEBERT MC CONDENSER WITH LEE-TEMP OPTION

Pressure Transducer

Pressure Transducer

INTERCONNECTING

PIPING

Optional Field Installed Fusible Plug

Document generated 06 April 2022 05:09 PM (EST).

Adam.Lensegrav Line

Adam.Lensegrav Line

Adam.Lensegrav Cross-Out

REV DATE : 2/17

DPN002169

Page :1 /3

PREMIUM EFFICIENCY CONTROL

F or m N o.

: D

P N

_R

E V

ELECTRICAL FIELD CONNECTIONS

LIEBERT MC CONDENSER

FAN 2

FAN 1

SH

NOTICE !

THIS HOLE FOR FIELD

SUPPLIED EXTRA LOW

VOLTAGE CONTROL WIRING

KEY ELECTRICAL DETAILS:

1) Three phase electrical service – Terminals are on top of disconnect switch for one and two fan units. Terminals are on bottom of disconnect switch for three and four fan units. Three phase service not by Liebert. See note 5.

2) Earth ground – Field lug terminal for earth ground connection. Ground terminal strip for fan motor ground connection.

3) Primary high voltage entrance – Two 7/8” (22.2mm) diameter knockouts located at the bottom of the enclosure.

4) SPD field connection terminals – High voltage surge protective device (SPD) terminals. SPD is an optional device.

Document generated 06 April 2022 05:09 PM (EST).

Adam.Lensegrav Line

Adam.Lensegrav Line

Adam.Lensegrav Cross-Out

DPN002169

Page :2 /3

PREMIUM EFFICIENCY CONTROL

F or m N o.

: D

P N

_R

E V

ELECTRICAL FIELD CONNECTIONS

LIEBERT MC CONDENSER

5) CANbus terminal connections – Field terminals for CANbus cable connection.

• 5A is the CANbus connectors.

o TB49-1 is the input terminal for CANbus high.

o TB49-3 is the input terminal for CANbus low.

o TB50-1 is output terminal for CANbus high.

o TB50-3 is the output terminal for CANbus low.

o…

This is the start of the file's text. The full file is on GovTribe.