The provided file is a technical cut sheet for the Liebert PDX Air Cooled DX Cooling Unit, specifically for the PX018 model. The document details the standard features of the precision cooling unit, which include:
Key technical specifications include a digital scroll compressor with R-410A refrigerant and variable capacity operation from 20-100%, an electronically commutated (EC) fan with backward curved blades, and a cabinet constructed of 20 gauge steel powder-coated in RAL7021 black gray matte color. The unit features a Liebert iCOM control system with a 7-inch high-definition capacitive color touchscreen that provides system information, allows parameter adjustments, and offers unit-to-unit communication capabilities. Additional features include a MERV8 filter, a unit disconnect switch, remote shutdown terminal, and comprehensive connectivity options for building management systems including Ethernet, RS-485, Modbus, BACnet, SNMP, and SMS messaging.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C26025Q0748.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REV : 5
REV DATE : 9/18
DPN003380
Page :1 /2
AIR COOLED
Fo rm
N o.
: D P
N
_R E
V
STANDARD FEATURES
LIEBERT PDX
DX COOLING COIL The evaporator coil is constructed of copper tubes and hydrophilic coated aluminum fins. A stainless steel condensate drain pan is provided.
REFRIGERATION SYSTEM Single refrigeration circuit shall include a liquid line filter drier, a refrigerant sight glass with moisture indicator, an expansion valve, pressure safety switch, and a liquid line solenoid valve.
DIGITAL SCROLL COMPRESSOR The compressor is an R-410A scroll-type with variable capacity operation from 20-100%.
Compressor solenoid valve unloads the compressor to provide variable capacity operation. The compressor has a suction gas cooled motor, EPDM vibration isolators, internal thermal overloads, automatic reset high pressure switch with lockout after three failure occurrences, RotoLock service valves, low pressure transducer and crankcase heater.
ELECTRONICALLY COMMUTATED (EC) FAN is plug type, integral direct driven fan with backward curved blades and Electronically Commutated DC motor; commonly referred to as an EC fan. The fan speed shall be variable and automatically regulated by the Liebert iCOM® control through all modes of operation. The impeller shall be made of aluminum and dynamically balanced. The fan shall be located to draw air through the coil to ensure even air distribution and maximum coil performance.
CABINET The exterior panels are 20 gauge steel and powder coated with RAL7021 black gray matte color paint to protect against corrosion. Exterior panels are insulated with ½” (sides) or 1”(front and rear), 1-1/2 lb insulation. Front and side panels have captive, 1/4 turn fasteners to allow quick panel removal. The cabinet is designed so that all components are serviceable and removable using the front and right sides of the unit.
FILTER - The filter shall be deep-pleated, 2 in (51mm) thick with a MERV8 rating efficiency based on ASHRAE 52.2-2007.
LIEBERT iCOM CONTROL SYSTEM The Liebert PDX is controlled by the iCOM Control System. A 7-inch, high definition, capacitive, color touchscreen presents system information and allows parameters to be viewed and adjusted. The controls shall be menu driven and shall display user menus for active alarms, event log, graphic data, unit view/status overview (including the monitoring of room conditions, operational status in percentage of each function, date and time), total run hours, various sensors, display setup and service contacts. It features a 3-level password protection system. Unit–to-Unit communication capability with other Liebert PDX units is included as standard.
BASE-COMMS FOR BMS CONNECTIVITY The Liebert iCOM controller provides one Ethernet Port and one RS-485 Port dedicated for BMS connectivity. Provides ground fault isolated RS-485 Modbus, BACnet IP & Modbus IP network connectivity to Building Management Systems for unit monitoring and management. Also, provides ground fault isolated 10/100 baseT Ethernet connectivity for unit monitoring and management. The supported management interfaces include: SNMP v1/v2c/v3 for Network Management Systems, HTTP for web page viewing, SMTP for e-mail, and SMS for mobile messaging. The iCOM controller can support dual IP on one network and one 485 protocol simultaneously.
UNIT DISCONNECT SWITCH A “Locking-Type” fused disconnect switch is available. The “Locking-Type” consists of a main unit switch operational from the outside of the unit. Access to the high voltage electric panel can be obtained only with the switch in the “off” position. The disconnect has main fuses within the disconnect.
65,000 AMP SHORT CIRCUIT CURRENT RATING (SCCR) The 60Hz electrical panel provides 65kA SCCR.
REMOTE SHUTDOWN TERMINAL The remote shutdown terminal shall provide the customer with a location to remotely shut down the unit, complying with the National Fire Code.
REV : 5
REV DATE : 9/18
DPN003380
Page :2 /2
AIR COOLED
Fo rm
N o.
: D P
N
_R E
V
STANDARD FEATURES
LIEBERT PDX
COMMON ALARM CONTACT The common alarm contacts shall provide the customer with a set of normally open contacts for remote indication of unit alarms. Four alarm contacts shall be provided for units without a condensate pump. Three alarm contacts shall be provided for units with a condensate pump.
SUPPLY AIR SENSOR The supply air temperature sensor shall provide real-time, direct feedback to the downflow raised floor cooling unit to provide a consistent supply air temperature by adjusting the compressor capacity or the chilled water valve accordingly to maintain set point. The supply air temperature sensor will provide real-time, monitoring of discharge air temperature on all other units.
INFRARED HUMIDIFIER High intensity infrared quartz lamps over a stainless steel humidifier pan. An automatic water supply system maintains water level in the pan and a timed flush system greatly reduces mineral precipitation, and is field adjustable to change the cycle time. A 1" (25mm) air-gap within the water supply piping assembly shall prevent backflow of the humidifier supply water.
ELECTRIC REHEAT Electric low watt density 304/304 stainless steel fin tubular electric reheat elements provide reheat to control room dry bulb temperature.
REV : 3
REV DATE : 8/18
DPN003381
Page :1 /2
AIR COOLED
F or m N o.
: D
P N
_R
E V
OPTIONAL FEATURES
LIEBERT PDX
(Refer to specification sheet for options supplied)
DUAL-FLOAT CONDENSATE PUMP has a capacity of 5 GPM (18.9 l/min) at 40ft (12.2 m) head. Pump is complete with integral primary and secondary float switches, pump, motor assembly and reservoir. The secondary float shall send a signal to the local alarm and shut down the unit upon high water condition. The condensate pump shall be factory-installed on upflow units and field-installed on downflow units.
DIGITAL SCROLL COMPRESSOR SOUND JACKET The compressor sound jacket shall reduce the level of sound emitted from the compressor. It shall consist of a 3/8 inch closed cell polymeric 4.5 - 8.5 lb/ft3 density jacket that encloses the compressor.
SMOKE SENSOR - The Smoke Sensor samples the return air and shuts down the unit upon activation and sends visual and audible alarms. Dry contacts are available for a remote customer alarm. This smoke sensor is not intended to function as or replace any room smoke detection system that may be required by local or national codes.
Adam.Lensegrav Cross-Out
Adam.Lensegrav Cross-Out
REV DATE : 8/18
DPN003381
Page :2 /2
F or m N o.
: D
P N
_R
E V
OPTIONAL FEATURES
LIEBERT PDX
AIR COOLED
UPFLOW UNIT PLENUM(S) are available in various configurations for upflow units: ducted air discharge with solid panels or 2 way, 3 way, or 4 way air discharge with grilles. Each plenum is constructed of 20 gauge steel with 1” (25.4mm), 1 1/2 Ib. (.68kg) insulation and is powder-coated with RAL7021 black gray matte color paint to protect against corrosion. The ducted air discharge plenum is available in 18
in. (457mm), 24 in. (610mm), 30 in. (762mm), 36 in. (914mm), 42 in. (1067mm), or 48 in. (1219mm), and the air discharge with grilles plenum is 18 in. (457mm) high.
LIQUI-TECT SENSOR - The water sensor is a hermetically sealed solid state device with no moving parts. When the sensor detects the presence of moisture, the alarm system is activated.
Document generated 06 April 2022 05:09 PM (EST).
Adam.Lensegrav Cross-Out
REV : 8
REV DATE : 12/17
DPN002929
Page :1 /1
AIR COOLED MODELS WITH TXV
F or m N o.
: D
P N
_R
E V
PIPING SCHEMATIC
LIEBERT PDX
Filter DrierSight Glass
SUCTION
LIQUID
COMPRESSOR
Thermal Expansion Valve
EVAPORATOR
COIL
Check Valve
CONDENSER COIL
FACTORY REFRIGERANT PIPING
FIELD PIPING
For rises over 25ft. (7.6m), trap every 20ft. (6m) or evenly divided
SERVICE / SCHRADER (ACCESS) CONNECTION NO VALVE CORE
LIQUID RETURN
HOT GAS DISCHARGE
Sensing Bulb
External Equalizer
Service Valve
Service Valve
SERVICE / SCHRADER (ACCESS) CONNECTION WITH VALVE CORE
LEE-TEMP RECEIVER
Service Valve
Relief Valve Check Valve
Head Pressure Control Valve
LIQUID RETURN
Digital Solenoid Valve
Optional Field Installed Fusible Plug
HOT GAS
DISCHARGE
LIEBERT MC CONDENSER
LIEBERT PDX UNIT
LIEBERT MC CONDENSER
WITH LEE-TEMP RECEIVER
LIQUID
LIQUID
HOT GAS DISCHARGE
Solenoid Valve
CONDENSER COIL
Includes factory provided inverted trap. No external trap required.
Includes factory provided inverted trap. No external trap required.
Notes:
1. Schematic representation shown. Do not use for specific connection locations.
2. Components are not supplied by Liebert but are required for proper circuit operation and maintenance.
3. Traps must be installed and horizontal lines pitched to ensure proper oil return and to reduce liquid floodback to compressor. Pitch horizontal hot gas piping at a minimum of 1/2" per 10 feet (42mm per 10m) so that gravity will aid in moving oil in the direction of the refrigeration flow.
4. Do not isolate any refrigerant circuits from over pressurization protection.
Trap at base of risers over 5ft. (1.5m)
INTERCONNECTING
PIPING
Pressure Transducer
Adam.Lensegrav Line
Adam.Lensegrav Line
REV : 7
REV DATE : 4/18
DPN002937
Page :1 /1
UPFLOW MODELS
Fo rm
N o.
: D P
N
_R E
V
CABINET DIMENSIONAL DATA
LIEBERT PDX & PCW
Note: Unit with front return shown. Bottom return with rear return floorstand is also available (24" height rear return floorstand is required for use with bottom return unit).
Liebert PDX Model No. PX011 PX018-023 PX029
Air Cooled 600 (272) 670 (304) 700 (317)
Air Cooled w/dual cool 700 (317) 750 (340) 790 (358)
Water/Glycol 620 (281) 690 (313) 720 (327)
GLYCOOL™ or Water/Glycol w/dual cool 720 (327) 770 (349) 810 (367)
Liebert PCW Model No. PW011 PW017 PW029
Chilled Water 575 (260) 600 (272) 650 (294)
DRY WEIGHT lb (kg) APPROXIMATE
Top View
Front View
1 1/4" 32mm
30 1/4" 768mm
Duct Flange
32 5/8" 827mm
Duct Flange
34 1/2" 876mm
77 1/2" 1970mm
3/4" 19mm
34" 864mm
24" 610mm
Shaded area indicates a recommended minimum clearance be provided for component access.
Recommended Clearance for unit installation and for servicing these components if equipped:
Reheat, Filter Clog Switch, Econ-O-Coil Valve, or Gravity Drain Connections.
5 5/8" 143mm
34 3/8" 874mm
Adam.Lensegrav Cross-Out
Adam.Lensegrav Cross-Out
Adam.Lensegrav Cross-Out
Adam.Lensegrav Cross-Out
Adam.Lensegrav Rectangle
Adam.Lensegrav Rectangle
REV : 10
REV DATE : 5/19
DPN002939
Page :1 /1
UPFLOW AIR COOLED MODELS
Fo rm
N o.
: D P
N
_R E
V
PRIMARY CONNECTION LOCATIONS
LIEBERT PDX
FRONT VIEW
PX011 PX018, PX023 PX029
L1 LIQUID LINE SYSTEM 25-5/8 (651) 3/8 1/2 5/8
G1 HOT GAS DISCHARGE 27-7/8 (708) 1/2 5/8 7/8
CD CONDENSATE DRAIN N/A 16-5/8 (422) 3-1/8 (89)
CDP CONDENSATE DRAIN WITH PUMP 3-1/4 (83) 5-7/8 (149)
HUM HUMIDIFIER SUPPLY LINE 29-1/2 (749) 26 (660)
ECS ECON-O-COIL SUPPLY 3-1/4 (83)
ECR ECON-O-COIL RETURN 8-1/4(210)
E1 ELECTRICAL CONN. (HIGH VOLT) 30 (762)
E2 ELECTRICAL CONN. (HIGH VOLT) 27-3/4 (705)
LV1 ELECTRICAL CONN. (LOW VOLT) 27-1/2 (699)
LV2 ELECTRICAL CONN. (LOW VOLT) 26-1/2 (673)
7/8, 1-3/8, 1-3/4
7/8
Z in. (mm)
N/A
N/A
1-1/8
CONNECTION SIZE in.
3/4 NPT FEMALE
1/2
1/4
POINT DESCRIPTION X in. (mm) Y in. (mm)
1-1/2 (38)
31-1/4 (794)
5-1/8 (130)
4-1/4 (108)
Notes:
1. Drawing not to scale. All dimensions from rear corner of unit including panels and have a tolerance of ± 1/2" (13mm).
2. Field pitch Condensate drain line a minimum of 1/8" (3mm) per 12" (305mm) All units contain a factory installed condensate trap. Do not trap external to the unit.
Drain line may contain boiling water. Select appropriate drain system materials The drain line must comply with local codes.
3. Supplied on Dual Cooling Systems only.
4. Unit with front return shown. Bottom return with rear return floorstand also available.
5. All refrigerant & water piping connections are O.D. Copper except as noted.
6. Concentric knockouts to be used based on field supplied conduit diameter.
LV1
ECS
LV2
X
Y
O
TOP VIEW
FRONT OF UNIT
L1
E1 E2
HUM
CDP
RIGHT SIDE VIEW
G1
ECR
ECSECR
L1G1
CD 25 5/8"
143mm
Document generated 06 April 2022 05:09 PM (EST).
Adam.Lensegrav Cross-Out
Adam.Lensegrav Cross-Out
Adam.Lensegrav Cross-Out
Adam.Lensegrav Cross-Out
Adam.Lensegrav Cross-Out
Adam.Lensegrav Cross-Out
REV : 0
REV DATE : 3/18
DPN004594
Page: 1/3
UPFLOW & DOWNFLOW MODELS
F or m N o.
: D
P N
_R
E V
ELECTRICAL FIELD CONNECTIONS
LIEBERT PDX & PCW
1. High Voltage Entrance. Supplied on top and bottom of electric box. Knockout size Ø1.75in (44.5mm).
2. Low Voltage Entrance. Ø1.375 in. (34.9mm) hole located on bottom of Electric Box.
3. Three phase Electric Service and earth ground. Field supplied.
4. Three phase connection. Electric service connection terminals on disconnect.
5. Factory installed disconnect switch. Fused disconnect switch provided on units.
6. Earth ground connection. Connection terminals for field supplied earth grounding wire.
7. Earth ground bar. Connection terminals with factory ground from each high voltage component for field supplied earth grounding wire.
8. Control and monitoring section of electric box.
9. Remote unit shutdown. Replace existing jumper between terminals 37 & 38 with normally closed switch having a minimum 75VA, 24VAC rating. Use field supplied Class 1 wiring. Two additional contact pairs available as an option (labeled as 37B & 38B, 37C & 38C). Replace existing jumper for appropriate pair as done for 37 & 38.
10. Remote Alarm Device (RAD) Connections. Alarm connections may be factory wired or field wired. See schematic, RAD1- 4, for factory wired alarms. For field wired alarms, use Class 1 wiring to connect normally open contacts between terminals 24 & 50, 24 & 51, 24 & 55, or 24 & 56. Suitable for 24VAC.
11. Smoke detector alarm connections. Field supplied Class 1 wiring to 1 Amp, 24VAC maximum remote alarm circuits.
Factory wired contacts from optional smoke detector are #91-Common, #92-NO, and #93-NC. Optional smoke detector trouble (SDT) connections #80 & # 81.
12. Common alarm connection. Field supplied Class 1 wiring to common alarm terminals 75 & 76 (and optional 94 & 95, and 96 & 97), which are factory connected to normally open contacts, 1 Amp, 24VAC maximum on common alarm relay (R3).
13. Heat rejection connection. Field supplied Class 1 wiring to heat rejection interlock terminals 70 & 71 which are factory connected to normally open compressor side switch (self contained units only) or to GLYCOOL relay K11 (GLYCOOL units only). On Dual Cool units only, connect auxilliary cooling source terminals 72 & 73 to relay K11. See indoor and outdoor electric schematic for more information.
14. Reheat and Humidifier Lockout. Optional emergency power lockout of reheat and/or humidifier: Connections #82 & #83 are provided for remote 24VAC source and Class 1 wiring by others.
15. Main Fan Auxiliary Switch. Optional main fan auxiliary side switch. Terminals located on customer connection terminal block for remote indication that the evaporator fan motor/unit is on. Field to connect 24V maximum, Class 1 wiring to connections #84 & #85.
16. Optional Condensate Alarm (Dual Float Condensate Pump only). Relay terminals located on customer connection terminal block for remote indication. Field supplied Class 1 wiring to connections #88 & #89.
17. Optional Remote Liquitect Indicator. Optional remote liquitect indicator for unit shutdown. Terminals located on customer connection terminal block. Field to connect 24V maximum, Class 1 wiring to connections #58 & #59.
18. Optional Analog Inputs #3 & #4. Customer connection to terminals 41, 42, 43, 44 for analog inputs.
19. Spare Terminals for Optional Devices. Customer connection when optional device is supplied. See unit schematic.
Document generated 06 April 2022 05:09 PM (EST).
Adam.Lensegrav Cross-Out
Adam.Lensegrav Cross-Out
DPN004594
Page: 2/3
UPFLOW & DOWNFLOW MODELS
F or m N o.
: D
P N
_R
E V
ELECTRICAL FIELD CONNECTIONS
LIEBERT PDX & PCW
20. CANbus Connector. Terminal block with terminals 49-1 (CAN-H) and 49-3 (CAN-L) + SH (shield connection).
The terminals are used to connect the CANbus communication cable (provided by others) from the indoor unit to the Liebert MC Condenser.
21. CANbus Cable. CANbus cable provided by others to connect to the outdoor condenser and optional PRE unit.
No special considerations are required when the total external cable connection between the indoor unit and outdoor unit(s) is less than 450FT (137M). For total external cable connections greater than 450FT (137M). For external cable connections greater than 450FT (137M), but less than 800FT (243M) a CANbus isolator is required (Contact Factory).
Cable must have the following specifications:
- Braided shield or foil shield with drain wire
- Shield must be wired to ground at indoor unit
- 22-18AWG stranded tinned copper
- Twisted pair (minimum 4 twists per foot)
- Low Capacitance (15pF/FT or less)
- Must be rated to meet local codes and conditions
- EXAMPLES BELDEN 89207 (PLENUM RATED), OR ALPHA WIRE 6454 CATEGORY 5, 5E, OR HIGHER
22. Do not run in same conduit, raceway, or chase as high voltage wiring.
23. For CANbus network lengths greater than 450FT (137M) call Factory.
OPTIONAL COMMUNICATION CONNECTIONS
24. Unit-To-Unit – Plug 64 is reserved for U2U communication.
25. Site and BMS – Plug 74 and terminal block 3 are reserved for Site and BMS connections. Plug 74 is an eight pin RJ45 for a Cat 5 cable. Terminal block 3 is a two position screw terminal block for use with twisted pair wires. Only one of these connections can be used at a time.
NOTE: Refer to specification sheet for total unit full load amps, wire size amps, and max overcurrent protective device size.
Document generated 06 April 2022 05:09 PM (EST).
DPN004594
Page: 3/3
UPFLOW & DOWNFLOW MODELS
F or m N o.
: D
P N
_R
E V
ELECTRICAL FIELD CONNECTIONS
LIEBERT PDX & PCW
UPFLOW UNIT
38B
38B
37B 38C
37C
37B 38C
37C S
H
S H
49-3 49-1
49-3 49-1
37 37
1 High Voltage Entrance
6 87
DOWNFLOW UNIT
Terminal Block For Customer Connection
2Low Voltage Entrance
24 25
Document generated 06 April 2022 05:09 PM (EST).
Adam.Lensegrav Line
Adam.Lensegrav Line
Adam.Lensegrav Cross-Out
Adam.Lensegrav Cross-Out
DPN004596
Page: 1/1
UPFLOW MODELS
F or m N o.
: D
P N
_R
E V
ELECTRICAL FIELD CONNECTIONS
LIEBERT PDX & PCW
1 Opening for field wiring. Suggested entry point for HV field wiring to unit.
2 Opening for field wiring. Suggested entry point for LV field wiring to unit.
3. Wire tie anchors. Use to secure customer wiring.
Notes:
1. Wire needs to be routed outside Electric Box to Low Voltage knockout on bottom of Electric Box.
REV : 2
REV DATE : 3/20
DPN004350
Page :1 /3
UNIT MOUNTED DISPLAY
Fo rm
N o.
: D P
N
_R E
V
PRODUCT INFORMATION
LIEBERT® iCOM™
The Liebert® iCOM™ display is a 7-inch capacitive, color-touchscreen display in an ergonomic, aesthetically pleasing housing. The display and housing will be viewable while the unit accent panels are open or closed.
The display can be easily detached to view while the panel is open.
Menu Layout- The menus will be broken out into two main menu screens: User screen and Service screen.
The User screen contains the menus to access parameters required for basic unit control and setup.
The Service screen is designed for service personal and provides access to advanced control setup features and diagnostic information.
Password Protection- The display will contain two unique passwords to protect against unauthorized changes.
An auto hide/show feature allows the user to see applicable information based on the login used. These four-digit passwords may be customized according to User preference.
Unit Backup and Restore- The user shall have the ability to create safety copies of important control parameters.
The display has the ability for the user to automatically backup unit configuration settings to internal memory or USB storage drive. Configuration settings may be transferred to another unit for a more streamlined unit startup.
Parameter Search- The display has search fields for efficient navigation and parameter lookup.
Parameter Download- The Liebert iCOM shall enable the user to download a report that lists parameter names, factory default settings, and the user programmed settings in .csv format for remote reference.
Parameter Directory- The Liebert iCOM shall provide a directory that lists all parameters in the control. The list shall provide Line ID numbers, parameter labels, and current parameter values.
DPN004350
Page :2 /3
UNIT MOUNTED DISPLAY
Fo rm
N o.
: D P
N
_R E
V
PRODUCT INFORMATION
LIEBERT® iCOM™
Context Sensitive Help- The display will have an onboard help database. The database will provide context sensitive help to assist with setup and navigation of the menus.
Display Setup- The user has the ability to configure the display information based on the specific user’s preference.
Language, units of measure, screen contrast, home screen layout, back light timer and the hide/show of certain readouts will be configurable through the display.
Additional Readouts- The display has the ability for the user to configure custom widgets on the main screen.
Widget options will include items such as fan speed, call for cooling, call for free cooling, maintenance status, call for hot water reheat, call for electric reheat, call for dehumidification, call for humidification, airflow, static pressure, fluid flow rate and cooling capacity.
Status LEDs- The display will provide the user with the unit’s operating status using an integrated LED.
The LED will indicate if the unit has an active alarm; if the unit has an active alarm that has been acknowledged;
or if the unit is on, off, or in a standby status.
Unit Alarms – All unit alarms are annunciated through both audio and visual cues, clearly displayed on the screen, automatically recorded in the event log, and communicated to monitoring plug connections.
Event Log – The display will automatically store the last 400 unit-only events (messages, warnings, and alarms).
Service Contact Information – The display has the ability to store the local service or sales contact information.
Upgradeable –Display and Control Board software upgrades are performed through a USB connection.
Unit-to-Unit (U2U) Communication – Communication via private Ethernet network allows for advanced control functionality (Teamwork modes, sharing sensor data, Standby Rotation, Lead-Lag, and Cascade operation).
Temperature Control- Precision temperature control is maintained while maximizing efficiency based on a user entered setpoint and tolerance.
Various Control Types- Proportional, PI (proportional-integral), or Intelligent control types can be selected for supply or return temperature. These control types have been developed to maximize component life and maintain precise environmental control.
Timers/Sleep Mode- The menus shall allow various customer settings for turning the unit On or Off.
Sensor Calibration- The menus shall allow unit sensors to be calibrated with external sensors.
Maintenance/Wellness Settings- The menus shall allow reporting of potential component problems before they occur.
DPN004350
Page :3 /3
UNIT MOUNTED DISPLAY
Fo rm
N o.
: D P
N
_R E
V
PRODUCT INFORMATION
LIEBERT® iCOM™
Options Setup- The menus shall provide operation settings for the installed components.
Auto Restart- The unit will return to its previous operating status after loss of power. Units can be stagger started to minimize system current draw.
Auxiliary Boards- The menus shall allow setup of optional expansion boards.
Various Sensors: The menus shall allow setup and display of optional custom sensors. The control shall include four customer accessible analog inputs for field-supplied sensors. The analog inputs shall accept a 4 to 20mA signal. The user shall be able to change the input to 0 to 5VDC or 0 to 10VDC. The gains for each analog input shall be programmable from the front display. The analog inputs shall be able to be monitored from the front display.
Diagnostics/Service Mode- The Liebert® iCOM™ control shall be provided with self-diagnostics to aid in troubleshooting. The microcontroller board shall be diagnosed and reported as pass/not pass. Control inputs shall be indicated as On or Off at the front display. Control outputs shall be able to be turned On or Off from the front display without using jumpers or a service terminal. Each control output shall be indicated by an LED on a circuit board.
590-1351-501B/SL-31050_REV2_6-17
LIEBERT® LIQUI-TECT® 410
POINT LEAK-DETECTION SENSOR
Product Specification/Installation Guide
The Liebert Liqui-tect 410 (LT410) provides single-point detection of leaks. The point-detection sensor has two gold-plated sensing probes to prevent corrosion and to provide accurate readings. The LT410 constantly monitors for leaks, internal faults, and power failures and warns of any abnormal conditions. Mounting brackets allow for sensor height adjustment and leveling.
The LT410 is the ideal solution for sensing leaks under a raised computer floor or air conditioning drip pans. Two independent outputs provide added flexibility with the capacity to signal both a local alarm panel and a remote building-management system or external equipment, such as motorized water shut-off valves.
LT410 APPLICATIONS
The LT410 is ideally-suited for:
• Glycol and chilled-water cooling,
• Humidification supply water piping,
• Condensate pumps and drains,
• Unit and ceiling auxillary drip pans,
• Overhead piping troughs.
LOCATIONS/PLACEMENT
The LT410 is an excellent choice for:
• Large-scale network control centers,
• Data centers,
• Server rooms and closets,
• Unattended, remote shelters,
• Mechanical equipment rooms,
• Sensitive areas with overhead piping,
• Industrial process-control rooms.
COMPONENTS OF THE
LIQUI-TECT 410 MODULE
The LT410 consists of a metal enclosure with a hinged top door that provides access to the internal wiring termination. It includes side access through a box connector for installation of the power and contact wiring. The mounting brackets attach to the enclosure with adjustable slots to allow custom setting of the height of the sensing probes.
LIEBERT® LT410 POINT LEAK-DETECTION SENSOR
Product Specification/Installation Guide
SPECIFICATIONS
Power Requirements 24 VAC 100 mA, 50/60 Hz, 3 VA (max.)
Dimensions, W x D x H 6.35 x 2.25 x 4.46 in (161.2 x 57.2 x 113.2 mm)
Weight (assembled) 2.0 lb (0.9 kg)
Metal Enclosure NEMA 1, IP 30
ENVIRONMENTAL CONDITIONS
Operating Temperature 50°F to 104°F (10°C to 40°C)
Operating Humidity 10% to 95% relative humidity (non-condensing)
Operating Altitude 0 to 10,000 ft (0 to 3,048 m)
Output Relay Contact Rating 2 Form-C; 3 A rating at 24 VAC
AGENCY LISTINGS
UL UL916
C-UL C22.2, No. 205-M1983
CE Yes
FCC Compliance 47 CFR, Part 15
TOP VIEW
FRONT VIEW SIDE VIEW5.85”
(148.5mm)
4.46” (113.2mm)
6.35” (161.2mm) 2.25”
(57.2mm)
Form-C relay outputs and power wiring
Adjustable probe height
0.0 - 0.5” (0.0 - 12.7mm)
DIMENSIONS -
TOP, FRONT AND SIDE
LIEBERT® LT410 POINT LEAK-DETECTION SENSOR
Product Specification/Installation Guide
WIRING INTERCONNECTIONS
Circuits are shown in powered, non-alarm state.
NOTE: All power and alarm connections must be Class 2 circuits.
Red Wires Orange Wires Yellow Wires
24 V, AC/DC
@ 0.10A, 50-60 Hz, DC Class 2 Circuit Only
Alarm Contact Rating
24 VAC @ 3A
Class 2 Circuit Only
Alarm Contact Rating
24 VAC @ 3A
Class 2 Circuit Only
PO
W
ER
PO
W
ER
1- N
O
1- N
C
1- C
O M
2- N
O
2- N
C
2- C
O M
Gold-plated Probes
Height adjustable 0-0.5” (0-12.7mm)
PLACEMENT ON SUBFLOOR
UNDER COOLING SUPPORT
EQUIPMENT
To a Liebert environmental unit and an optional monitoring panel
To external power supply or directly from unit (see Power Wiring on page 4)
Leak detection zone (directly beneath unit)
VertivCo.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA © 2017 Vertiv Co. All rights reserved. Vertiv and the Vertiv logo are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice.
590-1351-501B/SL-31050_REV2_6-17
LIEBERT® LT410 POINT LEAK-DETECTION SENSOR
Product Specification/Installation Guide
Liebert DS, DSE, LT410 CW, PDX or Mini-Mate2 (8 ton) Orange Wires Environmental
1-NC
Unit
1-COM 24 (24V)
1-NO 50, 51, 55 or 56
Note: Terminal 50 not available on Mini-Mate2 (8-ton)
Liebert Mini-Mate2, LT410 (1 to 5 ton) Orange Wires Environmental
1-NC
Unit
1-COM TB1-1 (24V)
1-NO TB1-2 or TB1-3
LT410 Liebert CRV Orange Wires Environmental
1-NC
Unit
1-COM 60
1-NO 61
NOTE: In iCOM, use the Service Options menu to add that the Liqui-tect is installed.
LT410 Liebert contact monitor panel Yellow Wires Alarm
2-NC
Panel
2-COM
2-NO
Liebert DS, DSE, CW, PDX, or Mini-Mate2 (8 ton) LT410
TB1 TB1
T5 (24V) Red
G5 (Ground) Red
Location of T5 (24V) connection on main controller board of Liebert unit.
Liebert Mini-Mate2 LT410 (1 to 5 ton)
TB1
From 24V Transformer Red
Red
* Requires external transformer (there are no designated terminal connections on the unit)
Liebert CRV LT410
Medium Control Board TB1
6 Red
4 Red
Transformer LT410
TB1
From 24V Transformer Red
Red
POWER WIRING
The LT410 is rated for 24 VAC, 50/60 Hz, and 0.10 A.
WIRING TO AUXILIARY ALARM PANELS
The LT410 has two Form-C dry contact alarm output contacts: orange wires (1) and yellow wires (2). Each contact is rated for 24 VAC at 3 amp.
TB1
Input Contact (N.O.)
Document generated 06 April 2022 05:09 PM (EST).
Adam.Lensegrav Rectangle
Adam.Lensegrav Rectangle
Adam.Lensegrav Cross-Out
REV : 8
REV DATE : 3/19
DPN002981
Page :1 /1
UPFLOW DISCHARGE GRILLE
Fo rm
N o.
: D P
N
_R E
V
PLENUM DIMENSIONAL DATA
LIEBERT PDX & PCW
WITH GRILLE
FRONT VIEW - UNIT WITH PLENUM
FRONT VIEWS - CHECK ONE (1):
REAR VIEWS - CHECK ONE (1):
LEFT SIDE VIEWS -
CHECK ONE (1): RIGHT SIDE VIEWS -
CHECK ONE (1):
WITH GRILLE
WITHOUT GRILLE
WITH GRILLE
WITHOUT GRILLE
WITHOUT GRILLEWITHOUT GRILLE
WITH GRILLE
SIDE VIEW - UNIT WITH PLENUM
ECS
ECR
E1
E2
LV1
LV2
L1 (PDX)
WS
G1 (PDX)
WR
CDP
HUM
Notes:
1. Two grilles minimum per plenum required.
The nominal grille size is 24" (609mm) x 14" (355mm).
2. All Plenums are shipped flat (non-assembled) and must be assembled on site.
3. Upflow bottom return units are available with required rear return floorstand with filter.
4. Units supplied with Dual Cooling systems only (4 pipe system).
5. Concentric knockouts to be used based on field supplied conduit diameter.
POINT DESCRIPTION X in. (mm) Y in. (mm) KNOCKOUT SIZE, in. (mm)
L1 LIQUID LINE SYSTEM 1
G1 HOT GAS DISCHARGE 1
CDP CONDENSATE DRAIN WITH PUMP 3-1/2 (89) 6-1/8 (155) 3/4 (19)
HUM HUMIDIFIER SUPPLY LINE 29-1/2 (748) 26 (662) 1/2 (13)
WS SUPPLY-CW/WATER/GLYCOL
WR RETURN-CW/WATER/GLYCOL/GLYCOOL™
ECS ECON-O-COIL SUPPLY / GLYCOOL™ SUPPLY 3-1/8 (80)
ECR ECON-O-COIL RETURN 8-1/4 (210)
E1 ELECTRICAL CONN. (HIGH VOLT) 29-1/8 (739) 28-5/8 (728)
E2 ELECTRICAL CONN. (HIGH VOLT) 31-1/4 (793) 27-5/8 (702)
LV1 ELECTRICAL CONN. (LOW VOLT) 32-1/4 (818)
LV2 ELECTRICAL CONN. (LOW VOLT) 30-1/2 (775)
5-1/8 (130)
4-1/4 (109)
5-1/8 (130)
1 (25)
25-5/8 (651)
25-5/8 (651)
25-5/8 (652)
7/8 (23), 1-3/8 (35), 1-3/4 (44)
2 (51)
2 (51)
31 3/4" 807mm
1 3/8" 35mm
77 1/2" 1970mm
18" 458mm
34 1/2" 876mm
REV : 4
REV DATE : 8/19
DPN002155
Page :1 /1
STANDARD & OPTIONAL FEATURES
Fo rm
N o.
: D P
N
_R E
V
PREMIUM EFFICIENCY CONTROL
LIEBERT MC CONDENSER
STANDARD FEATURES
COIL Liebert microchannel coils are all‐aluminum construction. Tubes are created by extruding small parallel refrigerant flow paths into aluminum.
Full‐depth louvered aluminum fins fill spaces between the tubes. Tubes, fins and aluminum headers are oven‐brazed to form a complete refrigerant‐to‐air heat exchange coil. Baffles are used in the headers to separate one coil slab into multiple passes as needed. Coils are factory leak tested at a minimum of 300 PSIG and dehydrated. Copper stub pipes are electric resistance welded to aluminum coils and joints are protected with polyolefin to seal joint from environmental corrosive elements. Hot gas and liquid lines are brazed to the stub pipes with spun closed ends for customer piping connections. Coil pipe assembles are filled and sealed with a nitrogen holding charge for shipment. One coil is used per fan assembly.
FAN/MOTOR ASSEMBLY The fan/motor assembly is complete with external rotor motor, fan blades and fan/finger guard. Fan blades are constructed of stamped aluminum or steel extrusion coated with PP plastic. Fan guards are heavy gauge, close meshed, steel wire, coated with a black corrosion resistant finish. Fan terminal blocks located on the top of the fan guard with IP54 protection class. Fans are factory balanced and tested before shipment.
FAN MOTORS Fan motors are specifically designed for variable speed and have ball bearings. The EC fans provide internal overload protection through the built‐in electronics. Each EC fan motor has built‐in controller and communication module, linked via RS485 communication wire to each fan and the Premium Control Board. This allows each fan to receive and respond to precise fan speed inputs from the Premium control board.
PREMIUM EFFICIENCY FAN CONTROL The Liebert premium efficiency condenser control system is complete with control board, EC fan motor(s),refrigerant‐pressure transducer(s), refrigerant‐temperature thermistor(s), ambient‐temperature thermistor, and motor overload protection in the factory wired control panel. The control board maintains EC fans on the same circuit to the same speed in order to maintain refrigerant head pressure. The control board receives a run signal from the compressor of the indoor unit via field‐supplied low voltage interlock wires and field‐supplied CANbus communication wires from the indoor unit iCOM. The control system provides refrigerant head pressure and system starting for outdoor ambient temperature as low as -30°F (‐35 °C), provided the total temperature design range (from minimum to maximum) is 125°F (70°C) or less.
HOUSING The condenser housing is constructed of bright aluminum sheet and divided into individual fan sections by full width baffles. Internal structural support members, including coil support frame, are galvanized steel for strength and corrosion resistance. Panel doors are provided on two sides of each coil/fan section to provide for coil cleaning. Aluminum legs are provided with rigging holes for hoisting the unit into position.
COMMUNICATION The Premium Efficiency Control communicates with the iCOM control of the indoor Liebert unit using field supplied CANbus wires. The communication link allows for condenser alarm condition communication to iCOM, communication of other measurable items on the condenser, and fan control features to improve efficiency, sound and wintertime operation based on iCOM programming.
UNIT DISCONNECT SWITCH Locking unit disconnect switch is factory installed and wired in attached condenser control section.
OPTIONAL FEATURES
LIEBERT LEE‐TEMP LOW AMBIENT CONTROL Lee‐Temp receiver kits can be added to achieve head pressure control down to minimum ambient temperatures of ‐30 °F (‐34 °C). The premium efficiency fan control when used with the Liebert Lee‐Temp receiver kits runs the fan(s) at lower speeds during cold temperatures saving fan energy.
575V POWER SUPPLY The factory installed condenser option will include a secondary enclosure, a 575V-to-480V, 3 phase, step down transformer, secondary fuses for the transformer, and all wiring between the main and secondary electrical enclosures. Site power connections will be made in the main electrical enclosure and the secondary enclosure will be located on the condenser end opposite of the main electrical enclosure.
E-COAT COIL PROTECTION The aluminum microchannel coil is epoxy-coated for extended coil life in corrosive environments, such as coastal areas.
Factory-applied E-coat using immersion and baking process provides a flexible epoxy-coating to all coil surfaces and ensures complete coil encapsulation. Coil color is black and a factory-applied UV topcoat protects the E-coat from solar UV ray degradation.
REV DATE : 12/16
DPN003436
Page :1 /1
1 FAN (MCS028, MCM040, MCL055)
F or m N o.
: D
P N
_R
E V
CABINET & ANCHOR DIMENSIONAL DATA
LIEBERT MC CONDENSER
With Receiver Option
Note:
1. Liebert recommends a clearance of 36” (915mm) on each side for proper operation and component access.
2. Cross Bracing required for legs longer than
18" (457.2mm). Quantity varies per model & options selected.
3. For PDX w/EEV systems & unheated refrigerant receivers, 6-1/2" (165mm) is 9-1/4" (235mm) and 15-1/4" (387) is not applicable.
A*
A
G
F
Typical all legs
18 (457) 36 (914) 48 (1219) 60 (1524)
DIM "G" 31-5/8 (803) 49-5/8 (1260) 61-5/8 (1565) 73-5/8 (1870)
DIM "H" 39-5/8 (1006) 57-5/8 (1464) 69-5/8 (1768) 81-5/8 (2073)
MCL055
DIM "G" 35-7/8 (911) 53-7/8 (1368) 65-7/8 (1673) 77-7/8 (1978)
DIM "H" 43-5/8 (1108) 61-5/8 (1565) 73-5/8 (1870) 85-5/8 (2175)
LIEBERT
MODEL
NUMBER
MCS028
MCM040
F in. (mm)
(LEG HEIGHT DIMENSIONS)
H
TOP OF
FAN GUARD
575V Option
Left Side of Unit
C D
M L K
Front View (Lee-Temp Shown)
6 1/2" 165mm Ref.
K
Entering Hot Gas and Leaving Liquid Piping
A
DETAIL A
MCS028 50-5/8 (1287) 58-7/8 (1495) 44-1/8 (1120) 42-1/2 (1080) 42-1/2 (1080) 40-7/8 (1038) 35-7/8 (910)
MCM040 57-3/16 (1453) 65-3/8 (1661) 48 (1219) 46-5/16 (1177) 46 (1168) 44-3/8 (1127) 39-5/16 (999)
MCL055 68 (1727) 77 (1956) 56 (1422) 54-3/8 (1381) 55-1/2 (1410) 53-7/8 (1368) 48-3/4 (1238)
K in (mm) L in (mm) M in (mm)D in (mm)C in (mm)
LIEBERT
MODEL
NUMBER
A in (mm) A* in (mm)
(575V ONLY)
1 7/8" 48mm Typ.
3 5/8" 93mm Typ.13/16"
21mm Typ.
7" 178mm
Typ.
1/2" (13mm) X 1" (25mm) Obround Typ.
Main Electric
Box End
575V Option
Anchor Plan
15 1/4" 387mm
Document generated 06 April 2022 05:09 PM (EST).
Adam.Lensegrav Cross-Out
Adam.Lensegrav Cross-Out
Adam.Lensegrav Cross-Out
Adam.Lensegrav Cross-Out
Adam.Lensegrav Cross-Out
Adam.Lensegrav Cross-Out
Adam.Lensegrav Line
Adam.Lensegrav Line
Adam.Lensegrav Line
Adam.Lensegrav Line
Adam.Lensegrav Line
Adam.Lensegrav Line
Adam.Lensegrav Line
Adam.Lensegrav Line
Adam.Lensegrav Rectangle
Adam.Lensegrav Rectangle
Adam.Lensegrav Rectangle
Adam.Lensegrav Cross-Out
Adam.Lensegrav Cross-Out
Adam.Lensegrav Cross-Out
Adam.Lensegrav Cross-Out
Adam.Lensegrav Cross-Out
REV DATE : 4/18
DPN003034
Page :1 /1
F or m N o.
: D
P N
_R
E V
CONDENSER AND OPTION WEIGHT DATA, lb(kg)
LIEBERT MC CONDENSER
Total weight is the sum of 'Condenser' + ('PDX-EEV Receiver' or 'Lee-Temp' or 'DSE Receiver 050/080/085' or 'DSE Receiver
125/150/165')'+'Coated Coil' + '575V Transformer'.+ 'Seismic/Wind Bracing'
MCS028 MCS056 MCM040 MCM160
1 2 1 1 2 2
18" Leg 154 ( 70) 270 ( 122) 231 ( 105) 441 ( 200) 441 ( 200) 860 ( 390)
36" Leg 286 ( 130) 419 ( 190) 363 ( 165) 590 ( 268) 590 ( 268) 1066 ( 484)
48" Leg 318 ( 144) 451 ( 205) 395 ( 179) 622 ( 282) 622 ( 282) 1114 ( 505)
60" Leg 349 ( 158) 482 ( 219) 426 ( 193) 653 ( 296) 653 ( 296) 1160 ( 526)
45 ( 20) 45 ( 20) 45 ( 20)
55 ( 25) 110 ( 50) 55 ( 25) 100 ( 45) 110 ( 50) 220 ( 100)
45 (20) 90 (41)
92 (42) 184 ( 83)
55 ( 25) 65 ( 29) 60 ( 27) 70 ( 32) 70 ( 32) 80 ( 36)
4 ( 2) 8 ( 4) 5 ( 2) 10 ( 5) 10 ( 5) 20 ( 9)
40 ( 18) 40 ( 18) 40 ( 18) 40 ( 18) 40 ( 18) 57 ( 26)
Additional Weight for Options
Refrigerant Circuits
Size Small (MCS) Medium (MCM)
MCM080Condenser Model
PDX-EEV Receiver
Condenser Dry
Weight
Lee-Temp
DSE Receiver DA050/080/085
DSE Receiver DA125/150/165
Seismic/Wind Bracing 18" legs
Coated Coil
575V Transformer
MCL055 MCL165
1 1 2 1 1 2
18" Leg 344 ( 156) 602 ( 273) 602 ( 273) 891 ( 404) 1186 ( 538) 1186 ( 538)
36" Leg 486 ( 220) 766 ( 347) 766 ( 347) 1136 ( 515) 1453 ( 659) 1453 ( 659)
48" Leg 518 ( 235) 798 ( 362) 798 ( 362) 1184 ( 537) 1501 ( 681) 1501 ( 681)
60" Leg 549 ( 249) 829 ( 376) 829 ( 376) 1230 ( 558) 1547 ( 702) 1547 ( 702)
45 ( 20)
60 ( 27) 115 ( 52) 120 ( 54) 175 ( 79) 215 ( 98) 240 ( 109)
45 ( 20) 90 ( 41) 45 (20) 45 ( 20) 90 ( 41)
94 ( 43) 94 ( 43) 94 ( 43) 188 ( 85)
67 ( 30) 77 ( 35) 77 ( 35) 118 ( 54) 118 ( 54) 118 ( 54)
8 ( 4) 16 ( 7) 16 ( 7) 24 ( 11) 32 ( 15) 32 ( 15)
40 ( 18) 40 ( 18) 41 ( 19) 57 ( 26) 57 ( 26) 57 ( 26)
575V Transformer
Coated Coil
Seismic/Wind Bracing 18" legs
Size Large (MCL)
Condenser Model MCL110 MCL220
Refrigerant Circuits
Condenser Dry weight
PDX-EEV Receiver
Lee-Temp
DSE Receiver DA050/080/085
DSE Receiver DA125/150/165
Additional Weight for Options
Document generated 06 April 2022 05:09 PM (EST).
Adam.Lensegrav Rectangle
Adam.Lensegrav Line
Line
DETAIL A
REV DATE : 12/16
DPN002166
Page :1 /1
SINGLE CIRCUIT 1 FAN, 2 FAN, 3 FAN & 4 FAN UNITS
F or m N o.
: D
P N
_R
E V
PIPING DIMENSIONAL DATA
LIEBERT MC CONDENSER
VERTICAL
HORIZONTAL
LEAVING LIQUID
LINE
ENTERING HOT
GAS LINE
OPTIONAL FUSIBLE PLUG SERVICE KIT TO BE BRAZED INTO THE LIQUID LINE(S) IN
EITHER THE VERTICAL OR HORIZONTAL POSITION. (WHERE REQUIRED)
(VERTICAL POSITION IS PREFERRED, HORIZONTAL POSITION IS OPTIONAL.)
HOT GAS LINE LIQUID LINE
MCS 028 1 1 7/8 5/8
MCM 040 1 1 7/8 5/8
MCM 080 2 1 1-1/8 7/8
MCL 055 1 1 1-1/8 7/8
MCL 110 2 1 1-3/8 1-1/8
MCL 165 3 1 1-3/8 1-1/8
MCL 220 4 1 1-5/8 1-3/8
CONDENSER
CIRCUITS
CONNECTION SIZES, OD, IN
MODEL NO.
NUMBER
OF FANS
FIELD PIPING
COVER*
* SHIPPING COVER IS NOT NECESSARY FOR PROPER CONDENSER OPERATION AND
MAY BE RECYCLED IF FIELD PIPING INTERFERES WITH PROPER REATTACHMENT.
VERTICAL
MCS028 ONLY
HORIZONTAL
LEAVING LIQUID
LINE
ENTERING HOT GAS LINE
INVERTED TRAPS
ARE FACTORY PROVIDED
INSIDE CONDENSER
Document generated 06 April 2022 05:09 PM (EST).
Adam.Lensegrav Line
Adam.Lensegrav Line
Adam.Lensegrav Line
Adam.Lensegrav Line
Adam.Lensegrav Line
Adam.Lensegrav Line
Adam.Lensegrav Cross-Out
Adam.Lensegrav Cross-Out
Adam.Lensegrav Cross-Out
Adam.Lensegrav Cross-Out
Adam.Lensegrav Rectangle
REV : 14
REV DATE : 2/20
DPN000788
Page :1 /2
Fo rm
N o.
: D
PN
_R
EV
RECOMMENDED REFRIGERANT LINE SIZES CU, OD
LIEBERT AIR COOLED SYSTEMS
Indoor Model Equivalent Length 50 ft (15m) 100 ft (30m) 150 ft (45m) 300 ft (91m) 450ft (137m) Hot Gas Line, in. 3/4 3/4 3/4 7/8 Liquid Line, in. 5/8 5/8 5/8 3/4
Hot Gas Line, in. 7/8 7/8 7/8 1-1/8 Liquid Line, in. 3/4 3/4 3/4 7/8
Hot Gas Line, in. 1/2 5/8 5/8 5/8 Liquid Line, in. 3/8 1/2 1/2 1/2
Hot Gas Line, in. 5/8 5/8 5/8 3/4 Liquid Line, in. 1/2 1/2 1/2 5/8
Hot Gas Line, in. 3/4 3/4 3/4 7/8 Liquid Line, in. 5/8 5/8 5/8 5/8
Hot Gas Line, in. 7/8 7/8 7/8 1-1/8 Liquid Line, in. 5/8 5/8 5/8 3/4
Hot Gas Line, in. 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 Liquid Line, in. 7/8 7/8 7/8 7/8 7/8
Hot Gas Line, in. 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8 Liquid Line, in. 7/8 7/8 7/8 7/8 7/8
Hot Gas Line, in. 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8 Liquid Line, in. 7/8 1-1/8 1-1/8 1-1/8 1-1/8
Hot Gas Line, in. 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8 Liquid Line, in. 7/8 1-1/8 1-1/8 1-1/8 1-1/8
Hot Gas Line, in. 1-5/8 1-5/8 1-5/8 1-5/8 Liquid Line, in. 1-3/8 1-3/8 1-3/8 1-3/8
DA165
System Fluid : R-410A
CR035RA
PX018
PX023
PX029
DA050 / DA080/
DA085
Any Compressor Type
CR019RA/ CR020RA
DA125
DA150
PX011
DA250 / DA265
LIEBERT AIR-COOLED SYSTEMS USING R-410A
Notes:
1. Consult factory for proper line sizing for runs longer than maximum equivalent length shown in table.
2. Must downsize vertical riser one trade size (1-1/8” to 7/8” or 7/8” to 3/4” or 3/4" to 5/8" or 5/8" to 1/2").
3. Consult factory when actual pipe length between condenser/Liebert EconoPhase and Liebert DSE unit will exceed 300 ft (91 m).
4. Liebert DA250-265 unit can be extended to max 200ft (61m) linear or 300ft. (91m) equivalent.
Indoor Model Equivalent Length 50 ft (15m) 75 ft (23m) 100 ft (30m) 125 ft (38m) 150 ft (45m) Suction Line, in. 7/8 7/8 7/8 7/8 7/8 Liquid Line, in. 1/2 1/2 1/2 1/2 1/2
Suction Line, in. 7/8 1-1/8 1-1/8 1-1/8 1-1/8 Liquid Line, in. 1/2 1/2 5/8 5/8 5/8
Suction Line, in. 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 Liquid Line, in. 1/2 5/8 5/8 5/8 5/8
System Fluid: R-410A Digital Scroll Models
MT060
MT048
MT036
2 2 2
2 2 2 2
Document generated 06 April 2022 05:09 PM (EST).
Adam.Lensegrav Rectangle
Adam.Lensegrav Line
Line
REV DATE : 9/19
DPN003954
Page :1/4
LIEBERT MC CONDENSER
F or m N o.
: D
P N
_R
E V
AIR COOLED PIPING SCHEMATIC
Indoor Unit
Notes:
1. Pitch horizontal hot gas piping at a minimum of 1/2" per 10 feet (42mm per 10m) so that gravity will aid in moving oil in the direction of the refrigeration flow.
2. Single circuit condenser shown.
3. Unit piping entrance varies by unit and may be through the top of the unit.
4. Indoor unit may be Liebert DS, PDX, or CRV and is shown for reference only while demonstrating proper pipe and unit/condenser height differences.
5. The bottom of the condenser coil or bottom of the receiver (if equipped) must be higher than the elevation of the TXV inside the indoor unit. The vertical height must not exceed 60 feet (18.3m).
6. Trapping must be practiced at bottom of riser with any rise over 5 feet high. If rise exceeds 25 feet (7.5m), then a trap is required in 20 foot (6 m) increments or evenly divided
Field piping
Gas
Gas
Liquid
Liquid
Gas
MC Condenser without Receiver
Liquid
Gas
CONDENSER ABOVE INDOOR UNIT
Liquid
MC Condenser with Receiver
H
60' 18.3m
Maximum Vertical Rise
7.6" 194mm
Internal TXV Height H in. (mm)
PDX Downflow 44 (1118)
PDX Upflow 20 (508)
DS035-105 Downflow/Upflow 43 (1092)
CRV - CR019 45 (1143)
CRV - CR020/CR035 27 (686)
TXV location
(Piping to Condenser & Receiver not shown for clarity)
(Piping to Condenser not shown for clarity)
Document generated 06 April 2022 05:09 PM (EST).
Adam.Lensegrav Line
Adam.Lensegrav Line
Rectangle
DPN003954
Page :3/4
LIEBERT MC CONDENSER
F or m N o.
: D
P N
_R
E V
AIR COOLED PIPING SCHEMATIC
Indoor Unit
H
TXV location
Liquid
Gas
CONDENSER AND INDOOR UNIT AT SAME LEVEL
Notes:
1. Pitch horizontal hot gas piping at a minimum of 1/2" per 10 feet (42mm per 10m) so that gravity will aid in moving oil in the direction of the refrigeration flow.
2. Single circuit condenser shown.
3. Unit piping entrance varies by unit and may be through the top of the unit.
4. Indoor unit may be Liebert DS, PDX, or CRV and is shown for reference only.
5. The bottom of the coil must be less than 15' (4.6m) below the elevation of the TXV inside the indoor unit.
Contact your Vertiv sales representative for additional information.
Field piping
Internal TXV Height H in. (mm)
PDX Downflow 44 (1118)
PDX Upflow 20 (508)
DS035-105 Downflow/Upflow 43 (1092)
CRV - CR019 45 (1143)
CRV - CR020/CR035 27 (686)
MC Condenser without Receiver
Document generated 06 April 2022 05:09 PM (EST).
DPN003954
Page :4/4
LIEBERT MC CONDENSER
F or m N o.
: D
P N
_R
E V
AIR COOLED PIPING SCHEMATIC
Notes:
1. Pitch horizontal hot gas piping at a minimum of 1/2" per 10 feet (42mm per 10m) so that gravity will aid in moving oil in the direction of the refrigeration flow.
2. Single circuit condenser shown.
3. Unit piping entrance varies by unit and may be through the top of the unit.
4. Indoor unit may be Liebert DS, PDX, or CRV and is shown for reference only while demonstrating proper pipe and unit/condenser height differences.
5. The bottom of the condenser coil must be less than 15 feet (4.6m) below the location of the TXV in the indoor unit, otherwise extended legs or a field piped subcooler needs to be utilized.
Contact your Vertiv sales representative for additional information.
6. This Configuration is not valid for Liebert MC with Lee-Temp or unheated receiver.
Indoor Unit
Field piping
Gas
Liquid
MC Condenser without receiver
CONDENSER BELOW INDOOR UNIT
Liquid
Gas
Gas
MC Condenser with Receiver 6
H
15' 4.6m
Maximum Vertical Drop
TXV location5
Internal TXV Height H in. (mm)
PDX Downflow 44 (1118)
PDX Upflow 20 (508)
DS035-105 Downflow/Upflow 43 (1092)
CRV - CR019 45 (1143)
CRV - CR020/CR035 27 (686)
Document generated 06 April 2022 05:09 PM (EST).
REV : 7
REV DATE : 12/17
DPN002188
Page :1 /1
F or m N o.
: D
P N
_R
E V
TYPICAL PIPING SCHEMATIC FOR AIR-COOLED DX SYSTEMS
LIEBERT MC CONDENSER
Field installed relief valve(s) required for 50Hz EU CE units.
Check Valve Relief Valve Service
Valve Head Pressure Control Valve
Service Valve
External Equalizer
Trap at base of risers over 5ft. (1.5m)
Check Valve
LEE-TEMP RECEIVER
HOT GAS DISCHARGE
LIQUID RETURN
EVAPORATOR
COIL
LIQUID
SUCTION
COMPRESSOR
Expansion Valve
Solenoid Valve
Sight Glass
Filter Drier LIQUID LINE
Check Valve
CONDENSER COIL
(Includes factory provided inverted trap. No external trap required)
CONDENSER COIL
(Includes factory provided inverted trap. No external trap required)
For rises over 25ft. (7.6m), trap every 20ft. (6m) or evenly divided
HOT GAS DISCHARGE
FIELD PIPING
FACTORY REFRIGERANT PIPING SERVICE/SCHRADER (ACCESS) CONNECTION NO VALVE CORE
SERVICE/SCHRADER (ACCESS) CONNECTION WITH VALVE CORE
Notes:
1. Single refrigeration circuit shown for clarity.
2. Schematic representation shown. Do not use for specific connection locations.
3. Components are not supplied by Liebert, but are required for proper operation and maintenance.
4. Traps must be installed and horizontal lines pitched to ensure proper oil return and to reduce liquid floodback to compressor. Pitch horizontal hot gas piping at a minimum of 1/2" per 10 feet (42mm per 10m) so that gravity will aid in moving oil in the direction of the refrigeration flow.
5. Do not islolate any refrigeration circuits from over pressurization protection.
Service Valve
Sensing Bulb
LIEBERT MC CONDENSER
LIEBERT MC CONDENSER WITH LEE-TEMP OPTION
Pressure Transducer
Pressure Transducer
INTERCONNECTING
PIPING
Optional Field Installed Fusible Plug
Document generated 06 April 2022 05:09 PM (EST).
Adam.Lensegrav Line
Adam.Lensegrav Line
Adam.Lensegrav Cross-Out
REV DATE : 2/17
DPN002169
Page :1 /3
PREMIUM EFFICIENCY CONTROL
F or m N o.
: D
P N
_R
E V
ELECTRICAL FIELD CONNECTIONS
LIEBERT MC CONDENSER
FAN 2
FAN 1
SH
NOTICE !
THIS HOLE FOR FIELD
SUPPLIED EXTRA LOW
VOLTAGE CONTROL WIRING
KEY ELECTRICAL DETAILS:
1) Three phase electrical service – Terminals are on top of disconnect switch for one and two fan units. Terminals are on bottom of disconnect switch for three and four fan units. Three phase service not by Liebert. See note 5.
2) Earth ground – Field lug terminal for earth ground connection. Ground terminal strip for fan motor ground connection.
3) Primary high voltage entrance – Two 7/8” (22.2mm) diameter knockouts located at the bottom of the enclosure.
4) SPD field connection terminals – High voltage surge protective device (SPD) terminals. SPD is an optional device.
Document generated 06 April 2022 05:09 PM (EST).
Adam.Lensegrav Line
Adam.Lensegrav Line
Adam.Lensegrav Cross-Out
DPN002169
Page :2 /3
PREMIUM EFFICIENCY CONTROL
F or m N o.
: D
P N
_R
E V
ELECTRICAL FIELD CONNECTIONS
LIEBERT MC CONDENSER
5) CANbus terminal connections – Field terminals for CANbus cable connection.
• 5A is the CANbus connectors.
o TB49-1 is the input terminal for CANbus high.
o TB49-3 is the input terminal for CANbus low.
o TB50-1 is output terminal for CANbus high.
o TB50-3 is the output terminal for CANbus low.
o…