Attachment B.pdf
PDF 4 MB Posted
- Attached to
- Nederman Exhaust System State and local contract opportunity
- Solicitation number
- 6065AB
- Issued by
- Colorado
About this file
The documents are design and construction drawings for the City of Aurora's Vehicle Exhaust System Upgrade project located at 25950 East Quincy Ave in Aurora, Colorado. The project involves upgrading the vehicle exhaust system at the Public Safety Training Center (PSTC), with comprehensive electrical, mechanical, and architectural plans detailing the demolition and installation of new exhaust fan systems, electrical infrastructure, and related components. The project is scheduled for construction, with key milestone dates including 65% construction documents on 12.10.2024, permit issue on 03.21.2025, and construction issue on 05.16.2025.
The project involves upgrading the existing vehicle emissions exhaust system, including removing old electrical and mechanical equipment and installing new exhaust fans, control panels, and associated electrical infrastructure. The electrical plans indicate work on existing panels including AH11, AH21, AL11, and others, with specific attention to power connections, demolition, and new installations. The one-line electrical diagram shows the existing electrical distribution system, with a 3000-amp main distribution panel and multiple transformers and sub-panels. The electrical contractor is required to verify panel capacity and perform 30-day metering to confirm sufficient capacity for added gas detection devices, following NEC 220.87 requirements.
View the file
Other files for this state and local contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment A.pdf | ||
| Bid Sheet.xlsx | XLSX spreadsheet | |
| Project Manual Nederman Exhaust System.pdf | ||
| Attachment C.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ISSUE LOG KEY:
D
AT
E
ISSUE LOG
ELECTRICAL SHEET INDEX
TITLE
ELECTRICAL COVER SHEETE-000
C
ON
ST
RU
CT
IO
N
DO
C
.1
0.
24ISSUED AS PART OF A SET
' ' NOT PART OF SET
' ' ISSUED FOR INFORMATION ONLY*
ELECTRICAL DEMOLITION PLANSED-100
ELECTRICAL PLANSE-100
ELECTRICAL ONE-LINE AND SCHEDULESE-200
GFCI DUPLEX RECEPTACLE
DUPLEX RECEPTACLE; HALF SWITCHED
ISOLATED GROUND DUPLEX RECEPTACLE
WALL MOUNTED SPECIAL OUTLET AS NOTED
SPECIAL OUTLET AS NOTED
JUNCTION BOX
WALL MOUNTED JUNCTION BOX
FLOOR MOUNTED JUNCTION BOX
DUPLEX RECEPTACLE MOUNTED ABOVE COUNTERC
FLUSH FLOOR MOUNTED DUPLEX RECEPTACLE
FLUSH FLOOR MOUNTED DOUBLE DUPLEX RECEPTACLE
FLUSH FLOOR MOUNTED DUPLEX RECEPTACLE; HALF SWITCHED
FLUSH FLOOR MOUNTED DUPLEX RECEPTACLE AND TELECOM
DIVISION 15 EQUIPMENT POWER CONNECTION
FUSED DISCONNECT
NON FUSED DISCONNECT
MOTOR STARTER
ENCLOSED CIRCUIT BREAKER
PULL BOX
PUSH BUTTON
TRANSFORMER
PANELBOARD OR LOADCENTER
CONTACTOR
ELECTRIC MOTOR
METER
THERMOSTAT
ATS AUTOMATIC TRANSFER SWITCH
ONE-LINE DIAGRAM SYMBOLS
CIRCUIT HOMERUN
CONDUIT RUN
CONDUIT RUN BELOW GRADE
CONDUIT UP
CONDUIT DOWN
DISCONNECT SWITCH
FUSE
CIRCUIT BREAKER
CURRENT TRANSFORMER
POTENTIAL TRANSFORMER
METER
SURGE SUPPRESSION DEVICE
VOLT-METER
SELECTOR SWITCH
GROUND
GF GROUND FAULT PROTECTION
AMP-METER
ST SHUNT TRIP
NORMALLY OPEN CONTACT
NORMALLY CLOSED CONTACT
COLD WATER GROUND CONNECTION
BUILDING STEEL GROUND CONNECTION
TIMER SWITCH
MULTI-OUTLET PLUG STRIP
TIME CLOCK
PHOTO-CELL
SWITCH
THERMAL OVERLOAD SWITCH
VARIABLE SPEED SWITCH
KEY SWITCH
LIGHTING FIXTURE SYMBOLS
RECESSED LIGHTING FIXTURE
WALL MOUNTED LIGHT
WALL MOUNTED UP-LIGHT
PENDANT MOUNTED LIGHT
SURFACE MOUNTED LIGHT
DIRECTIONAL/ADJUSTABLE RECESSED LIGHTING FIXTURE
MONO-POINT LIGHTING FIXTURE
RECESSED STEP LIGHT
FLUORESCENT STRIP LIGHT
WALL MOUNTED LINEAR FLUORESCENT LIGHT
RECESSED OR SURFACE MOUNTED FLUORESCENT TROFFER
FIXTURE WITH EMERGENCY BACKUP OR ON EM CIRCUIT
WALL MOUNTED EXIT SIGN W/ FACES & ARROWS AS SHOWN
EMERGENCY LIGHTS
CEILING MOUNTED EXIT SIGN W/ FACES & ARROWS AS SHOWN
SWITCH
THREE-WAY SWITCH
FOUR-WAY SWITCH
DOOR JAMB SWITCH
LIGHTING CONTROL SYMBOLS
EXTERIOR POLE MOUNTED LIGHT
EXTERIOR POST (BOLLARD) MOUNTED LIGHT
DAYLIGHT PHOTO SENSORDL
KEY SWITCH
LV
VARIABLE SPEED SWITCH
DIMMER
THREE-WAY DIMMER
LOW VOLTAGE SWITCH
WALL OCCUPANCY SENSOR/SWITCH
THERMAL OVERLOAD SWITCH
OCCUPANCY SENSOR - WALL MOUNTED
OCCUPANCY SENSOR - CORRIDOR CEILING MOUNTED
S
S3
ST
SO
D
D
SV
SK
SJ
S4
SK
SV
ST
S
PC
TC
TS
A
V
SS
M
T
C
T
PB
CB
N
J
J
J
ABBREVIATIONSPOWER SYMBOLS
SINGLE RECEPTACLE
DUPLEX RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
NOTE:
ALL SYMBOLS SHOWN ON LEGEND ARE
NOT NECESSARILY USED.
OS
OS OCCUPANCY SENSOR - CEILING MOUNTED
OS
NOTES:
· LIGHT LINEWEIGHT INDICATES EXISTING.
· HATCHED AREAS INDICATE DEMOLITION.
· 'C' ADJACENT TO A DEVICE INDICATES
MOUNTING ABOVE COUNTERTOP.
AFC
AFF
AFG
AHJ
- ABOVE FINISHED CEILING
- ABOVE FINISHED FLOOR
- ABOVE FINISHED GRADE
- AUTHORITY HAVING JURISDICTION
AL - ALUMINUM
AWG
AP - ACCESS POINT
- AMERICAN WIRE GAUGE
BFG
BMS
BAS - BUILDING AUTOMATION SYSTEM
- BELOW FINISH GRADE
- BUILDING MANAGEMENT SYSTEM
C
CATV
CCTV
- CONDUIT
- COMMUNITY (CABLE) ANTENNA TELEVISION SYSTEM
- CLOSED CIRCUIT TELEVISION
CKT - CIRCUIT
CPU - CENTRAL PROCESSING UNIT
CT - CURRENT TRANSFORMER
DISP - GARBAGE DISPOSAL
DW - DISHWASHER
(E) - EXISTING
EM - EMERGENCY
EWC - ELECTRIC WATER COOLER
FBO
GFI
FA
FACP
GRD
GC
- FIRE ALARM
- FIRE ALARM CONTROL PANEL
- FURNISHED BY OTHERS
- GENERAL CONTRACTOR
- GROUND FAULT CIRCUIT INTERRUPTER
- GROUND
IAW IN ACCORDANCE WITH-
IC
IDF
IG
IR
LAN
- INTERMEDIATE CROSS-CONNECT
- INTERMEDIATE DISTRIBUTION FRAME
- ISOLATED GROUND
- INFRARED
- LOCAL AREA NETWORK
NIC
MDF
(N)
MAIN DISTRIBUTION FRAME-
NEW-
NOT IN CONTRACT-
NL NIGHT LIGHT-
NTS NOT TO SCALE-
OC
PA
ON CENTER-
PUBLIC ADDRESS-
REF REFRIGERATOR-
TVSS
TTB TELECOMMUNICATIONS TERMINAL BOARD-
TRANSIENT VOLTAGE SURGE SUPPRESSOR-
TVTB TELEVISION TERMINAL BOARD-
UG
UNO
W
V
UNDERGROUND-
UNLESS NOTED OTHERWISE-
VOLT-
WATT-
WP
XP
WAN
WLAN
WAP
WIDE AREA NETWORK-
WIRELESS ACCESS POINT-
WIRELESS LOCAL AREA NETWORK-
WEATHERPROOF-
EXPLOSIONPROOF-
+18"
DEVICE ABOVE FINISH FLOOR (VERIFY W/ ARCH ELEVS)
MOUNTING HEIGHT TO CENTERLINE OF-
FIRE ALARM SYMBOLS
FIRE ALARM CONTROL PANEL
REMOTE ANNUNCIATOR PANEL
SMOKE DETECTOR
HEAT DETECTOR
COMBO SMOKE/HEAT DETECTOR
FIRE ALARM HORN
FIRE ALARM STROBE
FIRE ALARM COMBO HORN/STROBE
FIRE ALARM PULL STATION
S FIRE ALARM SPEAKER
S FIRE ALARM COMBO SPEAKER/STROBE
FIREMAN'S PHONE JACK
DUCT DETECTOR
SPRINKLER SYSTEM FLOW SWITCH
SPRINKLER SYSTEM TAMPER SWITCH
FIRE/SMOKE DAMPERFSD
FT
FF
F
F
H
H
ANN
FACP
H
SMOKE DETECTOR SOUND BARRIER
SB
CO
SMOKE DETECTOR W/ CARBON MONOXIDE
BD
T
BD
R
BEAM TYPE SMOKE DETECTOR TRANSMITTER
BEAM TYPE SMOKE DETECTOR RECEIVER
INDIVIDUAL ADDRESSABLE MODULE
MONITORED RELAY
POST-INDICATOR VALVE
CARBON MONOXIDE DETECTOR
PIV
MR
IAM
CO
FIRE ALARM CHIME
FIRE ALARM CHIME/STOBE
REMOTE TESTER SWITCHRTS
LOW TEMPERATURE SENSORLT
ELECTRICAL SYSTEMS LEGEND
F
C
18"
48" 64"
78"
90"
78"
64"
FIRE ALARM DEVICES
48"
ELECTRICAL DEVICES
96"
NOTES:
1. IF MOUNTING HEIGHT OF DEVICES INDICATED HERE IS IN
CONFLICT WITH ADA REQUIREMENTS DUE TO INSTALLATION
DETAIL, ADA DIMENSIONS SHALL GOVERN.
2. REFERENCE ARCHITECTURAL INTERIOR ELEVATIONS.
LOCATIONS SHOWN ON INTERIOR ELEVATIONS SHALL
SUPERCEDE LOCATIONS SHOWN HERE, UNLESS LOCATIONS
SHOWN ON INTERIOR ELEVATIONS ARE NOT CODE
COMPLIANT.
WALL-MOUNT
NO SCALE
TYPICAL DEVICE MOUNTING HEIGHTS
OC
DLVS
CBC
TSTC
ANN
FACP
F
120"
MAX.
80"
MIN.
96"
MAX.
TOP OF DEVICE
9'-0"+ CEILING
8'-0" CEILING
TOP OF CABINET
TOP OF CABINET
TOP OF DEVICE
CL OF DEVICE
TOP OF DEVICE
TOP OF CABINET
TOP OF CABINET
BOTTOM OF DEVICE
S
C
ON
ST
RU
CT
IO
N
DO
CS
.0
4.
1. THESE DRAWINGS ACCOMPANY THE PUBLISHED CONSTRUCTION DOCUMENT SPECIFICATION BOOK (PROJECT
MANUAL).
2. DO NOT SCALE DRAWINGS. VERIFY DIMENSIONS ON ARCHITECTURAL DRAWINGS AND IN FIELD PRIOR TO
COMMENCEMENT OF WORK.
3. VISIT SITE PRIOR TO BID AND VERIFY THAT CONDITIONS ARE AS INDICATED. CONTRACTOR SHALL INCLUDE IN
HIS BID COSTS REQUIRED TO MAKE HIS WORK MEET EXISTING CONDITIONS.
4. SYSTEM OUTAGES SHALL BE PERMITTED ONLY AT TIMES APPROVED BY OWNER - IN WRITING. WORK WHICH COULD RESULT IN AN ACCIDENTAL OUTAGE (BEYOND BRANCH CIRCUITS) SHALL BE PERFORMED WITH THE
OWNER'S MAINTENANCE PERSONNEL ADVISED OF SUCH WORK.
5. SERVICE SHALL BE MAINTAINED TO EXISTING AREAS DURING CONSTRUCTION. CONTRACTOR SHALL PROVIDE PORTABLE GENERATORS, CABLES, OUTLETS, ETC. AS REQUIRED TO MAINTAIN CONTINUITY OF SERVICE.
PLACEMENT OF SUCH PORTABLE EQUIPMENT SHALL BE SUBJECT TO OWNER APPROVAL.
6. REVIEW ARCHITECTURAL, STRUCTURAL, MECHANICAL AND OTHER DRAWINGS PRIOR TO BID.
7. WORK SHALL BE PERFORMED IN A WORKMANLIKE MANNER TO THE SATISFACTION OF THE ARCHITECT.
8. WORK, MATERIALS, AND EQUIPMENT SHALL CONFORM TO THE LATEST EDITIONS OF LOCAL, STATE, AND
NATIONAL CODES, ORDINANCES.
9. PROVIDE PERMITS AND INSPECTIONS REQUIRED.
10. CONTRACTOR'S FAILURE TO ORDER OR RELEASE ORDER FOR MATERIALS AND/OR EQUIPMENT WILL NOT BE ACCEPTED AS A REASON TO SUBSTITUTE ALTERNATE MATERIALS, EQUIPMENT, OR INSTALLATION METHODS.
11. PROVIDE ELECTRICAL DEMOLITION REQUIRED. REFER TO ARCHITECTURAL AND ELECTRICAL DEMOLITION DRAWINGS FOR LOCATION AND EXTENT OF DEMOLITION REQUIRED. CONTRACTOR SHALL VISIT SITE PRIOR
TO BID TO DETERMINE EXTENT OF WORK INVOLVED.
12. PROVIDE ALL NECESSARY DEMOLITION TO REMOVE EXISTING UNUSED CONDUIT, WIRE, CABLE, J-BOXES, RECEPTACLES, SWITCHES, LIGHTS, FIRE ALARMS DEVICES, ETC. COMPLETE WITH ASSOCIATED CIRCUITING
TO SOURCE.
13. ALL (E) EQUIPMENT, LAMPS, BALLASTS, ETC. BEING REMOVED SHALL BE DISCARDED IN ACCORDANCE WITH
APPLICABLE EPA REQUIREMENTS.
14. VERIFY EXACT LOCATION OF EQUIPMENT TO BE FURNISHED BY OTHERS PRIOR TO ROUGH-IN.
15. INSTALL ALL MATERIALS IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. ANY DEVIATIONS SHALL BE BROUGHT TO THE ARCHITECT/ENGINEER'S ATTENTION PRIOR TO INSTALLATION.
16. FINAL CONNECTIONS TO EQUIPMENT SHALL BE IN ACCORDANCE WITH MANUFACTURER'S APPROVED WIRING DIAGRAMS, DETAILS, AND INSTRUCTIONS. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE
MATERIALS AND EQUIPMENT COMPATIBLE WITH EQUIPMENT ACTUALLY SUPPLIED.
17. CONTRACTOR SHALL BE RESPONSIBLE FOR REPLACING EQUIPMENT WHICH IS DAMAGED DUE TO INCORRECT FIELD WIRING PROVIDED UNDER THIS SECTION, OR FACTORY WIRING IN EQUIPMENT PROVIDED UNDER THIS
SECTION.
18. ALL ELECTRICAL SYSTEMS COMPONENTS SHALL BE LISTED OR LABELED BY U.L. OR OTHER RECOGNIZED
TESTING FACILITY.
19. PROVIDE NEW UPDATED PANELBOARD DIRECTORIES FOR EXISTING AND NEW CIRCUITS BEING UTILIZED FOR
COMPLETION OF PROJECT.
20. PANEL DIRECTORIES SHALL BE REMOVABLE. ROOM NAMES AND NUMBERS SHALL BE AS DIRECTED BY
OWNER. DIRECTORIES SHALL BE TYPED AND INSTALLED UNDER CLEAR PLASTIC COVERS.
21. FINAL CONNECTIONS TO MOTORS, TRANSFORMERS, AND OTHER VIBRATING EQUIPMENT SHALL BE SEAL TITE FLEX AND APPROVED FITTINGS. DO NOT SECURE CONDUITS, DISCONNECTS, OR DEVICES TO DUCTWORK OR
MECHANICAL EQUIPMENT.
22. SYSTEMS SHALL BE TESTED FOR PROPER OPERATION. IF TESTS SHOW THAT WORK IS DEFECTIVE, CONTRACTOR SHALL MAKE CORRECTIONS NECESSARY AT NO COST TO OWNER.
23. GUARANTEE THE INSTALLATION AGAINST DEFECTS IN MATERIALS AND WORKMANSHIP WHICH MAY OCCUR UNDER NORMAL USAGE FOR A PERIOD OF ONE YEAR AFTER OWNER'S ACCEPTANCE. DEFECTS SHALL BE
PROMPTLY REMEDIED WITHOUT COST TO THE OWNER.
24. SYSTEMS SHALL BE COMPLETE, OPERABLE, AND READY FOR CONTINUOUS OPERATION. LIGHTS, SWITCHES, RECEPTACLES, MOTORS, ETC. SHALL BE CONNECTED AND OPERABLE.
25. CONTRACTOR SHALL PERFORM GROUND PENETRATING RADAR TEST IN AREA OF ANY AND ALL CORE DRILL AND OR HOLES IN BUILDING STRUCTURE MEMBERS PRIOR TO DRILLING TO LOCATE AND AVOID ANY AND ALL
REBAR.
NOTES:
PANEL
AH21
VEHICLE EXHAUST WIRING DIAGRAM
VER
CONTROL
(4#10+1#10G)3/4"
PANEL
N
(3#10+1#10G)3/4"
VER SVER
SYSTEM
MOTOR
30A3P, NON-FUSED
DISCONNECT
SWITCH
(3#10+1#10G)3/4"
.2 1.
IS
SU
E
FO
R
PE
RM
IT
IS
SU
E
FO
R
CO
NS
TR
UC
TI
ON
.1
6.
ELECTRCAL
COVER SHEET
MTR
MAS
E-000
Designed:
Reviewed:
Project No: 24.100000.5843
SEAL
Issued:
CITY COMMENTS 05.16.2025
S:
\B
G
PR
O
JE
C
TS
\2 4.
.5
AU
R
O R
A
- C
AP
ST
C
EX
H
AU
ST
\C
AD
\B G
C E
C
AD
\2 4.
.5
3_
E-
0.
D
W G
.1
6.
7:
:1
AM
Scale: As Shown
C ity o f A ur or a
PS
TC
Ve hi cl e
Ex ha us t U pg ra de
Ea st
Q ui nc y
Av e.
Au ro ra , C ol or ad o
Sheet Title:
Sheet No:
Date:
© 2018 BG BUILDINGWORKS INC.
Current Issue:
ISSUE FOR CONSTRUCTION
05.16.2025
5-16-25
PRACTICAL
APPS BAY
EQUIP.
STOR.
POLICE
AND FIRE
AIR
CASCADE
DEF.
TACTICS
EQUIP.
STORAGE
ELEC.
STAFF
BUNKER
GEAR
STOR.
RECRUIT
BUNKER
GEAR
STOR.
MULTI-USE
STOR.
CORRIDOR
LAUNDRY
STAIR
FIRE/WATER
ENTRY
STAIR
UP
E
F
1. DISCONNECT AND REMOVE WALL MOUNTED
DISCONNECT SWITCH, MOTOR STARTER AND
WALL MOUNTED VEHICLE EXHAUST SYSTEM.
REMOVE BRANCH CIRCUIT BACK TO SOURCE
PANEL.
FLAG NOTES:#
SCALE:1 FIRST FLOOR ELECTRICAL DEMOLITION PLAN
1/8" = 1'-0"
PRACTICAL
APPS BAY
REPELLING
BALCONY
BUILDING
MAINTENANCE
/ SUPPLY
JAN.
I.T.
STOR.
BOILER
SHOP &
STORAGE
STAIR
DN
E
F
SCALE:2 SECOND FLOOR ELECTRICAL DEMOLITION PLAN
1/8" = 1'-0"
FA
C
P
T1A
DEMOLITION NOTES:
1. DEMOLITION PLAN INDICATES A DESIRED SCOPE
OF WORK; THE CONTRACTOR SHALL BE
RESPONSIBLE TO VERIFY IN FIELD PRIOR TO
START OF WORK.
2. CONDITIONS MAY EXIST WHERE (E) CABLING
AND/OR EQUIPMENT IS INSTALLED WITHIN AN
AREA OF DEMOLITION THAT IS INTENDED TO
REMAIN IN ORDER TO KEEP SYSTEMS OUTSIDE
OF THE AREA OF DEMOLITION IN OPERABLE
CONDITION. CONTRACTOR SHALL PROVIDE
APPROPRIATE PROTECTION AND EXERCISE CARE
WHEN PERFROMING DEMOLITION AROUND SUCH
CABLING AND EQUIPMENT.
3. ALL SYSTEMS LOCATED OUTSIDE THE AREA OF
DEMOLITION ARE INTENDED TO REMAIN
OPERABLE.
4. FOR ALL ITEMS TO BE DEMOLISHED REMOVE
CIRCUIT BACK TO POINT OF CONNECTION. MAKE
BRANCH CIRCUIT WITH REMAINING DEVICES
CONTINUOUS.
5. ELECTRICAL CONTRACTOR SHALL REMOVE ALL
DEMOLISHED ITEMS FROM SITE UNLESS OWNER
WISHES TO RETAIN. ITEMS REMOVED FROM SITE
SHALL BE DISPOSED OF IN A LEGAL MANNER.
6. EVERY ATTEMPT WAS MADE TO LOCATE ALL
ITEMS TO BE INCLUDED IN THE DEMOLITION
SCOPE IN THIS OCCUPIED SPACE. ELECTRICAL
CONTRACTOR SHALL PROVIDE A REASONABLE
ALLOWANCE TO INCLUDE THE REMOVAL OF
ITEMS NOT INDICATED ON THE ELECTRICAL
DEMOLITION PLAN.
T2A T2B
(E)
CF
AH21-2,4,6
1 11
EXISTING PANEL
"LCP1"
EXISTING
TRANSFORMER
"T-T1A"
EXISTING PANEL
"AH11" - SECTION #2
EXISTING PANEL
"AH11" SECTION #1
EXISTING PANEL
"AH13"
EXISTING AUTOMATIC
TRANSFER SWITCH
EXISTING PANEL
"AH22"
EXISTING PANEL
"AH21"
EXISTING
TRANSFORMER
"T2A"
EXISTING PANEL
"AH21"
EXISTING TRANSFORMER
"T2B"
EXISTING PANEL
"AL22"
5 6 10987 10.15 6 10987 10.1
ELECTRICAL
DEMOLITION
PLANS
MTR
MAS
ED-100
Designed:
Reviewed:
Project No: 24.100000.5843
SEAL
Issued:
CITY COMMENTS 05.16.2025
S:
\B
G
PR
O
JE
C
TS
\2 4.
.5
AU
R
O R
A
- C
AP
ST
C
EX
H
AU
ST
\C
AD
\B G
C E
C
AD
\2 4.
.5
3_
ED
-1
.D
W G
.1
6.
7:
:2
AM
Scale: As Shown
C ity o f A ur or a
PS
TC
Ve hi cl e
Ex ha us t U pg ra de
Ea st
Q ui nc y
Av e.
Au ro ra , C ol or ad o
Sheet Title:
Sheet No:
Date:
© 2018 BG BUILDINGWORKS INC.
Current Issue:
ISSUE FOR CONSTRUCTION
1. VEHICLE EXHAUST FAN (VEF-1) CONTROL PANEL
AT +48" AFF. REFER TO MECHANICAL
EQUIPMENT SCHEDULE FOR BRANCH CIRCUIT
CONDUCTOR REQUIREMENTS.
2. VEHICLE EXHAUST FAN MOUNTED ON
MECHANICAL PLATFORM. REFER TO
MECHANICAL EQUIPMENT SCHEDULE FOR
BRANCH CIRCUIT CONDUCTOR REQUIREMENTS
FROM CONTROL PANEL TO EXHAUST FAN.
BRANCH CIRCUIT CONDUIT SHALL BE ATTACHED TO
STRUCTURE ABOVE FROM ELECTRICAL ROOM, DOWN
TO CONTROL PANEL, UP FROM CONTROL PANEL TO
STRUCTURE ABOVE, OVER TO VEF-1 DISCONNECT
SWITCH, DOWN WALL TO LINE SIDE OF DISCONNECT,
UP WALL ON LOAD SIDE OF DISCONNECT SWITCH TO
VEF-1.
3. INSTALL VEHICLE EXHAUST FAN SERVICE
DISCONNECT ON WALL AT +6'-0" TO TOP OF
DISCONNECT SWITCH.
4. PROVIDE SURFACE MOUNTED JUNCTION BOX AT
+48" AFF FOR INSTALLATION OF GAS DETECTION
SYSTEM.
FLAG NOTES:
SCALE:1 FIRST FLOOR ELECTRICAL PLAN
1/8" = 1'-0"SCALE:2 SECOND FLOOR ELECTRICAL PLAN
1/8" = 1'-0"
UP
PRACTICAL APPS
BAY
ELEC.
AIR CASCADE
LAUNDRY
CORRIDOR
RECRUIT BUNKER
GEAR STOR.
STAFF BUNKER
GEAR STOR.
CTICS
TORAGE
EQUIP. STOR.
POLICE AND FIRE
HALL
STAIR
E. VEST.
10.1
E
F
MULTI-USE
STOR.
FIRE/WATER
ENTRY
DN
BOILER
STOR.
BUILDING
MAINTENANCE /
SUPPLY
JAN.
I.T.
REPELLING
BALCONY
REAK
FE - STAIR
10.1
E
F
PRACTICAL
APPS BAY
SHOP
STORAGE
POWER NOTES:
1. REFER TO MECHANICAL EQUIPMENT SCHEDULE
FOR CIRCUIT, DISCONNECT, AND CONDUCTORS
FOR MECHANICAL EQUIPMENT.
2. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR
FIELD COORDINATING THE LOCATION OF
ELECTRICAL EQUIPMENT, JUNCTION BOXES,
DISCONNECTS, ETC. EC SHALL BE RESPONSIBLE
FOR COORDINATION AND THE ROUTING OF
FEEDERS, AND BRANCH CIRCUITS.
3. COORDINATE POWER CONNECTIONS FOR OWNER
PROVIDED EQUIPMENT AND ALL OTHER
EQUIPMENT PROVIDED BY OTHER DIVISIONS
WITH SUBMITTAL DATA CUT SHEETS, WIRING
DIAGRAMS, AND MANUFACTURER'S WRITTEN
INSTALLATION INSTRUCTIONS. FIELD
COORDINATE FINAL LOCATIONS OF EQUIPMENT
AND POWER CONNECTIONS WITH GENERAL
CONTRACTOR AND OTHER
DIVISIONS/CONTRACTORS PRIOR TO ROUGH-IN.
FA
C
P
T1A
T2A T2B
EXISTING PANEL
"LCP1"
EXISTING
TRANSFORMER
"T-T1A"
EXISTING PANEL
"AH11"
EXISTING PANEL
"AL11"
EXISTING PANEL
"AL13"
EXISTING AUTOMATIC
TRANSFER SWITCH
EXISTING PANEL
"AH22"
EXISTING PANEL
"AH21"
EXISTING
TRANSFORMER
"T2A"
EXISTING PANEL
"AL21"
EXISTING TRANSFORMER
"T2B"
EXISTING PANEL
"AL22"
N
VEF
1 3
AH21-14,16,18
5 6 109875 6 10987
AH21-14,16,18
J
AL11-29
ELECTRICAL
PLANS
MTR
MAS
E-100
Designed:
Reviewed:
Project No: 24.100000.5843
SEAL
Issued:
CITY COMMENTS 05.16.2025
S:
\B
G
PR
O
JE
C
TS
\2 4.
.5
AU
R
O R
A
- C
AP
ST
C
EX
H
AU
ST
\C
AD
\B G
C E
C
AD
\2 4.
.5
3_
E-
0.
D
W G
.1
6.
7:
:4
AM
Scale: As Shown
C ity o f A ur or a
PS
TC
Ve hi cl e
Ex ha us t U pg ra de
Ea st
Q ui nc y
Av e.
Au ro ra , C ol or ad o
Sheet Title:
Sheet No:
Date:
© 2018 BG BUILDINGWORKS INC.
Current Issue:
ISSUE FOR CONSTRUCTION
T G
3000A 3000/3
N G
0A
T
TVSS
EXISTING
TRANSFOREMR
"T1A" 112.5kVA 480V- 208Y/120
RTU-1
L E
N
125/3
277/480V, 3PH, 4W,
100KW DIESEL GENERATOR
GEN
SCALE:1 ONE-LINE DIAGRAM
NONE
T
T
T
T
T
M M
M
ONE-LINE NOTES:
1. ALL ITEMS ASSOCIATED WITH THE ONE-LINE
DIAGRAM ARE EXISTING TO REMAIN AND IS BEING
ISSUE FOR REFERENCE ONLY.
2. REFERENCE MECHANICAL EQUIPMENT SCHEDULE
ON SHEET M-000 AND E-200 FOR CONNECTION
REQUIREMENTS OF MECHANICAL EQUIPMENT
IDENTIFIED ON THIS SHEET.
3. REFERENCE PANEL SCHEDULES FOR PANEL
CONFIGURATION AND DEMAND LOAD
CALCULATIONS.
4. UNLESS OTHERWISE NOTED, FEEDER SIZES
NOTED ARE BASED ON COPPER CONDUCTORS,
75°C. CONTRACTOR.
EXISTING XCEL ENERGY
PAD MOUNTED
TRANSFORMER
EXISTING XCEL ENERGY
ELECTRICAL SERVICE
TRANSITION CABINET
XCEL ENERGY METER
#81-993-782
0A
F
0A
T
0A F
SP
AR
E
0A
T
0A F
SP
AR
E
5A
T
0A F
EXIST
PANEL
AL21
EXIST
PANEL
AL25
EXIST
PANEL
AL24
EXIST
PANEL
HPH
EXIST
PANEL
AL11
EXIST
PANEL
AL12
EXIST
PANEL
AL13
EXISTING
ELEVATOR
EXISTING
5A
T
0A F
0A
T
0A F
0A
T
0A F
EXIST
PANEL
AH11
5A
T
0A F
EXIST
PANEL
AH22
EXIST
PANEL
AL22
EXISTING
TRANSFOREMR
"T2B" 30 kVA 480V- 208Y/120
EXISTING
TRANSFOREMR
"T2A" 75kVA 480V- 208Y/120
EXIST
PANEL
LB1
EXISTING
TRANSFOREMR
"T1BB"
30kVA 480V- 208Y/120
EXIST
PANEL
HDT
EXIST
PANEL
LDT
EXISTING
TRANSFOREMR
"TDT"
45kVA 480V- 208Y/120
EXIST
PANEL
AH21
5A
T
0A F
5A
T
0A F
0A
T
0A F
0A
T
0A F
SP
AR
E
0A
T
0A F
SP
AR
E
AT
AF
SP
AC
E
SP
AC
E
SP
AC
E
GROUNDING ELECTRODE
CONDUCTORS SIZED PER
WIRING CHART, THIS SHEET.
BLDG. STEEL IN DIRECT
CONTACT WITH EARTH I.A.W.
N.E.C. 250.52
METAL UNDERGROUND
WATER PIPE I.A.W.
N.E.C. 250.52
CONCRETE-ENCASED
ELECTRODE I.A.W.
N.E.C. 250-52
GROUND ROD I.A.W.
N.E.C. 250-52
3000-AMPS, 480/277V, 3~, 4W.
DISTRIBUTIONS BOARD - MDP
PROJECT SCOPE
OF WORK
NEMA 3R, 65kAIC RATED
EXISTING 8 SETS OF
(4#500kCMIL)3"C.
EXISTING
(4#4/0+1#4G)2-1/2"C.
PROJECT SCOPE
OF WORK
1. ELECTRICAL CONTRACTOR SHALL METER PANEL
TO CONFIRM THAT SUFFICIENT CAPACITY EXISTS
IN PANEL TO ACCOMMODATE ADDED GAS
DETECTION DEVICES. METERING SHALL BE FOR
30 DAYS AND COMPLY WITH REQUIREMENTS OF
NEC 220.87. SUBMIT METERING RESULTS TO
ENGINEER FOR EVALUATION AND WRITTEN
DIRECTION PRIOR TO TERMINATING INDICATED
BRANCH CIRCUIT ONTO PANEL.
FLAG NOTES:#
ELECTRICAL
ONE-LINE AND
SCHEDULES
MTR
MAS
E-200
Designed:
Reviewed:
Project No: 24.100000.5843
SEAL
Issued:
CITY COMMENTS 05.16.2025
S:
\B
G
PR
O
JE
C
TS
\2 4.
.5
AU
R
O R
A
- C
AP
ST
C
EX
H
AU
ST
\C
AD
\B G
C E
C
AD
\2 4.
.5
3_
E-
0.
D
W G
.1
6.
7:
:0
AM
Scale: As Shown
C ity o f A ur or a
PS
TC
Ve hi cl e
Ex ha us t U pg ra de
Ea st
Q ui nc y
Av e.
Au ro ra , C ol or ad o
Sheet Title:
Sheet No:
Date:
© 2018 BG BUILDINGWORKS INC.
Current Issue:
ISSUE FOR CONSTRUCTION
| 2025-05-16 Electrical Drawings - Issue For Construction - Stamped.pdf |
| Sheets and Views |
| 24.100000.5843_E-000-30x42 |
| 24.100000.5843_ED-100-30x42 |
| 24.100000.5843_E-100-30x42 |
| 24.100000.5843_E-200-30x42 |
File details come from the government source that posted it. Updated .