SOW APPENDIX A

BASEMENT:

Morgue AHU

Thermostats
None
VAVs:
No VAVs

Sensors:

Rm B40-1 Space RH

Rm B41 Space RH

Outside Air Temperature

Discharge Air Temperature

Low Limit

HW Coil Pump FP-1 Status

Supply Fan Status

Pre-Filter Differential Pressure

Post-Filter Differential Pressure

H-1 Duct RH Limit

H-2 Duct RH Limit

Rm B40-1 Occupancy

Rm B41 Occupancy

EF-1 Status

Output Devices:

Zone Damper actuator

Mechanical RM Damper Actuator

H-1 Humidifier Isolation Valve

H-2 Humidifier Isolation Valve

CHW Valve

H-1 Humidifier Modulating Valve

H-2 Humidifier Modulating Valve

Pre-Heat Valve

Kitchen AHU

Thermostats
3 Electronic

Sensors:

Zone-1 Space Temperature

Zone-2 Space Temperature

Zone-3 Space Temperature

Face/Bypass Discharge Air Temperature

Outside Air Temperature

Discharge Air Temperature

Low Limit

Supply Fan Status

Pre-Filter Differential Pressure

EF-1 Status

EF-2 Status

EF-3 Status

EF-4 Status

EF-5 Status

Output Devices:

Outside Air Damper Actuator

Zone-1 Damper Actuator

Zone-2 Damper Actuator

Zone-3 Damper Actuator

CHW Valve

Face/Bypass HW Valve

Face/Bypass Damper Actuator

Re-Heat Valve

EF-3 Damper Actuator

SPD AHU (Room D12)

(All Stand Alone Pneumatic)

Sensors:

Discharge Air Temperature
RH Hight Limit
Mixed Air Temperature
Thermostat Pneumatic
Pre-Heat Coil Discharge Air Temperature
RH Pneumatic

Output Devices:

CHW Valve

HW Valve

Damper Actuators

Humidifier Valve

Main Tunnel Monitoring

30- O2, CO2, Temperature and RH Sensors

1ST FLOOR:

AHU-1C Clinic

Thermostats
None
VAVs:
28 Pneumatic

28 Pneumatic Re-Heat Valves

Sensors:

Return Air Temperature

Pre-Heat Coil Discharge Temperature

Mixed Air Temperature

Clinic Space Temperature

HX-1 HW Supply Temperature

Supply Air Temperature

Low Limit

HX-1 HW Return Temperature

Supply Fan Status

Filter Status

Return Fan Status

HW Coil Supply Temperature

HW Coil Return Temperature

HW Pump P-1 Status

HW Pump P-2 Status

Return Static Pressure

HW Coil Pump P-3 Status

HW Coil Pump P-4 Status

CHW Coil Supply Temperature

CHW Coil Return Temperature

Supply Air Static Pressure

CHW Pump P-5 Status

CHW Pump P-6 Status

HX-3 Pump P-4D Status

HX-3 Pump P-5D Status

HX-3 HW Supply Temperature

HX-3 HW Return Temperature

Output Devices:

CHW Valve

HW Coil Valve

HX-1 Steam Valve

HX-2 Steam Valve

HX-3 Steam Valve

Outside Air Damper Actuator

Return Air Damper Actuator

Exhaust Air Damper Actuator

AHU-1D Admitting

Thermostats
None
VAVs:
19 Pneumatic

36 Pneumatic Re-Heat Valves

Sensors:

Return Air Temperature

Pre-Heat Coil Discharge Temperature

Mixed Air Temperature

Discharge Air Temperature

Low Limit

Return Fan Status

Supply Fan Status

Discharge Air Static Pressure

Filter Status

HW Coil Supply Temperature

HW Coil Return Temperature

EF-1D Status

EF-2D Status

EF-3D Status

EF-4D Status

Return Static Pressure

Pump P-1D Status

CHW Coil Supply Temperature

CHW Coil Return Temperature

Output devices:

CHW Valve

HW Valve

Outside Air Damper Actuator

Return Air Damper Actuator

Exhaust Air Damper Actuator

HX Steam Valve

HX HW Valve

ICU AHU & Exhaust Fans

Thermostats
27 Electronic
VAVs:
6 Electronic

27 Electronic Re-Heat Valves

Sensors:

Heat Recovery Discharge Air Temperature

Face/Bypass Discharge Temperature

Discharge Air RH

Outside Air RH

Outside Air Temperature

Discharge Air Temperature

Low Limit

OA Damper Status

Recovery Pump P-1 Status

Recovery Pump P-2 Status

Supply Fan Status

Pre-Filter Status

Post-Filter Status

Recovery Coil Supply Temperature

HW Coil Supply Temperature

HW Coil Return Temperature

CHW Coil Supply Temperature

CHW Coil Return Temperature

Corridor 213 RH

Corridor 218 RH

EF-1 Discharge Air Temperature

EF-1 Exhaust Air Temperature

EF-1 Exhaust Air RH

EF-1 Recovery Coil Supply Temperature

EF-1 Recovery Coil Return Temperature

EF-1 Fan Status

EF-1 Filter Status

EF-2 Discharge Air Temperature

EF-2 Exhaust Air Temperature

EF-2 Exhaust Air RH

EF-2 Recovery Coil Supply Temperature

EF-2 Recovery Coil Return Temperature

EF-2 Fan Status

EF-2 Filter Status

EF-2 Damper Status

EF-3 Discharge Air Temperature

EF-3 Recovery Coil Supply Temperature

EF-3 Recovery Coil Return Temperature

EF-3 Fan Status

EF-3 Damper Status

Output devices:

Humidifier Isolation Valve

Humidifier Modulating Valve

Heat Recovery Valve

CHW Valve

Face/Bypass Damper Actuator

HW Valve

Outside Air Damper Actuator

Exhaust Air Damper Actuator

Operating Rooms and Support Rooms

There are five (5) ORs that each have the following points:

Occupy Status

5- Pheonix Control Valves including Local Monitors

13-Space Temperature Sensors

13- Humidity Space Sensors

13- OR Air Flow Sensors

13- Reheat Valves

HEPA DP Sensors

APM Status

HEPA Filter DP

Door Status

APM Jam Status

5- Thermostats

CFM Sensors

Room Pressure Sensors

8- Pheonix Control Valves including Nurse Station Remote Monitor

Space Temperature

Humidity Space Sensor

OR Air Flow Sensors

Reheat Valve

Humidifier Valve

APM Status

HEPA Filter DP

Door Status

APM Jam Status

Thermostats

OR AHU-1

Sensors:

Discharge Air RH

EA/OA/MA Damper Status

EA/OA/DA Air Temperature Status

CFM Meters

Filter Status

Supply Fan/Return Fan Status

Low Limit

CHW Supply Temperature

CHW leaving Temperature

HW Supply Temperature

HW Return Temperature

S/R Air Flow Status in CFMs

Output devices:

VFD's

Humidifier Valve

HW Coil Valve

CHW Valves

Humidifier Valve

EA/OA/MA Damper Controller

OR AHU-2

Sensors:

Discharge Air RH

EA/OA/MA Damper Status

EA/OA/DA Air Temperature Status

Filter Status

Supply Fan/Return Fan Status

Low Limit

CHW Supply Temperature

CHW leaving Temperature

HW Supply Temperature

HW Return Temperature

S/R Air Flow Status in CFMs

Output devices:

HW Coil Valve

CHW Valve

Humidifier Valve

EA/OA/MA Damper Controller

Pharmacy AHU-1

Pharmacy has 29 Supply VAVs total, and 16 Exhaust VAVs

AHU-1 and 2 work together

Thermostats 30

VAVs: 45 total

Sensors:

Pre-Heat Coil Discharge Temperature

Discharge Air Temperature

Discharge Air RH mixed Air Temperature low Limit

HW recirc Pump Status

Supply Fan Status

Pre-Filter Status final Filter Status

Return Fan Status

Return Air Temperature

Return Air RH

Return Static Pressure hi-Static Pressure cutout

low Return Fan Pressure cutout
Electronic

mixed Air Pressure equipment Room Temperature building Static Pressure

Steam heat trace Temperature

Supply Isolation Damper Status

Return Isolation Damper Status

Discharge Air Humidity hi-Limit

Space Humidity

Output devices:

CHW Valve

Pre-Heat Valve

Outside Air Damper Actuator

Return Air Damper Actuator

Exhaust Air Damper Actuator

Humidifier Valve (does both AHU-1 & 2)

Steam Heat Trace Valve

Pharmacy AHU-2

Pharmacy has 29 VAVs total, AHU-1 and 2 work together

Sensors:

Pre-Heat Coil Discharge Temperature

Discharge Air Temperature

Discharge Air RH

Mixed Air Temperature

Low Limit

HW Recirc Pump Status

Supply Fan Status

Pre-Filter Status

Final Filter Status

Return Fan Status

Return Air Temperature

Return Air RH

Return Static Pressure

Hi-Static Pressure Cutout

Low Return Fan Pressure Cutout

Mixed Air Pressure

Equipment Room Temperature

Building Static Pressure

Steam Heat Trace Temperature

Supply Isolation Damper Status

Return Isolation Damper Status

Discharge Air Humidity hi-Limit

Space Humidity

Output devices:

CHW Valve

Pre-Heat Valve

Outside Air Damper Actuator

Return Air Damper Actuator

Exhaust Air Damper Actuator

2ND FLOOR:

Radiology/ X-Ray 2A AHU

Thermostats
None
VAVs:
Reheats only with Pneumatic Valves

Sensors:

Discharge Air Temperature

Return Air Temperature

Space Temperature

Low Limit

Supply Fan Status

Output devices:

CHW Valve

AHU-2B Lab (New Unit in the Lab itself)

Sensors:

CHW Coil leaving Temperature

Pre-Heat Coil leaving Temperature

Discharge Air Temperature

Return Air Temperature

Mixed Air Temperature

Low Limit

Supply Fan DP

Supply Fan Status

Filter Status

Exhaust Fan Status

High Static Pressure

Space Static Pressure

Re-Heat Discharge Temperature

Supply Duct RH

Exhaust Fan DP

Space RH

Space Temperature

Output devices:

CHW Valve

Pre-Heat Valve

Re-Heat Valve

Outside Air Damper Actuator

Return Air Damper Actuator

Exhaust Air Damper Actuator

AHU-2B Lab (Old Unit in B201)

Thermostats
1
VAVs:
Reheats Only

CV Unit is Entirely Stand-Alone Pneumatic with 3 Pneumatic Re-Heat/T-Stats

Fan Only on Main Unit

CHW Valve on Main Unit

PACU AHU (Unit Located on Roof of 2nd Floor)

Thermostats
10 Electronic
VAVs:
7 Electronic

Plus some Radiant Panels

Sensors:

Discharge Air Temperature

Pre-Heat Coil Discharge Temperature

Mixed Air Temperature

CHW leaving Air Temperature

Outside Air Temperature

Outside Air RH

Low Limit

Return Fan Differential Pressure (CFM)

Supply Fan Differential Pressure (CFM)

Supply Fan Status

Return Fan Status

Pre Filter Status

Mid-Filter Status

Final Filter Status

Return Air Temperature

Return Air RH

HW Pump Status

Exhaust Fan Status

Remote Smoke Damper Status

Output Devices:

CHW Valve

Pre-Heat Valve

Humidifier

Outside Air Damper Actuator

Return Air Damper Actuator

Exhaust Air Damper Actuator

Reheat Valves

3RD FLOOR:

NEW ANGIO AHU

Sensors

Return Air Temperature

Supply Air Temperature

Pre-Heat Temperature

Mix Air Temperature

Cool Temperature

SA CFM

OA CFM

Filter Status

SA SP

SA Humidity

RA Humidity

OA Dmpr Pos

RA Dmpr Pos

PHT vlv Pos

DX Enable

EA Dmpr Pos

Output devices:

CHW Valve

HW Valve

2 RHT Valves

2 DAT Temperature

Eq RM Sensor

3B MICRO AC-1

Sensors:

Outside Air Temperature

HW Supply Temperature

Discharge Air Temperature

Low Limit

3 T-Stats and Reheat Valves

Output devices:

CHW Valve

HW Valve

Outside Air Damper Actuator

Return Air Damper Actuator

Humidifier Valve

Face/Bypass Damper Actuator

HX Steam Valve

3B MICRO AC-2

Unit is 100% Outside Air and CV

Sensors:

Outside Air Temperature

Discharge Air Temperature

Low Limit

Output devices:

CHW Valve

HW Valve

Humidifier Valve

Face/Bypass Damper Actuator

Outside Air Damper Actuator

5TH FLOOR:

AHU-5C

Thermostats
None
VAVs:
16 Pneumatic

39 Pneumatic Reheat Valves (Fin Tube and Reheat Coils)

Sensors:

Discharge Air Temperature

Mixed Air Temperature

Return Air Temperature

Return Air RH

Supply Fan Status

Return Fan Status

Supply Air Static Pressure

Return Air Static Pressure

Low Limit

EF-5C Status

HW Pump P-1 Status

HW Pump P-2 Status

HX-1 Supply water Temperature

HX-1 Return water Temperature

HX-1 Differential Pressure

Output devices:

CHW Valve

Outside Air Damper Actuator

Return Air Damper Actuator

Exhaust Air Damper Actuator

HX Steam Valve

HX bypass Valve

Reheat Valves

AHU-5A-1

Thermostats
None

7 Pneumatic Reheat Valves

Sensors:

Discharge Air Temperature

Mixed Air Temperature

Return Air Temperature

Return Air RH

Supply Fan Status

Low Limit

Output devices:

Pre-Heat Valve

CHW Valve

HW Valve

Humidifier Valve

Outside Air Damper Actuator

Return Air Damper Actuator

Exhaust Air Damper Actuator

AHU-5A-2

Thermostats
None

12 Pneumatic Reheat Valves

Sensors:

Discharge Air Temperature

Mixed Air Temperature

Return Air Temperature

Return Air RH

Supply Fan Status

Low Limit

Output devices:

Pre-Heat Valve

CHW Valve

HW Valve

Humidifier Valve

Outside Air Damper Actuator

Return Air Damper Actuator

Exhaust Air Damper Actuator

Reheat Valves

AHU-5A-3

Thermostats
None

12 Pneumatic Reheat Valves

Sensors:

Discharge Air Temperature

Mixed Air Temperature

Return Air Temperature

Return Air RH

Supply Fan Status

Low Limit

HW Supply Temperature

CHW Supply Temperature

Output devices:

Pre-Heat Valve

CHW Valve

HW Valve

Humidifier Valve

Outside Air Damper Actuator

Return Air Damper Actuator

Exhaust Air Damper Actuator

AHU-5B

Thermostats
None

33 Pneumatic Reheat Valves

Sensors:

Discharge Air Temperature

Mixed Air Temperature

Return Air Temperature

Return Air RH

Supply Fan Status

Return Fan-1 Status

Return Fan-2 Status

Supply Air RH

Low Limit

Output devices:

HW Valve

CHW Valve

Outside Air Damper Actuator

Return Air Damper Actuator

Exhaust Air Damper Actuator

6TH FLOOR:

AHU-6A Lab

34 Pneumatic VAVs

66 Pneumatic Reheat Valves (Fin Tube included)

Sensors:

Discharge Air Temperature

Outside Air Temperature

Heat Rec. Coil Discharge Temperature

HRC Exhaust Temperature

Mech Rm Space Temperature

Supply Fan Status

EF-2 Status

Glycol Pump P-5 Status

Low Limit

Pre-Filter Differential Pressure

Post-Filter Differential Pressure

EF-2 Pre-Filter Differential Pressure

A603 Space RH

A625 Space RH

A629 Space RH

A602 Space RH

Output devices:

Outside Air Damper Actuator

Mech Room Intake Damper Actuator

Mech Room Exhaust Damper Actuator

H-3 Humidifier Isolation Valve

H-4 Humidifier Isolation Valve

H-5 Humidifier Isolation Valve

H-6 Humidifier Isolation Valve

H-3 Humidifier Modulating Valve

H-4 Humidifier Modulating Valve

H-5 Humidifier Modulating Valve

H-6 Humidifier Modulating Valve

Unit Heater-1 HW Valve

Heat Recovery Coil Valve

HW Valve

CHW Valve

Face/Bypass Damper Actuator

VFD

9TH FLOOR:

AHU-9 Cardiac Cath Lab

Thermostats
4 Electronic
VAVs:
No VAVs

Sensors:

Outside Air Temperature

Outside Air RH

PreFilter Differential Pressure

Mixed Air Temperature

Low Limit

Supply Air Temperature

Supply Air RH

Post-Filter Differential Pressure

802A Room Temperature

802C Room Temperature

802D/Computer Room Temperature

802G Room Temperature

Supply Fan proving

Return Fan proving

Space RH

Return Air Temperature

Output devices:

Outside Air Damper Actuator

Return Air Damper Actuator

Exhaust Air Damper Actuator

CHW Valve

VFD

11TH FLOOR:

AHU-1

Thermostats
132 Electronic
VAVs:
132 Electronic

132 Pneumatic Re-Heat Valves

Sensors:

Supply Air Temperature

Supply Air RH

Mixed Air Temperature

Return Air Temperature

Return Air RH

Supply Fan Status

Return Fan Status

Discharge Static Pressure

Discharge Differential Pressure

Return Air Differential Pressure

Low Limit

Pre-Filter Alarm

Downstream Filter Alarm

Pump A-1 Status

Pump A-2 Status

HW Radiant Loop Temperature

HW Radiant Loop Differential Pressure

Ex Fan RV-9 Status

Ex Fan RV-9 Static Pressure

CFM Sensors

Output devices:

Outside Air Damper Actuator

Return Air Damper Actuator

Exhaust Air Damper Actuator

HW Valve

CHW Valve

Humidifier Modulating Valve

Humidifier Isolation Valve

Radiant Loop Mixing Valve

Radiant Loop Bypass Valve

Exhaust Fan RV-9 Damper Actuator

VFD's

AHU-2

Thermostats
None
VAVs:
No VAVs

20 Pneumatic Re-Heat Valves

Sensors:
2 CV Boxes

Supply Air Temperature

Supply Air RH

Heat Recovery Discharge Temperature

Return Air Temperature

Return Air RH

Supply Fan Status

Exhaust Fan Status

Outdoor Air Damper Status

Exhaust Air Damper Status

Low Limit

EF-9 Status

Supply Glycol Temperature

Exhaust Glycol Temperature

Pump A-4 Status

Supply Filter Alarm

Exhaust Filter Alarm

Downstream Filter Alarm

Output devices:

Outside Air Damper Actuator

Exhaust Air Damper Actuator

Glycol Valve

HW Valve

CHW Valve

Humidifier Modulating Valve

Humidifier Isolation Valve

VFD's

AHU-3

Thermostats
39 Electronic
VAVs:
31 Electronic

39 Pneumatic Re-Heat Valves

Sensors:

Supply Air Temperature

Supply Air RH

Mixed Air Temperature

Return Air Temperature

Return Air RH

Supply Fan Status

Return Fan Status

Discharge Static Pressure

Discharge Differential Pressure

Return Air Differential Pressure

Low Limit

Pre-Filter Alarm

Downstream Filter Alarm

Pump B-1 Status

Pump B-2 Status

HW Radiant Loop Temperature

HW Radiant Loop Differential Pressure

Ex Fan RV-10 Status

Ex Fan RV-10 Static Pressure

Output devices:

Outside Air Damper Actuator

Return Air Damper Actuator

Exhaust Air Damper Actuator

HW Valve

CHW Valve

Humidifier Modulating Valve

Humidifier Isolation Valve

Radiant Loop Mixing Valve

Radiant Loop Bypass Valve

Exhaust Fan RV-10 Damper Actuator

VFD's

AHU-4

Thermostats
None
VAVs:
No VAVs

59 Pneumatic Re-Heat Valves

Sensors:

Supply Air Temperature

Supply Air RH

Heat Recovery Discharge Temperature

Return Air Temperature

Return Air RH

Supply Fan Status

Exhaust Fan Status

Outdoor Air Damper Status

Exhaust Air Damper Status

Low Limit

EF-10 Status including 11 Isolation Room Air FLow Monitors

Supply Glycol Temperature

Exhaust Glycol Temperature

Pump B-4 Status

Supply Filter Alarm

Exhaust Filter Alarm

Downstream Filter Alarm

Output devices:

Outside Air Damper Actuator

Exhaust Air Damper Actuator

Glycol Valve

HW Valve

CHW Valve

Humidifier Modulating Valve

Humidifier Isolation Valve

EF-10 Damper Actuator

VFD's

AHU-5

Thermostats
39 Electronic
VAVs:
39 Electronic

39 Pneumatic Re-Heat Valves

Sensors:

Supply Air Temperature

Supply Air RH

Mixed Air Temperature

Return Air Temperature

Return Air RH

Supply Fan Status

Return Fan Status

Discharge Static Pressure

Discharge Differential Pressure

Return Air Differential Pressure

Low Limit

Pre-Filter Alarm

Downstream Filter Alarm

Pump C-1 Status

Pump C-2 Status

HW Radiant Loop Temperature

HW Radiant Loop Differential Pressure

Ex Fan RV-11 Status

Ex Fan RV-11 Static Pressure

Output devices:

Outside Air Damper Actuator

Return Air Damper Actuator

Exhaust Air Damper Actuator

HW Valve

CHW Valve

Humidifier Modulating Valve

Humidifier Isolation Valve

Radiant Loop Mixing Valve

Radiant Loop Bypass Valve

Exhaust Fan RV-11 Damper Actuator

VFD's

AHU-6

Thermostats
None
VAVs:
No VAVs

73 Pneumatic Re-Heat Valves

Sensors:

Supply Air Temperature

Supply Air RH

Heat Recovery Discharge Temperature

Return Air Temperature

Return Air RH

Supply Fan Status

Exhaust Fan Status

Outdoor Air Damper Status

Exhaust Air Damper Status

Low Limit

EF-11 Status

Supply Glycol Temperature

Exhaust Glycol Temperature

Pump B-4 Status

Supply Filter Alarm

Exhaust Filter Alarm

Downstream Filter Alarm

Output devices:

Outside Air Damper Actuator

Exhaust Air Damper Actuator

Glycol Valve

HW Valve

CHW Valve

Humidifier Modulating Valve

Humidifier Isolation Valve

EF-11 Damper Actuator

VFD's

AHU-7

Thermostats
37 Electronic
VAVs:
37 Electronic

37 Pneumatic Re-Heat Valves

Sensors:

Supply Air Temperature

Supply Air RH

Mixed Air Temperature

Return Air Temperature

Return Air RH

Supply Fan Status

Return Fan Status

Discharge Static Pressure

Discharge Differential Pressure

Return Air Differential Pressure

Low Limit

Pre-Filter Alarm

Downstream Filter Alarm

Pump D-1 Status

Pump D-2 Status

HW Radiant Loop Temperature

HW Radiant Loop Differential Pressure

Ex Fan RV-12 Status

Ex Fan RV-12 Static Pressure

CFM Sensors

Output devices:

Outside Air Damper Actuator

Return Air Damper Actuator

Exhaust Air Damper Actuator

HW Valve

CHW Valve

Humidifier Modulating Valve

Humidifier Isolation Valve

Radiant Loop Mixing Valve

Radiant Loop Bypass Valve

Exhaust Fan RV-11 Damper Actuator

VFD's

AHU-8

Thermostats
None
VAVs:
No VAVs

76 Pneumatic Re-Heat Valves

Sensors:

Supply Air Temperature

Supply Air RH

Heat Recovery Discharge Temperature

Return Air Temperature

Return Air RH

Supply Fan Status

Exhaust Fan Status

Outdoor Air Damper Status

Exhaust Air Damper Status

Low Limit

EF-12 Status

Supply Glycol Temperature

Exhaust Glycol Temperature

Pump D-4 Status

Supply Filter Alarm

Exhaust Filter Alarm

Downstream Filter Alarm

Output devices:

Outside Air Damper Actuator

Exhaust Air Damper Actuator

Glycol Valve

HW Valve

CHW Valve

Humidifier Modulating Valve

Humidifier Isolation Valve

EF-12 Damper Actuator

VFD's

BUILDING 26 (MEV):

MEV RTU

Main RTU Controller

DA Temperature Sensor

Duct Pressure Sensor

BUILDING 27 (NUC MEV):

RTU 2

Main RTU Controller, including Heating Controllers, Cooling Controllers and Associated Components

DA/EA/OA Temperature Sensors

ER wheel Leaving Temperature

SA CFM Status

Filter Status

Ex Fan Status

Refrigerant Pressure Transmitter

Supply Fan VFD Status

Supply Fan CFM Status

ARF BUILDING:

ARF Building

25 Re-Heat Coils

10 Exhaust Fans

ARF AHU-1

Primary CHW Coil Temperature

Energy Recovery Coil Temperature

Outside Air Temperature

Secondary CHW Coil Temperature

Discharge RH Sensor

Discharge Air Temperature

Low Limit

Final Filter Status

Pre-Heat Discharge Temperature

Supply Fan Status

Pre-Filter Status

Discharge RH High Limit

Low Pressure Steam (psi)

Output Devices:

Energy Recovery Coil Valve

HW Coil Valve

Primary Cool Coil (DX)

Face/Bypass Damper Actuator

CHW Coil Valve (Hydronic)

Humidifier Valve

ARF AHU-2

Sensors:

Primary CHW Coil Temperature

Energy Recovery Coil Temperature

Outside Air Temperature

Secondary CHW Coil Temperature

Discharge RH Sensor

Discharge Air Temperature

Low Limit final Filter Status

Pre-Heat Discharge Temperature

Supply Fan Status

Pre-Filter Status

Discharge RH high Limit

Low Pressure Steam (psi)

EF-6 Status

EF-11 Air Temperature

EF-11 Fan Status

Cage Wash Status

Cage Wash Hood Status

EF-1 Fan Status

EF-9 Fan Status

Output Devices:

Energy Recovery Coil Valve

HW Coil Valve

Primary Cool Coil (DX)

Face/Bypass Damper Actuator

CHW Coil Valve (Hydronic)

Humidifier Valve

HEAT RECOVERY

Sensors:

ER Pump 1A Status

ER Pump 1B Status

ER Pump 2A Status

ER Pump 2B Status

EF-2 Exhaust Air Temperature

EF-3 Exhaust Air Temperature

EF-5 Exhaust Air Temperature

EF-4 Exhaust Air Temperature

EF-7 Exhaust Air Temperature

EF-8 Exhaust Air Temperature

EF-11 Exhaust Air Temperature

Loop 1 Entering Temperature

Loop 1 Leaving Temperature

Loop 2 Entering Temperature

Loop 2 Leaving Temperature

Output Devices:

Loop 1 ER Valve

Loop 2 ER Valve

ARF DX Chiller

CHW Pump 3A Status

CHW Pump 3B Status

CHW Supply Temperature

CHW Return Temperature

VENTILATION REDUCTION:

Ventilation Reduction Dampers

16x MP580s Total for System

1x MP580 Per Wing for Floors 7 to 10

(so 4x MP580s Per Floors 7 to 10)

Total Number of Dampers = 67

Each Damper has one (1) Damper Actuator Motor and one (1) Damper End Switch to Prove Operation

(about four (4) Dampers Average Per MP580)

BCUs & PCs:

BCU #
Floor
Location
PC Location
1
Chiller Plant
Chiller Plant
Chiller Plant
2
Basement
HVAC Shop
Boiler Plant Control Room
3
5
C501
Boiler Supervisor Office
4
Basement
Core C46
HVAC Shop
5
Basement
Building 67
HVAC Supervisor
6
3
B301
ALC Main Computer Front End including any Hardware and Software Updates
7
7
Core 708
Trane Tracer ES Computers and Server Covered
8
8
Core 809
9
9
Core 907
10
10
MER 1102
11
2
D243
12
11
MER C-Wing
13
Basement
Bldg 27
14
1
C112