SOW APPENDIX A
BASEMENT:
Morgue AHU
| Thermostats |
| None |
| VAVs: |
| No VAVs |
Sensors:
Rm B40-1 Space RH
Rm B41 Space RH
Outside Air Temperature
Discharge Air Temperature
Low Limit
HW Coil Pump FP-1 Status
Supply Fan Status
Pre-Filter Differential Pressure
Post-Filter Differential Pressure
H-1 Duct RH Limit
H-2 Duct RH Limit
Rm B40-1 Occupancy
Rm B41 Occupancy
EF-1 Status
Output Devices:
Zone Damper actuator
Mechanical RM Damper Actuator
H-1 Humidifier Isolation Valve
H-2 Humidifier Isolation Valve
CHW Valve
H-1 Humidifier Modulating Valve
H-2 Humidifier Modulating Valve
Pre-Heat Valve
Kitchen AHU
| Thermostats |
| 3 Electronic |
Sensors:
Zone-1 Space Temperature
Zone-2 Space Temperature
Zone-3 Space Temperature
Face/Bypass Discharge Air Temperature
Outside Air Temperature
Discharge Air Temperature
Low Limit
Supply Fan Status
Pre-Filter Differential Pressure
EF-1 Status
EF-2 Status
EF-3 Status
EF-4 Status
EF-5 Status
Output Devices:
Outside Air Damper Actuator
Zone-1 Damper Actuator
Zone-2 Damper Actuator
Zone-3 Damper Actuator
CHW Valve
Face/Bypass HW Valve
Face/Bypass Damper Actuator
Re-Heat Valve
EF-3 Damper Actuator
SPD AHU (Room D12)
(All Stand Alone Pneumatic)
Sensors:
| Discharge Air Temperature |
| RH Hight Limit |
| Mixed Air Temperature |
| Thermostat Pneumatic |
| Pre-Heat Coil Discharge Air Temperature |
| RH Pneumatic |
Output Devices:
CHW Valve
HW Valve
Damper Actuators
Humidifier Valve
Main Tunnel Monitoring
30- O2, CO2, Temperature and RH Sensors
1ST FLOOR:
AHU-1C Clinic
| Thermostats |
| None |
| VAVs: |
| 28 Pneumatic |
28 Pneumatic Re-Heat Valves
Sensors:
Return Air Temperature
Pre-Heat Coil Discharge Temperature
Mixed Air Temperature
Clinic Space Temperature
HX-1 HW Supply Temperature
Supply Air Temperature
Low Limit
HX-1 HW Return Temperature
Supply Fan Status
Filter Status
Return Fan Status
HW Coil Supply Temperature
HW Coil Return Temperature
HW Pump P-1 Status
HW Pump P-2 Status
Return Static Pressure
HW Coil Pump P-3 Status
HW Coil Pump P-4 Status
CHW Coil Supply Temperature
CHW Coil Return Temperature
Supply Air Static Pressure
CHW Pump P-5 Status
CHW Pump P-6 Status
HX-3 Pump P-4D Status
HX-3 Pump P-5D Status
HX-3 HW Supply Temperature
HX-3 HW Return Temperature
Output Devices:
CHW Valve
HW Coil Valve
HX-1 Steam Valve
HX-2 Steam Valve
HX-3 Steam Valve
Outside Air Damper Actuator
Return Air Damper Actuator
Exhaust Air Damper Actuator
AHU-1D Admitting
| Thermostats |
| None |
| VAVs: |
| 19 Pneumatic |
36 Pneumatic Re-Heat Valves
Sensors:
Return Air Temperature
Pre-Heat Coil Discharge Temperature
Mixed Air Temperature
Discharge Air Temperature
Low Limit
Return Fan Status
Supply Fan Status
Discharge Air Static Pressure
Filter Status
HW Coil Supply Temperature
HW Coil Return Temperature
EF-1D Status
EF-2D Status
EF-3D Status
EF-4D Status
Return Static Pressure
Pump P-1D Status
CHW Coil Supply Temperature
CHW Coil Return Temperature
Output devices:
CHW Valve
HW Valve
Outside Air Damper Actuator
Return Air Damper Actuator
Exhaust Air Damper Actuator
HX Steam Valve
HX HW Valve
ICU AHU & Exhaust Fans
| Thermostats |
| 27 Electronic |
| VAVs: |
| 6 Electronic |
27 Electronic Re-Heat Valves
Sensors:
Heat Recovery Discharge Air Temperature
Face/Bypass Discharge Temperature
Discharge Air RH
Outside Air RH
Outside Air Temperature
Discharge Air Temperature
Low Limit
OA Damper Status
Recovery Pump P-1 Status
Recovery Pump P-2 Status
Supply Fan Status
Pre-Filter Status
Post-Filter Status
Recovery Coil Supply Temperature
HW Coil Supply Temperature
HW Coil Return Temperature
CHW Coil Supply Temperature
CHW Coil Return Temperature
Corridor 213 RH
Corridor 218 RH
EF-1 Discharge Air Temperature
EF-1 Exhaust Air Temperature
EF-1 Exhaust Air RH
EF-1 Recovery Coil Supply Temperature
EF-1 Recovery Coil Return Temperature
EF-1 Fan Status
EF-1 Filter Status
EF-2 Discharge Air Temperature
EF-2 Exhaust Air Temperature
EF-2 Exhaust Air RH
EF-2 Recovery Coil Supply Temperature
EF-2 Recovery Coil Return Temperature
EF-2 Fan Status
EF-2 Filter Status
EF-2 Damper Status
EF-3 Discharge Air Temperature
EF-3 Recovery Coil Supply Temperature
EF-3 Recovery Coil Return Temperature
EF-3 Fan Status
EF-3 Damper Status
Output devices:
Humidifier Isolation Valve
Humidifier Modulating Valve
Heat Recovery Valve
CHW Valve
Face/Bypass Damper Actuator
HW Valve
Outside Air Damper Actuator
Exhaust Air Damper Actuator
Operating Rooms and Support Rooms
There are five (5) ORs that each have the following points:
Occupy Status
5- Pheonix Control Valves including Local Monitors
13-Space Temperature Sensors
13- Humidity Space Sensors
13- OR Air Flow Sensors
13- Reheat Valves
HEPA DP Sensors
APM Status
HEPA Filter DP
Door Status
APM Jam Status
5- Thermostats
CFM Sensors
Room Pressure Sensors
8- Pheonix Control Valves including Nurse Station Remote Monitor
Space Temperature
Humidity Space Sensor
OR Air Flow Sensors
Reheat Valve
Humidifier Valve
APM Status
HEPA Filter DP
Door Status
APM Jam Status
Thermostats
OR AHU-1
Sensors:
Discharge Air RH
EA/OA/MA Damper Status
EA/OA/DA Air Temperature Status
CFM Meters
Filter Status
Supply Fan/Return Fan Status
Low Limit
CHW Supply Temperature
CHW leaving Temperature
HW Supply Temperature
HW Return Temperature
S/R Air Flow Status in CFMs
Output devices:
VFD's
Humidifier Valve
HW Coil Valve
CHW Valves
Humidifier Valve
EA/OA/MA Damper Controller
OR AHU-2
Sensors:
Discharge Air RH
EA/OA/MA Damper Status
EA/OA/DA Air Temperature Status
Filter Status
Supply Fan/Return Fan Status
Low Limit
CHW Supply Temperature
CHW leaving Temperature
HW Supply Temperature
HW Return Temperature
S/R Air Flow Status in CFMs
Output devices:
HW Coil Valve
CHW Valve
Humidifier Valve
EA/OA/MA Damper Controller
Pharmacy AHU-1
Pharmacy has 29 Supply VAVs total, and 16 Exhaust VAVs
AHU-1 and 2 work together
Thermostats 30
VAVs: 45 total
Sensors:
Pre-Heat Coil Discharge Temperature
Discharge Air Temperature
Discharge Air RH mixed Air Temperature low Limit
HW recirc Pump Status
Supply Fan Status
Pre-Filter Status final Filter Status
Return Fan Status
Return Air Temperature
Return Air RH
Return Static Pressure hi-Static Pressure cutout
| low Return Fan Pressure cutout |
| Electronic |
mixed Air Pressure equipment Room Temperature building Static Pressure
Steam heat trace Temperature
Supply Isolation Damper Status
Return Isolation Damper Status
Discharge Air Humidity hi-Limit
Space Humidity
Output devices:
CHW Valve
Pre-Heat Valve
Outside Air Damper Actuator
Return Air Damper Actuator
Exhaust Air Damper Actuator
Humidifier Valve (does both AHU-1 & 2)
Steam Heat Trace Valve
Pharmacy AHU-2
Pharmacy has 29 VAVs total, AHU-1 and 2 work together
Sensors:
Pre-Heat Coil Discharge Temperature
Discharge Air Temperature
Discharge Air RH
Mixed Air Temperature
Low Limit
HW Recirc Pump Status
Supply Fan Status
Pre-Filter Status
Final Filter Status
Return Fan Status
Return Air Temperature
Return Air RH
Return Static Pressure
Hi-Static Pressure Cutout
Low Return Fan Pressure Cutout
Mixed Air Pressure
Equipment Room Temperature
Building Static Pressure
Steam Heat Trace Temperature
Supply Isolation Damper Status
Return Isolation Damper Status
Discharge Air Humidity hi-Limit
Space Humidity
Output devices:
CHW Valve
Pre-Heat Valve
Outside Air Damper Actuator
Return Air Damper Actuator
Exhaust Air Damper Actuator
2ND FLOOR:
Radiology/ X-Ray 2A AHU
| Thermostats |
| None |
| VAVs: |
| Reheats only with Pneumatic Valves |
Sensors:
Discharge Air Temperature
Return Air Temperature
Space Temperature
Low Limit
Supply Fan Status
Output devices:
CHW Valve
AHU-2B Lab (New Unit in the Lab itself)
Sensors:
CHW Coil leaving Temperature
Pre-Heat Coil leaving Temperature
Discharge Air Temperature
Return Air Temperature
Mixed Air Temperature
Low Limit
Supply Fan DP
Supply Fan Status
Filter Status
Exhaust Fan Status
High Static Pressure
Space Static Pressure
Re-Heat Discharge Temperature
Supply Duct RH
Exhaust Fan DP
Space RH
Space Temperature
Output devices:
CHW Valve
Pre-Heat Valve
Re-Heat Valve
Outside Air Damper Actuator
Return Air Damper Actuator
Exhaust Air Damper Actuator
AHU-2B Lab (Old Unit in B201)
| Thermostats |
| 1 |
| VAVs: |
| Reheats Only |
CV Unit is Entirely Stand-Alone Pneumatic with 3 Pneumatic Re-Heat/T-Stats
Fan Only on Main Unit
CHW Valve on Main Unit
PACU AHU (Unit Located on Roof of 2nd Floor)
| Thermostats |
| 10 Electronic |
| VAVs: |
| 7 Electronic |
Plus some Radiant Panels
Sensors:
Discharge Air Temperature
Pre-Heat Coil Discharge Temperature
Mixed Air Temperature
CHW leaving Air Temperature
Outside Air Temperature
Outside Air RH
Low Limit
Return Fan Differential Pressure (CFM)
Supply Fan Differential Pressure (CFM)
Supply Fan Status
Return Fan Status
Pre Filter Status
Mid-Filter Status
Final Filter Status
Return Air Temperature
Return Air RH
HW Pump Status
Exhaust Fan Status
Remote Smoke Damper Status
Output Devices:
CHW Valve
Pre-Heat Valve
Humidifier
Outside Air Damper Actuator
Return Air Damper Actuator
Exhaust Air Damper Actuator
Reheat Valves
3RD FLOOR:
NEW ANGIO AHU
Sensors
Return Air Temperature
Supply Air Temperature
Pre-Heat Temperature
Mix Air Temperature
Cool Temperature
SA CFM
OA CFM
Filter Status
SA SP
SA Humidity
RA Humidity
OA Dmpr Pos
RA Dmpr Pos
PHT vlv Pos
DX Enable
EA Dmpr Pos
Output devices:
CHW Valve
HW Valve
2 RHT Valves
2 DAT Temperature
Eq RM Sensor
3B MICRO AC-1
Sensors:
Outside Air Temperature
HW Supply Temperature
Discharge Air Temperature
Low Limit
3 T-Stats and Reheat Valves
Output devices:
CHW Valve
HW Valve
Outside Air Damper Actuator
Return Air Damper Actuator
Humidifier Valve
Face/Bypass Damper Actuator
HX Steam Valve
3B MICRO AC-2
Unit is 100% Outside Air and CV
Sensors:
Outside Air Temperature
Discharge Air Temperature
Low Limit
Output devices:
CHW Valve
HW Valve
Humidifier Valve
Face/Bypass Damper Actuator
Outside Air Damper Actuator
5TH FLOOR:
AHU-5C
| Thermostats |
| None |
| VAVs: |
| 16 Pneumatic |
39 Pneumatic Reheat Valves (Fin Tube and Reheat Coils)
Sensors:
Discharge Air Temperature
Mixed Air Temperature
Return Air Temperature
Return Air RH
Supply Fan Status
Return Fan Status
Supply Air Static Pressure
Return Air Static Pressure
Low Limit
EF-5C Status
HW Pump P-1 Status
HW Pump P-2 Status
HX-1 Supply water Temperature
HX-1 Return water Temperature
HX-1 Differential Pressure
Output devices:
CHW Valve
Outside Air Damper Actuator
Return Air Damper Actuator
Exhaust Air Damper Actuator
HX Steam Valve
HX bypass Valve
Reheat Valves
AHU-5A-1
| Thermostats |
| None |
7 Pneumatic Reheat Valves
Sensors:
Discharge Air Temperature
Mixed Air Temperature
Return Air Temperature
Return Air RH
Supply Fan Status
Low Limit
Output devices:
Pre-Heat Valve
CHW Valve
HW Valve
Humidifier Valve
Outside Air Damper Actuator
Return Air Damper Actuator
Exhaust Air Damper Actuator
AHU-5A-2
| Thermostats |
| None |
12 Pneumatic Reheat Valves
Sensors:
Discharge Air Temperature
Mixed Air Temperature
Return Air Temperature
Return Air RH
Supply Fan Status
Low Limit
Output devices:
Pre-Heat Valve
CHW Valve
HW Valve
Humidifier Valve
Outside Air Damper Actuator
Return Air Damper Actuator
Exhaust Air Damper Actuator
Reheat Valves
AHU-5A-3
| Thermostats |
| None |
12 Pneumatic Reheat Valves
Sensors:
Discharge Air Temperature
Mixed Air Temperature
Return Air Temperature
Return Air RH
Supply Fan Status
Low Limit
HW Supply Temperature
CHW Supply Temperature
Output devices:
Pre-Heat Valve
CHW Valve
HW Valve
Humidifier Valve
Outside Air Damper Actuator
Return Air Damper Actuator
Exhaust Air Damper Actuator
AHU-5B
| Thermostats |
| None |
33 Pneumatic Reheat Valves
Sensors:
Discharge Air Temperature
Mixed Air Temperature
Return Air Temperature
Return Air RH
Supply Fan Status
Return Fan-1 Status
Return Fan-2 Status
Supply Air RH
Low Limit
Output devices:
HW Valve
CHW Valve
Outside Air Damper Actuator
Return Air Damper Actuator
Exhaust Air Damper Actuator
6TH FLOOR:
AHU-6A Lab
34 Pneumatic VAVs
66 Pneumatic Reheat Valves (Fin Tube included)
Sensors:
Discharge Air Temperature
Outside Air Temperature
Heat Rec. Coil Discharge Temperature
HRC Exhaust Temperature
Mech Rm Space Temperature
Supply Fan Status
EF-2 Status
Glycol Pump P-5 Status
Low Limit
Pre-Filter Differential Pressure
Post-Filter Differential Pressure
EF-2 Pre-Filter Differential Pressure
A603 Space RH
A625 Space RH
A629 Space RH
A602 Space RH
Output devices:
Outside Air Damper Actuator
Mech Room Intake Damper Actuator
Mech Room Exhaust Damper Actuator
H-3 Humidifier Isolation Valve
H-4 Humidifier Isolation Valve
H-5 Humidifier Isolation Valve
H-6 Humidifier Isolation Valve
H-3 Humidifier Modulating Valve
H-4 Humidifier Modulating Valve
H-5 Humidifier Modulating Valve
H-6 Humidifier Modulating Valve
Unit Heater-1 HW Valve
Heat Recovery Coil Valve
HW Valve
CHW Valve
Face/Bypass Damper Actuator
VFD
9TH FLOOR:
AHU-9 Cardiac Cath Lab
| Thermostats |
| 4 Electronic |
| VAVs: |
| No VAVs |
Sensors:
Outside Air Temperature
Outside Air RH
PreFilter Differential Pressure
Mixed Air Temperature
Low Limit
Supply Air Temperature
Supply Air RH
Post-Filter Differential Pressure
802A Room Temperature
802C Room Temperature
802D/Computer Room Temperature
802G Room Temperature
Supply Fan proving
Return Fan proving
Space RH
Return Air Temperature
Output devices:
Outside Air Damper Actuator
Return Air Damper Actuator
Exhaust Air Damper Actuator
CHW Valve
VFD
11TH FLOOR:
AHU-1
| Thermostats |
| 132 Electronic |
| VAVs: |
| 132 Electronic |
132 Pneumatic Re-Heat Valves
Sensors:
Supply Air Temperature
Supply Air RH
Mixed Air Temperature
Return Air Temperature
Return Air RH
Supply Fan Status
Return Fan Status
Discharge Static Pressure
Discharge Differential Pressure
Return Air Differential Pressure
Low Limit
Pre-Filter Alarm
Downstream Filter Alarm
Pump A-1 Status
Pump A-2 Status
HW Radiant Loop Temperature
HW Radiant Loop Differential Pressure
Ex Fan RV-9 Status
Ex Fan RV-9 Static Pressure
CFM Sensors
Output devices:
Outside Air Damper Actuator
Return Air Damper Actuator
Exhaust Air Damper Actuator
HW Valve
CHW Valve
Humidifier Modulating Valve
Humidifier Isolation Valve
Radiant Loop Mixing Valve
Radiant Loop Bypass Valve
Exhaust Fan RV-9 Damper Actuator
VFD's
AHU-2
| Thermostats |
| None |
| VAVs: |
| No VAVs |
20 Pneumatic Re-Heat Valves
| Sensors: |
| 2 CV Boxes |
Supply Air Temperature
Supply Air RH
Heat Recovery Discharge Temperature
Return Air Temperature
Return Air RH
Supply Fan Status
Exhaust Fan Status
Outdoor Air Damper Status
Exhaust Air Damper Status
Low Limit
EF-9 Status
Supply Glycol Temperature
Exhaust Glycol Temperature
Pump A-4 Status
Supply Filter Alarm
Exhaust Filter Alarm
Downstream Filter Alarm
Output devices:
Outside Air Damper Actuator
Exhaust Air Damper Actuator
Glycol Valve
HW Valve
CHW Valve
Humidifier Modulating Valve
Humidifier Isolation Valve
VFD's
AHU-3
| Thermostats |
| 39 Electronic |
| VAVs: |
| 31 Electronic |
39 Pneumatic Re-Heat Valves
Sensors:
Supply Air Temperature
Supply Air RH
Mixed Air Temperature
Return Air Temperature
Return Air RH
Supply Fan Status
Return Fan Status
Discharge Static Pressure
Discharge Differential Pressure
Return Air Differential Pressure
Low Limit
Pre-Filter Alarm
Downstream Filter Alarm
Pump B-1 Status
Pump B-2 Status
HW Radiant Loop Temperature
HW Radiant Loop Differential Pressure
Ex Fan RV-10 Status
Ex Fan RV-10 Static Pressure
Output devices:
Outside Air Damper Actuator
Return Air Damper Actuator
Exhaust Air Damper Actuator
HW Valve
CHW Valve
Humidifier Modulating Valve
Humidifier Isolation Valve
Radiant Loop Mixing Valve
Radiant Loop Bypass Valve
Exhaust Fan RV-10 Damper Actuator
VFD's
AHU-4
| Thermostats |
| None |
| VAVs: |
| No VAVs |
59 Pneumatic Re-Heat Valves
Sensors:
Supply Air Temperature
Supply Air RH
Heat Recovery Discharge Temperature
Return Air Temperature
Return Air RH
Supply Fan Status
Exhaust Fan Status
Outdoor Air Damper Status
Exhaust Air Damper Status
Low Limit
EF-10 Status including 11 Isolation Room Air FLow Monitors
Supply Glycol Temperature
Exhaust Glycol Temperature
Pump B-4 Status
Supply Filter Alarm
Exhaust Filter Alarm
Downstream Filter Alarm
Output devices:
Outside Air Damper Actuator
Exhaust Air Damper Actuator
Glycol Valve
HW Valve
CHW Valve
Humidifier Modulating Valve
Humidifier Isolation Valve
EF-10 Damper Actuator
VFD's
AHU-5
| Thermostats |
| 39 Electronic |
| VAVs: |
| 39 Electronic |
39 Pneumatic Re-Heat Valves
Sensors:
Supply Air Temperature
Supply Air RH
Mixed Air Temperature
Return Air Temperature
Return Air RH
Supply Fan Status
Return Fan Status
Discharge Static Pressure
Discharge Differential Pressure
Return Air Differential Pressure
Low Limit
Pre-Filter Alarm
Downstream Filter Alarm
Pump C-1 Status
Pump C-2 Status
HW Radiant Loop Temperature
HW Radiant Loop Differential Pressure
Ex Fan RV-11 Status
Ex Fan RV-11 Static Pressure
Output devices:
Outside Air Damper Actuator
Return Air Damper Actuator
Exhaust Air Damper Actuator
HW Valve
CHW Valve
Humidifier Modulating Valve
Humidifier Isolation Valve
Radiant Loop Mixing Valve
Radiant Loop Bypass Valve
Exhaust Fan RV-11 Damper Actuator
VFD's
AHU-6
| Thermostats |
| None |
| VAVs: |
| No VAVs |
73 Pneumatic Re-Heat Valves
Sensors:
Supply Air Temperature
Supply Air RH
Heat Recovery Discharge Temperature
Return Air Temperature
Return Air RH
Supply Fan Status
Exhaust Fan Status
Outdoor Air Damper Status
Exhaust Air Damper Status
Low Limit
EF-11 Status
Supply Glycol Temperature
Exhaust Glycol Temperature
Pump B-4 Status
Supply Filter Alarm
Exhaust Filter Alarm
Downstream Filter Alarm
Output devices:
Outside Air Damper Actuator
Exhaust Air Damper Actuator
Glycol Valve
HW Valve
CHW Valve
Humidifier Modulating Valve
Humidifier Isolation Valve
EF-11 Damper Actuator
VFD's
AHU-7
| Thermostats |
| 37 Electronic |
| VAVs: |
| 37 Electronic |
37 Pneumatic Re-Heat Valves
Sensors:
Supply Air Temperature
Supply Air RH
Mixed Air Temperature
Return Air Temperature
Return Air RH
Supply Fan Status
Return Fan Status
Discharge Static Pressure
Discharge Differential Pressure
Return Air Differential Pressure
Low Limit
Pre-Filter Alarm
Downstream Filter Alarm
Pump D-1 Status
Pump D-2 Status
HW Radiant Loop Temperature
HW Radiant Loop Differential Pressure
Ex Fan RV-12 Status
Ex Fan RV-12 Static Pressure
CFM Sensors
Output devices:
Outside Air Damper Actuator
Return Air Damper Actuator
Exhaust Air Damper Actuator
HW Valve
CHW Valve
Humidifier Modulating Valve
Humidifier Isolation Valve
Radiant Loop Mixing Valve
Radiant Loop Bypass Valve
Exhaust Fan RV-11 Damper Actuator
VFD's
AHU-8
| Thermostats |
| None |
| VAVs: |
| No VAVs |
76 Pneumatic Re-Heat Valves
Sensors:
Supply Air Temperature
Supply Air RH
Heat Recovery Discharge Temperature
Return Air Temperature
Return Air RH
Supply Fan Status
Exhaust Fan Status
Outdoor Air Damper Status
Exhaust Air Damper Status
Low Limit
EF-12 Status
Supply Glycol Temperature
Exhaust Glycol Temperature
Pump D-4 Status
Supply Filter Alarm
Exhaust Filter Alarm
Downstream Filter Alarm
Output devices:
Outside Air Damper Actuator
Exhaust Air Damper Actuator
Glycol Valve
HW Valve
CHW Valve
Humidifier Modulating Valve
Humidifier Isolation Valve
EF-12 Damper Actuator
VFD's
BUILDING 26 (MEV):
MEV RTU
Main RTU Controller
DA Temperature Sensor
Duct Pressure Sensor
BUILDING 27 (NUC MEV):
RTU 2
Main RTU Controller, including Heating Controllers, Cooling Controllers and Associated Components
DA/EA/OA Temperature Sensors
ER wheel Leaving Temperature
SA CFM Status
Filter Status
Ex Fan Status
Refrigerant Pressure Transmitter
Supply Fan VFD Status
Supply Fan CFM Status
ARF BUILDING:
ARF Building
25 Re-Heat Coils
10 Exhaust Fans
ARF AHU-1
Primary CHW Coil Temperature
Energy Recovery Coil Temperature
Outside Air Temperature
Secondary CHW Coil Temperature
Discharge RH Sensor
Discharge Air Temperature
Low Limit
Final Filter Status
Pre-Heat Discharge Temperature
Supply Fan Status
Pre-Filter Status
Discharge RH High Limit
Low Pressure Steam (psi)
Output Devices:
Energy Recovery Coil Valve
HW Coil Valve
Primary Cool Coil (DX)
Face/Bypass Damper Actuator
CHW Coil Valve (Hydronic)
Humidifier Valve
ARF AHU-2
Sensors:
Primary CHW Coil Temperature
Energy Recovery Coil Temperature
Outside Air Temperature
Secondary CHW Coil Temperature
Discharge RH Sensor
Discharge Air Temperature
Low Limit final Filter Status
Pre-Heat Discharge Temperature
Supply Fan Status
Pre-Filter Status
Discharge RH high Limit
Low Pressure Steam (psi)
EF-6 Status
EF-11 Air Temperature
EF-11 Fan Status
Cage Wash Status
Cage Wash Hood Status
EF-1 Fan Status
EF-9 Fan Status
Output Devices:
Energy Recovery Coil Valve
HW Coil Valve
Primary Cool Coil (DX)
Face/Bypass Damper Actuator
CHW Coil Valve (Hydronic)
Humidifier Valve
HEAT RECOVERY
Sensors:
ER Pump 1A Status
ER Pump 1B Status
ER Pump 2A Status
ER Pump 2B Status
EF-2 Exhaust Air Temperature
EF-3 Exhaust Air Temperature
EF-5 Exhaust Air Temperature
EF-4 Exhaust Air Temperature
EF-7 Exhaust Air Temperature
EF-8 Exhaust Air Temperature
EF-11 Exhaust Air Temperature
Loop 1 Entering Temperature
Loop 1 Leaving Temperature
Loop 2 Entering Temperature
Loop 2 Leaving Temperature
Output Devices:
Loop 1 ER Valve
Loop 2 ER Valve
ARF DX Chiller
CHW Pump 3A Status
CHW Pump 3B Status
CHW Supply Temperature
CHW Return Temperature
VENTILATION REDUCTION:
Ventilation Reduction Dampers
16x MP580s Total for System
1x MP580 Per Wing for Floors 7 to 10
(so 4x MP580s Per Floors 7 to 10)
Total Number of Dampers = 67
Each Damper has one (1) Damper Actuator Motor and one (1) Damper End Switch to Prove Operation
(about four (4) Dampers Average Per MP580)
BCUs & PCs:
| BCU # |
| Floor |
| Location |
| PC Location |
| 1 |
| Chiller Plant |
| Chiller Plant |
| Chiller Plant |
| 2 |
| Basement |
| HVAC Shop |
| Boiler Plant Control Room |
| 3 |
| 5 |
| C501 |
| Boiler Supervisor Office |
| 4 |
| Basement |
| Core C46 |
| HVAC Shop |
| 5 |
| Basement |
| Building 67 |
| HVAC Supervisor |
| 6 |
| 3 |
| B301 |
| ALC Main Computer Front End including any Hardware and Software Updates |
| 7 |
| 7 |
| Core 708 |
| Trane Tracer ES Computers and Server Covered |
| 8 |
| 8 |
| Core 809 |
| 9 |
| 9 |
| Core 907 |
| 10 |
| 10 |
| MER 1102 |
| 11 |
| 2 |
| D243 |
| 12 |
| 11 |
| MER C-Wing |
| 13 |
| Basement |
| Bldg 27 |
| 14 |
| 1 |
| C112 |