This document contains details for a federal solicitation from the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 22. The solicitation number is 36C26223B0013 and seeks proposals to modernize the supply chain in Building 1's basement for Project No. 664-21-301. An attachment provides three drawings related to the project scope. Interested offerors should review all provided documents for requirements and specifications prior to submitting a response for the work sought.

View the file

Other files for this federal contract opportunity

Show all 19

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FOR CONSTRUCTION

56 of 61 191

57 of 61 191

58 of 61 191

59 of 61 191

61 of 61 191

45 MIN

45 MIN

45 MIN

45 MIN

45 MIN

G E N E R A L S T R U C T U R A L N O T E S (G.S.N.)

STRUCTURAL OBSERVATION

GENERAL

DESIGN CRITERIA

MEP COORDINATION

FOUNDATION:

SHEET LIST

SHEET DESCRIPTION

ITEM STAGE

ITEMS TO BE ANCHORED TO THE BUILDING:

LOCATION

SUBMITTAL ITEM

CONCRETE

STEEL

COLD-FORMED STEEL

SHOP DRAWINGS / SUBMITTALS SPECIAL INSPECTION

SOIL: SPECIAL INSPECTION TASK

- X

CONCRETE: SPECIAL INSPECTION TASK

- X

STRUCTURAL STEEL: QUALITY ASSURANCE (QA) SPECIAL INSPECTION

PER AISC 360, CHAPTER N AND AISC 341, CHAPTER J

VA SAN DIEGO CA

on e ei gh th i nc h o ne f oo t th re e in ch es o ne f oo t 6"

6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t

6" 6" th re e qu ar te rs i nc h o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t

654321

A

B

C

D

E

A

B

C

D

E

654321

VA FORM 08-6231

100% CONSTRUCTION DOCUMENTS

- - 23 FEB, 2022 - -

CHAIN MANAGEMENT

MODERNIZE SUPPLY

BLDG. 1 - BASEMENT

664-21-301 Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

Office of Construction and Real Estate Management

Dwg. of

CONSULTANTS: ARCHITECT/ENGINEERS:

4849 Ronson Court, Suite 200 San Diego, CA 92111

858.344.8900 S1.1003131 Camino Del Rio North, Suite 1080

San Diego, California 92108

(619) 521-8500 Fax (619) 521-8591 www.kpff.com kpff project #2100127

P:

\1

\2

VA

S

U

PP

LY

C

H A

IN

\D

W G

\S 1.

.D W

G 2/

/2

1:

:4

PM

Exp. 9/30/22 No. S4775RE

G

IS

TE

RED PROFESS IONAL ENG

INEER

STATE OF CAL I FORN IA

FA

R I D MOHSEN

I

S T R U C T U R A L

GENERAL STRUCTURAL NOTES

http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com

(G.S.N. CONTINUED)

POST-INSTALLED CONCRETE ANCHORS

CONSTRUCTION JOINTSCONCRETE

MEMBER

COMPRESSIVE

STRENGTH

28 DAY U.N.O.

(PSI)

MAX

DENSITY

(PCF)

MAX

W/C

RATIO

MAX

SHRINKAGE (%)

(NOTE 4)

EXPOSURE

CATEGORY

REINFORCING STEEL

VA SAN DIEGO CA

on e ei gh th i nc h o ne f oo t th re e in ch es o ne f oo t 6"

6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t

6" 6" th re e qu ar te rs i nc h o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t

654321

A

B

C

D

E

A

B

C

D

E

654321

VA FORM 08-6231

100% CONSTRUCTION DOCUMENTS

- - 23 FEB, 2022 - -

CHAIN MANAGEMENT

MODERNIZE SUPPLY

BLDG. 1 - BASEMENT

664-21-301 Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

Office of Construction and Real Estate Management

Dwg. of

CONSULTANTS: ARCHITECT/ENGINEERS:

4849 Ronson Court, Suite 200 San Diego, CA 92111

858.344.8900 S1.1013131 Camino Del Rio North, Suite 1080

San Diego, California 92108

(619) 521-8500 Fax (619) 521-8591 www.kpff.com kpff project #2100127

P:

\1

\2

VA

S

U

PP

LY

C

H A

IN

\D

W G

\S 1.

1.

D W

G 2/

/2

1:

:5

PM

Exp. 9/30/22 No. S4775RE

G

IS

TE

RED PROFESS IONAL ENG

INEER

STATE OF CAL I FORN IA

FA

R I D MOHSEN

I

S T R U C T U R A L

GENERAL STRUCTURAL NOTES

http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com

(G.S.N. CONTINUED)

STEEL DECK

HEADED STUDS COLD-FORMED STEEL (a.k.a. METAL STUD)

IDENTIFICATION

COLD-FORMED STEEL (a.k.a. METAL STUDS)STRUCTURAL STEEL

DESCRIPTION ASTM DESIGNATION

VA SAN DIEGO CA

on e ei gh th i nc h o ne f oo t th re e in ch es o ne f oo t 6"

6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t

6" 6" th re e qu ar te rs i nc h o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t

654321

A

B

C

D

E

A

B

C

D

E

654321

VA FORM 08-6231

100% CONSTRUCTION DOCUMENTS

- - 23 FEB, 2022 - -

CHAIN MANAGEMENT

MODERNIZE SUPPLY

BLDG. 1 - BASEMENT

664-21-301 Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

Office of Construction and Real Estate Management

Dwg. of

CONSULTANTS: ARCHITECT/ENGINEERS:

4849 Ronson Court, Suite 200 San Diego, CA 92111

858.344.8900 S1.1023131 Camino Del Rio North, Suite 1080

San Diego, California 92108

(619) 521-8500 Fax (619) 521-8591 www.kpff.com kpff project #2100127

P:

\1

\2

VA

S

U

PP

LY

C

H A

IN

\D

W G

\S 1.

2.

D W

G 2/

/2

1:

:5

PM

Exp. 9/30/22 No. S4775RE

G

IS

TE

RED PROFESS IONAL ENG

INEER

STATE OF CAL I FORN IA

FA

R I D MOHSEN

I

S T R U C T U R A L

GENERAL STRUCTURAL NOTES

http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com

4.2 5 5.1 6 7

SHRINKING

WRAPPER

BREAKDOWN

PLATFORM - FRAMING PLAN

4.2 4.9 5.1 6.1

Q.2

R.1

PLATFORM - LOADING DOCK FOUNDATION PLAN

4.2 4.9 5.1 6.1

Q.2

R.1

4.2 5 5.1 6 7

SHRINKING

WRAPPER

BREAKDOWN

GRADE BEAM SCHEDULE

4.2 5 5.1 6 7

SHRINKING

WRAPPER

BREAKDOWN

PLATFORM - CEILING FRAMING PLAN

4.2 4.9 5.1 6.1

Q.2

R.1

DUCT

AHU

PARAPET

PLATFORM

COLUMN

NEW FOOTING

(E) FOOTING

3' -6

'-3

6' -3

'-7

4' -5

1 2"

1'-6"

4'-51 2"

48" CLR.

T.O.C.

SECTION1

Q.2R.1

VA SAN DIEGO CA

on e ei gh th i nc h o ne f oo t th re e in ch es o ne f oo t 6"

6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t

6" 6" th re e qu ar te rs i nc h o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t

654321

A

B

C

D

E

A

B

C

D

E

654321

VA FORM 08-6231

100% CONSTRUCTION DOCUMENTS

- - 23 FEB, 2022 - -

CHAIN MANAGEMENT

MODERNIZE SUPPLY

BLDG. 1 - BASEMENT

664-21-301 Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

Office of Construction and Real Estate Management

Dwg. of

CONSULTANTS: ARCHITECT/ENGINEERS:

4849 Ronson Court, Suite 200 San Diego, CA 92111

858.344.8900 S2.2003131 Camino Del Rio North, Suite 1080

San Diego, California 92108

(619) 521-8500 Fax (619) 521-8591 www.kpff.com kpff project #2100127

P:

\1

\2

VA

S

U

PP

LY

C

H A

IN

\D

W G

\S 2.

0.

D W

G 2/

/2

2:

:0

PM

Exp. 9/30/22 No. S4775RE

G

IS

TE

RED PROFESS IONAL ENG

INEER

STATE OF CAL I FORN IA

FA

R I D MOHSEN

I

S T R U C T U R A L

PLATFORM LOADING DOCK PLANS

AND SECTION

http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com

SECTION1 SECTION2

4.24.95.16.1

DUCT

AHU

PARAPET

PLATFORM

COLUMN

NEW FOOTING

(E) FOOTING

3' -6

'-3

6' -3

'-7

4' -5

1 2"

1'-6"

4'-51 2"

48" CLR.

T.O.C.

Q.2R.1

VA SAN DIEGO CA

on e ei gh th i nc h o ne f oo t th re e in ch es o ne f oo t 6"

6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t

6" 6" th re e qu ar te rs i nc h o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t

654321

A

B

C

D

E

A

B

C

D

E

654321

VA FORM 08-6231

100% CONSTRUCTION DOCUMENTS

- - 23 FEB, 2022 - -

CHAIN MANAGEMENT

MODERNIZE SUPPLY

BLDG. 1 - BASEMENT

664-21-301 Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

Office of Construction and Real Estate Management

Dwg. of

CONSULTANTS: ARCHITECT/ENGINEERS:

4849 Ronson Court, Suite 200 San Diego, CA 92111

858.344.8900 S3.3003131 Camino Del Rio North, Suite 1080

San Diego, California 92108

(619) 521-8500 Fax (619) 521-8591 www.kpff.com kpff project #2100127

P:

\1

\2

VA

S

U

PP

LY

C

H A

IN

\D

W G

\S 3.

0.

D W

G 2/

/2

1:

:2

PM

Exp. 9/30/22 No. S4775RE

G

IS

TE

RED PROFESS IONAL ENG

INEER

STATE OF CAL I FORN IA

FA

R I D MOHSEN

I

S T R U C T U R A L

SECTIONS

http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com

1 COLUMN BASE PLATE DETAIL

A

A

DECK PERPENDICULAR TO BEAM

DECK PARALLEL TO BEAM

COMPOSITE METAL DECK SCHEDULE16

PLAN

SECTION

A

B

TYPICAL BOLTED BEAM CONNECTION DETAIL3

STANDARD BOLTED CONNECTION SCHEDULE

AT ONE-SIDED CONNECTIONS AT TWO-SIDED CONNECTIONS

LATERAL BRACE DETAIL9

AT IN-LINE PARALLEL BEAM

14 COLUMN CLOSURE PLATE DETAIL

CONT 316"PL

CONC OVER MTL

DECK PER PLAN

BEAM PER PLAN

(2) 1/2"x8"

STUDS 16" OC

#3 @ 16"

(LOCATE BAR WITHIN 6"

MAX OF TYPICAL SLAB BAR

CONT #4 MIN AT HOOK

TYP BAR PER PLAN,

EXTEND TO WITHIN

4" OF BENT PLATE

STUDS AND CLIPS

PER

3/16 2-12

19 TYPICAL EDGE OF DECK

VA SAN DIEGO CA

on e ei gh th i nc h o ne f oo t th re e in ch es o ne f oo t 6"

6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t

6" 6" th re e qu ar te rs i nc h o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t

654321

A

B

C

D

E

A

B

C

D

E

654321

VA FORM 08-6231

100% CONSTRUCTION DOCUMENTS

- - 23 FEB, 2022 - -

CHAIN MANAGEMENT

MODERNIZE SUPPLY

BLDG. 1 - BASEMENT

664-21-301 Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

Office of Construction and Real Estate Management

Dwg. of

CONSULTANTS: ARCHITECT/ENGINEERS:

4849 Ronson Court, Suite 200 San Diego, CA 92111

858.344.8900 S4.4003131 Camino Del Rio North, Suite 1080

San Diego, California 92108

(619) 521-8500 Fax (619) 521-8591 www.kpff.com kpff project #2100127

P:

\1

\2

VA

S

U

PP

LY

C

H A

IN

\D

W G

\S 4.

0.

D W

G 2/

/2

1:

:3

PM

Exp. 9/30/22 No. S4775RE

G

IS

TE

RED PROFESS IONAL ENG

INEER

STATE OF CAL I FORN IA

FA

R I D MOHSEN

I

S T R U C T U R A L

DECK AND STEEL DETAILS

http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com

LAYOUT OF HEADED STUDS4

TYP. ROOF PENETRATION AT DRAIN9

PERPENDICULAR TO DECK

PARALLEL TO DECK

SECTION X

JOINT PERPENDICULAR TO DECK

JOINT PARALLEL TO DECKA

B

CONSTRUCTION JOINT IN COMPOSITE DECK8

TYPICAL OPENINGS IN COMPOSITE METAL DECK16

PLAN

SECTION D

SECTION E

SECTION F

SECTION G

PLAN

PLAN

MEMBER TO MEMBER CONNECTION AROUND OPENINGH

PLACEMENT AND SPACING OF OPENINGSA

SMALL OPENINGS IN COMPOSITE METAL DECKB

LARGE OPENINGS IN COMPOSITE METAL DECKC

DETAILA DETAILA

AHU-77 ANCHORAGE19

PLAN

A

AHU-78 ANCHORAGE20

PLAN

A

VA SAN DIEGO CA

on e ei gh th i nc h o ne f oo t th re e in ch es o ne f oo t 6"

6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t

6" 6" th re e qu ar te rs i nc h o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t

654321

A

B

C

D

E

A

B

C

D

E

654321

VA FORM 08-6231

100% CONSTRUCTION DOCUMENTS

- - 23 FEB, 2022 - -

CHAIN MANAGEMENT

MODERNIZE SUPPLY

BLDG. 1 - BASEMENT

664-21-301 Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

Office of Construction and Real Estate Management

Dwg. of

CONSULTANTS: ARCHITECT/ENGINEERS:

4849 Ronson Court, Suite 200 San Diego, CA 92111

858.344.8900 S4.4013131 Camino Del Rio North, Suite 1080

San Diego, California 92108

(619) 521-8500 Fax (619) 521-8591 www.kpff.com kpff project #2100127

P:

\1

\2

VA

S

U

PP

LY

C

H A

IN

\D

W G

\S 4.

1.

D W

G 2/

/2

1:

:3

PM

Exp. 9/30/22 No. S4775RE

G

IS

TE

RED PROFESS IONAL ENG

INEER

STATE OF CAL I FORN IA

FA

R I D MOHSEN

I

S T R U C T U R A L

DECK AND STEEL DETAILS

http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com

16 GRADE BEAM AT LOADING DOCK LEVER18

TIE RAMP DETAIL2 TYP NEW OPENING IN EXISTING CONC WALL4

A

B

4.2

PILASTER TO LOW GRADE BEAM15

PEDESTAL DETAILA

4.2

A

DETAIL NOTE6

4.2

Q.2

Q.1

14GRADE BEAM AT (E) COLUMN13

5.1

Q.2

Q.1

PEDESTAL AND GRADE BEAM AT (E) COLUMN

GRADE BEAM AT LOADING DOCK LEVER

A

PLAN

GRADE BEAM AT LOADING DOCK RETAINING WALL20

TIE CONCRETE RETAINING WALL (AT RAMP)1

GRID

VA SAN DIEGO CA

on e ei gh th i nc h o ne f oo t th re e in ch es o ne f oo t 6"

6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t

6" 6" th re e qu ar te rs i nc h o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t

654321

A

B

C

D

E

A

B

C

D

E

654321

VA FORM 08-6231

100% CONSTRUCTION DOCUMENTS

- - 23 FEB, 2022 - -

CHAIN MANAGEMENT

MODERNIZE SUPPLY

BLDG. 1 - BASEMENT

664-21-301 Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

Office of Construction and Real Estate Management

Dwg. of

CONSULTANTS: ARCHITECT/ENGINEERS:

4849 Ronson Court, Suite 200 San Diego, CA 92111

858.344.8900 S4.4023131 Camino Del Rio North, Suite 1080

San Diego, California 92108

(619) 521-8500 Fax (619) 521-8591 www.kpff.com kpff project #2100127

P:

\1

\2

VA

S

U

PP

LY

C

H A

IN

\D

W G

\S 4.

2.

D W

G 2/

/2

1:

:3

PM

Exp. 9/30/22 No. S4775RE

G

IS

TE

RED PROFESS IONAL ENG

INEER

STATE OF CAL I FORN IA

FA

R I D MOHSEN

I

S T R U C T U R A L

FOUNDATION DETAILS

http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com

TYPICAL STIFFENER PLATE DETAIL18

PLAN

MOMENT FRAME CONNECTION

DETAIL4

PLAN

B

DETAILA B

A

HSS TO WF TUBE COLUMN9

DETAILA

A

B

HEADER DETAILB

CANTILEVER HSS DETAIL14

TYP EXT STUD TO EDGE OF DECK20

A

A

ELEVATION AT DISCONTINUOUS COLUMN

TYPICAL BOLTED FLANGE PLATE DETAIL

PARAPET WALL SUPPORT19

GRID

VA SAN DIEGO CA

on e ei gh th i nc h o ne f oo t th re e in ch es o ne f oo t 6"

6" on e an d on e ha lf in ch es o ne f oo t on e in ch o ne f oo t

6" 6" th re e qu ar te rs i nc h o ne f oo t on e ha lf in ch o ne f oo t th re e ei gh th s in ch o ne f oo t on e qu ar te r in ch o ne f oo t

654321

A

B

C

D

E

A

B

C

D

E

654321

VA FORM 08-6231

100% CONSTRUCTION DOCUMENTS

- - 23 FEB, 2022 - -

CHAIN MANAGEMENT

MODERNIZE SUPPLY

BLDG. 1 - BASEMENT

664-21-301 Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

Office of Construction and Real Estate Management

Dwg. of

CONSULTANTS: ARCHITECT/ENGINEERS:

4849 Ronson Court, Suite 200 San Diego, CA 92111

858.344.8900 S4.4033131 Camino Del Rio North, Suite 1080

San Diego, California 92108

(619) 521-8500 Fax (619) 521-8591 www.kpff.com kpff project #2100127

P:

\1

\2

VA

S

U

PP

LY

C

H A

IN

\D

W G

\S 4.

3.

D W

G 2/

/2

1:

:4

PM

Exp. 9/30/22 No. S4775RE

G

IS

TE

RED PROFESS IONAL ENG

INEER

STATE OF CAL I FORN IA

FA

R I D MOHSEN

I

S T R U C T U R A L

MOMENT FRAME AND MISC STEEL

DETAILS

http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com http://www.kpff.com

M1.001 MECHANICAL LEGENDS AND NOTES

M1.002 MECHANICAL SCHEDULES

M1.003 MECHANICAL SCHEDULES

M1.200 BASEMENT MECHANICAL – OVERALL AND ZONING PLAN

M2.100 PHASE 1 BASEMENT MECHANICAL FLOOR PLAN

M2.101 PHASE 1 BASEMENT PIPING FLOOR PLAN

M2.102 PHASE 1 FIRST FLOOR MECHANICAL FLOOR PLAN

M2.300 PHASE 3 BASEMENT MECHANICAL DEMOLITION PLAN

M2.301 PHASE 3 BASEMENT MECHANICAL DEMOLITION PLAN

M2.302 PHASE 3 BASEMENT MECHANICAL FLOOR PLAN

M2.303 PHASE 3 BASEMENT MECHANICAL FLOOR PLAN

M2.304 PHASE 3 BASEMENT PIPING FLOOR PLAN

M2.305 PHASE 3 BASEMENT PIPING FLOOR PLAN

M2.400 PHASE 4 BASEMENT MECHANICAL DEMOLITION PLAN

M2.401 PHASE 4 BASEMENT MECHANICAL FLOOR PLAN

M2.500 PHASE 5 BASEMENT MECHANICAL DEMOLITION PLAN

M2.501 PHASE 5 BASEMENT MECHANICAL FLOOR PLAN

M2.502 PHASE 5 BASEMENT MECHANICAL PIPING PLAN

M2.600 PHASE 6 BASEMENT MECHANICAL DEMOLITION PLAN

M2.601 PHASE 6 BASEMENT MECHANICAL FLOOR PLAN

M2.700 PHASE 7 BASEMENT MECHANICAL DEMOLITION PLAN

M2.701 PHASE 7 BASEMENT MECHANICAL FLOOR PLAN

M2.702 PHASE 7 BASEMENT MECHANICAL PIPING PLAN

M3.100 MECHANICAL DETAILS

M3.101 MECHANICAL DETAILS

M3.102 MECHANICAL CONTROLS

TRANSFER ASSEMBLY (CEILING WITH FLEX DUCT)

TRANSFER ASSEMBLY (CEILING WITH LINED DUCT)

TRANSFER ASSEMBLY (WALL)

NEW DUCTWORK (1ST NUMBER INDICATES

MECHANICAL LEGEND

RETURN REGISTER / GRILLE

SUPPLY REGISTER WITH EXTRACTOR

DUCT TRANSITION (RECTANGULAR TO ROUND)

DUCT TRANSITION (RECTANGULAR OR ROUND)

EXHAUST REGISTER OR GRILLE

CEILING DIFFUSER

EXHAUST AIR DUCT

RETURN AIR DUCT/OUTSIDE AIR DUCT

SUPPLY AIR DUCT

ACCESS DOOR/ACCESS PANEL

FLEXIBLE DUCTWORK

WALL REGISTER OR GRILLE

RECTANGULAR DUCT DOWN

RECTANGULAR DUCT UP

ROUND DUCT DOWN

ROUND DUCT UP

DUCT DROP

DUCT RISE

FLEXIBLE CONNECTION TO EQUIPMENT

COMBINATION FIRE AND SMOKE DAMPER

MOTOR OPERATED DAMPER

LINED DUCTWORK (OR PLENUM)

SMOKE DAMPER

SQUARE ELBOW WITH TURNING VANES

ROUND ELBOW OR RECTANGULAR RADIUS ELBOW

MANUAL VOLUME DAMPER

UNION

DRAIN

DIRECTION OF SLOPE DOWN

BLIND FLANGE

PRESSURE RELIEF VALVE

PRESSURE GAUGE WITH GAUGE COCK

STRAINER WITH DRAIN VALVE AND HOSE END

THERMOMETER/TEMPERATURE GAUGE

RISE OR RISER

DOWN OR DROP

CAPPED LINE

DIFFERENTIAL

COMBINATION BALANCING VALVE

BALL VALVE

BUTTERFLY VALVE

MOTORIZED BUTTERFLY VALVE

FLEXIBLE CONNECTION (PIPE)

ECCENTRIC REDUCER

CONCENTRIC REDUCER

VALVE ON RISE OR DROP

OVERFLOW DRAIN PIPE

THERMOSTAT

HUMIDISTAT

UNDER CUT (DOOR 1/2'')

DOOR LOUVER

AUTOMATIC FLOW CONTROL VALVE

PIPE ANCHOR

HEATING HOT WATER RETURN

HEATING HOT WATER SUPPLY

PIPE DOWN

PIPE UP

DIRECTION OF FLOW IN PIPE

PIPE TO FLOOR SINK

PIPE RISE

PIPE GUIDE

CONTROL VALVE (2-WAY)

CHECK VALVE

BALANCING

GLOBE VALVE

GATE VALVE/SHUT-OFF VALVE

PRESSURE REDUCING VALVE

CONTROL VALVE (3-WAY)

POINT OF CONNECTION

ABBREV. DESCRIPTION SYMBOL DESCRIPTION

MECHANICAL ABBREVIATIONS

EF EXHAUST FAN

SYSTEM

SYMBOL

TOTAL

VALVE

VOLT

THERMOSTAT

TEMPERATURE

VOLUME

TERMINAL UNIT

VARIABLE FREQUENCY DRIVE

TURNING VANES

UNLESS NOTED OTHERWISE

UNDERGROUND

TOP OF PIPE

TOP OF DUCT

TEMPERATURE TRANSMITTER

VARIABLE AIR VOLUME

VERTICAL

VACUUM

TYPICAL

TEMPERATURE DIFFERENCE

WATT

LEVEL

EQUIPMENT

OPERATIONS AND MAINTENANCE

WET-BULB

WATER

WEIGHT

WITHOUT

LOW PRESSURE RETURN

LOW PRESSURE STEAM

LEAVING WATER TEMPERATURE

LEAVING AIR TEMPERATURE

MANUAL BALANCING DAMPER

1000 BTU PER HOUR

LENGTH, LONG

LONG RADIUS ELBOW

MAX

MBD

MECH

MBH

MIN MINIMUM

MECHANICAL

MAXIMUM

LPR

LBS

LF

LWT

LRE

LPS

KW

LAT

LG

LINEAR FEET

KILOWATT

POUNDS

VOL

HEAT RECOVERY COIL

HEATING WATER SUPPLY

HEATING WATER RETURN

HUMIDITY TRANSMITTER

HEATING, VENTILATING & AIR

INCH, INCHES

INSIDE DIAMETER

HORSE POWER

HEATING COIL

GALVANIZED SHEET METAL

HEAT PUMP UNIT

GRAVITY RELIEF

HS HAND SWITCH

HVAC

HRC

HHWS

HHWR

ID

IN

HT

HPU

GSM

HGT

HD

HC

HP

HR

GR

HSTAT

HEIGHT

HEAD

HOUR(S)

HUMIDISTAT

EQUIP

O&M

W/O

LVL

WTR

WT

WB

W

FLAT ON BOTTOM

ENTERING WATER TEMPERATURE

EXHAUST GRILLE

FIBERGLASS REINFORCED PLASTIC

GALLONS PER MINUTE

GALLONS PER HOUR

ELEC. WATER COOLER

DEGREES FAHRENHEIT

GAGE OR GAUGE

FEET PER MINUTE

GPM

GPH

FPM

FOB

GA

FT

FIN

FD

FLR

FRP

FS

FOOT, FEET

FINISH

FLOOR

FLOOR SINK

FIRE DAMPER

EWT

EWC

EXH

°F

EG

EXHAUST

VA

VAV

VFD

VERT

VAC

V

TV

TU

UNO

UG

TOP

TOD

TEMP

TT

TYP

TOT

SYM

SYS

TSTAT

ΔT

NOT TO SCALE

NORMALLY OPEN

NOT IN CONTRACT

NORMALLY CLOSED

NOT APPLICABLE

OWNER FURNISHED, CONTRACTOR

OUTSIDE AIR

OUTSIDE DIAMETER

OPPOSED BLADE DAMPER

RETURN GRILLE

RETURN AIR DUCT

POINT OF CONNECTION

REHEAT COIL

RELATIVE HUMIDITY

RETURN OR RELIEF FAN

RETURN/EXHAUST FAN

PHASE (ELECTRICAL)

PRESSURE DROP OR DIFFERENTIAL

PRESSURE

POUNDS PER SQUARE INCH

ROUND OR DIAMETER

RETURN AIR

REVOLUTIONS PER MINUTE

PSI GAGE

SUPPLY GRILLE

STANDARD

STAINLESS STEEL

SIDEWALL RETURN

SIDEWALL EXHAUST

SIDEWALL DIFFUSER

SPECIFICATION

SUPPLY AIR

SUPPLY FAN

STATIC PRESSURE

SQUARE

SECOND

PUMP

ALT ALTITUDE

RF

ENTERING AIR TEMPERATURE

INDIRECT DRAIN

CLEAN OUT TO GRADE

COEFFICIENT, VALVE FLOW

CONDENSATE PUMP

CONTINUATION

DRY-BULBDB

DBL

DRN

(E)

EA

EAT

DN

DIA

DRAIN

EXISTING

EXHAUST AIR

DOUBLE

DOWN

DIAMETER

COTG

CONT

CONN

CMPR

D

CV

CP

CONNECTION

COMPRESSOR

SD

SP

SS

SR

SQ

SPEC

STD

SEC

SF

SE

SG

SA

RHC

RPM

RH

RG

BACKDRAFT DAMPER

CHILLED WATER SUPPLY

CHILLED WATER RETURN

CUBIC FEET PER MINUTE

BRITISH THERMAL UNIT

CEILING GRILLE, CENTER OF GRAVITY

COOLING COIL

BTU PER HOUR

BRAKE HORSEPOWER (BOILER HP)

BOTTOM OF DUCT

BOTTOM OF PIPE

BELOW GRADE

BELOW FLOOR

AIR SEPARATOR

BTUH

BDD

CHWS

CHWR

CFM

CL

CG

CC

CENTERLINE

APPROX

AVG

AUTO

BTU

BOD

BOP

BHP

BF

BG

B

AS

BOILER

AUTOMATIC

AVERAGE

APPROXIMATE

RA

RAD

R/EF

PSIG

PSI

POC

PH

PRESS

P

ΔP

OA

OFCI

OD

OBD

ACID FLOOR CLEANOUT

ABOVE FINISHED FLOOR

ABOVE FINISH CEILING

AIR HANDLING UNIT

AIR CONDITIONING

ACCESS DOOR

AFC

AHU

AFCO

AC

AD

AFF

N/A

NIC

NTS

NO

NC

CO CLEAN OUT

CLR CLEAR

CONC CONCRETE

CONTRACTORCONTR

EFF EFFICIENCY

ELEVATIONELEV

ENTERINGENT

EXTERNAL STATIC PRESSUREESP

FAN COIL UNITFCU

FLA FULL LOAD AMP

GALLONSGAL

GALVANIZEDGALV

HEATINGHTG

LEAVINGLVG

LOCKED ROTOR AMPSLRA

MFG MANUFACTURER

PLUMBINGPLBG

REQUIREDREQD

RETURNRET

RUNNING LOAD AMPSRLA

SENSIBLESENS

VELOCITYVEL

AMS AIR MONITORING STATION

MANUAL OPERATED DAMPERMOD

MANUAL VOLUME DAMPERMVD

FSD COMBINATION FIRE & SMOKE DAMPER

ACCESS PANELAP

TEMPERATURE DIFFERENCE

AV AIR VENT

SMOKE DETECTOR

TERMINAL BOX

FFU FAN FILTER UNIT

DESCRIPTIONSYMBOL

CHILLED WATER SUPPLY

CHILLED WATER RETURN

REHEAT WATER SUPPLY

COMPRESSED AIR

INSTRUMENT TEST CONNECTION

STRAINER WITH BLOWDOWN

AIR ELIMINATOR/VACUUM BREAKER

CIRCUIT SETTER

EXPANSION JOINT

FLOW SWITCH

GATE, ANGLE

THROW ARROW

BOTTOM OF STEELBOS

PUMPED CONDENSATE RETURNPC

REHEAT WATER RETURN

LOW PRESSURE STEAM CONDENSATELPC

CLEAN OUT

OVERHEADOH

PRESSURE DROP INDICATORPDI

ANALOG INPUTAI

ANALOG OUTPUTAO

DIGITAL INPUTDI

FAIL OPENFO

TEST WELL (PETE'S PLUG - PRESSURE AND/OR

TEMPERATURE)

TRIPLE DUTY VALVE (COMBINATION SHUT-OFF,

CHECK AND GLOBE, ANGLE

ABBREV. DESCRIPTION

FLEXIBLE DUCT WITH SPIN-IN FITTING AND

DAMPER

TERMINAL BOX WITH REHEAT

STEELSTL

ABOVEABV

UNDERCUTUC

OVERFLOW CONDENSATE DRAIN

EXISTING DUCT OR PIPE

EXISTING TO BE REMOVED

EXISTING TO BE ABANDONED IN PLACE

DUCT MATERIALS SHALL COMPLY WITH SECTION 603 OF I.E.C.C.

PROVIDE DUCT MANUAL VOLUME DAMPERS IN EACH BRANCH DUCT AND IN EACH MAIN DUCT TO PROVIDE FOR COMPLETE AIR BALANCE OF THE SYSTEM. PROVIDE ADEQUATE ACCESS AND IDENTIFICATION.

ALL DUCTWORK AND PIPING SHALL BE INSULATED CONSISTENTLY WITH THE REQUIREMENTS OF SECTION

ROOM THERMOSTATS SHALL BE CAPABLE OF BEING SET TO MAINTAIN SPACE TEMPERATURE SET POINTS FROM 55 °F. TO 85 °F. AND BE CAPABLE OF OPERATING THE HEATING AND COOLING IN SEQUENCE.

THERMOSTATS SHALL BE ADJUSTABLE TO PROVIDE A TEMPERATURE RANGE OF UP TO 10°F. BETWEEN FULL HEATING AND FULL COOLING BEING SUPPLIED. CONTROLS SHALL HAVE CAPABILITY OF TERMINATING ALL HEATING AT A TEMPERATURE NOT MORE THAN 70 °F. AND COOLING AT A TEMPERATURE NOT LESS

TEMPERATURE CONTROL SYSTEM SHALL OPERATE IN ACCORDANCE WITH THE BASE BUILDING SEQUENCE OF

WALL MOUNTED THERMOSTATS SHALL BE MOUNTED 48" A.F.F. TEMPERATURE SENSORS SHALL BE WALL

PROVIDE SMOKE DETECTORS AT HVAC SYSTEMS EXCEEDING 2,000 CFM AT MAIN SUPPLY

DUCT. PROVIDE DUCT SMOKE DETECTORS LOCATED AT EACH STORY FOR RETURN AIR SYSTEMS WHICH

SEE PLUMBING DRAWINGS FOR PRIMARY AND SECONDARY CONDENSATE DRAINS .

NO COMBUSTION VENTS, DRYER VENTS, RANGE HOOD VENTS, OR HEATING DUCTS ARE PERMITTED IN AREA

MATERIAL EXPOSED WITHIN A DUCT OR PLENUM SHALL COMPLY WITH SECTION 602 I.M.C.

ALL OUTLETS FOR FUTURE CONNECTIONS SHALL BE INSTALLED SO AS TO PERMIT EASY CONNECTION.

COORDINATE DUCTWORK, STRUCTURAL CONDITIONS AND ARCHITECTURAL LAYOUT.

SEE ARCHITECTURAL DRAWINGS FOR ROOF ACCESS AND ADDITIONAL ENERGY CONSERVATION NOTES.

SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT LOCATION OF CEILING DIFFUSERS AND GRILLES.

ALL CEILING DIFFUSERS SHALL BE 4-WAY THROW UNLESS SHOWN OTHERWISE.

ALL H.V.A.C. SYSTEMS SHALL MEET THE REQUIREMENTS PER SECTION 503 I.E.C.C.

ALL H.V.A.C. PIPING SHALL MEET THE REQUIREMENTS PER SECTION 504 I.E.C.C.

SERVE MORE THAN ONE STORY AND EXCEED 15,000 CFM - PER NFPA 90A 6.4.2.1.

SEPARATION WALLS.

MINIMUM OUTDOOR AIR REQUIREMENTS : 15 C.F.M. / PERSON.

AIRCRAFT CABLE SHALL BE PRE-STRETCHED.

MOUNTED 48" A.F.F.

604 OF I.E.C.C.

OPERATION.

THAN 78 °F.

ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE CODES ADOPTED BY THE DEPARTMENT OF VETERAN

CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION AND PROVIDE REPAIR OF ADJACENT EXISTING

SURFACES, EQUIPMENT, AREAS, AND PROPERTY THAT MAY BE DAMAGED AS A RESULT OF ANY

ALL DRAWINGS ARE CONSIDERED TO BE PART OF THE CONTRACT DOCUMENTS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REVIEW AND COORDINATION OF ALL DRAWINGS PRIOR TO ANY CONSTRUCTION, INCLUDING ARCHITECTURAL, STRUCTURAL, AIR CONDITIONING, PLUMBING, AND ELECTRICAL. ANY DISCREPANCIES THAT OCCUR SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER PRIOR TO THE START OF CONSTRUCTION SO THAT A CLARIFICATION MAY BE ISSUED. ANY WORK PERFORMED IN CONFLICT

WITH THE CONTRACT DOCUMENTS OR ANY CODE REQUIREMENT SHALL BE CORRECTED BY THE

CONTRACTOR AT HIS OWN EXPENSE, AND AT NO EXPENSE TO THE OWNER.

DO NOT SCALE DRAWINGS - ALL DIMENSIONS AND JOB SITE CONDITIONS SHALL BE VERIFIED BY THE

CONTRACTOR AT THE JOB SITE PRIOR TO BID SUBMITTAL, START OF CONSTRUCTION AND / OR FABRICATION OF MATERIALS. IF DISCREPANCIES ARE ENCOUNTERED, THE ENGINEER SHALL BE NOTIFIED FOR

CONTRACTOR SHALL COORDINATE ALL DUCT, PIPE AND EQUIPMENT LOCATIONS WITH PLUMBING, ALL DUCTWORK SHALL BE CONSTRUCTED, ERECTED & TESTED IN ACCORDANCE WITH THE MOST

RESTRICTIVE OF LOCAL REGULATIONS AND PROCEDURES DETAILED IN THE A.S.H.R.A.E. HANDBOOK OF FUNDAMENTALS OR THE APPLICABLE STANDARDS ADOPTED BY S.M.A.C.N.A. PROVIDE RECTANGULAR DUCTS

OF GALVANIZED STEEL & PREFABRICATED SPIRAL LOCKSEAM DUCTS AND FITTINGS.

DEMOLITION AND/OR NEW WORK.

ELECTRICAL, STRUCTURAL, AND ALL OTHER TRADES.

CLARIFICATION.

AFFAIRS.

26.

25.

22.

23.

21.

20.

19.

18.

17.

16.

14.

15.

13.

11.

10.

9.

8.

7.

6.

5.

4.

1.

2.

3.

ELECTRICAL INTERLOCK BETWEEN AIR HANDLING UNIT AND EXHAUST AIR TO BE PROVIDED.12.

MECHANICAL GENERAL NOTES

OR FLOW INDICATOR

CONDITIONING

Ø

OWNER FURNISHED, OWNEROFOI

INSTALLED

INSTALLED

SIDE SHOWN)

MECHANICAL SHEET INDEX

POINT OF DISCONNECTION

27.

28.

SEISMIC BRACING AND RESTRAINT/SUPPORTS ARE REQUIRED PER SPECIFICATION SECTION 13 05 41.

ALL DUCTWORK IN SCOPE AND CONNECTED TO SYSTEM WILL BE CLEANED PER SPECIFICATION SECTION 23 01 30.52.

THE CONTRACTOR SHALL FURNISH ALL MATERIALS, LABOR, EQUIPMENT, TRANSPORTATION, AND SERVICES NECESSARY FOR THE COMPLETION OF THE WORK. ALL MATERIALS & WORK SHALL BE IN COMPLIANCE WITH

ALL APPLICABLE CODES AND GOVERNING REGULATIONS.

100% CONSTRUCTION DOCUMENTS

4849 Ronson Court, Suite 200 San Diego, CA 92111 858.344.8900

10680 TREENA ST# 163 320 San Diego, CA 92123 858-368-8630 Fax 866-517-3293 www.dce-inc.net

EF

EF

X

1 BASEMENT

EXISTING

CONDENSER

AREA

BASEMENT FORKLIFT

CHARGING

EXHAUST FAN SCHEDULE

UNIT NO. MFR. &

MODEL NO.

COOK 300 QMX

COOK

ACW-B

COOK

SQN-HP

BASEMENTBASEMENT

LOCATION SERVICE FAN TYPE

INLINE

SIDEWALL

INLINE 8540

16000

C.F.M. T.S.P.

(IN. WG.)

1.5

.5

1.25 BELT

BELT

BELT

DRIVE FAN

R.P.M.

811 460/3/60

460/3/60

460/3/60

V./PH./HZ.

ELECTRICAL

HP

7.5

1/4

5 7.6

.5

FLA

WEIGHT

(LBS.)

REMARKS

EXISTING FOR REFERENCE

AC

(E)

AC

6770AC

DAIKIN

OAH019GDGM ROOF BASEMENT WAREHOUSE

MFR. &

MODEL NO.UNIT NO.

2F DECK

BASEMENT CEILING BASEMENT OFFICES & IT

CENTRAL SUPPLY

SERVICELOCATION

C.F.M.

SUPPLY FAN

T.S.P (in.)

E.S.P (in.) DRIVE C.F.M.

RETURN FAN

T.S.P (in.)

E.S.P (in.) DRIVE TOTAL

MBH

SENS.

MBH D.b.

E.A.T.(°F) W.b. D.b.

L.A.T.(°F) W.b.

COOLING COILS

GPM

W.P.D.

(ft.hd.)

AIR HANDLING UNIT SCHEDULE

E.W.T (°F)

L.W.T (°F)

SENS.

MBH D.b.

E.A.T.(°F) D.b.

L.A.T.(°F)

HEATING COILS

GPM

W.P.D.

(ft.hd.)

E.W.T (°F)

L.W.T

(°F) HP

ELECTRICAL (SUPPLY FAN)

FLA MCA V/PH/HZ HP FLA MCA V/PH/HZ

ELECTRICAL (RETURN FAN)

FILTER

FILTERS

QTY.

EACH

OPER.

WEIGHT

(LBS.)

O.A.

(CFM) REMARKS

50%

100%8/8

2/2

15/10(E) 30% AND 85% EFF.

MERV 8 / MERV 14

MERV 8 / MERV 14460/3/60

460/3/60-

-12

-15

10460/3/60

460/3/60

460/3/60-

-23.5

6.6

-15

5.0

20150

1800.1

-18

5.855

45124.0

53855

4510.2

4.4

12.663.0

17.6

10357.8

53.9

53.754.7

54.4

60.867

80518

61.5

252.9322.3

88.5

728-

DIRECT2.5

2.598300

DIRECT

DIRECT3.5

2.5

-5.1

5.61

6.958300

20500 EXISTING FOR REFERENCE

DAIKIN

CAH006GDAC

2700AC

DAIKIN

CAH012GDAC ROOF

BASEMENT STERILE

CONSUMABLES 50%5/5MERV 8 / MERV 14----460/3/60-17.515-------55456.144.053.954.86780151.8221.8----DIRECT4.57.735500

EF

MED-GAS

STORAGE

MED-GAS

STORAGE

COOK

ACW-HP SIDEWALL 500 .5 BELT 1444 460/3/60 1/4 .5 93

(E)

PROVIDE SPARK 'A' CONSTRUCTION

PROVIDE SPARK 'A' CONSTRUCTION

SF

1 BASEMENT

EXISTING

CONDENSER

AREA

SUPPLY FAN SCHEDULE

UNIT NO. MFR. &

MODEL NO.

COOK

DB

LOCATION SERVICE FAN TYPE

INLINE 8300

C.F.M. T.S.P.

(IN. WG.)

1.0 BELT

DRIVE FAN

R.P.M.

693 460/3/60

V./PH./HZ.

ELECTRICAL

HP

5 -

FLA

WEIGHT

(LBS.)

REMARKS

CONTROL VALVES

UNIT

NO. SERVICE REMARKS(in)

SIZE

(gpm)

FLOW

Cv (psig) P.D.

TYPE

BODY

51.21/2 2.8

REHEAT COIL 1.81/2 .8 5

MANUFACTURER &

MODEL No.

BELIMO

BELIMO

CCV-B209

BELIMO

CCV-B207 51/2 .7 .3

REHEAT COILCCV-B210

BELIMO

CCV-B208 51/2 1.0 .46REHEAT COIL

REHEAT COIL 2-WAY

2-WAY

2-WAY

2-WAY

51.91/2 4.2BELIMO REHEAT COILCCV-B211 2-WAY

531/2 6.8BELIMO REHEAT COILCCV-B212 2-WAY

CV

CV

CV

CV

CV

CV

54.73/4 11BELIMO REHEAT COILCCV-B217 2-WAY

CV

EXHAUST TERMINAL BOX SCHEDULE

EV

1-1N

A 900 0.2 12 12 27 20 -

UNIT

NO.

MFR &

MODEL NO. TYPE MAX.

C.F.M.

MIN. SP

DROP

(IN. W.C.)

INLET

SIZE

(IN)

SOUND

LEVEL

(NC)

WEIGHT REMARKS

OUTLET

SIZE

(IN)

PHOENIX

THERIS

EV

1-7N

A 280 0.2 8 8 27 20 -PHOENIX

THERIS

EV

1-7E

A 220 0.2 8 8 27 20 EXISTING TO REMAIN, REBALANCE TO LISTED CFMPHOENIX

THERIS

EV

1-10E

A 225 0.2 8 8 27 20 EXISTING TO REMAIN, REBALANCE TO LISTED CFMPHOENIX

THERIS

FACTORY PROVIDED VFD. UNIT FURNISHED WITH INTERNAL VIBRATION

ISOLATORS. COOLING COIL WITH COPPER TUBE AND COPPER FINS. FACTORY

PROVIDED 4" BASE RAIL.

FACTORY PROVIDED VFD'S. UNIT FURNISHED WITH INTERNAL VIBRATION ISOLATORS.

COOLING COIL WITH COPPER TUBE AND COPPER FINS. PROVIDE 16" TALL FACTORY

ROOF CURB.

2-WAY CHARACTERIZED CONTROL VALVE, MODULATING TYPE.

PROVIDE WITH ELECTRONIC ACTUATOR.

57.41 18BELIMO AC-72 COOLING COILCCV-B222 2-WAY

CV

5292 65BELIMO AC-77 COOLING COILCCV-B248 2-WAY

CV

5291-1/2 45BELIMO AC-78 COOLING COILCCV-B239 2-WAY

CV

2-WAY CHARACTERIZED CONTROL VALVE, MODULATING TYPE.

PROVIDE WITH ELECTRONIC ACTUATOR.

2-WAY CHARACTERIZED CONTROL VALVE, MODULATING TYPE.

PROVIDE WITH ELECTRONIC ACTUATOR.

2-WAY CHARACTERIZED CONTROL VALVE, MODULATING TYPE.

PROVIDE WITH ELECTRONIC ACTUATOR.

2-WAY CHARACTERIZED CONTROL VALVE, MODULATING TYPE.

PROVIDE WITH ELECTRONIC ACTUATOR.

2-WAY CHARACTERIZED CONTROL VALVE, MODULATING TYPE.

PROVIDE WITH ELECTRONIC ACTUATOR.

2-WAY CHARACTERIZED CONTROL VALVE, MODULATING TYPE.

PROVIDE WITH ELECTRONIC ACTUATOR.

2-WAY CHARACTERIZED CONTROL VALVE, MODULATING TYPE.

PROVIDE WITH ELECTRONIC ACTUATOR.

2-WAY CHARACTERIZED CONTROL VALVE, MODULATING TYPE.

PROVIDE WITH ELECTRONIC ACTUATOR.

2-WAY CHARACTERIZED CONTROL VALVE, MODULATING TYPE.

PROVIDE WITH ELECTRONIC ACTUATOR.

EV

1-12E

A 475 0.2 10 10 27 20 EXISTING TO REMAIN, REBALANCE TO LISTED CFMPHOENIX

THERIS

EV

1-14E

A 900 0.2 12 12 27 20 EXISTING TO REMAIN, REBALANCE TO LISTED CFMPHOENIX

THERIS

EV

1-11E

A 1700 0.2 14 14 27 20 EXISTING TO REMAIN, REBALANCE TO LISTED CFMPHOENIX

THERIS

54.73/4 11BELIMO AC-77 HEATING COILCCV-B217 2-WAY

CV

2-WAY CHARACTERIZED CONTROL VALVE, MODULATING TYPE.

PROVIDE WITH ELECTRONIC ACTUATOR.

FACTORY PROVIDED VFD'S. UNIT FURNISHED WITH INTERNAL VIBRATION ISOLATORS.

COOLING COIL WITH COPPER TUBE AND COPPER FINS. PROVIDE 16" TALL FACTORY

ROOF CURB.

100% CONSTRUCTION DOCUMENTS

4849 Ronson Court, Suite 200 San Diego, CA 92111 858.344.8900

10680 TREENA ST# 163 320 San Diego, CA 92123 858-368-8630 Fax 866-517-3293 www.dce-inc.net

PROVIDE SUPPORT AT EACH

END OF UNIT PER 1/M3.101

1 FACTORY PROVIDED 30% FILTER AND BACKDRAFT DAMPER. 2 PROVIDE SUPPORT AT EACH END OF UNIT PER 1/M3.101

1 2

AIR DISTRIBUTION SCHEDULE

REMARKSMAKE &

MODELTAG

STEEL MODULAR CORE DIFFUSER, ADJUSTABLE PATTERN. T-BAR LAY-IN OR HARD CEILING.

ROUND OR SQUARE NECK. SEE FLOOR PLANS FOR NECK SIZES. TYPICAL DIFFUSER UNLESS NOTED OTHERWISE.

ASMCD IS ALUMINUM FACE FOR TOILET AND CANOPY AREA.

STEEL RETURN REGISTER. 3/4" BLADE SPACING, 35° FIXED DEFLECTION. T-BAR LAY-IN OR HARD CEILING.

ROUND OR SQUARE NECK. SEE FLOOR PLANS FOR NECK SIZES. TYPICAL CEILING RETURN/EXHASUT

GRILLE, UNLESS NOTED OTHERWISE. ALUMINUM FACE FOR TOILET AND CANOPY AREA.

FACE

SIZE

TITUS - 350RL STEEL RETURN GRILLE, 3/4" BLADE SPACING, 35° FIXED DEFLECTION.

BLADES PARALLEL TO LONG DIMENSION. NO OPPOSED BLADE DAMPER. ALUMINUM FACE FOR OUTDOOR

AREA

TITUS - MCD

TITUS - PAR

24x24, 12x12

24X24, 12x12

AS INDICATED

ON PLANS

C

D

DIFFUSER NECK SIZE (SUPPLY)

EXHAUST

REGISTER

SUPPLY AIR

DIFFUSER

REGISTER

RETURN

AIRFLOW (CFM)

AIRFLOW (CFM)

AIRFLOW (CFM)

REGISTER NECK SIZE (RETURN)

REGISTER NECK SIZE (EXHAUST)

DIFFUSERS

SLOT & BAR

AIR DISTRIBUTION LEGEND

PLENUM NECK SIZE (SUPPLY/RETURN)

AIRFLOW (CFM)

B

A

MECHANICAL NOTE

ALL HVAC SYSTEM CONTROLS SHALL BE INTERFACED WITH THE EXISTING BUILDING AUTOMATION SYSTEM/CONTROLS (BAS/CONTROLS) JOHNSON METASYS CONTROLS, EXISTING DIRECT DIGITAL CONTROLS (DDC), AND NETWORK AUTOMATION ENGINE (NAE). HVAC SYSTEM GRAPHICS SHALL BE DEVELOPED AND INCORPORATED INTO EXISTING JOHNSON METASYS BAC. ALL HVAC SYSTEMS SHALL BE COMPATIBLE WITH

THE EXISTING BUILDING AUTOMATION CONTROLS.

TITUS - 300R STEEL SUPPLY GRILLE, 3/4" BLADE SPACING, 35° FIXED DEFLECTION.

BLADES PARALLEL TO LONG DIMENSION. NO OPPOSED BLADE DAMPER.

AS INDICATED

ON PLANS

100% CONSTRUCTION DOCUMENTS

4849 Ronson Court, Suite 200 San Diego, CA 92111 858.344.8900

10680 TREENA ST# 163 320 San Diego, CA 92123 858-368-8630 Fax 866-517-3293 www.dce-inc.net

1 RATED FOR INDOOR USE, 22 GA FILLED WITH GLASS FIBER.

SOUND ATTENUATOR SCHEDULE

UNIT NO. MANUFACTURER MODEL NO. SERVICE AIRFLOW

(C.F.M.)

DUCT

TYPE W H L

FACE

VELOCITY

(F.P.M.)

PD (in.

w.g.)

ATTENUATION IN OCTAVE BAND (dB) OPER. WT.

(LBS.) REMARKS

63 125 250 500 1000 2000 4000 8000 SA-1 IAC 5UGS AC-102 2,200 SUPPLY 24" 24" 60" 550 0.12" 6 11 24 44 46 45 38 23 158 1

UP

145 SF

LOUNGE

B114

173 SF

OFFICE,

TECHNICIAN

B114A

167 SF

OFFICE,

STAFF

B115

415 SF

CORRIDOR

B117

655 SF

LOBBY

B100

422 SF

LOBBY

B101

293 SF

OFFICE,

TECHNICIAN

B141

201 SF

OFFICE,

TECHNICIAN

B142

214 SF

LAB

B142A

144 SF

OFFICE,

TECHNICIAN

B142B

124 SF

OFFICE,

TECHNICIAN

B142D

294 SF

OFFICE,

TECHNICIAN

B142E

343 SF

LAB

B143

179 SF

LOUNGE

B144

122 SF

CORRIDOR

B141A

564 SF

LOCKER,

WOMEN'S

B144A

396 SF

TOILET,

FEMALE

B146

435 SF

OFFICE

B147

243 SF

LOCKER,

MEN'S

B148

188 SF

LOUNGE

B149

699 SF

LOCKER,

MEN'S

B149A

38 SF

MECHANICAL

ROOM

B149B

549 SF

PHARMACY

B145

265 SF

CORRIDOR

B140

364 SF

CONFERENCE

ROOM

B152

113 SF

OFFICE,

STAFF

B152A

106 SF

OFFICE,

STAFF

B152B

99 SF

OFFICE,

STAFF

B152C

150 SF

OFFICE,

STAFF

B152D

135 SF

OFFICE,

STAFF

B152E

105 SF

STORAGE,

WARD

SUPPLIES

B153

317 SF

CORRIDOR

B154

396 SF

OFFICE,

STAFF

B155

132 SF

OFFICE

B155A

114 SF

OFFICE, ASST.

CHIEF

B155B

257 SF

OFFICE, CHIEF

B155C

138 SF

CORRIDOR

B155E

1727 SF

STORAGE,

WARD

SUPPLIES

B156

360 SF

LAB

B156A

156 SF

STORAGE,

WARD

SUPPLIES

B157

STAIRWELL

B158

91 SF

OFFICE

B159B

90 SF

OFFICE

B159A

91 SF

OFFICE

B159

611 SF

CLOSET,

TELEPHONE

B165

152 SF

STORAGE,

EQUIPMENT

B165A

737 SF

MECHANICAL

ROOM

B166

670 SF

CLOSET,

TELEPHONE

B167 1051 SF

ELECTRICAL

ROOM

B231

645 SF

OFFICE,

TECHNICIAN

B232

474 SF

OFFICE,

TECHNICIAN

B233

222 SF

OFFICE,

TECHNICIAN

B234

183 SF

REFRIGERATOR,

WALK-IN

B235

689 SF

MORGUE

B236

61 SF

HOUSEKEEPING

AID CLOSET

B237

79 SF

CORRIDOR

B238

262 SF

CORRIDOR

B239

708 SF

CORRIDOR

B240

133 SF

OFFICE,

STAFF

B241

86 SF

TOILET, MALE

B242

86 SF

TOILET,

FEMALE

B243

191 SF

STORAGE,

GENERAL

B244

263 SF

MORGUE

B245

160 SF

CORRIDOR

B246

212 SF

OFFICE,

TECHNICIAN

B232A

187 SF

OFFICE,

TECHNICIAN

B232B

3133 SF

MECHANICAL

ROOM

B251

850 SF

CORRIDOR

B1211266 SF

CORRIDOR

B125

210 SF

STAIRWELL

SW9-B-1

198 SF

MECHANICAL

ROOM

B180

408 SF

CORRIDOR

B177B

1174 SF

CORRIDOR

B117B

3565 SF

STORAGE,

GENERAL

B177-1

140 SF

STORAGE,

GENERAL

B172

127 SF

STORAGE,

EQUIPMENT

B172B

130 SF

OFFICE

B171C

103 SF

B171D

384 SF

BUILDING

SERVICES

B171B

57 SF

JANITOR

100 SF

STORAGE,

GENERAL

B172D

116 SF

TOILET,

FEMALE

99 SF

TOILET, MALE

B173

184 SF

HALLWAY

B-SPS-28

136 SF

LOUNGE

B174A

92 SF

FEMALE

LOCKERS

B174B

97 SF

LOCKER,

MEN'S

B174C

98 SF

TOILET, MALE

156 53 SF

JANITOR

B174E

215 SF

ETO

B-SPS-13

165 SF

CART WASH

TRANSFER

131 SF

AUTOMATIC

CARTWASH

B171H

314 SF

STERILE

STORAGE

B171G

697 SF

STORAGE

AREA

228 SF

STORAGE,

EQUIPMENT

B102B

1923 SF

STORAGE,

GENERAL

B191K

286 SF

BREAK

B175

23 SF

CLOSET

78 SF

BREAK

1303 SF

SPS/O.R.

SUPPLY

B175

121 SF

STORAGE,

GENERAL

B196

109 SF

PET ELEV

S5-B-1

659 SF

UTILITY

ROOM,

SOILED

B194

190 SF

SHOP, A/C

B190A

347 SF

SHOP, A/C

B254

142 SF

SHOP, A/C

B253

122 SF

OFFICE,

TECHNICIAN

B252

641 SF

SHOP, ELEC.

B255

68 SF

TOILET,

FEMALE

B191B

70 SF

TOILET, MALE

B191A

102 SF

SHOP, PAINT

B189A

97 SF

CORRIDOR

B212A

517 SF

CORRIDOR

B191M

893 SF

CORRIDOR

B191R

488 SF

CORRIDOR

B212B

1746 SF

STORAGE,

GENERAL

141 SF

OFFICE

123 SF

OFFICE

1035 SF

STORAGE,

GENERAL

B191G

819 SF

STORAGE,

GENERAL

B191J

899 SF

STORAGE,

GENERAL

B191I

214 SF

STORAGE,

GENERAL

B191E

80 SF

STORAGE,

GENERAL

B191D

332 SF

BIOMED

ENGINEERING

B191P

109 SF

OFFICE

B215B

107 SF

UTILITY

ROOM, CLEAN

B223A

1567 SF

STAGING

AREA

B223C

232 SF

OFFICE,

TECHNICIAN

B218

197 SF

STORAGE,

GENERAL

B220

235 SF

OFFICE,

TECHNICIAN

B223B

251 SF

UTILITY

ROOM,

SOILED

B224

159 SF

OFFICE,

TECHNICIAN

B230

144 SF

TOILET, MALE

B222

650 SF

UTILITY

ROOM,

SOILED

B216

283 SF

UTILITY

ROOM,

SOILED

B217A

536 SF

OFFICE,

STAFF

B172C

1035 SF

STORAGE,

EQUIPMENT

B217

53 SF

CLOSET,

TELEPHONE

B217B

70 SF

MECHANICAL

ROOM

B217C

1033 SF

OFFICE

B213

138 SF

OFFICE,

TECHNICIAN

B211

136 SF

OFFICE

B214

278 SF

MECHANICAL

ROOM

B210C

136 SF

OFFICE,

TECHNICIAN

B210A

20 SF

MECHANICAL

ROOM

B210B

831 SF

SHOP,

CARPENTER

B210

744 SF

SHOP, ELEC.

B198

87 SF

OFFICE,

STAFF

B198A

658 SF

SHOP, PAINT

B189

237 SF

OFFICE,

TECHNICIAN

B205

158 SF

OFFICE,

TECHNICIAN

B206

86 SF

STORAGE,

GENERAL

B189B

227 SF

OFFICE,

TECHNICIAN

B202

405 SF

OFFICE

B201

68 SF

STORAGE,

GENERAL

B201A

87 SF

STORAGE,

GENERAL

B201B

57 SF

STORAGE,

EQUIPMENT

B200A

202 SF

MECHANICAL

ROOM

B140A

165 SF

KITCHEN,

MISC.

B182

403 SF

KITCHEN,

MISC.

B184

239 SF

KITCHEN,

MISC.

B186

69 SF

UTILITY

ROOM,

SOILED

B187

175 SF

OFFICE,

STAFF

B127

161 SF

OFFICE

B126D

30 SF

UTILITY ROOM

SOILED

B120

225 SF

288 SF

OFFICE

B162

68 SF

CORRIDOR

B232C

260 SF

ELEVATORS

268 SF

KITCHEN,

MISC.

B183

911 SF

OFFICE,

STAFF

B110

287 SF

REFRIGERATOR,

WALK-IN

B137

249 SF

REFRIGERATOR,

WALK-IN

B138

373 SF

REFRIGERATOR,

WALK-IN

B181

230 SF

REFRIGERATOR,

WALK-IN

B136

160 SF

OFFICE,

STAFF

B129

150 SF

OFFICE,

STAFF

B130

47 SF

STORAGE,

GENERAL

B219

293 SF

STAIRWELL

SW6-B-1

267 SF

CORRIDOR

B212B

160 SF

DIETETICS

RESIDENTS

B115A

457 SF

OFFICE,

TECHNICIAN

B247

240 SF

OFFICE,

STAFF

B160

49 SF

CORRIDOR

B154

280 SF

CORRIDOR

135 SF

LOCKER,

MEN'S

B172E

383 SF

CORRIDOR

B174

413 SF

STORAGE,

FILE ROOM

B134

112 SF

IT

B135

108 SF

TOILET,

FEMALE

B133

95 SF

TOILET, MALE

B125A

154 SF

CORRIDOR

B125C

116 SF

OFFICE,

TECHNICIAN

B132

117 SF

OFFICE

B126C

87 SF

OFFICE

B126B

115 SF

OFFICE,

STAFF

B126A

176 SF

OFFICE,

STAFF

B131

124 SF

OFFICE

B127A

408 SF

CLASS ROOM

B126

180 SF

CLINICAL

NUTRITION

MANAGER

B128A

222 SF

OFFICE

B128C

30 SF

CLOSET

39 SF

STORAGE,

GENERAL

B195B

1321 SF

CORRIDOR

131 SF

TOILET,

CONGREGATE

B104

296 SF

UTILITY

ROOM,

SOILED

B102A

76 SF

DRESSING

ROOM

B144B

538 SF

MECHANICAL

ROOM

B200

1400 SF

OFFICE

B215

36 SF

CLOSET

793 SF

ELECTRICAL

B118

386 SF

EQUIPMENT

STORAGE

B128B

69 SF

B190E

293 SF

STAIRWELL

SW7-B-1

293 SF

STAIRWELL

SW8-B-1

6670 SF

KITCHEN,

DIETETICS

B128

148 SF

B229

97 SF

STAIRWELL

SW13-B-1

148 SF

EMS BREAK

B108C

497 SF

STORAGE,

EQUIPMENT

B108A/B

49 SF

MECHANICAL

ROOM

B108

229 SF

ENGINEERING/IT

B-SPS-48

463 SF

CORRIDOR

B224A

923 SF

CORRIDOR

B212

339 SF

CORRIDOR

B225

935 SF

CORRIDOR

B109

50 SF

HAC

B135A

293 SF

STAIRWELL

SW1-B-1

144 SF

OFFICE

B128D

418 SF

UTILITY

ROOM,

SOILED

B102

92 SF

ELEVATOR

S3

96 SF

ELEVATOR

S1

2398 SF

STERILE

STORAGE

CART

HOLDING

AREA

B172C

489 SF

STORAGE

1298 SF

STORAGE,

GENERAL

B191F

2636 SF

TEXTILE CARE

UNIT

B223

234 SF

KITCHEN,

MISC.

B183A

237 SF

KITCHEN,

MISC.

B185

998 SF

UTILITY

ROOM,

SOILED

B122397 SF

KITCHEN MISC

B123

490 SF

CART WASH

B119

115 SF

OFFICE,

STAFF

B249

30 SF

CLOSET,

TELEPHONE

B230A

88 SF

ELEVATOR

S2

92 SF

ELEVATOR

S4

2353 SF

STORAGE,

EQUIPMENT

B191

102 SF

STORAGE,

GENERAL

B195C

61 SF

UTILITY

ROOM, CLEAN

B223D

104 SF

FIRE PUMP

889 SF

SHOP, A/C

B190

99 SF

TOILET,

FEMALE

B-SPS-9

199 SF

BB191M

107 SF

STORAGE

KITCHEN

EQUIPMENT

S

R

Q.1

Q

P

O.1

O

N.7

N.6

N.5

N.4

N.2

N

M

L.1

L

K

J.4

J.5

J.1

J

H

1 2 2.1 3' 3.1 3.2 4 4.2 5 5.1 6 7 7.1 8 9 9.1 9.5 9.4 10 11 11.1 12 13 13.3 14 14.1 15 15.1 15.3 16 16.116.3 17 18

T

T

T T

T

T

T

T

T

T

T T

T

T

T

T

THERMOSTAT FOR

ZONE TEMPERATURE

CONTROL (TYP.)

DESIGNATES AREA COVERED

WITHIN TEMPERATURE

CONTROL ZONE (TYP.)

T

T

T

T

TCAV-1

CAV-2

CAV-3

CAV-8

CAV-18A

CAV-18B

CAV-5

CAV-7

CAV-4

CAV-9

CAV-20

CAV-22

CAV-10 CAV-11 CAV-12 CAV-13

CAV-14E CAV-15A

CAV-15B

CAV-16E

CAV-19E

CAV-23

T

CAV-6

CAV-18C

T

FOR ENLARGED VIEW

SEE SHEET 1/M110

KEY NOTESGENERAL NOTES

1. -

100% CONSTRUCTION DOCUMENTS

4849 Ronson Court, Suite 200 San Diego, CA 92111 858.344.8900

10680 TREENA ST# 163 320 San Diego, CA 92123

PHASE 1 SCOPE

BOUNDARY

389 SF

SPD

RECEIVING

408 SF

CORRIDOR

B177B

340 SF

STORAGE,

GENERAL

B177C

1174 SF

CORRIDOR

B117B

127 SF

STORAGE,

EQUIPMENT

B172B

RECEIVING

ISSUE

EQUIPMENT PREP, AND STAGING

STORAGE

BULK STORAGE

SHRINKING

WRAPPER

UNIT ITEM STORAGE

BREAKDOWN

WALL OPENINGS AS

HIGH AS POSSIBLE

BELOW TRUSSES

50x28 OSA

30x30

30x30 66x18 RA

30x30

EF

x3

R

A x2

SA

62x14 UP

TO AC-104

62x14 UP

TO AC-104

66x18 UP

TO AC-103

(TYP. 2)

52x32 UP

TO AC-103

100 CFM-E

165 CFM-S

(E ) 6

0X

-E

(E ) 5

0X

-E

XH

120X28

,5

C

FM

EX

H

(E

9, CF

M

EX

H

(E

F.D.

42 120 78X19

7, CF

M

EX

H

(E

78X16

165 CFM-E

13X6

6X 6-

T.

R.

165 CFM-S

CF

M

-S

F.D.

8X6

F.D.

8X6-B.R.

100 CFM-E

(E)(GX-1)

(E)(X-1)

S.F.D.

225 CFM-S

(E) FC-1

(E) HP-1

(E) VFD-1

(X-9)

(E) EXHAUST FAN

2 2.1 3' 3.1 3.2 4 4.2 5 5.1 6 7 7.1 8

SD SD

30x30 OSA

CAP

500 CFM

16x16

S

R

Q.1

Q

P

O.1

KEY NOTESGENERAL NOTES

1. DUCT SIZE FROM MAIN SUPPLY DUCT TO TERMINAL BOX INLET SHALL BE ROUND

SHEET METAL THE SAME SIZE AS THE BOX INLET UNLESS OVERALL LENGTH OF DUCT

IS MORE THAN 5 FEET. IN THAT CASE, ONE SIZE LARGER DUCT AND A REDUCER AT

THE TERMINAL BOX SHALL BE INSTALLED.

2. DUCT CONNECTION FROM TERMINAL BOX SUPPLY AIR PLENUM TO DIFFUSER SHALL

BE INSULATED FLEXIBLE DUCT MAX LENGTH OF 7 FEET. IF DISTANCE EXCEEDS 7

FEET, USE INSULATED ROUND SHEET METAL DUCT TO WITHIN 5 FEET OF DIFFUSER

THEN INSULATED FLEXIBLE DUCT TO DIFFUSER.

3. PROVIDE VOLUME DAMPER AT TAKE OFF FROM SUPPLY AND EXHAUST AIR MAINS

(TYPICAL).

4. REFER TO SHEET METAL DETAILS ON DETAIL SHEETS FOR METHOD OF BRANCH

DUCT TAKE-OFF FROM MAIN DUCT.

5. OUTLET DUCT SIZE ON TERMINAL BOX AS SHOWN MAY BE DIFFERENT THAN BOX

OUTLET. PROVIDE TRANSITION AS REQUIRED.

6. SEISMIC BRACING AND RESTRAINT/SUPPORTS ARE REQUIRED PER SPECIFICATION

SECTION 13 05 41.

7. ALL DUCTWORK IN SCOPE AND CONNECTED TO SYSTEM WILL BE CLEANED PER

SPECIFICATION SECTION 23 01 30 52.

1 FURNISH FLEXIBLE DUCT CONNECTOR WITH 4" TOTAL MOVEMENT, VERIFY WITH STRUCTURAL

PLAN FOR REQUIRED SEISMIC MOVEMENT. REFER TO 9/M3.101 FOR MOUNTING DETAIL.

EXISTING TO REMAIN

EXISTING TO BE MODIFIED, REFER TO PHASE 7 PLAN

EXISTING TO BE REMOVED, REFER TO PHASE 6 PLAN

EXISTING TO BE REMOVED, REFER TO PHASE 5 PLAN

LOCATION OF PUSH BUTTON DEVICE (VA TO VERIFY) WITH MOTORIZED DAMPER. SEE AHU

CONTROL DIAGRAM.

120"x42" OUTDOOR OSA INLET WITH BIRDSCREEN

MECHANICAL / CONTROLS CONTRACTOR TO PROVIDE NEMA-3R PUSH BUTTON FOR

AC-103/AC-104 TO OVERRIDE AND SHUTDOWN OUTSIDE AIR INTAKE DURING GREASE

INTERCEPTOR CLEANING.

REFER TO 8/M3.101 FOR MOUNTING DETAIL.

MOTORIZED DAMPER, REFER TO KEY NOTE 6.

PROVIDE FIRE DAMPER IN DUCT THRU 2-HR RATED WALL. REFER TO DAMPER DETAIL

5/M3.100.

1/8" = 1'-0" 01PHASE 1 BASEMENT MECHANICAL DUCTWORK PLAN

PHASING NOTES

PHASE BOUNDARY LINES ARE SHOWN ON LIMITS OF

THE ARCHITECTURAL SCOPE OF WORK. PLANS

IDENTIFY WORK THAT MUST BE CONDUCTED THIS

PHASE AND WORK OUTSIDE THE ARCHITECTURALLY

DEFINED PHASING AREA MUST BE COORDINATED WITH

OWNER AND CONSTRUCTION TEAM TO COMPLETE

WORK REQUIRED IN EACH PHASE.

100% CONSTRUCTION DOCUMENTS

4849 Ronson Court, Suite 200 San Diego, CA 92111 858.344.8900

10680 TREENA ST# 163 320 San Diego, CA 92123 858-368-8630 Fax 866-517-3293 www.dce-inc.net

3043 SF

STORAGE,

GENERAL

B177E

404 SF

STORAGE,

GENERAL

B177D

210 SF

STAIRWELL

SW9-B-1

198 SF

MECHANICAL

ROOM

B180

428 SF

OFFICE

B176

105 SF

TOILET, MALE

B176A

109 SF

TOILET,

FEMALE

B176B

160 SF

CORRIDOR

B117P

408 SF

CORRIDOR

B177B

1174 SF

CORRIDOR

B117B

556 SF

CORRIDOR

B177M

1575 SF

CORRIDOR

B177A

334 SF

STORAGE

B177N

3565 SF

STORAGE,

GENERAL

B177-1

1793 SF

IT SERVICE

CENTER

OFFICE

B1000

75 SF

STAIR

SW11-B-1

STORAGE,

EQUIPMENT

STORAGE,

KITCHEN

EQUIPMENT

CHWR

HH

W

S

HH

W R

2" MPS

1 1/2" MPS

3" CHWS

3" CHWR

2" RHWR

2" RHWS

3" CHWS

3" CHWR

3" CHWS

3" CHWR

2" CHWS

2" CHWR

2 1/2" CHWS/CHWR

CAP

REFER TO PARTIAL PLAN ON

THIS SHEET FOR PIPING

FROM EXISTING RISER 2

2 2.1 3' 3.1 3.2 4 4.2 5 5.1 6 7 7.1 8

1" HHWS

1" HHWR

1" HHWS

1" HHWR

1" HHWS/HHWR

1" HHWS

1" HHWR

PHASE 3 SCOPE

BOUNDARY

S

R

Q.1

Q

P

O.1

O N.7

N.6

N.5

N.4

287 SF

REFRIGERATOR,

WALK-IN

B137

249 SF

REFRIGERATOR,

WALK-IN

B138

230 SF

REFRIGERATOR,

WALK-IN

B136

STORAGE,

FILE ROOM

B134

112 SF

IT

B135

50 SF

HAC

B135A

293 SF

STAIRWELL

SW1-B-1

4"4"

3" CHWS

3" CHWR

2" RHWR

2" RHWS

(E) RISER 2

1" HHWS

1" HHWR

2 2.1 3' 3.1 3.2 4

M

L.1

L

K

KEY NOTESGENERAL NOTES

1. PLAN SHOWS THE EXISTING HVAC PIPING IS APPROXIMATE LAYOUT OF EXISTING

BUILDING AND IS NOT INTENDED TO REPRESENTED "AS-BUILT" CONDITIONS,

CONTRACTOR SHALL VISIT SITE AND BECOME FAMILIAR WITH ACTUAL CONDITIONS

WHEN BIDDING THE WORK.

2. PRIOR TO ANY WORK, INCLUDING DEMO AND NEW, CONTRACTOR MUST FIELD

VERIFY ALL EXISTING MECHANICAL WORK LOCATED IN THE SPACE WITH OTHER

TRADES WHICH MAY AFFECT THE SPACES, SINCE THE EXISTING CONDITIONS OF THE

INTERSTITIAL SPACE, THE ROUTING OF NEW PIPING WILL BE FOLLOWED THE SAME

AS THE EXISTING.

3. THE OWNER MUST BE NOTIFIED PRIOR TO SHUTDOWN OF ANY MECHANICAL HVAC

WATER SYSTEMS, INCLUDING HEATING HOT WATER LOOP AND REHEAT HOT WATER

LOOP.

4. EXISTING PIPING, VALVES, CONTROLS SHOWN TO REMAIN SHALL BE PROTECTED

DURING CONSTRUCTION, DAMAGE TO EXISTING CONSTRUCTION SHOWN TO REMAIN

SHALL BE RESTORED TO MATCH PRE-DAMAGED CONDITION.

5. PROVIDE 2-WAY CONTROL VALVE FOR TERMINAL BOX REHEAT WATER PIPING

CONNECTION, REFER TO PIPING DIAGRAM 10/M501, UNLESS NOTED OTHERWISE.

6. PROVIDE MINIMUM 3/4" BRANCH PIPE TO REHEAT COIL CONNECTION ON TERMINAL

BOX (TYPICAL), UNLESS NOTED OTHERWISE.

7. REFER TO DETAIL 10/M501 FOR TYPICAL REHEAT COIL PIPING

8. SEISMIC BRACING AND RESTRAINT/SUPPORTS ARE REQUIRED PER SPECIFICATION

SECTION 13 05 41

1 RUN 3" CHWS/R, 1" HHWS/R, AND 2" RHWS/R FROM EXISTING RISER #2.

2-1/2" CHWS/R UP THROUGH ROOF TO AC-103.REFER TO 10/M3.101 FOR PIPE THROUGH ROOF DETAIL.

2" CHWS/R UP THROUGH ROOF TO AC-104.REFER TO 10/M3.101 FOR PIPE THROUGH ROOF DETAIL.

1" HHWS/R UP THROUGH ROOF TO AC-103.REFER TO 10/M3.101 FOR PIPE THROUGH ROOF DETAIL.

HOT TAPPING AS NEEDED FOR NEW PIPE CONNECTIONS.

1/8" = 1'-0" 01PHASE 1 BASEMENT MECHANICAL PIPING PLAN

1/4" = 1'-0" 02PHASE 1 BASEMENT MECHANICAL PIPING PLAN

PHASING NOTES

PHASE BOUNDARY LINES ARE SHOWN ON LIMITS OF

THE ARCHITECTURAL SCOPE OF WORK. PLANS

IDENTIFY WORK THAT MUST BE CONDUCTED THIS

PHASE AND WORK OUTSIDE THE ARCHITECTURALLY

DEFINED PHASING AREA MUST BE COORDINATED WITH

OWNER AND CONSTRUCTION TEAM TO COMPLETE

WORK REQUIRED IN EACH PHASE.

100% CONSTRUCTION DOCUMENTS

4849 Ronson Court, Suite 200 San Diego, CA 92111 858.344.8900

10680 TREENA ST# 163 320 San Diego, CA 92123

UPDN

VOID

010-1-1

AC

66x18 RA

66x18 SA

52x32 OA

REQUIRED UNIT

CLEARANCES (TYP.)

AC

62x14 RA

62x14 SA

2 1/2" CHWS/CHWR

2" CHWS/CHWR

S

R

Q.1

Q

P

O.1

1 2 2.1 3' 3.1 3.2 4 4.2 5 5.1 6 7 7.1 8 9 9.1

2 1/2" CHWS/CHWR

1" HHWS/HHWR

KEY NOTESGENERAL NOTES

1 2-1/2" CHWS/R DOWN THROUGH ROOF TO BASEMENT. REFER TO 10/M3.101 FOR PIPE THROUGH ROOF DETAIL.

1" HHWS/R DOWN THROUGH ROOF TO BASEMENT. REFER TO 10/M3.101 FOR PIPE THROUGH ROOF DETAIL.

2" CHWS/R DOWN THROUGH ROOF TO BASEMENT. REFER TO 10/M3.101 FOR PIPE THROUGH ROOF DETAIL.

REFER TO 7/M3.101 FOR AHU MOUNTING DETAIL.

REFER TO ARCHITECTURAL PLANS FOR ACCESS TO MECHANICAL SPACE.

REFER TO PLUMBING PLANS FOR CONDENSATE LINES FROM AHUS.

1. MAINTAIN REQUIRED CLEARANCE FOR SERVICE AREAS PER AHU MANUFACTURER

DIRECTIONS.

2. SEISMIC BRACING AND RESTRAINT/SUPPORTS ARE REQUIRED PER SPECIFICATION

SECTION 13 05 41.

3. ALL DUCTWORK IN SCOPE AND CONNECTED TO SYSTEM WILL BE CLEANED PER

SPECIFICATION SECTION 23 01 30 52.

1/8" = 1'-0" 01PHASE 1 FIRST FLOOR MECHANICAL PLAN

PHASING NOTES

PHASE BOUNDARY LINES ARE SHOWN ON LIMITS OF

THE ARCHITECTURAL SCOPE OF WORK. PLANS

IDENTIFY WORK THAT MUST BE CONDUCTED THIS

PHASE AND WORK OUTSIDE THE ARCHITECTURALLY

DEFINED PHASING AREA MUST BE COORDINATED WITH

OWNER AND CONSTRUCTION TEAM TO COMPLETE

WORK REQUIRED IN EACH PHASE.

100% CONSTRUCTION DOCUMENTS

4849 Ronson Court, Suite 200 San Diego, CA 92111 858.344.8900

10680 TREENA ST# 163 320 San Diego, CA 92123 858-368-8630 Fax 866-517-3293 www.dce-inc.net

PHASE 3 SCOPE

BOUNDARY

1174 SF

CORRIDOR

B117B

140 SF

STORAGE,

GENERAL

B172

127 SF

STORAGE,

EQUIPMENT

B172B

130 SF

OFFICE

B171C

103 SF

B171D

384 SF

BUILDING

SERVICES

B171B

57 SF

JANITOR

100 SF

STORAGE,

GENERAL

B172D

116 SF

TOILET,

FEMALE

99 SF

TOILET, MALE

B173

184 SF

HALLWAY

B-SPS-28

136 SF

LOUNGE

B174A

92 SF

FEMALE

LOCKERS

B174B

97 SF

LOCKER,

MEN'S

B174C

98 SF

TOILET, MALE

156 53 SF

JANITOR

B174E

215 SF

ETO

B-SPS-13

165 SF

CART WASH

TRANSFER

131 SF

AUTOMATIC

CARTWASH

B171H

1923 SF

STORAGE,

GENERAL

B191K

286 SF

BREAK

B175

23 SF

CLOSET

78 SF

BREAK

1303 SF

SPS/O.R.

SUPPLY

B175

121 SF

STORAGE,

GENERAL

B196

109 SF

PET ELEV

S5-B-1

STORAGE,

GENERAL

280 SF

CORRIDOR

135 SF

LOCKER,

MEN'S

B172E

383 SF

CORRIDOR

B174

30 SF

CLOSET

1321 SF

CORRIDOR

36 SF

CLOSET

293 SF

STAIRWELL

SW7-B-1

293 SF

STAIRWELL

SW8-B-1

2398 SF

STERILE

STORAGE

CART

HOLDING

AREA

B172C

102 SF

STORAGE,

GENERAL

B195C

99 SF

TOILET,

FEMALE

B-SPS-9

99 SF

TOILET,

FEMALE

B-SPS-9

102 SF

STORAGE,

GENERAL

B195C

223 SF

STORAGE,

GENERAL

B173

2398 SF

STERILE

STORAGE

CART

HOLDING

AREA

B172C

293 SF

STAIRWELL

SW8-B-1 293 SF

STAIRWELL

SW7-B-1

36 SF

CLOSET

1321 SF

CORRIDOR

30 SF

CLOSET

383 SF

CORRIDOR

B174

135 SF

LOCKER,

MEN'S

B172E

280 SF

CORRIDOR

STORAGE,

GENERAL

109 SF

PET ELEV

S5-B-1

121 SF

STORAGE,

GENERAL

B1961303 SF

SPS/O.R.

SUPPLY

B175

78 SF

BREAK

23 SF

CLOSET

286 SF

BREAK

B175

227 SF

SPS

EDUCATION

HUB

B173C

135 SF

SPS

SUPERVISOR

B173B

1923 SF

STORAGE,

GENERAL

B191K

131 SF

AUTOMATIC

CARTWASH

B171H

165 SF

CART WASH

TRANSFER

215 SF

ETO

B-SPS-13

53 SF

JANITOR

B174E

98 SF

TOILET, MALE

97 SF

LOCKER,

MEN'S

B174C

92 SF

FEMALE

LOCKERS

B174B136 SF

LOUNGE

B174A

184 SF

HALLWAY

B-SPS-28

99 SF

TOILET, MALE

B173

116 SF

TOILET,

FEMALE

100 SF

STORAGE,

GENERAL

B172D

57 SF

JANITOR

384 SF

BUILDING

SERVICES

B171B

103 SF

B171D

130 SF

OFFICE

B171C

127 SF

STORAGE,

EQUIPMENT

B172B

140 SF

STORAGE,

GENERAL

B172

223 SF

OFFICE

B171A

178 SF

OFFICE,

STAFF

B171

1174 SF

CORRIDOR

B117B

340 SF

STORAGE,

GENERAL

B177C

225 CFM-E

100 CFM-E

165 CFM-S

(E ) 5

2X

(E ) 5

2X

(E ) E

F-

F.

D.165 CFM-E

12X10-T.R.

225 CFM-E

13X6 6X

6- T.

R.

165 CFM-S

CF

M

-S

F.D.

8X6

8X6

8X6-B.R.

100 CFM-E

5X

-D N

F.D.

X5

-E (E

) 5 6X

(E

) 5 6X

32X13-EXH

F.D.

2, CF

M -E

XH

X1

8- B.

R.

6"

6X12-EXH, DN

F.D.

12X6-EXH.

200 CFM-EXH

10X10-B.R. +6"

12X6-EXH

F.D.

12X12-T.R.

200 CFM-R

(BOTH SIDES)

(X-2) x1

8- E

SFDSFD

32X13-E. DN.

RH

W

R

RH

W S

(E)GX-109

S.F.D.

225 CFM-S

(E) EF-1 DISCHARGE

OUTLET

8 9 9.1 9.5 9.4 10 11

R

Q.1

Q

P

O.1

O N.7

N.6

N.5

N.4

N.2

KEY NOTESGENERAL NOTES

1. DEMOLITION PLAN SHOWS APPROXIMATE LAYOUT OF EXISTING BUILDING AND IS

NOT INTENDED TO REPRESENT "AS-BUILT" CONDITIONS, FOLLOW PROCEDURES

OUTLINED IN SPECIFICATIONS FOR REQUIREMENTS TO VISIT SITE AND OTHERWISE

BECOME FAMILIAR WITH ACTUAL CONDITIONS WHEN BIDDING THE WORK.

2. PRIOR TO ANY DEMOLITION WORK CONTRACTOR MUST FIELD VERIFY ALL EXISTING

MECHANICAL WORK LOCATED IN THE SPACE WHICH AFFECTS THE SPACES. THE

OWNER MUST BE NOTIFIED PRIOR TO SHUTDOWN OF ANY MECHANICAL SYSTEMS.

3. DUCTS, PIPES, AIR DIFFUSERS, TERMINAL UNITS, AND HVAC EQUIPMENT AND OTHER

ITEMS TO BE REMOVED ARE SHOWN HATCHED.

4. EXISTING CONSTRUCTION SHOWN TO REMAIN INCLUDING BUT NOT LIMITED TO

DUCTS, PIPES, DIFFUSERS, ETC.