Attachment_4_-_AAON_Ratings_data___drawings_with_HGBP.pdf

PDF 786 KB Posted

Attached to
HVAC Replacement, HPTC Ops Facility, Frederick, MD Federal contract opportunity
Solicitation number
140P2123Q0161
Issued by
Department of the Interior National Park Service

About this file

This document package includes technical specifications and submittals for HVAC equipment for a federal project. The specifications cover an air handling unit and condensing unit with details on components, controls, dimensions, performance criteria, and accessories. The submittal provides configuration options and includes a VCCX control panel. The related federal contract opportunity is for HVAC replacement at the Harpers Ferry National Historical Park and Training Center operations facility in Frederick, Maryland under National Park Service solicitation number 140P2123Q0161. The specifications and submittals appear to be for the technical requirements of the HVAC systems to be provided under this federal contract to replace HVAC equipment at the specified National Park Service facility.

View the file

Other files for this federal contract opportunity

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094 AAONEcat32 Ver. 4.332 (SN: 5371344-055LD5DL)

A

B

C

D

A

B

C 6 A

B

C

A

B

H3-BRB-8-0-141D-7C2:EG1 E-AAK-000-0A0-B0AA0B0-00-000000000

Air Handling Unit Tag: AHU-1 Cooling only low ambient

Condensing Unit Tag: CU-1 Cooling only low ambient

Job Information Unit Information

Job Name: Approx. Weights AHU/CU:

Job Number: Supply CFM/ESP:

Site Altitude:

Refrigerant

Outside CFM:

Ambient Temperature:

Return Temperature:

National Park Service Lead Abatement 652 / 397 lbs. (±5%) JK 1000 / 0.5 in. wg.

0 ft R-410A

88.7 ºF DB / 72.6 ºF WB

80 ºF DB / 67 ºF WB

Static Pressure

External: Economizer:

Coil: Heating:

Filters Clean: Cabinet:

Dirt Allowance Total:

0.50 in. wg. 0.00 in. wg.

0.23 in. wg. 0.03 in. wg.

0.04 in. wg. 0.00 in. wg.

0.15 in. wg. 0.96 in. wg.

Cooling Section Heating Section

Gross Net Total Capacity:

Sensible Capacity:

Latent Capacity:

Mixed Air Temp:

Entering Air Temp:

Lv Air Temp (Coil):

Lv Air Temp (Unit) Evap Suction Temp:

Supply Air Fan:

SA Fan RPM / Width:

DX Coil:

DX Face Velocity:

40.62 39.84 MBH

29.15 28.38 MBH

11.47 MBH

88.70 ºF DB 72.60 ºF WB

88.70 ºF DB 72.60 ºF WB

60.72 ºF DB 60.11 ºF WB

61.42 ºF DB 60.36 ºF WB

52.39 ºF 1 x RN150D70 @ 0.27 BHP 1311 / 2.352"

3.5 ft² / 4 Rows / 14 FPI

282.4 fpm

PreHeat Type: Std (No Preheat)

Auxiliary Heating Type*:

Heating CFM:

Total Capacity:

OA Temp:

RA Temp:

Entering Air Temp:

Leaving Air Temp:

Input:

Heater Qty (Hi/Low):

Electric Heat FLA:

Electric Heat

53.9 MBH

20.0 DB / 19.4ºF WB

75.0 ºF DB / 65.0 ºF WB

20.0 ºF DB / 19.4 ºF WB

69.9 ºF DB / 47.6 ºF WB

15.8 kW 43.9

Rating Information

Cooling Capacity (MBH): 35400 Cooling SEER: 14.45 Cooling EER: 12.2

Application EER @ Op. Conditions: Condensing Unit EER @ Op. Conditions:15.1 17.0

AH Electrical Data

Rating: Minimum Circuit Amp:

Unit FLA: Maximum Overcurrent:

208/3/60 58 46 60

CU Electrical Data

Rating: Minimum Circuit Amp:

Unit FLA: Maximum Overcurrent:

208/3/60 17 14 25

Qty HP VAC Phase RPM FLA RLA Compressor 1: 1 208 3 11.6 Condenser Fans: 1 0.33 208 1 1075 2.8 Supply Fan: 1 1.00 208 3 1760 2.3

*Motor heat is not included.

Condensing Unit Connection Sizes

System Suction Line Liquid Line Hot Gas Bypass 1 1.13" 0.5" 0.63"

Split System Rating

Date Created/Modified: 5/5/2023 7:46:15 AM Using Ver 4.334 (OSN# 0123456) Date Printed: 5/11/2023 8:36:51 AM

B

C

B

C

A

B

A

B

H 3 - B R B - 8 - 0 - 1 4 1 D - 7 C 2 : E G 1 E - A A K - 0 0 0 - 0 A 0 - B 0 A A 0 B 0 - 0 0 - 0 0 0 0 0 0 0 0 0

CFA-003-A-A-8-BA00G:A-00-A0-D0-AN0-L-EE00-00A0C00-0A000DB

Condensing Unit Tag: CU-1 Cooling only low ambient

Job Information

Job Name: National Park Service Lead Abatement

Job Number: JK

HGB Line Data

Elbow Qty: 4 Line Length: 30'

Oil return to be installed at the lowest point of the system.

Pipe

OD

Equiv.

Length

Temp.

Loss (ºF)

Velocity (fpm)

Min Tons For Oil Return

Suction Line Data

Elbow Qty: 4 Line Length: 30' Flow Direction of Suction Line: Down

Pipe

OD

Equiv.

Length

Temp.

Loss (ºF)

Velocity (fpm)

Min Tons For Oil Return

Qty. of Req. Traps

Liquid Line Data

Elbow Qty: 4 Line Length: 30' Vertical Lift: 10'

Pipe

OD

Equiv.

Length

Temp.

Loss (ºF)

Velocity (fpm)

Min Subcooling For Vertical Lift

Line Sizing Information

Date Created/Modified: 5/5/2023 7:46:15 AM Using Ver 4.334 (OSN# 0123456) Date Printed: 5/11/2023 8:36:51 AM

B

C

B

C

A

B

A

B

H 3 - B R B - 8 - 0 - 1 4 1 D - 7 C 2 : E G 1 E - A A K - 0 0 0 - 0 A 0 - B 0 A A 0 B 0 - 0 0 - 0 0 0 0 0 0 0 0 0

CFA-003-A-A-8-BA00G:A-00-A0-D0-AN0-L-EE00-00A0C00-0A000DB

Condensing Unit Tag: CU-1 Cooling only low ambient

Job Information

Job Name: National Park Service Lead Abatement

Job Number: JK

Factory Supplied / Factory Installed

Quantity Description Part #: Location

Factory Supplied / Field Installed

Quantity Description Part #: Location

- N/A - -

Field Supplied / Field Installed

Quantity Description Part #: Location

- P-Trap(s) AHU

Refrigeration Accessories

Date Created/Modified: 5/5/2023 7:46:15 AM Using Ver 4.334 (OSN# 0123456) Date Printed: 5/11/2023 8:36:51 AM

Circuit #: 1

Date Created/Modified: 5/5/2023 7:46:15 AM Using Ver 4.334 (OSN# 0123456) Date Printed: 5/11/2023 8:36:51 AM

JOB INFORMATION: WHEEL SPECIFICATION:

Job Name: Max RPM:

Job Tag: Diameter x Qty:

Rep Firm: CFM:

Date: Tip Speed:

Inertia:

National Park Service Lead Abatement

3,200

AHU-1 Cooling only low ambient

15.0 in. x 1

05/11/2023 5,148 FPM

05/11/2023 5,148 FPM

OPERATING CONDITIONS: MOTOR SELECTION:

Air Flow: Rated HP / Bypass:

Static Pressure: Frame Size:

Plenum DP: Nominal RPM:

Inlet Grill DP: VAC/PH/HZ:

TSP: Efficiency Site Altitude: Enclosure Type:

TSP @ Sea Level: Max Inertial Load:

1,000 CFM 1 / No

0.96 in. Wg. 143TC

0.00 in. Wg. 1760

0.00 in. Wg. 208/3/60

0.96 in. Wg. Premium / 0.893

0.00 Ft ODP

0.96 in. Wg. 15 WR²

FAN PERFORMANCE: FAN SOUND POWER (Inlet/Outlet):

RPM: Octave Band: (Re 10^-12 watts)

BHP: 1 2 3 4 5 6 7 8

Efficiency:

In/Out Velocity:

Plenum Out Velocity: SOUND POWER A-Weighted: 72 / 72 dB

Max Duct SP with Blocked Airway: 1.3 in. Wg. @ 1311 rpm

0.27 55.8% 70 71 71 67 63 61 57 51

/ FPM 70 71 71 67 63 61 57 51

11 FPM

RPM

BHP

SYSTEM

Efficiency

SP Surge

CFM Min

Supply Fan Model: RN150D70 @ 1311 RPM and 100% Width Design Conditions: 1000 CFM @ 0.96" SP

CFM x 1000

S P

B H

P

40%

20%

0%

RPM: 1311

BHP: 0.27

EFFICIENCY: 55.76

15.0" STAR Plenum

Date Created/Modified: 5/5/2023 7:46:15 AM Using Ver 4.334 (OSN# 0123456) Date Printed: 5/11/2023 8:36:55 AM

203 Gum Springs Road - Longview, TX 75602 - Ph. (903) 236-4403 Fax (903) 236-4463

A

B

C

B

C 6 A

B

A

B

Tag: AHU-1 Cooling only low ambient

Job Name: National Park Service Lead Abatement Unit Submittal For:

Job Number: JK Unit Submittal Date: May 05, 2023

Base Option Description

H Series Horizontal Unit

3 Generation Third Generation

B Unit Size Up to 2,000 cfm

R Unit Orientation Right Hand Connections - Front Discharge, Back Intake (Horizontal)

B Revision Second Revision

8 Voltage 208V/3Ø/60Hz

0 Corrosion Protection None

1 Cooling Type R-410A DX Cooling

4 Cooling Rows 4 Row Coil

1 Cooling Stages Single Circuit

D Cooling FPI 14 fpi

7 Heating Type Electric Heat

C Heating Designation 21 kW (15.8 kW @ 208V)

2 Heating Stages 2 Stage

Feature Option Description

E 1A. SA Blower Configuration 1 Blower + 1 Perm Magnet AC TEFC Motor+ 1 VFD

G 1B. SA Blower Model 15" Backward Curved Plenum , 70% Width

1 1C. SA Blower Motor 1 hp

E 1D. SA Blower Control/Contol Vendor VCC-X Orion Controls System

A 2. Refrigeration Options Single Circuit External Hot Gas Bypass (HGB)

A 3. Special Controls Constant Volume Controller - CV Cool + CV Heat

K 4. Additional Controls 1 Phase & Brownout Protection + Remote Safety Shutdown Terminals

0 5A. Mixing Box - RA Damper Position Standard - None

0 5B. Mixing Box - OA Damper Position Standard - None

0 5C. Damper Control Standard - None

0 6A. Filter Box - Pre Filter Box Standard - None

A 6B. Filter Box - Unit Filter 2" Pleated - 30% Eff.

0 6C. Filter Box - Final Filter Box Standard - None

B 7. Filter Options Clogged Filter Switch

0 8. Coil Coating Standard - None

A 9. Expansion Valve Thermal Expansion Valves

A 10. Expansion Valve Controls Standard Control

0 11. External Paint Standard - None

B 12. Tonnage 3 ton Capacity

0 13. Energy Recovery Type Standard - None

0 14A. Power Options Standard Power Block

0 14B. Electrical Rating Standard

0 15. Control Panel Internal Control Panel (Top or Bottom Blower Access Required)

0 16. Shipping Splits Standard (No Shipping Split)

0 17. Energy Recovery Cabinet Standard - None

0 18. Preheat Standard - None

0 19. Exhaust Fan Standard - None

0 20. Crating Standard

0 21. Additional Controls 2 Standard - None

0 22. Warranty Standard - 1 Year Parts

0 23. Type Standard

Unit Submittal

Date Created/Modified: 5/5/2023 7:46:15 AM Using Ver 4.334 (OSN# 0123456) Date Printed: 5/11/2023 8:36:53 AM

A

B

C

B

C 6 A

B

A

B

Tag: AHU-1 Cooling only low ambient Job Name: National Park Service Lead

Abatement VCCX For:

Job Number: JK VCCX Date: May 05, 2023

Hardware Included For VCCX Controller

Part # Included Parts Assigned Channel BACnet Point

ASM01698 VCCX2 CONTROLLER

ASM01643 Space Temp Sensor VCCX control point AI 1 AI:12 ASM01643 Space Temp Slide Adjust VCCX control point AI 2 AI:8

R82890 Supply Temp Sensor - Field Installed VCCX control point AI 3 AI:9 R81550 Outside Temp Sensor VCCX control point AI 7 AI:16 R64580 Dirty Filter Sensor VCCX control point BI 2 BI:25

Safety Shut Down VCCX control point BI 8 BI:26 Heat 1 Configured Relay Point BI:47 Heat 2 Configured Relay Point BI:48

VCCX Components

Date Created/Modified: 5/5/2023 7:46:15 AM Using Ver 4.334 (OSN# 0123456) Date Printed: 5/11/2023 8:36:54 AM

A

A

A

A

A

B 3 A

B

B

B

C

CFA-003-A-A-8-BA00G:A-0 0-A0-D0-AN0-L-EE00-00A0C00-0A000DB

Tag: CU-1 Cooling only low ambient

Job Name: National Park Service Lead Abatement Unit Submittal For:

Job Number: JK Unit Submittal Date: May 05, 2023

Base Option Description

CF Generation CF - Condensing Unit

A Major Rev Major Revision

003 Unit Size Three

A Series A Cabinet

A Revision Minor Revision

8 Voltage 208V/3Ø/60Hz

B Compressor Style R-410A Scroll 2-Step Capacity Comp

A Condenser Style Air-Cooled Microchannel Condenser

0 Configuration Standard

0 Coating Standard

G Staging 1 Two-Step Refrig System (2 Stage)

Feature Option Description

A 1. Unit Orientation Horizontal Condenser Discharge Standard Access

0 2A. Refrigeration Control Standard

0 2B. Blank Standard

A 3A. Refrigeration Options Hot Gas Bypass Lead Stage [HGB]

0 3B. Blank Standard

D 4. Refrigeration Accessories Flooded Condenser 0°F Low Ambient Control - One Circuit

0 5. Blank Standard

A 6A. Unit Disconnect Type Single Point Power Non-Fused Disconnect

N 6B. Disconnect Size 100 Amps

0 6C. Blank Standard

L 7. Accessories Phase & Brown Out Protection + Suction Pressure Transducer on Each Refrigeration System

E 8A. Control Sequence Constant Volume (CAV) Unit Controller - CAV Cool + CAV Heat

E 8B. Control suppliers VCC-X (Main Controller in Air Handling Unit)

0 8C. Control Supplier Options Standard

0 8D.

BMS Connection and Diagnostics Standard

0 9. Blank Standard

0 10. Blank Standard

A 11. Maintenance Accessories 115VAC Convenience Outlet - Factory Wired

0 12. Code Options Standard ETL U.S.A. Listing

C 13.

Air Cooled Condenser Accessories ECM Condenser Fan / Head Pressure Control

0 14. Blank Standard

0 15. Blank Standard

0 16. Electrical Options Standard

A 17. Shipping Options Crating

0 18. Blank Standard

0 19. Blank Standard

0 20. Cabinet Material Standard - Galvanized Steel Cabinet

D 21. Warranty Extended Compressor Warranty - Years 2-5

B 22. Paint and SPAs Premium AAON Gray Paint Exterior

Unit Submittal

Date Created/Modified: 5/5/2023 7:46:15 AM Using Ver 4.334 (OSN# 0123456) Date Printed: 5/11/2023 8:37:03 AM

A

A

A

A

A

B 3 A

B

B

B

C

CFA-003-A-A-8-BA00G:A-0 0-A0-D0-AN0-L-EE00-00A0C00-0A000DB

Tag: CU-1 Cooling only low ambient Job Name: National Park Service Lead

Abatement VCCX For:

Job Number: JK VCCX Date: May 05, 2023

Hardware Included For VCCX Controller

Part # Included Parts Assigned Channel BACnet Point

ASM02201 DIGITAL REFRIGERATION MODULE

V38391 Suction Pressure Sensor A RSMD point AI1 AI:48 V38410 Discharge Pressure Sensor A RSMD point HP-1 AI:50 R63950 Modulated Condenser Signal A RSMD point AO1 AI:46

Comp Status Input A RSMD point BIN1 BI:77 Emergency Shutdown RSMD point BIN4 BI:83 Comp Enable A RSMD Fixed Relay point BI:84 Comp Enable B RSMD Fixed Relay point BI:85

VCCX Components

Date Created/Modified: 5/5/2023 7:46:15 AM Using Ver 4.334 (OSN# 0123456) Date Printed: 5/11/2023 8:37:03 AM