Attachment_3-_Fire_Inspection_Certificate.pdf

PDF 629 KB Posted

Attached to
Fire Panel Replacement, Rhode Island Wildlife Refu Federal contract opportunity
Solicitation number
140FS325Q0119
Issued by
Department of the Interior Fish and Wildlife Service

About this file

This document is a Fire Alarm and Life Safety System Inspection Certificate for the Kettle Pond Visitors Center in Charlestown, Rhode Island. The inspection was conducted by ADT Commercial LLC on November 22, 2022, and tested to NFPA 72 Standards. The comprehensive report details the testing of various fire safety components, including 40 total devices across categories such as auxiliary, control, indicating, and initiating systems. Of the 40 devices, 28 passed inspection (70%), with 12 devices remaining untested, primarily smoke detectors and heat detectors in specific rooms that require alternative testing methods or are scheduled for state elevator inspection.

The inspection report includes detailed documentation of tested devices, their locations, service times, and dates. The fire alarm system uses a Gamewell IF610-126 control panel installed on July 11, 2017, with components including sealed lead acid batteries, communication lines, pull stations, smoke detectors, and heat detectors. The system covers various building areas such as exhibit spaces, rooms, stairwells, and hallways. While most devices passed inspection, some devices were marked as "untested" and require future testing, particularly those located in elevator machine rooms, inside specific rooms, and near elevator areas.

View the file

Other files for this federal contract opportunity

Other files attached to Fire Panel Replacement, Rhode Island Wildlife Refu, newest first.
File Type Posted
Attachment_6-_Images_0001.pdf PDF
Sol_140FS325Q0119_Amd_0001.pdf PDF
Attachment_5-_Past_Performance_Data_Document.docx DOCX document
Sol_140FS325Q0119.pdf PDF
Attachment_4-_SCA_Wage_Determintion.pdf PDF
Attachment_1-_Performance_Work_Statement.pdf PDF
Attachment_2-_Quote_Schedule.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Fire Alarm and Life Safety System Inspection Certificate

For

Kettle Pond Visitors Center 50 Bend Road Charlestown, RI 02813

Tested to NFPA 72 Standards

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Inspection Date Nov 22, 2022

Building: Kettle Pond Visitors Center Company: ADT Commercial LLC Contact: Karrie Schwaab Contact: Kevin Neagle

Title: . Title: Inspector

ADT Commercial LLC 1 Download Date: 11/22/2022

Executive Summary Generated by: BuildingReports.com

Building Information Building: Kettle Pond Visitors Center Contact: Karrie Schwaab

Address: 50 Bend Road Phone: 401-213-4402

Address: Fax:

City/State/ZIP Code: Charlestown, RI 02813 Mobile:

Country: United States of America Email: karrie_schwaab@fws.gov

Inspection Performed By Company: ADT Commercial LLC Inspector: Kevin Neagle

Address: 300 Myles Standish Blvd Phone: 508-884-6425

Address: Fax:

City/State/ZIP Code: Taunton, MA 02780 Mobile:

Country: United States of America Email: kevin.neagle@redhawkus.com

System Control Unit Manufacturer: Gamewell Inspection Date: 05/26/2022 IDC Style:

Model Number: IF610-126 (Address Install Date: 07/11/2017 SLC Style:

Software Version: Version Date: 07/11/2017 NAC Style:

Location: ( EVERY 6 MONTHS ) 1st Employee Main Entrance

Current Protection:

ADT Commercial LLC 2 Download Date: 11/22/2022

Inspection Summary

Category Total Items Serviced Passed Failed/Other Qty % Qty % Qty % Qty %

Auxiliary 1 2.50% 1 100.00% 1 100.00% 0 0.00% Control 3 7.50% 3 100.00% 3 100.00% 0 0.00% Indicating 1 2.50% 1 100.00% 1 100.00% 0 0.00% Initiating 35 87.50% 23 65.71% 23 100.00% 0 0.00%

Totals 40 100% 28 70.00% 28 100.00% 0 0.00%

Certification

Company: ADT Commercial LLC Building: Kettle Pond Visitors Center

Inspector: Kevin Neagle Contact: Karrie Schwaab

ADT Commercial LLC 3 Download Date: 11/22/2022

Notes & Recommendations

Building: Kettle Pond Visitors Center

The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.

General Note On 11/22/22, completed quarterly fire alarm system test and inspection.

ADT Commercial LLC 4 Download Date: 11/22/2022

Inspection & Testing

Control Panel: 1 - Gamewell IF610-126 (Address

The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

Passed Auxiliary

Releasing Device ( EVERY 6 MONTHS ) 1st ( DOOR HOLDERS ) by storage# 115 ( Outside Room 130 )

Tested 7:45:20 AM 05/26/2022

Control Battery ( EVERY 6 MONTHS ) 1st Above Ceiling ( exit sign) Outside Room 130 Tested 7:45:05 AM 05/26/2022

Communication Line ( EVERY 6 MONTHS ) 1st FACP Tested 7:45:13 AM 05/26/2022 Control Panel ( EVERY 6 MONTHS ) 1st Employee Main

Entrance Tested 7:44:47 AM 05/26/2022

Indicating Horn/Strobe ( EVERY 6 MONTHS ) ALL Tested 7:44:56 AM 05/26/2022

Initiating Heat Detector ( JULY THRU DECEMBER ) 1st In Exhibit (High

Ceiling) Tested 7:54:41 AM 05/26/2022

Pull Station ( JANUARY THRU JUNE ) 1st Outside Room 130 Tested 7:45:46 AM 05/26/2022 Pull Station ( JANUARY THRU JUNE ) 2nd Outside Room 202 Tested 8:37:22 AM 11/22/2022 Pull Station ( JANUARY THRU JUNE ) 2nd Outside Room 224 Tested 8:28:29 AM 11/22/2022 Pull Station ( JULY THRU DECEMBER ) 1st Exhibit Left Rear

Exit Tested 7:54:58 AM 05/26/2022

Pull Station ( JULY THRU DECEMBER ) 1st Exhibit Right Rear Exit

Tested 7:54:20 AM 05/26/2022

Pull Station ( JULY THRU DECEMBER ) 1st Exit for Exibit Deck Tested 8:48:56 AM 11/22/2022 Pull Station ( JULY THRU DECEMBER ) 1st Outside Elevator Tested 7:48:21 AM 05/26/2022 Pull Station ( JULY THRU DECEMBER ) 1st Outside Room 112 Tested 7:52:04 AM 05/26/2022 Smoke Detector ( JANUARY THRU JUNE ) 1st Above FACP Tested/Cleaned 1:56:07 PM 11/22/2022 Smoke Detector ( JANUARY THRU JUNE ) 1st Outside Room 132 Tested/Cleaned 7:46:47 AM 05/26/2022 Smoke Detector ( JANUARY THRU JUNE ) 2nd Outside Room 202 Tested/Cleaned 8:25:22 AM 11/22/2022 Smoke Detector ( JANUARY THRU JUNE ) 2nd Outside Room

205/230 Tested/Cleaned 8:26:12 AM 11/22/2022

Smoke Detector ( JANUARY THRU JUNE ) 2nd Outside Room 208 Tested/Cleaned 8:27:11 AM 11/22/2022 Smoke Detector ( JANUARY THRU JUNE ) 2nd Outside Room 214 Tested/Cleaned 8:31:11 AM 11/22/2022 Smoke Detector ( JANUARY THRU JUNE ) 2nd Outside Room 217 Tested/Cleaned 8:32:41 AM 11/22/2022 Smoke Detector ( JANUARY THRU JUNE ) 2nd Data/ Electrical

Closet Tested/Cleaned 8:38:06 AM 11/22/2022

Smoke Detector ( JANUARY THRU JUNE ) 2nd Inside Stairwell By Room# 202 ( Barcode on door jam )

Tested/Cleaned 8:25:10 AM 11/22/2022

Smoke Detector ( JANUARY THRU JUNE ) 2nd Inside Stairwell By Tested/Cleaned 8:35:04 AM 11/22/2022

ADT Commercial LLC 5 Download Date: 11/22/2022

Room# 224 ( Barcode on door jam )

Smoke Detector ( JULY THRU DECEMBER ) 1st Entrance of Room

Tested/Cleaned 7:50:22 AM 05/26/2022

Smoke Detector ( JULY THRU DECEMBER ) 1st Outside Room 113 Tested/Cleaned 7:50:41 AM 05/26/2022 Smoke Detector ( JULY THRU DECEMBER ) 1st Outside Room 122 Tested/Cleaned 7:48:03 AM 05/26/2022 Smoke Detector ( JULY THRU DECEMBER ) 1st Outside Room 135 Tested/Cleaned 7:47:29 AM 05/26/2022

Untested Initiating

Heat Detector ( JANUARY THRU JUNE ) 1st Inside Room 132 Heat Detector ( JANUARY THRU JUNE ) 1st Inside Room 132B (

Through Rm 132)

Heat Detector ( JANUARY THRU JUNE ) 2nd Inside Cafe ( Room# 213 ) ( Barcode on door jam )

Heat Detector ( JULY THRU DECEMBER ) 1st Inside Room 115 Pull Station ( JULY THRU DECEMBER ) 1st Inside Room 122 Smoke Detector ( JANUARY THRU JUNE ) 2nd Outside Room 211

( High ceiling)

Smoke Detector ( JULY THRU DECEMBER ) 1st Exit for Exibit Deck Smoke Detector ( JULY THRU DECEMBER ) 1st Inside Room 119 ( elevator machine room). TO BE TESTED AT

STATE ELEVATOR INSPECTION.

Smoke Detector ( JULY THRU DECEMBER ) 1st Inside Room 130 Smoke Detector ( JULY THRU DECEMBER ) 1st Outside Giftshop Smoke Detector ( JULY THRU DECEMBER ) 1st Inside Stairs Near

Elevator

Smoke Detector ( JULY THRU DECEMBER ) 1st TO BE TESTED AT STATE ELEVATOR INSPECTION. Outside Elevator

ADT Commercial LLC 6 Download Date: 11/22/2022

Service Summary

The Service Summary section provides an overview of the services performed in this report.

Device Type Service Quantity

Battery Tested 1

Communication Line Tested 1

Control Panel Tested 1

Heat Detector Tested 1

Horn/Strobe Tested 1

Pull Station Tested 8

Releasing Device Tested 1

Smoke Detector Tested/Cleaned 14

Total 28

Heat Detector

Pull Station

Smoke Detector

Total 12

Grand Total 40

ADT Commercial LLC 7 Download Date: 11/22/2022

Auxiliary Functions Testing

Control Panel: 1 - Gamewell IF610-126 (Address

The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.

Type Location Comment ScanID Simulated

Releasing Device

( EVERY 6 MONTHS ) 1st ( DOOR HOLDERS ) by storage# 115 ( Outside Room 130 )

Passed 39483810

Smoke Compartment ( JANUARY THRU JUNE ) 1st Above FACP Passed 35958463

Smoke Compartment ( JANUARY THRU JUNE ) 1st Outside Room

Passed 59352746

Smoke Compartment ( JANUARY THRU JUNE ) 2nd Outside Room

Passed 35958459

205/230

Passed 35958457

Passed 35958456

Passed 35958452

Passed 35958451

Smoke Compartment ( JANUARY THRU JUNE ) 2nd Data/ Electrical Closet

Passed 35958458

Smoke Compartment ( JANUARY THRU JUNE ) 2nd Inside Stairwell By Room# 202 ( Barcode on door jam )

Passed 35958461

Smoke Compartment ( JANUARY THRU JUNE ) 2nd Inside Stairwell By Room# 224 ( Barcode on door jam )

Passed 35958453

Smoke Compartment ( JULY THRU DECEMBER ) 1st Entrance of Room 117

Passed 35958473

Smoke Compartment ( JULY THRU DECEMBER ) 1st Outside Room

Passed 35958471

Passed 35958478

Passed 35958479

211 ( High ceiling)

35958455

Smoke Compartment ( JULY THRU DECEMBER ) 1st Exit for Exibit

35958467

ADT Commercial LLC 8 Download Date: 11/22/2022

Control Panel: 1 - Gamewell IF610-126 (Address

The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.

Type Location Comment ScanID Simulated

Deck

Smoke Compartment ( JULY THRU DECEMBER ) 1st Inside Room 119 ( elevator machine room). TO BE TESTED AT

STATE ELEVATOR INSPECTION.

35958475

Smoke Compartment ( JULY THRU DECEMBER ) 1st Inside Room 130

35958483

Smoke Compartment ( JULY THRU DECEMBER ) 1st Outside Giftshop

35958469

Smoke Compartment ( JULY THRU DECEMBER ) 1st Inside Stairs Near Elevator

35958462

Smoke Compartment ( JULY THRU DECEMBER ) 1st TO BE TESTED AT STATE ELEVATOR INSPECTION. Outside Elevator

35958474

ADT Commercial LLC 9 Download Date: 11/22/2022

Smoke Management Testing

IF610-126 (Address

The Smoke Management Testing section details the test and inspection of device items that are involved in controlling the spread of smoke in a building. Items are grouped by Passed or Failed/ Other.

Location Description Comment ScanID Simulated

Passed Releasing Device

( EVERY 6 MONTHS ) 1st ( DOOR HOLDERS ) by storage# 115 ( Outside Room 130 )

Passed 39483810

ADT Commercial LLC 10 Download Date: 11/22/2022

Battery & Power Supply Testing

IF610-126 (Address

The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.

Battery

Type Location Rated Ah

Rated Volts

Pre Test

Post Test

Min Ah

Tested Ah

Passed Sealed Lead Acid ( EVERY 6 MONTHS ) 1st Above

Ceiling ( exit sign) Outside Room 130

18 12

ADT Commercial LLC 11 Download Date: 11/22/2022

Inventory & Warranty Report

Building: Kettle Pond Visitors Center

Control Panel: 1 - Gamewell IF610-126 (Address

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity

Battery Control 2.50% 1

Communication Line Control 2.50% 1

Control Panel Control 2.50% 1

Heat Detector Initiating 12.50% 5

Horn/Strobe Indicating 2.50% 1

Pull Station Initiating 22.50% 9

Releasing Device Auxiliary 2.50% 1

Smoke Detector Initiating 52.50% 21

Type Qty Model # Description Install Date

In Service - 5 Years to 10 Years

Releasing Device 1

07/11/2017

Gamewell

Battery 1 PS-12180 NB Sealed Lead Acid 07/11/2017

Control Panel 1 IF610-126 (Address

Heat Detector 1 XP95-T Adjustable response 07/11/2017

Heat Detector 4 XP95A Rate-of-Rise 07/11/2017

Pull Station 1 MS-95

Pull Station 8 MS-95 Dual Action 07/11/2017

Smoke Detector 21 XP95A Photoelectric 07/11/2017

MT.PLEASANT ALARMS

Communication Line 1 ACCT#

Wheel lock

Horn/Strobe 1

File details come from the government source that posted it. Updated .