This document is a Fire Alarm and Life Safety System Inspection Certificate for the Kettle Pond Visitors Center in Charlestown, Rhode Island. The inspection was conducted by ADT Commercial LLC on November 22, 2022, and tested to NFPA 72 Standards. The comprehensive report details the testing of various fire safety components, including 40 total devices across categories such as auxiliary, control, indicating, and initiating systems. Of the 40 devices, 28 passed inspection (70%), with 12 devices remaining untested, primarily smoke detectors and heat detectors in specific rooms that require alternative testing methods or are scheduled for state elevator inspection.
The inspection report includes detailed documentation of tested devices, their locations, service times, and dates. The fire alarm system uses a Gamewell IF610-126 control panel installed on July 11, 2017, with components including sealed lead acid batteries, communication lines, pull stations, smoke detectors, and heat detectors. The system covers various building areas such as exhibit spaces, rooms, stairwells, and hallways. While most devices passed inspection, some devices were marked as "untested" and require future testing, particularly those located in elevator machine rooms, inside specific rooms, and near elevator areas.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment_6-_Images_0001.pdf | ||
| Sol_140FS325Q0119_Amd_0001.pdf | ||
| Attachment_5-_Past_Performance_Data_Document.docx | DOCX document | |
| Sol_140FS325Q0119.pdf | ||
| Attachment_4-_SCA_Wage_Determintion.pdf | ||
| Attachment_1-_Performance_Work_Statement.pdf | ||
| Attachment_2-_Quote_Schedule.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fire Alarm and Life Safety System Inspection Certificate
For
Kettle Pond Visitors Center 50 Bend Road Charlestown, RI 02813
Tested to NFPA 72 Standards
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Inspection Date Nov 22, 2022
Building: Kettle Pond Visitors Center Company: ADT Commercial LLC Contact: Karrie Schwaab Contact: Kevin Neagle
Title: . Title: Inspector
ADT Commercial LLC 1 Download Date: 11/22/2022
Executive Summary Generated by: BuildingReports.com
Building Information Building: Kettle Pond Visitors Center Contact: Karrie Schwaab
Address: 50 Bend Road Phone: 401-213-4402
Address: Fax:
City/State/ZIP Code: Charlestown, RI 02813 Mobile:
Country: United States of America Email: karrie_schwaab@fws.gov
Inspection Performed By Company: ADT Commercial LLC Inspector: Kevin Neagle
Address: 300 Myles Standish Blvd Phone: 508-884-6425
Address: Fax:
City/State/ZIP Code: Taunton, MA 02780 Mobile:
Country: United States of America Email: kevin.neagle@redhawkus.com
System Control Unit Manufacturer: Gamewell Inspection Date: 05/26/2022 IDC Style:
Model Number: IF610-126 (Address Install Date: 07/11/2017 SLC Style:
Software Version: Version Date: 07/11/2017 NAC Style:
Location: ( EVERY 6 MONTHS ) 1st Employee Main Entrance
Current Protection:
ADT Commercial LLC 2 Download Date: 11/22/2022
Inspection Summary
Category Total Items Serviced Passed Failed/Other Qty % Qty % Qty % Qty %
Auxiliary 1 2.50% 1 100.00% 1 100.00% 0 0.00% Control 3 7.50% 3 100.00% 3 100.00% 0 0.00% Indicating 1 2.50% 1 100.00% 1 100.00% 0 0.00% Initiating 35 87.50% 23 65.71% 23 100.00% 0 0.00%
Totals 40 100% 28 70.00% 28 100.00% 0 0.00%
Certification
Company: ADT Commercial LLC Building: Kettle Pond Visitors Center
Inspector: Kevin Neagle Contact: Karrie Schwaab
ADT Commercial LLC 3 Download Date: 11/22/2022
Notes & Recommendations
Building: Kettle Pond Visitors Center
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
General Note On 11/22/22, completed quarterly fire alarm system test and inspection.
ADT Commercial LLC 4 Download Date: 11/22/2022
Inspection & Testing
Control Panel: 1 - Gamewell IF610-126 (Address
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.
Device Type Location Service Time Date
Passed Auxiliary
Releasing Device ( EVERY 6 MONTHS ) 1st ( DOOR HOLDERS ) by storage# 115 ( Outside Room 130 )
Tested 7:45:20 AM 05/26/2022
Control Battery ( EVERY 6 MONTHS ) 1st Above Ceiling ( exit sign) Outside Room 130 Tested 7:45:05 AM 05/26/2022
Communication Line ( EVERY 6 MONTHS ) 1st FACP Tested 7:45:13 AM 05/26/2022 Control Panel ( EVERY 6 MONTHS ) 1st Employee Main
Entrance Tested 7:44:47 AM 05/26/2022
Indicating Horn/Strobe ( EVERY 6 MONTHS ) ALL Tested 7:44:56 AM 05/26/2022
Initiating Heat Detector ( JULY THRU DECEMBER ) 1st In Exhibit (High
Ceiling) Tested 7:54:41 AM 05/26/2022
Pull Station ( JANUARY THRU JUNE ) 1st Outside Room 130 Tested 7:45:46 AM 05/26/2022 Pull Station ( JANUARY THRU JUNE ) 2nd Outside Room 202 Tested 8:37:22 AM 11/22/2022 Pull Station ( JANUARY THRU JUNE ) 2nd Outside Room 224 Tested 8:28:29 AM 11/22/2022 Pull Station ( JULY THRU DECEMBER ) 1st Exhibit Left Rear
Exit Tested 7:54:58 AM 05/26/2022
Pull Station ( JULY THRU DECEMBER ) 1st Exhibit Right Rear Exit
Tested 7:54:20 AM 05/26/2022
Pull Station ( JULY THRU DECEMBER ) 1st Exit for Exibit Deck Tested 8:48:56 AM 11/22/2022 Pull Station ( JULY THRU DECEMBER ) 1st Outside Elevator Tested 7:48:21 AM 05/26/2022 Pull Station ( JULY THRU DECEMBER ) 1st Outside Room 112 Tested 7:52:04 AM 05/26/2022 Smoke Detector ( JANUARY THRU JUNE ) 1st Above FACP Tested/Cleaned 1:56:07 PM 11/22/2022 Smoke Detector ( JANUARY THRU JUNE ) 1st Outside Room 132 Tested/Cleaned 7:46:47 AM 05/26/2022 Smoke Detector ( JANUARY THRU JUNE ) 2nd Outside Room 202 Tested/Cleaned 8:25:22 AM 11/22/2022 Smoke Detector ( JANUARY THRU JUNE ) 2nd Outside Room
205/230 Tested/Cleaned 8:26:12 AM 11/22/2022
Smoke Detector ( JANUARY THRU JUNE ) 2nd Outside Room 208 Tested/Cleaned 8:27:11 AM 11/22/2022 Smoke Detector ( JANUARY THRU JUNE ) 2nd Outside Room 214 Tested/Cleaned 8:31:11 AM 11/22/2022 Smoke Detector ( JANUARY THRU JUNE ) 2nd Outside Room 217 Tested/Cleaned 8:32:41 AM 11/22/2022 Smoke Detector ( JANUARY THRU JUNE ) 2nd Data/ Electrical
Closet Tested/Cleaned 8:38:06 AM 11/22/2022
Smoke Detector ( JANUARY THRU JUNE ) 2nd Inside Stairwell By Room# 202 ( Barcode on door jam )
Tested/Cleaned 8:25:10 AM 11/22/2022
Smoke Detector ( JANUARY THRU JUNE ) 2nd Inside Stairwell By Tested/Cleaned 8:35:04 AM 11/22/2022
ADT Commercial LLC 5 Download Date: 11/22/2022
Room# 224 ( Barcode on door jam )
Smoke Detector ( JULY THRU DECEMBER ) 1st Entrance of Room
Tested/Cleaned 7:50:22 AM 05/26/2022
Smoke Detector ( JULY THRU DECEMBER ) 1st Outside Room 113 Tested/Cleaned 7:50:41 AM 05/26/2022 Smoke Detector ( JULY THRU DECEMBER ) 1st Outside Room 122 Tested/Cleaned 7:48:03 AM 05/26/2022 Smoke Detector ( JULY THRU DECEMBER ) 1st Outside Room 135 Tested/Cleaned 7:47:29 AM 05/26/2022
Untested Initiating
Heat Detector ( JANUARY THRU JUNE ) 1st Inside Room 132 Heat Detector ( JANUARY THRU JUNE ) 1st Inside Room 132B (
Through Rm 132)
Heat Detector ( JANUARY THRU JUNE ) 2nd Inside Cafe ( Room# 213 ) ( Barcode on door jam )
Heat Detector ( JULY THRU DECEMBER ) 1st Inside Room 115 Pull Station ( JULY THRU DECEMBER ) 1st Inside Room 122 Smoke Detector ( JANUARY THRU JUNE ) 2nd Outside Room 211
( High ceiling)
Smoke Detector ( JULY THRU DECEMBER ) 1st Exit for Exibit Deck Smoke Detector ( JULY THRU DECEMBER ) 1st Inside Room 119 ( elevator machine room). TO BE TESTED AT
STATE ELEVATOR INSPECTION.
Smoke Detector ( JULY THRU DECEMBER ) 1st Inside Room 130 Smoke Detector ( JULY THRU DECEMBER ) 1st Outside Giftshop Smoke Detector ( JULY THRU DECEMBER ) 1st Inside Stairs Near
Elevator
Smoke Detector ( JULY THRU DECEMBER ) 1st TO BE TESTED AT STATE ELEVATOR INSPECTION. Outside Elevator
ADT Commercial LLC 6 Download Date: 11/22/2022
Service Summary
The Service Summary section provides an overview of the services performed in this report.
Device Type Service Quantity
Battery Tested 1
Communication Line Tested 1
Control Panel Tested 1
Heat Detector Tested 1
Horn/Strobe Tested 1
Pull Station Tested 8
Releasing Device Tested 1
Smoke Detector Tested/Cleaned 14
Total 28
Heat Detector
Pull Station
Smoke Detector
Total 12
Grand Total 40
ADT Commercial LLC 7 Download Date: 11/22/2022
Auxiliary Functions Testing
Control Panel: 1 - Gamewell IF610-126 (Address
The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.
Type Location Comment ScanID Simulated
Releasing Device
( EVERY 6 MONTHS ) 1st ( DOOR HOLDERS ) by storage# 115 ( Outside Room 130 )
Passed 39483810
Smoke Compartment ( JANUARY THRU JUNE ) 1st Above FACP Passed 35958463
Smoke Compartment ( JANUARY THRU JUNE ) 1st Outside Room
Passed 59352746
Smoke Compartment ( JANUARY THRU JUNE ) 2nd Outside Room
Passed 35958459
205/230
Passed 35958457
Passed 35958456
Passed 35958452
Passed 35958451
Smoke Compartment ( JANUARY THRU JUNE ) 2nd Data/ Electrical Closet
Passed 35958458
Smoke Compartment ( JANUARY THRU JUNE ) 2nd Inside Stairwell By Room# 202 ( Barcode on door jam )
Passed 35958461
Smoke Compartment ( JANUARY THRU JUNE ) 2nd Inside Stairwell By Room# 224 ( Barcode on door jam )
Passed 35958453
Smoke Compartment ( JULY THRU DECEMBER ) 1st Entrance of Room 117
Passed 35958473
Smoke Compartment ( JULY THRU DECEMBER ) 1st Outside Room
Passed 35958471
Passed 35958478
Passed 35958479
211 ( High ceiling)
35958455
Smoke Compartment ( JULY THRU DECEMBER ) 1st Exit for Exibit
35958467
ADT Commercial LLC 8 Download Date: 11/22/2022
Control Panel: 1 - Gamewell IF610-126 (Address
The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.
Type Location Comment ScanID Simulated
Deck
Smoke Compartment ( JULY THRU DECEMBER ) 1st Inside Room 119 ( elevator machine room). TO BE TESTED AT
STATE ELEVATOR INSPECTION.
35958475
Smoke Compartment ( JULY THRU DECEMBER ) 1st Inside Room 130
35958483
Smoke Compartment ( JULY THRU DECEMBER ) 1st Outside Giftshop
35958469
Smoke Compartment ( JULY THRU DECEMBER ) 1st Inside Stairs Near Elevator
35958462
Smoke Compartment ( JULY THRU DECEMBER ) 1st TO BE TESTED AT STATE ELEVATOR INSPECTION. Outside Elevator
35958474
ADT Commercial LLC 9 Download Date: 11/22/2022
Smoke Management Testing
IF610-126 (Address
The Smoke Management Testing section details the test and inspection of device items that are involved in controlling the spread of smoke in a building. Items are grouped by Passed or Failed/ Other.
Location Description Comment ScanID Simulated
Passed Releasing Device
( EVERY 6 MONTHS ) 1st ( DOOR HOLDERS ) by storage# 115 ( Outside Room 130 )
Passed 39483810
ADT Commercial LLC 10 Download Date: 11/22/2022
Battery & Power Supply Testing
IF610-126 (Address
The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Battery
Type Location Rated Ah
Rated Volts
Pre Test
Post Test
Min Ah
Tested Ah
Passed Sealed Lead Acid ( EVERY 6 MONTHS ) 1st Above
Ceiling ( exit sign) Outside Room 130
18 12
ADT Commercial LLC 11 Download Date: 11/22/2022
Inventory & Warranty Report
Building: Kettle Pond Visitors Center
Control Panel: 1 - Gamewell IF610-126 (Address
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Device or Type Category % of Inventory Quantity
Battery Control 2.50% 1
Communication Line Control 2.50% 1
Control Panel Control 2.50% 1
Heat Detector Initiating 12.50% 5
Horn/Strobe Indicating 2.50% 1
Pull Station Initiating 22.50% 9
Releasing Device Auxiliary 2.50% 1
Smoke Detector Initiating 52.50% 21
Type Qty Model # Description Install Date
In Service - 5 Years to 10 Years
Releasing Device 1
07/11/2017
Gamewell
Battery 1 PS-12180 NB Sealed Lead Acid 07/11/2017
Control Panel 1 IF610-126 (Address
Heat Detector 1 XP95-T Adjustable response 07/11/2017
Heat Detector 4 XP95A Rate-of-Rise 07/11/2017
Pull Station 1 MS-95
Pull Station 8 MS-95 Dual Action 07/11/2017
Smoke Detector 21 XP95A Photoelectric 07/11/2017
MT.PLEASANT ALARMS
Communication Line 1 ACCT#
Wheel lock
Horn/Strobe 1