This document is a solicitation for the upgrade and expansion of utilities and wet lab construction at the USDA Agricultural Research Service Field Research Implementation and Information Delivery Plains Area in Edinburg, Texas. The solicitation requires contractors to provide construction services including upgrades to electrical utilities and the construction of a new wet lab facility. A mandatory site visit will be held on June 29, 2022 for interested contractors to register for by emailing the points of contact by June 26 with company information. The site visit will provide an opportunity for contractors to view the project location and infrastructure in preparation for submitting offers in response to the solicitation.
View the file
Other files for this federal contract opportunity
Show all 22
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
USDA Wet Lab Utility Upgrades Issue For Bidding And Construction
Edinburg, TX June 06, 2022
BASIC ELECTRICAL REQUIREMENTS 260000 - 1
SECTION 260000 - BASIC ELECTRICAL REQUIREMENTS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of Contract, including General and Supplementary
Conditions and Division 1 Specification Sections, apply to this section and all other
Electrical Specification Sections.
1.2 SUMMARY
A. This Section includes general administrative and procedural requirements, as well as the following basic electrical materials and methods:
1. Submittals.
2. Record documents.
3. Operation and Maintenance manuals.
4. Rough-ins.
5. Electrical installations.
6. Cutting and patching.
7. Access to electrical installations.
B. Summary of Work:
1. Provide a complete integrated electrical system in accordance with the intent of these specifications and the accompanying drawings.
1.3 REFERENCED ORGANIZATIONS AND CODES
A. The following list of abbreviations, are utilized within the specifications and are provided as a reference.
B. All electrical work shall meet or exceed the latest requirements and recommendations of the following codes, regulations, standards, and/or other authorities exercising jurisdiction over the electrical construction work and the project..
1. American National Standards Institute (ANSI); Latest Standards.
2. American Society for Testing and Materials (ASTM); Latest Standards.
3. Institute For Electrical And Electronics Engineers (IEEE); Latest Standards
4. Insulated Cable Engineer’s Association (ICEA); Latest Standards.
5. International Building Code (IBC); 2018 Edition with 2020 Georgia
Amendments.
6. International Existing Building Code (IEBC); 2018 Edition with 2020 Georgia
Amendments.
7. International Fire Code (IFC); 2018 Edition.
BASIC ELECTRICAL REQUIREMENTS 260000 - 2
8. Life Safety Code (LSC-NFPA 101); 2018 Edition.
9. Municipal And State Ordinances Governing Electrical Work.
10. National Electrical Code (NEC-NFPA 70); 2017 Edition.
11. NFPA (National Fire Protection Association).
12. National Electrical Manufacturer’s Association (NEMA). Latest Standards.
13. (National Electrical Contractors Association (NECA). All ANSI Standards and
Recommendation; Latest Edition of Each.
14. National Electrical Installation Standards (NEIS); Latest Standards.
15. National Electrical Safety Code (NESC-ANSI-C-2 or IEEE C2); Latest Edition.
16. National Fire Protection Association Standard for Electrical Safety in the
Workplace (NFPA 70E): 2018 Edition.
17. Occupational Safety and Health Administration (OSHA); Latest Regulations.
18. Underwriters Laboratories, LLC (UL); Latest Standards and Listing.
19. UGA Design and Construction Standards; Latest Edition.
1.4 SITE VISIT
A. Prior to preparing the bid, the electrical subcontractor shall visit the site and become familiar with all existing conditions. Make all necessary investigations as to locations of utilities and all other matters which can affect the work. No additional compensation will be made to the contractor as a result of his failure to familiarize himself with the existing conditions under which the work must be performed.
1.5 OUTAGES
A. For all work requiring an outage, the contractor shall submit an outage request to the
Project Manager minimum 72 hours in advance. The existing mechanical/electrical systems shall remain operational unless turned off by University personnel during the construction of the project. For each electrical outage request include a photograph of the panel index schedule for each panel affected by the outage.
B. Unless otherwise specified, outages of any services required for the performance of this contract and affecting areas other than the immediate work area shall be scheduled at least 72-hours in advance with the Office of Facilities Management. All such outages shall be performed on other than normal duty hours.
C. All electrical outages which will interfere with the normal use of the building in any manner shall be done at such times as shall be mutually agreed upon by the contractor and the Office of Facilities Management.
D. The contractor shall include in his price the cost of all premium time required for outages and other work which interferes with the normal use of the building, which will be performed, in most cases, during other than normal work time and at the convenience of the University.
E. The operation of electrical equipment; required to achieve an outage must be
BASIC ELECTRICAL REQUIREMENTS 260000 - 3
accomplished by University personnel only. Prospective subcontractors under this section are cautioned that the unauthorized operation of electrical equipment or other control devices by their personnel can result in extremely serious consequences for which the contractor will be held accountable.
1.6 INSTALLER’S QUALIFICATIONS
A. Electrical Installer shall submit the following evidence:
1. Five (5) comparable completed projects.
2. Reference letters from minimum of three (3) registered professional engineers, general contractors, building owners, explaining proficiency, quality of work, or other attribute on projects of similar size or substance.
3. Copy of Georgia Master Electrician's License.
4. Local or State license where required.
5. BICSI and NICET certification, where required by these specifications.
B. The electrical installer shall utilize a full time project foreman in charge of all electrical work.
1. Fully qualified and experienced in such work.
2. Available, on site, at all times during construction.
3. All communication shall be through this person.
C. Installer of specialized systems such as Fire Alarms, etc. shall meet the requirements of the associated spec section(s).
1.7 CUTTING, AND PATCHING
A. General trades contractor shall patch floors and walls in areas of removed conduit.
Coordinate location of core-drilling of walls and floors with other contractors and equipment. Provide all other cutting and patching required for own work. Patch to match adjacent surfaces. General trades contractor shall provide painting.
1.8 WORK PERFORMANCE
A. All electrical work must comply with the requirements of NFPA 70 (NEC), NFPA 70B, NFPA 70E, OSHA Part 1910 subpart J, OSHA Part 1910 subpart S and OSHA Part 1910 subpart K in addition to other references required by the contract.
B. Before initiating any work, a job specific work plan must be developed by the contractor.
The work plan must include procedures to be used on and near the live electrical equipment, barriers to be installed, and safety equipment to be used and exit pathways.
C. Job site and worker safety are the responsibility of the contractor. Compliance with the
BASIC ELECTRICAL REQUIREMENTS 260000 - 4
requirements of NFPA 70E is subject to ongoing inspection by University personnel and failure to comply will result in an immediate Stop Work order being issued and enforced at the contractor’s expense.
D. Energized electrical conductors and circuit parts to which an employee might be exposed shall be put into an electrically safe work condition before an employee performs work any time the employee is within the limited approach boundary or, where an increased risk of injury from an exposure to an arc flash hazard exists.
E. Outages should be scheduled a minimum of 72-hours in advance.
F. Mandatory Requirements: The following requirements are mandatory:
1. Protective Equipment: Electricians must use full protective equipment (i.e., certified and tested insulating material to cover exposed energized electrical components, certified and tested insulated tools, etc.) while working on energized systems in accordance with NFPA 70E.
2. Energized Work Permit: An Energized Work Permit is required for any work on energized circuits or equipment. Permit must be approved by Department of
Operations and Maintenance prior to performing energized work. Submit the work permit with the outage request.
1.9 SUBMITTALS
A. General: Follow the procedures specified in Division 01 Section "Submittals."
B. Product data as specified in the electrical specifications.
C. Shop drawings detailing fabrication and installation requirements for electrical equipment.
D. In addition to the following list, submit other shop drawings as may be requested by owner Representative.
1. Divisions 26, & 28:
a. Compression Wire Connectors
b. Fire Resistant Sealant
c. Ground Wire
d. Raceway, and Boxes
e. Wires and Cables
f. Fire Alarm System: Refer to Division 28 Section “Digital, Addressable
Fire Alarm System” for submittal requirements
E. Submittal File Format: File formats for each submittal shall be electronically as follows:
BASIC ELECTRICAL REQUIREMENTS 260000 - 5
1. Product Data: “pdf” file format.
2. Shop Drawings: “pdf” file format.
3. Coordinated Drawings: “pdf” or “dwg” file formats.
1.10 QUALITY ASSURANCE
A. Comply with NFPA 70 for components and installation.
B. Listing and Labeling: Provide products specified in this Section that are listed and labeled.
1. The Terms “Listed and Labeled”: As defined in the National Electrical Code, Article 100.
2. Listing and Labeling Agency Qualifications: A “Nationally Recognized Testing
Laboratory” (NRTL) as defined in OSHA Regulation 1910.7.
C. Install all components and equipment per manufacturer’s written instructions.
D. Provide installation in accordance with recognized trade organizations and standards:
1. NEMA.
2. NECA “Standards of Installation”
1.11 RECORD DOCUMENTS
A. Prepare record documents in accordance with the requirements in Division 01 Section
"Contract Closeout." In addition to the requirements specified in Division 01, indicate the following installed conditions:
1. Conduit and wire runs between the points
2. Equipment locations (exposed and concealed), dimensioned from prominent building lines.
3. Approved substitutions, Contract Modifications, RFI responses and actual equipment and materials installed.
1.12 OPERARTION AND MAINTENANCE MANUALS
A. Electrical O & M Manual File: Provide one (1) electronic file “pdf format” for the projects Electrical Operation and Maintenance Manual for the Material and Equipment installed in the project included in Divisions 26, and 28 on a CD-R. The electronic
Electrical O & M manual shall include one copy of each approved submittal, any manufacturer’s maintenance manuals, all warranty certificates, arranged in file folders for each submittal. Also include the address, phone number and contact person for each
BASIC ELECTRICAL REQUIREMENTS 260000 - 6
supplier. Files shall be stacked and include both a book mark and tree structure for accessing each submittal file as indicated in Division 01 Section “Closeout Procedures”.
B. Alternate O & M File: The CM/General Contractor has the option to include all disciplines in a single O&M Manual file for smaller type renovation projects. The electronic O & M manual shall include one copy of each approved submittal, approved
TAB report, any manufacturers maintenance manuals, all warranty certificates, arranged in file folders under each discipline for each submittal. Files shall be stacked and include both a book mark and tree structure for accessing each submittal file The electronic file structure for the single file shall be as follows:
1. Cover Sheet
2. Forward
3. General Information
4. Subcontractors List
5. Suppliers List
6. General Warranty Statement – include the manufacturer’s warranty with the equipment submittal in the appropriate discipline.
7. Mechanical: group all mechanical data under this heading with a tree structure.
8. Electrical: group all electrical data under this heading with a tree structure.
9. As Built Drawings: Contractors Markups.
A. Provide service and operating manuals for the following:
1. Division 28 Section “Digital, Addressable Fire Alarm System”.
1.13 DELIVERY, STORAGE, AND HANDLING
A. Deliver products to the project properly identified with names, model numbers, types, grades, compliance labels, and other information needed for identification.
1.14 SEQUENCING AND SCHEDULING
A. Coordinate electrical equipment installation with other building components.
B. Arrange for chases, slots, and openings in building structure during progress of construction to allow for electrical installations.
C. Coordinate the installation of required supporting devices and other structural components as they are constructed.
D. Sequence, coordinate, and integrate installations of mechanical materials and equipment for efficient flow of the Work. Coordinate installation of large equipment requiring positioning prior to closing in the building.
E. Coordinate connection of electrical services.
BASIC ELECTRICAL REQUIREMENTS 260000 - 7
F. Coordinate requirements for access panels and doors where electrical items requiring access are concealed behind finished surfaces. Access panels and doors are specified in the Architectural Specifications.
G. Coordinate installation of identifying devices after completing covering and painting where devices are applied to surfaces. Install identifying devices prior to installing acoustical ceilings and similar concealment.
1.15 VARIANCES
A. Where variances occur between the drawings and specifications or within either document itself, the item or arrangement of better quality, greater quantity or higher cost shall be included in the contract price. The Engineer shall decide on the item and manner in which the work shall be provided.
1.16 GUARANTEE/WARRANTY:
A. All materials, equipment, etc. provided by the general contractor and/or his subcontractors shall be guaranteed and warranted to be free from defects in workmanship and materials for a period of one (1) full year after date of certificate of completion and acceptance of work by Owner. Any defects in workmanship, materials, or performance which appear within the guarantee period shall be corrected by the contractor without cost to the owner, within a reasonable time, to be specified by Owner representative. In default thereof, owner may have such work done and charge the cost of same to the contractor. In addition to the above statement the Guarantee/Warranty Period shall include all labor cost related to all warranty work.
PART 2 - PRODUCTS
2.1 LISTED MANUFACTURERS:
A. Listed Manufacturers: The listed manufacturers indicated in Part 2 of each specification section as the basis of design represents the minimum level of quality for materials and equipment that is acceptable to Owner. Unless otherwise indicated in each specification section, contractors may submit material and equipment by non listed manufacturers provided said submittals meet the requirements of these specifications. All submitted materials and equipment are subject to approval by the project Architect/Engineer.
B. Approved Equal Equipment Layouts: The equipment layouts and the related mechanical and electrical service connections, access space and supports indicated on the construction documents represent equipment provided by the specified basis of design manufacturer and model number. When the successful bidder chooses to provide “or approved equal” equipment by one (1) of the other listed manufacturers in the specifications, the bidder shall be responsible for providing all adjustments and
BASIC ELECTRICAL REQUIREMENTS 260000 - 8
modifications to the services necessary to make connections to the equipment, the bidder shall be responsible for installing the equipment such that all required clear access space is maintained, and the bidder shall be responsible for providing all adjustments and modifications to the equipment mounting and supports. All adjustments and modifications shall be provided by the bidder and appropriate subcontractors at no additional cost to the project.
PART 3 – EXECUTION
3.1 ROUGH-IN
A. Verify final locations for rough-ins with field measurements and with the requirements of the actual equipment to be connected.
B. For equipment rough-in requirements see specifications for electrical equipment.
3.2 ELECTRICAL INSTALLATIONS
A. General: Sequence, coordinate, and integrate the various elements of electrical systems, materials, and equipment. Comply with the following requirements:
1. Coordinate electrical systems, equipment, and materials installation with other building components.
2. Verify all dimensions by field measurements.
3. Install systems, materials, and equipment to conform with approved submittal data, to greatest extent possible. Conform to arrangements indicated by the
Contract Documents, recognizing that portions of the Work are shown only in diagrammatic form. Where coordination requirements conflict with individual system requirements, refer conflict to Owner.
4. Install systems, materials, and equipment level and plumb, parallel and perpendicular to other building systems and components, where installed exposed in finished spaces.
5. Install electrical equipment to facilitate servicing, maintenance, and repair or replacement of equipment components. As much as practical, connect equipment for ease of disconnecting, with minimum of interference with other installations.
6. Install systems, materials, and equipment giving right-of-way priority to systems required to be installed at a specified slope.
3.3 CUTTING AND PATCHING
A. General: Perform cutting and patching in accordance with Division 1 Section "Cutting and Patching." In addition to the requirements specified in Division 1, the following requirements apply:
1. Protection of Installed Work: During cutting and patching operations, protect adjacent installations.
BASIC ELECTRICAL REQUIREMENTS 260000 - 9
B. Perform cutting, fitting, and patching of electrical equipment and materials required to:
1. Uncover Work to provide for installation of ill timed Work.
2. Remove and replace defective Work.
3. Remove and replace Work not conforming to requirements of the Contract
Documents.
4. Disconnect installed work as specified for testing.
5. Install equipment and materials in existing structures.
6. Upon written instructions from Owner representative, uncover and restore Work to provide for Owner Representative’s observation of concealed Work.
C. Cut, remove and legally dispose of selected electrical equipment, components, and materials as indicated, including but not limited to removal of electrical systems and equipment as indicated on the drawings and specifications and other electrical items made obsolete by the new Work.
D. Protect the structure, furnishings, finishes, and adjacent materials not indicated or scheduled to be removed.
E. Provide and maintain temporary partitions or dust barriers adequate to prevent the spread of dust and dirt to adjacent areas.
1. Patch existing finished surfaces and building components using new materials matching existing materials and experienced Installers. Installers' qualifications refer to the materials and methods required for the surface and building components being patched.
a. Refer to Division 01 Section "Definitions and Standards" for definition of
"experienced Installer."
2. Patch finished surfaces and building components using new materials specified for the original installation and experienced Installers. Installers' qualifications refer to the materials and methods required for the surface and building components being patched.
a. Refer to Division 01 Section "Definitions and Standards" for definition of
"experienced Installer."
3.4 PROTECTION OF WORK
A. Protect work, material and equipment from weather and construction operations before and after installation.
B. Properly store and handle all materials and equipment.
C. Cover temporary openings for electrical equipment to prevent the entrance of water, dirt, debris, and other foreign matter.
BASIC ELECTRICAL REQUIREMENTS 260000 - 10
3.5 PROVISIONS FOR ACCESS
A. Furnish and install adequate access to all electrical components. The following list shall be used as a guide only:
1. Disconnects.
2. Variable frequency drives.
B. Access shall be as required by code and/or as determined by the Architect and Engineer.
C. Refer to contract drawings where access panels have been specifically located.
D. Where access is by means of lift out ceiling tiles or panels mark access each panel using small color coded or numbered tabs. Provide an index chart for identification. Place markers in corner of tile.
3.6 RECORD DRAWINGS (As Built)
A. Upon completion of the electrical installations, the Installer shall deliver to the Architect one (1) complete set of marked-up blueprints of the electrical contract drawings.
1. The mark-ups shall be legibly marked in red pencil to show all changes and departures of the installation as compared with the original design.
2. Refer to General Requirements of Division 01 for additional requirements pertaining to Submittals and Record Drawings.
3.7 CLOSEOUT PROCEDURES
A. Operating and Maintenance Instructions: Submit Complete Package At Least Two (2)
Months Prior To Substantial Completion. Arrange for each installer of equipment that requires regular maintenance to meet with the Owner's personnel to provide instruction in proper operation and maintenance. If installers are not experienced in procedures, provide instruction by manufacturer's representatives. Include a detailed review of the following items:
1. Maintenance manuals, including a customized list of preventive maintenance items and annual schedule for maintenance.
2. Record documents.
3. Complete inventory of spare parts and materials.
4. Tools.
5. Identification systems.
6. Control sequences.
7. Hazards.
8. Cleaning.
9. Warranties and bonds.
BASIC ELECTRICAL REQUIREMENTS 260000 - 11
10. Maintenance agreements and similar continuing commitments.
3.8 INSPECTIONS
A. Contractor shall:
1. Schedule, pay for any other inspection fees and charges related to the installation of the electrical. Arrange for inspection of the work by the code authority having jurisdiction. Comply with NEC and all local, state & federal codes.
2. Deliver all certificates to the Owner prior to final acceptance of work.
B. Notify Owner Representative in advance of scheduled inspections.
C. An electrical foreman, superintendent or other supervisor familiar with the project shall be in attendance for all scheduled electrical inspections.
D. Electrical inspection shall be by the [third (3rd) Party Inspector approved by the UGA inspection department personnel.
E. Schedule the preliminary and rough-in inspections in a timely manner. Any work covered prior to any inspection in a manner which, in the inspector's opinion, precludes a complete inspection shall be uncovered at the installer’s cost.
3.9 DEMOLITION:
A. Remove and dispose of all existing materials not required for re-use or re-installation.
B. Deliver on the premises, where directed, existing material and equipment which is to be salvaged and remain property of Owner.
C. All other materials removed shall become the property of the Contractor and shall be removed from the premises.
D. Remove conduit, hangers, supports, etc. to a point below the finished floors or behind finished walls and cap. Cut such items flush with masonry surfaces.
E. Remove wiring and conduit back to source panelboard or switch, or to last remaining device on the circuit. Remove conduit, hangers, supports, etc. unless otherwise noted.
Conduit may remain to be reused for new work provided it is of the specified size and type and in condition acceptable to Owner Representative.
F. Any conduit abandoned in concrete slabs, walls, or other inaccessible locations shall be left with a nylon pull wire. Ends shall be capped with push plugs for future use.
3.10 REPAIRS & RESTORATION OF SURFACES AND FINISHES:
BASIC ELECTRICAL REQUIREMENTS 260000 - 12
A. Restore all finishes, equipment and surfaces to original condition, where affected by the work. Provide the following, where applicable, in accordance with accepted trade standards and to Owner’s satisfaction:
1. Replace damaged ceiling tiles.
2. Replace ceiling tiles where removal has left holes or cuts in original tiles.
3. Patch, repair and repaint all walls and surfaces cut, penetrated or otherwise disturbed by the work.
4. Patch holes and penetrations in wood, masonry and plaster.
5. Provide suitable cover plates for all recessed back boxes of equipment removed and not covered by new devices.
6. Provide larger trim or cover plates for new devices, where old back boxes, holes, etc. are not concealed by new work.
3.11 FINAL CLEANING
A. General: General cleaning during construction is required by the General Conditions and included in Section Temporary Facilities.
B. Cleaning: Employ experienced workers or professional cleaners for final cleaning. Clean each surface or unit to the condition expected in a normal, commercial building cleaning and maintenance program. Comply with manufacturer's instructions.
C. Remove all electrical clippings, wiring, nuts, bolts, etc. left on top of ceilings and ceiling tiles.
3.12 PROJECT PUNCH OUT
A. Architect/Engineer will perform punch out reviews and will provide the Contractor with a list of punch list items to be completed before contract close out. Each and every punch list item shall be initialed and dated by the Contractor when the work is complete. The
Architect/ Engineer will not perform any punch list verification until all items have been completed, initialed, dated and the list returned to the Architect/Engineer. If any items have been initialed as being completed by the Contractor and the Architect/Engineer determines that the work is not complete, the Architect/Engineer shall be reimbursed by the Contractor at his regular hourly rate for any and all items requiring revisiting of the site by the Architect/Engineer. Reimbursement shall be made by deducting the
Architect/Engineer fee from the Contractor's final payment.
END OF SECTION 260000
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260526 - 1
SECTION 260526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section includes grounding and bonding systems and equipment.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product indicated.
1.4 INFORMATIONAL SUBMITTALS
A. Qualification Data: For testing agency and testing agency's field supervisor.
B. Field quality-control reports.
1.5 CLOSEOUT SUBMITTALS
A. Operation and Maintenance Data: For grounding to include in emergency, operation, and maintenance manuals.
1.6 QUALITY ASSURANCE
A. Testing Agency Qualifications: Certified by NETA.
PART 2 - PRODUCTS
2.1 SYSTEM DESCRIPTION
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
B. Comply with UL 467 for grounding and bonding materials and equipment.
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260526 - 2
2.2 MANUFACTURERS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Advanced Lightning Technology, Ltd.
2. Burndy; Part of Hubbell Electrical Systems.
3. ERICO International Corporation.
4. Galvan Industries, Inc.; Electrical Products Division, LLC.
5. O-Z/Gedney; a brand of Emerson Industrial Automation.
6. Thomas & Betts Corporation; A Member of the ABB Group.
2.3 CONDUCTORS
A. Insulated Conductors: Copper wire or cable insulated for 600 V unless otherwise required by applicable Code or authorities having jurisdiction.
B. Bare Copper Conductors:
1. Solid Conductors: ASTM B 3.
2. Stranded Conductors: ASTM B 8.
3. Tinned Conductors: ASTM B 33.
4. Bonding Cable: 28 kcmil, 14 strands of No. 17 AWG conductor, 1/4 inch (6 mm) in diameter.
5. Bonding Conductor: No. 4 or No. 6 AWG, stranded conductor.
6. Bonding Jumper: Copper tape, braided conductors terminated with copper ferrules; 1-5/8 inches (41 mm) wide and 1/16 inch (1.6 mm) thick.
7. Tinned Bonding Jumper: Tinned-copper tape, braided conductors terminated with copper ferrules; 1-5/8 inches (41 mm) wide and 1/16 inch (1.6 mm) thick.
2.4 CONNECTORS-UL Listed
A. Listed and labeled by an NRTL acceptable to authorities having jurisdiction for applications in which used and for specific types, sizes, and combinations of conductors and other items connected.
B. Welded Connectors: Exothermic-welding kits of types recommended by kit manufacturer for materials being joined and installation conditions.
C. Bus-Bar Connectors: Mechanical type, cast silicon bronze, solderless compression-type wire terminals, and long-barrel, two-bolt connection to ground bus bar.
http://www.specagent.com/Lookup?ulid=7341 http://www.specagent.com/Lookup?uid=123457102197 http://www.specagent.com/Lookup?uid=123457071692 http://www.specagent.com/Lookup?uid=123457071694 http://www.specagent.com/Lookup?uid=123457071696 http://www.specagent.com/Lookup?uid=123457071699 http://www.specagent.com/Lookup?uid=123457071703
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260526 - 3
PART 3 - EXECUTION
3.1 APPLICATIONS
A. Conductors: Install solid conductor for No. 10 AWG and smaller, and stranded conductors for
No. 8 AWG and larger unless otherwise indicated. Minimum size for power or grounding conductors shall be #12 AWG.
B. Conductor Terminations and Connections:
1. Equipment Grounding Conductor Terminations: Bolted connectors.
3.2 EQUIPMENT GROUNDING
A. Install insulated equipment grounding conductors with all feeders and branch circuits.
B. Install insulated equipment grounding conductors with the following items, in addition to those required by NFPA 70:
1. Feeders and branch circuits.
2. Single-phase motor and appliance branch circuits.
3. Three-phase motor and appliance branch circuits.
4. Flexible raceway runs.
3.3 INSTALLATION
A. Grounding Conductors: Route along shortest and straightest paths possible unless otherwise indicated or required by Code. Avoid obstructing access or placing conductors where they may be subjected to strain, impact, or damage.
B. Bonding Straps and Jumpers: Install in locations accessible for inspection and maintenance except where routed through short lengths of conduit.
1. Bonding to Structure: Bond straps directly to basic structure, taking care not to penetrate any adjacent parts.
2. Bonding to Equipment Mounted on Vibration Isolation Hangers and Supports: Install bonding so vibration is not transmitted to rigidly mounted equipment.
3. Use exothermic-welded connectors for outdoor locations; if a disconnect-type connection is required, use a bolted clamp.
3.4 FIELD QUALITY CONTROL
A. Testing Agency: Engage a qualified testing agency to perform tests and inspections.
B. Perform tests and inspections.
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260526 - 4
C. Tests and Inspections:
1. After installing grounding system but before permanent electrical circuits have been energized, test for compliance with requirements.
2. Inspect physical and mechanical condition. Verify tightness of accessible, bolted, electrical connections with a calibrated torque wrench according to manufacturer's written instructions.
3. Test completed grounding system at each location where a maximum ground-resistance level is specified.
a. Perform tests by fall-of-potential method according to IEEE 81.
D. Grounding system will be considered defective if it does not pass tests and inspections.
E. Prepare test and inspection reports.
F. Excessive Ground Resistance: If resistance to ground exceeds specified values, notify Engineer promptly and include recommendations to reduce ground resistance.
END OF SECTION 260526
HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260529 - 1
SECTION 260529 - HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Steel slotted support systems.
2. Conduit and cable support devices.
3. Support for conductors in vertical conduit.
4. Structural steel for fabricated supports and restraints.
5. Mounting, anchoring, and attachment components, including powder-actuated fasteners, mechanical expansion anchors, concrete inserts, clamps, through bolts, toggle bolts, and hanger rods.
6. Fabricated metal equipment support assemblies.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product.
1. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for the following:
a. Slotted support systems, hardware, and accessories.
b. Clamps.
c. Hangers.
d. Sockets.
e. Eye nuts.
f. Fasteners.
g. Anchors.
h. Saddles.
i. Brackets.
2. Include rated capacities and furnished specialties and accessories.
HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260529 - 2
1.4 INFORMATIONAL SUBMITTALS
A. Coordination Drawings: Reflected ceiling plan(s) and other details, drawn to scale, on which the following items are shown and coordinated with each other, using input from installers of the items involved:
1. Suspended ceiling components.
2. Ductwork, piping, fittings, and supports.
3. Structural members to which hangers and supports will be attached.
4. Size and location of initial access modules for acoustical tile.
5. Items penetrating finished ceiling, including the following:
a. Luminaires.
b. Air outlets and inlets.
c. Speakers.
d. Sprinklers.
e. Access panels.
B. Welding certificates.
1.5 QUALITY ASSURANCE
A. Welding Qualifications: Qualify procedures and personnel according to AWS D1.1/D1.1M.
PART 2 - PRODUCTS
2.1 SUPPORT, ANCHORAGE, AND ATTACHMENT COMPONENTS
A. Steel Slotted Support Systems: Preformed steel channels and angles with minimum 13/32-inch-
(10-mm-) diameter holes at a maximum of 8 inches (200 mm) o.c. in at least one surface.
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Allied Tube & Conduit; a part of Atkore International.
b. ERICO International Corporation.
c. GS Metals Corp.
d. Thomas & Betts Corporation; A Member of the ABB Group.
e. Wesanco, Inc.
2. Standard: Comply with MFMA-4 factory-fabricated components for field assembly.
3. Material for Channel, Fittings, and Accessories: Galvanized steel.
4. Channel Width: Selected for applicable load criteria.
5. Metallic Coatings: Hot-dip galvanized after fabrication and applied according to MFMA-
4.
B. Conduit and Cable Support Devices: Steel hangers, clamps, and associated fittings, designed for types and sizes of raceway or cable to be supported.
http://www.specagent.com/Lookup?ulid=1736 http://www.specagent.com/Lookup?uid=123457119499 http://www.specagent.com/Lookup?uid=123457119501 http://www.specagent.com/Lookup?uid=123457119502 http://www.specagent.com/Lookup?uid=123457119506 http://www.specagent.com/Lookup?uid=123457119505
HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260529 - 3
C. Support for Conductors in Vertical Conduit: Factory-fabricated assembly consisting of threaded body and insulating wedging plug or plugs for non-armored electrical conductors or cables in riser conduits. Plugs shall have number, size, and shape of conductor gripping pieces as required to suit individual conductors or cables supported. Body shall be made of malleable iron.
D. Structural Steel for Fabricated Supports and Restraints: ASTM A 36/A 36M steel plates, shapes, and bars; black and galvanized.
E. Mounting, Anchoring, and Attachment Components: Items for fastening electrical items or their supports to building surfaces include the following:
1. Powder-Actuated Fasteners: Threaded-steel stud, for use in hardened portland cement concrete, steel, or wood, with tension, shear, and pullout capacities appropriate for supported loads and building materials where used.
a. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1) Hilti, Inc.
2) ITW Ramset/Red Head; Illinois Tool Works, Inc.
3) MKT Fastening, LLC.
4) Simpson Strong-Tie Co., Inc.
2. Mechanical-Expansion Anchors: Insert-wedge-type, zinc-coated steel, for use in hardened portland cement concrete, with tension, shear, and pullout capacities appropriate for supported loads and building materials where used.
a. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1) B-line, an Eaton business.
2) Empire Tool and Manufacturing Co., Inc.
3) Hilti, Inc.
4) ITW Ramset/Red Head; Illinois Tool Works, Inc.
3. Concrete Inserts: Steel or malleable-iron, slotted support system units are similar to MSS
Type 18 units and comply with MFMA-4 or MSS SP-58.
4. Clamps for Attachment to Steel Structural Elements: MSS SP-58 units are suitable for attached structural element.
5. Through Bolts: Structural type, hex head, and high strength. Comply with
ASTM F 3125/F 3125M, Grade A325 (Grade A325M).
6. Toggle Bolts: All-steel springhead type.
7. Hanger Rods: Threaded steel.
2.2 FABRICATED METAL EQUIPMENT SUPPORT ASSEMBLIES
A. Description: Welded or bolted structural-steel shapes, shop or field fabricated to fit dimensions of supported equipment.
http://www.specagent.com/Lookup?ulid=1742 http://www.specagent.com/Lookup?uid=123457119524 http://www.specagent.com/Lookup?uid=123457119525 http://www.specagent.com/Lookup?uid=123457119526 http://www.specagent.com/Lookup?uid=123457119527 http://www.specagent.com/Lookup?ulid=1746 http://www.specagent.com/Lookup?uid=123457119528 http://www.specagent.com/Lookup?uid=123457119529 http://www.specagent.com/Lookup?uid=123457119530 http://www.specagent.com/Lookup?uid=123457119531
HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260529 - 4
B. Materials: Comply with requirements in other section for "Metal Fabrications" for steel shapes and plates.
PART 3 - EXECUTION
3.1 APPLICATION
A. Comply with the following standards for application and installation requirements of hangers and supports, except where requirements on Drawings or in this Section are stricter:
1. NECA 1.
2. NECA 101
3. NECA 105.
B. Comply with requirements in other section for firestopping materials and installation for penetrations through fire-rated walls, ceilings, and assemblies.
C. Comply with requirements for raceways and boxes specified in other section for "Raceways and
Boxes for Electrical Systems."
D. Maximum Support Spacing and Minimum Hanger Rod Size for Raceways: Space supports for
EMT, IMC, and RMC as required by NFPA 70. Minimum rod size shall be 1/4 inch (6 mm) in diameter.
E. Multiple Raceways or Cables: Install trapeze-type supports fabricated with steel slotted support system, sized so capacity can be increased by at least 25 percent in future without exceeding specified design load limits.
1. Secure raceways and cables to these supports with two-bolt conduit clamps.
3.2 SUPPORT INSTALLATION
A. Comply with NECA 1 and NECA 101 for installation requirements except as specified in this article.
B. Raceway Support Methods: In addition to methods described in NECA 1, EMT, IMC and RMC may be supported by openings through structure members, according to NFPA 70.
C. Strength of Support Assemblies: Where not indicated, select sizes of components so strength will be adequate to carry present and future static loads within specified loading limits.
Minimum static design load used for strength determination shall be weight of supported components plus 200 lb (90 kg).
D. Mounting and Anchorage of Surface-Mounted Equipment and Components: Anchor and fasten electrical items and their supports to building structural elements by the following methods unless otherwise indicated by code:
HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260529 - 5
1. To Wood: Fasten with lag screws or through bolts.
2. To Masonry: Approved toggle-type bolts on hollow masonry units and expansion anchor fasteners on solid masonry units.
3. To Existing Concrete: Expansion anchor fasteners.
4. Instead of expansion anchors, powder-actuated driven threaded studs provided with lock washers and nuts may be used in existing standard-weight concrete 4 inches (100 mm) thick or greater. Do not use for anchorage to lightweight-aggregate concrete or for slabs less than 4 inches (100 mm) thick.
5. To Steel: Welded threaded studs complying with AWS D1.1/D1.1M, with lock washers and nuts.
6. To Light Steel: Sheet metal screws.
7. Items Mounted on Hollow Walls and Nonstructural Building Surfaces: Mount cabinets, panelboards, disconnect switches, control enclosures, pull and junction boxes, transformers, and other devices on slotted-channel racks attached to substrate by means that comply with seismic-restraint strength and anchorage requirements.
E. Drill holes for expansion anchors in concrete at locations and to depths that avoid the need for reinforcing bars.
3.3 INSTALLATION OF FABRICATED METAL SUPPORTS
A. Comply with installation requirements in other section for site-fabricated metal supports.
B. Cut, fit, and place miscellaneous metal supports accurately in location, alignment, and elevation to support and anchor electrical materials and equipment.
C. Field Welding: Comply with AWS D1.1/D1.1M.
3.4 PAINTING
A. Touchup: Clean field welds and abraded areas of shop paint. Paint exposed areas immediately after erecting hangers and supports. Use same materials as used for shop painting. Comply with
SSPC-PA 1 requirements for touching up field-painted surfaces.
1. Apply paint by brush or spray to provide minimum dry film thickness of 2.0 mils (0.05 mm).
B. Touchup: Comply with requirements in other sections for cleaning and touchup painting of field welds, bolted connections, and abraded areas of shop paint on miscellaneous metal.
C. Galvanized Surfaces: Clean welds, bolted connections, and abraded areas and apply galvanizing-repair paint to comply with ASTM A 780.
END OF SECTION 260529
HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260529 - 6
THIS PAGE INTENTIONALLY LEFT BLANK.
RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS 260533 - 1
SECTION 260533 - RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Metal conduits and fittings.
2. Boxes, and enclosures.
1.3 DEFINITIONS
A. GRC: Galvanized rigid steel conduit.
1.4 ACTION SUBMITTALS
A. Product Data: For raceways, and fittings, and hinged-cover enclosures.
B. Shop Drawings: For custom enclosures. Include plans, elevations, sections, and attachment details.
1.5 INFORMATIONAL SUBMITTALS
A. Coordination Drawings: Conduit routing plans, drawn to scale, on which the following items are shown and coordinated with each other, using input from installers of items involved:
1. Structural members in paths of conduit groups with common supports.
2. HVAC and plumbing items and architectural features in paths of conduit groups with common supports.
B. Seismic Qualification Data: Certificates, for enclosures, cabinets, and conduit racks and their mounting provisions, including those for internal components, from manufacturer.
1. Basis for Certification: Indicate whether withstand certification is based on actual test of assembled components or on calculation.
2. Dimensioned Outline Drawings of Equipment Unit: Identify center of gravity and locate and describe mounting and anchorage provisions.
RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS 260533 - 2
3. Detailed description of equipment anchorage devices on which the certification is based and their installation requirements.
4. Detailed description of conduit support devices and interconnections on which the certification is based and their installation requirements.
C. Source quality-control reports.
PART 2 - PRODUCTS
2.1 METAL CONDUITS AND FITTINGS
A. Metal Conduit:
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Allied Tube & Conduit; a part of Atkore International.
b. FSR Inc.
c. NEC, Inc.
d. O-Z/Gedney; a brand of Emerson Industrial Automation.
2. Listing and Labeling: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
3. GRC: Comply with ANSI C80.1 and UL 6.
4. EMT: Comply with ANSI C80.3 and UL 797.
5. FMC: Comply with UL 1; zinc-coated steel.
6. LFMC: Flexible steel conduit with PVC jacket and complying with UL 360.
B. Metal Fittings:
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Allied Tube & Conduit; a part of Atkore International.
b. FSR Inc.
c. NEC, Inc.
d. O-Z/Gedney; a brand of Emerson Industrial Automation.
2. Comply with NEMA FB 1 and UL 514B.
3. Listing and Labeling: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
4. Fittings, General: Listed and labeled for type of conduit, location, and use.
5. Fittings for EMT:
a. Material: Steel.
b. Type: compression.
http://www.specagent.com/Lookup?ulid=12972 http://www.specagent.com/Lookup?uid=123457087067 http://www.specagent.com/Lookup?uid=123457087071 http://www.specagent.com/Lookup?uid=123457102297 http://www.specagent.com/Lookup?uid=123457087075 http://www.specagent.com/Lookup?ulid=12973 http://www.specagent.com/Lookup?uid=123457087087 http://www.specagent.com/Lookup?uid=123457087091 http://www.specagent.com/Lookup?uid=123457100739 http://www.specagent.com/Lookup?uid=123457087095
RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS 260533 - 3
C. Joint Compound for GRC,: Approved, as defined in NFPA 70, by authorities having jurisdiction for use in conduit assemblies, and compounded for use to lubricate and protect threaded conduit joints from corrosion and to enhance their conductivity.
2.2 BOXES, AND ENCLOSURES
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Crouse-Hinds, an Eaton business.
2. EGS/Appleton Electric.
3. FSR Inc.
4. Hoffman; a brand of Pentair Equipment Protection.
5. Hubbell Incorporated.
6. O-Z/Gedney; a brand of Emerson Industrial Automation.
B. General Requirements for Boxes, and Enclosures: Boxes, and enclosures installed in wet locations shall be listed for use in wet locations.
C. Sheet Metal Outlet and Device Boxes: Comply with NEMA OS 1 and UL 514A.
D. Small Sheet Metal Pull and Junction Boxes: NEMA OS 1.
E. Cast-Metal Access, Pull, and Junction Boxes: Comply with NEMA FB 1 and UL 1773, cast aluminum with gasketed cover.
F. Device Box Dimensions: 4 inches square by 2-1/8 inches deep (100 mm square by 60 mm deep).
G. Gangable boxes are allowed.
H. Hinged-Cover Enclosures: Comply with UL 50 and NEMA 250, Type 1 with continuous-hinge cover with flush latch unless otherwise indicated.
1. Metal Enclosures: Steel, finished inside and out with manufacturer's standard enamel.
2. Interior Panels: Steel; all sides finished with manufacturer's standard enamel.
PART 3 - EXECUTION
3.1 RACEWAY APPLICATION
A. Outdoors: Apply raceway products as specified below unless otherwise indicated:
1. Exposed Conduit: GRC.
2. Connection to Vibrating Equipment (Including Transformers and Hydraulic, Pneumatic, Electric Solenoid, or Motor-Driven Equipment): LFMC.
3. Boxes and Enclosures, Aboveground: NEMA 250, Type 4.
http://www.specagent.com/Lookup?ulid=1754 http://www.specagent.com/Lookup?uid=123457087009 http://www.specagent.com/Lookup?uid=123457086998 http://www.specagent.com/Lookup?uid=123457087005 http://www.specagent.com/Lookup?uid=123457087010 http://www.specagent.com/Lookup?uid=123457087015 http://www.specagent.com/Lookup?uid=123457087011
RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS 260533 - 4
B. Indoors: Apply raceway products as specified below unless otherwise indicated:
1. Exposed, Not Subject to Physical Damage: EMT.
2. Exposed, Not Subject to Severe Physical Damage: EMT.
3. Exposed and Subject to Severe Physical Damage: GRC. Raceway locations include the following:
a. Mechanical rooms.
4. Concealed in Ceilings and Interior Walls and Partitions: EMT.
5. Connection to Vibrating Equipment (Including Transformers and Hydraulic, Pneumatic, Electric Solenoid, or Motor-Driven Equipment): FMC, except use LFMC in damp or wet locations.
6. Damp or Wet Locations: GRC.
7. Boxes and Enclosures: NEMA 250, Type 1, except use NEMA 250, Type 4 stainless steel in damp or wet locations.
C. Minimum Raceway Size: 3/4-inch (21-mm) trade size.
D. Raceway Fittings: Compatible with raceways and suitable for use and location.
1. Rigid Steel Conduit: Use threaded rigid steel conduit fittings unless otherwise indicated.
Comply with NEMA FB 2.10.
2. EMT: Use compression, steel fittings. Comply with NEMA FB 2.10.
3. Flexible Conduit: Use only fittings listed for use with flexible conduit. Comply with
NEMA FB 2.20.
3.2 INSTALLATION
A. Comply with requirements in other section for "Hangers and Supports for Electrical Systems" for hangers and supports.
B. Comply with NECA 1 and NECA 101 for installation requirements except where requirements on Drawings or in this article are stricter. Comply with NECA 102 for aluminum conduits.
Comply with NFPA 70 limitations for types of raceways allowed in specific occupancies and number of floors.
C. Do not install raceways or electrical items on any "explosion-relief" walls or rotating equipment.
D. Do not fasten conduits onto the bottom side of a metal deck roof.
E. Keep raceways at least 6 inches (150 mm) away from parallel runs of flues and steam or hot-water pipes. Install horizontal raceway runs above water and steam piping.
F. Complete raceway installation before starting conductor installation.
G. Install no more than the equivalent of three 90-degree bends in any conduit run except for control wiring conduits, for which fewer bends are allowed. Support within 12 inches (300 mm) of changes in direction.
RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS 260533 - 5
H. Make bends in raceway using large-radius preformed ells. Field bending shall be according to
NFPA 70 minimum radii requirements. Use only equipment specifically designed for material and size involved.
I. Conceal conduit within finished walls, ceilings, and floors unless otherwise indicated. Install conduits parallel or perpendicular to building lines.
J. Support conduit within 12 inches (300 mm) of enclosures to which attached.
K. Threaded Conduit Joints, Exposed to Wet, Damp, Corrosive, or Outdoor Conditions: Apply listed compound to…