Attachment 10 Electrical Utilities Drawings.pdf

PDF 6 MB Posted

Attached to
Upgrade/Expand Utilities and Wet Lab Construction Federal contract opportunity
Solicitation number
12805B22R0015
Issued by
Department of Agriculture Agricultural Research Service Field Research Implementation and Information Delivery Plains Area

About this file

This document package includes electrical construction drawings and specifications for the Upgrade/Expand Utilities and Wet Lab Construction solicitation. Key details include:

  • The project involves upgrading electrical utilities including a new utility transformer, switchboard, distribution panel, generators, and related infrastructure for a wet lab and other buildings. Drawings depict the existing site plan and electrical riser diagram, proposed site plan and riser diagram, and provide notes, schedules, and construction details.

  • The solicitation number is 12805B22R0015 issued by the US Department of Agriculture Agricultural Research Service for work located at their Field Research Implementation and Information Delivery Plains Area facility. A mandatory site visit is scheduled for June 29, 2022 at 10:00am CST at building 17 on the provided map location. Contractors must register for the site visit by emailing two named individuals by June 26.

  • Drawings include general notes outlining applicable codes, coordination requirements, inspection procedures and other construction standards. Schedules list panelboards and equipment. Details show grounding, ductbanks and specific construction requirements.

View the file

Other files for this federal contract opportunity

Show all 22

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

(NOTE : ALL ABBREVIATIONS MAY NOT APPEAR ON THE DRAWINGS)

PANEL-XX

A AMPERE

ADA AMERICANS WITH DISABILITIES ACT

AFF ABOVE FINISHED FLOOR

AL ALUMINUM

AWG AMERICAN WIRE GAUGE

C CONDUIT

CB CIRCUIT BREAKER

CU COPPER

D EXISTING TO BE DEMOLISHED

DISC. SW. DISCONNECT SWITCH

DWG DRAWING

E, EX EXISTING TO REMAIN

EM DEVICE ON EMERGENCY CIRCUIT

EMT ELECTRICAL METALLIC TUBING

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FATC FIRE ALARM TERMINAL CABINET

FASP FIRE ALARM SMOKE PURGE PANEL

FLA FULL LOAD AMPS

G GROUND

GFI GROUND FAULT INTERRUPTER

GRS GALVANIZED RESISTIVE CONDUIT

HP HORSE POWER

IG ISOLATED GROUND

KVA KILOVOLT-AMPS

KW KILOWATT

MCB MAIN CIRCUIT BREAKER

MLO MAIN LUGS ONLY

MDP MAIN DISTRIBUTION PANEL

N NEW

NEC NATIONAL ELECTRICAL CODE

NFSS NON FUSED SAFETY SWITCH

NL NIGHT LIGHT FIXTURE

NTS NOT TO SCALE

P POLE

PH, ∅ PHASE

PNL PANEL

R RELOCATED AT NEW LOCATION

RR REMOVE AND RELOCATE

S/N SOLID NEUTRAL

SWBD SWITCHBOARD

T, XFMR TRANSFORMER

TYP. TYPICAL

UON UNLESS OTHERWISE NOTED

V VOLTS

W WATTS

WP WEATHERPROOF

TX

(NOTE : ALL ABBREVIATIONS MAY NOT APPEAR ON

THE DRAWINGS)

SUBSCRIPTS

RECEPTACLE OUTLETS AND JUNCTION BOX DEVICES MAY BE INDICATED

WITH THE FOLLOWING SUBSCRIPTS:

EM : RECEPTACLE ON EMERGENCY POWER

GFI : GROUND FAULT INTERRUPTER

WP : WEATHER PROOF OUTLET WITH PROTECTIVE IN-USE COVER

MD : MOTORIZED DAMPER

NON-FUSIBLE DISCONNECT SWITCH

FUSIBLE DISCONNECT SWITCH

COMBINATION STARTER DISCONNECT SWITCH

DRY TYPE TRANSFORMER

GENERATOR

AUTOMATIC TRANSFER SWITCH

DISTRIBUTION BOARD

120/208V ELECTRICAL PANEL

480/277V ELECTRICAL PANEL

CIRCUIT NUMBER DESIGNATION FEEDING ELECTRICAL

DEVICES, FIXTURES AND EQUIPMENT.

PANEL : INDICATES THE PANEL NAME

XX : INDICATES THE CIRCUIT NUMBER

KEYED DRAWING NOTE

CONDUIT UP

CONDUIT DOWN

CONTINUATION CIRCUIT

1. INSTALLATION OF ALL WORK SHALL BE IN ACCORDANCE WITH THE FOLLOWING REGULATIONS, CODES, ETC.

A. LOCAL CODES AND ORDINANCES

B. THE EDITION OF THE NATIONAL ELECTRICAL CODE (NEC 2020), NFPA 70, IN EFFECT.

C. ARS FACILITIES DESIGN STANDARDS (ARS 2012) ARS-242.1.

2. CONTRACTOR TO PROVIDE SUFFICIENT NOTICE TO THE OWNER'S REPRESENTATIVE PRIOR TO ANY WORK TO ALLOW

ADEQUATE TIME FOR COORDINATION OF EXISTING BUILDING ACTIVITIES WITH THE CONSTRUCTION WORK.

3. CONTRACTOR TO INCLUDE IN THEIR SCOPE ALL LABOR, MATERIALS, SERVICES, APPARATUS AND SHOP DRAWINGS IN

ADDITION TO THE CONTRACT DOCUMENTS AS REQUIRED TO COMPLY WITH ALL APPLICABLE GOVERNING LAWS, CODES

AND JURISDICTION REQUIREMENTS. PROVIDE ELECTRICAL EQUIPMENT WITH ALL ASSOCIATED ACCESSORIES, BRANCH

CIRCUIT WIRING AND CONDUIT INFRASTRUCTURE AS REQUIRED TO ENSURE A COMPLETE AND OPERATIONAL SYSTEM.

4. ALL MATERIALS AND WORK SHALL BE ACCORDING TO PROJECT SPECIFICATIONS.

5. IF MATERIAL OR EQUIPMENT IS INSTALLED BEFORE IT IS APPROVED, THE CONTRACTOR SHALL BE LIABLE FOR ITS

REMOVAL AND REPLACEMENT AT NO ADDITIONAL CHARGE IF IN THE OPINION OF THE ARCHITECT OR ENGINEER, THE

MATERIAL OR EQUIPMENT DOES NOT MEET THE INTENT OF THE DRAWINGS AND/OR SPECIFICATIONS.

6. REFER TO ARCHITECTURAL DRAWINGS AND LAB DRAWINGS(Q-SERIES) FOR THE EXACT LOCATION, ELEVATION, MOUNTING HEIGHTS AND DETAILS OF ALL LIGHT FIXTURES AND DEVICES. REPORT ANY DISCREPANCIES TO THE

ARCHITECT IMMEDIATELY.

7. ALL NEW SLAB PENETRATIONS MUST BE X-RAYED OR RADAR PRIOR TO CORE DRILLING. OBTAIN APPROVAL FROM

OWNER'S REPRESENTATIVE PRIOR TO ANY CORE DRILLING.

8. ELECTRICAL SYSTEMS SHALL BE GROUNDED PER ARTICLE 250 OF THE NATIONAL ELECTRICAL CODE.

9. PROVIDE AN INSULATED EQUIPMENT GROUNDING CONDUCTOR IN ALL BRANCH CIRCUITS AND FEEDERS INSTALLED IN

RACEWAYS. THE DEDICATED EQUIPMENT GROUNDING CONDUCTOR SHALL BE SIZED PER NEC SECTION 250.122. SOLE

USE OF METAL RACEWAY AS A GROUNDING CONDUCTOR SHALL NOT BE ACCEPTABLE. WIRING METHODS SHALL BE IN

ACCORDANCE WITH NEC SECTION 518.4 FOR ALL ASSEMBLY AREAS.

10. PROVIDE RED COLOR LOCKABLE TYPE BREAKERS FOR CIRCUITS SERVING LIFE SAFETY PANEL BOARDS.

11. NUMBER OF WIRES MAY NOT BE INDICATED FOR ALL CIRCUITS, ONLY THOSE WHERE CLARIFICATION IS NECESSARY.

PROVIDE THE NUMBER AND SIZE AS NECESSARY FOR THE PROPER FUNCTION OF THE SYSTEM WHETHER SPECIFICALLY

INDICATED ON PLAN OR NOT.

12. ALL BACK BOXES INSTALLED IN PARTITION WALLS SHALL BE STAGGERED. BACK-TO-BACK INSTALLATION IS NOT

PERMITTED.

13. PROVIDE ACCESS PANELS FOR ALL INACCESSIBLE JUNCTION BOXES AS REQUIRED BY THE N.E.C.

14. PROVIDE PLASTER RING WITH PULL STRING TO SPACE ABOVE SUSPENDED CEILING FOR ALL TELEPHONE, DATA, FAX, MODEM, CATV, CARD READER, ETC. OUTLETS INSTALLED IN HOLLOW PARTITIONS. PROVIDE 3/4" EMPTY CONDUIT AND

PULL STRING TO SPACE ABOVE SUSPENDED CEILING FOR THESE OUTLETS INSTALLED IN AN INSULATED PARTITION.

PROVIDE 1" EMPTY CONDUIT WITH PULL STRINGS FOR DATA/TEL OUTLETS. .

15. ELECTRICAL CONTRACTOR TO COORDINATE WITH MECHANICAL, PLUMBING AND OTHER TRADES TO PROVIDE ALL

EQUIPMENT ASSOCIATED WITH THEIR RESPECTIVE TRADES WITH NECESSARY WIRING AND CONDUIT INFRASTRUCTURE

FOR ALL SENSORS, AND CONTROL SYSTEMS AS REQUIRED.

16. CONTRACTOR TO PROVIDE DEDICATED CIRCUIT FOR CONNECTION TO EACH MECHANICAL EQUIPMENT CONTROL

PANEL AS REQUIRED. COORDINATE EXACT LOCATION AND CONNECTION REQUIREMENTS WITH MECHANICAL AND

CONTROLS CONTRACTORS.

17. CONTRACTOR TO COORDINATE ELECTRICAL WORK TO AVOID INTERFERENCE BETWEEN ALL TRADES.

A. DETERMINE INTERFERENCE BEFORE WORK IS FABRICATED OR INSTALLED. THE CONTRACTOR SHALL BE

THOROUGHLY FAMILIAR WITH ALL DETAILS OF WORK AND WORKING CONDITIONS AND COORDINATE

WORK DURING PRELIMINARY STAGES TO ENSURE ACTUAL ERECTION WILL PROCEED WITHOUT INTERFERENCE.

COORDINATION IS OF PARAMOUNT IMPORTANCE AND REQUESTS FOR ADDITIONAL PAYMENT

WILL BE CONSIDERED WHERE REQUEST IS BASED ON INTERFERENCE.

B. WHERE JOB CONDITIONS REQUIRE REASONABLE DEVIATIONS FROM CONTRACT DOCUMENTS, MAKE

DEVIATIONS WITHOUT ADDITIONAL COST TO OWNER, AFTER OBTAINING APPROVAL OF ARCHITECT.

C. PROVIDE MAXIMUM PRACTICAL SPACE FOR OPERATION, REPAIR, REMOVAL, AND TESTING OF ELECTRICAL

EQUIPMENT. DEVIATIONS MAY BE MADE TO PROVIDE REQUIRED ACCESSIBILITY PROVIDED THEY ARE APPROVED

BY THE OWNERS OR THE ARCHITECTS.

D. KEEP CONDUITS, WIRE WAYS AND SIMILAR ITEMS AS CLOSE AS POSSIBLE TO CEILING, WALLS AND COLUMNS IN

ORDER TO TAKE UP MINIMUM AMOUNT OF SPACE. ALL WORK TO BE IN STALLED IN A NEAT AND

WORK MAN LIKE MANNER.

E. PROVIDE OFFSETS, FITTINGS AND SIMILAR ITEMS NECESSARY TO ACCOMPLISH REQUIREMENTS OF

COORDINATION WITHOUT ADDITIONAL EXPENSE TO OWNER.

F. PROVIDE ACCESS TO AND CLEARANCES AROUND ELECTRICAL EQUIPMENT AS REQUIRED BY THE N.E.C.

18. ELECTRICAL CONTRACTOR SHALL FOLLOW THE STANDARD OPERATING PROCEDURE FOR CLEANING AND

DISINFESTATION OF MACHINERY IMPACTED BY THE SOIL REFER TO THE USDA STANDARD OPERATING PROCEDURE, CLEANING AND DISINFESTING EQUIPMENT AT THE CATTLE FEVER TICK RESEARCH LABORATORY IN MISSION, TEXAS.

USDA EMPLOYEES AT THE EDINBURG LOCATION WILL PROVIDE CLEANING AND DISINFECTION OF MACHINERY. CONTRACTOR

TO PROVIDE 24 HOURS NOTICE OF CLEANING EQUIPMENT. FOR MORE INFORMATION. COORDINATE WITH

CONTRACTING OFFICER AS NEEDED.

VIF VERIFY IN FIELD

(STANDARD SYMBOLS ONLY, ALL SYMBOLS MAY NOT BE APPLICABLE TO THIS PROJECT)

G

ATS

DP

1465 NORTHSIDE DRIVE SUITE 220B

ATLANTA, GA 30318

P:706-248-7165 www. .com

TM

PROJECT NUMBER: SIGQ212911.15

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT MANAGER

PPM

EPM

SETTY

DATE

A

D

USDA S

U

DWG. NO

DRAWN BY

SOLICITATION NO. SHEET NAME

ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED

Revisions

Agricultural Research Service

6/6/2022 3:27:05 PM C:\Users\Nicholas.Carlis\Documents\80-SIGQ212911.15_REVIT ELECTRICAL UTILITIES_nicholas.carlisYDXF8.rvt

WET LAB UTILITY

UPGRADE

E001

GENERAL NOTES,

SYMBOLS, &

ABBREVIATIONS

CDC

NC 05/23/2022

JM BD

DC

LB

EO

NO. DATE BY DESCRIPTION

1 06/06/2022 JM ISSUE FOR BIDDING AND CONSTRUCTION

GENERAL NOTES ELECTRICAL SYMBOL LIST ABBREVIATIONS

DRAWING LIST

SHEET DRAWING TITLE

01 E001 GENERAL NOTES, SYMBOLS, & ABBREVIATIONS

02 EDS01 ELECTRICAL DEMOLITION SITE PLAN

03 ES01 ELECTRICAL SITE PLAN

04 E501 ELECTRICAL UTILITY POWER RISER

05 E601 ELECTRICAL SCHEDULES

06 E701 ELECTRICAL DETAILS

07 E702 ELECTRICAL DETAILS

08 E703 ELECTRICAL DETAILS

E

E

E

E

E

E

E

WWWW

W

1 STORY

WOOD

PREFAB

WOOD

PORCH

RAMP

STR

BARBED WIREFENCE

A/C

224.76 Air Conditioning Unit

STEEL ROOFOVERHANG

STEEL ROOFOVERHANG

1 STORYWOOD

PREFAB

C O N C

W A L

K CONC

WALK

V L T

V L T

CONC

PAD

STEEL ROOFOVERHANG

STEEL 1

STORYBUILDING

ABOVEGROUND6" PVC

ABOVEGROUND6" PVC

ABOVEGROUND6" PVC

BARBED WIREFENCE

B A R B E D

W

IR

E

F E N C E

CANOPY

G A M E

F E N C E

DEER

FEEDER

GAME

FENCE

G A M E

F E N C E

GAME

GATE

SHEET KEY NOTES#

TX

ATSG

D

1. EXISTING UTILITY TRANSFORMER SHALL BE DEMOLISHED. ALL

EXISTING CONDUIT AND FEEDERS SHALL BE DEMOLISHED BACK TO

SOURCE. COORDINATE DISCONNECTION SCHEDULE WITH UTILITY

PROVIDER AND CONTRACTING OFFICER PRIOR TO DEMOLITION.

1465 NORTHSIDE DRIVE SUITE 220B

ATLANTA, GA 30318

P:706-248-7165 www. .com

TM

PROJECT NUMBER: SIGQ212911.15

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT MANAGER

PPM

EPM

SETTY

DATE

A

D

USDA S

U

DWG. NO

DRAWN BY

SOLICITATION NO. SHEET NAME

ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED

Revisions

Agricultural Research Service

6/6/2022 3:27:19 PM C:\Users\Nicholas.Carlis\Documents\80-SIGQ212911.15_REVIT ELECTRICAL UTILITIES_nicholas.carlisYDXF8.rvt

WET LAB UTILITY

UPGRADE

EDS01

ELECTRICAL DEMOLITION

SITE PLAN

CDC

NC 05/23/2022

JM BD

DC

LB

EO

SCALE: 1 : 280

ELECTRICAL DEMOLITION SITE PLAN

NO. DATE BY DESCRIPTION

1 06/06/2022 JM ISSUE FOR BIDDING AND CONSTRUCTION

E

E

E

E

E

E

WWWW

W

TX

1 STORY

WOOD

PREFAB

WOOD

PORCH

RAMP

STR

BARBED WIREFENCE

A/C

224.76 Air Conditioning Unit

STEEL ROOFOVERHANG

STEEL ROOFOVERHANG

1 STORYWOOD

PREFAB

C O N C

W A L

K CONC

WALK

V L T

V L T

CONC

PAD

STEEL ROOFOVERHANG

STEEL 1STORYBUILDING

ABOVEGROUND6" PVC

ABOVEGROUND6" PVC

ABOVEGROUND6" PVC

BARBED WIREFENCE

B A R B E D

W

IR

E

F E N C E

CANOPY

G A M E

F E N C E

DEER

FEEDER

GAME

FENCE

G A M E

F E N C E

GAME

GATE

PROPOSED WET LABFFE-226.50

PROPOSED DEERWORKING FACILITYFFE-226.00

SHEET KEY NOTES#

UTILITY XFMR

2-1/2"C

4"C

75KVA

TX

2"C

SPARE 4"C (COORDINATE QUANTITY WITH

CONTRACTING OFFICER)

24" GROUND DISTURBANCE

18" GROUND DISTURBANCE

1.57% VOLTAGE DROP

GENERAL NOTES

1. REFER TO DRAWING E001 FOR ELECTRICAL GENERAL NOTES, LEGEND AND

ABBREVIATIONS. REFER TO DRAWING E501 FOR POWER RISER DIAGRAM.

2. SEE ARCHITECTURAL AND CIVIL DRAWINGS FOR EXACT LOCATION,

MOUNTING HEIGHTS, AND ADDITIONAL INFORMATION, PRIOR TO ROUGH-IN

WORK.

3. COORDINATE WITH CIVIL AND EQUIPMENT SUPPLIER FOR FOUNDATION

DETAIL, EXACT LOCATION AND REQUIREMENTS.

4. FIELD COORDINATE THE EXACT LOCATION OF UNDERGROUND CONDUITS

WITH ALL OTHER UNDERGROUND UTILITIES AND THE SITE CONDITIONS.

5. SEE DETAIL ON DRAWING E701 FOR SERVICE GROUNDING SYSTEM

INFORMATION.

6. INSTALLATION SHALL CONFORM TO N.E.C. ARTICLE 300-5.

7. ALL POWER COMPANY/INCOMING ELECTRIC SERVICE RELATED WORK MUST

BE PERFORMED IN ACORDANCE TO TEXAS RULES AND REGULATIONS AND

PER THEIR REQUIREMENTS. NO CONDUITS AND/OR EQUIPMENT PADS

SHALL BE INSTALLED, PRIOR TO THEIR WRITTEN APPROVAL.

8. ALL INCOMING ELECTRIC SERVICE CONDUITS AND EQUIPMENT SHALL BE

LOCATED AS PER TEXAS WRITTEN INSTRUCTIONS OR USING THEIR

APPROVED DRAWINGS AND IN PRE-APPROVED EASEMENT AREA ONLY.

9. FIELD COORDINATE ALL UNDERGROUND CONDUITS AND DUCT BANK

LOCATION/ROUTING WITH THE SITE CONDITIONS AS WELL AS STRUCTURAL

FOOTINGS, AND ONLY AFTER APPROVAL BY TEXAS AND THE STRUCTURAL

AND CIVIL ENGINEERS.

1. NEW UTLITY TRANSFORMER PROVIDED BY UTILITY PROVIDER.

COORDINATE CONDUIT AND CONDUCTOR SIZE TO TRANFORMER

WITH UTILITY. ALL CONDUIT SHALL BE RUN UNDERGROUND AND

ENCASED IN CONCRETE TO NEW TRANSFORMER. PROVIDE ALL

APPURTENANCES NEEDED FOR COMPLETE INSTALLATION.

2. REFER TO SHEET E702 FOR SWITCHBOARD DATA INFORMATION,

DIMENSIONS, AND MOUNTING DETAILS.

3. NEW 500KW GENERATOR SHALL BE PROVIDED WITH 48 HOURS FUEL

SUPPLY PER USDA DESIGN GUIDLINES AND SOUNDPROOF WEATHER

ENCLOSURE.

1465 NORTHSIDE DRIVE SUITE 220B

ATLANTA, GA 30318

P:706-248-7165 www. .com

TM

PROJECT NUMBER: SIGQ212911.15

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT MANAGER

PPM

EPM

SETTY

DATE

A

D

USDA S

U

DWG. NO

DRAWN BY

SOLICITATION NO. SHEET NAME

ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED

Revisions

Agricultural Research Service

6/6/2022 12:16:25 PM C:\Users\Nicholas.Carlis\Documents\80-SIGQ212911.15_REVIT ELECTRICAL UTILITIES_nicholas.carlisYDXF8.rvt

WET LAB UTILITY

UPGRADE

ES01ELECTRICAL SITE PLAN

CDC

NC 05/23/2022

JM BD

DC

LB

EO

SCALE: 1 : 280

ELECTRICAL SITE PLAN

NO. DATE BY DESCRIPTION

1 06/06/2022 JM ISSUE FOR BIDDING AND CONSTRUCTION

GG DP

UTILITY

XFMR

ATS(E) 225KVA XFMR

MSB

500KW GEN

G

G(E)

TX

SHEET KEY NOTES#

1. NEW UTLITY TRANSFORMER PROVIDED BY UTILITY PROVIDER.

COORDINATE CONDUIT AND CONDUCTOR SIZE TO TRANFORMER

WITH UTILITY. ALL CONDUIT SHALL BE RUN UNDERGROUND AND

ENCASED IN CONCRETE TO NEW TRANSFORMER. PROVIDE ALL

APPURTENANCES NEEDED FOR COMPLETE INSTALLATION.

2. REFER TO SHEET E702 FOR SWITCHBOARD DATA INFORMATION,

DIMENSIONS, AND MOUNTING DETAILS.

3. NEW 500KW GENERATOR SHALL BE PROVIDED WITH 48 HOURS FUEL

SUPPLY PER USDA DESIGN GUIDLINES AND SOUNDPROOF WEATHER

ENCLOSURE.

4. NEW 75KVA PAD MOUNTED DRY-TYPE TRANSFORMER. PROVIDE A

250A FUSIBLE DISCONNECT SWITCH WITHIN 10' OF THE SECONDARY

SIDE OF THE TRANSFORMER. PROVIDE NEMA 4X STAINLESS STEEL

ENCLOSURE FOR THE TRANSFORMER AND DISCONNECT SWITCH.

COORDINATE AND CONFIRM FINAL LOCATION WITH CIVIL DRAWINGS.

SEE E501 FOR RISER DIAGRAM AND MORE INFORMATION.

5. NEW 225KVA PAD MOUNTED DRY-TYPE TRANSFORMER. PROVIDE A

800A FUSIBLE DISCONNECT SWITCH WITHIN 10' OF THE SECONDARY

SIDE OF THE TRANSFORMER IF INSTALLED MORE THAN 10' AWAY

FROM EXISTING ATS. PROVIDE NEMA 4X STAINLESS STEEL

ENCLOSURE FOR THE TRANSFORMER AND DISCONNECT SWITCH.

COORDINATE AND CONFIRM FINAL LOCATION WITH CIVIL DRAWINGS

AND IN FIELD. SEE E501 FOR RISER DIAGRAM AND MORE

INFORMATION.

6. NEW 1200A 480/277V PAD-MOUNTED SERVICE ENTRANCE RATED

SWITCHBOARD MSB. PROVIDE NEMA 4X STAINLESS STEEL

ENCLOSURE FOR THE SWITCHBOARD AND ALL ASSOCIATED

APPURTENANCES. COORDINATE AND CONFIRM FINAL LOCATION WITH

CIVIL DRAWINGS AND IN FIELD. SEE E501 FOR RISER DIAGRAM AND

MORE INFORMATION.

7. NEW 800A 208/120V PAD-MOUNTED SERVICE ENTRANCE RATED

DISTRIBUTION PANELBOARD DP. PROVIDE NEMA 4X STAINLESS STEEL

ENCLOSURE FOR THE DISTRIBUTION BOARD AND ALL ASSOCIATED

APPURTENANCES. COORDINATE AND CONFIRM FINAL LOCATION WITH

CIVIL DRAWINGS AND IN FIELD. SEE E501 FOR RISER DIAGRAM AND

MORE INFORMATION.

8. NEW UTLITY TRANSFORMER PROVIDED BY UTILITY

PROVIDER. COORDINATE CONDUIT AND CONDUCTOR SIZE TO

TRANFORMER WITH UTILITY. PROVIDE ALL APPURTANCES NEEDED

FOR COMPLETE INSTALLATION.

18" GROUND DISTURBANCE

3 #500 KCMIL + 1 #2 AWG

G IN 3" C) (N)

FROM

UTILITY

3 SETS (4 #500KCMIL+ 1#2/0G IN 4"C)

CONCRETE ENCASED (N)

3 SETS (4 #300 KCMIL + 1

#2/0 AWG G IN 3-1/2" C (N)

FUTURE

PANEL

WETLAB

"PW"

400A

480/277V

3PH, 4W

MCB (N)

2 SETS (4 #3/0 AWG + 1 #

2 AWG G IN 2-1/2" C) (N)

FUTURE

PANEL BARN

"PB"

100A

208/120V

3PH, 4W

MCB

(N)

4 #1 AWG + 1 # 8 AWG G IN 2" C (N)

4 SETS (4 #350KCMIL IN 3-1/2"C)

CONCRETE ENCASED (N)

3 #1 AWG + 1 #6 AWG G IN 1 1/4" C (N)

4 #250 KCMIL + 1 #2 AWG

G IN 1 2 1/2" C (N)

3 SETS (4 #300 KCMIL + 1 #2/0 AWG G IN 3-1/2" C (N)

TRANSFORMER DISCONNECT

125AF/200AS 480V 3P (N)

3 #1 AWG + 1 #6 AWG G IN 1 1/2" C (N)

3 #1 AWG + 1 #6 AWG G

IN 1 1/4" C (N)

FUTURE BARN

2"C (N)

WILDLIFE BARN WETLAB WETLAB

3 SETS (4 #300 KCMIL + 1

#2/0 AWG G IN 3-1/2" C (N)

2/0 G (N)

4 #4 AWG + 1 #8 AWG G IN 1-1/2" C

EXISTING

UTILITY

POLEXFMR 208V

(E)

200KW

GENSET

EG-1(E)

208V 3P

(ATS)

800A 694A

(N)

(E)

225KVA

DRY-TYPE

XFMR (N)

(E)

200KW

GENSET

EG-1(E)

208V 3P

PANEL

"BLDG 1"

225A

208/120V

3PH, 4W

(E)

(D)

(ATS)

800A

694A

(E)

(E)(SERVICE DISCONNECT)

800A

208 3P

(D)

PANEL

"BLDG 5"

100A

208/120V

3PH, 4W

(E)

PANEL

"BLDG 6"

100A

208/120V

3PH, 4W

(E)

50A

LIFT STATION

208/120V

3PH, 3W

(E)

PANEL

"BLDG 2"

100A

208/120V

3PH, 4W

(E)

PANEL

"BLDG 3"

200A

208/120V

3PH, 4W

(E)

PANEL

"BLDG 4"

100A

208/120V

3PH, 4W

(E)

PANEL

"EXISTING"

250A

208/120V

3PH, 4W

(E)

PANEL

"BLDG 7"

200A

208/120V

3PH, 4W

(E)

ENCLOSED

CB

"BLDG 10"

40A

240V 1P

(E)

(E)

(E)

(E)

(E)(E)

500KW

GENSET

EG-2

480V 3P

1000A

800A

208Y/120V

DISTRIBUTION

BOARD

DP

(N)

(N)

PANEL

"BLDG 1"

225A

208/120V

3PH, 4W

(E)

PANEL

"BLDG 5"

100A

208/120V

3PH, 4W

(E)

PANEL

"BLDG 6"

100A

208/120V

3PH, 4W

(E)

50A

LIFT STATION

208/120V

3PH, 3W

(E)

PANEL

"BLDG 2"

100A

208/120V

3PH, 4W

(E)

PANEL

"BLDG 3"

200A

208/120V

3PH, 4W

(E)

PANEL

"BLDG 4"

100A

208/120V

3PH, 4W

(E)

PANEL

"EXISTING"

250A

208/120V

3PH, 4W

(E)

PANEL

"BLDG 7"

100A

208/120V

3PH, 4W

(E)

ENCLOSED

CB

"BLDG 10"

40A

240V 1P

(E)

(E)

PANEL

"BLDG 7"

100A

208/120V

3PH, 4W

(E)

(E) (E) (E) (E) (E)

(E)

(E) (E) (E) (E)

UTILITY

XFMR (N)

(N)

DISTRIBUTION

SECTION

(N)

C/T CABINET

ATS

(N)(N)(N)

FUTURE

75KVA

"T-RW"

XFMR (N)

FUTURE

PANEL

"RW"

225A

208/120V

3PH, 4W

MCB

(N)

75KVA

"T-RW"

XFMR (N)

(N)

350A

1000A

480/277V

3PH

M

MSB

60A

LOAD

CENTER

GENERAL NOTES

SHEET KEY NOTES#

1. UNLESS OTHERWISE NOTED, ALL ELECTRICAL EQUIPMENT, PANELS

AND FEEDERS ARE EXISTING TO REMAIN AND SHOWN FOR REFERENCE

ONLY.

2. CONTRACTOR TO PERFORM SHORT CIRCUIT AND COORDINATION

STUDY ALONG WITH AN ARC FLASH HAZARD ANALYSIS. COORDINATE

WITH EQUIPMENT MANUFACTURER TO SET THE TIME CURRENT

CURVES ON THE MAIN OVERCURRENT PROTECTIVE DEVICES AND

ASSOCIATED BRANCH CIRCUIT BREAKERS TO ENSURE THEY ARE

SELECTIVELY COORDINATED WITH EACH OTHER. THE INTERRUPTING

RATING OF ALL ELECTRICAL EQUIPMENT SHALL BE BAASED ON THE

DATA OF THE SHORT CIRCUIT AND COORDINATION STUDY.

CONTRACTOR TO SUBMIT A SHORT-CIRCUIT AND SELECTIVE

COORDINATION STUDY ALONG WITH THE SWITCHGEAR,

SWITCHBOARD, AND PANELBOARD SUBMITTAL SHOP DRAWINGS. THE

WORK REQUIRED TO CORRECT SELECTIVE COORDINATION ISSUES

DISCOVERED AFTER THE SHOP DRAWINGS ARE APPROVED SHALL BE

PROVIDED BY HTE CONTRACTOR AT NO ADDITIONAL FEES.

3. PROVIDE INSULATED CASE POWER CIRCUIT BREAKER FOR MAIN

BREAKERS AND LARGER FRAME SIZE MOLDED CIRCUIT BREAKERS FOR

BRANCH CIRUITS

1. EXISTING UTILITY TRANSFORMER SHALL BE DEMOLISHED. ALL

EXISTING CONDUIT AND FEEDERS SHALL BE DEMOLISHED BACK TO

SOURCE. COORDINATE DISCONNECTION SCHEDULE WITH UTILITY

PROVIDER AND CONTRACTING OFFICER PRIOR TO DEMOLITION.

2. UTILITY PROVIDER SHALL PROVIDE NEW SERVICE FEEDERS, RUN

UNDERGROUND AND TERMINATE AT LOCATION OF NEW UTILITY

TRANSFORMER. NEW UTLITY TRANSFORMER PROVIDED BY UTILITY

PROVIDER. COORDINATE CONDUIT AND CONDUCTOR SIZE TO

TRANFORMER WITH UTILITY. PROVIDE ALL APPURTANCES NEEDED

FOR COMPLETE INSTALLATION.

3. ALL CONDUIT SHALL BE RUN UNDERGROUND AND ENCASED IN

CONCRETE TO NEW TRANSFORMER PROVIDED BY ELECTRICAL

CONTRACTOR. ELECTRICAL CONTRACTOR SHALL LEAVE EXTRA

LENGTH OF CONDUCTORS FOR UTILITY PROVIDER TO TERMINATE

INSIDE THE NEW TRANSFORMER. COORDINATE WITH UTILITY

PROVIDER AND USDA PRIOR TO COMMENCEMENT OF WORK.

COORDINATE ALL SERVICE SHUTDOWN WITH USDA AND UTILITY

PROVIDER.

4. SWITCHBOARD SHALL BE SERVICE ENTRANCE RATED. PROVIDE

HOUSEKEEPING PAD, 6" HIGH AND PAD SHALL EXTEND 6" OUTSIDE

FOOT PRINT OF SWITCHBOARD. PROVIDE SERVICE ENTRANCE SPD

PER UL 1449 5TH EDITION, GROUND FAULT PROTECTION PER NEC

230.95 AND ARC ENERGY REDUCTION PER NEC 240.87.

5. PROVIDE AND INSTALL DIGITAL METERING FOR THE DISTRUBUTION

PANELBOARD TO MONITOR ENERGY CONSUMPTION

6. ELECTRICAL CONTRACTOR SHALL INTERCEPT AND EXTEND EXISTING

FEEDER AND CONDUIT PRESERVED DURING DEMOLITION TO

COMPLETE CONNECTION TO NEW DISTRIBUTION PANEL DP.

7. COORDINATE SERVICE FEEDER SIZE WITH UTILITY PROVIDER

8. EXISTING ATS SHALL REMAIN AND BE PROTECTED DURING

CONSTRUCTION, DISCONNECT EXISTING FEEDERS CONNECTED TO

EXISTING ATS. DISCONNECTED FEEDERS AND CONDUITS SHALL

REMAIN INTACT, BE CAPPED AND PROTECTED DURING

CONSTRUCTION.

9. PROVIDE 2" EMPTY CONDUIT FOR FUTURE BARN INSTALLATION.

COORDINATE FINAL LOCAL OF CONDUIT STUB-UP IN FIELD WITH

USDA CONTRACTING OFFICER

10. NEW 800A 208/120V PAD-MOUNTED SERVICE ENTRANCE RATED

DISTRIBUTION PANELBOARD DP. PROVIDE HOUSEKEEPING PAD, 6"

HIGH AND PAD SHALL EXTEND 6" OUTSIDE FOOT PRINT OF

SWITCHBOARD. PROVIDE SERVICE ENTRANCE SPD

PER UL 1449 5TH EDITION, GROUND FAULT PROTECTION PER NEC

230.95 AND ARC ENERGY REDUCTION PER NEC 240.87.

LOCATED IN INTERIOR OF RESPECTIVE BUILDINGS

1465 NORTHSIDE DRIVE SUITE 220B

ATLANTA, GA 30318

P:706-248-7165 www. .com

TM

PROJECT NUMBER: SIGQ212911.15

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT MANAGER

PPM

EPM

SETTY

DATE

A

D

USDA S

U

DWG. NO

DRAWN BY

SOLICITATION NO. SHEET NAME

ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED

Revisions

Agricultural Research Service

6/6/2022 3:27:08 PM C:\Users\Nicholas.Carlis\Documents\80-SIGQ212911.15_REVIT ELECTRICAL UTILITIES_nicholas.carlisYDXF8.rvt

WET LAB UTILITY

UPGRADE

E501

ELECTRICAL UTILITY

POWER RISER

CDC

NC 05/23/2022

JM BD

BD

DC

LB

EO

NO. DATE BY DESCRIPTION

1 06/06/2022 JM ISSUE FOR BIDDING AND CONSTRUCTION

NO SCALEE501

2 EXISTING ELECTRICAL RISER DIAGRAM

NO SCALEE501

3 NEW ELECTRICAL RISER DIAGRAM

3 7

2/0 G (N)

2/0 G (N)

WETLAB WETLABWILDLIFE BARN

EXISTING

UTILITY POLE

XFMR 208V

200A

1465 NORTHSIDE DRIVE SUITE 220B

ATLANTA, GA 30318

P:706-248-7165 www. .com

TM

PROJECT NUMBER: SIGQ212911.15

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT MANAGER

PPM

EPM

SETTY

DATE

A

D

USDA S

U

DWG. NO

DRAWN BY

SOLICITATION NO. SHEET NAME

ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED

Revisions

Agricultural Research Service

6/6/2022 3:27:27 PM C:\Users\Nicholas.Carlis\Documents\80-SIGQ212911.15_REVIT ELECTRICAL UTILITIES_nicholas.carlisYDXF8.rvt

WET LAB UTILITY

UPGRADE

E601ELECTRICAL SCHEDULES

05/23/2022

NO. DATE BY DESCRIPTION

1 06/06/2022 JM ISSUE FOR BIDDING AND CONSTRUCTION

PANELBOARD SCHEDULE NOTES

1. TURN ALL SPARE CIRCUIT BREAKERS TO "OFF" POSITION AT COMPLETION

OF WORK.

2. AT COMPLETION OF THE PROJECT, PROVIDE TYPE WRITTEN SCHEDULES

FOR ALL PANEL BOARDS UTILIZED DURING THE CONSTRUCTION PROCESS

INDICATING AS-BUILT CONDITIONS.

3. ALL UNGROUNDED AND GROUNDED CONDUCTORS OF EACH MULTI-WIRE

BRANCH CIRCUIT ARE TO BE GROUPED TOGETHER AT BOTH ENDS BY

WIRE TIES OR SIMILAR MEANS.

4. NEW CIRCUIT BREAKER (IF PROVIDED) MUST BE COMPATIBLE WITH

EXISTING PANELBOARD (UL LISTED, MANUFACTURED BY THE

PANELBOARD MANUFACTURER AND SHALL HAVE AN AIC RATING TO

MATCH THE EXISTING PANEL RATING).

5. ALL SPARE CIRCUIT BREAKERS MADE AVAILABLE AFTER DEMOLITION ARE

BASED ON THE EXISTING DOCUMENTS AND MAY BE INACCURATE. THE

ACTUAL CIRCUIT NUMBERS MAY BE DIFFERENT AND SHALL BE VERIFIED IN

FIELD DURING CONSTRUCTION.

6. ELECTRICAL CONTRACTOR TO PERFORM THE CIRCUIT TRACING AND

UP DATE THE PANEL SCHEDULE TO REFLECT THE ACTUAL CIRCUIT

NUMBERS.

7. ALL NEW LOADS ON EXISTING PANEL ARE INDICATED IN BOLD LETTERS.

N4X N4X

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT MANAGER

PPM

EPM

SETTY USDA

DRAWN BY

CDC

NC

JM BD

BD

DC

LB

EO

BUILDING COLD WATER

GRADE

BUILDING WALL

SERVICE PIPE

NEUTRAL BUS

TYPICAL

AS PER NEC [250-52(A)(1)

SEE NOTE 2

GROUND BUS

SEE NOTE 4

COPPER CLAD

GROUND RODS

THE EARTH

DRIVEN INTO

3/4" x 10'-0"

[250.52(A)]

SERVICE EQUIPMENT

#4/0 AWG TO TELECOMUNICATIONS

GROUNDING BUSBAR IN EACH

TELECOM CLOSET.

(SEE TELECOM DRAWINGS FOR

TELECOM CLOSET LOCATIONS)

MAIN TELECOMMUNICATIONS

GROUNDING BUSBAR IN

MAIN TELECOM ROOM

TO LIGHTNING

PROTECTION

GROUND ROD

AS PER NEC

[250.52(A)(3)]

#4/0 AWG

#4/0 AWG

(TYP. OF ALL)

BOND TO METAL FRAME OF

BUILDING OR STRUCTURE

WHERE PRESENT AS PER

NEC [250-52(A)(2)]

4"X1/4"X2' LONG

COPPER GROUND BAR IN

MAIN ELECTRICAL ROOM

SERVICE EQUIPMENT

NOT A SEPERATLY DERIVED

SYSTEM

EQUIPMENT GROUNDING CONDUCTOR

OR SUPPLY SIDE BONDING JUMPER

EQUIPMENT GROUNDING CONDUCTOR

3 POLE TRANSFER

SWITCH

LOADN

EQUIPMENT GROUNDING

CONDUCTOR

N

FINISHED GRADE

PROVIDE UTILITY

MARKER TAPE BURIED

12" BELOW FINISHED

GRADE

4" PVC DUCT (TYP. OF 6)

7 1/2" 6"

N O

M

IN

A L 1

/2

/2

2' - 0"

PROVIDE SPACERS EVERY 48"

AND BACKFILL

FRONT VIEW

PLAN VIEW

CONCRETE ENCASED

PVC CONDUIT PRIMARY

NUMBER AND SIZE AS INDICATED

PVC CONDUIT SECONDARY

NUMBER AND SIZE AS INDICATED

RGS TO PVC COUPLING (TYP.)

3/4" X 10' GROUND ROD

(TYPICAL FOR 4) MINIMUM

FUSES

TAP CHANGER

15kV, 200A LOAD BREAK

ELBOW (TYP. FOR 3)

REINFORCING BARS

CABLE SHIELD ADAPTER (TYP.)

CABLE SHIELDS

(TYP. FOR 3)

3/4" X 10' COPPER CLAD

GROUND ROD (TYP. AT EACH

CORNER OF CONCRETE PAD)

H3A

H1A

H2A

H3B

H2B

SWITCH H1B

X0

X1

X2

X3

G4

G

G4

G

G

G

TRANSFORMER PAD

PAD DIMENSIONS AS REQUIRED

TO PROVIDE NOT LESS THAN

6" SPACING BETWEEN

TRANSFORMER & EDGE OF

PAD ON ALL SIDES

G4

G

G

G4

TRANSFORMER

SURGE ARRESTER (TYP. FOR 3)

8" THICK CONCRETE PAD

3/4" CHAMFER ALL TOP EDGES

GRADE

GROUND BUS OR PAD; ONE IN

HV & ONE IN LV COMPARTMENT

4/0 BARE COPPER GROUNDING

CONDUCTOR

WATTHOUR DEMAND METER

(CT'S & WIRING NOT SHOWN)

#4 GROUND LEAD (TYP. FOR 3)

FACTORY INSTALLED STRAP

FOUR HOLE TERMINAL AS

REQUIRED (TYP. FOR 4)

OPENINGS SIZED TO TRANSFORMER

PRIMARY & SECONDARY

COMPARTMENTS; FILL WITH GRAVEL

AROUND CONDUIT & CABLE ENTRIES

#4 REINFORCING BARS

NOT TO EXCEED 18"

SPACING BOTH WAYS

4/0 GROUND RING (TYPICAL)

EXOTHERMIC WELD (TYPICAL)

MASTIC WRAPPED RGS

PVC END BELL (TYP.)

SWITCH

EXOTHERMIC CONNECTION

(TYPICAL)

C C

24" TYP

T Y

P

M

IN

1465 NORTHSIDE DRIVE SUITE 220B

ATLANTA, GA 30318

P:706-248-7165 www. .com

TM

PROJECT NUMBER: SIGQ212911.15

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT MANAGER

PPM

EPM

SETTY

DATE

A

D

USDA S

U

DWG. NO

DRAWN BY

SOLICITATION NO. SHEET NAME

ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED

Revisions

Agricultural Research Service

6/6/2022 3:27:12 PM C:\Users\Nicholas.Carlis\Documents\80-SIGQ212911.15_REVIT ELECTRICAL UTILITIES_nicholas.carlisYDXF8.rvt

WET LAB UTILITY

UPGRADE

E701ELECTRICAL DETAILS

CDC

NC 05/23/2022

JM BD

DC

LB

EO

SCALE: N.T.S.2

6W DUCTBANK DETAIL

SCALE: N.T.S.1

PAD MOUNTED TRANSFORMER W/GROUNDING

NO. DATE BY DESCRIPTION

1 06/06/2022 JM ISSUE FOR BIDDING AND CONSTRUCTION

SCALE: N.T.S.3

BUILDING GROUNDING DETAIL

SCALE: N.T.S.4

ATS AND GENERATOR GROUNDING DETAIL

.75/[19] DIA

MTG HOLES OFFSET

3.00/[76] TYP

FROM SIDE

SWITCHBOARD GENERAL NOTES - SERIES 2

PRODUCT DESCRIPTION & RATINGS

POWER SYSTEM DATA

480Y/277V 3PH 4W 60Hz / 3 PHASE WYE

SOLIDLY GROUNDED

SYSTEM SHORT CIRCUIT CURRENT RATING: 65kA RMS

INCOMING SECTION CABLE THROUGH THE BOTTOM

BUS SYSTEM DATA

2500A SILVER PLATED COPPER MAIN BUS

(4) .25X2.00/[6X51] CU BUS BAR PER PHASE

(2) .25X5.00/[6X127] CU BUS BAR PER NEUTRAL

(1) .25X1.25/[6X31] CU GROUND BUS

ENCLOSURE DATA

TYPE 1 FREE STANDING

EXTERIOR PAINT COLOR: ANSI 49

FRONT ACCESSIBILITY ONLY REQUIRED

HANDLING: ROLLERS & LIFTING ASSEMBLIES

ESTIMATED SHIPPING WEIGHT

822.00 LBS/372.86 kgs

CODE STANDARDS

UL DEADFRONT AND SUITABLE FOR USE AS SERVICE ENTRANCE

WHEN NOT MORE THAN SIX (6) DISCONNECTING MEANS ARE PROVIDED

RATING NAMEPLATES

ST1 - SERVICE ENTRANCE - SECTION BUS 2500A

PRODUCT INFORMATION

WIRING

ALL WIRING TO BE MACHINE TOOL WIRE TYPE

INSTRUCTION BULLETINS

REFERENCE 80043-055 FOR HANDLING, INSTALLATION.

ANCHORING, INSPECTION AND MAINTENANCE INFORMATION

PRODUCT ACCESSORIES/OPTIONS

SEISMIC QUALIFIED

24V TRIP UNIT DISPLAY POWER

LOCALLY MOUNTED AMS SWITCH

TOP VIEW - FRONT

FRONT VIEW

LEFT SIDE VIEW

FLOOR PLAN - FRONT

REQUIREMENTS FOR SEISMIC RATING

ANCHORING CONDITIONS:

TO MAINTAIN SEISMIC QUALIFICATIONS, EQUIPMENT MUST BE INSTALLED PER MANUAL (SEE GENERAL NOTES)

AND PER ANY SEISMIC ANCHORING DETAILS PROVIDED BY OTHERS. DO NOT INSTALL EQUIPMENT

BEFORE APPROVED SEISMIC ANCHORING DETAILS HAVE BEEN OBTAINED AND SITE PREPARATIONS HAVE

BEEN MADE IN ACCORDANCE WITH THE APPROVED SEISMIC ANCHORING DETAILS. ALL POST-INSTALLED ANCHORS

SHALL BE APPROVED FOR SEISMIC LOADS.

CONSIDERATION MUST BE MADE FOR CONDUIT ENTRY INTO EACH SECTION WHEN DEVELOPING MOUNTING

PAD REINFORCEMENT LOCATIONS. SEE CONDUIT ENTRY DETAILS (FLOOR PLAN) FOR DIMENSIONAL INFORMATION.

EACH SECTION MUST BE ANCHORED AT ALL LOCATIONS (REFER TO FLOOR PLAN AND MOUNTING DETAIL ABOVE). ANCHOR

BOLT MOUNTING POINTS ARE .75/[19] DIAMETER HOLES LOCATED 1.50/[38] OR 3.00/[76] ABOVE THE BASE OF THE

SECTION. USE DIMENSIONS FROM THE FLOOR PLAN TO DETERMINE MOUNTING LOCATIONS.

THE BELLEVILLE WASHER (SHOWN IN DETAIL ABOVE) USED FOR ANCHORING CONNECTIONS IS A TESTED COMPONENT AND IS

REQUIRED TO MAINTAIN POSITION RETENTION OF THE EQUIPMENT. THE SLIP CRITICAL CONNECTION PERFORMANCE OF THE

BOLTED CONNECTION WAS ESTABLISHED TO THE SHAKE TABLE TESTED SEISMIC CAPACITY OF THE EQUIPMENT AS SHOWN

ON THE EQUIPMENT SEISMIC CERTIFICATE SUPPLIED AT THE TIME OF ORDER.

CENTER OF GRAVITY CALCULATIONS:

ELEVATION CENTER OF GRAVITY: 55.00/[1387] UP FROM FLOOR

VERTICAL CENTER OF GRAVITY: USE CENTERLINE OF SECTION FROM LEFT TO RIGHT

DEPTH CENTER OF GRAVITY: USE CENTERLINE OF SECTION FROM FRONT TO REAR

MOUNTING DETAILS

BELLEVILLE WASHER

BASE CHANNEL

FLOOR

NUT

ANCHOR BOLT

(SAE GRADE 5)

SAE GRADE 5

BOLT

1/2-13 HEAVY

DUTY NUT

1-14 DIA

BELLEVILLE

WASHER

TYPICAL BASE

CHANNEL MOUNTING

HARDWARE

PM

28.5

10.5

AMS91.50

[2324]

1.50 [38]

31.00 [787]2.50

[64]

15.60 [396]

5.40 [137]

2.80 [71]

3.10 [79]

36.00 [914]

1.50 [38]

21.00 [533]24.00

[610]

91.50 [2324]

90.00 [2286]

24.00 [610]

2.94 [75]

1.47 [37]

X=HEIGHT

36.00 [914]

1465 NORTHSIDE DRIVE SUITE 220B

ATLANTA, GA 30318

P:706-248-7165 www. .com

TM

PROJECT NUMBER: SIGQ212911.15

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT MANAGER

PPM

EPM

SETTY

DATE

A

D

USDA S

U

DWG. NO

DRAWN BY

SOLICITATION NO. SHEET NAME

ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED

Revisions

Agricultural Research Service

6/6/2022 3:27:16 PM C:\Users\Nicholas.Carlis\Documents\80-SIGQ212911.15_REVIT ELECTRICAL UTILITIES_nicholas.carlisYDXF8.rvt

WET LAB UTILITY

UPGRADE

E702ELECTRICAL DETAILS

CDC

NC 05/23/2022

JM BD

DC

LB

EO

NO. DATE BY DESCRIPTION

1 06/06/2022 JM ISSUE FOR BIDDING AND CONSTRUCTION

SCALE: N.T.S.1

SWITCHBOARD DETAIL

1465 NORTHSIDE DRIVE SUITE 220B

ATLANTA, GA 30318

P:706-248-7165 www. .com

TM

PROJECT NUMBER: SIGQ212911.15

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT MANAGER

PPM

EPM

SETTY

DATE

A

D

USDA S

U

DWG. NO

DRAWN BY

SOLICITATION NO. SHEET NAME

ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED

Revisions

Agricultural Research Service

6/6/2022 3:27:24 PM C:\Users\Nicholas.Carlis\Documents\80-SIGQ212911.15_REVIT ELECTRICAL UTILITIES_nicholas.carlisYDXF8.rvt

WET LAB UTILITY

UPGRADE

E703ELECTRICAL DETAILS

05/23/2022

NO. DATE BY DESCRIPTION

1 06/06/2022 JM ISSUE FOR BIDDING AND CONSTRUCTION

SCALE: N.T.S.1

SWITCHBOARD DETAILGENERATOR DETAIL

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT MANAGER

PPM

EPM

SETTY USDA

DRAWN BY

CDC

NC

JM BD

BD

DC

LB

EO

80-SIGQ212911.15_REVIT ELECTRICAL UTILITIES_nicholas.carlisYDXF8
E001 - GENERAL NOTES, SYMBOLS, & ABBREVIATIONS
EDS01 - ELECTRICAL DEMOLITION SITE PLAN
E501 - ELECTRICAL UTILITY POWER RISER
E601 - ELECTRICAL SCHEDULES
E701 - ELECTRICAL DETAILS
E702 - ELECTRICAL DETAILS
ES01 - ELECTRICAL SITE PLAN
E703 - ELECTRICAL DETAILS

E601 - ELECTRICAL SCHEDULES

File details come from the government source that posted it. Updated .