Attachment 10 Electrical Utilities Drawings.pdf
PDF 6 MB Posted
- Attached to
- Upgrade/Expand Utilities and Wet Lab Construction Federal contract opportunity
- Solicitation number
- 12805B22R0015
About this file
This document package includes electrical construction drawings and specifications for the Upgrade/Expand Utilities and Wet Lab Construction solicitation. Key details include:
-
The project involves upgrading electrical utilities including a new utility transformer, switchboard, distribution panel, generators, and related infrastructure for a wet lab and other buildings. Drawings depict the existing site plan and electrical riser diagram, proposed site plan and riser diagram, and provide notes, schedules, and construction details.
-
The solicitation number is 12805B22R0015 issued by the US Department of Agriculture Agricultural Research Service for work located at their Field Research Implementation and Information Delivery Plains Area facility. A mandatory site visit is scheduled for June 29, 2022 at 10:00am CST at building 17 on the provided map location. Contractors must register for the site visit by emailing two named individuals by June 26.
-
Drawings include general notes outlining applicable codes, coordination requirements, inspection procedures and other construction standards. Schedules list panelboards and equipment. Details show grounding, ductbanks and specific construction requirements.
View the file
Other files for this federal contract opportunity
Show all 22
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
(NOTE : ALL ABBREVIATIONS MAY NOT APPEAR ON THE DRAWINGS)
PANEL-XX
A AMPERE
ADA AMERICANS WITH DISABILITIES ACT
AFF ABOVE FINISHED FLOOR
AL ALUMINUM
AWG AMERICAN WIRE GAUGE
C CONDUIT
CB CIRCUIT BREAKER
CU COPPER
D EXISTING TO BE DEMOLISHED
DISC. SW. DISCONNECT SWITCH
DWG DRAWING
E, EX EXISTING TO REMAIN
EM DEVICE ON EMERGENCY CIRCUIT
EMT ELECTRICAL METALLIC TUBING
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FATC FIRE ALARM TERMINAL CABINET
FASP FIRE ALARM SMOKE PURGE PANEL
FLA FULL LOAD AMPS
G GROUND
GFI GROUND FAULT INTERRUPTER
GRS GALVANIZED RESISTIVE CONDUIT
HP HORSE POWER
IG ISOLATED GROUND
KVA KILOVOLT-AMPS
KW KILOWATT
MCB MAIN CIRCUIT BREAKER
MLO MAIN LUGS ONLY
MDP MAIN DISTRIBUTION PANEL
N NEW
NEC NATIONAL ELECTRICAL CODE
NFSS NON FUSED SAFETY SWITCH
NL NIGHT LIGHT FIXTURE
NTS NOT TO SCALE
P POLE
PH, ∅ PHASE
PNL PANEL
R RELOCATED AT NEW LOCATION
RR REMOVE AND RELOCATE
S/N SOLID NEUTRAL
SWBD SWITCHBOARD
T, XFMR TRANSFORMER
TYP. TYPICAL
UON UNLESS OTHERWISE NOTED
V VOLTS
W WATTS
WP WEATHERPROOF
TX
(NOTE : ALL ABBREVIATIONS MAY NOT APPEAR ON
THE DRAWINGS)
SUBSCRIPTS
RECEPTACLE OUTLETS AND JUNCTION BOX DEVICES MAY BE INDICATED
WITH THE FOLLOWING SUBSCRIPTS:
EM : RECEPTACLE ON EMERGENCY POWER
GFI : GROUND FAULT INTERRUPTER
WP : WEATHER PROOF OUTLET WITH PROTECTIVE IN-USE COVER
MD : MOTORIZED DAMPER
NON-FUSIBLE DISCONNECT SWITCH
FUSIBLE DISCONNECT SWITCH
COMBINATION STARTER DISCONNECT SWITCH
DRY TYPE TRANSFORMER
GENERATOR
AUTOMATIC TRANSFER SWITCH
DISTRIBUTION BOARD
120/208V ELECTRICAL PANEL
480/277V ELECTRICAL PANEL
CIRCUIT NUMBER DESIGNATION FEEDING ELECTRICAL
DEVICES, FIXTURES AND EQUIPMENT.
PANEL : INDICATES THE PANEL NAME
XX : INDICATES THE CIRCUIT NUMBER
KEYED DRAWING NOTE
CONDUIT UP
CONDUIT DOWN
CONTINUATION CIRCUIT
1. INSTALLATION OF ALL WORK SHALL BE IN ACCORDANCE WITH THE FOLLOWING REGULATIONS, CODES, ETC.
A. LOCAL CODES AND ORDINANCES
B. THE EDITION OF THE NATIONAL ELECTRICAL CODE (NEC 2020), NFPA 70, IN EFFECT.
C. ARS FACILITIES DESIGN STANDARDS (ARS 2012) ARS-242.1.
2. CONTRACTOR TO PROVIDE SUFFICIENT NOTICE TO THE OWNER'S REPRESENTATIVE PRIOR TO ANY WORK TO ALLOW
ADEQUATE TIME FOR COORDINATION OF EXISTING BUILDING ACTIVITIES WITH THE CONSTRUCTION WORK.
3. CONTRACTOR TO INCLUDE IN THEIR SCOPE ALL LABOR, MATERIALS, SERVICES, APPARATUS AND SHOP DRAWINGS IN
ADDITION TO THE CONTRACT DOCUMENTS AS REQUIRED TO COMPLY WITH ALL APPLICABLE GOVERNING LAWS, CODES
AND JURISDICTION REQUIREMENTS. PROVIDE ELECTRICAL EQUIPMENT WITH ALL ASSOCIATED ACCESSORIES, BRANCH
CIRCUIT WIRING AND CONDUIT INFRASTRUCTURE AS REQUIRED TO ENSURE A COMPLETE AND OPERATIONAL SYSTEM.
4. ALL MATERIALS AND WORK SHALL BE ACCORDING TO PROJECT SPECIFICATIONS.
5. IF MATERIAL OR EQUIPMENT IS INSTALLED BEFORE IT IS APPROVED, THE CONTRACTOR SHALL BE LIABLE FOR ITS
REMOVAL AND REPLACEMENT AT NO ADDITIONAL CHARGE IF IN THE OPINION OF THE ARCHITECT OR ENGINEER, THE
MATERIAL OR EQUIPMENT DOES NOT MEET THE INTENT OF THE DRAWINGS AND/OR SPECIFICATIONS.
6. REFER TO ARCHITECTURAL DRAWINGS AND LAB DRAWINGS(Q-SERIES) FOR THE EXACT LOCATION, ELEVATION, MOUNTING HEIGHTS AND DETAILS OF ALL LIGHT FIXTURES AND DEVICES. REPORT ANY DISCREPANCIES TO THE
ARCHITECT IMMEDIATELY.
7. ALL NEW SLAB PENETRATIONS MUST BE X-RAYED OR RADAR PRIOR TO CORE DRILLING. OBTAIN APPROVAL FROM
OWNER'S REPRESENTATIVE PRIOR TO ANY CORE DRILLING.
8. ELECTRICAL SYSTEMS SHALL BE GROUNDED PER ARTICLE 250 OF THE NATIONAL ELECTRICAL CODE.
9. PROVIDE AN INSULATED EQUIPMENT GROUNDING CONDUCTOR IN ALL BRANCH CIRCUITS AND FEEDERS INSTALLED IN
RACEWAYS. THE DEDICATED EQUIPMENT GROUNDING CONDUCTOR SHALL BE SIZED PER NEC SECTION 250.122. SOLE
USE OF METAL RACEWAY AS A GROUNDING CONDUCTOR SHALL NOT BE ACCEPTABLE. WIRING METHODS SHALL BE IN
ACCORDANCE WITH NEC SECTION 518.4 FOR ALL ASSEMBLY AREAS.
10. PROVIDE RED COLOR LOCKABLE TYPE BREAKERS FOR CIRCUITS SERVING LIFE SAFETY PANEL BOARDS.
11. NUMBER OF WIRES MAY NOT BE INDICATED FOR ALL CIRCUITS, ONLY THOSE WHERE CLARIFICATION IS NECESSARY.
PROVIDE THE NUMBER AND SIZE AS NECESSARY FOR THE PROPER FUNCTION OF THE SYSTEM WHETHER SPECIFICALLY
INDICATED ON PLAN OR NOT.
12. ALL BACK BOXES INSTALLED IN PARTITION WALLS SHALL BE STAGGERED. BACK-TO-BACK INSTALLATION IS NOT
PERMITTED.
13. PROVIDE ACCESS PANELS FOR ALL INACCESSIBLE JUNCTION BOXES AS REQUIRED BY THE N.E.C.
14. PROVIDE PLASTER RING WITH PULL STRING TO SPACE ABOVE SUSPENDED CEILING FOR ALL TELEPHONE, DATA, FAX, MODEM, CATV, CARD READER, ETC. OUTLETS INSTALLED IN HOLLOW PARTITIONS. PROVIDE 3/4" EMPTY CONDUIT AND
PULL STRING TO SPACE ABOVE SUSPENDED CEILING FOR THESE OUTLETS INSTALLED IN AN INSULATED PARTITION.
PROVIDE 1" EMPTY CONDUIT WITH PULL STRINGS FOR DATA/TEL OUTLETS. .
15. ELECTRICAL CONTRACTOR TO COORDINATE WITH MECHANICAL, PLUMBING AND OTHER TRADES TO PROVIDE ALL
EQUIPMENT ASSOCIATED WITH THEIR RESPECTIVE TRADES WITH NECESSARY WIRING AND CONDUIT INFRASTRUCTURE
FOR ALL SENSORS, AND CONTROL SYSTEMS AS REQUIRED.
16. CONTRACTOR TO PROVIDE DEDICATED CIRCUIT FOR CONNECTION TO EACH MECHANICAL EQUIPMENT CONTROL
PANEL AS REQUIRED. COORDINATE EXACT LOCATION AND CONNECTION REQUIREMENTS WITH MECHANICAL AND
CONTROLS CONTRACTORS.
17. CONTRACTOR TO COORDINATE ELECTRICAL WORK TO AVOID INTERFERENCE BETWEEN ALL TRADES.
A. DETERMINE INTERFERENCE BEFORE WORK IS FABRICATED OR INSTALLED. THE CONTRACTOR SHALL BE
THOROUGHLY FAMILIAR WITH ALL DETAILS OF WORK AND WORKING CONDITIONS AND COORDINATE
WORK DURING PRELIMINARY STAGES TO ENSURE ACTUAL ERECTION WILL PROCEED WITHOUT INTERFERENCE.
COORDINATION IS OF PARAMOUNT IMPORTANCE AND REQUESTS FOR ADDITIONAL PAYMENT
WILL BE CONSIDERED WHERE REQUEST IS BASED ON INTERFERENCE.
B. WHERE JOB CONDITIONS REQUIRE REASONABLE DEVIATIONS FROM CONTRACT DOCUMENTS, MAKE
DEVIATIONS WITHOUT ADDITIONAL COST TO OWNER, AFTER OBTAINING APPROVAL OF ARCHITECT.
C. PROVIDE MAXIMUM PRACTICAL SPACE FOR OPERATION, REPAIR, REMOVAL, AND TESTING OF ELECTRICAL
EQUIPMENT. DEVIATIONS MAY BE MADE TO PROVIDE REQUIRED ACCESSIBILITY PROVIDED THEY ARE APPROVED
BY THE OWNERS OR THE ARCHITECTS.
D. KEEP CONDUITS, WIRE WAYS AND SIMILAR ITEMS AS CLOSE AS POSSIBLE TO CEILING, WALLS AND COLUMNS IN
ORDER TO TAKE UP MINIMUM AMOUNT OF SPACE. ALL WORK TO BE IN STALLED IN A NEAT AND
WORK MAN LIKE MANNER.
E. PROVIDE OFFSETS, FITTINGS AND SIMILAR ITEMS NECESSARY TO ACCOMPLISH REQUIREMENTS OF
COORDINATION WITHOUT ADDITIONAL EXPENSE TO OWNER.
F. PROVIDE ACCESS TO AND CLEARANCES AROUND ELECTRICAL EQUIPMENT AS REQUIRED BY THE N.E.C.
18. ELECTRICAL CONTRACTOR SHALL FOLLOW THE STANDARD OPERATING PROCEDURE FOR CLEANING AND
DISINFESTATION OF MACHINERY IMPACTED BY THE SOIL REFER TO THE USDA STANDARD OPERATING PROCEDURE, CLEANING AND DISINFESTING EQUIPMENT AT THE CATTLE FEVER TICK RESEARCH LABORATORY IN MISSION, TEXAS.
USDA EMPLOYEES AT THE EDINBURG LOCATION WILL PROVIDE CLEANING AND DISINFECTION OF MACHINERY. CONTRACTOR
TO PROVIDE 24 HOURS NOTICE OF CLEANING EQUIPMENT. FOR MORE INFORMATION. COORDINATE WITH
CONTRACTING OFFICER AS NEEDED.
VIF VERIFY IN FIELD
(STANDARD SYMBOLS ONLY, ALL SYMBOLS MAY NOT BE APPLICABLE TO THIS PROJECT)
G
ATS
DP
1465 NORTHSIDE DRIVE SUITE 220B
ATLANTA, GA 30318
P:706-248-7165 www. .com
TM
PROJECT NUMBER: SIGQ212911.15
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A
D
USDA S
U
DWG. NO
DRAWN BY
SOLICITATION NO. SHEET NAME
ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED
Revisions
Agricultural Research Service
6/6/2022 3:27:05 PM C:\Users\Nicholas.Carlis\Documents\80-SIGQ212911.15_REVIT ELECTRICAL UTILITIES_nicholas.carlisYDXF8.rvt
WET LAB UTILITY
UPGRADE
E001
GENERAL NOTES,
SYMBOLS, &
ABBREVIATIONS
CDC
NC 05/23/2022
JM BD
DC
LB
EO
NO. DATE BY DESCRIPTION
1 06/06/2022 JM ISSUE FOR BIDDING AND CONSTRUCTION
GENERAL NOTES ELECTRICAL SYMBOL LIST ABBREVIATIONS
DRAWING LIST
SHEET DRAWING TITLE
01 E001 GENERAL NOTES, SYMBOLS, & ABBREVIATIONS
02 EDS01 ELECTRICAL DEMOLITION SITE PLAN
03 ES01 ELECTRICAL SITE PLAN
04 E501 ELECTRICAL UTILITY POWER RISER
05 E601 ELECTRICAL SCHEDULES
06 E701 ELECTRICAL DETAILS
07 E702 ELECTRICAL DETAILS
08 E703 ELECTRICAL DETAILS
E
E
E
E
E
E
E
WWWW
W
1 STORY
WOOD
PREFAB
WOOD
PORCH
RAMP
STR
BARBED WIREFENCE
A/C
224.76 Air Conditioning Unit
STEEL ROOFOVERHANG
STEEL ROOFOVERHANG
1 STORYWOOD
PREFAB
C O N C
W A L
K CONC
WALK
V L T
V L T
CONC
PAD
STEEL ROOFOVERHANG
STEEL 1
STORYBUILDING
ABOVEGROUND6" PVC
ABOVEGROUND6" PVC
ABOVEGROUND6" PVC
BARBED WIREFENCE
B A R B E D
W
IR
E
F E N C E
CANOPY
G A M E
F E N C E
DEER
FEEDER
GAME
FENCE
G A M E
F E N C E
GAME
GATE
SHEET KEY NOTES#
TX
ATSG
D
1. EXISTING UTILITY TRANSFORMER SHALL BE DEMOLISHED. ALL
EXISTING CONDUIT AND FEEDERS SHALL BE DEMOLISHED BACK TO
SOURCE. COORDINATE DISCONNECTION SCHEDULE WITH UTILITY
PROVIDER AND CONTRACTING OFFICER PRIOR TO DEMOLITION.
1465 NORTHSIDE DRIVE SUITE 220B
ATLANTA, GA 30318
P:706-248-7165 www. .com
TM
PROJECT NUMBER: SIGQ212911.15
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A
D
USDA S
U
DWG. NO
DRAWN BY
SOLICITATION NO. SHEET NAME
ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED
Revisions
Agricultural Research Service
6/6/2022 3:27:19 PM C:\Users\Nicholas.Carlis\Documents\80-SIGQ212911.15_REVIT ELECTRICAL UTILITIES_nicholas.carlisYDXF8.rvt
WET LAB UTILITY
UPGRADE
EDS01
ELECTRICAL DEMOLITION
SITE PLAN
CDC
NC 05/23/2022
JM BD
DC
LB
EO
SCALE: 1 : 280
ELECTRICAL DEMOLITION SITE PLAN
NO. DATE BY DESCRIPTION
1 06/06/2022 JM ISSUE FOR BIDDING AND CONSTRUCTION
E
E
E
E
E
E
WWWW
W
TX
1 STORY
WOOD
PREFAB
WOOD
PORCH
RAMP
STR
BARBED WIREFENCE
A/C
224.76 Air Conditioning Unit
STEEL ROOFOVERHANG
STEEL ROOFOVERHANG
1 STORYWOOD
PREFAB
C O N C
W A L
K CONC
WALK
V L T
V L T
CONC
PAD
STEEL ROOFOVERHANG
STEEL 1STORYBUILDING
ABOVEGROUND6" PVC
ABOVEGROUND6" PVC
ABOVEGROUND6" PVC
BARBED WIREFENCE
B A R B E D
W
IR
E
F E N C E
CANOPY
G A M E
F E N C E
DEER
FEEDER
GAME
FENCE
G A M E
F E N C E
GAME
GATE
PROPOSED WET LABFFE-226.50
PROPOSED DEERWORKING FACILITYFFE-226.00
SHEET KEY NOTES#
UTILITY XFMR
2-1/2"C
4"C
75KVA
TX
2"C
SPARE 4"C (COORDINATE QUANTITY WITH
CONTRACTING OFFICER)
24" GROUND DISTURBANCE
18" GROUND DISTURBANCE
1.57% VOLTAGE DROP
GENERAL NOTES
1. REFER TO DRAWING E001 FOR ELECTRICAL GENERAL NOTES, LEGEND AND
ABBREVIATIONS. REFER TO DRAWING E501 FOR POWER RISER DIAGRAM.
2. SEE ARCHITECTURAL AND CIVIL DRAWINGS FOR EXACT LOCATION,
MOUNTING HEIGHTS, AND ADDITIONAL INFORMATION, PRIOR TO ROUGH-IN
WORK.
3. COORDINATE WITH CIVIL AND EQUIPMENT SUPPLIER FOR FOUNDATION
DETAIL, EXACT LOCATION AND REQUIREMENTS.
4. FIELD COORDINATE THE EXACT LOCATION OF UNDERGROUND CONDUITS
WITH ALL OTHER UNDERGROUND UTILITIES AND THE SITE CONDITIONS.
5. SEE DETAIL ON DRAWING E701 FOR SERVICE GROUNDING SYSTEM
INFORMATION.
6. INSTALLATION SHALL CONFORM TO N.E.C. ARTICLE 300-5.
7. ALL POWER COMPANY/INCOMING ELECTRIC SERVICE RELATED WORK MUST
BE PERFORMED IN ACORDANCE TO TEXAS RULES AND REGULATIONS AND
PER THEIR REQUIREMENTS. NO CONDUITS AND/OR EQUIPMENT PADS
SHALL BE INSTALLED, PRIOR TO THEIR WRITTEN APPROVAL.
8. ALL INCOMING ELECTRIC SERVICE CONDUITS AND EQUIPMENT SHALL BE
LOCATED AS PER TEXAS WRITTEN INSTRUCTIONS OR USING THEIR
APPROVED DRAWINGS AND IN PRE-APPROVED EASEMENT AREA ONLY.
9. FIELD COORDINATE ALL UNDERGROUND CONDUITS AND DUCT BANK
LOCATION/ROUTING WITH THE SITE CONDITIONS AS WELL AS STRUCTURAL
FOOTINGS, AND ONLY AFTER APPROVAL BY TEXAS AND THE STRUCTURAL
AND CIVIL ENGINEERS.
1. NEW UTLITY TRANSFORMER PROVIDED BY UTILITY PROVIDER.
COORDINATE CONDUIT AND CONDUCTOR SIZE TO TRANFORMER
WITH UTILITY. ALL CONDUIT SHALL BE RUN UNDERGROUND AND
ENCASED IN CONCRETE TO NEW TRANSFORMER. PROVIDE ALL
APPURTENANCES NEEDED FOR COMPLETE INSTALLATION.
2. REFER TO SHEET E702 FOR SWITCHBOARD DATA INFORMATION,
DIMENSIONS, AND MOUNTING DETAILS.
3. NEW 500KW GENERATOR SHALL BE PROVIDED WITH 48 HOURS FUEL
SUPPLY PER USDA DESIGN GUIDLINES AND SOUNDPROOF WEATHER
ENCLOSURE.
1465 NORTHSIDE DRIVE SUITE 220B
ATLANTA, GA 30318
P:706-248-7165 www. .com
TM
PROJECT NUMBER: SIGQ212911.15
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A
D
USDA S
U
DWG. NO
DRAWN BY
SOLICITATION NO. SHEET NAME
ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED
Revisions
Agricultural Research Service
6/6/2022 12:16:25 PM C:\Users\Nicholas.Carlis\Documents\80-SIGQ212911.15_REVIT ELECTRICAL UTILITIES_nicholas.carlisYDXF8.rvt
WET LAB UTILITY
UPGRADE
ES01ELECTRICAL SITE PLAN
CDC
NC 05/23/2022
JM BD
DC
LB
EO
SCALE: 1 : 280
ELECTRICAL SITE PLAN
NO. DATE BY DESCRIPTION
1 06/06/2022 JM ISSUE FOR BIDDING AND CONSTRUCTION
GG DP
UTILITY
XFMR
ATS(E) 225KVA XFMR
MSB
500KW GEN
G
G(E)
TX
SHEET KEY NOTES#
1. NEW UTLITY TRANSFORMER PROVIDED BY UTILITY PROVIDER.
COORDINATE CONDUIT AND CONDUCTOR SIZE TO TRANFORMER
WITH UTILITY. ALL CONDUIT SHALL BE RUN UNDERGROUND AND
ENCASED IN CONCRETE TO NEW TRANSFORMER. PROVIDE ALL
APPURTENANCES NEEDED FOR COMPLETE INSTALLATION.
2. REFER TO SHEET E702 FOR SWITCHBOARD DATA INFORMATION,
DIMENSIONS, AND MOUNTING DETAILS.
3. NEW 500KW GENERATOR SHALL BE PROVIDED WITH 48 HOURS FUEL
SUPPLY PER USDA DESIGN GUIDLINES AND SOUNDPROOF WEATHER
ENCLOSURE.
4. NEW 75KVA PAD MOUNTED DRY-TYPE TRANSFORMER. PROVIDE A
250A FUSIBLE DISCONNECT SWITCH WITHIN 10' OF THE SECONDARY
SIDE OF THE TRANSFORMER. PROVIDE NEMA 4X STAINLESS STEEL
ENCLOSURE FOR THE TRANSFORMER AND DISCONNECT SWITCH.
COORDINATE AND CONFIRM FINAL LOCATION WITH CIVIL DRAWINGS.
SEE E501 FOR RISER DIAGRAM AND MORE INFORMATION.
5. NEW 225KVA PAD MOUNTED DRY-TYPE TRANSFORMER. PROVIDE A
800A FUSIBLE DISCONNECT SWITCH WITHIN 10' OF THE SECONDARY
SIDE OF THE TRANSFORMER IF INSTALLED MORE THAN 10' AWAY
FROM EXISTING ATS. PROVIDE NEMA 4X STAINLESS STEEL
ENCLOSURE FOR THE TRANSFORMER AND DISCONNECT SWITCH.
COORDINATE AND CONFIRM FINAL LOCATION WITH CIVIL DRAWINGS
AND IN FIELD. SEE E501 FOR RISER DIAGRAM AND MORE
INFORMATION.
6. NEW 1200A 480/277V PAD-MOUNTED SERVICE ENTRANCE RATED
SWITCHBOARD MSB. PROVIDE NEMA 4X STAINLESS STEEL
ENCLOSURE FOR THE SWITCHBOARD AND ALL ASSOCIATED
APPURTENANCES. COORDINATE AND CONFIRM FINAL LOCATION WITH
CIVIL DRAWINGS AND IN FIELD. SEE E501 FOR RISER DIAGRAM AND
MORE INFORMATION.
7. NEW 800A 208/120V PAD-MOUNTED SERVICE ENTRANCE RATED
DISTRIBUTION PANELBOARD DP. PROVIDE NEMA 4X STAINLESS STEEL
ENCLOSURE FOR THE DISTRIBUTION BOARD AND ALL ASSOCIATED
APPURTENANCES. COORDINATE AND CONFIRM FINAL LOCATION WITH
CIVIL DRAWINGS AND IN FIELD. SEE E501 FOR RISER DIAGRAM AND
MORE INFORMATION.
8. NEW UTLITY TRANSFORMER PROVIDED BY UTILITY
PROVIDER. COORDINATE CONDUIT AND CONDUCTOR SIZE TO
TRANFORMER WITH UTILITY. PROVIDE ALL APPURTANCES NEEDED
FOR COMPLETE INSTALLATION.
18" GROUND DISTURBANCE
3 #500 KCMIL + 1 #2 AWG
G IN 3" C) (N)
FROM
UTILITY
3 SETS (4 #500KCMIL+ 1#2/0G IN 4"C)
CONCRETE ENCASED (N)
3 SETS (4 #300 KCMIL + 1
#2/0 AWG G IN 3-1/2" C (N)
FUTURE
PANEL
WETLAB
"PW"
400A
480/277V
3PH, 4W
MCB (N)
2 SETS (4 #3/0 AWG + 1 #
2 AWG G IN 2-1/2" C) (N)
FUTURE
PANEL BARN
"PB"
100A
208/120V
3PH, 4W
MCB
(N)
4 #1 AWG + 1 # 8 AWG G IN 2" C (N)
4 SETS (4 #350KCMIL IN 3-1/2"C)
CONCRETE ENCASED (N)
3 #1 AWG + 1 #6 AWG G IN 1 1/4" C (N)
4 #250 KCMIL + 1 #2 AWG
G IN 1 2 1/2" C (N)
3 SETS (4 #300 KCMIL + 1 #2/0 AWG G IN 3-1/2" C (N)
TRANSFORMER DISCONNECT
125AF/200AS 480V 3P (N)
3 #1 AWG + 1 #6 AWG G IN 1 1/2" C (N)
3 #1 AWG + 1 #6 AWG G
IN 1 1/4" C (N)
FUTURE BARN
2"C (N)
WILDLIFE BARN WETLAB WETLAB
3 SETS (4 #300 KCMIL + 1
#2/0 AWG G IN 3-1/2" C (N)
2/0 G (N)
4 #4 AWG + 1 #8 AWG G IN 1-1/2" C
EXISTING
UTILITY
POLEXFMR 208V
(E)
200KW
GENSET
EG-1(E)
208V 3P
(ATS)
800A 694A
(N)
(E)
225KVA
DRY-TYPE
XFMR (N)
(E)
200KW
GENSET
EG-1(E)
208V 3P
PANEL
"BLDG 1"
225A
208/120V
3PH, 4W
(E)
(D)
(ATS)
800A
694A
(E)
(E)(SERVICE DISCONNECT)
800A
208 3P
(D)
PANEL
"BLDG 5"
100A
208/120V
3PH, 4W
(E)
PANEL
"BLDG 6"
100A
208/120V
3PH, 4W
(E)
50A
LIFT STATION
208/120V
3PH, 3W
(E)
PANEL
"BLDG 2"
100A
208/120V
3PH, 4W
(E)
PANEL
"BLDG 3"
200A
208/120V
3PH, 4W
(E)
PANEL
"BLDG 4"
100A
208/120V
3PH, 4W
(E)
PANEL
"EXISTING"
250A
208/120V
3PH, 4W
(E)
PANEL
"BLDG 7"
200A
208/120V
3PH, 4W
(E)
ENCLOSED
CB
"BLDG 10"
40A
240V 1P
(E)
(E)
(E)
(E)
(E)(E)
500KW
GENSET
EG-2
480V 3P
1000A
800A
208Y/120V
DISTRIBUTION
BOARD
DP
(N)
(N)
PANEL
"BLDG 1"
225A
208/120V
3PH, 4W
(E)
PANEL
"BLDG 5"
100A
208/120V
3PH, 4W
(E)
PANEL
"BLDG 6"
100A
208/120V
3PH, 4W
(E)
50A
LIFT STATION
208/120V
3PH, 3W
(E)
PANEL
"BLDG 2"
100A
208/120V
3PH, 4W
(E)
PANEL
"BLDG 3"
200A
208/120V
3PH, 4W
(E)
PANEL
"BLDG 4"
100A
208/120V
3PH, 4W
(E)
PANEL
"EXISTING"
250A
208/120V
3PH, 4W
(E)
PANEL
"BLDG 7"
100A
208/120V
3PH, 4W
(E)
ENCLOSED
CB
"BLDG 10"
40A
240V 1P
(E)
(E)
PANEL
"BLDG 7"
100A
208/120V
3PH, 4W
(E)
(E) (E) (E) (E) (E)
(E)
(E) (E) (E) (E)
UTILITY
XFMR (N)
(N)
DISTRIBUTION
SECTION
(N)
C/T CABINET
ATS
(N)(N)(N)
FUTURE
75KVA
"T-RW"
XFMR (N)
FUTURE
PANEL
"RW"
225A
208/120V
3PH, 4W
MCB
(N)
75KVA
"T-RW"
XFMR (N)
(N)
350A
1000A
480/277V
3PH
M
MSB
60A
LOAD
CENTER
GENERAL NOTES
SHEET KEY NOTES#
1. UNLESS OTHERWISE NOTED, ALL ELECTRICAL EQUIPMENT, PANELS
AND FEEDERS ARE EXISTING TO REMAIN AND SHOWN FOR REFERENCE
ONLY.
2. CONTRACTOR TO PERFORM SHORT CIRCUIT AND COORDINATION
STUDY ALONG WITH AN ARC FLASH HAZARD ANALYSIS. COORDINATE
WITH EQUIPMENT MANUFACTURER TO SET THE TIME CURRENT
CURVES ON THE MAIN OVERCURRENT PROTECTIVE DEVICES AND
ASSOCIATED BRANCH CIRCUIT BREAKERS TO ENSURE THEY ARE
SELECTIVELY COORDINATED WITH EACH OTHER. THE INTERRUPTING
RATING OF ALL ELECTRICAL EQUIPMENT SHALL BE BAASED ON THE
DATA OF THE SHORT CIRCUIT AND COORDINATION STUDY.
CONTRACTOR TO SUBMIT A SHORT-CIRCUIT AND SELECTIVE
COORDINATION STUDY ALONG WITH THE SWITCHGEAR,
SWITCHBOARD, AND PANELBOARD SUBMITTAL SHOP DRAWINGS. THE
WORK REQUIRED TO CORRECT SELECTIVE COORDINATION ISSUES
DISCOVERED AFTER THE SHOP DRAWINGS ARE APPROVED SHALL BE
PROVIDED BY HTE CONTRACTOR AT NO ADDITIONAL FEES.
3. PROVIDE INSULATED CASE POWER CIRCUIT BREAKER FOR MAIN
BREAKERS AND LARGER FRAME SIZE MOLDED CIRCUIT BREAKERS FOR
BRANCH CIRUITS
1. EXISTING UTILITY TRANSFORMER SHALL BE DEMOLISHED. ALL
EXISTING CONDUIT AND FEEDERS SHALL BE DEMOLISHED BACK TO
SOURCE. COORDINATE DISCONNECTION SCHEDULE WITH UTILITY
PROVIDER AND CONTRACTING OFFICER PRIOR TO DEMOLITION.
2. UTILITY PROVIDER SHALL PROVIDE NEW SERVICE FEEDERS, RUN
UNDERGROUND AND TERMINATE AT LOCATION OF NEW UTILITY
TRANSFORMER. NEW UTLITY TRANSFORMER PROVIDED BY UTILITY
PROVIDER. COORDINATE CONDUIT AND CONDUCTOR SIZE TO
TRANFORMER WITH UTILITY. PROVIDE ALL APPURTANCES NEEDED
FOR COMPLETE INSTALLATION.
3. ALL CONDUIT SHALL BE RUN UNDERGROUND AND ENCASED IN
CONCRETE TO NEW TRANSFORMER PROVIDED BY ELECTRICAL
CONTRACTOR. ELECTRICAL CONTRACTOR SHALL LEAVE EXTRA
LENGTH OF CONDUCTORS FOR UTILITY PROVIDER TO TERMINATE
INSIDE THE NEW TRANSFORMER. COORDINATE WITH UTILITY
PROVIDER AND USDA PRIOR TO COMMENCEMENT OF WORK.
COORDINATE ALL SERVICE SHUTDOWN WITH USDA AND UTILITY
PROVIDER.
4. SWITCHBOARD SHALL BE SERVICE ENTRANCE RATED. PROVIDE
HOUSEKEEPING PAD, 6" HIGH AND PAD SHALL EXTEND 6" OUTSIDE
FOOT PRINT OF SWITCHBOARD. PROVIDE SERVICE ENTRANCE SPD
PER UL 1449 5TH EDITION, GROUND FAULT PROTECTION PER NEC
230.95 AND ARC ENERGY REDUCTION PER NEC 240.87.
5. PROVIDE AND INSTALL DIGITAL METERING FOR THE DISTRUBUTION
PANELBOARD TO MONITOR ENERGY CONSUMPTION
6. ELECTRICAL CONTRACTOR SHALL INTERCEPT AND EXTEND EXISTING
FEEDER AND CONDUIT PRESERVED DURING DEMOLITION TO
COMPLETE CONNECTION TO NEW DISTRIBUTION PANEL DP.
7. COORDINATE SERVICE FEEDER SIZE WITH UTILITY PROVIDER
8. EXISTING ATS SHALL REMAIN AND BE PROTECTED DURING
CONSTRUCTION, DISCONNECT EXISTING FEEDERS CONNECTED TO
EXISTING ATS. DISCONNECTED FEEDERS AND CONDUITS SHALL
REMAIN INTACT, BE CAPPED AND PROTECTED DURING
CONSTRUCTION.
9. PROVIDE 2" EMPTY CONDUIT FOR FUTURE BARN INSTALLATION.
COORDINATE FINAL LOCAL OF CONDUIT STUB-UP IN FIELD WITH
USDA CONTRACTING OFFICER
10. NEW 800A 208/120V PAD-MOUNTED SERVICE ENTRANCE RATED
DISTRIBUTION PANELBOARD DP. PROVIDE HOUSEKEEPING PAD, 6"
HIGH AND PAD SHALL EXTEND 6" OUTSIDE FOOT PRINT OF
SWITCHBOARD. PROVIDE SERVICE ENTRANCE SPD
PER UL 1449 5TH EDITION, GROUND FAULT PROTECTION PER NEC
230.95 AND ARC ENERGY REDUCTION PER NEC 240.87.
LOCATED IN INTERIOR OF RESPECTIVE BUILDINGS
1465 NORTHSIDE DRIVE SUITE 220B
ATLANTA, GA 30318
P:706-248-7165 www. .com
TM
PROJECT NUMBER: SIGQ212911.15
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A
D
USDA S
U
DWG. NO
DRAWN BY
SOLICITATION NO. SHEET NAME
ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED
Revisions
Agricultural Research Service
6/6/2022 3:27:08 PM C:\Users\Nicholas.Carlis\Documents\80-SIGQ212911.15_REVIT ELECTRICAL UTILITIES_nicholas.carlisYDXF8.rvt
WET LAB UTILITY
UPGRADE
E501
ELECTRICAL UTILITY
POWER RISER
CDC
NC 05/23/2022
JM BD
BD
DC
LB
EO
NO. DATE BY DESCRIPTION
1 06/06/2022 JM ISSUE FOR BIDDING AND CONSTRUCTION
NO SCALEE501
2 EXISTING ELECTRICAL RISER DIAGRAM
NO SCALEE501
3 NEW ELECTRICAL RISER DIAGRAM
3 7
2/0 G (N)
2/0 G (N)
WETLAB WETLABWILDLIFE BARN
EXISTING
UTILITY POLE
XFMR 208V
200A
1465 NORTHSIDE DRIVE SUITE 220B
ATLANTA, GA 30318
P:706-248-7165 www. .com
TM
PROJECT NUMBER: SIGQ212911.15
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A
D
USDA S
U
DWG. NO
DRAWN BY
SOLICITATION NO. SHEET NAME
ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED
Revisions
Agricultural Research Service
6/6/2022 3:27:27 PM C:\Users\Nicholas.Carlis\Documents\80-SIGQ212911.15_REVIT ELECTRICAL UTILITIES_nicholas.carlisYDXF8.rvt
WET LAB UTILITY
UPGRADE
E601ELECTRICAL SCHEDULES
05/23/2022
NO. DATE BY DESCRIPTION
1 06/06/2022 JM ISSUE FOR BIDDING AND CONSTRUCTION
PANELBOARD SCHEDULE NOTES
1. TURN ALL SPARE CIRCUIT BREAKERS TO "OFF" POSITION AT COMPLETION
OF WORK.
2. AT COMPLETION OF THE PROJECT, PROVIDE TYPE WRITTEN SCHEDULES
FOR ALL PANEL BOARDS UTILIZED DURING THE CONSTRUCTION PROCESS
INDICATING AS-BUILT CONDITIONS.
3. ALL UNGROUNDED AND GROUNDED CONDUCTORS OF EACH MULTI-WIRE
BRANCH CIRCUIT ARE TO BE GROUPED TOGETHER AT BOTH ENDS BY
WIRE TIES OR SIMILAR MEANS.
4. NEW CIRCUIT BREAKER (IF PROVIDED) MUST BE COMPATIBLE WITH
EXISTING PANELBOARD (UL LISTED, MANUFACTURED BY THE
PANELBOARD MANUFACTURER AND SHALL HAVE AN AIC RATING TO
MATCH THE EXISTING PANEL RATING).
5. ALL SPARE CIRCUIT BREAKERS MADE AVAILABLE AFTER DEMOLITION ARE
BASED ON THE EXISTING DOCUMENTS AND MAY BE INACCURATE. THE
ACTUAL CIRCUIT NUMBERS MAY BE DIFFERENT AND SHALL BE VERIFIED IN
FIELD DURING CONSTRUCTION.
6. ELECTRICAL CONTRACTOR TO PERFORM THE CIRCUIT TRACING AND
UP DATE THE PANEL SCHEDULE TO REFLECT THE ACTUAL CIRCUIT
NUMBERS.
7. ALL NEW LOADS ON EXISTING PANEL ARE INDICATED IN BOLD LETTERS.
N4X N4X
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY USDA
DRAWN BY
CDC
NC
JM BD
BD
DC
LB
EO
BUILDING COLD WATER
GRADE
BUILDING WALL
SERVICE PIPE
NEUTRAL BUS
TYPICAL
AS PER NEC [250-52(A)(1)
SEE NOTE 2
GROUND BUS
SEE NOTE 4
COPPER CLAD
GROUND RODS
THE EARTH
DRIVEN INTO
3/4" x 10'-0"
[250.52(A)]
SERVICE EQUIPMENT
#4/0 AWG TO TELECOMUNICATIONS
GROUNDING BUSBAR IN EACH
TELECOM CLOSET.
(SEE TELECOM DRAWINGS FOR
TELECOM CLOSET LOCATIONS)
MAIN TELECOMMUNICATIONS
GROUNDING BUSBAR IN
MAIN TELECOM ROOM
TO LIGHTNING
PROTECTION
GROUND ROD
AS PER NEC
[250.52(A)(3)]
#4/0 AWG
#4/0 AWG
(TYP. OF ALL)
BOND TO METAL FRAME OF
BUILDING OR STRUCTURE
WHERE PRESENT AS PER
NEC [250-52(A)(2)]
4"X1/4"X2' LONG
COPPER GROUND BAR IN
MAIN ELECTRICAL ROOM
SERVICE EQUIPMENT
NOT A SEPERATLY DERIVED
SYSTEM
EQUIPMENT GROUNDING CONDUCTOR
OR SUPPLY SIDE BONDING JUMPER
EQUIPMENT GROUNDING CONDUCTOR
3 POLE TRANSFER
SWITCH
LOADN
EQUIPMENT GROUNDING
CONDUCTOR
N
FINISHED GRADE
PROVIDE UTILITY
MARKER TAPE BURIED
12" BELOW FINISHED
GRADE
4" PVC DUCT (TYP. OF 6)
7 1/2" 6"
N O
M
IN
A L 1
/2
/2
2' - 0"
PROVIDE SPACERS EVERY 48"
AND BACKFILL
FRONT VIEW
PLAN VIEW
CONCRETE ENCASED
PVC CONDUIT PRIMARY
NUMBER AND SIZE AS INDICATED
PVC CONDUIT SECONDARY
NUMBER AND SIZE AS INDICATED
RGS TO PVC COUPLING (TYP.)
3/4" X 10' GROUND ROD
(TYPICAL FOR 4) MINIMUM
FUSES
TAP CHANGER
15kV, 200A LOAD BREAK
ELBOW (TYP. FOR 3)
REINFORCING BARS
CABLE SHIELD ADAPTER (TYP.)
CABLE SHIELDS
(TYP. FOR 3)
3/4" X 10' COPPER CLAD
GROUND ROD (TYP. AT EACH
CORNER OF CONCRETE PAD)
H3A
H1A
H2A
H3B
H2B
SWITCH H1B
X0
X1
X2
X3
G4
G
G4
G
G
G
TRANSFORMER PAD
PAD DIMENSIONS AS REQUIRED
TO PROVIDE NOT LESS THAN
6" SPACING BETWEEN
TRANSFORMER & EDGE OF
PAD ON ALL SIDES
G4
G
G
G4
TRANSFORMER
SURGE ARRESTER (TYP. FOR 3)
8" THICK CONCRETE PAD
3/4" CHAMFER ALL TOP EDGES
GRADE
GROUND BUS OR PAD; ONE IN
HV & ONE IN LV COMPARTMENT
4/0 BARE COPPER GROUNDING
CONDUCTOR
WATTHOUR DEMAND METER
(CT'S & WIRING NOT SHOWN)
#4 GROUND LEAD (TYP. FOR 3)
FACTORY INSTALLED STRAP
FOUR HOLE TERMINAL AS
REQUIRED (TYP. FOR 4)
OPENINGS SIZED TO TRANSFORMER
PRIMARY & SECONDARY
COMPARTMENTS; FILL WITH GRAVEL
AROUND CONDUIT & CABLE ENTRIES
#4 REINFORCING BARS
NOT TO EXCEED 18"
SPACING BOTH WAYS
4/0 GROUND RING (TYPICAL)
EXOTHERMIC WELD (TYPICAL)
MASTIC WRAPPED RGS
PVC END BELL (TYP.)
SWITCH
EXOTHERMIC CONNECTION
(TYPICAL)
C C
24" TYP
T Y
P
M
IN
1465 NORTHSIDE DRIVE SUITE 220B
ATLANTA, GA 30318
P:706-248-7165 www. .com
TM
PROJECT NUMBER: SIGQ212911.15
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A
D
USDA S
U
DWG. NO
DRAWN BY
SOLICITATION NO. SHEET NAME
ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED
Revisions
Agricultural Research Service
6/6/2022 3:27:12 PM C:\Users\Nicholas.Carlis\Documents\80-SIGQ212911.15_REVIT ELECTRICAL UTILITIES_nicholas.carlisYDXF8.rvt
WET LAB UTILITY
UPGRADE
E701ELECTRICAL DETAILS
CDC
NC 05/23/2022
JM BD
DC
LB
EO
SCALE: N.T.S.2
6W DUCTBANK DETAIL
SCALE: N.T.S.1
PAD MOUNTED TRANSFORMER W/GROUNDING
NO. DATE BY DESCRIPTION
1 06/06/2022 JM ISSUE FOR BIDDING AND CONSTRUCTION
SCALE: N.T.S.3
BUILDING GROUNDING DETAIL
SCALE: N.T.S.4
ATS AND GENERATOR GROUNDING DETAIL
.75/[19] DIA
MTG HOLES OFFSET
3.00/[76] TYP
FROM SIDE
SWITCHBOARD GENERAL NOTES - SERIES 2
PRODUCT DESCRIPTION & RATINGS
POWER SYSTEM DATA
480Y/277V 3PH 4W 60Hz / 3 PHASE WYE
SOLIDLY GROUNDED
SYSTEM SHORT CIRCUIT CURRENT RATING: 65kA RMS
INCOMING SECTION CABLE THROUGH THE BOTTOM
BUS SYSTEM DATA
2500A SILVER PLATED COPPER MAIN BUS
(4) .25X2.00/[6X51] CU BUS BAR PER PHASE
(2) .25X5.00/[6X127] CU BUS BAR PER NEUTRAL
(1) .25X1.25/[6X31] CU GROUND BUS
ENCLOSURE DATA
TYPE 1 FREE STANDING
EXTERIOR PAINT COLOR: ANSI 49
FRONT ACCESSIBILITY ONLY REQUIRED
HANDLING: ROLLERS & LIFTING ASSEMBLIES
ESTIMATED SHIPPING WEIGHT
822.00 LBS/372.86 kgs
CODE STANDARDS
UL DEADFRONT AND SUITABLE FOR USE AS SERVICE ENTRANCE
WHEN NOT MORE THAN SIX (6) DISCONNECTING MEANS ARE PROVIDED
RATING NAMEPLATES
ST1 - SERVICE ENTRANCE - SECTION BUS 2500A
PRODUCT INFORMATION
WIRING
ALL WIRING TO BE MACHINE TOOL WIRE TYPE
INSTRUCTION BULLETINS
REFERENCE 80043-055 FOR HANDLING, INSTALLATION.
ANCHORING, INSPECTION AND MAINTENANCE INFORMATION
PRODUCT ACCESSORIES/OPTIONS
SEISMIC QUALIFIED
24V TRIP UNIT DISPLAY POWER
LOCALLY MOUNTED AMS SWITCH
TOP VIEW - FRONT
FRONT VIEW
LEFT SIDE VIEW
FLOOR PLAN - FRONT
REQUIREMENTS FOR SEISMIC RATING
ANCHORING CONDITIONS:
TO MAINTAIN SEISMIC QUALIFICATIONS, EQUIPMENT MUST BE INSTALLED PER MANUAL (SEE GENERAL NOTES)
AND PER ANY SEISMIC ANCHORING DETAILS PROVIDED BY OTHERS. DO NOT INSTALL EQUIPMENT
BEFORE APPROVED SEISMIC ANCHORING DETAILS HAVE BEEN OBTAINED AND SITE PREPARATIONS HAVE
BEEN MADE IN ACCORDANCE WITH THE APPROVED SEISMIC ANCHORING DETAILS. ALL POST-INSTALLED ANCHORS
SHALL BE APPROVED FOR SEISMIC LOADS.
CONSIDERATION MUST BE MADE FOR CONDUIT ENTRY INTO EACH SECTION WHEN DEVELOPING MOUNTING
PAD REINFORCEMENT LOCATIONS. SEE CONDUIT ENTRY DETAILS (FLOOR PLAN) FOR DIMENSIONAL INFORMATION.
EACH SECTION MUST BE ANCHORED AT ALL LOCATIONS (REFER TO FLOOR PLAN AND MOUNTING DETAIL ABOVE). ANCHOR
BOLT MOUNTING POINTS ARE .75/[19] DIAMETER HOLES LOCATED 1.50/[38] OR 3.00/[76] ABOVE THE BASE OF THE
SECTION. USE DIMENSIONS FROM THE FLOOR PLAN TO DETERMINE MOUNTING LOCATIONS.
THE BELLEVILLE WASHER (SHOWN IN DETAIL ABOVE) USED FOR ANCHORING CONNECTIONS IS A TESTED COMPONENT AND IS
REQUIRED TO MAINTAIN POSITION RETENTION OF THE EQUIPMENT. THE SLIP CRITICAL CONNECTION PERFORMANCE OF THE
BOLTED CONNECTION WAS ESTABLISHED TO THE SHAKE TABLE TESTED SEISMIC CAPACITY OF THE EQUIPMENT AS SHOWN
ON THE EQUIPMENT SEISMIC CERTIFICATE SUPPLIED AT THE TIME OF ORDER.
CENTER OF GRAVITY CALCULATIONS:
ELEVATION CENTER OF GRAVITY: 55.00/[1387] UP FROM FLOOR
VERTICAL CENTER OF GRAVITY: USE CENTERLINE OF SECTION FROM LEFT TO RIGHT
DEPTH CENTER OF GRAVITY: USE CENTERLINE OF SECTION FROM FRONT TO REAR
MOUNTING DETAILS
BELLEVILLE WASHER
BASE CHANNEL
FLOOR
NUT
ANCHOR BOLT
(SAE GRADE 5)
SAE GRADE 5
BOLT
1/2-13 HEAVY
DUTY NUT
1-14 DIA
BELLEVILLE
WASHER
TYPICAL BASE
CHANNEL MOUNTING
HARDWARE
PM
28.5
10.5
AMS91.50
[2324]
1.50 [38]
31.00 [787]2.50
[64]
15.60 [396]
5.40 [137]
2.80 [71]
3.10 [79]
36.00 [914]
1.50 [38]
21.00 [533]24.00
[610]
91.50 [2324]
90.00 [2286]
24.00 [610]
2.94 [75]
1.47 [37]
X=HEIGHT
36.00 [914]
1465 NORTHSIDE DRIVE SUITE 220B
ATLANTA, GA 30318
P:706-248-7165 www. .com
TM
PROJECT NUMBER: SIGQ212911.15
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A
D
USDA S
U
DWG. NO
DRAWN BY
SOLICITATION NO. SHEET NAME
ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED
Revisions
Agricultural Research Service
6/6/2022 3:27:16 PM C:\Users\Nicholas.Carlis\Documents\80-SIGQ212911.15_REVIT ELECTRICAL UTILITIES_nicholas.carlisYDXF8.rvt
WET LAB UTILITY
UPGRADE
E702ELECTRICAL DETAILS
CDC
NC 05/23/2022
JM BD
DC
LB
EO
NO. DATE BY DESCRIPTION
1 06/06/2022 JM ISSUE FOR BIDDING AND CONSTRUCTION
SCALE: N.T.S.1
SWITCHBOARD DETAIL
1465 NORTHSIDE DRIVE SUITE 220B
ATLANTA, GA 30318
P:706-248-7165 www. .com
TM
PROJECT NUMBER: SIGQ212911.15
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A
D
USDA S
U
DWG. NO
DRAWN BY
SOLICITATION NO. SHEET NAME
ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED
Revisions
Agricultural Research Service
6/6/2022 3:27:24 PM C:\Users\Nicholas.Carlis\Documents\80-SIGQ212911.15_REVIT ELECTRICAL UTILITIES_nicholas.carlisYDXF8.rvt
WET LAB UTILITY
UPGRADE
E703ELECTRICAL DETAILS
05/23/2022
NO. DATE BY DESCRIPTION
1 06/06/2022 JM ISSUE FOR BIDDING AND CONSTRUCTION
SCALE: N.T.S.1
SWITCHBOARD DETAILGENERATOR DETAIL
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY USDA
DRAWN BY
CDC
NC
JM BD
BD
DC
LB
EO
| 80-SIGQ212911.15_REVIT ELECTRICAL UTILITIES_nicholas.carlisYDXF8 |
| E001 - GENERAL NOTES, SYMBOLS, & ABBREVIATIONS |
| EDS01 - ELECTRICAL DEMOLITION SITE PLAN |
| E501 - ELECTRICAL UTILITY POWER RISER |
| E601 - ELECTRICAL SCHEDULES |
| E701 - ELECTRICAL DETAILS |
| E702 - ELECTRICAL DETAILS |
| ES01 - ELECTRICAL SITE PLAN |
| E703 - ELECTRICAL DETAILS |
E601 - ELECTRICAL SCHEDULES