This document provides details for a federal solicitation seeking construction services. The U.S. Department of Agriculture Agricultural Research Service is soliciting proposals to upgrade and expand utilities and wet lab construction at its facility in Edinburg, Texas. A mandatory site visit will be held on June 29, 2022 at 10:00am CST at Building 17 on the research center campus. Contractors must register for the site visit by emailing the points of contact, Kelly Wright and David De La Paz, by June 26 with company and attendee information. The solicitation number is 12805B22R0015. Proposals are due by the date specified in the solicitation, though no due date is provided in this attachment.
View the file
Other files for this federal contract opportunity
Show all 22
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TRANSFORMER TO
BE RELOCATED
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A D
USDA S
U
DWG. NO
DRAWN BY
SOLICITATION NO. SHEET NAME
ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED
Revisions
Agricultural Research Service
1465 NORTHSIDE DRIVE SUITE 220B
ATLANTA, GA 30318
P:706-248-7165 www. .com
TM
PROJECT NUMBER:SIGQ212911.15
WET LAB
05/06/2022
NO. DATE BY DESCRIPTION
1 03/04/2022 50% DOCUMENTS
X:\Y03\2021\21007-00 USDA Wet Lab and Barns\3-Production\03-Sheets\LAB\Y03-21007-00-LAB-DM.dwgJun 15, 2022 - 3:41pm
AJH
NRS
AJH
VDA
2 04/20/2022 90% DOCUMENTS
3 05/06/2022 100% DOCUMENTS
Benchmark Information:
4 05/20/2022 ISSUE FOR BIDDING AND CONSTRUCTION
05/27/2022 ADDENDUM 1
AJH
AJH
AJH
AJH
AJH
06/16/2022 ADDENDUM 2AJH
Key Notes:
Sheet Notes:
Construction Notes:
DEMOLITION PLAN C100
06/16/20225
PROPOSED WET LAB
FFE-226.50
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A D
USDA S
U
DWG. NO
DRAWN BY
SOLICITATION NO. SHEET NAME
ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED
Revisions
Agricultural Research Service
1465 NORTHSIDE DRIVE SUITE 220B
ATLANTA, GA 30318
P:706-248-7165 www. .com
TM
PROJECT NUMBER:SIGQ212911.15
WET LAB
05/06/2022
NO. DATE BY DESCRIPTION
1 03/04/2022 50% DOCUMENTS
X:\Y03\2021\21007-00 USDA Wet Lab and Barns\3-Production\03-Sheets\LAB\Y03-21007-00-LAB-UTIL.dwgJun 15, 2022 - 3:42pm
AJH
NRS
AJH
VDA
2 04/20/2022 90% DOCUMENTS
3 05/06/2022 100% DOCUMENTS
Benchmark Information:
4 05/20/2022 ISSUE FOR BIDDING AND CONSTRUCTION
05/27/2022 ADDENDUM 1
AJH
AJH
AJH
AJH
AJH
06/16/2022 ADDENDUM 2AJH
Key Notes:
Sheet Notes:
UTILITY PLAN -
BASE BUILD
C300
General Construction Notes:
M
ATC
H
LIN
E TO
U
TILITY O
VER
ALL SH
EET
1 14" 2
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A D
USDA S
U
DWG. NO
DRAWN BY
SOLICITATION NO. SHEET NAME
ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED
Revisions
Agricultural Research Service
1465 NORTHSIDE DRIVE SUITE 220B
ATLANTA, GA 30318
P:706-248-7165 www. .com
TM
PROJECT NUMBER:SIGQ212911.15
WET LAB
05/06/2022
NO. DATE BY DESCRIPTION
1 03/04/2022 50% DOCUMENTS
X:\Y03\2021\21007-00 USDA Wet Lab and Barns\3-Production\03-Sheets\LAB\Y03-21007-00-LAB-UTIL.dwgJun 15, 2022 - 3:42pm
AJH
NRS
AJH
VDA
2 04/20/2022 90% DOCUMENTS
3 05/06/2022 100% DOCUMENTS
Benchmark Information:
4 05/20/2022 ISSUE FOR BIDDING AND CONSTRUCTION
05/27/2022 ADDENDUM 1
AJH
AJH
AJH
AJH
AJH
06/16/2022 ADDENDUM 2AJH
Key Notes:
Sheet Notes:
UTILITY PLAN -
ALTERNATE 1
C300.01
General Construction Notes:
M
ATC
H
LIN
E TO
U
TILITY O
VER
ALL SH
EET
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A D
USDA S
U
DWG. NO
DRAWN BY
SOLICITATION NO. SHEET NAME
ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED
Revisions
Agricultural Research Service
1465 NORTHSIDE DRIVE SUITE 220B
ATLANTA, GA 30318
P:706-248-7165 www. .com
TM
PROJECT NUMBER:SIGQ212911.15
WET LAB
05/06/2022
NO. DATE BY DESCRIPTION
1 03/04/2022 50% DOCUMENTS
X:\Y03\2021\21007-00 USDA Wet Lab and Barns\3-Production\03-Sheets\LAB\Y03-21007-00-LAB-UTIL.dwgJun 15, 2022 - 3:42pm
AJH
NRS
AJH
VDA
2 04/20/2022 90% DOCUMENTS
3 05/06/2022 100% DOCUMENTS
Benchmark Information:
4 05/20/2022 ISSUE FOR BIDDING AND CONSTRUCTION
05/27/2022 ADDENDUM 1
AJH
AJH
AJH
AJH
AJH
06/16/2022 ADDENDUM 2AJH
Key Notes:
Sheet Notes:
UTILITY PLAN -
ALTERNATE 2
C300.02
General Construction Notes:
M
ATC
H
LIN
E TO
U
TILITY O
VER
ALL SH
EET
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A D
USDA S
U
DWG. NO
DRAWN BY
SOLICITATION NO. SHEET NAME
ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED
Revisions
Agricultural Research Service
1465 NORTHSIDE DRIVE SUITE 220B
ATLANTA, GA 30318
P:706-248-7165 www. .com
TM
PROJECT NUMBER:SIGQ212911.15
WET LAB
05/06/2022
NO. DATE BY DESCRIPTION
1 03/04/2022 50% DOCUMENTS
X:\Y03\2021\21007-00 USDA Wet Lab and Barns\3-Production\03-Sheets\LAB\Y03-21007-00-LAB-SWPPP.dwgJun 15, 2022 - 3:42pm
AJH
NRS
AJH
VDA
2 04/20/2022 90% DOCUMENTS
3 05/06/2022 100% DOCUMENTS
Benchmark Information:
4 05/20/2022 ISSUE FOR BIDDING AND CONSTRUCTION
05/27/2022 ADDENDUM 1
AJH
AJH
AJH
AJH
AJH
06/16/2022 ADDENDUM 2AJH
LEGEND
SWPPP - BASE BUILD C400
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A D
USDA S
U
DWG. NO
DRAWN BY
SOLICITATION NO. SHEET NAME
ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED
Revisions
Agricultural Research Service
1465 NORTHSIDE DRIVE SUITE 220B
ATLANTA, GA 30318
P:706-248-7165 www. .com
TM
PROJECT NUMBER:SIGQ212911.15
WET LAB
05/06/2022
NO. DATE BY DESCRIPTION
1 03/04/2022 50% DOCUMENTS
X:\Y03\2021\21007-00 USDA Wet Lab and Barns\3-Production\03-Sheets\LAB\Y03-21007-00-LAB-SWPPP.dwgJun 15, 2022 - 3:42pm
AJH
NRS
AJH
VDA
2 04/20/2022 90% DOCUMENTS
3 05/06/2022 100% DOCUMENTS
Benchmark Information:
4 05/20/2022 ISSUE FOR BIDDING AND CONSTRUCTION
05/27/2022 ADDENDUM 1
AJH
AJH
AJH
AJH
AJH
06/16/2022 ADDENDUM 2AJH
LEGEND
SWPPP - ALTERNATE 1 C400.01
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A D
USDA S
U
DWG. NO
DRAWN BY
SOLICITATION NO. SHEET NAME
ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED
Revisions
Agricultural Research Service
1465 NORTHSIDE DRIVE SUITE 220B
ATLANTA, GA 30318
P:706-248-7165 www. .com
TM
PROJECT NUMBER:SIGQ212911.15
WET LAB
05/06/2022
NO. DATE BY DESCRIPTION
1 03/04/2022 50% DOCUMENTS
X:\Y03\2021\21007-00 USDA Wet Lab and Barns\3-Production\03-Sheets\LAB\Y03-21007-00-LAB-SWPPP.dwgJun 15, 2022 - 3:42pm
AJH
NRS
AJH
VDA
2 04/20/2022 90% DOCUMENTS
3 05/06/2022 100% DOCUMENTS
Benchmark Information:
4 05/20/2022 ISSUE FOR BIDDING AND CONSTRUCTION
05/27/2022 ADDENDUM 1
AJH
AJH
AJH
AJH
AJH
06/16/2022 ADDENDUM 2AJH
LEGEND
SWPPP - ALTERNATE 2 C400.02
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A D
USDA S
U
DWG. NO
DRAWN BY
SOLICITATION NO. SHEET NAME
ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED
Revisions
Agricultural Research Service
1465 NORTHSIDE DRIVE SUITE 220B
ATLANTA, GA 30318
P:706-248-7165 www. .com
TM
PROJECT NUMBER:SIGQ212911.15
WET LAB
05/06/2022
NO. DATE BY DESCRIPTION
1 03/04/2022 50% DOCUMENTS
X:\Y03\2021\21007-00 USDA Wet Lab and Barns\3-Production\03-Sheets\LAB\Y03-21007-00-LAB-SWPPP.dwgJun 15, 2022 - 3:42pm
AJH
NRS
AJH
VDA
2 04/20/2022 90% DOCUMENTS
3 05/06/2022 100% DOCUMENTS
Benchmark Information:
4 05/20/2022 ISSUE FOR BIDDING AND CONSTRUCTION
05/27/2022 ADDENDUM 1
AJH
AJH
AJH
AJH
AJH
06/16/2022 ADDENDUM 2AJH
LEGEND
SWPPP C401
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A D
USDA S
U
DWG. NO
DRAWN BY
SOLICITATION NO. SHEET NAME
ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED
Revisions
Agricultural Research Service
1465 NORTHSIDE DRIVE SUITE 220B
ATLANTA, GA 30318
P:706-248-7165 www. .com
TM
PROJECT NUMBER:SIGQ212911.15
WET LAB
05/06/2022
NO. DATE BY DESCRIPTION
1 03/04/2022 50% DOCUMENTS
X:\Y03\2021\21007-00 USDA Wet Lab and Barns\3-Production\03-Sheets\LAB\Y03-21007-00-LAB-GN.dwgJun 15, 2022 - 3:42pm
AJH
NRS
AJH
VDA
2 04/20/2022 90% DOCUMENTS
3 05/06/2022 100% DOCUMENTS
4 05/20/2022 ISSUE FOR BIDDING AND CONSTRUCTION
05/27/2022 ADDENDUM 1
AJH
AJH
AJH
AJH
AJH
06/16/2022 ADDENDUM 2AJH
A
A
NOT TO SCALE
RO
RO
RO
RO
RO
BUSINESS
A201.1
A201.1
A201.1A201.2
A201.2
A201.2
BUSINESS
A201.1
A201.1
A201.1
A201.1
A201.2
A201.2
A201.2
BUSINESS
A201.1
A201.1
A201.1
A201.1
A201.2
A201.2
A201.2
6/16/2022 1:46:30 PM C:\EYP_Temp\Revit_2020\2021060.01_Edinburg Wet Lab-add-alt_jbaughmanVUZ7P.rvt
NO. DATE BY DESCRIPTION
A201.1
A201.1
A201.1
A201.1
6/16/2022 1:55:59 PM C:\EYP_Temp\Revit_2020\2021060.01_Edinburg Wet Lab-add-alt_jbaughmanVUZ7P.rvt
REFLECTED CEILING PLAN - LEVEL 01 ADD ALT. #1
A201.2
A201.2
A201.2
A201.2
6/16/2022 1:50:21 PM C:\EYP_Temp\Revit_2020\2021060.01_Edinburg Wet Lab-add-alt_jbaughmanVUZ7P.rvt
REFLECTED CEILING PLAN - LEVEL 01 ADD ALT. #2
6/16/2022 1:59:47 PM C:\EYP_Temp\Revit_2020\2021060.01_Edinburg Wet Lab-add-alt_jbaughmanVUZ7P.rvt
SHEET KEY NOTES#
1. WALL MOUNTED THERMOSTAT. COORDINATE LOCATION WITH
OTHER WALL MOUNTED COMPONENTS. MOUNT THERMOSTAT AT
4'-0" AFF (TYPICAL).
2. REFRIGERANT PIPING SIZING AND CONNECTION SHALL BE AS PER
MANUFACTURER GUIDELINES (TYPICAL).
3. 1-1/4" PVC CONDENSATE DRAIN PIPING. RUN PIPING AT 1/8" SLOPE
PER FOOT.
4. 12" DIAMETER FUME HOOD EXHAUST AIR DUCTWORK UP.
5. 14"x12" GENERAL EXHAUST AIR DUCTWORK UP.
6. 16"x12" SUPPLY AIR DUCTWORK UP.
7. STRUCTURAL PLATFORM WITH GAURD RAIL AND STAIR ENTRY,
REFER TO STRUCTURAL DRAWINGS FOR DETAILS.
8. VARIABLE FREQUENCY DRIVE (VFD) SERVING GEF-1, MOUNT ON A
UNISTRUT CHANNEL.
9. 28"x12" GENERAL EXHAUST AIR DUCTWORK UP.
10. 42"x12" SUPPLY AIR DUCTWORK UP.
11. CONTRACTOR TO PROVIDE OPEN SITE DRAIN WITH BALL-FLOAT
BACKWATER VALVE AND WITH MIN 4" HIGH HUB ADAPTER. DRAIN
PIPING TO BE 2" SDR26, REFER CIVIL DRAWINGS FOR
CONTINUATION.
12. CONTRACTOR TO PROVIDE DRAIN OPENING WITH STAINLESS
STEEL INSECT AND BIRD SCREEN.
5 6 7 8
11 12 131415
MEN. RR
WOMEN RR
23ENTRY/ VESTIBULE
GROUP OFFICE
GEN. STORAGE
OFFICE
ENTRY EQM
CONF RM
CHEM STORAGE
EQM STORAGE
FUME HOOD
CORRIDOR
OPEN WET LAB
OFFICE
ELEC. RM.
ENTRY VEST.
JAN. RM.
M401
M402
"x
CU-1
OUTDOOR
AIR
VFD
"Ø G
E X
24"Ø GEX
CONCRETE
EQUIPMENT PAD
M401
M401
M401
14"x12" GEX12"x10"8"x10"
6"x10"
6"x10"
16"x12" SA 8"x10"8"x10"
28"x8" 28"x8"
28"x12" 20"x10"
10"x10"
"x
" 1
"x
6"Ø 6"Ø
8"x10"
8"x8"
"x
" 8"x8"
6"Ø6"x12"
12"x8"
6"x12" 6"Ø10"Ø6"Ø8"x10"
"Ø
6"x8"6"Ø
10"x10"
6"x6"
"x
"Ø
6"Ø
"x
"Ø
"x
12"Ø 12"Ø
"Ø
"Ø
"x
"x
"Ø
"x
"x
10"Ø
10"Ø
10"Ø 10"Ø
42"x12" SA 28"x12"
6"Ø 6"x8"
"Ø10"Ø
"Ø
"x
12"Ø
"Ø
18"x12"
"x
"x
10"Ø
10"Ø
10"Ø
"x
"x
8"x6"
8"x6"
8"x6"
28"x12"
"x
12"x10"10"x8"
"x
10"x8"
RD-2
RD-2
RHCAV-1-1
EXCAV-1-8
RHCAV-1-4
RHCAV-1-7
RHCAV-1-3RHCAV-1-2
RHCAV-1-12RHCAV-1-10
RHCAV-1-5
RHCAV-1-8
RHCAV-1-11
RHCAV-1-9
RHCAV-1-6
EXCAV-1-3
EXCAV-1-2
EXCAV-1-1
EXCAV-1-7
EXCAV-1-6
EXCAV-1-5
CD-1
CD-1
CD-4
CD-4
RD-5
RD-2
CD-2
RD-2
CD-3
CD-3
RD-3
CD-2
CD-1
RD-2
CD-1
RD-1
SG-1
SG-1
EG-1
EG-1
LFD-1
LFD-1
LFD-1
LFD-1
LFD-1
LFD-1
LFD-1
LFD-1
LFD-1
CD-4
CD-4
375CD-1
CD-1
RD-3
CD-1
100 RD-3
CD-4
CD-1
CD-4
LFD-2
LFD-2
RD-7
RD-7
M402
MECH.
T T
TTT
T
T
T T
TT
T
FUME HOOD
(FH-2)
FUME HOOD
(FH-1)
8"Ø
AHU-1
12"x10"
6"Ø
24"x12"
28"x12" GEX
12"x8"
"x
8"x12"
EXCAV-1-4
RHCAV-1-7
RHCAV-1-1
RHCAV-1-5
RHCAV-1-4
RHCAV-1-3
RHCAV-1-2
RHCAV-1-9
RHCAV-1-11
RHCAV-1-6
RHCAV-1-8
RHCAV-1-10
RHCAV-1-12
VD
VD
VD
VD
VD
VD
VD
VD
VD
VD
VD
VDVD
VD
VD
VDVDVD
VD
VD
VD
VD
VD VD
VD
VD VD
VD
VD
VD
VD
VD
VD VD
VD
VD
VD
VD
VD
VD VD
VD
VD
VD
VD
VD
VD
VDVD
LFD-1
VFD
SD
SD
MD
1 1/4"
COIL PULL
CLEARANCE
GENERAL EXHAUST
DUCTWORK UP
SUPPLY AIR
DUCTWORK UP
REFRIGERANT
PIPING
SMOKE
DETECTOR (TYP)
CONDENSATE
PIPING
16"x38" SA
34"x14" GEX
VD
28"x12"
"x
8"x8"
24"Ø GEX
24"Ø GEX
VD
VD
MD
MD
V F
D
GEX-1A
GEF-1B
ELECTRIC
HEATER PANEL
DUCT SUPPORT
(TYPICAL)
10"x12"
LFD-2
LFD-2
VD
VD
COIL PULL
CLEARANCE
"x
8"x8"
1465 NORTHSIDE DRIVE SUITE 220B
ATLANTA, GA 30318
P:706-248-7165 www. .com
TM
PROJECT NUMBER: SIGQ212911.15
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A
D
USDA S
U
DWG. NO
DRAWN BY
SOLICITATION NO. SHEET NAME
ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED
Revisions
Agricultural Research Service
6/15/2022 11:21:57 AM C:\Users\gowtham.sl\Documents\SIGQ212911.15_R20_Mechanical_gowtham.sl.rvt
WET LAB
M101
LEVEL 1 MECHANICAL PLAN
BASE BID
JM
GSL 05/06/2022
JM BD
BD
DC
GSL
NO. DATE BY DESCRIPTION
1 03/04/2022 JM 50% DOCUMENTS
2 04/20/2022 JM 90% DOCUMENTS
3 05/06/2022 JM 100% DOCUMENTS
4 05/20/2022 JM ISSUE FOR BIDDING AND CONSTRUCTION
5 06/16/2022 JM ADDENDUM 1
8' 16'4'0 1/4" = 1'-0"M101
1 LEVEL 1 MECHANICAL PLAN BASE BID
5 6 7 8
11 12 131415
26"x12" SA 18"x12"16"x12"14"x12"
OUTDOOR
AIR
VFD
CONCRETE
EQUIPMENT PAD
26"x12" GEX20"x12" 22"x12"
18"x12"
18"x12"16"x12"
RHCAV-1-1
EXCAV-1-8
RHCAV-1-4
RHCAV-1-7
RHCAV-1-3RHCAV-1-2
RHCAV-1-12RHCAV-1-10
RHCAV-1-5
RHCAV-1-8
RHCAV-1-11
RHCAV-1-9
RHCAV-1-6
EXCAV-1-3
EXCAV-1-2
EXCAV-1-1
EXCAV-1-7
EXCAV-1-6
EXCAV-1-5
RHCAV-1-14
RHCAV-1-13
EXCAV-1-9
EXCAV-1-10
M402
RD-2
RD-2
CD-1
CD-1
CD-4
CD-4
RD-5
RD-2
CD-2
RD-2
CD-3
CD-3
RD-3
CD-2
CD-1
RD-2
CD-1
RD-1
SG-1
SG-1
EG-1
EG-1
LFD-1
LFD-1
LFD-1
LFD-1
LFD-1
LFD-1
LFD-1
LFD-1
LFD-1
CD-4
CD-4
375CD-1
CD-1
RD-3
CD-1
100 RD-3
CD-4
CD-1
CD-4
RD-7
RD-7
"x
10"x10"
"x
" 1
"x
6"Ø 6"Ø
12"x8" 8"x10"
8"x8"
"x
8"x8"
6"Ø6"x12"6"x12" 6"Ø10"Ø6"Ø8"x10"
"Ø
6"x8"6"Ø
10"x10"
6"x6"
"x
28"x8" 28"x8"
28"x12" 20"x10"
"Ø
6"Ø
"x
"Ø
"x
12"Ø 12"Ø
"Ø
"Ø
"x
"x
"Ø
"x
"x
10"Ø 10"Ø
10"Ø 10"Ø
42"x12" SA 28"x12"
6"Ø 6"x8"
"Ø10"Ø
"Ø
"x
12"Ø
"Ø
18"x12"
"x
"x
10"Ø
10"Ø
10"Ø
12"x10"
"x
"x
8"x6"
8"x6"
8"x6"
28"x12"
"x
12"x10"10"x8"
"x
10"x8"
LFD-1
LFD-1
LFD-1
RD-7
"x
"x
"x
CD-3
CD-3
RD-5
"x
"x
"x
"x
"x
"Ø
8"Ø
MEN. RR
WOMEN RR
ENTRY/ VESTIBULE
GROUP OFFICE
GEN. STORAGE
OFFICE
ENTRY EQM
CONF RM
CHEM STORAGE
EQM STORAGE
FUME HOOD
CORRIDOR
OPEN WET LAB
OFFICE
ELEC. RM.
ENTRY VEST.
JAN. RM.
MECH.
FIELD LABORATORY
FIELD LAB OFFICE
T T
TTT
T
T
T
T
T T
TT
T
16"x34" GEX
38"x18" SA
8"Ø
"Ø G
E X
26"Ø GEX
AHU-1
26"Ø GEX
CU-1
LFD-1
22"x12"
18"x12"16"x12"14"x12"
10"Ø
10"Ø
RHCAV-1-7
RHCAV-1-1
RHCAV-1-5
RHCAV-1-4
RHCAV-1-3
RHCAV-1-2
RHCAV-1-9
RHCAV-1-11
RHCAV-1-6
RHCAV-1-8
RHCAV-1-10
RHCAV-1-12
R H
C A
V -1
-1
RHCAV-1-14
12"x10"
"x
VD
VD
VD
VD
VD
VD
VD
VD
VD
VD
VD
VD
VD
VD
VDVDVD
VD
VD
VD
VD
VD VD
VD
VD VD
VD
VD
VD
VD
VD
VD VD
VD
VD
VD
VD
VD
VD VD
VD
VD
VD
VD
VD
VD
VDVD
VD
VD
VD
VD
VD
VD
VD
EXCAV-1-4
SD
SD
MD
1 1/4"
GENERAL EXHAUST
DUCTWORK UP
SUPPLY AIR
DUCTWORK UP
REFRIGERANT
PIPING
SMOKE
DETECTOR (TYP)
CONDENSATE
PIPING
VD
8"x12"
28"x12" GEX
24"x12"
28"x12"
"x
10"Ø
12"x8"
M402
8"x8"
VFD
V F
D
GEX-1A
GEF-1B
VD
VD
MD
MD
COIL PULL
CLEARANCE
ELECTRIC
HEATER PANEL
DUCT SUPPORT
(TYPICAL)
LFD-2
LFD-2
LFD-2
LFD-2
VD
VD
10"x12"
FUME HOOD
(FH-2)
FUME HOOD
(FH-1)
COIL PULL
CLEARANCE
24"x12"
8"x8"
1. WALL MOUNTED THERMOSTAT. COORDINATE LOCATION WITH
OTHER WALL MOUNTED COMPONENTS. MOUNT THERMOSTAT AT
4'-0" AFF (TYPICAL).
2. REFRIGERANT PIPING SIZING AND CONNECTION SHALL BE AS PER
MANUFACTURER GUIDELINES (TYPICAL).
3. 1-1/4" PVC CONDENSATE DRAIN PIPING. RUN PIPING AT 1/8" SLOPE
PER FOOT.
4. 12" DIAMETER FUME HOOD EXHAUST AIR DUCTWORK UP.
5. 26"x12" GENERAL EXHAUST AIR DUCTWORK UP.
6. 26"x12" SUPPLY AIR DUCTWORK UP.
7. STRUCTURAL PLATFORM WITH GAURD RAIL AND STAIR ENTRY,
REFER TO STRUCTURAL DRAWINGS FOR DETAILS.
8. VARIABLE FREQUENCY DRIVE (VFD) SERVING GEF-1, MOUNT ON A
UNISTRUT CHANNEL.
9. 28"x12" GENERAL EXHAUST AIR DUCTWORK UP.
10. 42"x12" SUPPLY AIR DUCTWORK UP.
11. CONTRACTOR TO PROVIDE OPEN SITE DRAIN WITH BALL-FLOAT
BACKWATER VALVE AND WITH MIN 4" HIGH HUB ADAPTER. DRAIN
PIPING TO BE 2" SDR26, REFER CIVIL DRAWINGS FOR
CONTINUATION.
12. CONTRACTOR TO PROVIDE DRAIN OPENING WITH STAINLESS
STEEL INSECT AND BIRD SCREEN.
1465 NORTHSIDE DRIVE SUITE 220B
ATLANTA, GA 30318
P:706-248-7165 www. .com
TM
PROJECT NUMBER: SIGQ212911.15
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A
D
USDA S
U
DWG. NO
DRAWN BY
SOLICITATION NO. SHEET NAME
ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED
Revisions
Agricultural Research Service
6/15/2022 11:22:00 AM C:\Users\gowtham.sl\Documents\SIGQ212911.15_R20_Mechanical_gowtham.sl.rvt
WET LAB
M101.1
LEVEL 1 MECHANICAL PLAN
ADD ALT. #1
JM
GSL 05/06/2022
JM BD
BD
DC
GSL
NO. DATE BY DESCRIPTION
1 03/04/2022 JM 50% DOCUMENTS
2 04/20/2022 JM 90% DOCUMENTS
3 05/06/2022 JM 100% DOCUMENTS
4 05/20/2022 JM ISSUE FOR BIDDING AND CONSTRUCTION
5 06/16/2022 JM ADDENDUM 1
8' 16'4'0 1/4" = 1'-0"M101.1
1 LEVEL 1 MECHANICAL PLAN ADD ALT. #1
11 12 131415
30"x12" SA24"x12"20"x12"
30"x12" GEX
42"x12" SA
28"x12" GEX
28"x12"
CU-1
OUTDOOR
AIR
VFD
GENERAL EXHAUST
DUCTWORK UP
SUPPLY AIR
DUCTWORK UP
CONCRETE
EQUIPMENT PAD
RHCAV-1-1
RHCAV-1-7
RHCAV-1-4
RHCAV-1-3RHCAV-1-2
RHCAV-1-13
RHCAV-1-14
RHCAV-1-12
RHCAV-1-5
RHCAV-1-10
RHCAV-1-8
RHCAV-1-11
RHCAV-1-9
RHCAV-1-6
EXCAV-1-8
EXCAV-1-3
EXCAV-1-2
EXCAV-1-1
EXCAV-19
EXCAV-10
EXCAV-1-7
EXCAV-1-6
EXCAV-1-5
M402
"x
6"Ø 6"Ø
"x
"x
6"Ø6"x12"6"x12"
8"x10"
8"x8"
8"x8"
26"x12"24"x12"
22"x12"
22"x12"20"x12"20"x12"
"x
12"x12"
"x
"x
10"Ø
10"Ø
"x
"10"Ø
14"x12"
8"Ø12"x12"
"Ø
10"Ø
10"Ø
6"Ø10"Ø
"x
12"x8"
6"Ø8"x10"
"Ø
6"x8"6"Ø
10"x10"
"x
6"x6"
6"Ø
"Ø
"x
"Ø
"Ø
"x
"x
8"x6"
"x
12"Ø 12"Ø
"Ø
"Ø
"x
10"Ø
10"Ø 10"Ø
10"Ø1
"x
6"Ø 6"x8"
"Ø
"x
"x
"10"Ø
10"Ø
10"Ø
"Ø
"x
12"Ø
"Ø
12"Ø
10"Ø18"x12"
12"x10"
"x
"x
8"x6"
"x
28"x12" 20"x10"
28"x8"28"x8"
"x
12"x10"10"x8"
"x
8"x8"
RD-2
RD-2
CD-1
CD-1
MEN. RR
WOMEN RR
ENTRY/ VESTIBULE
GROUP OFFICE
FIELD LAB OFFICE
GEN. STORAGE
OFFICE
ENTRY EQM
CONF RM
CHEM STORAGE
31EQM STORAGE
FUME HOOD
CORRIDOR
OPEN WET LAB
OFFICE
FIELD LABORATORY
ELEC. RM.
ENTRY VEST.
JAN. RM.
MECH.
RD-2
CD-2
RD-2
CD-3
RD-3
CD-3
CD-2
CD-1
RD-2
CD-1
R D
-1
CD-3
CD-3
RD-5
CD-3
LFD-1
LFD-1
LFD-1
LFD-1
LFD-1
RD-7
CD-4
CD-4
RD-5
CD-4
375CD-1
CD-4
CD-4
CD-1
CD-4
SG-1
EG-1
EG-1
SG-1
LFD-1
LFD-1
LFD-1
LFD-1
LFD-1
LFD-1
LFD-1
LFD-1
LFD-1
RD-3
CD-1
CD-1
100 RD-3
RD-7
RD-7
T T
TTT
T
T
T
T
T T
TT
T
16"x38" GEX
40"x18" SA
8"Ø
"Ø G
E X
28"Ø GEX
AHU-1
28"Ø GEX
LFD-1
26"x12"
"x
22"x12" 22"x12" 24"x12"
10"Ø
"x
20"x12"
24"x12"
RHCAV-1-7
RHCAV-1-1
RHCAV-1-5
RHCAV-1-4
RHCAV-1-3
R H
C A
V -1
-2
RHCAV-1-9
RHCAV-1-11
RHCAV-1-6
RHCAV-1-8
RHCAV-1-10
RHCAV-1-12
R H
C A
V -1
-1
RHCAV-1-14
FD
VD
VD
VD
VD
VD
VD
VD
VD
VD
VD
VD
VDVD
VD
VD
VDVDVD
VD
VD
VD
VD
VD VD
VD
VD VD
VD
VD
VD
VD
VD
VD VD
VD
VD
VD
VD
VD
VD VD
VD
VD
VD
VD
VD
VD
VDVD
VD
VD
VD
VD
VD
VD
VD
VD
VD
VD
EXCAV-1-4
12"x8"
SD
SD
MD
1 1/4"
REFRIGERANT
PIPING
SMOKE
DETECTOR (TYP)
CONDENSATE
PIPING
VD
8"x12"
M402
8"x8"
28"Ø GEX
VFD
V F
D
GEX-1A
GEF-1B
VD
VD
MD
MD
COIL PULL
CLEARANCE
ELECTRIC
HEATER PANEL
DUCT SUPPORT
(TYPICAL)
LFD-2
LFD-2
LFD-2
LFD-2
FUME HOOD
(FH-2)
FUME HOOD
(FH-1)
COIL PULL
CLEARANCE
24"x12"
VD
VD
1. WALL MOUNTED THERMOSTAT. COORDINATE LOCATION WITH
OTHER WALL MOUNTED COMPONENTS. MOUNT THERMOSTAT AT
4'-0" AFF (TYPICAL).
2. REFRIGERANT PIPING SIZING AND CONNECTION SHALL BE AS PER
MANUFACTURER GUIDELINES (TYPICAL).
3. 1-1/4" PVC CONDENSATE DRAIN PIPING. RUN PIPING AT 1/8" SLOPE
PER FOOT.
4. 12" DIAMETER FUME HOOD EXHAUST AIR DUCTWORK UP.
5. 30"x12" GENERAL EXHAUST AIR DUCTWORK UP.
6. 30"x12" SUPPLY AIR DUCTWORK UP.
7. STRUCTURAL PLATFORM WITH GAURD RAIL AND STAIR ENTRY,
REFER TO STRUCTURAL DRAWINGS FOR DETAILS.
8. VARIABLE FREQUENCY DRIVE (VFD) SERVING GEF-1, MOUNT ON A
UNISTRUT CHANNEL.
9. 28"x12" GENERAL EXHAUST AIR DUCTWORK UP.
10. 42"x12" SUPPLY AIR DUCTWORK UP.
11. CONTRACTOR TO PROVIDE OPEN SITE DRAIN WITH BALL-FLOAT
BACKWATER VALVE AND WITH MIN 4" HIGH HUB ADAPTER. DRAIN
PIPING TO BE 2" SDR26, REFER CIVIL DRAWINGS FOR
CONTINUATION.
12. CONTRACTOR TO PROVIDE DRAIN OPENING WITH STAINLESS
STEEL INSECT AND BIRD SCREEN.
1465 NORTHSIDE DRIVE SUITE 220B
ATLANTA, GA 30318
P:706-248-7165 www. .com
TM
PROJECT NUMBER: SIGQ212911.15
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A
D
USDA S
U
DWG. NO
DRAWN BY
SOLICITATION NO. SHEET NAME
ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED
Revisions
Agricultural Research Service
6/15/2022 11:22:03 AM C:\Users\gowtham.sl\Documents\SIGQ212911.15_R20_Mechanical_gowtham.sl.rvt
WET LAB
M101.2
LEVEL 1 MECHANICAL PLAN
ADD ALT. #2
JM
GSL 05/06/2022
JM BD
BD
DC
GSL
NO. DATE BY DESCRIPTION
1 03/04/2022 JM 50% DOCUMENTS
2 04/20/2022 JM 90% DOCUMENTS
3 05/06/2022 JM 100% DOCUMENTS
4 05/20/2022 JM ISSUE FOR BIDDING AND CONSTRUCTION
5 06/16/2022 JM ADDENDUM 1
8' 16'4'0 1/4" = 1'-0"M101.2
1 LEVEL 1 MECHANICAL PLAN ADD ALT. #2
DS
(NOTE : ALL ABBREVIATIONS MAY NOT APPEAR ON THE DRAWINGS)
LIGHT FIXTURE SUBSCRIPT DETAIL:
a HP-2
EM A
LIGHT FIXTURES MAY BE INDICATED WITH THE FOLLOWING SUBSCRIPTS:
EM : LIGHT FIXTURE ON EMERGENCY CIRCUIT
A : UPPER CASE SUBSCRIPT INDICATES LIGHT FIXTURE IDENTIFICATION TAG
a : LOWER CASE SUBSCRIPT INDICATES LIGHTING ZONE IDENTIFICATION
HP-2 : PANEL NAME AND CIRCUIT NUMBER SERVING LIGHT FIXTURE
S
PANEL-XX
AA
F
S
EL
S
D
15cd
AV 15cdAV
15cd
V 15cdV
FACP
J J J
M
MS
a
K
MS
VS VS
T a
CR
TV
F
MWIRE SIZE
(AWG TYP.)
LENGTH (FEET) VOLTAGE (V)
1200-66
0-102 120
20 #12
20 #10
AMPACITY (A)
WALL MOUNTED FIRE ALARM SYSTEM MANUAL PULL STATION
AT 48" AFF
CEILING/WALL MOUNTED FIRE ALARM SMOKE DETECTOR,
DEVICES MAY HAVE THE FOLLOWING SUBSCRIPTS:
EL
: DEVICE DEDICATED FOR ELEVATOR RECALL
FUNCTION
FIRE ALARM DUCT SMOKE DETECTOR
CEILING/WALL MOUNTED FIRE ALARM COMBINATION AUDIO (USDA
SPEAKER )/VISUAL DEVICE, ADA COMPLIANT NUMBER
MOUNTING HEIGHT FROM 80" UP TO A MAXIMUM OF 96" AFF
CEILING/WALL MOUNTED FIRE ALARM VISUAL DEVICE (STROBE),
ADA COMPLIANT NUMBER DENOTES CANDELA INTENSITY RATING,
TO A MAXIMUM
CEILING/WALL MOUNTED FIRE ALARM AUDIO ( HORN )
DEVICE, MOUNTING HEIGHT NOT LESS THAN 90" AFF AND 6"
FIRE ALARM CONTROL PANEL
FIRE ALARM SYMBOL LIST
A AMPERE
ADA AMERICANS WITH DISABILITIES ACT
AFF ABOVE FINISHED FLOOR
AL ALUMINUM
AWG AMERICAN WIRE GAUGE
C CONDUIT
CB CIRCUIT BREAKER
CU COPPER
D EXISTING TO BE DEMOLISHED
DISC. SW. DISCONNECT SWITCH
DWG DRAWING
E, EX EXISTING TO REMAIN
EM DEVICE ON EMERGENCY CIRCUIT
EMT ELECTRICAL METALLIC TUBING
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FATC FIRE ALARM TERMINAL CABINET
FASP FIRE ALARM SMOKE PURGE PANEL
FLA FULL LOAD AMPS
G GROUND
GFI GROUND FAULT INTERRUPTER
GRS GALVANIZED RESISTIVE CONDUIT
HP HORSE POWER
IG ISOLATED GROUND
KVA KILOVOLT-AMPS
KW KILOWATT
MCB MAIN CIRCUIT BREAKER
MLO MAIN LUGS ONLY
MDP MAIN DISTRIBUTION PANEL
N NEW
NEC NATIONAL ELECTRICAL CODE
NFSS NON FUSED SAFETY SWITCH
NL NIGHT LIGHT FIXTURE
NTS NOT TO SCALE
P POLE
PH, ∅ PHASE
PNL PANEL
R RELOCATED AT NEW LOCATION
RR REMOVE AND RELOCATE
S/N SOLID NEUTRAL
SWBD SWITCHBOARD
T, XFMR TRANSFORMER
TYP. TYPICAL
UON UNLESS OTHERWISE NOTED
V VOLTS
W WATTS
WP WEATHERPROOF
T
(NOTE : ALL ABBREVIATIONS MAY NOT APPEAR ON
THE DRAWINGS)
SUBSCRIPTS
RECEPTACLE OUTLETS AND JUNCTION BOX DEVICES MAY BE INDICATED
WITH THE FOLLOWING SUBSCRIPTS:
EM : RECEPTACLE ON EMERGENCY POWER
GFI : GROUND FAULT INTERRUPTER
WP : WEATHER PROOF OUTLET WITH PROTECTIVE IN-USE COVER
MD : MOTORIZED DAMPER
EM
PT
PT
120V BRANCH CIRCUIT WIRING CONDUCTOR SIZE
DEPENDING ON BRANCH CIRCUIT RUN LENGTH FROM PANELBOARD TO THE LAST DEVICE ON THE
BRANCH CIRCUIT, THE CONTRACTOR SHALL INCREASE THE BRANCH CIRCUIT WIRE SIZE AS PER THE
TABLE BELOW.
MAXIMUM #10 WIRE SHALL BE USED FOR GENERAL RECEPTACLE CIRCUIT WIRING.
BELOW FINISHED CEILING
MINIMUM 15cd, MOUNTING HEIGHT FROM 80" UP
OF 96" AFF
DENOTES CANDELA INTENSITY RATING, MINIMUM 15cd, EXIT SIGN LIGHTING FIXTURES ON EMERGENCY LIGHTING CIRCUIT
TYPICAL INTERIOR LIGHTING FIXTURES
TYPICAL INTERIOR LIGHTING FIXTURES ON EMERGENCY LIGHTING
CIRCUIT, FIXTURES MAY HAVE THE FOLLOWING SUBSCRIPTS:
EM : EMERGENCY
NL : NIGHT LIGHT
WALL-MOUNTED DUPLEX OR QUAD RECEPTACLE, 20A, 125V,
NEMA 5-20R
# : INDICATES THE TOTAL NUMBER OF RECEPTACLE.
USB: USB CHARGER
WALL/FLOOR MOUNTED SPECIAL PURPOSE OUTLET.
COORDINATE NEMA CONFIGURATION WITH EQUIPMENT VENDOR
WALL-MOUNTED ISOLATED GROUND DUPLEX OR QUAD
RECEPTACLE (ORANGE COLOR) 20A, 125V, NEMA 5-20R
WALL-MOUNTED ABOVE COUNTER DUPLEX OR QUAD
RECEPTACLE, 20A, 125V, NEMA 5-20R
FLUSH FLOOR MOUNTED ADA COMPLIANT DUPLEX /
QUADRUPLEX NEMA 5-20R RECEPTACLE, 20A, 125V OUTLET,
COORDINATE FINISH SPECIFICATION AND EXACT LOCATION WITH
ARCHITECT, OUTLETS MAY HAVE THE FOLLOWING SUBSCRIPTS:
PT : POKE-THRU
FB : FLOOR BOX
FLUSH MOUNTED ADA COMPLIANT COMBINATION
DUPLEX/QUADRUPLEX POWER AND TELE-DATA-AV OUTLET.
REFER TO TECHNOLOGY PATHWAY DRAWINGS FOR TELE-DATA-AV
OUTLET REQUIREMENTS. COORDINATE FINISH, SPECIFICATION
AND EXACT LOCATION WITH ARCHITECT AND COMMUNICATION
VENDOR, OUTLETS MAY HAVE THE FOLLOWING
SUBSCRIPTS:
PT : POKE-THRU
FB : FLOOR BOX
RECESSED CEILING MOUNTED DUPLEX OR QUADRUPLEX NEMA
5-20R RECEPTACLE, 20A, 125V
WALL-MOUNTED DUPLEX OR QUADRUPLEX TAMPER PROOF
RECEPTACLE, 20A, 125V, NEMA 5-20R
WALL/FLOOR/CEILING MOUNTED COMBINATION
TELEPHONE/DATA OUTLET, OUTLETS MAY HAVE THE FOLLOWING
SUBSCRIPTS:
F : TWO WAY COMMUNICATION CALL STATION
WALL MOUNTED TELEPHONE OUTLET
WALL/FLOOR/CEILING MOUNTED DATA OUTLET
LOW VOLTAGE SINGLE POLE TOGGLE SWITCH, SWITCHES MAY
HAVE THE FOLLOWING SUBSCRIPTS:
a : LOWER CASE SUBSCRIPT INDICATES LIGHTING ZONE
IDENTIFICATION
LOW VOLTAGE 3 - WAY SWITCH
DIMMER SWITCH RATED FOR 2000 WATTS, PROVIDE NECESSARY
MODULES FOR LED LAMP SOURCE
LOW VOLTAGE KEY OPERATED SWITCH
LOW VOLTAGE TIMER SWITCH WITH HOLD-ON OPTION
MOTOR RATED SWITCH WITH THERMAL OVERLOAD CURRENT
PROTECTION, MOUNTED @ 48" AFF OR UNIT MOUNTED
LOW VOLTAGE SINGLE POLE SWITCH
LOW VOLTAGE 2 BUTTON SWITCH WITH RAISE-LOWER.
LOW VOLTAGE 3 BUTTON SWITCH WITH RAISE-LOWER.
WALL/CEILING MOUNTED LOW VOLTAGE OCCUPANCY SENSOR
SWITCH CONFIGURED AS AUTO-ON, AUTO OFF, CONFIGURE TIME-
OUT SETTING FOR 15 MINUTES UNLESS OTHERWISE
NOTED, DEVICES MAY HAVE THE FOLLOWING SUBSCRIPTS:
2 : DUAL SWITCH
D : DIMMER SWITCH
a,b : LIGHTING ZONE(S) CONTROLLED BY SENSOR
WALL/CEILING MOUNTED LOW VOLTAGE VACANCY SENSOR
SWITCH CONFIGURED AS MANUAL ON, AUTO OFF, CONFIGURE
TIME-OUT SETTING FOR 15 MINUTES UNLESS
OTHERWISE NOTED, DEVICES MAY HAVE THE FOLLOWING
SUBSCRIPTS:
2 : DUAL SWITCH
D : DIMMER SWITCH
a,b : LIGHTING ZONE(S) CONTROLLED BY SENSOR
LOW VOLTAGE CEILING MOUNTED DAYLIGHT SENSOR, DEVICES
MAY HAVE THE FOLLOWING SUBSCRIPTS:
a : LOWER CASE SUBSCRIPT INDICATES LIGHTING ZONE
IDENTIFICATION
WALL/CEILING/FLOOR MOUNTED JUNCTION BOX
NON-FUSIBLE DISCONNECT SWITCH
FUSIBLE DISCONNECT SWITCH
COMBINATION STARTER DISCONNECT SWITCH
MOTOR
DRY TYPE TRANSFORMER
120/208V ELECTRICAL PANEL
480/277V ELECTRICAL PANEL
CIRCUIT NUMBER DESIGNATION FEEDING ELECTRICAL DEVICES,
FIXTURES AND EQUIPMENT.
PANEL : INDICATES THE PANEL NAME
XX : INDICATES THE CIRCUIT NUMBER
KEYED DRAWING NOTE
WALL MOUNTED TV OUTLET
WALL MOUNTED CARD READER
CONDUIT UP
CONDUIT DOWN
CONTINUATION CIRCUIT
1. REFER TO THE LIGHTING FIXTURE SCHEDULE ON DRAWING E601 FOR LIGHTING
FIXTURE SPECIFICATIONS.
2. REFER TO DETAIL ON DRAWING E701 FOR TYPICAL DEVICE MOUNTING HEIGHTS.
1. INSTALLATION OF ALL WORK SHALL BE IN ACCORDANCE WITH THE FOLLOWING REGULATIONS, CODES, ETC.
A. LOCAL CODES AND ORDINANCES
B. THE EDITION OF THE NATIONAL ELECTRICAL CODE (NEC 2014), NFPA 72 AND 72D, IN EFFECT.
2. CONTRACTOR TO PROVIDE SUFFICIENT NOTICE TO THE OWNER'S REPRESENTATIVE PRIOR TO ANY WORK TO ALLOW
ADEQUATE TIME FOR COORDINATION OF EXISTING BUILDING ACTIVITIES WITH THE CONSTRUCTION WORK.
3. CONTRACTOR TO INCLUDE IN THEIR SCOPE ALL LABOR, MATERIALS, SERVICES, APPARATUS AND SHOP DRAWINGS IN
ADDITION TO THE CONTRACT DOCUMENTS AS REQUIRED TO COMPLY WITH ALL APPLICABLE GOVERNING LAWS, CODES
AND JURISDICTION REQUIREMENTS. PROVIDE ELECTRICAL EQUIPMENT WITH ALL ASSOCIATED ACCESSORIES, BRANCH
CIRCUIT WIRING AND CONDUIT INFRASTRUCTURE AS REQUIRED TO ENSURE A COMPLETE AND OPERATIONAL SYSTEM.
4. ALL MATERIALS AND WORK SHALL BE ACCORDING TO PROJECT SPECIFICATIONS.
5. IF MATERIAL OR EQUIPMENT IS INSTALLED BEFORE IT IS APPROVED, THE CONTRACTOR SHALL BE LIABLE FOR ITS
REMOVAL AND REPLACEMENT AT NO ADDITIONAL CHARGE IF IN THE OPINION OF THE ARCHITECT OR ENGINEER, THE
MATERIAL OR EQUIPMENT DOES NOT MEET THE INTENT OF THE DRAWINGS AND/OR SPECIFICATIONS.
6. REFER TO ARCHITECTURAL DRAWINGS AND LAB DRAWINGS(Q-SERIES) FOR THE EXACT LOCATION, ELEVATION, MOUNTING HEIGHTS AND DETAILS OF ALL LIGHT FIXTURES AND DEVICES. REPORT ANY DISCREPANCIES TO THE
ARCHITECT IMMEDIATELY.
7. ALL NEW SLAB PENETRATIONS MUST BE X-RAYED OR RADAR PRIOR TO CORE DRILLING. OBTAIN APPROVAL FROM
OWNER'S REPRESENTATIVE PRIOR TO ANY CORE DRILLING.
8. CONTRACTOR TO PROVIDE ALL LIGHT FIXTURE AND EQUIPMENT WITH INTEGRAL OR REMOTE MOUNTED ACCESSORY
DEVICES WITH ALL NECESSARY COMPONENTS, BRANCH CIRCUIT WIRING AND CONDUITS TO ENSURE A COMPLETE AND
OPERATIONAL SYSTEM. CONTRACTOR TO MAKE ALL FINAL CONNECTIONS TO THE EQUIPMENT.
9. ELECTRICAL SYSTEMS SHALL BE GROUNDED PER ARTICLE 250 OF THE NATIONAL ELECTRICAL CODE.
10. PROVIDE AN INSULATED EQUIPMENT GROUNDING CONDUCTOR IN ALL BRANCH CIRCUITS AND FEEDERS INSTALLED IN
RACEWAYS. THE DEDICATED EQUIPMENT GROUNDING CONDUCTOR SHALL BE SIZED PER NEC SECTION 250.122. SOLE
USE OF METAL RACEWAY AS A GROUNDING CONDUCTOR SHALL NOT BE ACCEPTABLE. WIRING METHODS SHALL BE IN
ACCORDANCE WITH NEC SECTION 518.4 FOR ALL ASSEMBLY AREAS.
11. PROVIDE RED COLOR LOCKABLE TYPE BREAKERS FOR CIRCUITS SERVING LIFE SAFETY PANEL BOARDS.
12. NUMBER OF WIRES MAY NOT BE INDICATED FOR ALL CIRCUITS, ONLY THOSE WHERE CLARIFICATION IS NECESSARY.
PROVIDE THE NUMBER AND SIZE AS NECESSARY FOR THE PROPER FUNCTION OF THE SYSTEM WHETHER SPECIFICALLY
INDICATED ON PLAN OR NOT.
13. ALL BACK BOXES INSTALLED IN PARTITION WALLS SHALL BE STAGGERED. BACK-TO-BACK INSTALLATION IS NOT
PERMITTED.
14. PROVIDE ACCESS PANELS FOR ALL INACCESSIBLE JUNCTION BOXES AS REQUIRED BY THE N.E.C.
15. PROVIDE PLASTER RING WITH PULL STRING TO SPACE ABOVE SUSPENDED CEILING FOR ALL TELEPHONE, DATA, FAX, MODEM, CATV, CARD READER, ETC. OUTLETS INSTALLED IN HOLLOW PARTITIONS. PROVIDE 3/4" EMPTY CONDUIT AND
PULL STRING TO SPACE ABOVE SUSPENDED CEILING FOR THESE OUTLETS INSTALLED IN AN INSULATED PARTITION.
PROVIDE 1" EMPTY CONDUIT WITH PULL STRINGS FOR DATA/TEL OUTLETS.
16. CONTRACTOR TO TEST AND VERIFY THE CAPACITY OF THE EXISTING FIRE ALARM SYSTEM SERVING BUILDING PRIOR TO
STARTING ANY ASSOCIATED WORK. REPORT IN WRITING, THE TEST RESULTS INCLUDING ANY DEFICIENCIES IDENTIFIED
WITHIN THE EXISTING SYSTEM. SUBMIT ASSOCIATED COSTS FOR OWNERS APPROVAL TO REPLACE AND/OR PROVIDE
ADDITIONAL EQUIPMENT AND COMPONENTS AS REQUIRED TO ENSURE A COMPLETE AND OPERATIONAL SYSTEM.
17. PROVIDE FIRE ALARM INTERFACE HARDWARE, MODULES AND WIRING TO ALL ELECTRICALLY SECURED DOORS.
COORDINATE WITH BUILDING SECURITY SYSTEM.
18. FOR ALL ELEVATOR SYSTEMS,
A. PROVIDE A DEDICATED 125 VOLT, 20 AMPERE SINGLE-PHASE BRANCH CIRCUIT, WITH A FUSED DISCONNECT
SWITCH CAPABLE OF BEING LOCKED IN THE OPEN POSITION FOR THE CAR LIGHTS AND VENTILATION IN EACH
CAR.
B. ALL 125 VOLT, 15 OR 20 AMPERE SINGLE-PHASE RECEPTACLES INSTALLED IN PITS, MACHINE SPACES, CONTROL
ROOMS SHALL BE OF THE GROUND-FAULT CIRCUIT-INTERRUPTER TYPE (GFCI).
19. ELECTRICAL CONTRACTOR TO COORDINATE WITH MECHANICAL, PLUMBING AND OTHER TRADES TO PROVIDE ALL
EQUIPMENT ASSOCIATED WITH THEIR RESPECTIVE TRADES WITH NECESSARY WIRING AND CONDUIT INFRASTRUCTURE
FOR ALL SENSORS, AND CONTROL SYSTEMS AS REQUIRED.
20. CONTRACTOR TO PROVIDE DEDICATED CIRCUIT FOR CONNECTION TO EACH MECHANICAL EQUIPMENT CONTROL PANEL AS
REQUIRED. COORDINATE EXACT LOCATION AND CONNECTION REQUIREMENTS WITH MECHANICAL AND CONTROLS
CONTRACTORS.
21. CONTRACTOR TO COORDINATE ELECTRICAL WORK TO AVOID INTERFERENCE BETWEEN ALL TRADES.
A. DETERMINE INTERFERENCE BEFORE WORK IS FABRICATED OR INSTALLED. THE CONTRACTOR SHALL BE
THOROUGHLY FAMILIAR WITH ALL DETAILS OF WORK AND WORKING CONDITIONS AND COORDINATE WORK
DURING PRELIMINARY STAGES TO ENSURE ACTUAL ERECTION WILL PROCEED WITHOUT INTERFERENCE.
COORDINATION IS OF PARAMOUNT IMPORTANCE AND REQUESTS FOR ADDITIONAL PAYMENT WILL BE
CONSIDERED WHERE REQUEST IS BASED ON INTERFERENCE.
B. WHERE JOB CONDITIONS REQUIRE REASONABLE DEVIATIONS FROM CONTRACT DOCUMENTS, MAKE
DEVIATIONS WITHOUT ADDITIONAL COST TO OWNER, AFTER OBTAINING APPROVAL OF ARCHITECT.
C. PROVIDE MAXIMUM PRACTICAL SPACE FOR OPERATION, REPAIR, REMOVAL, AND TESTING OF ELECTRICAL
EQUIPMENT. DEVIATIONS MAY BE MADE TO PROVIDE REQUIRED ACCESSIBILITY PROVIDED THEY ARE APPROVED BY
THE OWNERS OR THE ARCHITECTS.
D. KEEP CONDUITS, WIRE WAYS AND SIMILAR ITEMS AS CLOSE AS POSSIBLE TO CEILING, WALLS AND COLUMNS IN
ORDER TO TAKE UP MINIMUM AMOUNT OF SPACE. ALL WORK TO BE IN STALLED IN A NEAT AND WORK MAN LIKE
MANNER.
E. PROVIDE OFFSETS, FITTINGS AND SIMILAR ITEMS NECESSARY TO ACCOMPLISH REQUIREMENTS OF
COORDINATION WITHOUT ADDITIONAL EXPENSE TO OWNER.
F. PROVIDE ACCESS TO AND CLEARANCES AROUND ELECTRICAL EQUIPMENT AS REQUIRED BY THE N.E.C.
22. ELECTRICAL CONTRACTOR SHALL FOLLOW THE STANDARD OPERATING PROCEDURE FOR CLEANING AND DISINFESTATION
OF MACHINERY IMPACTED BY THE SOIL REFER TO THE USDA STANDARD OPERATING PROCEDURE, CLEANING AND
DISINFESTING EQUIPMENT AT THE CATTLE FEVER TICK RESEARCH LABORATORY IN MISSION, TEXAS. USDA EMPLOYEES AT
THE EDINBURG LOCATION WILL PROVIDE CLEANING AND DISINFECTION OF MACHINERY. CONTRACTOR TO PROVIDE 24
HOURS NOTICE OF CLEANING EQUIPMENT. FOR MORE INFORMATION. COORDINATE WITH CONTRACTING OFFICER AS
NEEDED.
VIF VERIFY IN FIELD
(STANDARD SYMBOLS ONLY, ALL SYMBOLS MAY NOT BE APPLICABLE TO THIS PROJECT)
LV
L2
L3
FS SPRINKLER FLOW SWITCH
TS TAMPER SWITCH
1465 NORTHSIDE DRIVE SUITE 220B
ATLANTA, GA 30318
P:706-248-7165 www. .com
TM
PROJECT NUMBER: SIGQ212911.15
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A
D
USDA S
U
DWG. NO
DRAWN BY
SOLICITATION NO. SHEET NAME
ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED
Revisions
Agricultural Research Service
6/15/2022 4:36:41 PM C:\Users\Nicholas.Carlis\Documents\SIGQ212911.15_R20_Electrical_nicholas.carlisYDXF8.rvt
WET LAB
E001
GENERAL NOTES,
SYMBOLS, &
ABBREVIATIONS
CDC
NC 06/16/2022
JM BD
DC
LB
EO
NO. DATE BY DESCRIPTION
1 03/04/2022 JM 50% DOCUMENTS
2 04/20/2022 JM 90% DOCUMENTS
3 05/06/2022 JM 100% DOCUMENTS
4 05/20/2022 JM ISSUE FOR BIDDING AND CONSTRUCTION
5 06/16/2022 JM ADDENDUM 1
GENERAL NOTES ELECTRICAL SYMBOL LIST ABBREVIATIONS
DRAWING LIST
SHEET DRAWING TITLE
01 E001 GENERAL NOTES, SYMBOLS, & ABBREVIATIONS
02 E101 LEVEL 1 ELECTRICAL LIGHTING BASE BID
03 E101.1 LEVEL 1 ELECTRICAL LIGHTING ADD ALT. #1
04 E101.2 LEVEL 1 ELECTRICAL LIGHTING ADD ALT. #2
06 E201 LEVEL 1 ELECTRICAL POWER BASE BID
07 E201.1 LEVEL 1 ELECTRICAL POWER ADD ALT. #1
08 E201.2 LEVEL 1 ELECTRICAL POWER ADD ALT. #2
05 E202 ROOF ELECTRICAL POWER PLAN
09 E301 LEVEL 1 FIRE ALARM BASE BID
10 E301.1 LEVEL 1 FIRE ALARM ADD ALT. #1
11 E301.2 LEVEL 1 FIRE ALARM ADD ALT. #2
12 E501 ELECTRICAL RISER DIAGRAMS
13 E503 FIRE ALARM ANNUNCIATOR PANEL
14 E601 ELECTRICAL SCHEDULES
15 E602 ELECTRICAL SCHEDULES
16 E701 ELECTRICAL DETAILS
BD
G
FI
GFI GFI
GFI GFI
G
FI
GFIGFI GFI GFI GFI
TV
G
FI
G
FI
FACP
J
J
J
J J
J
J
J
J
J
J
J
J
GFI GFI
GFI
F A
A P
J
J
GENERAL NOTES
SHEET KEY NOTES#
5 6 7 8
11 12 131415
MEN. RR
WOMEN RR
23ENTRY/ VESTIBULE
GROUP OFFICE
GEN. STORAGE
OFFICE
ENTRY EQM
CONF RM
CHEM STORAGE
EQM STORAGE
FUME HOOD
CORRIDOR
OPEN WET LAB
OFFICE
ELEC. RM.
ENTRY VEST.
JAN. RM.
2 2 2 2 2
1 1
PANEL "RW"
MECH.
DWH-1
EXCAV-1-1
RHCAV-1-9
RHCAV-1-11
RHCAV-1-8
RHCAV-1-6
EXCAV-1-5
RHCAV-1-5
EXCAV-1-4
EXCAV-1-6
RHCAV-1-10
EXCAV-1-7
RHCAV-1-12
RHCAV-1-7
RHCAV-1-1
EXCAV-1-8
RHCAV-1-4
EXCAV-1-3
EXCAV-1-2
RHCAV-1-3
RHCAV-1-2
CU-1
AHU-1
GEF-1
RW-8
RW-8
RW-8
RW-8
RW-10
RW-10 RW-10
RW-12
RW-12
RW-12
RW-14
RW-14
RW-14RW-14
RW-16
RW-16
RW-16
RW-18
RW-18
RW-18
RW-18
RW-20RW-20RW-20
RW-20RW-22
RW-22
RW-22
RW-24
RW-24
RW-24
RW-26
RW-26
RW-26
RW-28
RW-28RW-28
RW-30
RW-30RW-30
RW-32
RW-32
RW-32
RW-34
RW-34
RW-34
RW-36
RW-36
RW-36 RW-38 RW-38 RW-38 RW-40
RW-40
RW-40
RW-42
RW-42RW-42RW-42
RW-31
RW-31
RW-31
RW-31
RW-33
RW-33
RW-33
RW-33
PW-8
ROS-1
PP-1
RW-7
RW-9
PW-13,15,17
PW-43,45,47
PW-19,21,23
PW-19,21,23
PW-19,21,23
PW-25,27,29
PW-25,27,29
PW-31,33,35
PW-37,39,41
PW-20,22,24
PW-26,28,30
PW-32,34,36
PW-38,40,42
PW-37,39,41
PW-14,16,18
PW-7,9,11 PW-1,3,5 RW-1
RW-5
WP WP
WP
RW-37 RW-37
RW-37
WS-1
RW-11
RW-11
RW-15
RW-15
PANEL "PW"(S1)
PANEL "PW"(S2)
1. REFER TO THE ELECTRICAL COVER SHEET DRAWING FOR GENERAL
NOTES, LEGEND AND ABBREVIATIONS.
2. REFER TO ARCHITECTURAL DRAWINGS TO VERIFY THE ELEVATIONS,
DETAILS, LOCATION, MOUNTING HEIGHTS AND ADDITIONAL
INFORMATION PRIOR TO THE ROUGH-IN OF ELECTRICAL OUTLETS AND
DEVICES.
3. COORDINATE WITH CONTRACT DOCUMENTS FOR ALL OTHER
DISCIPLINES AND TRADES FOR EXACT LOCATION OF ASSOCIATED
EQUIPMENT.
4. ALL NEW OUTLETS AND DEVICES MUST BE FLUSH MOUNTED WITH
CONCEALED CONDUITS. ANY SURFACE MOUNTED OUTLETS, DEVICES
AND CONDUITS IN THE SCOPE OF WORK AREA MUST BE APPROVED BY
THE ARCHITECT PRIOR TO INSTALLATION.
5. COORDINATE WITH MECHANICAL CONTRACT DOCUMENTS TO VERIFY
THE EXACT LOCATION AND QUANTITY OF DUCT SMOKE DETECTORS
RESPECTIVELY.
6. THE CONTINUITY OF ALL EXISTING FIRE ALARM INITIATING DEVICE,
NOTIFICATION APPLIANCE AND SIGNALING LINE CIRCUITS TO REMAIN
SHALL BE MAINTAINED.
1. COORDINATE FINAL GFI LOCATION SHALL BE INSTALLED NEXT TO
SINK. SEE ARCH DRAWINGS FOR MORE INFORMATION.
2. RECEPTACLE SHALL BE DEDICATED TO WS-1.
1465 NORTHSIDE DRIVE SUITE 220B
ATLANTA, GA 30318
P:706-248-7165 www. .com
TM
PROJECT NUMBER: SIGQ212911.15
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A
D
USDA S
U
DWG. NO
DRAWN BY
SOLICITATION NO. SHEET NAME
ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED
Revisions
Agricultural Research Service
5/20/2022 5:44:44 PM C:\Users\Nicholas.Carlis\Documents\SIGQ212911.15_R20_Electrical_nicholas.carlisYDXF8.rvt
WET LAB
E201
LEVEL 1 ELECTRICAL
POWER BASE BID
CDC
NC 04/20/2022
JM BD
DC
LB
EO
NO SCALEE201
1 LEVEL 1 ELECTRICAL POWER BASE BID
NO. DATE BY DESCRIPTION
1 03/04/2022 JM 50% DOCUMENTS
2 04/20/2022 JM 90% DOCUMENTS
3 05/06/2022 JM 100% DOCUMENTS
4 05/20/2022 JM ISSUE FOR BIDDING AND CONSTRUCTION
SHEET KEY NOTES#
1. COORDINATE FINAL GFI LOCATION SHALL BE INSTALLED NEXT TO
SINK. SEE ARCH DRAWINGS FOR MORE INFORMATION.
2. RECEPTACLE SHALL BE DEDICATED TO WS-1.
3. FOR EACH PANEL PROVIDE TWO WHIPS TO CONNECT ELECTRICAL
SERVICE TO OWNERS EQUIPMENT. COORDINATE CONNECTION
REQUIREMENTS WITH OWNER THROUGH SUBMITTAL. REFER TO
ARCHITECURAL DRAWING A803 FOR MORE INFORMATION
4. FOR EACH PANEL PROVIDE 2 WHIPS TO CONNECT DATA SERVICE TO
OWNERS EQUIPMENT. COORDINATE CONNECTION REQUIREMENTS
WITH OWNER THROUGH SUBMITTAL REFER TO ARCHITECURAL
DRAWING A803 FOR MORE INFORMATION
5. RECEPTACLES SHALL BE INSTALLED UNDERNEATH TABLE FOR
OWNER EQUIPMENT REQUIREMENTS
G
FI
GFI GFI
GFI GFI
G
FI
GFIGFI GFI GFI GFI
TV
G
FI
G
FI
FACP
J
J
J
J J
J
J
J
J
J
J
J
GFI GFI
GFI
F A
A P
J
J
GFI GFI GFI GFI GFI
GFIGFIGFIGFI
G
FI
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
GFI
5 6 7 8
11 12 131415
MEN. RR
WOMEN RR
23ENTRY/ VESTIBULE
GROUP OFFICE
GEN. STORAGE
OFFICE
ENTRY EQM
CONF RM
CHEM STORAGE
EQM STORAGE
FUME HOOD
CORRIDOR
OPEN WET LAB
OFFICE
ELEC. RM.
ENTRY VEST.
JAN. RM.
2 2 2 2 2
1 1
PANEL "PW"
PANEL "RW"
MECH.
DWH-1
EXCAV-1-1
RHCAV-1-9
RHCAV-1-11
RHCAV-1-8
RHCAV-1-6
EXCAV-1-5
RHCAV-1-5
EXCAV-1-4
EXCAV-1-6
RHCAV-1-10
EXCAV-1-7
RHCAV-1-12
RHCAV-1-7
RHCAV-1-1
EXCAV-1-8
RHCAV-1-4
EXCAV-1-3
EXCAV-1-2
RHCAV-1-3
RHCAV-1-2
CU-1
AHU-1
RW-8
RW-8
RW-8
RW-8
RW-10
RW-10 RW-10
RW-12
RW-12
RW-12
RW-14
RW-14
RW-14RW-14
RW-16
RW-16
RW-16
RW-18
RW-18
RW-18
RW-18
RW-20RW-20RW-20
RW-20RW-22
RW-22
RW-22
RW-24
RW-24
RW-24
RW-26
RW-26
RW-26
RW-28
RW-28RW-28
RW-30
RW-30RW-30
RW-32
RW-32
RW-32
RW-34
RW-34
RW-34
RW-31
RW-31
RW-31
RW-31
RW-33
RW-33
RW-33
RW-33
PW-8
ROS-1
PP-1
RW-7
RW-9
PW-43,45,47
PW-19,21,23
PW-19,21,23
PW-19,21,23
PW-25,27,29
PW-25,27,29
PW-31,33,35
PW-37,39,41
PW-20,22,24
PW-26,28,30
PW-32,34,36
PW-38,40,42
PW-37,39,41
PW-14,16,18
PW-7,9,11 PW-1,3,5 RW-1
RW-5
WP WP
WP
RW-37 RW-37
RW-37
WS-1
RW-15
RW-15
TSTSFS
PANEL "LW"
RW-34
RW-32
2 2 2 2 2 2 2 2 2 2
RW-17,19,21
LW-1
LW-1
LW-1
LW-3
LW-3 LW-3 LW-5 LW-5 LW-5 LW-7 LW-7 LW-7 LW-9 LW-9
LW-9
LW-11
LW-11
LW-11
LW-15 LW-13 LW-13
LW-13
LW-15LW-15
LW-17
LW-17
x3
LW-21
x3 x3 x3 x3 x3 x3 x3 x3 x3 x2 x2 x2 x2 x2 x2 x2 x2
LW-25 LW-29 LW-33 LW-37
LW-19 LW-23 LW-27 LW-35
x2 x2
LW-31
LW-10
LW-12
LW-14
LW-16
5 5555
4 4
NO SCALEE201
1 LEVEL 1 ELECTRICAL POWER BASE BID
J
GEF-1
PW-13,15,17PW-13,15,17
BD
5 06/16/2022 JM ADDENDUM 1
06/16/2022
GFI GFI
GFI GFI
G
FI
GFIGFI GFI GFI GFIGFI
G
FI
TV
G
FI
G
FI
G
FI
G
FI
G
FI
J
J
J
J J
J
J
J
J
J
J
J
J
J
J
GFI GFI
GFI
J
J
GFI GFI GFI GFI GFIGFI GFI
G
FI
G
FI
G
FI
G
FI
GFIGFIGFIGFI
G
FI
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
GFI
5 6 7 8
11 12 131415
MEN. RR
20 WOMEN RR
ENTRY/ VESTIBULE
GROUP OFFICE
GEN. STORAGE
OFFICE
ENTRY EQM
CONF RM
CHEM STORAGE
EQM STORAGE
FUME HOOD
CORRIDOR
OPEN WET LAB
OFFICE
ELEC. RM.
ENTRY VEST.
JAN. RM.
2 2 2 2 2 2
1 1
PANEL "PW"
PANEL "RW"
FIELD LAB OFFICE
FIELD LABORATORY
MECH.
DWH-1
EXCAV-1-1
EXCAV-1-9
EXCAV-1-10
RHCAV-1-14
RHCAV-1-13
RHCAV-1-9
RHCAV-1-11
RHCAV-1-8
RHCAV-1-6
EXCAV-1-5
RHCAV-1-5
EXCAV-1-4
EXCAV-1-6
RHCAV-1-10
EXCAV-1-7
RHCAV-1-12
RHCAV-1-7
RHCAV-1-1
EXCAV-1-8
RHCAV-1-4
EXCAV-1-3
EXCAV-1-2
RHCAV-1-3
RHCAV-1-2
CU-1
AHU-1
GEF-1
RW-8
RW-8
RW-8
RW-8
RW-10
RW-10 RW-10
RW-12
RW-12
RW-12
RW-14
RW-14
RW-14RW-14
RW-16
RW-16
RW-16
RW-18
RW-18
RW-18
RW-18
RW-20RW-20RW-20
RW-20RW-22
RW-22
RW-22
RW-24
RW-24
RW-24
RW-26
RW-26
RW-26
RW-28
RW-28RW-28
RW-30
RW-30RW-30
RW-32
RW-32
RW-32
RW-34
RW-34
RW-34
RW-31
RW-31
RW-31
RW-31
RW-33
RW-33
RW-33
RW-33
RW-23
RW-23
RW-23
LW-18
LW-18
LW-28
LW-20
RW-35
RW-35
RHCAV-1-6
ROS-1
PP-1
RW-7
RW-9
PW-13,15,17
PW-19,21,23
PW-19,21,23
PW-19,21,23
PW-25,27,29
PW-25,27,29
PW-31,33,35
PW-37,39,41
PW-37,39,41
PW-20,22,24
PW-26,28,30
PW-32,34,36
PW-38,40,42
PW-43,45,47
PW-7,9,11
PW-13,15,17
PW-14,16,18
PW-1,3,5 RW-1
PW-38,40,42
PW-44,46,48
RW-5
WP WP
WP
RW-37 RW-37
RW-37
WS-1
RW-13
RW-13
PANEL "LW"
LW-18
LW-22
LW-20
RW-34
RW-32
2 2 2 2 2 2 2 2 2 2
RW-15,17,19
LW-1
LW-1
LW-1
LW-3
LW-3 LW-3 LW-5 LW-5 LW-5 LW-7 LW-7 LW-7 LW-9 LW-9
LW-9
LW-11
LW-11
LW-11
LW-15 LW-13 LW-13
LW-13
LW-15LW-15
LW-17
LW-17
x3
LW-21
x3 x3 x3 x3 x3 x3 x3 x3 x3 x2 x2 x2 x2 x2 x2
LW-25 LW-29 LW-33 LW-37
LW-19 LW-23 LW-27 LW-35
x2 x2
LW-31
LW-39
LW-41
LW-2
LW-4
LW-10
LW-12
LW-14
LW-16
5 5555 x2 x2
LW-20
LW-22LW-22LW-24
LW-24
LW-24
LW-26
LW-26
LW-26
1465 NORTHSIDE DRIVE SUITE 220B
ATLANTA, GA 30318
P:706-248-7165 www. .com
TM
PROJECT NUMBER: SIGQ212911.15
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A
D
USDA S
U
DWG. NO
DRAWN BY
SOLICITATION NO. SHEET NAME
ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED
Revisions
Agricultural Research Service
6/16/2022 6:41:23 PM C:\Users\Nicholas.Carlis\Documents\SIGQ212911.15_R20_Electrical_nicholas.carlisYDXF8.rvt
WET LAB
E201.1
LEVEL 1 ELECTRICAL
POWER ADD ALT. #1
CDC
NC 06/16/2022
JM BD
BD
DC
LB
EO
NO. DATE BY DESCRIPTION
1 03/04/2022 JM 50% DOCUMENTS
2 04/20/2022 JM 90% DOCUMENTS
3 05/06/2022 JM 100% DOCUMENTS
4 05/20/2022 JM ISSUE FOR BIDDING AND CONSTRUCTION
5 06/16/2022 JM ADDENDUM 1
NO SCALEE201.1
1 LEVEL 1 ELECTRICAL POWER ADD ALT. #1
GENERAL NOTES
SHEET KEY NOTES#
1. REFER TO THE ELECTRICAL COVER SHEET DRAWING FOR GENERAL
NOTES, LEGEND AND ABBREVIATIONS.
2. REFER TO ARCHITECTURAL DRAWINGS TO VERIFY THE ELEVATIONS,
DETAILS, LOCATION, MOUNTING HEIGHTS AND ADDITIONAL
INFORMATION PRIOR TO THE ROUGH-IN OF ELECTRICAL OUTLETS AND
DEVICES.
3. COORDINATE WITH CONTRACT DOCUMENTS FOR ALL OTHER
DISCIPLINES AND TRADES FOR EXACT LOCATION OF ASSOCIATED
EQUIPMENT.
4. ALL NEW OUTLETS AND DEVICES MUST BE FLUSH MOUNTED WITH
CONCEALED CONDUITS. ANY SURFACE MOUNTED OUTLETS, DEVICES
AND CONDUITS IN THE SCOPE OF WORK AREA MUST BE APPROVED BY
THE ARCHITECT PRIOR TO INSTALLATION.
5. COORDINATE WITH MECHANICAL CONTRACT DOCUMENTS TO VERIFY
THE EXACT LOCATION AND QUANTITY OF DUCT SMOKE DETECTORS
RESPECTIVELY.
6. THE CONTINUITY OF ALL EXISTING FIRE ALARM INITIATING DEVICE,
NOTIFICATION APPLIANCE AND SIGNALING LINE CIRCUITS TO REMAIN
SHALL BE MAINTAINED.
1. COORDINATE FINAL GFI LOCATION SHALL BE INSTALLED NEXT TO
SINK. SEE ARCH DRAWINGS FOR MORE INFORMATION.
2. RECEPTACLE SHALL BE DEDICATED TO WS-1.
SHEET KEY NOTES#
1. COORDINATE FINAL GFI LOCATION SHALL BE INSTALLED NEXT TO
SINK. SEE ARCH DRAWINGS FOR MORE INFORMATION.
2. RECEPTACLE SHALL BE DEDICATED TO WS-1.
3. FOR EACH PANEL PROVIDE TWO WHIPS TO CONNECT ELECTRICAL
SERVICE TO OWNERS EQUIPMENT. COORDINATE CONNECTION
REQUIREMENTS WITH OWNER THROUGH SUBMITTAL. REFER TO
ARCHITECURAL DRAWING A803 FOR MORE INFORMATION
4. FOR EACH PANEL PROVIDE 2 WHIPS TO CONNECT DATA SERVICE TO
OWNERS EQUIPMENT. COORDINATE CONNECTION REQUIREMENTS
WITH OWNER THROUGH SUBMITTAL REFER TO ARCHITECURAL
DRAWING A803 FOR MORE INFORMATION
5. RECEPTACLES SHALL BE INSTALLED UNDERNEATH TABLE FOR
OWNER EQUIPMENT REQUIREMENTS
GFI GFI
GFI GFI
G
FI
GFIGFI GFI GFI GFI
G
FI
G
FI
GFI GFI
G
FI
G
FI
G
FI
G
FI
TV
G
FI
G
FI
J
J
J
J
J J
J
J
J
J
J
J
J
J
J
GFI GFI
GFI
J
J
5 6 7 8
11 12 131415
MEN. RR
WOMEN RR
ENTRY/ VESTIBULE
GROUP OFFICE
GEN. STORAGE
OFFICE
ENTRY EQM
CONF RM
CHEM STORAGE
EQM STORAGE
FUME HOOD
CORRIDOR
OPEN WET LAB
OFFICE
ELEC. RM.
ENTRY VEST.
JAN. RM.
2 2 2 2 2 2
1 1
PANEL "PW"(S1)
MECH.
FIELD LAB OFFICE
FIELD LABORATORY
DWH-1
EXCAV-1-1
EXCAV-1-9
EXCAV-1-10
RHCAV-1-14
RHCAV-1-13
RHCAV-1-9
RHCAV-1-11
RHCAV-1-8
RHCAV-1-6
EXCAV-1-5
RHCAV-1-5
EXCAV-1-4
EXCAV-1-6
RHCAV-1-10
EXCAV-1-7
RHCAV-1-12
RHCAV-1-7
RHCAV-1-1
EXCAV-1-8
RHCAV-1-4
EXCAV-1-3
EXCAV-1-2
RHCAV-1-3
RHCAV-1-2
AHU-1
GEF-1
CU-1
RW-8
RW-8
RW-8
RW-8
RW-10
RW-10 RW-10
RW-12
RW-12
RW-12
RW-14
RW-14
RW-14RW-14
RW-16
RW-16
RW-16
RW-18
RW-18
RW-18
RW-18
RW-20RW-20RW-20
RW-20RW-22
RW-22
RW-22
RW-24
RW-24
RW-24
RW-26
RW-26
RW-26
RW-28
RW-28RW-28
RW-30
RW-30RW-30
RW-32
RW-32
RW-32
RW-34
RW-34
RW-34
RW-36
RW-36
RW-36 RW-38 RW-38 RW-38 RW-40
RW-40
RW-40
RW-42
RW-42RW-42RW-42
RW-23RW-23
RW-23
RW-23
RW-25
RW-25
RW-25
RW-25
RW-27
RW-27
RW-27
RW-29RW-29
RW-29
RW-29
RW-31
RW-31
RW-31
RW-31
RW-33
RW-33
RW-33
RW-33
RW-35
RW-35
PW-19,21,23
PW-19,21,23
PW-19,21,23
PW-25,27,29
PW-25,27,29
PW-31,33,35
PW-37,39,41
PW-37,39,41
PW-20,22,24
PW-26,28,30
PW-32,34,36
PW-38,40,42
PW-43,45,47
PW-7,9,11
PW-13,15,17
ROS-1
PP-1
PW-14,16,18
RW-7
RW-9
PW-1,3,5 RW-1
PW-38,40,42
PW-44,46,48
RW-5
WP WP
WP
RW-37 RW-37
RW-37
WS-1
RW-21
RW-21
RW-13
RW-13
PANEL "PW"(S2)
PANEL "RW"
1465 NORTHSIDE DRIVE SUITE 220B
ATLANTA, GA 30318
P:706-248-7165 www. .com
TM
PROJECT NUMBER: SIGQ212911.15
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A
D
USDA S
U
DWG. NO
DRAWN BY
SOLICITATION NO. SHEET NAME
ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED
Revisions
Agricultural Research Service
5/20/2022 5:44:56 PM C:\Users\Nicholas.Carlis\Documents\SIGQ212911.15_R20_Electrical_nicholas.carlisYDXF8.rvt
WET LAB
E201.2
LEVEL 1 ELECTRICAL
POWER ADD ALT. #2
CDC
NC 04/20/2022
JM BD
DC
LB
EO
NO. DATE BY DESCRIPTION
1 03/04/2022 JM 50% DOCUMENTS
2 04/20/2022 JM 90% DOCUMENTS
3 05/06/2022 JM 100% DOCUMENTS
4 05/20/2022 JM ISSUE FOR BIDDING AND CONSTRUCTION
NO SCALEE201.2
1 LEVEL 1 ELECTRICAL POWER ADD ALT. #2
GENERAL NOTES
SHEET KEY NOTES#
1. REFER TO THE ELECTRICAL COVER SHEET DRAWING FOR GENERAL
NOTES, LEGEND AND ABBREVIATIONS.
2. REFER TO ARCHITECTURAL DRAWINGS TO VERIFY THE ELEVATIONS,
DETAILS, LOCATION, MOUNTING HEIGHTS AND ADDITIONAL
INFORMATION PRIOR TO THE ROUGH-IN OF ELECTRICAL OUTLETS AND
DEVICES.
3. COORDINATE WITH CONTRACT DOCUMENTS FOR ALL OTHER
DISCIPLINES AND TRADES FOR EXACT LOCATION OF ASSOCIATED
EQUIPMENT.
4. ALL NEW OUTLETS AND DEVICES MUST BE FLUSH MOUNTED WITH
CONCEALED CONDUITS. ANY SURFACE MOUNTED OUTLETS, DEVICES
AND CONDUITS IN THE SCOPE OF WORK AREA MUST BE APPROVED BY
THE ARCHITECT PRIOR TO INSTALLATION.
5. COORDINATE WITH MECHANICAL CONTRACT DOCUMENTS TO VERIFY
THE EXACT LOCATION AND QUANTITY OF DUCT SMOKE DETECTORS
RESPECTIVELY.
6. THE CONTINUITY OF ALL EXISTING FIRE ALARM INITIATING DEVICE,
NOTIFICATION APPLIANCE AND SIGNALING LINE CIRCUITS TO REMAIN
SHALL BE MAINTAINED.
1. COORDINATE FINAL GFI LOCATION SHALL BE INSTALLED NEXT TO
SINK. SEE ARCH DRAWINGS FOR MORE INFORMATION.
2. RECEPTACLE SHALL BE DEDICATED TO WS-1.
G
FI
GFI GFI
GFI GFI
G
FI
GFIGFI GFI GFI GFI
G
FI
G
FI
GFI GFI
G
FI
G
FI
G
FI
G
FI
TV
G
FI
G
FI
J
J
J
J
J J
J
J
J
J
J
J
J
J
GFI GFI
GFI
J
J
GFI GFI GFI GFI GFI
G
FI
G
FI
GFIGFI
G
FI
GFIGFIGFIGFI
G
FI
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J J J J
J JJ J
GFI
5 6 7 8
11 12 131415
MEN. RR
WOMEN RR
ENTRY/ VESTIBULE
GROUP OFFICE
GEN. STORAGE
OFFICE
ENTRY EQM
CONF RM
CHEM STORAGE
EQM STORAGE
FUME HOOD
CORRIDOR
OPEN WET LAB
OFFICE
ELEC. RM.
ENTRY VEST.
JAN. RM.
2 2 2 2 2 2
1 1
PANEL "PW"
PANEL "RW"
MECH.
FIELD LAB OFFICE
FIELD LABORATORY
DWH-1
EXCAV-1-1
EXCAV-1-9
EXCAV-1-10
RHCAV-1-14
RHCAV-1-13
RHCAV-1-9
RHCAV-1-11
RHCAV-1-8
RHCAV-1-6
EXCAV-1-5
RHCAV-1-5
EXCAV-1-4
EXCAV-1-6
RHCAV-1-10
EXCAV-1-7
RHCAV-1-12
RHCAV-1-7
RHCAV-1-1
EXCAV-1-8
RHCAV-1-4
EXCAV-1-3
EXCAV-1-2
RHCAV-1-3
RHCAV-1-2
AHU-1
CU-1
RW-8
RW-8
RW-8
RW-8
RW-10
RW-10 RW-10
RW-12
RW-12
RW-12
RW-14
RW-14
RW-14RW-14
RW-16
RW-16
RW-16
RW-18
RW-18
RW-18
RW-18
RW-20RW-20RW-20
RW-20RW-22
RW-22
RW-22
RW-24
RW-24
RW-24
RW-26
RW-26
RW-26
RW-28
RW-28RW-28
RW-30
RW-30RW-30
RW-32
RW-32
RW-32
RW-34
RW-34
RW-34
RW-23RW-23
RW-23
RW-23
LW-26
RW-31
RW-31
RW-31
RW-31
RW-33
RW-33
RW-33
RW-33
RW-35
RW-35
PW-19,21,23
PW-19,21,23
PW-19,21,23
PW-25,27,29
PW-25,27,29
PW-31,33,35
PW-37,39,41
PW-37,39,41
PW-20,22,24
PW-26,28,30
PW-32,34,36
PW-38,40,42
PW-43,45,47
PW-7,9,11
ROS-1
PP-1
PW-14,16,18
RW-7
RW-9
PW-1,3,5 RW-1
PW-38,40,42
PW-44,46,48
RW-5
WP WP
WP
RW-37 RW-37
RW-37
WS-1
RW-13
RW-13
PANEL "LW"
LW-1
LW-1
LW-1
LW-3
LW-3 LW-3 LW-5 LW-5 LW-5 LW-7 LW-7 LW-7 LW-9 LW-9
LW-9
LW-11
LW-11
LW-11
LW-15 LW-13 LW-13
LW-13
LW-15LW-15
LW-17
LW-17
x3
LW-21
2 2 2 2 2 2 2 2 2 2
RW-34
RW-32
RW-15,17,19
x3 x3 x3 x3 x3 x3 x3 x3 x3 x2 x2 x2 x2 x2 x2 x2 x2 x3x3x2 x2 x3x3x2 x2
LW-25 LW-29 LW-33 LW-37
LW-19 LW-23 LW-27 LW-35
x2 x2
LW-31
LW-39
LW-41
LW-2
LW-4
LW-6
LW-8
LW-10
LW-12
LW-14
LW-16
LW-26
LW-24
LW-32LW-30
5 5555
LW-18
LW-20
LW-24
LW-22
LW-26
LW-26
LW-28
LW-28
LW-28
LW-30
LW-30
LW-30
LW-32LW-32LW-32LW-34
LW-34
LW-34
LW-34
LW-36
LW-36
1. COORDI
SINK. SE
2. RECEPTA
3. FOR EAC
SERVICE
REQUIRE
ARCHITE
4. FOR EAC
OWNERS
WITH OW
DRAWIN
5. RECEPTA
OWNER
NO SCALEE201.2
1 LEVEL 1 ELECTRICAL POWER ADD ALT. #2
SHEET KEY NOTES#
1. COORDINATE FINAL GFI LOCATION SHALL BE INSTALLED NEXT TO
SINK. SEE ARCH DRAWINGS FOR MORE INFORMATION.
2. RECEPTACLE SHALL BE DEDICATED TO WS-1.
SHEET KEY NOTES#
1. COORDINATE FINAL GFI LOCATION SHALL BE INSTALLED NEXT TO
SINK. SEE ARCH DRAWINGS FOR MORE INFORMATION.
2. RECEPTACLE SHALL BE DEDICATED TO WS-1.
3. FOR EACH PANEL PROVIDE TWO WHIPS TO CONNECT ELECTRICAL
SERVICE TO OWNERS EQUIPMENT. COORDINATE CONNECTION
REQUIREMENTS WITH OWNER THROUGH SUBMITTAL. REFER TO
ARCHITECURAL DRAWING A803 FOR MORE INFORMATION
4. FOR EACH PANEL PROVIDE 2 WHIPS TO CONNECT DATA SERVICE TO
OWNERS EQUIPMENT. COORDINATE CONNECTION REQUIREMENTS
WITH OWNER THROUGH SUBMITTAL REFER TO ARCHITECURAL
DRAWING A803 FOR MORE INFORMATION
5. RECEPTACLES SHALL BE INSTALLED UNDERNEATH TABLE FOR
OWNER EQUIPMENT REQUIREMENTS
BD
AV
AV
AV
AV
15cd
AV
15cd
AV
AV
75 AV
AV
AV
AV
F
F
AV
15cd
AV
15cd
A V c d
S
S
S
FACP
AV
S
S
F
D
D
F A
A P
5 6 7 8
11 12 131415
MEN. RR
WOMEN RR
23ENTRY/ VESTIBULE
GROUP OFFICE
GEN. STORAGE
OFFICE
ENTRY EQM
CONF RM
CHEM STORAGE
EQM STORAGE
FUME HOOD
CORRIDOR
OPEN WET LAB
OFFICE
ELEC. RM.
ENTRY VEST.
JAN. RM.
PANEL "PW"
PANEL "RW"
MECH.
TSTSFS
1465 NORTHSIDE DRIVE SUITE 220B
ATLANTA, GA 30318
P:706-248-7165 www. .com
TM
PROJECT NUMBER: SIGQ212911.15
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A
D
USDA S
U
DWG. NO
DRAWN BY
SOLICITATION NO. SHEET NAME
ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED
Revisions
Agricultural Research Service
6/15/2022 4:36:44 PM C:\Users\Nicholas.Carlis\Documents\SIGQ212911.15_R20_Electrical_nicholas.carlisYDXF8.rvt
WET LAB
E301
LEVEL 1 FIRE ALARM BASE
BID
CDC
NC 06/16/2022
JM BD
BD
DC
LB
EO
NO SCALEE301
1 LEVEL 1 FIRE ALARM BASE BID
NO. DATE BY DESCRIPTION
1 03/04/2022 JM 50% DOCUMENTS
2 04/20/2022 JM 90% DOCUMENTS
3 05/06/2022 JM 100% DOCUMENTS
4 05/20/2022 JM ISSUE FOR BIDDING AND CONSTRUCTION
5 06/16/2022 JM ADDENDUM 1
AREA OF WORK
FACP(E)
KEYPLAN
FIRE ALARM GENERAL NOTES
1. REFER TO THE ELECTRICAL COVER SHEET DRAWING FOR GENERAL NOTES,
LEGEND AND ABBREVIATIONS. REFER TO DETAIL DRAWINGS FOR THE
PROPOSED MOUNTING REQUIREMENTS OF TYPICAL FIRE ALARM DEVICES.
2. REFER TO ARCHITECTURAL DRAWINGS TO COORDINATE AND VERIFY
AGAINST THE CEILING PLANS, ELEVATIONS AND DETAILS AT THE PROPOSED
FIRE ALARM DEVICE INSTALLATION LOCATIONS PRIOR TO THE ROUGH-IN.
3. COORDINATE WITH MECHANICAL AND FIRE PROTECTION CONTRACT
DOCUMENTS TO VERIFY THE EXACT LOCATION AND QUANTITY OF DUCT
SMOKE DETECTORS AND ALL FLOW AND TAMPER SWITCHES
RESPECTIVELY.
4. ALL NEW FIRE ALARM DEVICES SHALL BE INSTALLED AS FLUSH MOUNTED
WITH CONCEALED CONDUITS. ANY SURFACE MOUNTED DEVICES AND
CONDUITS IN THE SCOPE OF WORK AREA MUST BE APPROVED BY THE
ARCHITECT PRIOR TO INSTALLATION.
5. ALL NEW AND RELOCATED FIRE ALARM DEVICES MUST BE COMPATIBLE
WITH AND CONNECTED TO THE EXISTING FIRE ALARM SYSTEM, ZONED BY
FLOOR. EXTEND EXISTING WIRING AND CONDUIT FOR RELOCATED DEVICES
TO NEW LOCATIONS AS REQUIRED.
6. WHERE MORE THAN TWO VISUAL (STROBE) NOTIFICATION APPLIANCES ARE
IN THE FIELD OF VIEW, THEY SHALL FLASH IN SYNCHRONIZATION. PROVIDE
EXTERNAL SYNC MODULE OR SYNC PROTOCOL BUILT IN TO THE FIRE
ALARM CONTROL PANEL.
7. CONNECT NEW FIRE ALARM DEVICES TO EXISTING SITE FIRE ALARM
CONTROL PANEL LOCATED IN BUILDING 1. CONTRACTOR TO MODIFY OR
PROVIDE NEW FIRE ALARM CONTROL PANEL TO ACCOMMODATE
INSTALLATIONS OF NEW DEVICES AS NEEDED
AV
AV
AV
15cd
AV
15cd
AV
AV
75 AV
AV
AV
AV
F
F
AV
15cd
AV
15cd
A V c d
S
S
S
FACP
AV
S
AV
S
F
V
D
D
F A
A P
5 6 7 8
11 12 131415
MEN. RR
WOMEN RR
ENTRY/ VESTIBULE
GROUP OFFICE
GEN. STORAGE
OFFICE
ENTRY EQM
CONF RM
CHEM STORAGE
EQM STORAGE
FUME HOOD
CORRIDOR
OPEN WET LAB
OFFICE
ELEC. RM.
ENTRY VEST.
JAN. RM.
PANEL "PW"
PANEL "RW"
MECH.
TSTSFS
1465 NORTHSIDE DRIVE SUITE 220B
ATLANTA, GA 30318
P:706-248-7165 www. .com
TM
PROJECT NUMBER: SIGQ212911.15
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT…