Attachment 15 Wetlab Drawings Addendum 1.pdf

PDF 29 MB Posted

Attached to
Upgrade/Expand Utilities and Wet Lab Construction Federal contract opportunity
Solicitation number
12805B22R0015
Issued by
Department of Agriculture Agricultural Research Service Field Research Implementation and Information Delivery Plains Area

About this file

This document provides details for a federal solicitation seeking construction services. The U.S. Department of Agriculture Agricultural Research Service is soliciting proposals to upgrade and expand utilities and wet lab construction at its facility in Edinburg, Texas. A mandatory site visit will be held on June 29, 2022 at 10:00am CST at Building 17 on the research center campus. Contractors must register for the site visit by emailing the points of contact, Kelly Wright and David De La Paz, by June 26 with company and attendee information. The solicitation number is 12805B22R0015. Proposals are due by the date specified in the solicitation, though no due date is provided in this attachment.

View the file

Other files for this federal contract opportunity

Show all 22

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TRANSFORMER TO

BE RELOCATED

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT MANAGER

PPM

EPM

SETTY

DATE

A D

USDA S

U

DWG. NO

DRAWN BY

SOLICITATION NO. SHEET NAME

ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED

Revisions

Agricultural Research Service

1465 NORTHSIDE DRIVE SUITE 220B

ATLANTA, GA 30318

P:706-248-7165 www. .com

TM

PROJECT NUMBER:SIGQ212911.15

WET LAB

05/06/2022

NO. DATE BY DESCRIPTION

1 03/04/2022 50% DOCUMENTS

X:\Y03\2021\21007-00 USDA Wet Lab and Barns\3-Production\03-Sheets\LAB\Y03-21007-00-LAB-DM.dwgJun 15, 2022 - 3:41pm

AJH

NRS

AJH

VDA

2 04/20/2022 90% DOCUMENTS

3 05/06/2022 100% DOCUMENTS

Benchmark Information:

4 05/20/2022 ISSUE FOR BIDDING AND CONSTRUCTION

05/27/2022 ADDENDUM 1

AJH

AJH

AJH

AJH

AJH

06/16/2022 ADDENDUM 2AJH

Key Notes:

Sheet Notes:

Construction Notes:

DEMOLITION PLAN C100

06/16/20225

PROPOSED WET LAB

FFE-226.50

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT MANAGER

PPM

EPM

SETTY

DATE

A D

USDA S

U

DWG. NO

DRAWN BY

SOLICITATION NO. SHEET NAME

ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED

Revisions

Agricultural Research Service

1465 NORTHSIDE DRIVE SUITE 220B

ATLANTA, GA 30318

P:706-248-7165 www. .com

TM

PROJECT NUMBER:SIGQ212911.15

WET LAB

05/06/2022

NO. DATE BY DESCRIPTION

1 03/04/2022 50% DOCUMENTS

X:\Y03\2021\21007-00 USDA Wet Lab and Barns\3-Production\03-Sheets\LAB\Y03-21007-00-LAB-UTIL.dwgJun 15, 2022 - 3:42pm

AJH

NRS

AJH

VDA

2 04/20/2022 90% DOCUMENTS

3 05/06/2022 100% DOCUMENTS

Benchmark Information:

4 05/20/2022 ISSUE FOR BIDDING AND CONSTRUCTION

05/27/2022 ADDENDUM 1

AJH

AJH

AJH

AJH

AJH

06/16/2022 ADDENDUM 2AJH

Key Notes:

Sheet Notes:

UTILITY PLAN -

BASE BUILD

C300

General Construction Notes:

M

ATC

H

LIN

E TO

U

TILITY O

VER

ALL SH

EET

1 14" 2

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT MANAGER

PPM

EPM

SETTY

DATE

A D

USDA S

U

DWG. NO

DRAWN BY

SOLICITATION NO. SHEET NAME

ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED

Revisions

Agricultural Research Service

1465 NORTHSIDE DRIVE SUITE 220B

ATLANTA, GA 30318

P:706-248-7165 www. .com

TM

PROJECT NUMBER:SIGQ212911.15

WET LAB

05/06/2022

NO. DATE BY DESCRIPTION

1 03/04/2022 50% DOCUMENTS

X:\Y03\2021\21007-00 USDA Wet Lab and Barns\3-Production\03-Sheets\LAB\Y03-21007-00-LAB-UTIL.dwgJun 15, 2022 - 3:42pm

AJH

NRS

AJH

VDA

2 04/20/2022 90% DOCUMENTS

3 05/06/2022 100% DOCUMENTS

Benchmark Information:

4 05/20/2022 ISSUE FOR BIDDING AND CONSTRUCTION

05/27/2022 ADDENDUM 1

AJH

AJH

AJH

AJH

AJH

06/16/2022 ADDENDUM 2AJH

Key Notes:

Sheet Notes:

UTILITY PLAN -

ALTERNATE 1

C300.01

General Construction Notes:

M

ATC

H

LIN

E TO

U

TILITY O

VER

ALL SH

EET

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT MANAGER

PPM

EPM

SETTY

DATE

A D

USDA S

U

DWG. NO

DRAWN BY

SOLICITATION NO. SHEET NAME

ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED

Revisions

Agricultural Research Service

1465 NORTHSIDE DRIVE SUITE 220B

ATLANTA, GA 30318

P:706-248-7165 www. .com

TM

PROJECT NUMBER:SIGQ212911.15

WET LAB

05/06/2022

NO. DATE BY DESCRIPTION

1 03/04/2022 50% DOCUMENTS

X:\Y03\2021\21007-00 USDA Wet Lab and Barns\3-Production\03-Sheets\LAB\Y03-21007-00-LAB-UTIL.dwgJun 15, 2022 - 3:42pm

AJH

NRS

AJH

VDA

2 04/20/2022 90% DOCUMENTS

3 05/06/2022 100% DOCUMENTS

Benchmark Information:

4 05/20/2022 ISSUE FOR BIDDING AND CONSTRUCTION

05/27/2022 ADDENDUM 1

AJH

AJH

AJH

AJH

AJH

06/16/2022 ADDENDUM 2AJH

Key Notes:

Sheet Notes:

UTILITY PLAN -

ALTERNATE 2

C300.02

General Construction Notes:

M

ATC

H

LIN

E TO

U

TILITY O

VER

ALL SH

EET

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT MANAGER

PPM

EPM

SETTY

DATE

A D

USDA S

U

DWG. NO

DRAWN BY

SOLICITATION NO. SHEET NAME

ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED

Revisions

Agricultural Research Service

1465 NORTHSIDE DRIVE SUITE 220B

ATLANTA, GA 30318

P:706-248-7165 www. .com

TM

PROJECT NUMBER:SIGQ212911.15

WET LAB

05/06/2022

NO. DATE BY DESCRIPTION

1 03/04/2022 50% DOCUMENTS

X:\Y03\2021\21007-00 USDA Wet Lab and Barns\3-Production\03-Sheets\LAB\Y03-21007-00-LAB-SWPPP.dwgJun 15, 2022 - 3:42pm

AJH

NRS

AJH

VDA

2 04/20/2022 90% DOCUMENTS

3 05/06/2022 100% DOCUMENTS

Benchmark Information:

4 05/20/2022 ISSUE FOR BIDDING AND CONSTRUCTION

05/27/2022 ADDENDUM 1

AJH

AJH

AJH

AJH

AJH

06/16/2022 ADDENDUM 2AJH

LEGEND

SWPPP - BASE BUILD C400

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT MANAGER

PPM

EPM

SETTY

DATE

A D

USDA S

U

DWG. NO

DRAWN BY

SOLICITATION NO. SHEET NAME

ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED

Revisions

Agricultural Research Service

1465 NORTHSIDE DRIVE SUITE 220B

ATLANTA, GA 30318

P:706-248-7165 www. .com

TM

PROJECT NUMBER:SIGQ212911.15

WET LAB

05/06/2022

NO. DATE BY DESCRIPTION

1 03/04/2022 50% DOCUMENTS

X:\Y03\2021\21007-00 USDA Wet Lab and Barns\3-Production\03-Sheets\LAB\Y03-21007-00-LAB-SWPPP.dwgJun 15, 2022 - 3:42pm

AJH

NRS

AJH

VDA

2 04/20/2022 90% DOCUMENTS

3 05/06/2022 100% DOCUMENTS

Benchmark Information:

4 05/20/2022 ISSUE FOR BIDDING AND CONSTRUCTION

05/27/2022 ADDENDUM 1

AJH

AJH

AJH

AJH

AJH

06/16/2022 ADDENDUM 2AJH

LEGEND

SWPPP - ALTERNATE 1 C400.01

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT MANAGER

PPM

EPM

SETTY

DATE

A D

USDA S

U

DWG. NO

DRAWN BY

SOLICITATION NO. SHEET NAME

ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED

Revisions

Agricultural Research Service

1465 NORTHSIDE DRIVE SUITE 220B

ATLANTA, GA 30318

P:706-248-7165 www. .com

TM

PROJECT NUMBER:SIGQ212911.15

WET LAB

05/06/2022

NO. DATE BY DESCRIPTION

1 03/04/2022 50% DOCUMENTS

X:\Y03\2021\21007-00 USDA Wet Lab and Barns\3-Production\03-Sheets\LAB\Y03-21007-00-LAB-SWPPP.dwgJun 15, 2022 - 3:42pm

AJH

NRS

AJH

VDA

2 04/20/2022 90% DOCUMENTS

3 05/06/2022 100% DOCUMENTS

Benchmark Information:

4 05/20/2022 ISSUE FOR BIDDING AND CONSTRUCTION

05/27/2022 ADDENDUM 1

AJH

AJH

AJH

AJH

AJH

06/16/2022 ADDENDUM 2AJH

LEGEND

SWPPP - ALTERNATE 2 C400.02

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT MANAGER

PPM

EPM

SETTY

DATE

A D

USDA S

U

DWG. NO

DRAWN BY

SOLICITATION NO. SHEET NAME

ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED

Revisions

Agricultural Research Service

1465 NORTHSIDE DRIVE SUITE 220B

ATLANTA, GA 30318

P:706-248-7165 www. .com

TM

PROJECT NUMBER:SIGQ212911.15

WET LAB

05/06/2022

NO. DATE BY DESCRIPTION

1 03/04/2022 50% DOCUMENTS

X:\Y03\2021\21007-00 USDA Wet Lab and Barns\3-Production\03-Sheets\LAB\Y03-21007-00-LAB-SWPPP.dwgJun 15, 2022 - 3:42pm

AJH

NRS

AJH

VDA

2 04/20/2022 90% DOCUMENTS

3 05/06/2022 100% DOCUMENTS

Benchmark Information:

4 05/20/2022 ISSUE FOR BIDDING AND CONSTRUCTION

05/27/2022 ADDENDUM 1

AJH

AJH

AJH

AJH

AJH

06/16/2022 ADDENDUM 2AJH

LEGEND

SWPPP C401

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT MANAGER

PPM

EPM

SETTY

DATE

A D

USDA S

U

DWG. NO

DRAWN BY

SOLICITATION NO. SHEET NAME

ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED

Revisions

Agricultural Research Service

1465 NORTHSIDE DRIVE SUITE 220B

ATLANTA, GA 30318

P:706-248-7165 www. .com

TM

PROJECT NUMBER:SIGQ212911.15

WET LAB

05/06/2022

NO. DATE BY DESCRIPTION

1 03/04/2022 50% DOCUMENTS

X:\Y03\2021\21007-00 USDA Wet Lab and Barns\3-Production\03-Sheets\LAB\Y03-21007-00-LAB-GN.dwgJun 15, 2022 - 3:42pm

AJH

NRS

AJH

VDA

2 04/20/2022 90% DOCUMENTS

3 05/06/2022 100% DOCUMENTS

4 05/20/2022 ISSUE FOR BIDDING AND CONSTRUCTION

05/27/2022 ADDENDUM 1

AJH

AJH

AJH

AJH

AJH

06/16/2022 ADDENDUM 2AJH

A

A

NOT TO SCALE

RO

RO

RO

RO

RO

BUSINESS

A201.1

A201.1

A201.1A201.2

A201.2

A201.2

BUSINESS

A201.1

A201.1

A201.1

A201.1

A201.2

A201.2

A201.2

BUSINESS

A201.1

A201.1

A201.1

A201.1

A201.2

A201.2

A201.2

6/16/2022 1:46:30 PM C:\EYP_Temp\Revit_2020\2021060.01_Edinburg Wet Lab-add-alt_jbaughmanVUZ7P.rvt

NO. DATE BY DESCRIPTION

A201.1

A201.1

A201.1

A201.1

6/16/2022 1:55:59 PM C:\EYP_Temp\Revit_2020\2021060.01_Edinburg Wet Lab-add-alt_jbaughmanVUZ7P.rvt

REFLECTED CEILING PLAN - LEVEL 01 ADD ALT. #1

A201.2

A201.2

A201.2

A201.2

6/16/2022 1:50:21 PM C:\EYP_Temp\Revit_2020\2021060.01_Edinburg Wet Lab-add-alt_jbaughmanVUZ7P.rvt

REFLECTED CEILING PLAN - LEVEL 01 ADD ALT. #2

6/16/2022 1:59:47 PM C:\EYP_Temp\Revit_2020\2021060.01_Edinburg Wet Lab-add-alt_jbaughmanVUZ7P.rvt

SHEET KEY NOTES#

1. WALL MOUNTED THERMOSTAT. COORDINATE LOCATION WITH

OTHER WALL MOUNTED COMPONENTS. MOUNT THERMOSTAT AT

4'-0" AFF (TYPICAL).

2. REFRIGERANT PIPING SIZING AND CONNECTION SHALL BE AS PER

MANUFACTURER GUIDELINES (TYPICAL).

3. 1-1/4" PVC CONDENSATE DRAIN PIPING. RUN PIPING AT 1/8" SLOPE

PER FOOT.

4. 12" DIAMETER FUME HOOD EXHAUST AIR DUCTWORK UP.

5. 14"x12" GENERAL EXHAUST AIR DUCTWORK UP.

6. 16"x12" SUPPLY AIR DUCTWORK UP.

7. STRUCTURAL PLATFORM WITH GAURD RAIL AND STAIR ENTRY,

REFER TO STRUCTURAL DRAWINGS FOR DETAILS.

8. VARIABLE FREQUENCY DRIVE (VFD) SERVING GEF-1, MOUNT ON A

UNISTRUT CHANNEL.

9. 28"x12" GENERAL EXHAUST AIR DUCTWORK UP.

10. 42"x12" SUPPLY AIR DUCTWORK UP.

11. CONTRACTOR TO PROVIDE OPEN SITE DRAIN WITH BALL-FLOAT

BACKWATER VALVE AND WITH MIN 4" HIGH HUB ADAPTER. DRAIN

PIPING TO BE 2" SDR26, REFER CIVIL DRAWINGS FOR

CONTINUATION.

12. CONTRACTOR TO PROVIDE DRAIN OPENING WITH STAINLESS

STEEL INSECT AND BIRD SCREEN.

5 6 7 8

11 12 131415

MEN. RR

WOMEN RR

23ENTRY/ VESTIBULE

GROUP OFFICE

GEN. STORAGE

OFFICE

ENTRY EQM

CONF RM

CHEM STORAGE

EQM STORAGE

FUME HOOD

CORRIDOR

OPEN WET LAB

OFFICE

ELEC. RM.

ENTRY VEST.

JAN. RM.

M401

M402

"x

CU-1

OUTDOOR

AIR

VFD

"Ø G

E X

24"Ø GEX

CONCRETE

EQUIPMENT PAD

M401

M401

M401

14"x12" GEX12"x10"8"x10"

6"x10"

6"x10"

16"x12" SA 8"x10"8"x10"

28"x8" 28"x8"

28"x12" 20"x10"

10"x10"

"x

" 1

"x

6"Ø 6"Ø

8"x10"

8"x8"

"x

" 8"x8"

6"Ø6"x12"

12"x8"

6"x12" 6"Ø10"Ø6"Ø8"x10"

"Ø

6"x8"6"Ø

10"x10"

6"x6"

"x

"Ø

6"Ø

"x

"Ø

"x

12"Ø 12"Ø

"Ø

"Ø

"x

"x

"Ø

"x

"x

10"Ø

10"Ø

10"Ø 10"Ø

42"x12" SA 28"x12"

6"Ø 6"x8"

"Ø10"Ø

"Ø

"x

12"Ø

"Ø

18"x12"

"x

"x

10"Ø

10"Ø

10"Ø

"x

"x

8"x6"

8"x6"

8"x6"

28"x12"

"x

12"x10"10"x8"

"x

10"x8"

RD-2

RD-2

RHCAV-1-1

EXCAV-1-8

RHCAV-1-4

RHCAV-1-7

RHCAV-1-3RHCAV-1-2

RHCAV-1-12RHCAV-1-10

RHCAV-1-5

RHCAV-1-8

RHCAV-1-11

RHCAV-1-9

RHCAV-1-6

EXCAV-1-3

EXCAV-1-2

EXCAV-1-1

EXCAV-1-7

EXCAV-1-6

EXCAV-1-5

CD-1

CD-1

CD-4

CD-4

RD-5

RD-2

CD-2

RD-2

CD-3

CD-3

RD-3

CD-2

CD-1

RD-2

CD-1

RD-1

SG-1

SG-1

EG-1

EG-1

LFD-1

LFD-1

LFD-1

LFD-1

LFD-1

LFD-1

LFD-1

LFD-1

LFD-1

CD-4

CD-4

375CD-1

CD-1

RD-3

CD-1

100 RD-3

CD-4

CD-1

CD-4

LFD-2

LFD-2

RD-7

RD-7

M402

MECH.

T T

TTT

T

T

T T

TT

T

FUME HOOD

(FH-2)

FUME HOOD

(FH-1)

8"Ø

AHU-1

12"x10"

6"Ø

24"x12"

28"x12" GEX

12"x8"

"x

8"x12"

EXCAV-1-4

RHCAV-1-7

RHCAV-1-1

RHCAV-1-5

RHCAV-1-4

RHCAV-1-3

RHCAV-1-2

RHCAV-1-9

RHCAV-1-11

RHCAV-1-6

RHCAV-1-8

RHCAV-1-10

RHCAV-1-12

VD

VD

VD

VD

VD

VD

VD

VD

VD

VD

VD

VDVD

VD

VD

VDVDVD

VD

VD

VD

VD

VD VD

VD

VD VD

VD

VD

VD

VD

VD

VD VD

VD

VD

VD

VD

VD

VD VD

VD

VD

VD

VD

VD

VD

VDVD

LFD-1

VFD

SD

SD

MD

1 1/4"

COIL PULL

CLEARANCE

GENERAL EXHAUST

DUCTWORK UP

SUPPLY AIR

DUCTWORK UP

REFRIGERANT

PIPING

SMOKE

DETECTOR (TYP)

CONDENSATE

PIPING

16"x38" SA

34"x14" GEX

VD

28"x12"

"x

8"x8"

24"Ø GEX

24"Ø GEX

VD

VD

MD

MD

V F

D

GEX-1A

GEF-1B

ELECTRIC

HEATER PANEL

DUCT SUPPORT

(TYPICAL)

10"x12"

LFD-2

LFD-2

VD

VD

COIL PULL

CLEARANCE

"x

8"x8"

1465 NORTHSIDE DRIVE SUITE 220B

ATLANTA, GA 30318

P:706-248-7165 www. .com

TM

PROJECT NUMBER: SIGQ212911.15

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT MANAGER

PPM

EPM

SETTY

DATE

A

D

USDA S

U

DWG. NO

DRAWN BY

SOLICITATION NO. SHEET NAME

ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED

Revisions

Agricultural Research Service

6/15/2022 11:21:57 AM C:\Users\gowtham.sl\Documents\SIGQ212911.15_R20_Mechanical_gowtham.sl.rvt

WET LAB

M101

LEVEL 1 MECHANICAL PLAN

BASE BID

JM

GSL 05/06/2022

JM BD

BD

DC

GSL

NO. DATE BY DESCRIPTION

1 03/04/2022 JM 50% DOCUMENTS

2 04/20/2022 JM 90% DOCUMENTS

3 05/06/2022 JM 100% DOCUMENTS

4 05/20/2022 JM ISSUE FOR BIDDING AND CONSTRUCTION

5 06/16/2022 JM ADDENDUM 1

8' 16'4'0 1/4" = 1'-0"M101

1 LEVEL 1 MECHANICAL PLAN BASE BID

5 6 7 8

11 12 131415

26"x12" SA 18"x12"16"x12"14"x12"

OUTDOOR

AIR

VFD

CONCRETE

EQUIPMENT PAD

26"x12" GEX20"x12" 22"x12"

18"x12"

18"x12"16"x12"

RHCAV-1-1

EXCAV-1-8

RHCAV-1-4

RHCAV-1-7

RHCAV-1-3RHCAV-1-2

RHCAV-1-12RHCAV-1-10

RHCAV-1-5

RHCAV-1-8

RHCAV-1-11

RHCAV-1-9

RHCAV-1-6

EXCAV-1-3

EXCAV-1-2

EXCAV-1-1

EXCAV-1-7

EXCAV-1-6

EXCAV-1-5

RHCAV-1-14

RHCAV-1-13

EXCAV-1-9

EXCAV-1-10

M402

RD-2

RD-2

CD-1

CD-1

CD-4

CD-4

RD-5

RD-2

CD-2

RD-2

CD-3

CD-3

RD-3

CD-2

CD-1

RD-2

CD-1

RD-1

SG-1

SG-1

EG-1

EG-1

LFD-1

LFD-1

LFD-1

LFD-1

LFD-1

LFD-1

LFD-1

LFD-1

LFD-1

CD-4

CD-4

375CD-1

CD-1

RD-3

CD-1

100 RD-3

CD-4

CD-1

CD-4

RD-7

RD-7

"x

10"x10"

"x

" 1

"x

6"Ø 6"Ø

12"x8" 8"x10"

8"x8"

"x

8"x8"

6"Ø6"x12"6"x12" 6"Ø10"Ø6"Ø8"x10"

"Ø

6"x8"6"Ø

10"x10"

6"x6"

"x

28"x8" 28"x8"

28"x12" 20"x10"

"Ø

6"Ø

"x

"Ø

"x

12"Ø 12"Ø

"Ø

"Ø

"x

"x

"Ø

"x

"x

10"Ø 10"Ø

10"Ø 10"Ø

42"x12" SA 28"x12"

6"Ø 6"x8"

"Ø10"Ø

"Ø

"x

12"Ø

"Ø

18"x12"

"x

"x

10"Ø

10"Ø

10"Ø

12"x10"

"x

"x

8"x6"

8"x6"

8"x6"

28"x12"

"x

12"x10"10"x8"

"x

10"x8"

LFD-1

LFD-1

LFD-1

RD-7

"x

"x

"x

CD-3

CD-3

RD-5

"x

"x

"x

"x

"x

"Ø

8"Ø

MEN. RR

WOMEN RR

ENTRY/ VESTIBULE

GROUP OFFICE

GEN. STORAGE

OFFICE

ENTRY EQM

CONF RM

CHEM STORAGE

EQM STORAGE

FUME HOOD

CORRIDOR

OPEN WET LAB

OFFICE

ELEC. RM.

ENTRY VEST.

JAN. RM.

MECH.

FIELD LABORATORY

FIELD LAB OFFICE

T T

TTT

T

T

T

T

T T

TT

T

16"x34" GEX

38"x18" SA

8"Ø

"Ø G

E X

26"Ø GEX

AHU-1

26"Ø GEX

CU-1

LFD-1

22"x12"

18"x12"16"x12"14"x12"

10"Ø

10"Ø

RHCAV-1-7

RHCAV-1-1

RHCAV-1-5

RHCAV-1-4

RHCAV-1-3

RHCAV-1-2

RHCAV-1-9

RHCAV-1-11

RHCAV-1-6

RHCAV-1-8

RHCAV-1-10

RHCAV-1-12

R H

C A

V -1

-1

RHCAV-1-14

12"x10"

"x

VD

VD

VD

VD

VD

VD

VD

VD

VD

VD

VD

VD

VD

VD

VDVDVD

VD

VD

VD

VD

VD VD

VD

VD VD

VD

VD

VD

VD

VD

VD VD

VD

VD

VD

VD

VD

VD VD

VD

VD

VD

VD

VD

VD

VDVD

VD

VD

VD

VD

VD

VD

VD

EXCAV-1-4

SD

SD

MD

1 1/4"

GENERAL EXHAUST

DUCTWORK UP

SUPPLY AIR

DUCTWORK UP

REFRIGERANT

PIPING

SMOKE

DETECTOR (TYP)

CONDENSATE

PIPING

VD

8"x12"

28"x12" GEX

24"x12"

28"x12"

"x

10"Ø

12"x8"

M402

8"x8"

VFD

V F

D

GEX-1A

GEF-1B

VD

VD

MD

MD

COIL PULL

CLEARANCE

ELECTRIC

HEATER PANEL

DUCT SUPPORT

(TYPICAL)

LFD-2

LFD-2

LFD-2

LFD-2

VD

VD

10"x12"

FUME HOOD

(FH-2)

FUME HOOD

(FH-1)

COIL PULL

CLEARANCE

24"x12"

8"x8"

1. WALL MOUNTED THERMOSTAT. COORDINATE LOCATION WITH

OTHER WALL MOUNTED COMPONENTS. MOUNT THERMOSTAT AT

4'-0" AFF (TYPICAL).

2. REFRIGERANT PIPING SIZING AND CONNECTION SHALL BE AS PER

MANUFACTURER GUIDELINES (TYPICAL).

3. 1-1/4" PVC CONDENSATE DRAIN PIPING. RUN PIPING AT 1/8" SLOPE

PER FOOT.

4. 12" DIAMETER FUME HOOD EXHAUST AIR DUCTWORK UP.

5. 26"x12" GENERAL EXHAUST AIR DUCTWORK UP.

6. 26"x12" SUPPLY AIR DUCTWORK UP.

7. STRUCTURAL PLATFORM WITH GAURD RAIL AND STAIR ENTRY,

REFER TO STRUCTURAL DRAWINGS FOR DETAILS.

8. VARIABLE FREQUENCY DRIVE (VFD) SERVING GEF-1, MOUNT ON A

UNISTRUT CHANNEL.

9. 28"x12" GENERAL EXHAUST AIR DUCTWORK UP.

10. 42"x12" SUPPLY AIR DUCTWORK UP.

11. CONTRACTOR TO PROVIDE OPEN SITE DRAIN WITH BALL-FLOAT

BACKWATER VALVE AND WITH MIN 4" HIGH HUB ADAPTER. DRAIN

PIPING TO BE 2" SDR26, REFER CIVIL DRAWINGS FOR

CONTINUATION.

12. CONTRACTOR TO PROVIDE DRAIN OPENING WITH STAINLESS

STEEL INSECT AND BIRD SCREEN.

1465 NORTHSIDE DRIVE SUITE 220B

ATLANTA, GA 30318

P:706-248-7165 www. .com

TM

PROJECT NUMBER: SIGQ212911.15

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT MANAGER

PPM

EPM

SETTY

DATE

A

D

USDA S

U

DWG. NO

DRAWN BY

SOLICITATION NO. SHEET NAME

ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED

Revisions

Agricultural Research Service

6/15/2022 11:22:00 AM C:\Users\gowtham.sl\Documents\SIGQ212911.15_R20_Mechanical_gowtham.sl.rvt

WET LAB

M101.1

LEVEL 1 MECHANICAL PLAN

ADD ALT. #1

JM

GSL 05/06/2022

JM BD

BD

DC

GSL

NO. DATE BY DESCRIPTION

1 03/04/2022 JM 50% DOCUMENTS

2 04/20/2022 JM 90% DOCUMENTS

3 05/06/2022 JM 100% DOCUMENTS

4 05/20/2022 JM ISSUE FOR BIDDING AND CONSTRUCTION

5 06/16/2022 JM ADDENDUM 1

8' 16'4'0 1/4" = 1'-0"M101.1

1 LEVEL 1 MECHANICAL PLAN ADD ALT. #1

11 12 131415

30"x12" SA24"x12"20"x12"

30"x12" GEX

42"x12" SA

28"x12" GEX

28"x12"

CU-1

OUTDOOR

AIR

VFD

GENERAL EXHAUST

DUCTWORK UP

SUPPLY AIR

DUCTWORK UP

CONCRETE

EQUIPMENT PAD

RHCAV-1-1

RHCAV-1-7

RHCAV-1-4

RHCAV-1-3RHCAV-1-2

RHCAV-1-13

RHCAV-1-14

RHCAV-1-12

RHCAV-1-5

RHCAV-1-10

RHCAV-1-8

RHCAV-1-11

RHCAV-1-9

RHCAV-1-6

EXCAV-1-8

EXCAV-1-3

EXCAV-1-2

EXCAV-1-1

EXCAV-19

EXCAV-10

EXCAV-1-7

EXCAV-1-6

EXCAV-1-5

M402

"x

6"Ø 6"Ø

"x

"x

6"Ø6"x12"6"x12"

8"x10"

8"x8"

8"x8"

26"x12"24"x12"

22"x12"

22"x12"20"x12"20"x12"

"x

12"x12"

"x

"x

10"Ø

10"Ø

"x

"10"Ø

14"x12"

8"Ø12"x12"

"Ø

10"Ø

10"Ø

6"Ø10"Ø

"x

12"x8"

6"Ø8"x10"

"Ø

6"x8"6"Ø

10"x10"

"x

6"x6"

6"Ø

"Ø

"x

"Ø

"Ø

"x

"x

8"x6"

"x

12"Ø 12"Ø

"Ø

"Ø

"x

10"Ø

10"Ø 10"Ø

10"Ø1

"x

6"Ø 6"x8"

"Ø

"x

"x

"10"Ø

10"Ø

10"Ø

"Ø

"x

12"Ø

"Ø

12"Ø

10"Ø18"x12"

12"x10"

"x

"x

8"x6"

"x

28"x12" 20"x10"

28"x8"28"x8"

"x

12"x10"10"x8"

"x

8"x8"

RD-2

RD-2

CD-1

CD-1

MEN. RR

WOMEN RR

ENTRY/ VESTIBULE

GROUP OFFICE

FIELD LAB OFFICE

GEN. STORAGE

OFFICE

ENTRY EQM

CONF RM

CHEM STORAGE

31EQM STORAGE

FUME HOOD

CORRIDOR

OPEN WET LAB

OFFICE

FIELD LABORATORY

ELEC. RM.

ENTRY VEST.

JAN. RM.

MECH.

RD-2

CD-2

RD-2

CD-3

RD-3

CD-3

CD-2

CD-1

RD-2

CD-1

R D

-1

CD-3

CD-3

RD-5

CD-3

LFD-1

LFD-1

LFD-1

LFD-1

LFD-1

RD-7

CD-4

CD-4

RD-5

CD-4

375CD-1

CD-4

CD-4

CD-1

CD-4

SG-1

EG-1

EG-1

SG-1

LFD-1

LFD-1

LFD-1

LFD-1

LFD-1

LFD-1

LFD-1

LFD-1

LFD-1

RD-3

CD-1

CD-1

100 RD-3

RD-7

RD-7

T T

TTT

T

T

T

T

T T

TT

T

16"x38" GEX

40"x18" SA

8"Ø

"Ø G

E X

28"Ø GEX

AHU-1

28"Ø GEX

LFD-1

26"x12"

"x

22"x12" 22"x12" 24"x12"

10"Ø

"x

20"x12"

24"x12"

RHCAV-1-7

RHCAV-1-1

RHCAV-1-5

RHCAV-1-4

RHCAV-1-3

R H

C A

V -1

-2

RHCAV-1-9

RHCAV-1-11

RHCAV-1-6

RHCAV-1-8

RHCAV-1-10

RHCAV-1-12

R H

C A

V -1

-1

RHCAV-1-14

FD

VD

VD

VD

VD

VD

VD

VD

VD

VD

VD

VD

VDVD

VD

VD

VDVDVD

VD

VD

VD

VD

VD VD

VD

VD VD

VD

VD

VD

VD

VD

VD VD

VD

VD

VD

VD

VD

VD VD

VD

VD

VD

VD

VD

VD

VDVD

VD

VD

VD

VD

VD

VD

VD

VD

VD

VD

EXCAV-1-4

12"x8"

SD

SD

MD

1 1/4"

REFRIGERANT

PIPING

SMOKE

DETECTOR (TYP)

CONDENSATE

PIPING

VD

8"x12"

M402

8"x8"

28"Ø GEX

VFD

V F

D

GEX-1A

GEF-1B

VD

VD

MD

MD

COIL PULL

CLEARANCE

ELECTRIC

HEATER PANEL

DUCT SUPPORT

(TYPICAL)

LFD-2

LFD-2

LFD-2

LFD-2

FUME HOOD

(FH-2)

FUME HOOD

(FH-1)

COIL PULL

CLEARANCE

24"x12"

VD

VD

1. WALL MOUNTED THERMOSTAT. COORDINATE LOCATION WITH

OTHER WALL MOUNTED COMPONENTS. MOUNT THERMOSTAT AT

4'-0" AFF (TYPICAL).

2. REFRIGERANT PIPING SIZING AND CONNECTION SHALL BE AS PER

MANUFACTURER GUIDELINES (TYPICAL).

3. 1-1/4" PVC CONDENSATE DRAIN PIPING. RUN PIPING AT 1/8" SLOPE

PER FOOT.

4. 12" DIAMETER FUME HOOD EXHAUST AIR DUCTWORK UP.

5. 30"x12" GENERAL EXHAUST AIR DUCTWORK UP.

6. 30"x12" SUPPLY AIR DUCTWORK UP.

7. STRUCTURAL PLATFORM WITH GAURD RAIL AND STAIR ENTRY,

REFER TO STRUCTURAL DRAWINGS FOR DETAILS.

8. VARIABLE FREQUENCY DRIVE (VFD) SERVING GEF-1, MOUNT ON A

UNISTRUT CHANNEL.

9. 28"x12" GENERAL EXHAUST AIR DUCTWORK UP.

10. 42"x12" SUPPLY AIR DUCTWORK UP.

11. CONTRACTOR TO PROVIDE OPEN SITE DRAIN WITH BALL-FLOAT

BACKWATER VALVE AND WITH MIN 4" HIGH HUB ADAPTER. DRAIN

PIPING TO BE 2" SDR26, REFER CIVIL DRAWINGS FOR

CONTINUATION.

12. CONTRACTOR TO PROVIDE DRAIN OPENING WITH STAINLESS

STEEL INSECT AND BIRD SCREEN.

1465 NORTHSIDE DRIVE SUITE 220B

ATLANTA, GA 30318

P:706-248-7165 www. .com

TM

PROJECT NUMBER: SIGQ212911.15

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT MANAGER

PPM

EPM

SETTY

DATE

A

D

USDA S

U

DWG. NO

DRAWN BY

SOLICITATION NO. SHEET NAME

ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED

Revisions

Agricultural Research Service

6/15/2022 11:22:03 AM C:\Users\gowtham.sl\Documents\SIGQ212911.15_R20_Mechanical_gowtham.sl.rvt

WET LAB

M101.2

LEVEL 1 MECHANICAL PLAN

ADD ALT. #2

JM

GSL 05/06/2022

JM BD

BD

DC

GSL

NO. DATE BY DESCRIPTION

1 03/04/2022 JM 50% DOCUMENTS

2 04/20/2022 JM 90% DOCUMENTS

3 05/06/2022 JM 100% DOCUMENTS

4 05/20/2022 JM ISSUE FOR BIDDING AND CONSTRUCTION

5 06/16/2022 JM ADDENDUM 1

8' 16'4'0 1/4" = 1'-0"M101.2

1 LEVEL 1 MECHANICAL PLAN ADD ALT. #2

DS

(NOTE : ALL ABBREVIATIONS MAY NOT APPEAR ON THE DRAWINGS)

LIGHT FIXTURE SUBSCRIPT DETAIL:

a HP-2

EM A

LIGHT FIXTURES MAY BE INDICATED WITH THE FOLLOWING SUBSCRIPTS:

EM : LIGHT FIXTURE ON EMERGENCY CIRCUIT

A : UPPER CASE SUBSCRIPT INDICATES LIGHT FIXTURE IDENTIFICATION TAG

a : LOWER CASE SUBSCRIPT INDICATES LIGHTING ZONE IDENTIFICATION

HP-2 : PANEL NAME AND CIRCUIT NUMBER SERVING LIGHT FIXTURE

S

PANEL-XX

AA

F

S

EL

S

D

15cd

AV 15cdAV

15cd

V 15cdV

FACP

J J J

M

MS

a

K

MS

VS VS

T a

CR

TV

F

MWIRE SIZE

(AWG TYP.)

LENGTH (FEET) VOLTAGE (V)

1200-66

0-102 120

20 #12

20 #10

AMPACITY (A)

WALL MOUNTED FIRE ALARM SYSTEM MANUAL PULL STATION

AT 48" AFF

CEILING/WALL MOUNTED FIRE ALARM SMOKE DETECTOR,

DEVICES MAY HAVE THE FOLLOWING SUBSCRIPTS:

EL

: DEVICE DEDICATED FOR ELEVATOR RECALL

FUNCTION

FIRE ALARM DUCT SMOKE DETECTOR

CEILING/WALL MOUNTED FIRE ALARM COMBINATION AUDIO (USDA

SPEAKER )/VISUAL DEVICE, ADA COMPLIANT NUMBER

MOUNTING HEIGHT FROM 80" UP TO A MAXIMUM OF 96" AFF

CEILING/WALL MOUNTED FIRE ALARM VISUAL DEVICE (STROBE),

ADA COMPLIANT NUMBER DENOTES CANDELA INTENSITY RATING,

TO A MAXIMUM

CEILING/WALL MOUNTED FIRE ALARM AUDIO ( HORN )

DEVICE, MOUNTING HEIGHT NOT LESS THAN 90" AFF AND 6"

FIRE ALARM CONTROL PANEL

FIRE ALARM SYMBOL LIST

A AMPERE

ADA AMERICANS WITH DISABILITIES ACT

AFF ABOVE FINISHED FLOOR

AL ALUMINUM

AWG AMERICAN WIRE GAUGE

C CONDUIT

CB CIRCUIT BREAKER

CU COPPER

D EXISTING TO BE DEMOLISHED

DISC. SW. DISCONNECT SWITCH

DWG DRAWING

E, EX EXISTING TO REMAIN

EM DEVICE ON EMERGENCY CIRCUIT

EMT ELECTRICAL METALLIC TUBING

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FATC FIRE ALARM TERMINAL CABINET

FASP FIRE ALARM SMOKE PURGE PANEL

FLA FULL LOAD AMPS

G GROUND

GFI GROUND FAULT INTERRUPTER

GRS GALVANIZED RESISTIVE CONDUIT

HP HORSE POWER

IG ISOLATED GROUND

KVA KILOVOLT-AMPS

KW KILOWATT

MCB MAIN CIRCUIT BREAKER

MLO MAIN LUGS ONLY

MDP MAIN DISTRIBUTION PANEL

N NEW

NEC NATIONAL ELECTRICAL CODE

NFSS NON FUSED SAFETY SWITCH

NL NIGHT LIGHT FIXTURE

NTS NOT TO SCALE

P POLE

PH, ∅ PHASE

PNL PANEL

R RELOCATED AT NEW LOCATION

RR REMOVE AND RELOCATE

S/N SOLID NEUTRAL

SWBD SWITCHBOARD

T, XFMR TRANSFORMER

TYP. TYPICAL

UON UNLESS OTHERWISE NOTED

V VOLTS

W WATTS

WP WEATHERPROOF

T

(NOTE : ALL ABBREVIATIONS MAY NOT APPEAR ON

THE DRAWINGS)

SUBSCRIPTS

RECEPTACLE OUTLETS AND JUNCTION BOX DEVICES MAY BE INDICATED

WITH THE FOLLOWING SUBSCRIPTS:

EM : RECEPTACLE ON EMERGENCY POWER

GFI : GROUND FAULT INTERRUPTER

WP : WEATHER PROOF OUTLET WITH PROTECTIVE IN-USE COVER

MD : MOTORIZED DAMPER

EM

PT

PT

120V BRANCH CIRCUIT WIRING CONDUCTOR SIZE

DEPENDING ON BRANCH CIRCUIT RUN LENGTH FROM PANELBOARD TO THE LAST DEVICE ON THE

BRANCH CIRCUIT, THE CONTRACTOR SHALL INCREASE THE BRANCH CIRCUIT WIRE SIZE AS PER THE

TABLE BELOW.

MAXIMUM #10 WIRE SHALL BE USED FOR GENERAL RECEPTACLE CIRCUIT WIRING.

BELOW FINISHED CEILING

MINIMUM 15cd, MOUNTING HEIGHT FROM 80" UP

OF 96" AFF

DENOTES CANDELA INTENSITY RATING, MINIMUM 15cd, EXIT SIGN LIGHTING FIXTURES ON EMERGENCY LIGHTING CIRCUIT

TYPICAL INTERIOR LIGHTING FIXTURES

TYPICAL INTERIOR LIGHTING FIXTURES ON EMERGENCY LIGHTING

CIRCUIT, FIXTURES MAY HAVE THE FOLLOWING SUBSCRIPTS:

EM : EMERGENCY

NL : NIGHT LIGHT

WALL-MOUNTED DUPLEX OR QUAD RECEPTACLE, 20A, 125V,

NEMA 5-20R

# : INDICATES THE TOTAL NUMBER OF RECEPTACLE.

USB: USB CHARGER

WALL/FLOOR MOUNTED SPECIAL PURPOSE OUTLET.

COORDINATE NEMA CONFIGURATION WITH EQUIPMENT VENDOR

WALL-MOUNTED ISOLATED GROUND DUPLEX OR QUAD

RECEPTACLE (ORANGE COLOR) 20A, 125V, NEMA 5-20R

WALL-MOUNTED ABOVE COUNTER DUPLEX OR QUAD

RECEPTACLE, 20A, 125V, NEMA 5-20R

FLUSH FLOOR MOUNTED ADA COMPLIANT DUPLEX /

QUADRUPLEX NEMA 5-20R RECEPTACLE, 20A, 125V OUTLET,

COORDINATE FINISH SPECIFICATION AND EXACT LOCATION WITH

ARCHITECT, OUTLETS MAY HAVE THE FOLLOWING SUBSCRIPTS:

PT : POKE-THRU

FB : FLOOR BOX

FLUSH MOUNTED ADA COMPLIANT COMBINATION

DUPLEX/QUADRUPLEX POWER AND TELE-DATA-AV OUTLET.

REFER TO TECHNOLOGY PATHWAY DRAWINGS FOR TELE-DATA-AV

OUTLET REQUIREMENTS. COORDINATE FINISH, SPECIFICATION

AND EXACT LOCATION WITH ARCHITECT AND COMMUNICATION

VENDOR, OUTLETS MAY HAVE THE FOLLOWING

SUBSCRIPTS:

PT : POKE-THRU

FB : FLOOR BOX

RECESSED CEILING MOUNTED DUPLEX OR QUADRUPLEX NEMA

5-20R RECEPTACLE, 20A, 125V

WALL-MOUNTED DUPLEX OR QUADRUPLEX TAMPER PROOF

RECEPTACLE, 20A, 125V, NEMA 5-20R

WALL/FLOOR/CEILING MOUNTED COMBINATION

TELEPHONE/DATA OUTLET, OUTLETS MAY HAVE THE FOLLOWING

SUBSCRIPTS:

F : TWO WAY COMMUNICATION CALL STATION

WALL MOUNTED TELEPHONE OUTLET

WALL/FLOOR/CEILING MOUNTED DATA OUTLET

LOW VOLTAGE SINGLE POLE TOGGLE SWITCH, SWITCHES MAY

HAVE THE FOLLOWING SUBSCRIPTS:

a : LOWER CASE SUBSCRIPT INDICATES LIGHTING ZONE

IDENTIFICATION

LOW VOLTAGE 3 - WAY SWITCH

DIMMER SWITCH RATED FOR 2000 WATTS, PROVIDE NECESSARY

MODULES FOR LED LAMP SOURCE

LOW VOLTAGE KEY OPERATED SWITCH

LOW VOLTAGE TIMER SWITCH WITH HOLD-ON OPTION

MOTOR RATED SWITCH WITH THERMAL OVERLOAD CURRENT

PROTECTION, MOUNTED @ 48" AFF OR UNIT MOUNTED

LOW VOLTAGE SINGLE POLE SWITCH

LOW VOLTAGE 2 BUTTON SWITCH WITH RAISE-LOWER.

LOW VOLTAGE 3 BUTTON SWITCH WITH RAISE-LOWER.

WALL/CEILING MOUNTED LOW VOLTAGE OCCUPANCY SENSOR

SWITCH CONFIGURED AS AUTO-ON, AUTO OFF, CONFIGURE TIME-

OUT SETTING FOR 15 MINUTES UNLESS OTHERWISE

NOTED, DEVICES MAY HAVE THE FOLLOWING SUBSCRIPTS:

2 : DUAL SWITCH

D : DIMMER SWITCH

a,b : LIGHTING ZONE(S) CONTROLLED BY SENSOR

WALL/CEILING MOUNTED LOW VOLTAGE VACANCY SENSOR

SWITCH CONFIGURED AS MANUAL ON, AUTO OFF, CONFIGURE

TIME-OUT SETTING FOR 15 MINUTES UNLESS

OTHERWISE NOTED, DEVICES MAY HAVE THE FOLLOWING

SUBSCRIPTS:

2 : DUAL SWITCH

D : DIMMER SWITCH

a,b : LIGHTING ZONE(S) CONTROLLED BY SENSOR

LOW VOLTAGE CEILING MOUNTED DAYLIGHT SENSOR, DEVICES

MAY HAVE THE FOLLOWING SUBSCRIPTS:

a : LOWER CASE SUBSCRIPT INDICATES LIGHTING ZONE

IDENTIFICATION

WALL/CEILING/FLOOR MOUNTED JUNCTION BOX

NON-FUSIBLE DISCONNECT SWITCH

FUSIBLE DISCONNECT SWITCH

COMBINATION STARTER DISCONNECT SWITCH

MOTOR

DRY TYPE TRANSFORMER

120/208V ELECTRICAL PANEL

480/277V ELECTRICAL PANEL

CIRCUIT NUMBER DESIGNATION FEEDING ELECTRICAL DEVICES,

FIXTURES AND EQUIPMENT.

PANEL : INDICATES THE PANEL NAME

XX : INDICATES THE CIRCUIT NUMBER

KEYED DRAWING NOTE

WALL MOUNTED TV OUTLET

WALL MOUNTED CARD READER

CONDUIT UP

CONDUIT DOWN

CONTINUATION CIRCUIT

1. REFER TO THE LIGHTING FIXTURE SCHEDULE ON DRAWING E601 FOR LIGHTING

FIXTURE SPECIFICATIONS.

2. REFER TO DETAIL ON DRAWING E701 FOR TYPICAL DEVICE MOUNTING HEIGHTS.

1. INSTALLATION OF ALL WORK SHALL BE IN ACCORDANCE WITH THE FOLLOWING REGULATIONS, CODES, ETC.

A. LOCAL CODES AND ORDINANCES

B. THE EDITION OF THE NATIONAL ELECTRICAL CODE (NEC 2014), NFPA 72 AND 72D, IN EFFECT.

2. CONTRACTOR TO PROVIDE SUFFICIENT NOTICE TO THE OWNER'S REPRESENTATIVE PRIOR TO ANY WORK TO ALLOW

ADEQUATE TIME FOR COORDINATION OF EXISTING BUILDING ACTIVITIES WITH THE CONSTRUCTION WORK.

3. CONTRACTOR TO INCLUDE IN THEIR SCOPE ALL LABOR, MATERIALS, SERVICES, APPARATUS AND SHOP DRAWINGS IN

ADDITION TO THE CONTRACT DOCUMENTS AS REQUIRED TO COMPLY WITH ALL APPLICABLE GOVERNING LAWS, CODES

AND JURISDICTION REQUIREMENTS. PROVIDE ELECTRICAL EQUIPMENT WITH ALL ASSOCIATED ACCESSORIES, BRANCH

CIRCUIT WIRING AND CONDUIT INFRASTRUCTURE AS REQUIRED TO ENSURE A COMPLETE AND OPERATIONAL SYSTEM.

4. ALL MATERIALS AND WORK SHALL BE ACCORDING TO PROJECT SPECIFICATIONS.

5. IF MATERIAL OR EQUIPMENT IS INSTALLED BEFORE IT IS APPROVED, THE CONTRACTOR SHALL BE LIABLE FOR ITS

REMOVAL AND REPLACEMENT AT NO ADDITIONAL CHARGE IF IN THE OPINION OF THE ARCHITECT OR ENGINEER, THE

MATERIAL OR EQUIPMENT DOES NOT MEET THE INTENT OF THE DRAWINGS AND/OR SPECIFICATIONS.

6. REFER TO ARCHITECTURAL DRAWINGS AND LAB DRAWINGS(Q-SERIES) FOR THE EXACT LOCATION, ELEVATION, MOUNTING HEIGHTS AND DETAILS OF ALL LIGHT FIXTURES AND DEVICES. REPORT ANY DISCREPANCIES TO THE

ARCHITECT IMMEDIATELY.

7. ALL NEW SLAB PENETRATIONS MUST BE X-RAYED OR RADAR PRIOR TO CORE DRILLING. OBTAIN APPROVAL FROM

OWNER'S REPRESENTATIVE PRIOR TO ANY CORE DRILLING.

8. CONTRACTOR TO PROVIDE ALL LIGHT FIXTURE AND EQUIPMENT WITH INTEGRAL OR REMOTE MOUNTED ACCESSORY

DEVICES WITH ALL NECESSARY COMPONENTS, BRANCH CIRCUIT WIRING AND CONDUITS TO ENSURE A COMPLETE AND

OPERATIONAL SYSTEM. CONTRACTOR TO MAKE ALL FINAL CONNECTIONS TO THE EQUIPMENT.

9. ELECTRICAL SYSTEMS SHALL BE GROUNDED PER ARTICLE 250 OF THE NATIONAL ELECTRICAL CODE.

10. PROVIDE AN INSULATED EQUIPMENT GROUNDING CONDUCTOR IN ALL BRANCH CIRCUITS AND FEEDERS INSTALLED IN

RACEWAYS. THE DEDICATED EQUIPMENT GROUNDING CONDUCTOR SHALL BE SIZED PER NEC SECTION 250.122. SOLE

USE OF METAL RACEWAY AS A GROUNDING CONDUCTOR SHALL NOT BE ACCEPTABLE. WIRING METHODS SHALL BE IN

ACCORDANCE WITH NEC SECTION 518.4 FOR ALL ASSEMBLY AREAS.

11. PROVIDE RED COLOR LOCKABLE TYPE BREAKERS FOR CIRCUITS SERVING LIFE SAFETY PANEL BOARDS.

12. NUMBER OF WIRES MAY NOT BE INDICATED FOR ALL CIRCUITS, ONLY THOSE WHERE CLARIFICATION IS NECESSARY.

PROVIDE THE NUMBER AND SIZE AS NECESSARY FOR THE PROPER FUNCTION OF THE SYSTEM WHETHER SPECIFICALLY

INDICATED ON PLAN OR NOT.

13. ALL BACK BOXES INSTALLED IN PARTITION WALLS SHALL BE STAGGERED. BACK-TO-BACK INSTALLATION IS NOT

PERMITTED.

14. PROVIDE ACCESS PANELS FOR ALL INACCESSIBLE JUNCTION BOXES AS REQUIRED BY THE N.E.C.

15. PROVIDE PLASTER RING WITH PULL STRING TO SPACE ABOVE SUSPENDED CEILING FOR ALL TELEPHONE, DATA, FAX, MODEM, CATV, CARD READER, ETC. OUTLETS INSTALLED IN HOLLOW PARTITIONS. PROVIDE 3/4" EMPTY CONDUIT AND

PULL STRING TO SPACE ABOVE SUSPENDED CEILING FOR THESE OUTLETS INSTALLED IN AN INSULATED PARTITION.

PROVIDE 1" EMPTY CONDUIT WITH PULL STRINGS FOR DATA/TEL OUTLETS.

16. CONTRACTOR TO TEST AND VERIFY THE CAPACITY OF THE EXISTING FIRE ALARM SYSTEM SERVING BUILDING PRIOR TO

STARTING ANY ASSOCIATED WORK. REPORT IN WRITING, THE TEST RESULTS INCLUDING ANY DEFICIENCIES IDENTIFIED

WITHIN THE EXISTING SYSTEM. SUBMIT ASSOCIATED COSTS FOR OWNERS APPROVAL TO REPLACE AND/OR PROVIDE

ADDITIONAL EQUIPMENT AND COMPONENTS AS REQUIRED TO ENSURE A COMPLETE AND OPERATIONAL SYSTEM.

17. PROVIDE FIRE ALARM INTERFACE HARDWARE, MODULES AND WIRING TO ALL ELECTRICALLY SECURED DOORS.

COORDINATE WITH BUILDING SECURITY SYSTEM.

18. FOR ALL ELEVATOR SYSTEMS,

A. PROVIDE A DEDICATED 125 VOLT, 20 AMPERE SINGLE-PHASE BRANCH CIRCUIT, WITH A FUSED DISCONNECT

SWITCH CAPABLE OF BEING LOCKED IN THE OPEN POSITION FOR THE CAR LIGHTS AND VENTILATION IN EACH

CAR.

B. ALL 125 VOLT, 15 OR 20 AMPERE SINGLE-PHASE RECEPTACLES INSTALLED IN PITS, MACHINE SPACES, CONTROL

ROOMS SHALL BE OF THE GROUND-FAULT CIRCUIT-INTERRUPTER TYPE (GFCI).

19. ELECTRICAL CONTRACTOR TO COORDINATE WITH MECHANICAL, PLUMBING AND OTHER TRADES TO PROVIDE ALL

EQUIPMENT ASSOCIATED WITH THEIR RESPECTIVE TRADES WITH NECESSARY WIRING AND CONDUIT INFRASTRUCTURE

FOR ALL SENSORS, AND CONTROL SYSTEMS AS REQUIRED.

20. CONTRACTOR TO PROVIDE DEDICATED CIRCUIT FOR CONNECTION TO EACH MECHANICAL EQUIPMENT CONTROL PANEL AS

REQUIRED. COORDINATE EXACT LOCATION AND CONNECTION REQUIREMENTS WITH MECHANICAL AND CONTROLS

CONTRACTORS.

21. CONTRACTOR TO COORDINATE ELECTRICAL WORK TO AVOID INTERFERENCE BETWEEN ALL TRADES.

A. DETERMINE INTERFERENCE BEFORE WORK IS FABRICATED OR INSTALLED. THE CONTRACTOR SHALL BE

THOROUGHLY FAMILIAR WITH ALL DETAILS OF WORK AND WORKING CONDITIONS AND COORDINATE WORK

DURING PRELIMINARY STAGES TO ENSURE ACTUAL ERECTION WILL PROCEED WITHOUT INTERFERENCE.

COORDINATION IS OF PARAMOUNT IMPORTANCE AND REQUESTS FOR ADDITIONAL PAYMENT WILL BE

CONSIDERED WHERE REQUEST IS BASED ON INTERFERENCE.

B. WHERE JOB CONDITIONS REQUIRE REASONABLE DEVIATIONS FROM CONTRACT DOCUMENTS, MAKE

DEVIATIONS WITHOUT ADDITIONAL COST TO OWNER, AFTER OBTAINING APPROVAL OF ARCHITECT.

C. PROVIDE MAXIMUM PRACTICAL SPACE FOR OPERATION, REPAIR, REMOVAL, AND TESTING OF ELECTRICAL

EQUIPMENT. DEVIATIONS MAY BE MADE TO PROVIDE REQUIRED ACCESSIBILITY PROVIDED THEY ARE APPROVED BY

THE OWNERS OR THE ARCHITECTS.

D. KEEP CONDUITS, WIRE WAYS AND SIMILAR ITEMS AS CLOSE AS POSSIBLE TO CEILING, WALLS AND COLUMNS IN

ORDER TO TAKE UP MINIMUM AMOUNT OF SPACE. ALL WORK TO BE IN STALLED IN A NEAT AND WORK MAN LIKE

MANNER.

E. PROVIDE OFFSETS, FITTINGS AND SIMILAR ITEMS NECESSARY TO ACCOMPLISH REQUIREMENTS OF

COORDINATION WITHOUT ADDITIONAL EXPENSE TO OWNER.

F. PROVIDE ACCESS TO AND CLEARANCES AROUND ELECTRICAL EQUIPMENT AS REQUIRED BY THE N.E.C.

22. ELECTRICAL CONTRACTOR SHALL FOLLOW THE STANDARD OPERATING PROCEDURE FOR CLEANING AND DISINFESTATION

OF MACHINERY IMPACTED BY THE SOIL REFER TO THE USDA STANDARD OPERATING PROCEDURE, CLEANING AND

DISINFESTING EQUIPMENT AT THE CATTLE FEVER TICK RESEARCH LABORATORY IN MISSION, TEXAS. USDA EMPLOYEES AT

THE EDINBURG LOCATION WILL PROVIDE CLEANING AND DISINFECTION OF MACHINERY. CONTRACTOR TO PROVIDE 24

HOURS NOTICE OF CLEANING EQUIPMENT. FOR MORE INFORMATION. COORDINATE WITH CONTRACTING OFFICER AS

NEEDED.

VIF VERIFY IN FIELD

(STANDARD SYMBOLS ONLY, ALL SYMBOLS MAY NOT BE APPLICABLE TO THIS PROJECT)

LV

L2

L3

FS SPRINKLER FLOW SWITCH

TS TAMPER SWITCH

1465 NORTHSIDE DRIVE SUITE 220B

ATLANTA, GA 30318

P:706-248-7165 www. .com

TM

PROJECT NUMBER: SIGQ212911.15

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT MANAGER

PPM

EPM

SETTY

DATE

A

D

USDA S

U

DWG. NO

DRAWN BY

SOLICITATION NO. SHEET NAME

ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED

Revisions

Agricultural Research Service

6/15/2022 4:36:41 PM C:\Users\Nicholas.Carlis\Documents\SIGQ212911.15_R20_Electrical_nicholas.carlisYDXF8.rvt

WET LAB

E001

GENERAL NOTES,

SYMBOLS, &

ABBREVIATIONS

CDC

NC 06/16/2022

JM BD

DC

LB

EO

NO. DATE BY DESCRIPTION

1 03/04/2022 JM 50% DOCUMENTS

2 04/20/2022 JM 90% DOCUMENTS

3 05/06/2022 JM 100% DOCUMENTS

4 05/20/2022 JM ISSUE FOR BIDDING AND CONSTRUCTION

5 06/16/2022 JM ADDENDUM 1

GENERAL NOTES ELECTRICAL SYMBOL LIST ABBREVIATIONS

DRAWING LIST

SHEET DRAWING TITLE

01 E001 GENERAL NOTES, SYMBOLS, & ABBREVIATIONS

02 E101 LEVEL 1 ELECTRICAL LIGHTING BASE BID

03 E101.1 LEVEL 1 ELECTRICAL LIGHTING ADD ALT. #1

04 E101.2 LEVEL 1 ELECTRICAL LIGHTING ADD ALT. #2

06 E201 LEVEL 1 ELECTRICAL POWER BASE BID

07 E201.1 LEVEL 1 ELECTRICAL POWER ADD ALT. #1

08 E201.2 LEVEL 1 ELECTRICAL POWER ADD ALT. #2

05 E202 ROOF ELECTRICAL POWER PLAN

09 E301 LEVEL 1 FIRE ALARM BASE BID

10 E301.1 LEVEL 1 FIRE ALARM ADD ALT. #1

11 E301.2 LEVEL 1 FIRE ALARM ADD ALT. #2

12 E501 ELECTRICAL RISER DIAGRAMS

13 E503 FIRE ALARM ANNUNCIATOR PANEL

14 E601 ELECTRICAL SCHEDULES

15 E602 ELECTRICAL SCHEDULES

16 E701 ELECTRICAL DETAILS

BD

G

FI

GFI GFI

GFI GFI

G

FI

GFIGFI GFI GFI GFI

TV

G

FI

G

FI

FACP

J

J

J

J J

J

J

J

J

J

J

J

J

GFI GFI

GFI

F A

A P

J

J

GENERAL NOTES

SHEET KEY NOTES#

5 6 7 8

11 12 131415

MEN. RR

WOMEN RR

23ENTRY/ VESTIBULE

GROUP OFFICE

GEN. STORAGE

OFFICE

ENTRY EQM

CONF RM

CHEM STORAGE

EQM STORAGE

FUME HOOD

CORRIDOR

OPEN WET LAB

OFFICE

ELEC. RM.

ENTRY VEST.

JAN. RM.

2 2 2 2 2

1 1

PANEL "RW"

MECH.

DWH-1

EXCAV-1-1

RHCAV-1-9

RHCAV-1-11

RHCAV-1-8

RHCAV-1-6

EXCAV-1-5

RHCAV-1-5

EXCAV-1-4

EXCAV-1-6

RHCAV-1-10

EXCAV-1-7

RHCAV-1-12

RHCAV-1-7

RHCAV-1-1

EXCAV-1-8

RHCAV-1-4

EXCAV-1-3

EXCAV-1-2

RHCAV-1-3

RHCAV-1-2

CU-1

AHU-1

GEF-1

RW-8

RW-8

RW-8

RW-8

RW-10

RW-10 RW-10

RW-12

RW-12

RW-12

RW-14

RW-14

RW-14RW-14

RW-16

RW-16

RW-16

RW-18

RW-18

RW-18

RW-18

RW-20RW-20RW-20

RW-20RW-22

RW-22

RW-22

RW-24

RW-24

RW-24

RW-26

RW-26

RW-26

RW-28

RW-28RW-28

RW-30

RW-30RW-30

RW-32

RW-32

RW-32

RW-34

RW-34

RW-34

RW-36

RW-36

RW-36 RW-38 RW-38 RW-38 RW-40

RW-40

RW-40

RW-42

RW-42RW-42RW-42

RW-31

RW-31

RW-31

RW-31

RW-33

RW-33

RW-33

RW-33

PW-8

ROS-1

PP-1

RW-7

RW-9

PW-13,15,17

PW-43,45,47

PW-19,21,23

PW-19,21,23

PW-19,21,23

PW-25,27,29

PW-25,27,29

PW-31,33,35

PW-37,39,41

PW-20,22,24

PW-26,28,30

PW-32,34,36

PW-38,40,42

PW-37,39,41

PW-14,16,18

PW-7,9,11 PW-1,3,5 RW-1

RW-5

WP WP

WP

RW-37 RW-37

RW-37

WS-1

RW-11

RW-11

RW-15

RW-15

PANEL "PW"(S1)

PANEL "PW"(S2)

1. REFER TO THE ELECTRICAL COVER SHEET DRAWING FOR GENERAL

NOTES, LEGEND AND ABBREVIATIONS.

2. REFER TO ARCHITECTURAL DRAWINGS TO VERIFY THE ELEVATIONS,

DETAILS, LOCATION, MOUNTING HEIGHTS AND ADDITIONAL

INFORMATION PRIOR TO THE ROUGH-IN OF ELECTRICAL OUTLETS AND

DEVICES.

3. COORDINATE WITH CONTRACT DOCUMENTS FOR ALL OTHER

DISCIPLINES AND TRADES FOR EXACT LOCATION OF ASSOCIATED

EQUIPMENT.

4. ALL NEW OUTLETS AND DEVICES MUST BE FLUSH MOUNTED WITH

CONCEALED CONDUITS. ANY SURFACE MOUNTED OUTLETS, DEVICES

AND CONDUITS IN THE SCOPE OF WORK AREA MUST BE APPROVED BY

THE ARCHITECT PRIOR TO INSTALLATION.

5. COORDINATE WITH MECHANICAL CONTRACT DOCUMENTS TO VERIFY

THE EXACT LOCATION AND QUANTITY OF DUCT SMOKE DETECTORS

RESPECTIVELY.

6. THE CONTINUITY OF ALL EXISTING FIRE ALARM INITIATING DEVICE,

NOTIFICATION APPLIANCE AND SIGNALING LINE CIRCUITS TO REMAIN

SHALL BE MAINTAINED.

1. COORDINATE FINAL GFI LOCATION SHALL BE INSTALLED NEXT TO

SINK. SEE ARCH DRAWINGS FOR MORE INFORMATION.

2. RECEPTACLE SHALL BE DEDICATED TO WS-1.

1465 NORTHSIDE DRIVE SUITE 220B

ATLANTA, GA 30318

P:706-248-7165 www. .com

TM

PROJECT NUMBER: SIGQ212911.15

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT MANAGER

PPM

EPM

SETTY

DATE

A

D

USDA S

U

DWG. NO

DRAWN BY

SOLICITATION NO. SHEET NAME

ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED

Revisions

Agricultural Research Service

5/20/2022 5:44:44 PM C:\Users\Nicholas.Carlis\Documents\SIGQ212911.15_R20_Electrical_nicholas.carlisYDXF8.rvt

WET LAB

E201

LEVEL 1 ELECTRICAL

POWER BASE BID

CDC

NC 04/20/2022

JM BD

DC

LB

EO

NO SCALEE201

1 LEVEL 1 ELECTRICAL POWER BASE BID

NO. DATE BY DESCRIPTION

1 03/04/2022 JM 50% DOCUMENTS

2 04/20/2022 JM 90% DOCUMENTS

3 05/06/2022 JM 100% DOCUMENTS

4 05/20/2022 JM ISSUE FOR BIDDING AND CONSTRUCTION

SHEET KEY NOTES#

1. COORDINATE FINAL GFI LOCATION SHALL BE INSTALLED NEXT TO

SINK. SEE ARCH DRAWINGS FOR MORE INFORMATION.

2. RECEPTACLE SHALL BE DEDICATED TO WS-1.

3. FOR EACH PANEL PROVIDE TWO WHIPS TO CONNECT ELECTRICAL

SERVICE TO OWNERS EQUIPMENT. COORDINATE CONNECTION

REQUIREMENTS WITH OWNER THROUGH SUBMITTAL. REFER TO

ARCHITECURAL DRAWING A803 FOR MORE INFORMATION

4. FOR EACH PANEL PROVIDE 2 WHIPS TO CONNECT DATA SERVICE TO

OWNERS EQUIPMENT. COORDINATE CONNECTION REQUIREMENTS

WITH OWNER THROUGH SUBMITTAL REFER TO ARCHITECURAL

DRAWING A803 FOR MORE INFORMATION

5. RECEPTACLES SHALL BE INSTALLED UNDERNEATH TABLE FOR

OWNER EQUIPMENT REQUIREMENTS

G

FI

GFI GFI

GFI GFI

G

FI

GFIGFI GFI GFI GFI

TV

G

FI

G

FI

FACP

J

J

J

J J

J

J

J

J

J

J

J

GFI GFI

GFI

F A

A P

J

J

GFI GFI GFI GFI GFI

GFIGFIGFIGFI

G

FI

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

GFI

5 6 7 8

11 12 131415

MEN. RR

WOMEN RR

23ENTRY/ VESTIBULE

GROUP OFFICE

GEN. STORAGE

OFFICE

ENTRY EQM

CONF RM

CHEM STORAGE

EQM STORAGE

FUME HOOD

CORRIDOR

OPEN WET LAB

OFFICE

ELEC. RM.

ENTRY VEST.

JAN. RM.

2 2 2 2 2

1 1

PANEL "PW"

PANEL "RW"

MECH.

DWH-1

EXCAV-1-1

RHCAV-1-9

RHCAV-1-11

RHCAV-1-8

RHCAV-1-6

EXCAV-1-5

RHCAV-1-5

EXCAV-1-4

EXCAV-1-6

RHCAV-1-10

EXCAV-1-7

RHCAV-1-12

RHCAV-1-7

RHCAV-1-1

EXCAV-1-8

RHCAV-1-4

EXCAV-1-3

EXCAV-1-2

RHCAV-1-3

RHCAV-1-2

CU-1

AHU-1

RW-8

RW-8

RW-8

RW-8

RW-10

RW-10 RW-10

RW-12

RW-12

RW-12

RW-14

RW-14

RW-14RW-14

RW-16

RW-16

RW-16

RW-18

RW-18

RW-18

RW-18

RW-20RW-20RW-20

RW-20RW-22

RW-22

RW-22

RW-24

RW-24

RW-24

RW-26

RW-26

RW-26

RW-28

RW-28RW-28

RW-30

RW-30RW-30

RW-32

RW-32

RW-32

RW-34

RW-34

RW-34

RW-31

RW-31

RW-31

RW-31

RW-33

RW-33

RW-33

RW-33

PW-8

ROS-1

PP-1

RW-7

RW-9

PW-43,45,47

PW-19,21,23

PW-19,21,23

PW-19,21,23

PW-25,27,29

PW-25,27,29

PW-31,33,35

PW-37,39,41

PW-20,22,24

PW-26,28,30

PW-32,34,36

PW-38,40,42

PW-37,39,41

PW-14,16,18

PW-7,9,11 PW-1,3,5 RW-1

RW-5

WP WP

WP

RW-37 RW-37

RW-37

WS-1

RW-15

RW-15

TSTSFS

PANEL "LW"

RW-34

RW-32

2 2 2 2 2 2 2 2 2 2

RW-17,19,21

LW-1

LW-1

LW-1

LW-3

LW-3 LW-3 LW-5 LW-5 LW-5 LW-7 LW-7 LW-7 LW-9 LW-9

LW-9

LW-11

LW-11

LW-11

LW-15 LW-13 LW-13

LW-13

LW-15LW-15

LW-17

LW-17

x3

LW-21

x3 x3 x3 x3 x3 x3 x3 x3 x3 x2 x2 x2 x2 x2 x2 x2 x2

LW-25 LW-29 LW-33 LW-37

LW-19 LW-23 LW-27 LW-35

x2 x2

LW-31

LW-10

LW-12

LW-14

LW-16

5 5555

4 4

NO SCALEE201

1 LEVEL 1 ELECTRICAL POWER BASE BID

J

GEF-1

PW-13,15,17PW-13,15,17

BD

5 06/16/2022 JM ADDENDUM 1

06/16/2022

GFI GFI

GFI GFI

G

FI

GFIGFI GFI GFI GFIGFI

G

FI

TV

G

FI

G

FI

G

FI

G

FI

G

FI

J

J

J

J J

J

J

J

J

J

J

J

J

J

J

GFI GFI

GFI

J

J

GFI GFI GFI GFI GFIGFI GFI

G

FI

G

FI

G

FI

G

FI

GFIGFIGFIGFI

G

FI

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

GFI

5 6 7 8

11 12 131415

MEN. RR

20 WOMEN RR

ENTRY/ VESTIBULE

GROUP OFFICE

GEN. STORAGE

OFFICE

ENTRY EQM

CONF RM

CHEM STORAGE

EQM STORAGE

FUME HOOD

CORRIDOR

OPEN WET LAB

OFFICE

ELEC. RM.

ENTRY VEST.

JAN. RM.

2 2 2 2 2 2

1 1

PANEL "PW"

PANEL "RW"

FIELD LAB OFFICE

FIELD LABORATORY

MECH.

DWH-1

EXCAV-1-1

EXCAV-1-9

EXCAV-1-10

RHCAV-1-14

RHCAV-1-13

RHCAV-1-9

RHCAV-1-11

RHCAV-1-8

RHCAV-1-6

EXCAV-1-5

RHCAV-1-5

EXCAV-1-4

EXCAV-1-6

RHCAV-1-10

EXCAV-1-7

RHCAV-1-12

RHCAV-1-7

RHCAV-1-1

EXCAV-1-8

RHCAV-1-4

EXCAV-1-3

EXCAV-1-2

RHCAV-1-3

RHCAV-1-2

CU-1

AHU-1

GEF-1

RW-8

RW-8

RW-8

RW-8

RW-10

RW-10 RW-10

RW-12

RW-12

RW-12

RW-14

RW-14

RW-14RW-14

RW-16

RW-16

RW-16

RW-18

RW-18

RW-18

RW-18

RW-20RW-20RW-20

RW-20RW-22

RW-22

RW-22

RW-24

RW-24

RW-24

RW-26

RW-26

RW-26

RW-28

RW-28RW-28

RW-30

RW-30RW-30

RW-32

RW-32

RW-32

RW-34

RW-34

RW-34

RW-31

RW-31

RW-31

RW-31

RW-33

RW-33

RW-33

RW-33

RW-23

RW-23

RW-23

LW-18

LW-18

LW-28

LW-20

RW-35

RW-35

RHCAV-1-6

ROS-1

PP-1

RW-7

RW-9

PW-13,15,17

PW-19,21,23

PW-19,21,23

PW-19,21,23

PW-25,27,29

PW-25,27,29

PW-31,33,35

PW-37,39,41

PW-37,39,41

PW-20,22,24

PW-26,28,30

PW-32,34,36

PW-38,40,42

PW-43,45,47

PW-7,9,11

PW-13,15,17

PW-14,16,18

PW-1,3,5 RW-1

PW-38,40,42

PW-44,46,48

RW-5

WP WP

WP

RW-37 RW-37

RW-37

WS-1

RW-13

RW-13

PANEL "LW"

LW-18

LW-22

LW-20

RW-34

RW-32

2 2 2 2 2 2 2 2 2 2

RW-15,17,19

LW-1

LW-1

LW-1

LW-3

LW-3 LW-3 LW-5 LW-5 LW-5 LW-7 LW-7 LW-7 LW-9 LW-9

LW-9

LW-11

LW-11

LW-11

LW-15 LW-13 LW-13

LW-13

LW-15LW-15

LW-17

LW-17

x3

LW-21

x3 x3 x3 x3 x3 x3 x3 x3 x3 x2 x2 x2 x2 x2 x2

LW-25 LW-29 LW-33 LW-37

LW-19 LW-23 LW-27 LW-35

x2 x2

LW-31

LW-39

LW-41

LW-2

LW-4

LW-10

LW-12

LW-14

LW-16

5 5555 x2 x2

LW-20

LW-22LW-22LW-24

LW-24

LW-24

LW-26

LW-26

LW-26

1465 NORTHSIDE DRIVE SUITE 220B

ATLANTA, GA 30318

P:706-248-7165 www. .com

TM

PROJECT NUMBER: SIGQ212911.15

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT MANAGER

PPM

EPM

SETTY

DATE

A

D

USDA S

U

DWG. NO

DRAWN BY

SOLICITATION NO. SHEET NAME

ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED

Revisions

Agricultural Research Service

6/16/2022 6:41:23 PM C:\Users\Nicholas.Carlis\Documents\SIGQ212911.15_R20_Electrical_nicholas.carlisYDXF8.rvt

WET LAB

E201.1

LEVEL 1 ELECTRICAL

POWER ADD ALT. #1

CDC

NC 06/16/2022

JM BD

BD

DC

LB

EO

NO. DATE BY DESCRIPTION

1 03/04/2022 JM 50% DOCUMENTS

2 04/20/2022 JM 90% DOCUMENTS

3 05/06/2022 JM 100% DOCUMENTS

4 05/20/2022 JM ISSUE FOR BIDDING AND CONSTRUCTION

5 06/16/2022 JM ADDENDUM 1

NO SCALEE201.1

1 LEVEL 1 ELECTRICAL POWER ADD ALT. #1

GENERAL NOTES

SHEET KEY NOTES#

1. REFER TO THE ELECTRICAL COVER SHEET DRAWING FOR GENERAL

NOTES, LEGEND AND ABBREVIATIONS.

2. REFER TO ARCHITECTURAL DRAWINGS TO VERIFY THE ELEVATIONS,

DETAILS, LOCATION, MOUNTING HEIGHTS AND ADDITIONAL

INFORMATION PRIOR TO THE ROUGH-IN OF ELECTRICAL OUTLETS AND

DEVICES.

3. COORDINATE WITH CONTRACT DOCUMENTS FOR ALL OTHER

DISCIPLINES AND TRADES FOR EXACT LOCATION OF ASSOCIATED

EQUIPMENT.

4. ALL NEW OUTLETS AND DEVICES MUST BE FLUSH MOUNTED WITH

CONCEALED CONDUITS. ANY SURFACE MOUNTED OUTLETS, DEVICES

AND CONDUITS IN THE SCOPE OF WORK AREA MUST BE APPROVED BY

THE ARCHITECT PRIOR TO INSTALLATION.

5. COORDINATE WITH MECHANICAL CONTRACT DOCUMENTS TO VERIFY

THE EXACT LOCATION AND QUANTITY OF DUCT SMOKE DETECTORS

RESPECTIVELY.

6. THE CONTINUITY OF ALL EXISTING FIRE ALARM INITIATING DEVICE,

NOTIFICATION APPLIANCE AND SIGNALING LINE CIRCUITS TO REMAIN

SHALL BE MAINTAINED.

1. COORDINATE FINAL GFI LOCATION SHALL BE INSTALLED NEXT TO

SINK. SEE ARCH DRAWINGS FOR MORE INFORMATION.

2. RECEPTACLE SHALL BE DEDICATED TO WS-1.

SHEET KEY NOTES#

1. COORDINATE FINAL GFI LOCATION SHALL BE INSTALLED NEXT TO

SINK. SEE ARCH DRAWINGS FOR MORE INFORMATION.

2. RECEPTACLE SHALL BE DEDICATED TO WS-1.

3. FOR EACH PANEL PROVIDE TWO WHIPS TO CONNECT ELECTRICAL

SERVICE TO OWNERS EQUIPMENT. COORDINATE CONNECTION

REQUIREMENTS WITH OWNER THROUGH SUBMITTAL. REFER TO

ARCHITECURAL DRAWING A803 FOR MORE INFORMATION

4. FOR EACH PANEL PROVIDE 2 WHIPS TO CONNECT DATA SERVICE TO

OWNERS EQUIPMENT. COORDINATE CONNECTION REQUIREMENTS

WITH OWNER THROUGH SUBMITTAL REFER TO ARCHITECURAL

DRAWING A803 FOR MORE INFORMATION

5. RECEPTACLES SHALL BE INSTALLED UNDERNEATH TABLE FOR

OWNER EQUIPMENT REQUIREMENTS

GFI GFI

GFI GFI

G

FI

GFIGFI GFI GFI GFI

G

FI

G

FI

GFI GFI

G

FI

G

FI

G

FI

G

FI

TV

G

FI

G

FI

J

J

J

J

J J

J

J

J

J

J

J

J

J

J

GFI GFI

GFI

J

J

5 6 7 8

11 12 131415

MEN. RR

WOMEN RR

ENTRY/ VESTIBULE

GROUP OFFICE

GEN. STORAGE

OFFICE

ENTRY EQM

CONF RM

CHEM STORAGE

EQM STORAGE

FUME HOOD

CORRIDOR

OPEN WET LAB

OFFICE

ELEC. RM.

ENTRY VEST.

JAN. RM.

2 2 2 2 2 2

1 1

PANEL "PW"(S1)

MECH.

FIELD LAB OFFICE

FIELD LABORATORY

DWH-1

EXCAV-1-1

EXCAV-1-9

EXCAV-1-10

RHCAV-1-14

RHCAV-1-13

RHCAV-1-9

RHCAV-1-11

RHCAV-1-8

RHCAV-1-6

EXCAV-1-5

RHCAV-1-5

EXCAV-1-4

EXCAV-1-6

RHCAV-1-10

EXCAV-1-7

RHCAV-1-12

RHCAV-1-7

RHCAV-1-1

EXCAV-1-8

RHCAV-1-4

EXCAV-1-3

EXCAV-1-2

RHCAV-1-3

RHCAV-1-2

AHU-1

GEF-1

CU-1

RW-8

RW-8

RW-8

RW-8

RW-10

RW-10 RW-10

RW-12

RW-12

RW-12

RW-14

RW-14

RW-14RW-14

RW-16

RW-16

RW-16

RW-18

RW-18

RW-18

RW-18

RW-20RW-20RW-20

RW-20RW-22

RW-22

RW-22

RW-24

RW-24

RW-24

RW-26

RW-26

RW-26

RW-28

RW-28RW-28

RW-30

RW-30RW-30

RW-32

RW-32

RW-32

RW-34

RW-34

RW-34

RW-36

RW-36

RW-36 RW-38 RW-38 RW-38 RW-40

RW-40

RW-40

RW-42

RW-42RW-42RW-42

RW-23RW-23

RW-23

RW-23

RW-25

RW-25

RW-25

RW-25

RW-27

RW-27

RW-27

RW-29RW-29

RW-29

RW-29

RW-31

RW-31

RW-31

RW-31

RW-33

RW-33

RW-33

RW-33

RW-35

RW-35

PW-19,21,23

PW-19,21,23

PW-19,21,23

PW-25,27,29

PW-25,27,29

PW-31,33,35

PW-37,39,41

PW-37,39,41

PW-20,22,24

PW-26,28,30

PW-32,34,36

PW-38,40,42

PW-43,45,47

PW-7,9,11

PW-13,15,17

ROS-1

PP-1

PW-14,16,18

RW-7

RW-9

PW-1,3,5 RW-1

PW-38,40,42

PW-44,46,48

RW-5

WP WP

WP

RW-37 RW-37

RW-37

WS-1

RW-21

RW-21

RW-13

RW-13

PANEL "PW"(S2)

PANEL "RW"

1465 NORTHSIDE DRIVE SUITE 220B

ATLANTA, GA 30318

P:706-248-7165 www. .com

TM

PROJECT NUMBER: SIGQ212911.15

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT MANAGER

PPM

EPM

SETTY

DATE

A

D

USDA S

U

DWG. NO

DRAWN BY

SOLICITATION NO. SHEET NAME

ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED

Revisions

Agricultural Research Service

5/20/2022 5:44:56 PM C:\Users\Nicholas.Carlis\Documents\SIGQ212911.15_R20_Electrical_nicholas.carlisYDXF8.rvt

WET LAB

E201.2

LEVEL 1 ELECTRICAL

POWER ADD ALT. #2

CDC

NC 04/20/2022

JM BD

DC

LB

EO

NO. DATE BY DESCRIPTION

1 03/04/2022 JM 50% DOCUMENTS

2 04/20/2022 JM 90% DOCUMENTS

3 05/06/2022 JM 100% DOCUMENTS

4 05/20/2022 JM ISSUE FOR BIDDING AND CONSTRUCTION

NO SCALEE201.2

1 LEVEL 1 ELECTRICAL POWER ADD ALT. #2

GENERAL NOTES

SHEET KEY NOTES#

1. REFER TO THE ELECTRICAL COVER SHEET DRAWING FOR GENERAL

NOTES, LEGEND AND ABBREVIATIONS.

2. REFER TO ARCHITECTURAL DRAWINGS TO VERIFY THE ELEVATIONS,

DETAILS, LOCATION, MOUNTING HEIGHTS AND ADDITIONAL

INFORMATION PRIOR TO THE ROUGH-IN OF ELECTRICAL OUTLETS AND

DEVICES.

3. COORDINATE WITH CONTRACT DOCUMENTS FOR ALL OTHER

DISCIPLINES AND TRADES FOR EXACT LOCATION OF ASSOCIATED

EQUIPMENT.

4. ALL NEW OUTLETS AND DEVICES MUST BE FLUSH MOUNTED WITH

CONCEALED CONDUITS. ANY SURFACE MOUNTED OUTLETS, DEVICES

AND CONDUITS IN THE SCOPE OF WORK AREA MUST BE APPROVED BY

THE ARCHITECT PRIOR TO INSTALLATION.

5. COORDINATE WITH MECHANICAL CONTRACT DOCUMENTS TO VERIFY

THE EXACT LOCATION AND QUANTITY OF DUCT SMOKE DETECTORS

RESPECTIVELY.

6. THE CONTINUITY OF ALL EXISTING FIRE ALARM INITIATING DEVICE,

NOTIFICATION APPLIANCE AND SIGNALING LINE CIRCUITS TO REMAIN

SHALL BE MAINTAINED.

1. COORDINATE FINAL GFI LOCATION SHALL BE INSTALLED NEXT TO

SINK. SEE ARCH DRAWINGS FOR MORE INFORMATION.

2. RECEPTACLE SHALL BE DEDICATED TO WS-1.

G

FI

GFI GFI

GFI GFI

G

FI

GFIGFI GFI GFI GFI

G

FI

G

FI

GFI GFI

G

FI

G

FI

G

FI

G

FI

TV

G

FI

G

FI

J

J

J

J

J J

J

J

J

J

J

J

J

J

GFI GFI

GFI

J

J

GFI GFI GFI GFI GFI

G

FI

G

FI

GFIGFI

G

FI

GFIGFIGFIGFI

G

FI

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J J J J

J JJ J

GFI

5 6 7 8

11 12 131415

MEN. RR

WOMEN RR

ENTRY/ VESTIBULE

GROUP OFFICE

GEN. STORAGE

OFFICE

ENTRY EQM

CONF RM

CHEM STORAGE

EQM STORAGE

FUME HOOD

CORRIDOR

OPEN WET LAB

OFFICE

ELEC. RM.

ENTRY VEST.

JAN. RM.

2 2 2 2 2 2

1 1

PANEL "PW"

PANEL "RW"

MECH.

FIELD LAB OFFICE

FIELD LABORATORY

DWH-1

EXCAV-1-1

EXCAV-1-9

EXCAV-1-10

RHCAV-1-14

RHCAV-1-13

RHCAV-1-9

RHCAV-1-11

RHCAV-1-8

RHCAV-1-6

EXCAV-1-5

RHCAV-1-5

EXCAV-1-4

EXCAV-1-6

RHCAV-1-10

EXCAV-1-7

RHCAV-1-12

RHCAV-1-7

RHCAV-1-1

EXCAV-1-8

RHCAV-1-4

EXCAV-1-3

EXCAV-1-2

RHCAV-1-3

RHCAV-1-2

AHU-1

CU-1

RW-8

RW-8

RW-8

RW-8

RW-10

RW-10 RW-10

RW-12

RW-12

RW-12

RW-14

RW-14

RW-14RW-14

RW-16

RW-16

RW-16

RW-18

RW-18

RW-18

RW-18

RW-20RW-20RW-20

RW-20RW-22

RW-22

RW-22

RW-24

RW-24

RW-24

RW-26

RW-26

RW-26

RW-28

RW-28RW-28

RW-30

RW-30RW-30

RW-32

RW-32

RW-32

RW-34

RW-34

RW-34

RW-23RW-23

RW-23

RW-23

LW-26

RW-31

RW-31

RW-31

RW-31

RW-33

RW-33

RW-33

RW-33

RW-35

RW-35

PW-19,21,23

PW-19,21,23

PW-19,21,23

PW-25,27,29

PW-25,27,29

PW-31,33,35

PW-37,39,41

PW-37,39,41

PW-20,22,24

PW-26,28,30

PW-32,34,36

PW-38,40,42

PW-43,45,47

PW-7,9,11

ROS-1

PP-1

PW-14,16,18

RW-7

RW-9

PW-1,3,5 RW-1

PW-38,40,42

PW-44,46,48

RW-5

WP WP

WP

RW-37 RW-37

RW-37

WS-1

RW-13

RW-13

PANEL "LW"

LW-1

LW-1

LW-1

LW-3

LW-3 LW-3 LW-5 LW-5 LW-5 LW-7 LW-7 LW-7 LW-9 LW-9

LW-9

LW-11

LW-11

LW-11

LW-15 LW-13 LW-13

LW-13

LW-15LW-15

LW-17

LW-17

x3

LW-21

2 2 2 2 2 2 2 2 2 2

RW-34

RW-32

RW-15,17,19

x3 x3 x3 x3 x3 x3 x3 x3 x3 x2 x2 x2 x2 x2 x2 x2 x2 x3x3x2 x2 x3x3x2 x2

LW-25 LW-29 LW-33 LW-37

LW-19 LW-23 LW-27 LW-35

x2 x2

LW-31

LW-39

LW-41

LW-2

LW-4

LW-6

LW-8

LW-10

LW-12

LW-14

LW-16

LW-26

LW-24

LW-32LW-30

5 5555

LW-18

LW-20

LW-24

LW-22

LW-26

LW-26

LW-28

LW-28

LW-28

LW-30

LW-30

LW-30

LW-32LW-32LW-32LW-34

LW-34

LW-34

LW-34

LW-36

LW-36

1. COORDI

SINK. SE

2. RECEPTA

3. FOR EAC

SERVICE

REQUIRE

ARCHITE

4. FOR EAC

OWNERS

WITH OW

DRAWIN

5. RECEPTA

OWNER

NO SCALEE201.2

1 LEVEL 1 ELECTRICAL POWER ADD ALT. #2

SHEET KEY NOTES#

1. COORDINATE FINAL GFI LOCATION SHALL BE INSTALLED NEXT TO

SINK. SEE ARCH DRAWINGS FOR MORE INFORMATION.

2. RECEPTACLE SHALL BE DEDICATED TO WS-1.

SHEET KEY NOTES#

1. COORDINATE FINAL GFI LOCATION SHALL BE INSTALLED NEXT TO

SINK. SEE ARCH DRAWINGS FOR MORE INFORMATION.

2. RECEPTACLE SHALL BE DEDICATED TO WS-1.

3. FOR EACH PANEL PROVIDE TWO WHIPS TO CONNECT ELECTRICAL

SERVICE TO OWNERS EQUIPMENT. COORDINATE CONNECTION

REQUIREMENTS WITH OWNER THROUGH SUBMITTAL. REFER TO

ARCHITECURAL DRAWING A803 FOR MORE INFORMATION

4. FOR EACH PANEL PROVIDE 2 WHIPS TO CONNECT DATA SERVICE TO

OWNERS EQUIPMENT. COORDINATE CONNECTION REQUIREMENTS

WITH OWNER THROUGH SUBMITTAL REFER TO ARCHITECURAL

DRAWING A803 FOR MORE INFORMATION

5. RECEPTACLES SHALL BE INSTALLED UNDERNEATH TABLE FOR

OWNER EQUIPMENT REQUIREMENTS

BD

AV

AV

AV

AV

15cd

AV

15cd

AV

AV

75 AV

AV

AV

AV

F

F

AV

15cd

AV

15cd

A V c d

S

S

S

FACP

AV

S

S

F

D

D

F A

A P

5 6 7 8

11 12 131415

MEN. RR

WOMEN RR

23ENTRY/ VESTIBULE

GROUP OFFICE

GEN. STORAGE

OFFICE

ENTRY EQM

CONF RM

CHEM STORAGE

EQM STORAGE

FUME HOOD

CORRIDOR

OPEN WET LAB

OFFICE

ELEC. RM.

ENTRY VEST.

JAN. RM.

PANEL "PW"

PANEL "RW"

MECH.

TSTSFS

1465 NORTHSIDE DRIVE SUITE 220B

ATLANTA, GA 30318

P:706-248-7165 www. .com

TM

PROJECT NUMBER: SIGQ212911.15

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT MANAGER

PPM

EPM

SETTY

DATE

A

D

USDA S

U

DWG. NO

DRAWN BY

SOLICITATION NO. SHEET NAME

ORIGINAL DRAWING SIZE IS 30"x 42"; SCALE ENTITIES ACCORDINGLY IF REDUCED/ENLARGED

Revisions

Agricultural Research Service

6/15/2022 4:36:44 PM C:\Users\Nicholas.Carlis\Documents\SIGQ212911.15_R20_Electrical_nicholas.carlisYDXF8.rvt

WET LAB

E301

LEVEL 1 FIRE ALARM BASE

BID

CDC

NC 06/16/2022

JM BD

BD

DC

LB

EO

NO SCALEE301

1 LEVEL 1 FIRE ALARM BASE BID

NO. DATE BY DESCRIPTION

1 03/04/2022 JM 50% DOCUMENTS

2 04/20/2022 JM 90% DOCUMENTS

3 05/06/2022 JM 100% DOCUMENTS

4 05/20/2022 JM ISSUE FOR BIDDING AND CONSTRUCTION

5 06/16/2022 JM ADDENDUM 1

AREA OF WORK

FACP(E)

KEYPLAN

FIRE ALARM GENERAL NOTES

1. REFER TO THE ELECTRICAL COVER SHEET DRAWING FOR GENERAL NOTES,

LEGEND AND ABBREVIATIONS. REFER TO DETAIL DRAWINGS FOR THE

PROPOSED MOUNTING REQUIREMENTS OF TYPICAL FIRE ALARM DEVICES.

2. REFER TO ARCHITECTURAL DRAWINGS TO COORDINATE AND VERIFY

AGAINST THE CEILING PLANS, ELEVATIONS AND DETAILS AT THE PROPOSED

FIRE ALARM DEVICE INSTALLATION LOCATIONS PRIOR TO THE ROUGH-IN.

3. COORDINATE WITH MECHANICAL AND FIRE PROTECTION CONTRACT

DOCUMENTS TO VERIFY THE EXACT LOCATION AND QUANTITY OF DUCT

SMOKE DETECTORS AND ALL FLOW AND TAMPER SWITCHES

RESPECTIVELY.

4. ALL NEW FIRE ALARM DEVICES SHALL BE INSTALLED AS FLUSH MOUNTED

WITH CONCEALED CONDUITS. ANY SURFACE MOUNTED DEVICES AND

CONDUITS IN THE SCOPE OF WORK AREA MUST BE APPROVED BY THE

ARCHITECT PRIOR TO INSTALLATION.

5. ALL NEW AND RELOCATED FIRE ALARM DEVICES MUST BE COMPATIBLE

WITH AND CONNECTED TO THE EXISTING FIRE ALARM SYSTEM, ZONED BY

FLOOR. EXTEND EXISTING WIRING AND CONDUIT FOR RELOCATED DEVICES

TO NEW LOCATIONS AS REQUIRED.

6. WHERE MORE THAN TWO VISUAL (STROBE) NOTIFICATION APPLIANCES ARE

IN THE FIELD OF VIEW, THEY SHALL FLASH IN SYNCHRONIZATION. PROVIDE

EXTERNAL SYNC MODULE OR SYNC PROTOCOL BUILT IN TO THE FIRE

ALARM CONTROL PANEL.

7. CONNECT NEW FIRE ALARM DEVICES TO EXISTING SITE FIRE ALARM

CONTROL PANEL LOCATED IN BUILDING 1. CONTRACTOR TO MODIFY OR

PROVIDE NEW FIRE ALARM CONTROL PANEL TO ACCOMMODATE

INSTALLATIONS OF NEW DEVICES AS NEEDED

AV

AV

AV

15cd

AV

15cd

AV

AV

75 AV

AV

AV

AV

F

F

AV

15cd

AV

15cd

A V c d

S

S

S

FACP

AV

S

AV

S

F

V

D

D

F A

A P

5 6 7 8

11 12 131415

MEN. RR

WOMEN RR

ENTRY/ VESTIBULE

GROUP OFFICE

GEN. STORAGE

OFFICE

ENTRY EQM

CONF RM

CHEM STORAGE

EQM STORAGE

FUME HOOD

CORRIDOR

OPEN WET LAB

OFFICE

ELEC. RM.

ENTRY VEST.

JAN. RM.

PANEL "PW"

PANEL "RW"

MECH.

TSTSFS

1465 NORTHSIDE DRIVE SUITE 220B

ATLANTA, GA 30318

P:706-248-7165 www. .com

TM

PROJECT NUMBER: SIGQ212911.15

SAFETY & HEALTH

REAL PROPERTY

DESIGNER

CHECKED BY

PROJECT…