Attachment 1 combine.pdf

PDF 5 MB Posted

Attached to
AHU 19 and 10 coil repair
Solicitation number
36C25623Q0980
Issued by

View the file

Other files

File Type Posted
36C25623Q0980 0004.docx DOCX document
QA.docx DOCX document
36C25623Q0980 0003.docx DOCX document
Addendum 52.212-2 Evaluation of Offerors 05-19-2023.docx DOCX document
36C25623Q0980 0002.docx DOCX document
Original AHU 19 drawing.pdf PDF
ahu 10-1 damaged coil.jpg JPG image
Attachment 5 AHU 19 product drawing.pdf PDF
36C25623Q0980 0001.pdf PDF
Wage Determination 2015-5233.pdf PDF
PWS AHU 19 and 10 coil repair.docx DOCX document
36C25623Q0980 Coil Repair.docx DOCX document
Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CC Coil – 01 Coil General/Physical Details Air Side Performance Fluid Side Performance

Location: 0 Rows: 4 Air Flow (acfm): 11100 EWT (°F): 44.0 Tag: AirCoil Fins Per Inch: 8 Altitude (ft.): 640 LWT (°F): 55.9 Application: Cooling Tubes Per Circuit: 4 EAT-DB (°F): 95.0 GPM: 125.4 Coil Type: Water Finned Height (in.): 48.25 EAT-WB (°F): 79.0 WPD (ft): 19.1 Face Type: Full Finned Length (in.): 83 LAT-DB (°F): 60.9 FPS: 4.4 Tube Diameter: 5/8" CDW Coil Face Area (ft²): 27.8 LAT-WB (°F): 59.9 Fluid Type: Water Tube Material: Copper Coil Conn. Loc.: Left(Left) FV (ft/min): 399 Fluid Weight(lb): 129.0 Tube Wall Thickness: .020" Supp Conn Size: 2" SMBH: 396.7 Fluid Volume(ft³): 2.1 Fin Type: Sine Rtn Conn Size: 2" TMBH: 751.9

Fin Thickness: .008" # of Supply APD (in. w.g.): 0.33

Fin Material: Copper Conn. (per coil): 1

Casing Material: Stainless

Steel

Connection Material: Steel*

Connection Type: MPT

Coating: Phenolic

*Johnson Controls suggests using red brass or copper connectors when the coil is to be attached to a copper or brass piping system.

Unit Tag Qty Model Air Flow (CFM) 100-AH19 1 Indoor Air Handler 57 x 96 11100

Ratings are for coils manufactured by Johnson Controls, Inc., 507 E. Michigan St., Milwaukee WI 53202.

CDW Tube Spacing: 1.50" x 1.30"

AHRI Messages:

This coil is certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the range of Standard rating conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory at www.ahridirectory.org.

Coil Dll Version: 7.2b

Epoxy immersive coating equivalent to ElectroFin coating

1. Epoxy Immersion Coating – Electrically Deposited: The multi-stage corrosion-resistant coating application comprises of cleaning

(heated alkaline immersion bath) and reverse-osmosis immersion rinse prior to the start of the coating process. The coating thickness shall be maintained between 0.6-mil and 1.2-mil. Before the coils are subjected to high-temperature oven cure, they are treated to permeate immersion rinse and spray. Where the coils are subject to

UV exposure, UV protection spray treatment comprising of UV-resistant urethane mastic topcoat shall be applied. Provide complete coating process traceability for each coil and minimum five years of limited warranty.

2. The coating process shall such that uniform coating thickness is maintained at the fin edges. The quality control shall be maintained by ensuring compliance to the applicable ASTM Standards for the following:

a. Salt Spray Resistance (Minimum 6,000 Hours)

b. Humidity Resistance (Minimum 1,000 Hours)

c. Water Immersion (Minimum 260 Hours)

d. Cross-Hatch Adhesion (Minimum 4B-5B Rating)

e. Impact Resistance (Up to 160 Inch/Pound)

Attachment 1 AHU 19 cooling coil
Attachment 2 AHU 19
Attachment 3 AHU 10 label
Attachment 4 Epoxy immersive coating