Attachment 1 combine.pdf
PDF 5 MB Posted
- Attached to
- AHU 19 and 10 coil repair
- Solicitation number
- 36C25623Q0980
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25623Q0980 0004.docx | DOCX document | |
| QA.docx | DOCX document | |
| 36C25623Q0980 0003.docx | DOCX document | |
| Addendum 52.212-2 Evaluation of Offerors 05-19-2023.docx | DOCX document | |
| 36C25623Q0980 0002.docx | DOCX document | |
| Original AHU 19 drawing.pdf | ||
| ahu 10-1 damaged coil.jpg | JPG image | |
| Attachment 5 AHU 19 product drawing.pdf | ||
| 36C25623Q0980 0001.pdf | ||
| Wage Determination 2015-5233.pdf | ||
| PWS AHU 19 and 10 coil repair.docx | DOCX document | |
| 36C25623Q0980 Coil Repair.docx | DOCX document |
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CC Coil – 01 Coil General/Physical Details Air Side Performance Fluid Side Performance
Location: 0 Rows: 4 Air Flow (acfm): 11100 EWT (°F): 44.0 Tag: AirCoil Fins Per Inch: 8 Altitude (ft.): 640 LWT (°F): 55.9 Application: Cooling Tubes Per Circuit: 4 EAT-DB (°F): 95.0 GPM: 125.4 Coil Type: Water Finned Height (in.): 48.25 EAT-WB (°F): 79.0 WPD (ft): 19.1 Face Type: Full Finned Length (in.): 83 LAT-DB (°F): 60.9 FPS: 4.4 Tube Diameter: 5/8" CDW Coil Face Area (ft²): 27.8 LAT-WB (°F): 59.9 Fluid Type: Water Tube Material: Copper Coil Conn. Loc.: Left(Left) FV (ft/min): 399 Fluid Weight(lb): 129.0 Tube Wall Thickness: .020" Supp Conn Size: 2" SMBH: 396.7 Fluid Volume(ft³): 2.1 Fin Type: Sine Rtn Conn Size: 2" TMBH: 751.9
Fin Thickness: .008" # of Supply APD (in. w.g.): 0.33
Fin Material: Copper Conn. (per coil): 1
Casing Material: Stainless
Steel
Connection Material: Steel*
Connection Type: MPT
Coating: Phenolic
*Johnson Controls suggests using red brass or copper connectors when the coil is to be attached to a copper or brass piping system.
Unit Tag Qty Model Air Flow (CFM) 100-AH19 1 Indoor Air Handler 57 x 96 11100
Ratings are for coils manufactured by Johnson Controls, Inc., 507 E. Michigan St., Milwaukee WI 53202.
CDW Tube Spacing: 1.50" x 1.30"
AHRI Messages:
This coil is certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the range of Standard rating conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory at www.ahridirectory.org.
Coil Dll Version: 7.2b
Epoxy immersive coating equivalent to ElectroFin coating
1. Epoxy Immersion Coating – Electrically Deposited: The multi-stage corrosion-resistant coating application comprises of cleaning
(heated alkaline immersion bath) and reverse-osmosis immersion rinse prior to the start of the coating process. The coating thickness shall be maintained between 0.6-mil and 1.2-mil. Before the coils are subjected to high-temperature oven cure, they are treated to permeate immersion rinse and spray. Where the coils are subject to
UV exposure, UV protection spray treatment comprising of UV-resistant urethane mastic topcoat shall be applied. Provide complete coating process traceability for each coil and minimum five years of limited warranty.
2. The coating process shall such that uniform coating thickness is maintained at the fin edges. The quality control shall be maintained by ensuring compliance to the applicable ASTM Standards for the following:
a. Salt Spray Resistance (Minimum 6,000 Hours)
b. Humidity Resistance (Minimum 1,000 Hours)
c. Water Immersion (Minimum 260 Hours)
d. Cross-Hatch Adhesion (Minimum 4B-5B Rating)
e. Impact Resistance (Up to 160 Inch/Pound)
| Attachment 1 AHU 19 cooling coil |
| Attachment 2 AHU 19 |
| Attachment 3 AHU 10 label |
| Attachment 4 Epoxy immersive coating |
File details come from the government source that posted it. Updated .