Attachment 06 CRWC 22419 HVAC Calculations.pdf
PDF 377 KB Posted
- Attached to
- CRRD Work Center Construction Project Federal contract opportunity
- Solicitation number
- 12445224R0011
- Issued by
- Department of Agriculture Forest Service
About this file
This document appears to be a detailed HVAC calculation file related to a federal contract opportunity for the construction of a new work center building. The file provides technical specifications and sizing data for the HVAC system, including ventilation airflow requirements, heating and cooling loads, and zoning information. The related federal contract opportunity is a solicitation issued by the Department of Agriculture Forest Service for the CRRD Work Center Construction Project in Rabun County, Georgia. The solicitation includes a site visit on 6/13/2024 and a deadline for questions on 6/17/2024.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amendment 01 12445224R0011 CRRD Work Center.pdf | ||
| Attachment 02 CRRD Work Center OPM Specifications.pdf | ||
| Attachment 09 WD Building GA20240104 Rabun County.pdf | ||
| Attachment 00 SOW CRRD Work Center Con. (Section C).docx | DOCX document | |
| RFP 12445224R0011 CRRD Work Center Construction P.pdf | ||
| Attachment 04 CRRD Work Center Geotechnical Report.pdf | ||
| Attachment 07 CRWC 22419 Hydrologic Calculations.pdf | ||
| Attachment 01 SOI (Section B).xlsx | XLSX spreadsheet | |
| Attachment 03 CRWC Full Set Drawings (Signed).pdf | ||
| Attachment 05 CRRD office work center NEPA docs- 2006.pdf | ||
| Attachment 08 IBC Special Inspections.pdf |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Work Building - Heated/Ventilated Only Project: 2022-419 CRWC 12/08/2023
Prepared by: CROFT & Associates, Inc. 5:04 PM
1. General Information
Space Model Work Building - Heated/Ventilated Only Building Work Center Building Notes:
2. Spaces
The space model contains 7 spaces with total floor area of 4,205 sqft.
2.1. Ventilation
Ventilation
Index Space Level Floor Area Space Type ASHRAE Standard 62.1-2019 OA Requirement 1 OA Requirement 2 Direct Exhaust
(sqft) Space Usage Airflow Units Airflow Units Airflow Units
1 101 - Work Bay Level 1 3162.4 (None) EDUCATION: Wood/metal shop 10.0 CFM/person 0.18 CFM/sqft 0.0 CFM
2 102 - Laundry Level 1 141.5 (None) RETAIL: Coin-operated laundry 7.5 CFM/person 0.12 CFM/sqft 0.12 CFM/sqft
3 103 - Toilet Level 1 79.6 (None) User Defined 0.0 CFM 0.00 CFM/sqft 150.0 CFM
4 104 - Janitor Level 1 42.5 (None) GENERAL: Occupiable storage room (liq/gel)
5.0 CFM/person 0.12 CFM/sqft 150.0 CFM
5 105 - Toilet Level 1 88.8 (None) User Defined 0.0 CFM/person 0.00 CFM/sqft 150.0 CFM
6 106 - Storage Level 1 347.2 (None) MISCELLANEOUS: Warehouse 10.0 CFM/person 0.06 CFM/sqft 0.0 CFM
7 107 - Fire Cache Level 1 343.4 (None) MISCELLANEOUS: Warehouse 10.0 CFM/person 0.06 CFM/sqft 0.0 CFM
Hourly Analysis Program 6.1 Page 1 of 5
Prepared by: CROFT & Associates, Inc. 5:04 PM
2.2. Overhead Lighting and Daylighting Control
Overhead Lighting Daylighting Control
Index Space ASHRAE Standard 90.1-2019 Power Units Lighting Schedule Power Control Illum. Units
Lighting Method
Space Usage Type
Multi. Type Setpoint
1 101 - Work Bay Building Area Workshop 0.91 W/sqft LED: Free Hanging 90.1 Warehouse Lights/Elec
1.00 Not Used --- ---
2 102 - Laundry Building Area Multifamily 0.45 W/sqft LED: Recessed, Unvented
90.1 Warehouse Lights/Elec
1.00 Not Used --- ---
3 103 - Toilet Building Area Warehouse 0.45 W/sqft LED: Recessed, Unvented
90.1 Warehouse Lights/Elec
1.00 Not Used --- ---
4 104 - Janitor Building Area Warehouse 0.45 W/sqft LED: Recessed, Unvented
90.1 Warehouse Lights/Elec
1.00 Not Used --- ---
5 105 - Toilet Building Area Warehouse 0.45 W/sqft LED: Recessed, Unvented
90.1 Warehouse Lights/Elec
1.00 Not Used --- ---
6 106 - Storage Building Area Warehouse 0.45 W/sqft LED: Free Hanging 90.1 Warehouse Lights/Elec
1.00 Not Used --- ---
7 107 - Fire Cache Building Area Warehouse 0.45 W/sqft LED: Free Hanging 90.1 Warehouse Lights/Elec
1.00 Not Used --- ---
2.3. Task Lighting, Electric Equipment and Miscellaneous Heat Gain
Index Space Task Lighting Electric Equipment Miscellaneous Heat Gain
Power Units Schedule Power Units Schedule Sens.
(BTU/hr) Schedule
Latent (BTU/hr)
Schedule
1 101 - Work Bay 0.00 W/sqft (None) 0.00 W/sqft (None) 0 (None) 0 (None)
2 102 - Laundry 0.00 W/sqft (None) 0.00 W/sqft (None) 0 (None) 0 (None)
3 103 - Toilet 0.00 W/sqft (None) 0.00 W/sqft (None) 0 (None) 0 (None)
4 104 - Janitor 0.00 W/sqft (None) 0.00 W/sqft (None) 0 (None) 0 (None)
5 105 - Toilet 0.00 W/sqft (None) 0.00 W/sqft (None) 0 (None) 0 (None)
6 106 - Storage 0.00 W/sqft (None) 0.00 W/sqft (None) 0 (None) 0 (None)
7 107 - Fire Cache 0.00 W/sqft (None) 0.00 W/sqft (None) 0 (None) 0 (None)
Hourly Analysis Program 6.1 Page 2 of 5
Prepared by: CROFT & Associates, Inc. 5:04 PM
2.4. Occupancy and Infiltration
Index Space Occupants Infiltration
Occupancy Units Schedule Activity Level Sens.
(BTU/hr/person) Latent
(BTU/hr/person) Cooling Airflow
Heating Airflow
Simulation Airflow
Units Occurs
1 101 - Work Bay 2 People
90.1 Warehouse
Occupants
Medium Work 295.0 455.0 0.03 0.03 0.00 CFM/sqft All Hours
2 102 - Laundry 1 People
90.1 Warehouse
Occupants
Medium Work 295.0 455.0 0.03 0.03 0.00 CFM/sqft All Hours
3 103 - Toilet 0 People
90.1 Warehouse
Occupants
User Defined 245.0 205.0 0.03 0.03 0.00 CFM/sqft All Hours
4 104 - Janitor 0 People
90.1 Warehouse
Occupants
User Defined 245.0 205.0 0.03 0.03 0.00 CFM/sqft All Hours
5 105 - Toilet 0 People
90.1 Warehouse
Occupants
User Defined 245.0 205.0 0.03 0.03 0.00 CFM/sqft All Hours
6 106 - Storage 0 People
90.1 Warehouse
Occupants
User Defined 245.0 205.0 0.03 0.03 0.00 CFM/sqft All Hours
7 107 - Fire Cache 0 People
90.1 Warehouse
Occupants
User Defined 245.0 205.0 0.03 0.03 0.00 CFM/sqft All Hours
Hourly Analysis Program 6.1 Page 3 of 5
Prepared by: CROFT & Associates, Inc. 5:04 PM
3. Zoning
Zone Space Level
Zone 1
101 - Work Bay Level 1
Zone 2
102 - Laundry Level 1
Zone 3
103 - Toilet Level 1
Zone 4
104 - Janitor Level 1
Zone 5
105 - Toilet Level 1
Unconditioned
106 - Storage Level 1
107 - Fire Cache Level 1
Unassigned (no spaces)
4. Assemblies
Category Surface Group Selected Assembly
Exterior Above Grade Wall
Default 2016 Zone 2 Above-Grade Steel-Framed Wall
Interior Wall
Default Default Wall
Roof
Default 2016 Zone 2-3 Insulation Entirely Above Deck
Slab Floor On Grade
At-Grade Floors Default Floor
Hourly Analysis Program 6.1 Page 4 of 5
Prepared by: CROFT & Associates, Inc. 5:04 PM
5. Windows & Doors
Category Tag Width x Height, Elevation Selected Assembly
Window
Window 2 3' 6" x 4' 2" , 3' 2016 Zone 2 Metal framing, fixed
Door
Double Fiberglass Exterior Door 1 6' x 7' 2016 Zone 3 Opaque Swinging
Fiberglass Exterior Door 1 3' x 7' 2016 Zone 3 Opaque Swinging
Ins. Steel Rollup Exterior Door 1 12' x 14' 2016 Zone 3 Opaque Nonswinging
Hourly Analysis Program 6.1 Page 5 of 5
H&V Zone 1 Input Data
Prepared by: CROFT & Associates, Inc. 5:04 PM
1. General Details:
Air System Name H&V Zone 1 Equipment Type Undefined Air System Type Single Zone CAV Space Model: Work Building - Heated/Ventilated Only
2. System Components:
Ventilation Air Data:
Airflow Control Constant Ventilation Airflow Ventilation Sizing Method Sum of Space OA Airflows Unocc. Damper Position Closed Damper Leak Rate 0 %
Central Heating Data:
Supply Temperature 85.0 F Heating Source Any Schedule JFMAMJJASOND Capacity Control Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type User defined Configuration Draw-thru Fan Performance 0.00 in wg Overall Efficiency 100 %
Duct System Data:
Supply Duct Data:
Duct Leakage 0 %
Return Duct or Plenum Data:
Return Air Via Ducted Return
3. Zone Components:
Assigned Zones:
Zone Zone Name
1 Zone 1
Number of zones 1
Thermostats and Zone Data:
Zone
Cooling T-Stat Occ.
Cooling T-Stat Unocc.
Heating T-Stat Occ.
Heating T-Stat Unocc.
T-Stat Throttling
Range Diversity
Factor
Direct Exhaust
Fan
(F) (F) (F) (F) (F) (%) (kW)
1 75.0 80.0 68.0 60.0 1.50 100 0.0
Thermostat Schedule 90.1 Warehouse HVAC Unoccupied Cooling is Available
Supply Terminals Data:
Zone Terminal Type Air
Distribution
Air Distribution
Effectiveness Specification
Air Distribution
Effectiveness Minimum Airflow
Design Supply Temp. Fan Perf.
Fan Efficiency
Diffuser (no reheat)
Ceiling supply / ceiling return
Not Used - 0.00 CFM/person - - -
4. Sizing Data (Computer-Generated):
System Sizing Data:
Sizing Data:
Supply Fan Airflow 1835.4 CFM Ventilation Airflow 589.2 CFM Heating Supply Temperature 85.0 F
Hourly Analysis Program 6.1 Page 1 of 10
H&V Zone 1 Input Data
Prepared by: CROFT & Associates, Inc. 5:04 PM
Hydronic Sizing Specifications:
Chilled Water Supply Temperature 44.0 F Chilled Water Delta-T 10.0 F Hot Water Supply Temperature 140.0 F Hot Water Delta-T 20.0 F
Safety Factors:
Cooling Sensible 0 % Cooling Latent 0 % Heating 0 %
Zone Sizing Data:
Zone Airflow Sizing Method Sum of space airflow rates Space Airflow Sizing Method Individual peak space loads
Zone Supply Airflow Zone Htg Unit Reheat Coil FPMBX Fan
(CFM) (MBH) (MBH) (CFM)
1 1835.4 - - -
5. Equipment Data No equipment data required for this system.
Hourly Analysis Program 6.1 Page 2 of 10
H&V Zone 2 Input Data
Prepared by: CROFT & Associates, Inc. 5:04 PM
1. General Details:
Air System Name H&V Zone 2 Equipment Type Undefined Air System Type Single Zone CAV
Airflow Control Constant Ventilation Airflow Ventilation Sizing Method Sum of Space OA Airflows Unocc. Damper Position Closed Damper Leak Rate 0 %
Central Heating Data:
Supply Temperature 85.0 F Heating Source Any Schedule JFMAMJJASOND Capacity Control Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type User defined Configuration Draw-thru Fan Performance 0.00 in wg Overall Efficiency 100 %
Duct System Data:
Supply Duct Data:
Duct Leakage 0 %
Return Duct or Plenum Data:
Return Air Via Ducted Return
3. Zone Components:
Assigned Zones:
Zone Zone Name
1 Zone 2
Number of zones 1
Thermostats and Zone Data:
Zone
Cooling T-Stat Occ.
Cooling T-Stat Unocc.
Heating T-Stat Occ.
Heating T-Stat Unocc.
T-Stat Throttling
Range Diversity
Factor
Direct Exhaust
Fan
(F) (F) (F) (F) (F) (%) (kW)
1 75.0 80.0 68.0 60.0 1.50 100 0.0
Thermostat Schedule 90.1 Warehouse HVAC Unoccupied Cooling is Available
Supply Terminals Data:
Zone Terminal Type Air
Distribution
Air Distribution
Effectiveness Specification
Air Distribution
Effectiveness Minimum Airflow
Design Supply Temp. Fan Perf.
Fan Efficiency
Diffuser (no reheat)
Ceiling supply / ceiling return
Not Used - 0.00 CFM/person - - -
4. Sizing Data (Computer-Generated):
System Sizing Data:
Sizing Data:
Supply Fan Airflow 73.5 CFM Ventilation Airflow 24.5 CFM Heating Supply Temperature 85.0 F
Hydronic Sizing Specifications:
Hourly Analysis Program 6.1 Page 3 of 10
H&V Zone 2 Input Data
Prepared by: CROFT & Associates, Inc. 5:04 PM
Chilled Water Supply Temperature 44.0 F Chilled Water Delta-T 10.0 F Hot Water Supply Temperature 140.0 F Hot Water Delta-T 20.0 F
Safety Factors:
Cooling Sensible 0 % Cooling Latent 0 % Heating 0 %
Zone Sizing Data:
Zone Airflow Sizing Method Sum of space airflow rates Space Airflow Sizing Method Individual peak space loads
Zone Supply Airflow Zone Htg Unit Reheat Coil FPMBX Fan
(CFM) (MBH) (MBH) (CFM)
1 73.5 - - -
5. Equipment Data
Hourly Analysis Program 6.1 Page 4 of 10
H&V Zone 3 Input Data
Prepared by: CROFT & Associates, Inc. 5:04 PM
1. General Details:
Air System Name H&V Zone 3 Equipment Type Undefined Air System Type Single Zone CAV
Airflow Control Constant Ventilation Airflow Ventilation Sizing Method Sum of Space OA Airflows Unocc. Damper Position Closed Damper Leak Rate 0 %
Central Heating Data:
Supply Temperature 85.0 F Heating Source Any Schedule JFMAMJJASOND Capacity Control Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type User defined Configuration Draw-thru Fan Performance 0.00 in wg Overall Efficiency 100 %
Duct System Data:
Supply Duct Data:
Duct Leakage 0 %
Return Duct or Plenum Data:
Return Air Via Ducted Return
3. Zone Components:
Assigned Zones:
Zone Zone Name
1 Zone 3
Number of zones 1
Thermostats and Zone Data:
Zone
Cooling T-Stat Occ.
Cooling T-Stat Unocc.
Heating T-Stat Occ.
Heating T-Stat Unocc.
T-Stat Throttling
Range Diversity
Factor
Direct Exhaust
Fan
(F) (F) (F) (F) (F) (%) (kW)
1 75.0 80.0 68.0 60.0 1.50 100 0.0
Thermostat Schedule 90.1 Warehouse HVAC Unoccupied Cooling is Available
Supply Terminals Data:
Zone Terminal Type Air
Distribution
Air Distribution
Effectiveness Specification
Air Distribution
Effectiveness Minimum Airflow
Design Supply Temp. Fan Perf.
Fan Efficiency
Diffuser (no reheat)
Ceiling supply / ceiling return
Not Used - 0.00 CFM/person - - -
4. Sizing Data (Computer-Generated):
System Sizing Data:
Sizing Data:
Supply Fan Airflow 150.0 CFM Ventilation Airflow 150.0 CFM Heating Supply Temperature 85.0 F
Hourly Analysis Program 6.1 Page 5 of 10
H&V Zone 3 Input Data
Prepared by: CROFT & Associates, Inc. 5:04 PM
Chilled Water Supply Temperature 44.0 F Chilled Water Delta-T 10.0 F Hot Water Supply Temperature 140.0 F Hot Water Delta-T 20.0 F
Safety Factors:
Cooling Sensible 0 % Cooling Latent 0 % Heating 0 %
Zone Sizing Data:
Zone Airflow Sizing Method Sum of space airflow rates Space Airflow Sizing Method Individual peak space loads
Zone Supply Airflow Zone Htg Unit Reheat Coil FPMBX Fan
(CFM) (MBH) (MBH) (CFM)
1 150.0 - - -
5. Equipment Data
Hourly Analysis Program 6.1 Page 6 of 10
H&V Zone 4 Input Data
Prepared by: CROFT & Associates, Inc. 5:04 PM
1. General Details:
Air System Name H&V Zone 4 Equipment Type Undefined Air System Type Single Zone CAV
Airflow Control Constant Ventilation Airflow Ventilation Sizing Method Sum of Space OA Airflows Unocc. Damper Position Closed Damper Leak Rate 0 %
Central Heating Data:
Supply Temperature 85.0 F Heating Source Any Schedule JFMAMJJASOND Capacity Control Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type User defined Configuration Draw-thru Fan Performance 0.00 in wg Overall Efficiency 100 %
Duct System Data:
Supply Duct Data:
Duct Leakage 0 %
Return Duct or Plenum Data:
Return Air Via Ducted Return
3. Zone Components:
Assigned Zones:
Zone Zone Name
1 Zone 4
Number of zones 1
Thermostats and Zone Data:
Zone
Cooling T-Stat Occ.
Cooling T-Stat Unocc.
Heating T-Stat Occ.
Heating T-Stat Unocc.
T-Stat Throttling
Range Diversity
Factor
Direct Exhaust
Fan
(F) (F) (F) (F) (F) (%) (kW)
1 75.0 80.0 68.0 60.0 1.50 100 0.0
Thermostat Schedule 90.1 Warehouse HVAC Unoccupied Cooling is Available
Supply Terminals Data:
Zone Terminal Type Air
Distribution
Air Distribution
Effectiveness Specification
Air Distribution
Effectiveness Minimum Airflow
Design Supply Temp. Fan Perf.
Fan Efficiency
Diffuser (no reheat)
Ceiling supply / ceiling return
Not Used - 0.00 CFM/person - - -
4. Sizing Data (Computer-Generated):
System Sizing Data:
Sizing Data:
Supply Fan Airflow 150.0 CFM Ventilation Airflow 150.0 CFM Heating Supply Temperature 85.0 F
Hourly Analysis Program 6.1 Page 7 of 10
H&V Zone 4 Input Data
Prepared by: CROFT & Associates, Inc. 5:04 PM
Chilled Water Supply Temperature 44.0 F Chilled Water Delta-T 10.0 F Hot Water Supply Temperature 140.0 F Hot Water Delta-T 20.0 F
Safety Factors:
Cooling Sensible 0 % Cooling Latent 0 % Heating 0 %
Zone Sizing Data:
Zone Airflow Sizing Method Sum of space airflow rates Space Airflow Sizing Method Individual peak space loads
Zone Supply Airflow Zone Htg Unit Reheat Coil FPMBX Fan
(CFM) (MBH) (MBH) (CFM)
1 150.0 - - -
5. Equipment Data
Hourly Analysis Program 6.1 Page 8 of 10
H&V Zone 5 Input Data
Prepared by: CROFT & Associates, Inc. 5:04 PM
1. General Details:
Air System Name H&V Zone 5 Equipment Type Undefined Air System Type Single Zone CAV
Airflow Control Constant Ventilation Airflow Ventilation Sizing Method Sum of Space OA Airflows Unocc. Damper Position Closed Damper Leak Rate 0 %
Central Heating Data:
Supply Temperature 85.0 F Heating Source Any Schedule JFMAMJJASOND Capacity Control Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type User defined Configuration Draw-thru Fan Performance 0.00 in wg Overall Efficiency 100 %
Duct System Data:
Supply Duct Data:
Duct Leakage 0 %
Return Duct or Plenum Data:
Return Air Via Ducted Return
3. Zone Components:
Assigned Zones:
Zone Zone Name
1 Zone 5
Number of zones 1
Thermostats and Zone Data:
Zone
Cooling T-Stat Occ.
Cooling T-Stat Unocc.
Heating T-Stat Occ.
Heating T-Stat Unocc.
T-Stat Throttling
Range Diversity
Factor
Direct Exhaust
Fan
(F) (F) (F) (F) (F) (%) (kW)
1 75.0 80.0 68.0 60.0 1.50 100 0.0
Thermostat Schedule 90.1 Warehouse HVAC Unoccupied Cooling is Available
Supply Terminals Data:
Zone Terminal Type Air
Distribution
Air Distribution
Effectiveness Specification
Air Distribution
Effectiveness Minimum Airflow
Design Supply Temp. Fan Perf.
Fan Efficiency
Diffuser (no reheat)
Ceiling supply / ceiling return
Not Used - 0.00 CFM/person - - -
4. Sizing Data (Computer-Generated):
System Sizing Data:
Sizing Data:
Supply Fan Airflow 150.0 CFM Ventilation Airflow 150.0 CFM Heating Supply Temperature 85.0 F
Hourly Analysis Program 6.1 Page 9 of 10
H&V Zone 5 Input Data
Prepared by: CROFT & Associates, Inc. 5:04 PM
Chilled Water Supply Temperature 44.0 F Chilled Water Delta-T 10.0 F Hot Water Supply Temperature 140.0 F Hot Water Delta-T 20.0 F
Safety Factors:
Cooling Sensible 0 % Cooling Latent 0 % Heating 0 %
Zone Sizing Data:
Zone Airflow Sizing Method Sum of space airflow rates Space Airflow Sizing Method Individual peak space loads
Zone Supply Airflow Zone Htg Unit Reheat Coil FPMBX Fan
(CFM) (MBH) (MBH) (CFM)
1 150.0 - - -
5. Equipment Data
Hourly Analysis Program 6.1 Page 10 of 10
Zone Sizing Summary for H&V Zone 1 (In Alternative: Default Alternative)
Project: 2022-419 CRWC 12/08/2023
Prepared by: CROFT & Associates, Inc. 5:02 PM
Air System Information Air System Name H&V Zone 1 Equipment Class UNDEF Air System Type SZCAV
Number of zones 1 Floor Area 3162.4 sqft Location Occonee County Regional, SC, USA
Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated
Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads
Zone Terminal Sizing Data
Zone Name
Design Supply Airflow
(CFM)
Minimum Supply Airflow
(CFM)
Zone CFM/sqft
Reheat Coil
Capacity
(MBH)
Reheat Coil
Water gpm
@ 20.0 F
Zone Htg Unit
Coil Capacity
(MBH)
Zone Htg Unit Water gpm
@ 20.0 F
Mixing Box Fan Airflow
(CFM)
Zone 1 1835 1835 0.58 0.0 0.00 0.0 0.00 0
Zone Peak Sensible Loads
Zone Zone Zone
Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (sqft)
Zone 1 0.0 September 18:00 32.6 3162.4
Space Loads and Airflows
Zone Name / Space Name
Cooling Sensible
(MBH)
Time of Peak
Sensible Load
Air Flow
(CFM)
Heating Load
(MBH)
Floor Area (sqft)
Space CFM/sqft
Zone 1
101 - Work Bay 0.0 September 18:00 1835 32.6 3162.4 0.58
Hourly Analysis Program 6.1 Page 1 of 10
Zone Heat Balance Summary for H&V Zone 1
Project: 2022-419 CRWC 12/08/2023
Prepared by: CROFT & Associates, Inc. 5:02 PM
Table 1. Heat Balance Loads for Zone Zone 1
DESIGN COOLING - SEPTEMBER 18:00 DESIGN HEATING
OA DB / WB 90.8 F / 72.3 F OA DB / WB 24.9 F / 20.8 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 68.0 F
Zone Heat Balance Component Details Sensible [BTU/hr]
Latent [BTU/hr]
Details Sensible [BTU/hr]
Latent [BTU/hr]
Exterior Wall Convection 1956 sqft -111 - 1956 sqft 5097 -
Roof Convection 3162 sqft -299 - 3162 sqft 7860 -
Window Convection 15 sqft -18 - 15 sqft 142 -
Skylight Convection 0 sqft 0 - 0 sqft 0 -
Door Convection 714 sqft -31 - 714 sqft 3430 -
Floor Convection 3162 sqft -682 - 3162 sqft 9560 -
Interior Wall Convection 1338 sqft -196 - 1338 sqft 2571 -
Ceiling Convection 0 sqft 0 - 0 sqft 0 -
Overhead Lighting Convection 144 W 208 - 0 W 0 -
Task Lighting Convection 0 W 0 - 0 W 0 -
Electric Equipment Convection 0 W 0 - 0 W 0 -
People Convection 0 0 0 0 0 0
Infiltration 76 CFM -956 -540 88 CFM 3966 0
Miscellaneous Equipment - 0 0 - 0 0
Air Internal Energy Change - 2085 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
0 -540 - 32626 0
Key:
Positive values are cooling loads Negative values are heating loads
Positive values are heating loads Negative values are cooling loads
Note 1: Surface convection line items show the combined effects of conductive heat gain to the surface and radiative heat gains absorbed at the surface which are then convected to room air.
Note 2: Lighting, equipment, and people line items include only the direct convective heat gain from the heat source to the room air. The radiative portion of the heat gain is first absorbed by surfaces in the room and then later convected from the surface to the air.
Therefore the effect of the radiative portion of the heat gain is found in the surface convection line items.
Note 3: Solar heat gain is absorbed by surfaces in the room, re-radiated to other surfaces, and finally convected from the surfaces to room air. Therefore, the effect of solar heat gain is found in the surface convection line items.
Hourly Analysis Program 6.1 Page 2 of 10
Zone Sizing Summary for H&V Zone 2
Project: 2022-419 CRWC 12/08/2023
Prepared by: CROFT & Associates, Inc. 5:02 PM
Air System Information Air System Name H&V Zone 2 Equipment Class UNDEF Air System Type SZCAV
Number of zones 1 Floor Area 141.5 sqft Location Occonee County Regional, SC, USA
Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated
Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads
Zone Terminal Sizing Data
Zone Name
Design Supply Airflow
(CFM)
Minimum Supply Airflow
(CFM)
Zone CFM/sqft
Reheat Coil
Capacity
(MBH)
Reheat Coil
Water gpm
@ 20.0 F
Zone Htg Unit
Coil Capacity
(MBH)
Zone Htg Unit Water gpm
@ 20.0 F
Mixing Box Fan Airflow
(CFM)
Zone 2 74 74 0.52 0.0 0.00 0.0 0.00 0
Zone Peak Sensible Loads
Zone Zone Zone
Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (sqft)
Zone 2 0.0 July 7:00 1.3 141.5
Space Loads and Airflows
Zone Name / Space Name
Cooling Sensible
(MBH)
Time of Peak
Sensible Load
Air Flow
(CFM)
Heating Load
(MBH)
Floor Area (sqft)
Space CFM/sqft
Zone 2
102 - Laundry 0.0 July 7:00 74 1.3 141.5 0.52
Hourly Analysis Program 6.1 Page 3 of 10
Zone Heat Balance Summary for H&V Zone 2
Project: 2022-419 CRWC 12/08/2023
Prepared by: CROFT & Associates, Inc. 5:02 PM
Table 1. Heat Balance Loads for Zone Zone 2
DESIGN COOLING - JULY 7:00 DESIGN HEATING
OA DB / WB 78.2 F / 69.3 F OA DB / WB 24.9 F / 20.8 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 68.0 F
Zone Heat Balance Component Details Sensible [BTU/hr]
Latent [BTU/hr]
Details Sensible [BTU/hr]
Latent [BTU/hr]
Exterior Wall Convection 144 sqft -63 - 144 sqft 298 -
Roof Convection 141 sqft -55 - 141 sqft 231 -
Window Convection 0 sqft 0 - 0 sqft 0 -
Skylight Convection 0 sqft 0 - 0 sqft 0 -
Door Convection 0 sqft 0 - 0 sqft 0 -
Floor Convection 141 sqft 34 - 141 sqft 350 -
Interior Wall Convection 733 sqft -7 - 733 sqft 215 -
Ceiling Convection 0 sqft 0 - 0 sqft 0 -
Overhead Lighting Convection 64 W 138 - 0 W 0 -
Task Lighting Convection 0 W 0 - 0 W 0 -
Electric Equipment Convection 0 W 0 - 0 W 0 -
People Convection 1 89 455 0 0 0
Infiltration 4 CFM -92 -87 5 CFM 213 0
Miscellaneous Equipment - 0 0 - 0 0
Air Internal Energy Change - -43 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
0 368 - 1307 0
Key:
Positive values are cooling loads Negative values are heating loads
Positive values are heating loads Negative values are cooling loads
Note 1: Surface convection line items show the combined effects of conductive heat gain to the surface and radiative heat gains absorbed at the surface which are then convected to room air.
Note 2: Lighting, equipment, and people line items include only the direct convective heat gain from the heat source to the room air. The radiative portion of the heat gain is first absorbed by surfaces in the room and then later convected from the surface to the air.
Therefore the effect of the radiative portion of the heat gain is found in the surface convection line items.
Note 3: Solar heat gain is absorbed by surfaces in the room, re-radiated to other surfaces, and finally convected from the surfaces to room
Hourly Analysis Program 6.1 Page 4 of 10
Zone Sizing Summary for H&V Zone 3
Project: 2022-419 CRWC 12/08/2023
Prepared by: CROFT & Associates, Inc. 5:02 PM
Air System Information Air System Name H&V Zone 3 Equipment Class UNDEF Air System Type SZCAV
Number of zones 1 Floor Area 79.6 sqft Location Occonee County Regional, SC, USA
Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated
Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads
Zone Terminal Sizing Data
Zone Name
Design Supply Airflow
(CFM)
Minimum Supply Airflow
(CFM)
Zone CFM/sqft
Reheat Coil
Capacity
(MBH)
Reheat Coil
Water gpm
@ 20.0 F
Zone Htg Unit
Coil Capacity
(MBH)
Zone Htg Unit Water gpm
@ 20.0 F
Mixing Box Fan Airflow
(CFM)
Zone 3 150 150 1.88 0.0 0.00 0.0 0.00 0
Zone Peak Sensible Loads
Zone Zone Zone
Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (sqft)
Zone 3 0.0 February 15:00 2.0 79.6
Space Loads and Airflows
Zone Name / Space Name
Cooling Sensible
(MBH)
Time of Peak
Sensible Load
Air Flow
(CFM)
Heating Load
(MBH)
Floor Area (sqft)
Space CFM/sqft
Zone 3
103 - Toilet 0.0 February 15:00 150 2.0 79.6 1.88
Hourly Analysis Program 6.1 Page 5 of 10
Zone Heat Balance Summary for H&V Zone 3
Project: 2022-419 CRWC 12/08/2023
Prepared by: CROFT & Associates, Inc. 5:02 PM
Table 1. Heat Balance Loads for Zone Zone 3
DESIGN COOLING - FEBRUARY 15:00 DESIGN HEATING
OA DB / WB 76.2 F / 63.9 F OA DB / WB 24.9 F / 20.8 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 68.0 F
Zone Heat Balance Component Details Sensible [BTU/hr]
Latent [BTU/hr]
Details Sensible [BTU/hr]
Latent [BTU/hr]
Exterior Wall Convection 297 sqft -49 - 297 sqft 815 -
Roof Convection 80 sqft 13 - 80 sqft 177 -
Window Convection 0 sqft 0 - 0 sqft 0 -
Skylight Convection 0 sqft 0 - 0 sqft 0 -
Door Convection 0 sqft 0 - 0 sqft 0 -
Floor Convection 80 sqft -7 - 80 sqft 435 -
Interior Wall Convection 297 sqft 13 - 297 sqft 182 -
Ceiling Convection 0 sqft 0 - 0 sqft 0 -
Overhead Lighting Convection 36 W 78 - 0 W 0 -
Task Lighting Convection 0 W 0 - 0 W 0 -
Electric Equipment Convection 0 W 0 - 0 W 0 -
People Convection 0 0 0 0 0 0
Infiltration 9 CFM -34 0 10 CFM 439 0
Miscellaneous Equipment - 0 0 - 0 0
Air Internal Energy Change - -13 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
0 0 - 2047 0
Key:
Positive values are cooling loads Negative values are heating loads
Positive values are heating loads Negative values are cooling loads
Note 1: Surface convection line items show the combined effects of conductive heat gain to the surface and radiative heat gains absorbed at the surface which are then convected to room air.
Note 2: Lighting, equipment, and people line items include only the direct convective heat gain from the heat source to the room air. The radiative portion of the heat gain is first absorbed by surfaces in the room and then later convected from the surface to the air.
Therefore the effect of the radiative portion of the heat gain is found in the surface convection line items.
Note 3: Solar heat gain is absorbed by surfaces in the room, re-radiated to other surfaces, and finally convected from the surfaces to room
Hourly Analysis Program 6.1 Page 6 of 10
Zone Sizing Summary for H&V Zone 4
Project: 2022-419 CRWC 12/08/2023
Prepared by: CROFT & Associates, Inc. 5:02 PM
Air System Information Air System Name H&V Zone 4 Equipment Class UNDEF Air System Type SZCAV
Number of zones 1 Floor Area 42.5 sqft Location Occonee County Regional, SC, USA
Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated
Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads
Zone Terminal Sizing Data
Zone Name
Design Supply Airflow
(CFM)
Minimum Supply Airflow
(CFM)
Zone CFM/sqft
Reheat Coil
Capacity
(MBH)
Reheat Coil
Water gpm
@ 20.0 F
Zone Htg Unit
Coil Capacity
(MBH)
Zone Htg Unit Water gpm
@ 20.0 F
Mixing Box Fan Airflow
(CFM)
Zone 4 150 150 3.53 0.0 0.00 0.0 0.00 0
Zone Peak Sensible Loads
Zone Zone Zone
Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (sqft)
Zone 4 0.0 January 2:00 0.8 42.5
Space Loads and Airflows
Zone Name / Space Name
Cooling Sensible
(MBH)
Time of Peak
Sensible Load
Air Flow
(CFM)
Heating Load
(MBH)
Floor Area (sqft)
Space CFM/sqft
Zone 4
104 - Janitor 0.0 January 2:00 150 0.8 42.5 3.53
Hourly Analysis Program 6.1 Page 7 of 10
Zone Heat Balance Summary for H&V Zone 4
Project: 2022-419 CRWC 12/08/2023
Prepared by: CROFT & Associates, Inc. 5:02 PM
Table 1. Heat Balance Loads for Zone Zone 4
DESIGN COOLING - JANUARY 2:00 DESIGN HEATING
OA DB / WB 57.1 F / 55.9 F OA DB / WB 24.9 F / 20.8 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 68.0 F
Zone Heat Balance Component Details Sensible [BTU/hr]
Latent [BTU/hr]
Details Sensible [BTU/hr]
Latent [BTU/hr]
Exterior Wall Convection 106 sqft 23 - 106 sqft 252 -
Roof Convection 42 sqft -7 - 42 sqft 80 -
Window Convection 0 sqft 0 - 0 sqft 0 -
Skylight Convection 0 sqft 0 - 0 sqft 0 -
Door Convection 0 sqft 0 - 0 sqft 0 -
Floor Convection 42 sqft 5 - 42 sqft 179 -
Interior Wall Convection 312 sqft 47 - 312 sqft 112 -
Ceiling Convection 0 sqft 0 - 0 sqft 0 -
Overhead Lighting Convection 1 W 2 - 0 W 0 -
Task Lighting Convection 0 W 0 - 0 W 0 -
Electric Equipment Convection 0 W 0 - 0 W 0 -
People Convection 0 0 0 0 0 0
Infiltration 3 CFM -74 0 3 CFM 156 0
Miscellaneous Equipment - 0 0 - 0 0
Air Internal Energy Change - 5 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
0 0 - 779 0
Key:
Positive values are cooling loads Negative values are heating loads
Positive values are heating loads Negative values are cooling loads
Note 1: Surface convection line items show the combined effects of conductive heat gain to the surface and radiative heat gains absorbed at the surface which are then convected to room air.
Note 2: Lighting, equipment, and people line items include only the direct convective heat gain from the heat source to the room air. The radiative portion of the heat gain is first absorbed by surfaces in the room and then later convected from the surface to the air.
Therefore the effect of the radiative portion of the heat gain is found in the surface convection line items.
Note 3: Solar heat gain is absorbed by surfaces in the room, re-radiated to other surfaces, and finally convected from the surfaces to room
Hourly Analysis Program 6.1 Page 8 of 10
Zone Sizing Summary for H&V Zone 5
Project: 2022-419 CRWC 12/08/2023
Prepared by: CROFT & Associates, Inc. 5:02 PM
Air System Information Air System Name H&V Zone 5 Equipment Class UNDEF Air System Type SZCAV
Number of zones 1 Floor Area 88.8 sqft Location Occonee County Regional, SC, USA
Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated
Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads
Zone Terminal Sizing Data
Zone Name
Design Supply Airflow
(CFM)
Minimum Supply Airflow
(CFM)
Zone CFM/sqft
Reheat Coil
Capacity
(MBH)
Reheat Coil
Water gpm
@ 20.0 F
Zone Htg Unit
Coil Capacity
(MBH)
Zone Htg Unit Water gpm
@ 20.0 F
Mixing Box Fan Airflow
(CFM)
Zone 5 150 150 1.69 0.0 0.00 0.0 0.00 0
Zone Peak Sensible Loads
Zone Zone Zone
Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (sqft)
Zone 5 0.0 January 15:00 1.0 88.8
Space Loads and Airflows
Zone Name / Space Name
Cooling Sensible
(MBH)
Time of Peak
Sensible Load
Air Flow
(CFM)
Heating Load
(MBH)
Floor Area (sqft)
Space CFM/sqft
Zone 5
105 - Toilet 0.0 January 15:00 150 1.0 88.8 1.69
Hourly Analysis Program 6.1 Page 9 of 10
Zone Heat Balance Summary for H&V Zone 5
Project: 2022-419 CRWC 12/08/2023
Prepared by: CROFT & Associates, Inc. 5:02 PM
Table 1. Heat Balance Loads for Zone Zone 5
DESIGN COOLING - JANUARY 15:00 DESIGN HEATING
OA DB / WB 73.2 F / 61.9 F OA DB / WB 24.9 F / 20.8 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 68.0 F
Zone Heat Balance Component Details Sensible [BTU/hr]
Latent [BTU/hr]
Details Sensible [BTU/hr]
Latent [BTU/hr]
Exterior Wall Convection 120 sqft 23 - 120 sqft 264 -
Roof Convection 89 sqft 2 - 89 sqft 156 -
Window Convection 0 sqft 0 - 0 sqft 0 -
Skylight Convection 0 sqft 0 - 0 sqft 0 -
Door Convection 0 sqft 0 - 0 sqft 0 -
Floor Convection 89 sqft -17 - 89 sqft 264 -
Interior Wall Convection 498 sqft -58 - 498 sqft 174 -
Ceiling Convection 0 sqft 0 - 0 sqft 0 -
Overhead Lighting Convection 40 W 87 - 0 W 0 -
Task Lighting Convection 0 W 0 - 0 W 0 -
Electric Equipment Convection 0 W 0 - 0 W 0 -
People Convection 0 0 0 0 0 0
Infiltration 4 CFM -24 0 4 CFM 178 0
Miscellaneous Equipment - 0 0 - 0 0
Air Internal Energy Change - -13 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
0 0 - 1036 0
Key:
Positive values are cooling loads Negative values are heating loads
Positive values are heating loads Negative values are cooling loads
Note 1: Surface convection line items show the combined effects of conductive heat gain to the surface and radiative heat gains absorbed at the surface which are then convected to room air.
Note 2: Lighting, equipment, and people line items include only the direct convective heat gain from the heat source to the room air. The radiative portion of the heat gain is first absorbed by surfaces in the room and then later convected from the surface to the air.
Therefore the effect of the radiative portion of the heat gain is found in the surface convection line items.
Note 3: Solar heat gain is absorbed by surfaces in the room, re-radiated to other surfaces, and finally convected from the surfaces to room
Hourly Analysis Program 6.1 Page 10 of 10
| H&V Warehouse HVAC Bldg Data |
| H&V Warehouse HVAC Zone Data |
| H&V Warehouse HVAC System Data |