Attachment 03 CRWC Full Set Drawings (Signed).pdf
PDF 26 MB Posted
- Attached to
- CRRD Work Center Construction Project Federal contract opportunity
- Solicitation number
- 12445224R0011
- Issued by
- Department of Agriculture Forest Service
About this file
This document appears to be a set of full construction drawings for the CRRD Work Center Construction Project, which is a solicitation issued by the Department of Agriculture Forest Service. The solicitation is for the construction of a new work center building at the Chattooga River Ranger District in South Lakemont, Georgia (Rabun County). A site visit will be held on 6/13/2024 at 9am, and all questions are due by 6/17/2024 at 1pm via email. The solicitation number is 12445224R0011.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amendment 01 12445224R0011 CRRD Work Center.pdf | ||
| Attachment 01 SOI (Section B).xlsx | XLSX spreadsheet | |
| Attachment 05 CRRD office work center NEPA docs- 2006.pdf | ||
| Attachment 08 IBC Special Inspections.pdf | ||
| Attachment 00 SOW CRRD Work Center Con. (Section C).docx | DOCX document | |
| Attachment 06 CRWC 22419 HVAC Calculations.pdf | ||
| Attachment 02 CRRD Work Center OPM Specifications.pdf | ||
| Attachment 09 WD Building GA20240104 Rabun County.pdf | ||
| RFP 12445224R0011 CRRD Work Center Construction P.pdf | ||
| Attachment 04 CRRD Work Center Geotechnical Report.pdf | ||
| Attachment 07 CRWC 22419 Hydrologic Calculations.pdf |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT DIRECTORY
STRUCTURAL ENGINEER
MH STRUCTURES
POWDER SPRINGS, GA 30127
404.317.0746
MATT HAMMOND, P.E.
MATT@MHSTRUCTURES.COM
PROJECT SITE
LAKE RABUN
OWNER
USDA
U.S. FOREST SERVICE,
SOUTHERN REGION
1720 PEACHTREE STREET, NW
SUITE 716 NORTH
ATLANTA, GA 30309
CIVIL ENGINEER
CROFT & ASSOCIATES, INC.
3380 BLUE SPRINGS ROAD
KENNESAW, GA 30144
770.529.7714
CHRIS JUNG, P.E.
CJUNG@CROFTAE.COM
ARCHITECT
CROFT & ASSOCIATES, INC.
3380 BLUE SPRINGS ROAD
KENNESAW, GA 30144
770.529.7714
ANTHONY IORILLO
ANTHONY@CROFTAE.COM
MEP ENGINEER
CROFT & ASSOCIATES, INC.
3380 BLUE SPRINGS ROAD
KENNESAW, GA 30144
770.529.7714
MILES JOHNSON
MJOHNSON@CROFTAE.COM
LOW VOLTAGE SYSTEMS ENGINEER
J & A ENGINEERING CONSULTANTS
4994 LOWER ROSWELL ROAD, SUITE 1
MARIETTA, GA 30068
770.817.4220
STUART WALL
SWALL@JAENGINEERING.NET
CHATTOOGA RIVER
WORK CENTER
PROJECT
12445222C008
FOREST SERVICE REGION 8
UNITED STATES DEPARTMENT OF AGRICULTURE
PROJECT FINANCED BY
2"
ARCHITECT
CROFT & ASSOCIATES, INC.
2"1'-8"2"1'-8 1/2"
8'-0"
BLACK LOGOS
8'x4' EARTH CONTACT
PLYWOOD, PAINTED
WHITE
4x4x8' POST
3' MIN. DEPTH
IN GROUND
ARIAL BLACK
3" BOLD TEXT
ARIAL BLACK
2" BOLD TEXT
ARIAL BLACK
3" TEXT
M
IN
United States Department of Agriculture Forest Service
USDA FOREST SERVICE
REGION 8
PROJECT NO.
CHECKED
DRAWN
DESIGNER
ARCHIVE NO.
DATE SIGNED
DRAWING TITLE
PROJECT NAME
SHEET
DWG SHEET NO.
Croft & Associates 3380 Blue Springs Road
Kennesaw, Georgia 30144
770.529.7714 (p) www.croftae.com
G-001
COVER SHEET
2022-419
SLA
MJ
CHATTOOGA
RIVER WORK
CENTER
9975 Highway 441S Lakemont, GA
30552
AWI
05-10-24
A PROJECT FOR
UNITED STATES DEPARTMENT OF AGRICULTURE
U.S. FOREST SERVICE, SOUTHERN REGION
CHATTOOGA RIVER WORK CENTER
9975 Highway 441S Lakemont, GA 30552
DRAWING ISSUANCE LOG
N U
M B
E R
SHEET NAME 2
-1 -0
S
U B
M
IT
T A
L
-0 -2
S
U B
M
IT
T
-1 -1
S
U B
M
IT
T
-1
-1
C
D 's
-0 -2
M O
D P
-0 -0
S
IG
N A
P P
R O
V A
L S
E T
-0 -1
R E
V
IS
IO
N
GENERAL
G-001 COVER SHEET X X X X X X
LS101 LIFE SAFETY PLAN X X X X X X
1 SURVEY X X X
CIVIL
C-001 GENERAL NOTES X X X X
C-100 SITE & UTILITY PLAN X X X X
C-101 TRUCK MOVEMENT PLAN X X X
C-102 GRADING PLAN X X X
C-103 EROSION CONTROL PLAN X X X
C-500 CIVIL DETAILS 1 OF 3 X X X
C-501 CIVIL DETAILS 2 OF 3 X X X
C-502 CIVIL DETAILS 3 OF 3 X X X
C-800 SANITARY SEWER PROFILE X X X
STRUCTURAL
S-001 GENERAL NOTES X X X X
S-002 TYPICAL WOOD & SLAB DETAILS X X X X
S-003 TYPICAL WOOD DETAILS X X X X
S-101 FOUNDATION PLAN X X X X
S-102 ROOF FRAMING PLAN X X X X
S-201 WIND PRESSURE PLAN X X X X
ARCHITECTURAL
A-001 WALL TYPES X X X X X
A-100 SLAB PLAN X X X X
A-101 FLOOR PLAN X X X X X
A-131 REFLECTED CEILING PLAN X X X X
A-151 ROOF PLAN AND DETAILS X X X X
A-201 EXTERIOR ELEVATIONS X X X X
A-301 BUILDING SECTIONS X X X X
A-351 DETAILS X X X X X
A-352 DETAILS X X X X
A-353 DETAILS X X X X
A-401 ENLARGED RESTROOM PLAN AND INTERIOR ELEVATIONS X X X X
A-402 STANDARD RESTROOM DETAILS & MILLWORK X X
A-601 DOOR SCHEDULE AND WINDOW SCHEDULE X X X X
A-701 FINISH SCHEDULES X X X X
PLUMBING
P-001 PLUMBING CALCULATIONS AND LEGEND X X X X
P-101 UNDERGROUND PLUMBING AND SANITARY PLANS X X X X
P-102 DOMESTIC WATER, AIR, AND GAS PLAN X X X X
P-501 PLUMBING DETAILS X X X
P-601 PLUMBING SCHEDULES X X X X
P-901 PLUMBING RISERS X X X
MECHANICAL
M-001 MECHANICAL LEGEND AND SCHEDULES X X X X
M-101 MECHANICAL PLAN X X X X
ELECTRICAL
E-001 ELECTRICAL GENERAL NOTES X X X X
E-100 ELECTRICAL SITE PLAN X X X X
E-101 FLOOR PLAN - LIGHTING X X X X
E-102 FLOOR PLAN - POWER X X X X
E-401 ELECTRICAL DETAILS X X X X
E-501 ELECTRICAL SCHEDULES X X X
LOW VOLTAGE SYSTEMS
LV-000 COVER PAGE X
LV-101 SITE PLAN X
LV-201 LEVEL 1 - FLOOR PLAN X
LV-301 LARGE SCAPE X
LV-401 ONE-LINE DIAGRAMS X
LV-501 DETAILS X
LV-502 DETAILS X
LV-503 DETAILS X
Grand total: 54
0 1 2 3 FT
3/4" = 1'-0"
G-001
PROJECT SIGN
DEDUCTIVE ALTERNATES
N0. DESCRIPTION
1 CHANGE WIDTH OF CONCRETE APRON. REPLACE A PORTION OF THE CONCRETE APRON
WITH GRAVEL PAVEMENT IN THE SCOPE ACCORDING TO THE FOLLOWING: ALONG THE
PERIMETER OF THE BUILDING REDUCE THE WIDTH OF THE CONCRETE FROM 9’ WIDE TO 6’
WIDE. REPLACE THE REMOVED CONCRETE PAVEMENT.
2 REMOVE PARKING BUMPERS. REMOVE FROM THE SCOPE 24 METAL PIPE BOLLARDS AT
CORNERS OF THE BUILDING AND AT OVERHEAD DOORS, LEAVING THE THREE BOLLARDS AT
THE COMPRESSOR.
3 REPLACE ROOF SYSTEM WITH PLYWOOD. IN THE SCOPE REPLACE THE SIPS ROOF PANELS
WITH 5/8” THICK WOOD SHEATHING. THE SHEATHING SHALL BE LAID WITH THE STRONG
DIRECTION OF THE PANEL PERPENDICULAR TO THE TRUSSES AND BE LAID WITH
STAGGERED JOINTS. THE SHEATHING SHALL BE ATTACHED TO STRUCTURE WITH 8D NAILS
SPACED AT 6-INCHES ON-CENTER ALONG THE EDGES AND IN THE FIELD OF THE PANEL;
BOUNDARY EDGES SHALL ALSO BE ATTACHED WITH 8D NAILS SPACED AT 6-INCHES
ON-CENTER. PANEL EDGES DO NOT NEED TO BE BLOCKED BUT PROVIDE “H” PANEL EDGE
CLIPS AT MID-SPAN ALONG UNSUPPORTED EDGES OF PANELS. RIGID INSULATION TO
ACHIEVE THE REQUIRED R VALUE IS TO BE FASTENED PER MANUFACTURER DIRECTIONS TO
THE PLYWOOD DECKING.
4 REDUCE ACCESS PANEL. REMOVE FROM SCOPE FIVE (5) ATTIC ACCESS PANELS.
5 REMOVE URINAL (1 EA.). REMOVE FROM SCOPE THE URINAL IN TOILET #103, AND
ASSOCIATED PLUMBING.
6 REMOVE HAND DRYERS (2). REMOVE FROM SCOPE TWO (2) HAND DRYERS FROM TOILET
#103 AND TOILET #105, AND ASSOCIATED ELECTRICAL.
7 REMOVE PROPANE SOURCE FOR RADIANT HEAT AND USE ELECTRIC. REPLACE PROPANE
RADIANT HEATERS IN THE WORK BAY WITH ELECTRIC RADIANT HEATERS FROM THE SCOPE:
MECHANICAL DEDUCTIONS: REMOVE (3) 50MBH IR PROPANE-FIRED UNIT HEATERS FROM
WORK BAY #101.
PLUMBING DEDUCTIONS: REMOVE (1) 60-GALLON 120 MBH PROPANE-FIRED HIGH-RECOVERY
WATER HEATER FROM JANITOR #104. REMOVE ALL PROPANE GAS SUPPLY PIPING SCOPE AND
ACCESSORIES FROM THE BUILDING AND ALL PROPANE GAS SUPPLY PIPING SCOPE
ASSOCIATED WITH THE SITE THAT SERVES THIS FACILITY.
ELECTRICAL DECUCTIONS: REMOVE (1) 20-AMP BREAKER AND (4) SETS EACH OF (2) #12 AND
(1) #12GROUND FEEDERS WITHIN 1/2" CONDUIT SERVING THE (3) PROPANE-FIRED IR
HEATERS AND THE (1) PROPANE-FIRED WATER HEATER.
MECHANICAL ADDITIONS: ADD (9) 60-INCH 5.0-KW 240V ELECTRIC IR HEATERS SPACED
EVENLY IN THE LOCATIONS PREVIOUSLY INDICATED FOR THE GAS-FIRED IR HEATERS, WITH
OUTERMOST HEATERS IN EACH SECTION BEING PLACED AS CLOSE TO THE ENDS OF THE
EXISTING LOCATIONS AS POSSIBLE TO ENSURE COVERAGE AND MAXIMUM FREEZE
PROTECTION FOR THE WATER SUPPLY REEL PIPING ADJACENT TO THE ROLLUP DOORS.
PLUMBING ADDITIONS: ADD (1) 60-GALLON COMMERCIAL ELECTRIC TANK-TYPE WATER
HEATER WITH MINIMUM 7.5KW 240V ELECTRIC HEATING ELEMENT.
ELECTRICAL ADDITIONS: INCREASE INCOMING SERVICE FEEDER SIZE TO 2-SETS 4-600KCMIL
AND 1#1/0 GROUND INSIDE 3-1/2” CONDUIT TO INCREASE MAIN SERVICE SIZE FROM 240V /
600A TO 240V / 800A. ADD (1) NEW PANELBOARD, PANELBOARD “C”, 240V / 200A MLO, FED BY
(2) #3/0 AND (1) #6 GROUND INSIDE 2” CONDUIT FROM PANELBOARD “A” TO SERVE THE NEW IR
HEATERS AND THE NEW WATER HEATER. ADD (9) SETS EACH OF (2) #8 AND (1) #10 GROUND
FEEDERS WITHIN 3/4" CONDUIT SERVING THE (9) 5.0-KW ELECTRIC IR HEATERS. ADD (1) SET
OF (2) #8 AND (1) #10 GROUND FEEDERS WITHIN 3/4" CONDUIT SERVING THE NEW 7.5-KW
ELECTRIC TANK WATER HEATER.
8 REMOVE LIGHT DUTY CONCRETE PAVEMENT EXCEPT AT DOORS (HEAVY DUTY CONCRETE
PAVING TO REMAIN AT WIDTH OF VEHICLE AND MAN DOORS). REPLACE A PORTION OF THE
CONCRETE APRON WITH GRAVEL PAVEMENT IN THE SCOPE ACCORDING TO THE
FOLLOWING: ALONG THE PERIMETER OF THE BUILDING REMOVE THE 6’ WIDE CONCRETE
LEAVING THE CONCRETE AT OVERHEAD AND MAN DOORS.
RECOMMENDED BY:
FOREST ENGINEER DATE
ENGINEERING STAFF OFFICER DATE
DISTRICT RANGER DATE
FOREST SUPERVISOR DATE
RO FACILITIES PROGRAM MANAGER DATE
APPROVED BY:
DIRECTOR OF ENGINEERING DATE
X
S H
O W
E R
48' - 10"
31' - 11"
28' - 8"
48' - 8"
R
P 160
303 SF
STORAGE
303 SF
FIRE CACHE
3010 SF
WORK BAY
FEC
FEC
FEC
FEC
DRINKING
FOUNTAIN
R
P 160
MESHED
PARTITION
CAGED AREA
(TYP. 4)2 HR RATED
FIRE BARRIER
WALL
INDUSTRIAL OCC.PER NFPA 101 - 3,619
SF(DIAGONAL HATCH)
STORAGE OCC. PER NFPA 101 - 726
SF(CROSS HATCH)
CONC. SIDEWALK
CONC. SIDEWALK
TOILET
JAN
LAUNDRY
TOILET
TD1
FE1
FE2
EYE WASH/
SHOWER
STATION
R
P 160
TD2
AIR
COMPRESSOR
• INTERNATIONAL BUILDING CODE, 2018 EDITION
(WITH 2020, & 2022 GEORGIA AMENDMENTS)
• INTERNATIONAL EXISTING BUILDING CODE, 2018 EDITION
(WITH 2021 GEORGIA AMENDMENTS)
• INTERNATIONAL FIRE CODE, 2018 EDITION
(NO GEORGIA AMENDMENTS)
• INTERNATIONAL MECHANICAL CODE, 2018 EDITION
(WITH 2020 GEORGIA AMENDMENTS)
• INTERNATIONAL PLUMBING CODE, 2018 EDITION
(WITH 2020, & 2022 GEORGIA AMENDMENTS)
• INTERNATIONAL FUEL GAS CODE, 2018 EDITION
(WITH 2020, & 2022 GEORGIA AMENDMENTS)
• NATIONAL ELECTRICAL CODE, 2020 EDITION
(WITH 2021 GEORGIA AMENDMENTS)
• INTERNATIONAL ENERGY CONSERVATION CODE, 2015 EDITION
(WITH 2020, & 2022 GEORGIA AMENDMENTS & SUPPLEMENTS)
• THE ADOPTED EDITION OF THE NFPA CODES AND STANDARDS AS
MODIFIED BY THE GEORGIA STATE FIRE MARSHAL
• NFPA 10, 2018 EDITION, STANDARD FOR PORTABLE FIRE
EXTINGUISHERS
• NFPA 13, 2019 EDITION, STANDARD FOR THE INSTALLATION OF
SPRINKLER SYSTEMS
• NFPA 70, 2017 EDITION, NATIONAL ELECTRIC CODE
• NFPA 72, 2019 EDITION, NATIONAL FIRE ALARM AND SIGNALING CODE
• NFPA 101, 2018 EDITION, LIFE SAFETY CODE
• ADA STANDARDS FOR ACCESSIBLE DESIGN, 2010 EDITION
• ADA STANDARDS FOR ACCESSIBLE DESIGN AS ADOPTED BY
OCGA TITLE(S) 25 AND 30
APPLICABLE CODES:
FEC
23'-0"
23'-0"
LIFE SAFETY LEGEND:
2-HOUR FIRE RATED WALL
EXIT SIGN
EMERGENCY LIGHT
TRAVEL DISTANCE
FIRE EXTINGUISHER & CABINET
FIRE EXTINGUISHER & BRACKET
DOOR RATING (MINUTES)
TRAVEL DISTANCE TO FEC
DOOR EGRESS LOAD TAG
P = PROVIDED R = REQUIRED
FEB
R
P 160
CODE RESEARCH:
GROUP S-1
STORAGE
TYPE VB
TYPE V(000)
OCCUPANCY CLASSIFICATION & TYPE OF CONSTRUCTION
INTERNATIONAL
BUILDING CODE
EDITION
NFPA 101
APPLICABLE CODE OCCUPANCY CLASS. TYPE OF CONST.
2018 EDITION
THIS BUILDING IS NON-SPRINKLERED
STORAGE
EXITS PROVIDED
SIZE # OF DOORS NUMBER OF OCCUPANTS
= 480 OCC. PROVIDED FOR@ 160 OCC/ DR3 DOOR(S)3'-0"
INDUSTRIAL
/ NON-
SEPARATED
BUILDING HEIGHT, STORIES AND AREAS PER IBC TABLES 504.3,
504.4 AND 506.2:
• HEIGHT ALLOWED = 40'-0" / ACTUAL = 21'-0"
• STORIES ALLOWED = 1 / ACTUAL = 1
• AREA ALLOWED = 9,000 SF / ACTUAL = 4,335 SF
PROVIDED
MIN. ALLOW
WATER
CLOSET(S)
URINAL(S) LAV(S) DF(S) BATHTUB(S)/
SHOWER(S)
OTHER
(SERVICE
SINK)
N/A
N/A 0%
OF
REQD.
WC(S)
M
PLUMBING FIXTURE COUNT PER IBC 403.1 (2018)
5,047 - BUILDING AREA UNDER ROOF
4,208 - LEASABLE AREA
FEC
T .O
O
P E
N
IN
G
A F
F
GA AMENDMENT 120-3-3-.04 (3)(i)12 DELETES 906.9 of the 2018 INTERNATIONAL
FIRE CODE AND REFERS TO NFPA 10. GA AMENDMENT 120-3-3-.04 (6)(a) AMENDS
6.1.3.8.1 AND 6.1.3.10.5 OF THE 2018 NFPA 10:
6.1.3.8.1 PORTABLE FIRE EXTINGUISHERS </= 40LB SHALL HAVE T.O.
EXTINGUISHER </= 48" AFF.
6.1.3.8.2 PORTABLE FIRE EXTINGUISHERS > 40 LB SHALL HAVE T.O.
EXTINGUISHER =/< 42" AFF.
6.1.3.8.3 IN NO CASE SHALL THE CLEARANCE BETWEEN THE BOTTOM OF
THE FIRE EXTINGUISHER AND THE FF BE < 4".
6.1.3.10.5 CABINETS OR WALL RECESSES FOR FIRE EXTINGUISHERS SHALL
BE INSTALLED W/ T.O. OPENING AT 50" AFF.
6.1.3.10.6 FOR FIRE RESISTANCE-RATED WALLS, ONLY SURFACE MOUNTED
CABINETS OR LISTED FIRE-RATED CABINETS SHALL BE INSTALLED.
S E
T A
T
A F
F i f
L
B
S E
T A
T
A F
F i f
L
B
LIGHT SWITCHES, DIMMERS, ACCESS CONTROL DEVICES
NON-ACCESSIBLE THERMOSTAT / H.M.I.
FIRE STROBE / LIGHT SENSOR / MOTION DETECTOR
EDGE OF WALL OR LATCH SIDE OF DOOR FRAME
NOTES:
1. COORDINATE WITH SPECIFIC WALL ELEVATION AND LOCATION.
2. GROUP AND ALIGN ALL WALL-MOUNTED DEVICES ON EACH WALL IN AN ORGANIZED
MANNER. VERIFY WITH ARCHITECT IN CASE OF CONFLICT.
3. REFER TO MECHANICAL/HVAC DRAWINGS FOR MOUNTING HEIGHT OF THERMOSTAT
AND OTHER HUMAN MACHINE INTERFACE (H.M.I.) DEVICES
4. REFER TO ELECTRICAL DRAWINGS FOR MOUNTING HEIGHTS OF ALL OTHER DEVICES.
5. FAILURE TO ALIGN DEVICES WILL REQUIRE CORRECTION AT CONTRACTOR'S EXPENSE.
IN CASE OF NARROW WALL OR COLUMN -
CENTER ON WALL OR COLUMN
ACCESSIBLE THERMOSTAT / H.M.I.
U.N.O.
1' - 0"
United States Department of Agriculture Forest Service
USDA FOREST SERVICE
REGION 8
PROJECT NO.
CHECKED
DRAWN
DESIGNER
ARCHIVE NO.
DATE SIGNED
DRAWING TITLE
PROJECT NAME
SHEET
DWG SHEET NO.
Croft & Associates 3380 Blue Springs Road
Kennesaw, Georgia 30144
770.529.7714 (p) www.croftae.com
LS101
LIFE SAFETY PLAN
2022-419
SLA
MJ
CHATTOOGA
RIVER WORK
CENTER
9975 Highway 441S Lakemont, GA
30552
AWI
04-01-24
0 5 25 FT10
1/8" = 1'-0"
LS101
LEVEL 1 - LIFE SAFETY PLAN
OCCUPANT LOAD TABLE
RM # RM NAME AREA Occupancy
OCC.
FACTOR
OCC.
LOAD
101 WORK BAY 3010 SF INDUSTRIAL 100 SF 30
102 LAUNDRY 124 SF STORAGE 300 SF 0
103 TOILET 56 SF --- 0 SF
104 JAN 32 SF STORAGE 300 SF 0
105 TOILET 68 SF --- 0 SF
106 STORAGE 303 SF STORAGE 300 SF 1
107 FIRE CACHE 303 SF STORAGE 300 SF 1
3896 SF 33
N
3/4" = 1'-0"
LS101
FIRE EXTINGUISHER MOUNTING HGT
TRAVEL DISTANCES
PATH TOTAL DISTANCE MAX
FE1 28'-8" 75'
FE2 31'-11" 75'
TD1 48'-10" 200'
TD2 48'-8" 200'
1/4" = 1'-0"
LS101
TYPICAL WALL MOUNTED DEVICE ALIGNMENT
T
T
0.
8.
p w w w .ro ch es te r-as so c.
co m
O ak S t N W
, G ai ne sv ill e, G A
R oc he st er a nd
A ss oc ia te s, L
LCG
R
ID
N O
R
TH
G A
. W
EST ZO
N E
2022-419
United States Department of Agriculture Forest Service
USDA FOREST SERVICE
REGION 8
CHATTOOGA
RIVER WORK
CENTER
9975 Highway 441S Lakemont, GA
30552
PROJECT NO.
CHECKED
DRAWN
DESIGNER
ARCHIVE NO.
DATE SIGNED
DRAWING TITLE
PROJECT NAME
SHEET
DWG SHEET NO.
CROFT & Associates 3380 Blue Springs Road Kennesaw, Georgia 30144
770.529.7714 (p) 770.529.7716 (f) www.croftandassociates.com
LMC
CKJ
CKJ
C-001
GENERAL NOTES
12/18/2023
12/18/2023
Forest Service
USDA FOREST SERVICE
REGION 8
CHATTOOGA
RIVER WORK
CENTER
9975 Highway 441S Lakemont, GA
30552
PROJECT NO.
CHECKED
DRAWN
DESIGNER
ARCHIVE NO.
DATE SIGNED
DRAWING TITLE
PROJECT NAME
SHEET
DWG SHEET NO.
CROFT & Associates 3380 Blue Springs Road Kennesaw, Georgia 30144
770.529.7714 (p) 770.529.7716 (f) www.croftandassociates.com
LMC
CKJ
CKJ
C-100
SITE & UTILITY PLAN
N O
R
TH
1" = 20'
0 10 40 FT20
12/18/2023
Forest Service
USDA FOREST SERVICE
REGION 8
CHATTOOGA
RIVER WORK
CENTER
9975 Highway 441S Lakemont, GA
30552
PROJECT NO.
CHECKED
DRAWN
DESIGNER
ARCHIVE NO.
DATE SIGNED
DRAWING TITLE
PROJECT NAME
SHEET
DWG SHEET NO.
CROFT & Associates 3380 Blue Springs Road Kennesaw, Georgia 30144
770.529.7714 (p) 770.529.7716 (f) www.croftandassociates.com
LMC
CKJ
CKJ
C-101
TRUCK MOVEMENT PLAN
N O
R
TH
1" = 20'
0 10 40 FT20
12/18/2023
SD
SD
SD
SD
SD
SD
SD
SD
ST
ST
ST
ST
ST
ST
ST
ST
ST
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
2022-419
United States Department of Agriculture Forest Service
USDA FOREST SERVICE
REGION 8
CHATTOOGA
RIVER WORK
CENTER
9975 Highway 441S Lakemont, GA
30552
PROJECT NO.
CHECKED
DRAWN
DESIGNER
ARCHIVE NO.
DATE SIGNED
DRAWING TITLE
PROJECT NAME
SHEET
DWG SHEET NO.
CROFT & Associates 3380 Blue Springs Road Kennesaw, Georgia 30144
770.529.7714 (p) 770.529.7716 (f) www.croftandassociates.com
LMC
CKJ
CKJ
N O
R
TH
1" = 20'
0 10 40 FT20
C-102
GRADING PLAN
SD
12/18/2023
Forest Service
USDA FOREST SERVICE
REGION 8
CHATTOOGA
RIVER WORK
CENTER
9975 Highway 441S Lakemont, GA
30552
PROJECT NO.
CHECKED
DRAWN
DESIGNER
ARCHIVE NO.
DATE SIGNED
DRAWING TITLE
PROJECT NAME
SHEET
DWG SHEET NO.
CROFT & Associates 3380 Blue Springs Road Kennesaw, Georgia 30144
770.529.7714 (p) 770.529.7716 (f) www.croftandassociates.com
LMC
CKJ
CKJ
N O
R
TH
1" = 20'
0 10 40 FT20
C-103
EROSION CONTROL
PLAN
Sd1-S
Ds3
Ds3
Ds3
St
St St
CODE PRACTICE DETAIL DESCRIPTIONMAP
SYMBOL
Ds3 Ds3
Sd1-S
Co Co
Co
Sd1-S
Cd
Cd Ss Ss
Ss
12/18/2023
Forest Service
USDA FOREST SERVICE
REGION 8
CHATTOOGA
RIVER WORK
CENTER
9975 Highway 441S Lakemont, GA
30552
PROJECT NO.
CHECKED
DRAWN
DESIGNER
ARCHIVE NO.
DATE SIGNED
DRAWING TITLE
PROJECT NAME
SHEET
DWG SHEET NO.
CROFT & Associates 3380 Blue Springs Road Kennesaw, Georgia 30144
770.529.7714 (p) 770.529.7716 (f) www.croftandassociates.com
LMC
CKJ
CKJ
C-500
CIVIL DETAILS
12/18/2023
Forest Service
USDA FOREST SERVICE
REGION 8
CHATTOOGA
RIVER WORK
CENTER
9975 Highway 441S Lakemont, GA
30552
PROJECT NO.
CHECKED
DRAWN
DESIGNER
ARCHIVE NO.
DATE SIGNED
DRAWING TITLE
PROJECT NAME
SHEET
DWG SHEET NO.
CROFT & Associates 3380 Blue Springs Road Kennesaw, Georgia 30144
770.529.7714 (p) 770.529.7716 (f) www.croftandassociates.com
LMC
CKJ
CKJ
C-501
CIVIL DETAILS
SILT FENCE - TYPE SENSITIVE
SIDE VIEW
FRONT VIEW
Sd1-S FASTENERS FOR SILT FENCES
OVERLAP AT FABRIC ENDS
Ds3
Ds3
Ds3
Ds3
PIPE OUTLET TO WELL DEFINED CHANNEL
PIPE OUTLET TO FLAT AREA -- NO WELL DEFINED CHANNEL
RIPRAP OUTLET PROTECTIONSt
CRUSHED STONE CONSTRUCTION EXIT
EXIT DIAGRAM
ENTRANCE ELEVATION
12/18/2023
Forest Service
USDA FOREST SERVICE
REGION 8
CHATTOOGA
RIVER WORK
CENTER
9975 Highway 441S Lakemont, GA
30552
PROJECT NO.
CHECKED
DRAWN
DESIGNER
ARCHIVE NO.
DATE SIGNED
DRAWING TITLE
PROJECT NAME
SHEET
DWG SHEET NO.
CROFT & Associates 3380 Blue Springs Road Kennesaw, Georgia 30144
770.529.7714 (p) 770.529.7716 (f) www.croftandassociates.com
LMC
CKJ
CKJ
C-502
CIVIL DETAILS
STONE CHECK DAM
CROSS SECTION
PROFILE VIEW
TYPICAL INSTALLATION GUIDELINES FOR ROLLED
EROSION CONTROL PRODUCTS (RECP)
BLANKET AND MATTING CROSS-SECTIONS
Cd Ss
12/18/2023
Forest Service
USDA FOREST SERVICE
REGION 8
CHATTOOGA
RIVER WORK
CENTER
9975 Highway 441S Lakemont, GA
30552
PROJECT NO.
CHECKED
DRAWN
DESIGNER
ARCHIVE NO.
DATE SIGNED
DRAWING TITLE
PROJECT NAME
SHEET
DWG SHEET NO.
CROFT & Associates 3380 Blue Springs Road Kennesaw, Georgia 30144
770.529.7714 (p) 770.529.7716 (f) www.croftandassociates.com
LMC
CKJ
CKJ
1" = 10'
0 5 20 FT10
C-800
SANITARY SEWER
PROFILE
12/18/2023
GENERAL NOTES
1. These notes complement the drawings and should not be considered inclusive of all items.
2. Where a detail is shown for one condition, it shall apply for all like or similar conditions, even though not specifically shown on the drawings.
3. The contractor is responsible for means, methods, and sequences of construction to meet the requirements of the construction documents.
4. It is the contractor's responsibility to be in compliance with all applicable OSHA regulations.
5. Contractor is responsible for all temporary shoring and erection bracing required during construction.
6. All retaining walls relying on top slab for lateral support shall be braced until the slab has cured for a minimum of three days.
7. Contractor shall verify all dimensions and conditions before executing work. Notify the architect and engineer in writing of any discrepancy.
8. Coordinate structural contract documents with architectural, mechanical, electrical, plumbing, and civil documents. Notify the architect and engineer in writing of any conflict and/or omission prior to performing work.
9. Coordinate and verify floor and roof opening sizes and locations with architectural, mechanical, electrical, and plumbing documents. For additional openings, inserts, sleeves, curbs, and pads not shown in the structural documents, see architectural, mechanical, electrical, and plumbing documents.
10. Shop drawings shall be independently developed. Reproduction of structural design drawings for use as shop drawings is prohibited.
SUBMITTALS
1. All submittals shall be submitted to the architect for approval prior to work.
2. The contractor shall review all shop drawings prior to submittal to the architect and/or engineer for review of general compliance, dimensions, and quantity. Shop drawings submitted to the architect shall be stamped by the contractor to indicate completion of review.
3. Contractor is not relieved of any requirements of the contract documents by virtue of the structural engineer's review of shop drawings, product data, etc., unless the contractor has clearly and explicitly informed the structural engineer in writing of any deviations or substitutions at time of submission, and the structural engineer has given written approval for the specific deviations or substitutions.
4. The review of shop drawings by the structural engineer is to make sure the main structural intent is correct. Review will exclude dimensions and quantities.
5. Each submittal will be reviewed and returned within 10 business days. Expedited review may be requested but may not be possible.
6. Submit concrete mix designs for approval prior to pouring concrete. Refer to concrete notes, plans, and details for mix design requirements.
7. Submit rebar drawings for approval prior to rebar fabrication and placement. Drawing shall include the following at a minimum: rebar size, quantity, steel grade, bend schedule & diagram, lap slices, layout drawing for placement, and details as required for placement. Show wall steel in elevation. Indicate control joint locations. No fabrication shall begin until shop drawings are completed and approved.
8. Submit wood truss shop drawings for approval prior to fabrication. Drawings shall include the following as a minimum: engineer's stamp, design loads, detailed truss layout, truss/wall connection loads, truss bracing requirements, and field erection requirements. The truss submittal package shall meet the requirements of section 2303.4 of the 2018 IBC.
Shear and uplift anchorage requirements shall be clearly noted on the shop drawings so that these designed connections can be verified.
9. Submit structural insulated panel drawings for approval prior to fabrication. Drawings shall include at a minimum the panel materials, plan layout, construction details, show that connection details meet structural loading criteria, and show certification that panels meet all applicable design standards and tests. Shop drawings must be stamped by a professional engineer licensed in Georgia.
CONCRETE & REINFORCING:
1. All concrete work shall conform to ACI 301, "Specifications for Structural Concrete for Buildings". Design is based on ACI 318, "Building Code Requirements for Structural Concrete".
2. Unless noted otherwise, provide a 10-mil polyethylene vapor barrier beneath the interior slab-on-grade with joints lapped not less than 6 inches and taped. In areas with vapor sensitive coverings, humidity control, or storage of moisture sensitive materials in direct contact with the exposed slab-on-ground surface, provide 15 mil polyethylene vapor barrier beneath the floor slab.
3. Contraction joints shall be placed where shown on plans, at column lines and at intermediate lines such that spacing between joints does not exceed 20'-0", with an aspect ratio of panels not to exceed 1.5. Locate construction joints at contraction joints. Provide a 4” subbase layer of compacted graded aggregate beneath the vapor barrier.
4. Use of calcium chloride, chloride ions, or other salts in concrete is not permitted.
5. The air content in all concrete exposed to weather at point of placement shall be proportioned according to ACI 318 Table 19.3.3.1 for exposure class F1, moderate. Provide air content that complies with floor system fire rating requirements.
6. See construction testing section of the general notes for minimum concrete testing requirements.
7. Begin curing slabs immediately after finishing concrete. Curing method shall be compatible with adhered finishes. A moist cure or dissipating curing compound shall be used at cementitious finishes. Submit product data to the architect for review.
8. Horizontal construction joints are permitted only where indicated. The architect shall approve the location of vertical construction joints. Construction joints shall be thoroughly roughened by mechanical means, and cleaned.
9. Detail concrete reinforcing and accessories in accordance with ACI "detailing manual", SP-66(04). Submit shop drawings for approval, showing all fabrication dimensions and locations for placing reinforcing steel and accessories. Do not begin fabrication until shop drawings are completed and reviewed.
A. Detail all concrete walls and beams in elevation unless specifically approved otherwise. Cut sections showing bar locations and concrete cover.
10. Reinforcing steel shall conform to ASTM A615, Grade 60, unless noted otherwise.
11. Welded wire fabric (mesh) shall conform to ASTM A1064 and shall be provided in flat sheets (rolls not permitted). Lap two squares at splices.
12. Tie all reinforcing steel and embedments securely in place prior to placing concrete. Provide sufficient supports to maintain the position of reinforcing within specified tolerances during all construction activities. "Sticking" dowels into wet concrete is not permitted.
13. Provide continuous reinforcing wherever possible; splice only as shown or approved; stagger splices where possible. All bar splices shall be at a minimum the following lengths, unless noted otherwise on the drawings: 36" for #6 bars, 30" for #5 bars, and 24" for #4 bars. Dowels shall match the size and spacing of the specified reinforcing and shall have full tension lap splices.
14. Wall footing reinforcing bars shall run continuous through column footings.
15. Reinforcing steel shall have the following concrete cover unless noted otherwise:
A. Concrete cast against earth (not formed): 3" B. Formed concrete exposed to earth or weather:
a. #6 through #18 bars: 2"
b. #5 bars and smaller: 1-1/2"
C. Concrete not exposed to earth or weather:
a. Slabs and walls: 1"
b. Beam stirrups and column ties: 1-1/2"
16. Do not place pipes or ducts exceeding one-third wall thickness within the wall unless specifically shown and detailed on structural drawings.
17. Pipes and conduit shall not be placed within elevated slabs, they must be properly hung from structure beneath. Refer to mechanical, electrical and plumbing drawings for utility support.
18. Concrete mix designs, in accordance with ACI 318 section 5.3, shall be submitted to the testing agency and the architect.
19. All concrete shall meet the following requirements:
A. General concrete requirements:
a. All concrete, unless noted otherwise, shall be normal weight and have the following minimum 28-day compressive strength.
1. Slab-on-grade: 3,000 PSI
b. Portland cement: ASTM C150. Type I
c. Fly ash, if used: ASTM C618, class F or C, maximum 25%, by weight, of total cementitious material.
d. Ground granulated blast-furnace slag (GGBFS), if used: ASTM C989, grade 100 or 120, maximum 25%, by weight, of total cementitious material.
e. Combined fly ash and GGBFS shall not exceed 33%, by weight, of total cementitious material.
f. Do not use admixtures containing calcium chloride.
g. Air-entraining admixture: ASTM C260 (as needed; follow manufacturing dosage)
h. Water-reducing admixture: ASTM C494 / C494M, type A (as needed; follow manufacturing dosage.)
i. Normal weight aggregates shall meet ASTM C33 with a maximum size of 1" unless noted otherwise on plans
j. Welded wire reinforcement shall meet ASTM A1064
k. Reinforcing bars shall meet ASTM A615, grade 60, deformed
l. All concrete exposed to weather shall be air-entrained with air content at point of placement of 3 - 6%
m. Do not air-entrain slab concrete (entrapped air content not to exceed 3%)
n. Slump limit: 5 inches
o. Maximum water / cement ratio: 0.50
WOOD:
1. Sawn members that are headers, joists, rafters, and posts shall be Spruce-Pine-Fur (SPF) of #2 grade or better; wall studs shall be Spruce-Pine-Fur of #3 or stud grade.
Southern Pine is an acceptable substitute for Spruce-Pine-Fur.
2. All references to "nails" on the plans shall be common nails unless noted otherwise on the plans.
3. All wood embedded or in contact with concrete, masonry, earth or directly exposed to weather shall be pressure treated.
4. Refer to the "Wood Truss Notes" for additional notes for the wood truss manufacturer.
5. Refer to the "Wood Framing Fastening Schedule" on the plans for typical framing attachments not otherwise detailed.
6. Refer to the "Wood Sheathing Attachment Plan" for the required nailing pattern.
7. All metal (plates, nails, bolts, etc.) In contact with pressure treated and fire-retardant wood shall have G185 zinc galvanized coating.
8. Top and bottom plates of all walls shall be the thickness of a nominal 2x and at least equal to the stud width.
9. A double top plate shall be provided for all load bearing stud walls. The top plate shall be nailed together with 16d common wire nails @ 16" on-center. Top plate splices shall have (8) 16d nails on each side of splice, and the splice shall be lapped with adjacent wall at intersections and corners.
10. Provide double joists directly under partition walls which run parallel to framing.
11. Provide triple studs at all corners and at all beam bearings through to foundation, unless noted otherwise.
12. Refer to the typical wood details for limitations of cutting, notching, and boring of studs and joists.
13. All wood connectors and product model numbers are based off Simpson Strong-Tie. Alternate connectors shall meet or exceed the design values specified by Simpson
Strong-Tie.
WOOD TRUSSES:
1. Wood trusses are a deferred submittal. See deferred submittal section of the general notes. Submittal shall include species, sizes, lumber grades, and connection details.
2. Submit calculations and shop drawings for details, fabrication, and erection of wood trusses:
A. Coordinate calculations with shop drawings.
B. Drawings shall clearly indicate location of details for erection.
C. Drawings shall include design loads.
D. Drawings shall include truss layout, spacing, type, material member properties and all details of connections including type, size, and spacing of connectors.
E. Drawings shall include truss/wall connection loads and truss bracing requirements.
F. Provide calculations for all typical and non-typical connections and for attachment to primary structural frame.
3. Fabrication shall not begin until shop drawings are submitted and approved.
4. Wood trusses shall be designed in accordance with the applicable provisions of the latest edition of the National Design Specifications for Wood Construction, Design Specifications For
Metal Plate Connected Wood Trusses, The Truss Plate Institute, and Section 2303.4 of the 2018 International Building Code.
5. Wood roof trusses shall be designed for:
A. TC Dead Load = 10 psf B. BC Dead Load = 10 psf C. TC Live Load = 20 psf or 300 lbs anywhere (worst of) D. BC Mechanical Live Load = 10 psf E. WL per Components & Cladding Wind Pressure Plan on S-201 F. TC Snow Load = As required by code G. Roof Truss Live Load Deflection: L/240 & 5/8"
6. Truss layout on the plan is generic in nature; the truss manufacturer shall locate trusses to meet all plan requirements.
7. Shear and uplift anchorage requirements shall be clearly noted on the shop drawings so that these designed connections can be verified.
8. The wood truss cross-section shown in building sections are schematic in nature. The roof truss manufacturer is responsible for the exact truss layout that meets the intent of the structural and architectural drawings & details.
9. Gypsum board attached directly to the bottom chord of the truss shall be considered adequate for bracing truss bottom chord. Where gypsum board is attached to the bottom chord of the truss by resilient channels or hat channels, the bottom chord of the truss shall not be considered braced and the truss manufacturer shall design & provide bracing for the bottom chord.
The truss manufacturer shall coordinate ceiling type and locations with the architectural drawings.
10. All truss-to-truss connections shall be furnished by the truss manufacturer.
11. The top chord shall be considered permanently braced by the wood roof sheathing.
12. Trusses shall be permanently restrained and braced in a manner consistent with good building practices as outlined in BCSI and in accordance with the requirements of the construction documents. Trusses shall furthermore be anchored or restrained to prevent out-of-plane movement so as to keep all truss members from simultaneously buckling together in the same direction. Such permanent later restraint shall be accomplished by: (a) anchorage to solid end walls; (b) permanent diagonal bracing in the plane of the web members; or (c) other suitable means.
13. Truss temporary bracing, permanent truss restraint bracing, & truss member/component bracing shall be designed and specified by the truss design engineer and shall be furnished by the contractor.
14. All bracing for the trusses shall follow current BCSI standards.
15. Permanent building stability bracing to transfer lateral load forces to the lateral load resisting system has been designed by the structural engineer of record and is shown on the plans.
16. The roof truss manufacturer is responsible for all the gable end wall trusses.
STRUCTURAL INSULATED PANELS (SIPs):
1. SIPs and SIP connections shall be designed by a professional engineer licensed in Georgia to meet all project requirements. The SIP engineer shall be responsible for the design of the panel and connections to meet the following loading conditions: uplift, gravity, and shear. Refer to the plans for the required loading.
2. Exterior facing of panel shall be plywood. Interior facing of panel shall be OSB.
3. Refer to specification section 06 1219 for additional requirements.
DELEGATED DESIGN:
1. Delegated designs include, but are not limited to, the following building components:
A. SIPs and SIP Connections B. Wood trusses
2. Shop drawings and calculations for these components shall be submitted to the architect unless noted otherwise. Deferred submittals shall be sealed, signed, and dated by the delegated component Structural engineer registered in the project state. Refer to other sections of these general notes for specific requirements of deferred submittals. Review of deferred submittals shall be for general conformance with the contract documents and shall not relieve the contractor and its engineer of the full responsibility for design. Do not begin fabrication until deferred submittals are approved.
3. Deferred submittal building components shall accommodate allowable building deflections and drift as set forth by the building code and construction tolerances as defined by the AISC “code of standard practice for steel buildings and bridges” and ACI “specification for tolerances for concrete construction and materials”. See specifications for design criteria.
APPLICABLE CODES FOR DESIGN:
1. International Building Code: 2018 IBC with Ga. Amendments (2020 & 2022)
RISK CATEGORY:
1. Risk category: II
STRUCTURAL LOAD CRITERIA:
1. DEAD LOADS:
A. Roof: 20 PSF
2. LIVE LOADS:
A. Roof: Live Load: 20 PSF & 300 lbs. (not concurrent) B. Floor (Slab-on-grade): 125 PSF & 3000 lbs. (not concurrent)
3. SNOW LOAD CRITERIA:
A. Snow Load Importance Factor; Is: 1.0 B. Ground Snow Load, Pg: 10 PSF C. Flat-Roof Snow Load, Pf: 6.3 PSF D. Sloped-Roof Snow Load, Pf: 5.0 PSF (Balanced snow load for design) E. Exposure Factor, Ce: 0.9 F. Thermal Factor, Ct: 1.0
4. WIND LOADS PER IBC 2018, ASCE 7-16
A. Basic Wind Speed (3 second gust)
a. Vult: 107 MPH
b. Vasd: 83 MPH
B. Wind Exposure: B C. Internal Pressure Coefficients: +0.18, -0.18 D. Refer to drawing on S-201 for velocity pressures for components & cladding design.
5. SEISMIC DESIGN DATA
A. Seismic Importance factor; Ie: 1.0 B. Seismic Site Class: C
C. SS: 0.289
D. S1: 0.097 E. Fa: 1.3 F. Fv: 1.5
G. SDS: 0.251
H. SD1: 0.097
I. Seismic Design Category: B J. Basic Seismic Force Resisting System
a. Light Frame (Wood) Walls Sheathed with Wood Structural Panels Rated for Shear Resistance (Section A.15)
• Response Modification Coefficient, R: 6.5
• System Overstrength Factor, Ωo: 3.0
• Deflection Amplification Factor, Cd: 4.0
K. Seismic Response Coefficients, CS: 0.039 L. Seismic Base Shear:
a. Plan North / South: 8 kips
b. Plan East / West: 8 kips
M. Seismic Forces Analysis per Equivalent Lateral Force Procedure
FOUNDATIONS:
1. The design of foundations, retaining walls and slabs-on-ground are based on the recommendations in the geotechnical report from GEOHYDRO ENGINEERS dated November 22, 2022 (Project # 222708.20). Foundation sizes are based on an allowable bearing pressure of 2,000 PSF.
2. Retaining walls are based on the following Equivalent Lateral Fluid Pressure criteria:
A. Active Pressure: 42 PCF B. At Rest Pressure: 63 PCF C. Passive Pressure: 375 PCF D. Coefficient of Friction: 0.4 (ultimate level)
3. All foundations to be supported on suitable bearing material as determined by the owner's on-site geotechnical representative. Notify the architect / engineer immediately if suitable bearing material cannot be obtained, prior to installing foundations, footings, slabs, or walls.
4. Sub-grade shall be compacted to 98% of standard proctor (ASTM 695,) unless a site-specific geotechnical report recommends otherwise.
5. Coordinate flooring elevations with below slab plumbing, and lower footing elevations as required to avoid interference. All top of footings required to be lower further than 2'-8" below finished floor elevation shall be coordinated with the structural engineer.
6. Plumbing lines that run parallel with wall footings shall be at least 2'-0" from the edge of the footing.
7. Plumbing lines that cross wall footings shall either cross below the footing with at least 12" of compacted fill between the top of the pipe and the bottom of the footing, or cross above the footing and through the wall. All pipes that cross footings, either above or below, shall be sleeved. Coordinate sleeve requirements with plumbing plans.
8. Piping (including conduit) shall not be embedded in or pass through foundations without written consent of the structural engineer.
9. Where footing steps are necessary, they shall be no steeper than one vertical to two horizontal.
10. Basement walls (walls supported at the top and bottom by slabs or floor framing) require the following precaution: do not backfill against the wall before the slabs at top and bottom are cast and have reached 75% of design strength.
A
B
C
D
E
F
G
H
I
J
K
ADD'L
ADJ.
A/E A.F.F.
ALT
ARCH.
BC
BLDG
BOTT.
B/
CANT.
CFMF
C.J.
CL
CLR
CMU
COL.
CONC.
CONT.
DBA
DIM.
DWL
EA.
E.E.
E.F.
E.S.
E.W.
EIFS
ELEV.
EMBED.
EOR
EQ.
E.W.T.
EX.
EXP. JT.
FFE
FFL
F.M.
FT
FTG
FDN
GALV.
GA.
G.C.
GR.
HK
HORIZ.
HVAC
ID
INSUL.
INFO.
INT.
JT
K
KSF
ADDITIONAL
ADJUSTABLE
ARCHITECT/ENGINEER
ABOVE FINISHED FLOOR
ALTERNATE
ARCHITECT
BOTTOM CHORD
BUILDING
BOTTOM
BOTTOM OF
CANTILEVER
COLD FORMED METAL FRAMING
CONTRACTION JOINT
CENTER LINE
CLEAR
CONCRETE MASONRY UNIT
COLUMN
CONCRETE
CONTINUOUS
DEFORMED BAR ANCHOR
DIMENSION
DOWEL
EACH
EACH END
EACH FACE
EACH SIDE
EACH WAY
EXTERIOR INSULATION & FINISHING SYSTEM
ELEVATION
EMBEDMENT
ENGINEER OF RECORD
EQUAL
END WALL TRUSS
EXISTING
EXPANSION JOINT
FINISHED FLOOR ELEVATION
FINISHED FLOOR LINE
FIELD MEASURE
FOOT/FEET
FOOTING
FOUNDATION
GALVANIZED
GAUGE
GENERAL CONTRACTOR
GRADE
HOOK
HORIZONTAL
HEATING, VENTILATION & AIR CONDITIONING
INSIDE DIAMETER
INSULATION
INFORMATION
INTERIOR
JOINT
KIPS
KIPS PER SQUARE FOOT
L
M
N
O
P
R
S
T
U
V
W
LDT
LLH
LLV
MANUF.
MAX.
MECH.
MEP
MEZZ.
MIN.
MISC.
MHS
N/A
NIC
NTS
o/c
OD
OFS
O.H.
OPP.
PAF
PL.
PREFAB.
PT
REINF.
REQ'D
RTU
SCHED.
SIM.
SOG
SP
SPEC.
STIFF.
STRUCT.
T&B
TBD
TC
T.D.
TEMP.
T/
TYP.
U.N.O.
VAR.
VERT.
WF
W.P.
WWF
W/
LARGE DIAMETER TAPCON
LONG LEG HORIZONTAL
LONG LEG VERTICAL
MANUFACTURER
MAXIMUM
MECHANICAL
MECHANICAL, ELECTRICAL, PLUMBING
MEZZANINE
MINIMUM
MISCELLANEOUS
MH STRUCTURES
NOT APPLICABLE
NOT IN CONTRACT
NOT TO SCALE
ON CENTER
OUTSIDE DIAMETER
OUTSIDE FACE OF STUD
OPPOSITE HAND
OPPOSITE
POWER ACTUATED FASTENER
PLATE
PREFABRICATED
PRESSURE TREATED
REINFORCE (D) (ING) (MENT)
REQUIRED
ROOF TOP UNIT
SCHEDULE
SIMILAR
SLAB-ON-GROUND
SOUTHERN PINE
SPECIFICATION
STIFFENER
STRUCTURAL
TOP AND BOTTOM
TO BE DETERMINED
TOP CHORD
TURN DOWN
TEMPERATURE
TOP OF
TYPICAL
UNLESS NOTED OTHERWISE
VARIES
VERTICAL
WIDE FLANGE
WORK POINT
WELDED WIRE FABRIC
WITH
ABBREVIATIONS
5077 Dallas Hwy Suite 201 Powder Springs, GA 30127
(404) 495-4889 www.mhstructures.com
Integrity is our foundation.
United States Department of Agriculture Forest Service
USDA FOREST SERVICE
REGION 8
PROJECT NO.
CHECKED
DRAWN
DESIGNER
ARCHIVE NO.
DATE SIGNED
DRAWING TITLE
PROJECT NAME
SHEET
DWG SHEET NO.
12-18-2023
S-001
GENERAL NOTES
2022-419
MH
MH
CHATTOOGA
RIVER WORK
CENTER
9975 Highway 441S Lakemont, GA
30552
MH
2 ADDITIONAL 20d
NAILS AT ENDS
WINDOW SILL PLATE
BOTTOM PLATE
FULL
HEIGHT
(KING) STUD
JACK STUD
HEADER
DOUBLE
TOP
PLATE
UPPER TOP PLATE LAPS
OVER
CONTINUOUS BOTTOM PLATE
PLATE PLATE
PLATE
BLOCKING
SHIM
NAILER
STUD
STUD
STUD PLATE
STUD
PLATE
POST POST
END JOINT
TYPICAL DETAIL - Nailing Built-up Beams and Girders TYPICAL DETAIL - Wall Opening
TYPICAL DETAIL - Multiple Studs at CornersTYPICAL DETAIL - Wall Framing at Intersecting Partitions
TYPICAL DETAIL - Top Plate Intersection Detail
20d @ 32" o/c
& BOT ROWS
STAGGER TOP
5/8" MIN.
FROM STUD
FACE
NOTCH 25%
MAX. OF STUD
WIDTH
BORED HOLES:
• MAX. DIA. = 40% OF
SINGLE STUD WIDTH
• MAX. DIA. = 60% OF
DOUBLE STUD WIDTH,
PROVIDED NOT MORE
THAN TWO SUCCESSIVE
DOUBLE STUDS ARE
BORED
BORED HOLES:
MAX. DIA. = 60%
OF STUD WIDTH
NOTCHING LIMITS
STUD
SIZE
2x4 2x6 2x8
25%
NOTCH
7/8" 1 3/8" 1 13/16"
40%
NOTCH
1 3/8" 2 3/16" 2 7/8"
BORING LIMITS
STUD
SIZE
2x4 2x6 2x8
40%
DIA.
1 3/8" 2 3/16" 2 7/8"
60%
DIA.
2" 3 1/4" 4 1/4"
EXTERIOR AND LOAD BEARING WALLS INTERIOR, NON-LOAD BEARING WALLS
TYPICAL DETAIL - STUD WALL NOTCHING & BORING LIMITS
5/8" MIN.
FROM STUD
FACE
NOTCH 40%
MAX. OF STUD
WIDTH
4' - 0" M
IN.
(8) 16d NAILS
ON EACH SIDE
OF SPLICE
16d NAILS @ 16" o/c
2x STUD WALL
2x DOUBLE TOP
PLATE SAME
WIDTH AS STUDS
NOTE:
TOP PLATE SHALL OVERLAP AT
CORNERS AND ADJACENT WALL
INTERSECTIONS. PROVIDE NAILED
SPLICE CONNECTION SHOWN AT
ALL SPLICES, INCLUDING CORNERS
AND INTERSECTIONS.
TYPICAL DETAIL - Top Plate Splice Detail
(8) 16d NAILS
ON EACH SIDE
OF SPLICE
16d NAILS @ 16" o/c
LOAD BEARING WOOD HEADER SCHEDULE
MARK
H-1
H-2
H-3
MAX.
SPAN (ft.)
4'-0"
5'-0"
6'-0"
SIZE
(3) 2x8
(3) 2x10
(3) 2x12
JACK
STUDS
2 ADDITIONAL NAILS AT EACH END
NAILING PATTERN FOR EACH PLY
• 16d @ 16" o/c (TOP & BOTT)
1/2" SHEATHING SPACERS
NOTES:
- NAIL ALL HEADERS, BEAMS, AND LINTELS w/ 16d NAILS @ 16"
TOP & BOTTOM (MIN.)
- NAIL EACH ADDITIONAL PLY WITH AN ADDITIONAL ROWS OF
NAILS.
- ALL HEADERS TO BE PLACED DIRECTLY ABOVE OPENING.
- NAIL ALL JACK STUDS AND KING STUDS TOGETHER WITH 16d NAILS @ 24" o/c
CONNECTION
1. Blocking between joists or rafters to top plate
2. Ceiling joists to plate
3. Ceiling joists, laps over partitions
(see 2012 IBC Table 2308.10.4.1)
4. Ceiling joists to parallel rafters
(see 2012 IBC Table 2308.10.4.1)
5. Rafter to plate
(see 2012 IBC Table 2308.10.4.1)
6. Built-up girder and beams
7. Collar tie to rafter
8. Jack rafter to hip
9. Jack rafter to hip
10. Roof rafter to 2-by ridge beam
LOCATION
toenail toenail face nail face nail toe nail face nail at top and bottom staggered on opposite side face nail at ends and at each splice face nail toenail face nail toenail or face nail
FASTENING
3 - 8d common 3 - 8d common 3 - 16d common minimum
3 - 16d common minimum
3 - 10d common
20d common @ 32" o/c
2 - 20d common 3 - 10d common 4 - 16d common 3 - 16d common 2 - 16d common
TYPICAL WOOD FRAMING FASTENING SCHEDULE
11. Sole plate to joist or blocking
12. Sole plate to joist or blocking at braced wall panel
13. Top plate to stud
14. Stud to sole plate
15. Stud to sole plate
16. Double studs 17.Double top plates 18.Double top plate splice
19. Top plates, laps and intersections
20. Continuous header, two pieces
21. Continuous header to stud
22. 1" diagonal brace to each stud and plate
23. 1" x 8" sheathing to each bearing
24. Wider than 1" x 8" sheathing to each bearing
25. Built-up corner studs face nail braced wall panels end nail toenail end nail face nail face nail each side of lap splice face nail 16" o/c along each edge toenail face nail face nail face nail 12" o/c
16d @ 16" o/c 3 - 16d @ 16" o/c 2 - 16d common 4 - 8d common 2 - 16d common 16d @ 24" o/c 16d @ 16" o/c 8 - 16d common 2 - 16d common 16d common 4 - 8d common 2 - 8d common 3 - 8d common 3 - 8d common 16d common
26. Joist to sill or girder
27. Bridging to joist
28. 1" x 6" subfloor or less to each joist
29. Wider than 1" x 6" subfloor to each joist
30. 2" subfloor to joist or girder
31. Rim joist to top plate
32. Built-up girder and beams
33. 2" planks at each bearing
34. Joist to band joist
35. Ledger strip
36. Band (rim) joist or blocking to sill plate
Note:
1. Schedule is based on the 2018 IBC Table 2304.10.1
2. 8d common (2-1/2" x 0.131")
3. 10d common (3" x 0.148")
4. 16d common (3-1/2" x 0.162")
5. 20d common (4" x 0.192") toenail toenail each end face nail face nail blind and face nail toenail face nail at top and bottom staggered on opposite side face nail at ends and at each splice face nail face nail face nail at each joist toe nail
3 - 8d common 2 - 8d common 2 - 8d common 3 - 8d common 2 - 16d common 8d @ 6" o/c 20d common @ 32" o/c
2 - 20d common 2 - 16d common 3 - 16d common 3 - 16d common 8d common @ 6" o/c
W A
L L
R O
O F
F L
O O
R
TYPICAL DEPRESSED SLAB-ON-GRADE
t
W.W.F.
KEYED JOINT
TYPICAL SLAB CONTROL JOINT
t
W.W.F.
SAWN JOINT
WIDTH: 1/8"
DEPTH: 1/4 OF "t"
2t
OVERLAP VAPOR BARRIER
TAPE VAPOR
BARRIER
SEAM
3/4" DIA. x 12" LONG SMOOTH (A36) DOWEL @ 24" o/c
• 6" EMBEDMENT IN EACH
SIDE OF SLAB
• GREASE DOWEL ONE
SIDE OF JOINT
W.W.F.
6" t
TYPICAL SLAB CONSTRUCTION JOINT w/ DOWELS
VAPOR BARRIER,
PER PLAN
STONE BASE, PER PLAN
TYPICAL STEPPED FOOTING
M A
X
1' - 0" 1' - 0"
S T
E P
WALL
FOOTING
BARS
BENT BARS TO MATCH
SIZE & QUANTITY OF
WALL FOOTING BARS
• PROVIDE FULL LAP
SPLICE
C L R
3"
C L
R
STEP SPACING
3'-0" MIN.
5077 Dallas Hwy Suite 201 Powder Springs, GA 30127
(404) 495-4889 www.mhstructures.com
Integrity is our foundation.
United States Department of Agriculture Forest Service
USDA FOREST SERVICE
REGION 8
PROJECT NO.
CHECKED
DRAWN
DESIGNER
ARCHIVE NO.
DATE SIGNED
DRAWING TITLE
PROJECT NAME
SHEET
DWG SHEET NO.
12-18-2023
S-002
TYPICAL WOOD &
SLAB DETAILS
2022-419
MH
MH
CHATTOOGA
RIVER WORK
CENTER
9975 Highway 441S Lakemont, GA
30552
OPEN
SHEAR WALL KEYNOTES
1. PROVIDE BLOCKING AT SHEAR WALL SHEATHING JOINTS.
2. "STUD-PACK" AT ENDS OF SHEAR WALL. PROVIDE THE
NUMBER OF FULL HEIGHT STUDS AT ENDS OF SHEAR
WALL AS REQUIRED BY SHEAR WALL SCHEDULE.
3. PROVIDE HOLDOWN AND SLAB ANCHOR PER THE SHEAR
WALL SCHEDULE. ATTACH THE HOLDOWN TO THE STUD-
PACK PER THE HOLDOWN MANUFACTURER'S
INSTRUCTIONS.
4. 2x BLOCKING OVER SHEAR WALL. ATTACH TO TOP PLATE WITH 10d TOENAILS AT 6" o/c ON EACH SIDE OF
BLOCKING.
5. "EDGE" NAILING AT ALL EDGES OF SHEATHING; SEE
SHEAR WALL SCHEDULE FOR NAIL SIZE & SPACING.
6. "FIELD" NAILING AT ALL STUDS EXCEPT THOSE AT EDGES
OF SHEATHING PANELS.
7. SHEAR WALL SHEATHING PANEL; REFER TO SHEAR
WALL SCHEDULE FOR TYPE AND THICKNESS.
8. SIP CONNECTOR. SIZE AND SPACING BY SIP
MANUFACTURER'S PROFESSIONAL ENGINEER. DESIGN
FOR SHEAR LOAD AS INDICATED ON S-102.
TYPICAL SHEAR WALL ELEVATION
(AS SHOWN ON PLANS)
SHEAR WALL LENGTH
NOTE: WHERE THE SHEAR WALL LENGTH IS NOT INDICATED
ON THE PLANS, THE SHEAR WALL SHALL BE LOCATED
BETWEEN WALL OPENINGS .
STRUCTURAL WOOD SHEATHING SCHEDULE
LOCATION
1. Typical Exterior Wall
2. Exterior Shear Wall
APA RATING
24/16 24/16
MINIMUM
THICKNESS
7/16" 7/16"
NAIL
SIZE
6d 8d
BOUNDARY
6" 6"
Unblocked Blocked
FIELD
NAIL SPACING
BLOCKED vs UNBLOCKED
12" 12"
DIAPHRAGM
OPEN
OPEN
EXTERIOR WALL KEYNOTES
1. PROVIDE BLOCKING @ 48" o/c IF WALL IS NOT SHEATHED
ON BOTH SIDES.
2. ROOF TRUSSES. ATTACH EACH TRUSS TO THE TOP
PLATE (OR BEAM) WITH (2)-12d TOENAILS AND A
SIMPSON 'H2.5A' HURRICANE TIE.
3. ATTACH THE DOUBLE 2x TOP PLATE TO THE FULL- HEIGHT VERTICAL STUDS @ 48" o/c WITH A SIMPSON 'H6'
TIE. ALSO PROVIDE THE 'H6' TIE ON THE KING STUD ON
BOTH SIDES OF AN OPENING. THE 'H6' TOP PLATE
ANCHOR SHOULD ATTACH TO THE SAME STUD AS THE
'H8' SILL PLATE TIE.
4. PROVIDE DOUBLE KING STUDS AT OPENINGS.
5. PROVIDE A SIMPSON 'H8' HURRICANE TIE @ 48" TO TIE
STUD TO SILL PLATE. ALSO PROVIDE THE 'H8' TIE ON
BOTH SIDES OF OPENINGS. THE 'H8' SILL PLATE TIE
SHOULD ATTACH TO THE SAME STUD AS THE 'H6' TOP
PLATE TIE.
6. 1/2" DIAMETER SILL PLATE ANCHOR @ 48" o/c, AND
PROVIDE A MINIMUM OF 2 ANCHORS PER SILL PLATE.
PROVIDE ANCHORS AT CORNERS AND EACH SIDE OF
OPENINGS. ACCEPTABLE ANCHORS: 'LDT' (LARGE
DIAMETER TAPCON, BY RED HEAD, 'TITEN HD' BY
SIMPSON STRONGTIE, OR EQUAL.
7. PROVIDE SIMPSON 'LSTA18' STRAP AT ENDS OF HEADER
TO JACK STUD. BEND AND NAIL TOP OF STRAP OVER
HEADER AS REQUIRED.
8. SIP CONNECTOR. SIZE AND SPACING BY SIP
MANUFACTURER'S PROFESSIONAL ENGINEER. DESIGN
FOR SHEAR LOAD AS INDICATED ON S1.1.
5 6
TYPICAL EXTERIOR & LOAD BEARING WALL ELEVATION
WOOD SHEAR WALL SCHEDULE
MARK
SW-1
SHEATHING
7/16" OSB (EXT.)
FASTENERS
OSB: 8d NAILS
FASTENER SPACING
EDGE: @ 6" o/c FIELD: @ 12" o/c
SIMPSON HOLDOWN
AT ENDS OF WALL
HDU5 W/ 5/8" x 6" LDT
ANCHOR
STUD-PACK @ ENDS
OF WALL
(2) 2x6
5077 Dallas Hwy Suite 201 Powder Springs, GA 30127
(404) 495-4889 www.mhstructures.com
Integrity is our foundation.
United States Department of Agriculture Forest Service
USDA FOREST SERVICE
REGION 8
PROJECT NO.
CHECKED
DRAWN
DESIGNER
ARCHIVE NO.
DATE SIGNED
DRAWING TITLE
PROJECT NAME
SHEET
DWG SHEET NO.
12-18-2023
S-003
TYPICAL WOOD
DETAILS
2022-419
MH
MH
CHATTOOGA
RIVER WORK
CENTER
9975 Highway 441S Lakemont, GA
30552
H
O W
E R
1 2
A
B
(OUTSIDE FACE OF STUD)
99' - 10"
(O U
T S
ID
E
F A
C E
O F
S T
U D
SLOPE SLAB AT DOORS 1/2"
S-101
S-101
S-101
S-101
6" CONCRETE SLAB ON GRADE OVER 15 MIL
VAPOR RETARDER OVER 4" GAB STONE BASE
• 4000 PSI CONCR. @ 28 DAYS
• REINF. SLAB W/ 6x6-W2.9xW2.9 W.W.F. 2"
FROM TOP OF SLAB
SW-1
HD HD
HD
HD
HD
HD
SW-1SW-1
S W
-1
HD
HD
HD
HD
8" WIDE CONCRETE CURB
• TOP OF CURB +1'-0" ABOVE FFE
8" WIDE CONCRETE CURB
• TOP OF CURB +1'-0" ABOVE FFE
8" WIDE CONCRETE
CURB
• TOP OF CURB +
1'-0" ABOVE FFE
8" WIDE CONCRETE CURB
• TOP OF CURB +1'-0" ABOVE FFE
C.J.
C .J
C .J
C .J
C .J
C .J
C.J.
TOF -1' - 4"
TOF -1' - 4"
TOF -3' - 4"
TOF -1' - 4"
TOF -1' - 4"
SEE SLAB PLAN ON
A1.0 FOR ADDITIONAL
SLAB AND DRAIN INFO
C .J
HD HD
S-101
SLOPE SLAB AT DOORS 1/2"
TRENCH DRAIN,
LOCATION & SPECS.
PER ARCH. & PLUMBING
DRAWINGS
TOF -1' - 4"
S
8' - 0"
S
S
TOF -3' - 4"
TOF -1' - 4"
TOF -2' - 8"
TOF -1' - 4"
TOF -2' - 8"
S S
S
BELOW SLAB
PLUMBING, COORD. w/
PLUMBING PLANS
SLEEVE PIPE
CROSSING BELOW
FTG., COORD. SLEEVE
SPEC. w/ PLUMBING
PLANS
SLEEVE THRU-WALL
PIPE
SLEEVE PIPE
CROSSING BELOW
FTG., COORD. SLEEVE
SPEC. w/ PLUMBING
PLANS
14' - 1" 14' - 1" 14' - 1" 14' - 1" 14' - 1" 14' - 1" 14' - 1"
SW-1
S W
-1
(O U
T S
ID
E
F A
C E
O F
C O
N C
C
U R
B
(OUTSIDE FACE OF CONC. CURB)
99' - 11"
P L A
N
S E
E F
D N
2' - 6"
C L R
CLR
3"
REFER TO FOUNDATION
PLAN FOR SLAB
THICKNESS & REINF.
VAPOR BARRIER
4" GRAVEL BASE
TURN VAPOR BARRIER
UP FOR SLAB/WALL
BOND BREAKER
2x6 STUDS @ 12" o/c
#4 DOWEL @ 18" o/c
(3) - #5 BARS, CONT.
(1 TOP, 2 BOTT.)
#4 CONSTRUCTION
BAR @ 48" o/c
#5 @ 12" o/c
• LOCATE AS SHOWN TO
AVOID INTERFERENCE
WITH WALL ANCHORS
11" 8" 11"
7 1/2"
CLR
5"
EXTERIOR SLAB-ON-GRADE
1/2" PRE-MOLDED JOINT FILLER
1-1/2" CHAMFER
OUTSIDE FACE
OF STUD
REFER TO TYPICAL EXTERIOR &
LOAD BEARING WALL ELEVATION
ON S-003 FOR WALL ANCHORAGE
REQUIRED
SHEATHING (SEE ARCH. PLANS)
2x6 P.T. SILL PLATE
FOUNDATION NOTES
HOLD-DOWN ANCHOR WITH STUD-PACK PER WOOD
SHEAR WALL SCHEDULE ON S-003
TOP OF FOOTING ELEVATION RELATIVE TO FFE 0'-0"
SHEAR WALL; SEE SCHEDULE ON S-003
SLAB CONTROL JOINT; SEE S-002 FOR TYPICAL DETAIL
STEPPED FOOTING MARK; SEE S-002 FOR TYPICAL DETAIL
TOF
SW-#
C.J.
S
8" t
W.W.F.
2-#5 CONT. (TOP & BOTT.)
SITE PAVING, SEE
ARCH. PLANS
SLOPE
CONTINUE WALL FOOTING
ACROSS OPENING
CONCR. CURB AT
WALL BEYOND
5077 Dallas Hwy Suite 201 Powder Springs, GA 30127
(404) 495-4889 www.mhstructures.com
Integrity is our foundation.
United States Department of Agriculture Forest Service
USDA FOREST SERVICE
REGION 8
PROJECT NO.
CHECKED
DRAWN
DESIGNER
ARCHIVE NO.
DATE SIGNED
DRAWING TITLE
PROJECT NAME
SHEET
DWG SHEET NO.
12-18-2023
S-101
FOUNDATION PLAN
2022-419
MH
MH
CHATTOOGA
RIVER WORK
CENTER
9975 Highway 441S Lakemont, GA
30552
MH
3/16" = 1'-0"
FOUNDATION PLAN
3/4" = 1'-0"S-101
1 TYPICAL EXTERIOR WALL FOOTING
N
3/4" = 1'-0"S-101
2 TURND DOWN SLAB AT EXTERIOR DOOR
S-201
1 2
A
B
PRE-FAB. WOOD TRUSSES @ 24" o/c
G A
B L E
E N
D W
A L L T
R U
S S
D
IA
P
H R
A G
M L
O A
D