Attachment 02 - Final Drawings.pdf
PDF 3 MB Posted
- Attached to
- Y1AZ--402-21-724 Boiler Plant Stack Pad Repairs
- Solicitation number
- 36C24124B0034
About this file
This is an invitation for bid (IFB) from the Department of Veterans Affairs for boiler plant stack pad repairs at the Togus, Maine VA Medical Center. The IFB is set aside for service-disabled veteran-owned small businesses. Bids are due by the date specified in the Instructions to All Bidders document. The statement of work outlines the required repairs to the concrete pad and supporting structure below the medical center's boiler stack, which includes removing portions of the existing concrete pad and pile cap, installing temporary shoring, removing and reinstalling structural steel components, and pouring new concrete. The bid package contains engineering drawings detailing the scope of demolition, temporary shoring plans, structural repairs, concrete and masonry details.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment 03 - Final Specifications.pdf | ||
| Attachment 01 - Wage Determination ME20240022 Heavy.pdf | ||
| Attachment 04 - Records Management Verbiage for 6500 SOW.pdf | ||
| 36C24124B0034.docx | DOCX document | |
| SOW 402-21-724.doc | DOC document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
Department of Veterans Affairs Medical Center
ABOVE GROUP, INC.
STRUCTURAL
305 EAST DRIVE, SUITE H
MELBOURNE, FL 32904
321.345.9026 P
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s /0
V
A T o g u s B o ile r S ta c k P a d
R e p a ir /0
V A
T o g u s B o ile r R e p a ir
R
S
.r v t
/1
/2
:4
:1
P
M
GI001
COVER SHEET VA TOGUS BOILER STACK
PAD REPAIR
AUGUSTA, ME
402-21-724
12/16/2022 NPC RAS
CONSTRUCTION DOCUMENT
SUBMISSION
VA TOGUS BOILER STACK PAD REPAIR
1 VA Center, Augusta, ME 04330 PROJECT #: 402-21-724
PROJECT LOCATION
© Google Maps
SHEET LIST
Sheet Number Sheet Name
GI001 COVER SHEET
SG001 GENERAL NOTES AND ABBREVIATIONS
SG002 STATEMENT OF SPECIAL INSPECTIONS
SS101 SITE PLAN
SD101 DEMOLITION AND TEMPORARY SHORING PLAN
SB101 STRUCTURAL NEW WORK PLAN
SE301 CONCRETE AND MASONRY DETAILS AND SECTIONS
SE302 STEEL DETAILS AND SECTIONS
Revisions Date
AB ANCHOR BOLT
ABV ABOVE
ACI AMERICAN CONCRETE INSTITUTE
ADDL ADDITIONAL
ADH ADHESIVE
ADJ ADJACENT, ADJUSTMENT
A/E ARCHITECT/ENGINEER
AESS ARCHITECTURALLY EXPOSED STRUCTURAL STEEL
AFF ABOVE FINISHED FLOOR
AGG AGGREGATE
AHJ AUTHORITY HAVING JURISDICTION
AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION
AISI AMERICAN IRON AND STEEL INSTITUTE
ALT ALTERNATE
ANCH ANCHOR
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
APA ENGINEERED WOOD ASSOCIATION
APRX APPROXIMATE
AR ANCHOR ROD
ARCH ARCHITECT(URAL)
ASCE AMERICAN SOCIETY OF CIVIL ENGINEERS
ASD ALLOWABLE STRESS DESIGN
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS
AWC AMERICAN WOOD COUNCIL
AWPA AMERICAN WOOD PROTECTION AGENCY
AWS AMERICAN WELDING SOCIETY
AVG AVERAGE
B BOTTOM
B/ BOTTOM OF
B-B BACK-TO-BACK
BAL BALANCE
BEL BELOW
BF BRACED FRAME
BLDG BUILDING
BLK(G) BLOCK(ING)
BM BEAM
BOT BOTTOM
BP BASE PLATE, BEARING PLATE
BR BRACE(ING)
BRDG BRIDGING
BRG BEARING
BRK BRICK
BRKT BRACKET
BS BOTH SIDES
BSMT BASEMENT
BT BENT
BTWN BETWEEN
BYD BEYOND
C STEEL CHANNEL
CAIS CAISSON
CALC CALCULATION
CANT CANTILEVER
CAP CAPACITY
C-C CENTER-TO-CENTER
CE CONCRETE ENCASED
CFM COLD FORMED METAL
CHAM CHAMFER
CI CAST IRON
CIP CAST IN PLACE
CJ CONTROL/CONTRACTION JOINT
CL CENTERLINE, COLUMN LINE
CLG CEILING
CLR CLEAR
CM CONSTRUCTION MANAGER
CMU CONCRETE MASONRY UNIT
COL COLUMN
COMB COMBINED
COMP COMPOSITE
CONC CONCRETE
COND CONDITION
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
COV COVER
CP CAP PLATE
CRSI CONCRETE REINFORCING STEEL INSTITUTE
CSK COUNTERSUNK
CTR CENTER(ED)
CY CUBIC YARD
CYL CYLINDER
d PENNY (AS IN NAIL, Id)
DBL DOUBLE
DD DESIGN DEVELOPMENT
DEF DEFLECTION
DEG DEGREE
DEMO DEMOLITION/DEMOLISH
DEPR DEPRESS(ED)/DEPRESSION
DET(S) DETAIL(S)
DEV DEVELOP/DEVELOPMENT
DIA DIAMETER
DIAG DIAGONAL
DIM(S) DIMENSION(S)
DIR DIRECTION
DK DECK
DL DEAD LOAD
DN DOWN
DO DITTO
DP DEEP
DWG(S) DRAWING(S)
DWL DOWEL
(E) EXISTING
E EAST
EA EACH
EF EACH FACE
EIFS EXTERIOR INSULATION FINISH SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
EMBED EMBEDMENT/EMBEDDED
ENGR ENGINEER
EO EDGE OF
EOD EDGE OF DECK
EOM EDGE OF MASONRY
EOS EDGE OF SLAB
EQ EQUAL
EQUIP EQUIPMENT
ES EACH SIDE
STRUCTURAL ABBREVIATIONS
ES EACH SIDE
EXCAV EXCAVATE/EXCAVATION
EXP EXPANSION
EXT EXTERIOR
EXIST EXISTING
EW EACH WAY
F/ FACE OF
FAB FABRICATE
FB FLAT BAR
FBO FURNISHED BY OTHERS
FDN FOUNDATION
FFE FINISHED FLOOR ELEVATION
FIN FINISH(ED)
FL(R) FLOOR
FLG FLANGE
FND FOUNDATION
FO FACE OF
FOC FACE OF CONCRETE
FOF FACE OF FINISH
FOM FACE OF MASONRY
FOS FACE OF STUD
FP FIREPROOFING
FRMG FRAMING
FRP FIBER-REINFORCED POLYMER
FRT FIRE RETARDANT TREATED
FS FAR SIDE
FT FEET
FTG FOOTING
FUT FUTURE
FV FIELD VERIFY
GA GAUGE
GALV GALVANIZE(D)
GB GRADE BEAM
GC GENERAL CONTRACTOR
GLB GLUE LAMINATED BEAM
GR GRADE
GYP GYPSUM
HD HEAVY DUTY
HDR HEADER
HEF HORIZONTAL EACH FACE
HGR HANGER
HI HIGH
HIF HORIZONTAL INSIDE FACE
HK HOOK(ED)
HOF HORIZONTAL OUTSIDE FACE
HORIZ HORIZONTAL
HP HIGH POINT
HS HIGH STRENGTH
HT HEIGHT
H&V HORIZONTAL & VERTICAL
HVAC HEATING, VENTILATING & AIR CONDITIONING
IBC INTERNATIONAL BUILDING COUNCIL
ICC INTERNATIONAL CODE COUNCIL
ID INSIDE DIAMETER
IF INSIDE FACE
IFC ISSUE FOR CONSTRUCTION
IN INCH
INCL INCLUDE(D)(ING)
INFO INFORMATION
INSTL INSTALL/INSTALLATION
INSUL INSULATION
INT INTERIOR
INV INVERT(ED)
JST(S) JOIST(S)
JT JOINT
K KIP (THOUSAND POUNDS)
KB KNEE BRACE
KSI KIPS PER SQUARE INCH
LB, # POUND
LDGR LEDGER (BOARD)
LEN LENGTH
LG LONG
LL LIVE LOAD
LLBB LONG LEGS BACK TO BACK
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LOCN LOCATION
LONGIT LONGITUDINAL
LP LOW POINT
LRFD LOAD AND RESISTANCE FACTOR DESIGN
LSL LONG SLOTTED HOLE,
LAMINATED STRAND LUMBER
LVL LAMINATED VENEER LUMBER
LW LONG WAY
LWC LIGHT WEIGHT CONCRETE
M MOMENT
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MEP MECHANICAL, ELECTRICAL & PLUMBING
MEZZ MEZZANINE
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MONO MONOLITHIC
MPH MILES PER HOUR
MTL METAL
NA NOT APPLICABLE
NDS NATIONAL DESIGN SPECIFICATION FOR WOOD
CONSTRUCTION
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NS NEAR SIDE
NTS NOT TO SCALE
NWC NORMAL WEIGHT CONCRETE
OC ON CENTER
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
O-O OUT-TO-OUT
OPG OPENING
OPP OPPOSITE
OSB ORIENTED STRAND BOARD
OSHA OCCUPATIONAL SAFETY AND HEALTH
ADMINISTRATION
OSL OUTSTANDING LEG,
ORIENTED STRAND LUMBER
OVS OVERSIZED HOLE
PAF POWDER ACTUATED FASTENER
PC PRECAST CONCRETE, PIECE
PCF POUNDS PER CUBIC FOOT
PED PEDESTAL
PERP PERPENDICULAR
PREFAB PREFABRICATE(D)
PL PLATE
PLF POUNDS PER LINEAR FOOT
PLYWD PLYWOOD
PMF PREMOLDED FILLER
PROJ PROJECT(ION)
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PSL PARALLEL STRAND LUMBER
PT PRESERVATIVE-TREATED,
POST-TENSIONED
PVC POLYVINYL CHLORIDE
QTY QUANTITY
R RADIUS
RCMU REINFORCED CONCRETE MASONRY UNIT
RCSC RESEARCH COUNCIL ON STRUCTURAL
CONNECTIONS
RD ROOF DRAIN
RDK ROOF DECK
REF REFERENCE
REINF REINFORCE(D)/REINFORCEMENT
REQ(D) REQUIRE(D)
RET RETAINING
REV REVISE(D)/REVISION
RO ROUGH OPENING
RQMT(S) REQUIREMENT(S)
RTU ROOFTOP UNIT
RXN REACTION
SAN SANITARY
SC SLIP-CRITICAL (CONNECTION)
SCHED SCHEDULE
SECT SECTION
SD STORM DRAIN
SDI STEEL DECK INSTITUTE
SF SQUARE FOOT
SHRG SHORING
SHTHG SHEATHING
SIM SIMILAR
SL SLOPE(D)
SLBB SHORT LEGS BACK TO BACK
SLV SLEEVE
SOD SLAB ON DECK
SOG SLAB ON GRADE
SPA SPACE(S)/SPACING
SPEC(S) SPECIFICATION(S)
SQ SQUARE
SS STAINLESS STEEL
SSL SHORT SLOTTED HOLE
STD STANDARD
STIFF STIFFENER
STIR STIRRUP
STL STEEL
STRUC STRUCTURAL
SUPT SUPPORT
SW SHORT WAY, SHEAR WALL
SYM SYMMETRICAL
T TOP
T/ TOP OF
T&B TOP AND BOTTOM
TB TRUSS BEARING
TC TERRA COTTA
TEMP TEMPORARY,TEMPERATURE
T&G TONGUE AND GROOVE
THD THREAD(ED)
THK THICK(NESS)
TMS THE MASONRY SOCIETY
TOS TOP OF SLAB
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
U-P UNDERPINNING
V SHEAR
VAR VARIES
VB VAPOR BARRIER
VEF VERTICAL EACH FACE
VERT VERTICAL
VIF VERTICAL INSIDE FACE,
VERIFY IN FIELD
VOF VERTICAL OUTSIDE FACE
VR VAPOR RETARDER
W/ WITH
W/O WITHOUT
WD WOOD
WI WROUGHT IRON
WP WORK POINT, WATERPROOFING
WT WEIGHT
WWF WELDED WIRE FABRIC
XS EXTRA STRONG
XXS DOUBLE EXTRA STRONG
∅ DIAMETER
± PLUS OR MINUS
ABBR. DESCRIPTION ABBR. DESCRIPTION ABBR. DESCRIPTIONGENERAL:
1. CONTRACTOR IS SOLELY RESPONSIBLE FOR MEANS AND METHODS
DURING THE COURSE OF THE WORK. DO NOT DAMAGE OR
ENDANGER THE STRUCTURAL INTEGRITY OF THE WORK.
2. NOTIFY COR IN CASE OF DISCREPANCIES BETWEEN DRAWINGS,
THESE NOTES, AND SPECIFICATIONS BEFORE PROCEEDING WITH THE
WORK.
3. IF CONDITIONS DISCLOSED DURING EXCAVATION REVEAL
UNFORESEEN CONDITIONS, PROMPTLY REQUEST DIRECTION FROM
COR BEFORE PROCEEDING.
4. CONTRACTOR IS RESPONSIBLE FOR COORDINATING BETWEEN
TRADES.
5. DO NOT SCALE DRAWINGS.
6. SECTIONS AND DETAILS SHOWN, WHILE DRAWN FOR SPECIFIC
LOCATIONS, ARE INTENDED TO ESTABLISH THE GENERAL TYPES OF
DETAILS WILL APPLY TO OTHER LOCATIONS.
7. THE ENGINEER'S REVIEW OF A SUBMITTAL SHALL NOT RELIEVE THE
CONTRACTOR OF THEIR RESPONSIBILITY TO FOLLOW THE INTENT OF
THE CONTRACT DRAWINGS.
8. REPRODUCTION OF CONTRACT DOCUMENTS WILL NOT BE ACCEPTED
AS SHOP DRAWINGS.
9. ALL WORK SPECIFIED HEREIN SHALL BE INSPECTED IN ACCORDANCE
WITH IBC CHAPTER 17 (EXCEPTIONS NOTED SHALL NOT BE
PERMITTED) AND ALL LOCAL ORDINANCES. INSPECTIONS REQUIRED
SHALL BE PER THE STATEMENT OF SPECIAL INSPECTIONS NOTED ON
THIS SHEET. THE CONTRACTOR SHALL HIRE AN EXPERIENCED,
QUALIFIED INSPECTOR TO PERFORM ALL THE REQUIRED INSPECTION
WORK. THE ENGINEER WILL NOT PERFORM THE REQUIRED
INSPECTION AS A PART OF HIS DESIGN SERVICE. THE ENGINEER MAY
VISIT THE SITE TO ASCERTAIN GENERAL CONFORMANCE TO THE
CONTRACT DOCUMENTS, AND SUCH VISITS ARE NOT TO BE
CONSTRUED AS MEETING INSPECTION REQUIREMENTS.
GENERAL NOTES
RIGGING, HOISTING AND SCAFFOLDING REQUIREMENTS:
1. THE CONTRACTOR SHALL PREPARE AND SUBMIT TO THE COR FOR
REVIEW A SITE SPECIFIC RIGGING AND HOISTING PLAN. THE PLAN
SHALL INCLUDE THE SEQUENCE OF OPERATION, THE DESCRIPTION
OF THE RIGGING, HOISTING AND TRANSPORTATION EQUIPMENT AND
THE SITE PREPARATIONS THAT WILL BE NEEDED TO COMPLETE THE
INSTALLATION.
2. THE PROPOSED RIGGING, HOISTING OR SCAFFOLDING PLAN SHALL BE
REVIEWED BY A PROFESSIONAL ENGINEER REGISTERED IN THE
LOCAL JURISDICTION. OPERATIONS SHALL COMPLY WITH OSHA
REGULATIONS.
EXISTING CONSTRUCTION:
1. ABOVE GROUP, INC. HAS PREPARED THESE PLANS BASED ON A
LIMITED AMOUNT OF FIELD EXPLORATION AND ON THE STRUCTURAL
INFORMATION SHOWN IN DRAWINGS 239-S1 PREPARER UNKNOWN
DATED APRIL 30, 1963 AND D96068 S2-1, S3-1, AND S4-1 PREPARED BY
WARREN ENVIRONMENT, INC. DATED SEPTEMBER 9, 1996 AND REPAIR
SKETCHES AND CALCULATIONS 1-8 BY J.R. TRIMBLE DATED JANUARY
15, 1997. THE EXISTING MEMBER SIZES ARE NOTED (E) AND ARE
SHOWN IN THE PLANS. THE CONTRACTOR SHALL VERIFY THAT THE
EXISTING MEMBERS SHOWN IN THE PLANS MATCH EXISTING AS BUILT
CONDITIONS PRIOR TO PREPARING SHOP DRAWINGS. IF THE AS BUILT
CONDITIONS DO NOT CONFORM TO THE INFORMATION SHOWN IN THE
PLANS, OR IF ANY STRUCTURAL MEMBER IS FOUND TO BE IN POOR
CONDITION, THE CONTRACTOR SHALL INFORM COR OF THE ACTUAL
SIZES AND/OR CONDITION. RE-DESIGN AND ADDITIONAL FRAMING MAY
BE REQUIRED IN THAT CASE.
POST-INSTALLED ANCHORS AND REINFORCING:
1. DRILL AND INSTALL POST-INSTALLED ANCHORS/REINFORCING
ACCORDING TO MANUFACTURER'S PRINTED INSTALLATION
INSTRUCTIONS AND PER MANUFACTURER'S ON-SITE TRAINING.
2. ALL INSTALLERS OF POST-INSTALLED ANCHORS/REINFORCING SHALL
BE ACI/CRSI ADHESIVE ANCHOR INSTALLER CERTIFIED. SUBMIT
CERTIFICATES FOR RECORD.
3. ALL POST-INSTALLED ANCHORS/REINFORCING SHALL MEET ICC-ES
COMPLIANCE FOR EACH TYPE OF APPLICATION.
4. SUBMIT PRODUCT INFORMATION AND ICC-ES EVALUATION REPORT
FOR EACH APPLICATION.
5. ALL POST-INSTALLED DESIGNS ARE FOR INSTALLATION IN THE
FOLLOWING CONDITIONS, UNLESS NOTED OTHERWISE. WRITTEN
APPROVAL MUST BE RECEIVED FROM ENGINEER PRIOR TO
INSTALLATION OF ADHESIVE ANCHORS/REINFORCING IN ALTERNATE
CONDITIONS.
A. DRY CONCRETE, UNLESS NOTED OTHERWISE.
B. CONCRETE TEMPERATURE AT TIME OF INSTALLATION MUST BE
BETWEEN 14° F AND 104° F. SEE MANUFACTURER’S PRINTED
INSTALLATION INSTRUCTION FOR ADHESIVE GEL AND CURE
TIMES.
C. HOLES TO BE HAMMER DRILLED.
D. HOLES TO BE CLEANED PER MANUFACTURER’S PRINTED
INSTALLATION INSTRUCTIONS PRIOR TO ADHESIVE INJECTION.
E. POST-INSTALLED ANCHORS/REINFORCING SHALL NOT BE LOADED
UNTIL CONCRETE OR GROUT HAS BEEN ALLOWED TO CURE FOR
21 DAYS AND/OR HAS ATTAINED 70% OF ITS DESIGN STRENGTH.
6. ALL POST-INSTALLED ANCHORS/REINFORCING IN CONCRETE SHALL
BE SUITED FOR USE IN SEISMIC AND CRACKED CONCRETE
APPLICATIONS.
7. ADHESIVE IN CONCRETE SHALL BE HILTI HIT HY-200, OR APPROVED
EQUAL.
8. PROVIDE STANDARD AISC HOLES IN ALL STEEL MEMBERS RECEIVING
POST-INSTALLED ANCHORS. IF OVERSIZED HOLES ARE PROVIDED TO
EASE INSTALLATION OF THE ANCHORS, A PLATE WASHER (1/4"X2"X2")
WITH AN AISC STANDARD HOLE SHALL BE INSTALLED AND 1/8" FILLET
WELDED (ALL AROUND) TO THE MEMBER.
9. ALL ANCHORS AND REINFORCING SHALL BE INSTALLED IN
ACCORDANCE WITH THE SPACING AND EDGE DISTANCES SHOWN IN
THE DRAWINGS. THE CONTRACTOR SHALL INFORM THE COR PRIOR
TO INSTALLATION IF THE SPACING AND EDGE DISTANCES SHOWN IN
THE DRAWINGS CANNOT BE ACHIEVED. IF THIS IS THE CASE, RE-
DESIGN MIGHT BE REQUIRED AND THE ANCHORS/REINFORCING
SHOULD NOT BE INSTALLED UNTIL APPROVAL HAS BEEN PROVIDED
BY THE ENGINEER.
10. DO NOT CUT ANY REINFORCING UNLESS IT IS SPECIFICALLY
INDICATED IN THE DRAWINGS OR IS APPROVED BY THE ENGINEER.
11. POST INSTALLED ANCHORS/REINFORCING SHALL ONLY BE USED
WHERE SPECIFIED IN THE CONTRACT DRAWINGS. THE CONTRACTOR
SHALL OBTAIN APPROVAL FROM THE ENGINEER PRIOR TO INSTALLING
POST INSTALLED ANCHORS WHERE CAST-IN PLACE ANCHORS ARE
MISSING, MISPLACED OR DAMAGED.
STEEL:
1. STRUCTURAL STEEL FOR WIDE FLANGE SHAPES SHALL CONFORM TO
ASTM SPECIFICATION A992 GRADE 50. STRUCTURAL STEEL FOR
TUBES SHALL CONFORM TO ASTM SPECIFICATION A500 GRADE C. ALL
OTHER STEEL SHALL CONFORM TO ASTM SPECIFICATION A36. MILL
TEST REPORTS SHALL BE SUBMITTED. ALL STEEL SHALL BE DETAILED,
FABRICATED AND ERECTED IN ACCORDANCE WITH THE AISC MANUAL,
AISC SPECIFICATION AND AISC CODE OF STANDARD PRACTICE. IN
GENERAL, FIELD CONNECTIONS SHALL BE MADE WITH 3/4" DIAMETER
A325 BOLTS UNLESS OTHERWISE NOTED AND SHOP CONNECTIONS
SHALL BE WELDED.
2. BOLTS, EXCEPT AS NOTED, NEED ONLY BE INSTALLED TO THE "SNUG
TIGHT" CONDITION AS DEFINED IN THE RCSC "SPECIFICATION FOR
STRUCTURAL JOINTS."
3. WELDS SHALL BE MADE WITH E70XX LOW HYDROGEN ELECTRODES.
4. ALL GROOVE WELDS SHALL BE FULL PENETRATION GROOVE WELDS IN
ACCORDANCE WITH ANSI/AWS D1.1, "STRUCTURAL WELDING CODE".
THESE WELDS SHALL BE MADE ONLY BY OPERATORS QUALIFIED BY
PRESCRIBED TESTS IN THE "STRUCTURAL WELDING CODE."
ACCEPTANCE SHALL BE SUBJECT TO THE INSPECTION AND REVIEW OF
AN INDEPENDENT INSPECTION AGENCY. ALL FULL PENETRATION
WELDS SHALL BE ULTRASONICALLY TESTED.
5. FIELD MODIFICATION OF THE STRUCTURAL STEEL IS NOT ALLOWED
WITHOUT PRIOR REVIEW BY THE ENGINEER.
6. WELDING SEQUENCE AND TECHNIQUE SHALL BE SUCH THAT
DISTORTION OF STEEL MEMBERS IS MINIMIZED AND UNDUE
DISTORTION IS AVOIDED.
DESIGN CODES:
VA DESIGN AND CONSTRUCTION PROCEDURES
PG-18-3
VA HANDBOOK FOR SEISMIC DESIGN REQUIREMENTS
H18-8
VA STRUCTURAL DESIGN MANUAL FOR ENERGY CENTER PROJECTS
INTERNATIONAL BUILDING CODE:
IBC 2021
INTERNATIONAL EXISTING BUILDING CODE:
IEBC 2021
BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE:
ACI 318-19
SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS:
AISC 14TH EDITION 360-16
SEISMIC PROVISIONS FOR STRUCTURAL STEEL BUILDINGS:
AISC 341-16
DESIGN LOADS:
RISK CATEGORY IV
LATERAL FORCE-RESISTING SYSTEMS:
STEEL STACK, R=2
SEISMIC DESIGN DATA:
EQUIVALENT LATERAL FORCE PROCEDURE
SOIL SITE CLASS ASSUMED D
SEISMIC DESIGN CATEGORY C
SEISMIC IMPORTANCE FACTOR, Ie = 1.5
MAPPED SPECTRAL RESPONSE ACCELERATION PARAMETERS:
Ss = 0.314g S1 = 0.077g
DESIGN SPECTRAL RESPONSE ACCELERATION PARAMETERS:
Sds = 0.324g Sd1 = 0.123g
SEISMIC RESPONSE COEFFICIENT, Cs = 0.176
DESIGN BASE SHEAR = 7 KIPS
WIND LOADS:
DESIGN WIND SPEED:
Vult = 123 MPH (3 SECOND GUST)
WIND EXPOSURE C
CONCRETE:
1. ALL CONCRETE EXPOSED TO THE WEATHER SHALL BE f'c=5000 PSI
MINIMUM AND SHALL BE AIR ENTRAINED FOR EXPOSURE CLASS F2
PER ACI 318 "BUILDING CODE REQUIREMENTS FOR STRUCTURAL
CONCRETE".
2. ALL REINFORCING STEEL SHALL BE CONFORMING TO ASTM
DESIGNATION A615, GRADE 60. ALL REINFORCING STEEL SHALL BE
DETAILED, FABRICATED AND PLACED IN ACCORDANCE WITH ACI
SP-66, "ACI DETAILING MANUAL".
3. ALL SPLICES IN REINFORCING SHALL BE CLASS "B" SPLICES IN
ACCORDANCE WITH ACI 318, "BUILDING CODE REQUIREMENTS FOR
STRUCTURAL CONCRETE" EXCEPT AS OTHERWISE NOTED.
4. UNLESS OTHERWISE NOTED ON STRUCTURAL DRAWINGS, PROVIDE
CONCRETE PROTECTION FOR REINFORCING AS FOLLOWS:
A. CAST AGAINST EARTH = 3"
B. EXPOSED TO EARTH OR WEATHER:
1. NO. 6 AND LARGER BARS = 2"
2. NO. 5 AND SMALLER BARS = 1 1/2"
5. THE CONTRACTOR MUST SUBMIT A CONCRETE DESIGN MIX IN
ACCORDANCE WITH ACI 318. SUCH DESIGN MIX SHALL BE
ACCOMPANIED BY THE APPROPRIATE GRAPHS AND BACKGROUND
DATA. CONCRETE DESIGN MIX SHALL INDICATE 7 AND 28 DAY
STRENGTHS, CEMENT CONTENT, WATER-CEMENT RATIO, FINE AND
COARSE AGGREGATES AND ADMIXTURES FOR EACH DESIGN
STRENGTH. THE ADDITION OF WATER AT THE PLANT OR IN THE FIELD
GREATER THAN THE SPECIFIED WATER CONTENT IS STRICTLY
PROHIBITED.
6. ALL CONCRETE WORK SHALL CONFORM TO THE LATEST LOCAL
APPROVED EDITIONS OF THE FOLLOWING ACI AND ASTM
DOCUMENTS:
A. ACI-301 SPECIFICATIONS FOR STRUCTURAL CONCRETE
B. ACI-318 CODE
C. ACI-214 COMPRESSIVE TEST
D. ACI-306 COLD WEATHER
E. ACI SP-66 DETAILING
F. ACI-347 FORMWORK
G. ACI-305 HOT WEATHER
H. ACI-211 PROPORTIONS OF CONCRETE
I. ACI-304 PLACING CONCRETE
J. ASTM C-94 READY-MIX CONCRETE
7. ALL FIELD AND LAB TESTING OF CONCRETE SHALL CONFORM TO THE
LATEST LOCAL APPROVED EDITIONS OF ASTM:
A. ASTM C-31 FIELD CYLINDER SPECIMENS
B. ASTM C-143 SLUMP TEST
C. ASTM C-231 AIR CONTENT (WHEN REQUIRED)
D. ASTM C-39 LAB TESTING CYLINDERS
E. ASTM C-172 SAMPLING FRESH CONCRETE
F. ASTM C-42 HARDENED CORES (WHEN REQUIRED)
TEST RESULTS SHALL BE SIGNED AND SEALED BY A
PROFESSIONAL ENGINEER REGISTERED IN THE LOCAL
JURISDICTION.
8. ALL FORMWORK SHALL BE IN ACCORDANCE WITH ACI 347, "GUIDE TO
FORMWORK FOR CONCRETE".
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s /0
V
A T o g u s B o ile r S ta c k P a d
R e p a ir /0
V A
T o g u s B o ile r R e p a ir
R
S
.r v t
/1
/2
:4
:1
P
M
SG001
GENERAL NOTES AND
ABBREVIATIONS
VA TOGUS BOILER STACK
PAD REPAIR
AUGUSTA, ME
402-21-724
12/16/2022 NPC RAS
CONSTRUCTION DOCUMENT
SUBMISSION
STATEMENT OF SPECIAL INSPECTIONS
STRUCTURAL TESTING & INSPECTION PROGRAM NOTES:
1. THE INTENTION OF THIS TABLE IS TO IDENTIFY THE CONSTRUCTION REQUIRING SPECIAL INSPECTION AS REQUIRED BY THE INTERNATIONAL BUILDING CODE (IBC). COR SHALL ENGAGE INDEPENDENT SPECIAL INSPECTION AGENCY. CONTRACTOR TO NOTIFY SPECIAL INSPECTOR OF PROGRESS OF CONSTRUCTION AND PROVIDE ACCESS TO THE SITE TO COMPLETE INSPECTIONS. EACH SPECIAL INSPECTOR IS RESPONSIBLE FOR JOB SPECIFIC ITEMS AS DEFINED IN
CHAPTER 17 OF THE IBC (AND IN ACCORDANCE WITH THE SPECIFICATION).
2. THE ITEMS CHECKED WITH AN "X" SHALL BE INSPECTED IN ACCORDANCE WITH IBC CHAPTER 17 BY A CERTIFIED SPECIAL INSPECTOR FROM AN ESTABLISHED TESTING AGENCY. FOR MATERIAL SAMPLING AND TESTING REQUIREMENTS, REFER TO THE MATERIAL SAMPLING AND TESTING SECTION OF THE PROJECT SPECIFICATIONS AND THE GENERAL NOTES. THE TESTING AGENCY SHALL SEND COPIES OF ALL STRUCTURAL TESTING AND INSPECTION REPORTS DIRECTLY TO THE ENGINEER, CONTRACTOR AND COR. ANY CONSTRUCTION WHICH FAILS TO MEET THE PROJECT SPECIFICATIONS AND IBC REQUIREMENTS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE CONTRACTOR FOR CORRECTION AND THE ENGINEER IF UNCORRECTED.
SPECIAL INSPECTION TESTING REQUIREMENTS APPLY EQUALLY TO ALL BIDDER DESIGNED COMPONENTS.
3. FREQUENCY OF INSPECTIONS.
A. CONTINUOUS SPECIAL INSPECTION MEANS THAT THE SPECIAL INSPECTOR SHALL BE ON SITE AT ALL TIMES OBSERVING THE WORK REQUIRING SPECIAL
INSPECTION. FOR STRUCTURAL STEEL, INSPECTION TASK MUST BE COMPLETED FOR EACH MEMBER OR CONNECTION.
B. PERIODIC SPECIAL INSPECTION MEANS THAT THE SPECIAL INSPECTOR IN ON THE SITE AT THE TIME INTERVALS NECESSARY TO CONFIRM THAT ALL
WORK REQUIRING SPECIAL INSPECTIONS IN COMPLIANCE. OPERATIONS NEED NOT BE DELAYED PENDING THESE INSPECTIONS.
4. STRUCTURAL STEEL SPECIAL INSPECTIONS
A. QUALITY CONTROL (QC) SHALL BE PROVIDED BY THE FABRICATOR AND ERECTOR.
B. QUALITY ASSURANCE (QA) SHALL BE PROVIDED BY THE TESTING AGENCY.
C. "O" INDICATES OBSERVATIONS TO BE PERFORMED ON A RANDOM BASIS. OPERATIONS NEED NOT BE DELAYED PENDING THESE INSPECTIONS.
D. "P" INDICATES TASKS TO BE PERFORMED FOR EACH WELDED JOINT OR MEMBER.
5. ALL WELDS SHALL BE VISUALLY INSPECTED BY AN AWS CERTIFIED WELDING INSPECTOR. ALL PROVISIONS OF AWS D1.1/D1.1M "STRUCTURAL WELDING CODE- STEEL" SHALL APPLY TO STEEL CONSTRUCTION. NON-DESTRUCTIVE TESTING OF WELD JOINTS SHALL BE IN ACCORDANCE WITH AISC 360-16
SECTION N5.
A. WELDS CLEANED
B. SIZE, LENGTH AND LOCATION OF WELDS
C. WELDS MEET VISUAL ACCEPTANCE CRITERIA
• CRACK PROHIBITION
• WELD/BASE-METAL FUSION
• CRATER CROSS SECTION
• WELD PROFILES
• WELD SIZE
• UNDERCUT
• POROSITY
D. ARC STRIKES
E. k-AREA
F. BACKING REMOVED AND WELD TABS REMOVED
(IF REQUIRED)
H. REPAIR ACTIVITIES
QC QA COMMENTS
7. AFTER WELDING
(IBC SECTION 1705.5.2.1)
I. DOCUMENT ACCEPTANCE OR REJECTION OF
WELDED JOINT OR MEMBER
J. NO PROHIBITED WELDS HAVE BEEN ADDED
WITHOUT THE APPROVAL OF THE EOR
AFTER ROLLED HEAVY SHAPES
AND BUILT-UP HEAVY SHAPES ARE
WELDED, VISUALLY INSPECT THE
WELD ACCESS HOLE FOR CRACKS.
OO
P P
PP
P P
PP
PP
P P
PP
OO
STRUCTURAL STEEL
SPECIAL INSPECTION OR TEST QC QA COMMENTS
1. FABRICATION
3. ANCHOR RODS AND
OTHER EMBEDMENTS
SUPPORTING
STRUCTURAL STEEL
A. FABRICATED STEEL TO COMPLY WITH DETAILS
ON THE SHOP DRAWINGS
C. CORRECT APPLICATION OF SHOP JOINT DETAILS
AT EACH CONNECTION
P
P
B. FABRICATED STEEL TO COMPLY WITH DETAILS
ON CONTRACT DOCUMENTS
P P
2. ERECTION A. ERECTED STEEL TO COMPLY WITH DETAILS ON
THE ERECTION DRAWINGS
B. ERECTED STEEL TO COMPLY WITH DETAILS ON
CONTRACT DOCUMENTS
C. BRACES
D. DOCUMENT ACCEPTANCE OR REJECTION OF
JOINT DETAILS P P
F. DOCUMENT ACCEPTANCE OR REJECTION OF
JOINT DETAILS
P
P
P P
D. STIFFENERS P P
E. MEMBER LOCATIONS P P
P P
B. VERIFY AND DOCUMENT EXTENT OR DEPTH OF
EMBEDMENT INTO CONCRETE PRIOR TO
PLACEMENT OF CONCRETE
A. DIAMETER, GRADE, TYPE AND LENGTH OF
ANCHOR ROD OR EMBEDDED ITEM P
P
4. GALVANIZED
STRUCTURAL STEEL
A. VISUALLY INSPECT EXPOSED CUT SURFACES OF
GALVANIZED STRUCTURAL STEEL MAIN MEMBERS
OR CORNERS OF RECTANGULAR HSS FOR
CRACKS AFTER GALVANIZATION
B. DOCUMENT REPAIR OF MEMBERS IN WHICH
CRACKS WERE FOUND
P
P
5. PRIOR TO WELDING A. WELDER QUALIFICATION RECORDS AND
CONTINUITY RECORDS
B. WPS AVAILABLE
C. MANUFACTURER CERTIFICATIONS FOR WELDING
CONSUMABLES AVAILABLE
D. MATERIAL IDENTIFICATION (TYPE/GRADE)
F. FIT-UP OF GROOVE WELDS (INCLUDING JOINT
GEOMETRY)
• JOINT PREPARATIONS
• DIMENSIONS (ALIGNMENT, ROOT OPENING,
ROOT FACE, BEVEL)
• CLEANLINESS (CONDITION OF STEEL
SURFACES)
• TACKING (TACK WELD QUALITY AND LOCATION)
• BACKING TYPE AND FIT (IF APPLICABLE)
H. CONFIGURATION AND FINISH OF ACCESS HOLES
G. FIT-UP OF CJP GROOVE WELDS OF HSS T-, Y-, AND
K- JOINTS WITHOUT BACKING (INCLUDING JOINT
GEOMETRY)
• JOINT PREPARATIONS
• DIMENSIONS (ALIGNMENT, ROOT OPENING,
ROOT FACE, BEVEL)
• CLEANLINESS (CONDITION OF STEEL
SURFACES)
• TACKING (TACK WELD QUALITY AND LOCATION)
I. FIT-UP OF FILLET WELDS
• DIMENSIONS (ALIGNMENT, GAPS AT ROOT)
• CLEANLINESS (CONDITION OF STEEL
SURFACES)
• TACKING (TACK WELD QUALITY AND LOCATION)
J. CHECK WELDING EQUIPMENT
E. WELDER IDENTIFICATION SYSTEM
P O
PP
OP
P O
OP
OO
O
O O
O
P P
O -
THE FABRICATOR OR ERECTOR, AS
APPLICABLE, SHALL MAINTAIN A
SYSTEM BY WHICH A WELDER WHO
HAS WELDED A JOINT OR MEMBER
CAN BE IDENTIFIED. STAMPS, IF
USED, SHALL BE THE LOW-STRESS
TYPE
(IBC SECTION 1705.5.2.1)
(AISC 360-16 CHAPTER N &
AISC 341-16 CHAPTER J)
STRUCTURAL STEEL CONTINUED
SPECIAL INSPECTION OR TEST
6. DURING WELDING A. CONTROL AND HANDLING OF WELDING
CONSUMABLES
• PACKAGING
• EXPOSURE CONTROL
B. NO WELDING OVER CRACKED TACK WELDS
C. ENVIRONMENTAL CONDITIONS
• WIND SPEED WITHIN LIMITS
• PRECIPITATION AND TEMPERATURE
D. WPS FOLLOWED
• SETTINGS ON WELDING EQUIPMENT
• TRAVEL SPEED
• SELECTED WELDING MATERIALS
• SHIELDING GAS TYPE/FLOW RATE
• PREHEAT APPLIED
• INTERPASS TEMPERATURE MAINTAINED
(MIN./MAX.)
• PROPER POSITION (F, V, H, OH)
• INTERMIX OF FILLER METALS AVOIDED UNLESS
APPROVED
OO
O O
O O
O O
G. PLACEMENT OF REINFORCING OR CONTOURING
OF FILLET WELDS (IF REQUIRED) PP
(AISC 360-16 CHAPTER N &
AISC 341-16 CHAPTER J)
F. PLACEMENT AND INSTALLATION OF STEEL
HEADED STUD ANCHORS
E. WELDING TECHNIQUES
• INTERPASS AND FINAL CLEANING
• EACH PASS WITHIN PROFILE LIMITATIONS
• EACH PASS MEETS QUALITY REQUIREMENTS
O O
PP
6. DURING WELDING
CONTINUED
CONCRETE
SPECIAL INSPECTION OR TEST CONTINUOUS PERIODIC COMMENTS
1. INSPECT REINFORCEMENT AND VERIFY PLACEMENT - X
(IBC SECTION 1705.3)
A. MANUFACTURER'S CERTIFICATIONS AVAILABLE
FOR FASTENER MATERIALS
B. FASTENERS MARKED IN ACCORDANCE WITH ASTM
REQUIREMENTS
C. CORRECT FASTENERS SELECTED FOR THE JOINT
DETAIL (GRADE, TYPE, BOLT LENGTH IF THREADS
ARE TO BE EXCLUDED FROM SHEAR PLANE)
D. CORRECT BOLTING PROCEDURE SELECTED FOR
JOINT DETAIL
E. CONNECTING ELEMENTS, INCLUDING THE
APPROPRIATE FAYING SURFACE CONDITION AND
HOLE PREPARATION, IF SPECIFIED, MEET
APPLICABLE REQUIREMENTS
F. PRE-INSTALLATION VERIFICATION TESTING BY
INSTALLATION PERSONNEL OBSERVED AND
DOCUMENTED FOR FASTENER ASSEMBLIES AND
METHODS USED
G. PROTECTED STORAGE PROVIDED FOR BOLTS,
NUTS, WASHERS AND OTHER FASTENER
COMPONENTS
A. FASTENER ASSEMBLIES PLACED IN ALL HOLES
AND WASHERS AND NUTS ARE POSITIONED AS
REQUIRED
B. JOINT BROUGHT TO THE SNUG-TIGHT CONDITION
PRIOR TO THE PRETENSIONING OPERATION
C. FASTENER COMPONENT NOT TURNED BY THE
WRENCH PREVENTED FROM ROTATING
D. FASTENERS ARE PRETENSIONED IN
ACCORDANCE WITH THE RCSC SPECIFICATION,
PROGRESSING SYSTEMATICALLY FROM THE
MOST RIGID POINT TOWARD THE FREE EDGES
8. PRIOR TO BOLTING
9. DURING BOLTING
10. AFTER BOLTING A. DOCUMENT ACCEPTANCE OR REJECTION OF
BOLTED CONNECTIONS PP
O O
OO
OO
O O
PO
OO
O O
OO
O O
O O
P O
3. INSPECT ANCHORS
POST-INSTALLED IN
HARDENED
CONCRETE MEMBERS
2. INSPECT ANCHORS CAST IN CONCRETE
X -
- X
- X
A. ADHESIVE ANCHORS INSTALLED IN
HORIZONTALLY OR UPWARDLY INCLINED
ORIENTATIONS TO RESIST SUSTAINED TENSION
LOADS
B. MECHANICAL ANCHORS AND ADHESIVE ANCHORS
NOT DEFINED ABOVE
4. VERIFY USE OF REQUIRED DESIGN MIX - X
5. PRIOR TO CONCRETE PLACEMENT, FABRICATE SPECIMENS FOR STRENGTH
TESTS, PERFORM SLUMP AND AIR CONTENT TESTS, AND DETERMINE THE
TEMPERATURE OF THE CONCRETE
X -
6. INSPECT CONCRETE PLACEMENT FOR PROPER APPLICATION TECHNIQUES X -
7. VERIFY MAINTENANCE OF SPECIFIED CURING TEMPERATURES AND
TECHNIQUES - X
8. INSPECT FORMWORK FOR SHAPE, LOCATION AND DIMENSIONS OF THE
CONCRETE MEMBER BEING FORMED - X
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s /0
V
A T o g u s B o ile r S ta c k P a d
R e p a ir /0
V A
T o g u s B o ile r R e p a ir
R
S
.r v t
/1
/2
:4
:2
P
M
SG002
STATEMENT OF SPECIAL
INSPECTIONS
VA TOGUS BOILER STACK
PAD REPAIR
AUGUSTA, ME
402-21-724
12/16/2022 NPC RAS
CONSTRUCTION DOCUMENT
SUBMISSION
BUILDING 238
B U
IL
D
IN
G
STEEL
STAIR (E)
CONCRETE
STAIR (E)
STEEL STAIR (E)
14' - 10"
3' - 6"
8'
0"
6'
PROPANE TANK
PLATFORM (E)
CHILLED WATER
SUPPLY AND RETURN
DOGHOUSE (E)
EXISTING
75,000 GAL
OIL TANK
3' - 7" 2' - 6" 6' - 7 1/2" 6' - 3"
3'
3'
W 8X
E
HSS4X4X1/4 (E)
2.
4'
3/ 4"
5'-0" ORIGINAL PILE CAP +
2'-0" BOILER STACK PAD WITH TURN DOWN
OVERHEAD
DUCT SUPPORT
HSS8X8X1/4
OVERHEAD
DUCT SUPPORT
STEAM SILENCER SUPPORT
TRUSSED TOWER
5'-0" DIA. BOILER STACK (E)
(36) #6 DOWELS
HSS4X4X1/4 (E)
4' - 8 1/2"
4'
5' - 6" 6" 3' - 5"
1'
- 5
1'
- 9
1' - 6 1/2"
1' - 8 1/4"
6 1/4"
12' - 2"
1' - 4 3/4" TYP.
8' - 0"
1' - 2 1/4"
7' - 10" 2" TYP. 11' - 0" TYP.
2' - 6" TYP.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s /0
V
A T o g u s B o ile r S ta c k P a d
R e p a ir /0
V A
T o g u s B o ile r R e p a ir
R
S
.r v t
/1
/2
:4
:2
P
M
SS101
SITE PLAN VA TOGUS BOILER STACK
PAD REPAIR
AUGUSTA, ME
402-21-724
12/16/2022 NPC RAS
CONSTRUCTION DOCUMENT
SUBMISSION
DRAWING NOTES:
1. TOP OF EXISTING PAD IS APPROXIMATELY 4'-9" ABOVE GROUND SURFACE, WHICH VARIES.
CONTRACTOR TO FIELD VERIFY ELEVATIONS DURING CONSTRUCTION.
2. ALL DIMENSIONS SHOWN ARE EXISTING.
N
0 2' 4' 8' 12'
1/4" = 1'-0"
1/4" = 1'-0"1
SITE PLAN
U
IL
D
IN
G
STEEL
STAIR (E)
CONCRETE
STAIR (E)
PROPANE TANK
PLATFORM (E)
CHILLED WATER
SUPPLY AND RETURN
DOGHOUSE (E)
EXISTING
75,000 GAL
OIL TANK
SE301
SE301
SE302
BUILDING 238
B U
IL
D
IN
G
STEEL
STAIR (E)
CONCRETE
STAIR (E)
PROPANE TANK
PLATFORM (E)
CHILLED WATER
SUPPLY AND RETURN
DOGHOUSE (E)
EXISTING
75,000 GAL
OIL TANK
STEEL STAIR (E)
H S
S
X
X 1/
HSS12X12X1/2
.2
.2
4'
4'
6'
SD1012
SD101
HSS12X12X1/2
3' - 9"
3'
2'1'
CENTER OF STACK
CENTER OF STACK
HSS12X12X1/2
HSS12X12X1/2
HSS12X12X1/2HSS12X12X1/2
HSS12X12X1/2
( 16.25 )( 13.25 )
B'
A'
HSS12X12X1/2
( 16.25 )( 13.25 )
4' - 6"
( 16.25 )( 13.25 )
SE302
Top of Pile Cap 4' - 9"
Bottom of Shoring 12' - 3"
Top of Shoring 16' - 3"
HSS12X12X1/2 HSS12X12X1/2
HSS12X12X1/2HSS12X12X1/2
CENTER OF STACK
4' - 0" 4' - 0" 6' - 2"
HSS12X12X1/2
SE301
TYP.
SE302
SE302
TYP.
B' A'
H S
S
X
X 1/
H S
S
X
X 1/
Top of Pile Cap 4' - 9"
Bottom of Shoring 12' - 3"
Top of Shoring 16' - 3"
CENTER OF STACK
SE301
TYP.
2'1'
SE302
TYP.
HSS12X12X1/2
HSS12X12X1/2
H S
S
X
X 1/
H S
S
X
X 1/
4' - 6"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s /0
V
A T o g u s B o ile r S ta c k P a d
R e p a ir /0
V A
T o g u s B o ile r R e p a ir
R
S
.r v t
/1
/2
:4
:2
P
M
SD101
DEMOLITION AND TEMPORARY
SHORING PLAN
VA TOGUS BOILER STACK
PAD REPAIR
AUGUSTA, ME
402-21-724
12/16/2022 NPC RAS
CONSTRUCTION DOCUMENT
SUBMISSION
CODED NOTES:
DRAWING NOTES:
1. TOP OF EXISTING PAD IS APPROXIMATELY 4'-9" ABOVE GROUND SURFACE, WHICH VARIES.
CONTRACTOR TO FIELD VERIFY ELEVATIONS DURING CONSTRUCTION.
2. TOP OF STEEL NOTED ON PLANS MEASURED FROM ABOVE GROUND SURFACE (0.00').
3. DENOTES FULL PENETRATION WELDED CONNECTIONS, FIELD WELD AS NEEDED.
REMOVE TOP 2'-0" OF CONCRETE PAD AND TURN DOWN SLAB TO SOUND CONCRETE ~4'-2" FROM EDGE
(21 CY). IF CRACK CONTINUES PAST 4'-2", NOTIFY COR.
CONCRETE TO BE REMOVED IN SUCH A MANNER AS TO PRESERVE EXISTING STEEL REBAR IN THE SLAB, SUCH AS HYDRODEMOLITION OR SIMILAR METHOD. CONTRACTOR TO NOTE THAT THE REBAR IN THE SLAB IS MUCH MORE THAN SHOWN ON THE REPAIR SKETCHES OF #6 AT 12" O.C. AND ALL REBAR
SHALL BE PRESERVED.
ANY REBAR CUT DURING CORING IS TO BE REPAIRED BY SPLICING ON REBAR TO THE ORIGINAL LENGTH WITH MECHANICAL SPLICE CONNECTORS. PROVIDE COR WITH REPORT SHOWING LOCATIONS
OF SPLICED REBAR.
N
0 2' 4' 8' 12'
1/4" = 1'-0"
1/4" = 1'-0"1
DEMOLITION PLAN
1/4" = 1'-0"4
TEMPORARY SHORING PLAN
1/4" = 1'-0"2
MOMENT FRAME ELEVATION - EAST
1/4" = 1'-0"
MOMENT FRAME ELEVATION - SOUTH
AFTER TEMPORARY SHORING IS IN PLACE, CUT EXISTING COLUMNS 8" BELOW BOTTOM OF SHORING.
REMOVE GROUT PAD BELOW COLUMNS AND CUT OFF EXISTING ANCHOR BOLTS FLUSH WITH TOP OF
CONCRETE. REMOVE STEEL COLUMNS AND BASE PLATES AS A UNIT WITH CROSS BRACING TO
REMAIN FOR REINSTALLATION.
AFTER REMOVING DUCT, REMOVE POST AND SUPPORTING BEAM.
5 REMOVE EXISTING DUCT ABANDONED IN PLACE UP TO BOILER STACK LOWER INLET DUCT.
4 REMOVE STEEL STAIR FOR REINSTALLATION.
REMOVE VERTICAL COMPONENT OF EXISTING DUCT OPENING STEEL CHANNEL FRAME.7
1" THICK BASE PLATES WITH (4) 1" DIA. HILTI HAS-V-36 THREADED RODS INTO EXISTING CONCRETE WITH HILTI HY-200 ADHESIVE (9" MINIMUM EMBEDMENT). BASE PLATES TO BE SHIPPED LOOSE FROM STEEL POSTS. LOCATION OF ANCHOR BOLTS TO BE VERIFIED BY GPR SCANNING ON PILE CAP PRIOR
TO DRILLING. IF REBAR INTERFERES WITH PROPOSED LOCATION OF ANCHOR BOLTS, THE
CONTRACTOR IS TO NOTIFY THE COR FOR DIRECTION. STRUCTURAL STEEL SHALL NOT BE
FABRICATED UNTIL LOCATION OF THE ANCHOR BOLTS ON SITE HAS BEEN VERIFIED.
(4) 3/4" THICK TOP & BOTTOM COLLAR PLATES, WELDED TO EXISTING TUBES AND TOP AND BOTTOM OF SUPPORTING HSS BEAMS. PLATES TO BE FIELD CUT AND FIELD WELDED WITH FULL PENETRATION
WELDS.
REMOVE TOP ~1'-3" OF CONCRETE PILE CAP TO SOUND CONCRETE ~1'-0" FROM EDGE (5 CY). IF CRACK CONTINUES PAST 1'-0" INTO EXISTING PILE CAP, NOTIFY COR. CONCRETE TO BE REMOVED IN SUCH A MANNER AS TO PRESERVE EXISTING STEEL REBAR IN THE SLAB, SUCH AS HYDRODEMOLITION OR SIMILAR METHOD. IF EXISTING STANDEES/CHAIRS FOR REBAR DOES NOT EXIST, CONTRACTOR SHALL
PROVIDE AS REQUIRED TO KEEP REBAR IN POSITION.
U
IL
D
IN
G
STEEL
STAIR (E)
CONCRETE
STAIR (E)
PROPANE TANK
PLATFORM (E)
CHILLED WATER
SUPPLY AND RETURN
DOGHOUSE (E)
EXISTING
75,000 GAL
OIL TANK
SE301
SE301
2'
7 3/4"
7 3/4"
SE302
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s /0
V
A T o g u s B o ile r S ta c k P a d
R e p a ir /0
V A
T o g u s B o ile r R e p a ir
R
S
.r v t
/1
/2
:4
:2
P
M
SB101
STRUCTURAL NEW WORK PLAN VA TOGUS BOILER STACK
PAD REPAIR
AUGUSTA, ME
402-21-724
12/16/2022 NPC RAS
CONSTRUCTION DOCUMENT
SUBMISSION
CODED NOTES:
DRAWING NOTES:
1. TOP OF EXISTING PAD IS APPROXIMATELY 4'-9" ABOVE GROUND SURFACE, WHICH VARIES.
CONTRACTOR TO FIELD VERIFY ELEVATIONS DURING CONSTRUCTION.
ADD CONCRETE PAD AND TURN DOWN SLAB TO REPLACE CONCRETE REMOVED (26 CY). COAT
ENTIRE CONCRETE PAD WITH WATERPROOF CONCRETE SEALANT. SEALANT TO BE SIKAGARD 706
THIXO OR APPROVED EQUAL. PROVIDE REINFORCING DOWELS PER SECTION CUT ON PLAN.
REINSTALL EXISTING HSS TUBES.
• WHERE BASE PLATE TO BE REINSTALLED INTO EXISTING CONCRETE, CUT OFF EXISTING BASE
PLATE AND WELD ON 12"x18"x3/4" PLATE. LOCATION OF ANCHOR BOLTS TO BE VERIFIED BY GPR SCANNING ON PILE CAP PRIOR TO DRILLING. IF REBAR INTERFERES WITH PROPOSED LOCATION OF ANCHOR BOLTS, THE CONTRACTOR IS TO NOTIFY THE COR FOR DIRECTION. (ESTIMATE (4)
LOCATIONS)
• CJP WELDED TO TUBE ABOVE.
• ANCHOR BASE PLATE TO NEW OR EXISTING CONCRETE (3) 1/2" DIA. AND (1) 3/4" DIA. HILTI
HAS-E-55 THREADED RODS (TO MATCH EXISTING) WITH HILTI HY-200 ADHESIVE (14" EMBEDMENT
AND 20" EMBEDMENT, RESPECTIVELY).
• GROUT BELOW BASEPLATE WITH QUIKRETE FASTSET NON-SHRINK GROUT OR EQUIVALENT,
ALLOW TO SET PER MANUFACTURER'S RECOMMENDATIONS TO f'c=3000 PSI MIN.
• REMOVE SHORING BY CUTTING OFF PLATES WELDED TO EXISTING TUBE AND GRIND SMOOTH.
PAINT REPAIR AREA WITH PAINT TO MATCH EXISTING.
1'-0" WIDE x 1'-0" THICK CONCRETE SLAB FOR STAIR POST SUPPORT.3
HSS2"x2"x1/4"x1'-0" LONG WELDED TO EXISTING STAIR POSTS.4
REINSTALL EXISTING STAIR. EMBED POSTS 6" INTO WET CONCRETE.5
CAP OFF DUCT OPENING AT MAIN TRUNK OF BOILER STACK INLET WITH INSULATION AND SHEET
METAL TO MATCH EXISTING.
INFILL EXISTING WALL PENETRATION WITH 4" CMU AND 4" BRICK TO MATCH EXISTING.
N
0 2' 4' 8' 12'
1/4" = 1'-0"
1/4" = 1'-0"1
STRUCTURAL NEW WORK PLAN
DEMOLITION
3'
1'
2'
THEORETICAL LOCATION OF CRACK
IF CRACK CONTINUES PAST
VERTICAL DOWEL, NOTIFY COR
EXISTING #6 DOWEL AT 8'-0" FROM
CENTER OF STACK
ORIGINAL PILE CAP
TURNED DOWN SLAB
OF CONCRETE PAD
ADDED CONCRETE PAD
FOUNDATION PILE
3' - 0"
EXISTING
EXISTING #6 AT 12" O.C. EACH WAY TOP &
BOTTOM (ADDITIONAL REBAR OBSERVED
ON SITE AT CLOSER SPACING ~4" O.C.)
EXISTING #6 AT 12" O.C. EACH WAY TOP &
BOTTOM (ADDITIONAL REBAR OBSERVED
ON SITE AT CLOSER SPACING ~4" O.C.)2"
C
LE
A R
, T Y
P
2' - 6"
THEORETICAL LOCATION OF CRACK
IF CRACK CONTINUES BEYOND 1'-0"
INTO EXISTING PILE CAP, NOTIFY COR
APPROXIMATE 2" THICK EXTERIOR CONCRETE
COATING ON EXISTING PILE CAP
A P
P R
O X
IM
A
T E
1'
V A
R
IE
S
EXISTING PAVEMENT
REFER TO 1/SD101 CODED NOTES
APPROXIMATE EXTENT OF REMOVAL 4' - 2"
1' - 6" 1' - 2"
A P
P R
O X
IM
A
T E
V A
R
IE
S
2'
/4
A P
P R
O X
IM
A
T E
1'
1/ 4"
V A
R
IE
S
REMOVE PORTION OF EXISTING
CONCRETE PAD AND PILE CAP
COATING
REMOVE PORTION OF EXISTING PILE
CAP
REPAIR
1' - 6" 1' - 0"
A P
P R
O X
IM
A
T E
V A
R
IE
S
2'
/4
A P
P R
O X
IM
A
T E
1'
1/ 4"
V A
R
IE
S
EXISTING REINFORCING TO BE PRESERVED
DURING DEMOLITION
EXISTING ADDED CONCRETE PAD
TO REMAIN, REFER TO PLAN
APPROXIMATE EXTENT OF REPAIR 4' - 0"
ROUGHEN CONCRETE SURFACE
TO 1/4" AMPLITUDE
NEW CONCRETE
#4 AT 12" O.C. DOWELED INTO
ORIGINAL PILE CAP WITH HILTI HIT
HY-200 ADHESIVE OR EQUIVALENT
1'
4" CLEAR
#4 AT 12" O.C. DOWELED INTO
ORIGINAL PILE CAP WITH HILTI HIT
HY-200 ADHESIVE OR EQUIVALENT
2'-4"
3' -7
2'-4"
5' -6
0"
4" CLEAR
EXISTING PAVEMENT EXISTING PAVEMENT
/1 SD101
THEORETICAL LOCATION OF CRACK
FOLLOWING EXISTING PILE CAP
CHAMFER
STANDARD LADDER TYPE
JOINT REINFORCEMENT AT
EACH JOINT
4" BRICK TO MATCH EXISTING
TOOTHED INTO EXISTING AT
EDGE OF OPENING
EXISTING CHANNEL
FRAME HEADER
4" SOLID CMU TO MATCH
EXISTING TOOTHED INTO
EXISTING AT EDGE OF OPENING
EXISTING CHANNEL FRAME
SILL
REMOVE VERTICAL
COMPONENT OF EXISTING
CHANNEL FRAME AT EACH
EDGE
(8) 1" DIA. HILTI HAS THREADED RODS WITH
3"x3"x3/8" PLATE WASHERS AND HEAVY HEX
NUTS EMBEDDED INTO EXISTING
CONCRETE PAD WITH HILTI HIT HY-200
ADHESIVE (9" MIN. EMBEDMENT)
PORTION OF EXISTING ADDED
CONCRETE PAD TO BE REMOVED
EXISTING REINFORCING TO BE PRESERVED
DURING DEMOLITION
EXISTING ADDED CONCRETE PAD
TO REMAIN
STEEL POST, REFER TO PLAN
1" THICK STEEL BASE PLATE, PER
LAYOUT BELOW
2" 7 1/2" 7 1/2" 2"
CL
CL 1'
5/16"
1'
2"
1/ 2"
1/
2" 2"
1/4"
TYPICAL
1' - 7"
CL 2'
5/16"
1'
- 7
1/4"
TYPICAL
1' - 7"
1/
2" 2"
1/
2"
5 1/2" 2" 7 1/2"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s /0
V
A T o g u s B o ile r S ta c k P a d
R e p a ir /0
V A
T o g u s B o ile r R e p a ir
R
S
.r v t
/1
/2
:4
:3
P
M
SE301
CONCRETE AND MASONRY
DETAILS AND SECTIONS
VA TOGUS BOILER STACK
PAD REPAIR
AUGUSTA, ME
402-21-724
12/16/2022 NPC RAS
CONSTRUCTION DOCUMENT
SUBMISSION
1" = 1'-0"
SECTION
1" = 1'-0"
SECTION
1" = 1'-0"
SECTION
DEMOLITIONTEMPORARY
4'
8"
TOP OF SHORING
11.50'
BOTTOM OF SHORING
7.50'
EXISTING STEEL
TRUSSED TOWER
POSTS, TYP. OF 4
FIELD CUT EXISTING STEEL
POSTS AFTER ALL PLATES
ARE INSTALLED AND WELDS
COMPLETED
SALVAGE EXISTING STEEL
TRUSSED TOWER AS ONE PIECE
WITH ALL BRACING IN TACT AND
BASEPLATES ATTACHED
EXISTING PIPING TO BE
PRESERVED IN PLACE AND
PROTECTED DURING
CONSTRUCTION
EXISTING STEEL ANGLE
BETWEEN EXISTING STEEL
POSTS TO REMAIN
FINAL
STEEL BEAM,
REFER TO PLAN
STEEL BEAM,
REFER TO PLAN
3/16"
TYP.
3/16"
TYP.
3/16"
TYP.
AS NEEDED
TYP.
STEEL PLATE,
REFER TO PLAN, TYP. OF 4
MAY BE CUT IN FIELD AND WELDED
BACK TOGETHER AS NEEDED
FIELD CUT EXISTING STEEL 2"x1/4"
THICK PLATE BRACES AS
REQUIRED TO PERMIT
TEMPORARY STEEL INSTALLATION
1' - 10 1/2" 1' - 10 1/2"
3' - 9"
REINSTALL EXISTING STEEL
TRUSSED TOWER
REPLACE 2"x1/4" THICK PLATE
BRACES IN THE SAME LOCATIONS
AS PREVIOUSLY REMOVED
3/16"
I.F. OF POST
TYP.
3/16"
TYP.
2'
STEEL BEAM,
REFER TO PLAN, TYP.
STEEL COLUMN,
REFER TO PLAN
TOP OF SHORING
11.50'
BOTTOM OF SHORING
7.50'
4'
12"x12"x1/4" CAP PLATE
CL
3/16"
TYP.
TYP.
TOP OF SHORING
11.50'
BOTTOM OF SHORING
7.50'
2'
STEEL BEAM,
REFER TO PLAN
5/16"
N.S. & F.S.
TYP.
STEEL POST,
REFER TO PLAN
STEEL BEAM,
REFER TO PLAN
3/16"
TYP.
3/16"
TYP.
4'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
A u to d e s k D o c s /0
V
A T o g u s B o ile r S ta c k P a d
R e p a ir /0
V A
T o g u s B o ile r R e p a ir
R
S
.r v t
/1
/2
:4
:3
P
M
SE302
STEEL DETAILS AND SECTIONS VA TOGUS BOILER STACK
PAD REPAIR
AUGUSTA, ME
402-21-724
12/16/2022 NPC RAS
CONSTRUCTION DOCUMENT
SUBMISSION
1" = 1'-0"1
SECTION
N.T.S.
HSS MOMENT FRAME CONNECTION DETAIL
21" = 1'-0"3
SECTION