This document outlines a federal contract opportunity for repair work at a Corrosion Control Facility. The solicitation calls for contractors to reconfigure approximately 2,500 square feet of space including a bath/locker room and shop area for a project magnitude between $500,000 to $1,000,000. The scope of work involves providing all necessary material, equipment, labor and supervision to complete a fully functional and usable space. Contractors must designate a dedicated superintendent through project completion. The award will be a stand-alone contract not a task order. The selected contractor must submit a critical path schedule within five days of award and all personnel accessing the military base where the work is located will require background checks.
View the file
Other files for this federal contract opportunity
Show all 28
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SPIEZLE ARCHITECTURAL GROUP, INC.SPIEZLE ARCHITECTURAL GROUP, INC.
COVER SHEET
AND DRAWING INDEX
GI001
DRTH
APPLICABLE CODES (NJ)
1. NJ UNIFORM CONSTRUCTION CODE NJAC 5:23
2. INTERNATIONAL BUILDING CODE, 2015, NEW JERSEY EDITION
3. NATIONAL STANDARD PLUMBING CODE, 2015
4. NATIONAL ELECTRICAL CODE (NFPA 70), 2014
5. ENERGY SUBCODE, ASHRAE 90.1-2013
6. INTERNATIONAL MECHANICAL CODE, 2015
7. INTERNATIONAL FUEL GAS CODE, 2015
8. REHABILITATION SUBCODE, NJAC 5:23-6
9. BARRIER FREE SUBCODE, CHAPTER 11 OF IBC/2015 &
NJAC 5:23-7 & ICC/ANSI A117.1-2009.
FIRE EXTINGUISHER CABINETS
LEGEND
W
S
B
FIRE BARRIER
(U.L. #U905 OR #U906)
FIRE WALL (U.L. #U905)
SMOKE PARTITION
(NO RATING)
2 HOUR FIRE RATING
FEC
MAXIMUM PATH OF EGRESS
TEMPORARY EGRESS
ACUTAL EGRESS LOAD
EGRESS CAPACITY
MAXIMUM OCCUPANT LOAD AS SHOWN IS USED FOR EGRESS CALCULATIONS
ONLY.
EGRESS CAPACITY IS BASED ON CLEAR WIDTH OF DOORS MINUS 3" FOR
SINGLE DOOR, 6" FOR DOUBLE DOOR.
NEW JERSEY INTERNATIONAL BUILDING CODE (2015)
MIXED USE GROUP CLASSIFICATION H2 / B
CONSTRUCTION TYPE FOR REVIEW IIB, (FULLY SPRINKLERED)
ACTUAL BUILDING HEIGHT 55'-8"
BUILDING/AREA DESIGNATION
ACTUAL NUMBER OF STORIES 1
BUILDING AREA FOR REVIEW ±3,240 SF
ACTUAL BUILDING AREA 29,340 SF
MAXIMUM TRAVEL DISTANCE (SP) 300 FT
VOLUME OF WORK FOR REVIEW 150,000 FT3
OCC:
249 SF
WOMEN'S
LOCKER
ROOM
OCC:
450 SF
MEN'S
LOCKER
ROOM
102 SF
CORRIDOR
194 SF
CORRIDOR
OCC:
33 SF
CHANGING
ROOM
OCC:
88 SF
TOILET /
SHOWER
EXISTING
PAINT ROOM
EXISTING AIRPLANE HANGAR
USE GROUP H2
EXISTING OFFICE AREA
USE GROUP B
EXISTING 2 HR FIRE BARRIER SEPARATING USES
EXISTING 2 HR FIRE BARRIER SEPARATING USES
MAXIMUM
175'-0" TRAVEL DISTANCE
EXISTING EXIT
NOT AN EXIT
ACCESS PLATFORM ABOVE
(MAINTENANCE USE ONLY)
2 HR FIRE BARRIER SEPARATING USES
FE
FLOOR
REFER TO FLOOR
PLANS AND
PARTITION TYPES
FOR ADDITIONAL
INFORMATION
FRAMED
HEADER
FIRE EXTINGUISHER
CABINET
(SEMI-RECESSED
SHOWN)
(2) LAYERS OF
TYPE 'X' GYPSUM
BOARD WHERE
REQUIRED FOR
RATED WALL
CONSTRUCTION
FRAMED WALLS
A Se rv ic e D i s a b le d Ve t e r an Owned
S m a l l B u s iness
SDVOSB
CVE
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
CONSULTANTS:
o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
1 2 3 4 5 6 87 9
97 8654321
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0700-0008
B
A
C
D
E
F
NO. DESCRIPTION DATE
PLAN
NORTH
ACTUAL
NORTH
Phone 609.695.7400
HAMILTON, N.J. 08691
1395 YARDVILLE HAMILTON SQUARE ROAD
Architecture Planning Design
SPIEZLE ARCHITECTURAL GROUP, INC.
Architecture Planning Design
Fax 609.394.2274
SPIEZLE ARCHITECTURAL GROUP, INC.
NOT FOR CONSTRUCTION - FULLY SPRINKLERED
B3 SUBMISSION
REPAIR CORROSION
CONTROL FACILITY BLDG.
JOINT BASE
McGUIRE-DIX-LAKEHURST AFB, NJ
PTFL132039
12-05-2019
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE PROFESSIONAL
ENGINEER. CODE PLAN
CP-1
1/8" = 1'-0"1
CODE PLAN
1" = 1'-0"
FIRE EXSTINGUISHER DETAIL
GENERAL DEMOLITION NOTES
1. DEMOLITION WORK INCLUDES, BUT IS NOT LIMITED TO THE WORK INDICATED
HEREWITH, AS COORDINATED WITH WORK OF ALL OTHER TRADES. AS
INDICATED ELSEWHERE, AND AS REQUIRED TO ACCOMODATE CONSTRUCTION.
ALL DEMOLITION REQUIRED SHALL BE INCLUDED IN EACH CONTRACTOR'S
BASE BID TO PERFORM AND COMPLETE CONSTRUCTION, UNLESS OTHERWISE
INDICATED. REFER TO ASBESTOS ABATEMENT REPORT AS WELL AS
MECHANICAL, ELECTRICAL AND PLUMBING DRAWINGS FOR ADDITIONAL
INFORMATION.
2. ITEMS TO BE RELOCATED OR REINSTALLED SHALL BE AS INDICATED. SPECIAL
CARE SHALL BE TAKEN SO AS NOT TO DAMAGE THESE ITEMS. THE
CONTRACTOR SHALL COORDINATE THE STORAGE OF ALL SALVAGED ITEMS TO
BE EITHER RELOCATED OR REINSTALLED WITH THE OWNER.
3. LOCATIONS AND/OR ELEVATIONS OF EXISTING ITEMS AS SHOWN ON THE
DRAWINGS ARE APPROXIMATE. RESPECTIVE TRADES SHALL FIELD VERIFY ALL
LOCATIONS.
4. WHEN A NEW WALL, CEILING, ROOF OR FLOOR ASSEMBLY IS INDICATED
WHERE AN EXISTING WALL, CEILING, ROOF OR FLOOR ASSEMBLY EXISTS, THE
EXISTING SHALL BE COMPLETELY REMOVED, WITH ASSOCIATED UTILITIES
REMOVED AND CAPPED BEHIND THE SURFACES TO REMAIN. ALL
DEPRESSIONS, INDENTATIONS, OR PROTRUSIONS LEFT AFTER THE REMOVAL
OF ITEMS WHICH MAY INTERFERE WITH THE CONSTRUCTION SHALL BE
REPAIRED, REPLACED OR REMOVED TO PROVIDE A SMOOTH TRANSITION
BETWEEN NEW AND EXISTING SURFACES.
5. CONTRACTORS SHALL VERIFY ALL CONDITIONS PRIOR TO COMMENCING
DEMOLITION. SHOULD QUESTIONS OR DISCREPENCIES ARISE, THE
CONTRACTOR SHALL NOTIFY THE ARCHITECT, IN WRITING, PRIOR TO
PROCEEDING WITH DEMOLITION.
6. WHERE OPENINGS ARE INDICATED TO BE MADE IN EXISTING MASONRY WALLS,
OR EXISTING OPENINGS ARE TO BE INFILLED, THE CONTRACTOR SHALL TOOTH
IN NEW MASONRY CONSTRUCTION TO MATCH ADJACENT COURSING.
7. CONTRACTOR(S) ARE RESPONSIBLE FOR SHORING, BRACING AND
UNDERPINNING RELATED TO THE DEMOLITION, REMOVAL OR CUTTING OF ANY
WALL, PARTITION, OR ANY OTHER LOAD-BEARING OR STRUCTURAL ELEMENT.
D7
V
IF
'-0
EXISTING
PAINT ROOM
D7
CLEAN EXISTING EPOXY FLOOR AND PREP TO RECEIVE NEW EPOXY FLOORING.
SEE FINISH PLAN FOR AREA OF PREP WORK.
EXISTING
EQUIPMENT
REMOVE AND REPLACE EXISTING FLOORING
AS NEEDED TO ACCOMMODATE TRENCHING
FOR UNDERSLAB PIPING
A Se rv ic e D i s a b le d Ve t e r an Owned
S m a l l B u s iness
SDVOSB
CVE
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
CONSULTANTS:
o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
1 2 3 4 5 6 87 9
97 8654321
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0700-0008
B
A
C
D
E
F
NO. DESCRIPTION DATE
PLAN
NORTH
ACTUAL
NORTH
Phone 609.695.7400
HAMILTON, N.J. 08691
1395 YARDVILLE HAMILTON SQUARE ROAD
Architecture Planning Design
SPIEZLE ARCHITECTURAL GROUP, INC.
Architecture Planning Design
Fax 609.394.2274
SPIEZLE ARCHITECTURAL GROUP, INC.
NOT FOR CONSTRUCTION - FULLY SPRINKLERED
B3 SUBMISSION
REPAIR CORROSION
CONTROL FACILITY BLDG.
JOINT BASE
McGUIRE-DIX-LAKEHURST AFB, NJ
PTFL132039
12-05-2019
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE PROFESSIONAL
ENGINEER. DEMOLITION PLAN
AD101
D - DEMO KEYNOTE LEGEND
Key Value Keynote Text
D7 REMOVE EXISTING DOOR, FRAME AND HARDWARE IN ITS
ENTIRETY. PATCH AND REPAIR ADJACENT WALLS, FLOORS AND
CEILINGS AS REQUIRED. PREPARE SURFACES FOR PROPOSED
INSTALLATION.
1/8" = 1'-0"1
DEMOLITION FLOOR PLAN
GENERAL NOTES
1. ELEVATION AT TOP OF FINISHED FLOOR SLAB SHALL BE REFERENCED AS
DATUM ELEVATION 0'-0".
2. DO NOT SCALE THE DRAWINGS. IF A DIMENSION IS UNCLEAR OR A
DISCREPENCY IS FOUND IT SHALL BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT.
3. ALL DIMENSIONS SHALL BE FIELD VERIFIED PRIOR TO THE COMMENCEMENT
OF WORK. WHERE FABRICATION IS REQUIRED, DIMENSIONS SHALL BE
VERIFIED PRIOR TO THE PRODUCTION OF SHOP DRAWINGS.
4. CONTRACTOR SHALL COMPLY WITH ALL APPLICABLE CODES, STATUTES, AND
REGULATIONS IN PERFORMANCE OF THE WORK.
5. REFER TO THE FIRE RESISTANCE DIRECTORY (LATEST EDITION) BY
UNDERWRITER'S LABORATORIES FOR THE REQUIREMENTS OF ALL SPECIFIED
FIRE RATED ASSEMBLIES.
6. DETAILS AND SECTIONS ON THE DRAWINGS ARE SHOWN AT SPECIFIC
LOCATIONS AND ARE INTENDED TO SHOW GENERAL REQUIREMENTS
THROUGHOUT. CONDITIONS NOT SPECIFICALLY SHOWN SHALL BE
CONSTRUCTED IN A SIMILAR MANNER OR BROUGHT TO THE ATTENTION OF
THE ARCHITECT FOR CLARIFICATION. MODIFICATIONS MAY BE REQUIRED BY
THE CONTRACTOR TO ACCOMODATE FOR MINOR VARIATIONS IN THE WORK.
7. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION AND
INSTALLATION OF OWNER SUPPLIED EQUIPMENT AS IDENTIFIED IN THE
DRAWINGS AND SPECIFICATIONS, INCLUDING THE RELOCATION OF EXISTING
EQUIPMENT.
8. THE CONTRACTOR IS RESPONSIBLE FOR LOCATING ALL EXISTING
UNDERGROUND UTILITIES AND COORDINATING WITH NEW WORK. ADVISE
ARCHITECT/ENGINEER OF CONFLICTS PRIOR TO COMMENCEMENT OF WORK.
9. ALL GRADING SHALL SLOPE AWAY FROM THE BUILDING.
10. PRIOR TO POURING OF CONCRETE FOOTINGS, THE CONCRETE
REINFORCEMENT STEEL SHALL BE GROUNDED AND BONDED BY THE
ELECTRICAL CONTRACTOR IN ACCORDANCE WITH THE NATIONAL ELECTRIC
CODE (NEC) SECTION 250-50. A CONDUCTIVE REINFORCING BAR
MEASURING AT LEAST 1/2" IN DIAMETER AND A MINIMUM OF 20 FEET IN
LENGTH THAT IS ENCASED IN A MINIMUM OF 2" CONCRETE COVER SHALL
SUFFICE FOR USE AS AN ELECTRODE.
11. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE
COORDINATION OF THE PROJECT AND SCHEDULING OF THE WORK
CONDUCTED BY OTHER TRADES.
12. THE CONTRACTOR SHALL CONSTRUCT CHASES AND/OR RECESSES AS
SHOWN, AND AS REQUIRED TO CONCEAL THE WORK OF OTHER TRADES AS
DIRECTED BY THE ARCHITECT TO MATCH ADJACENT CONSTRUCTION,
REGARDLESS IF SHOWN ON THE DRAWINGS.
13. THE CONTRACTOR SHALL INSTALL LOOSE LINTELS FOR ALL WALL
PENETRATIONS WIDER THAN 6" AS A RESULT OF DUCT, PIPE OR OTHER
EQUIPMENT INSTALLATIONS.
14. ALL WALL AND FLOOR PENETRATIONS SHALL BE PATCHED AND SEALED BY
THEIR RESPECTIVE TRADES.
15. ALL FLOORS SHALL BE SLEEVED AND SEALED IN PLUMBING CHASES.
16. PARTITIONS SHALL BE LAYED OUT STARTING FROM CONDITIONS WHERE
ALIGNMENT WITH EXISTING CONSTRUCTION IS SHOWN. UNLESS OTHERWISE
NOTED, DIMENSIONS ARE TAKEN TO THE FACE OF WALLS/PARTITIONS.
17. DIMENSIONS TO MASONRY CONSTRUCTION ARE GIVEN TO THE NOMINAL
FACE OF THE WALL. EXTERIOR MASONRY DIMENSIONS ARE TAKEN TO THE
NOMINAL FACE OF THE WALL, UNLESS OTHERWISE NOTED. CLEAR
DIMENSIONS SHALL BE TAKEN FROM THE FINISHED FACE OF WALLS.
18. WALLS OVERLAPPING COLUMN LINES SHALL BE ASSUMED CENTERED ON
THE COLUMN UNLESS OTHERWISE INDICATED.
19. THE CONTRACTOR SHALL FURNISH AND INSTALL BLOCKING IN FRAMED WALL
ASSEMBLIES WHERE WALL MOUNTED ACCESSORIES, CABINETS OR OTHER
ACCESSORIES ARE INDICATED.
20. TERMINATE ALL INTERIOR WALLS TO THE UNDERSIDE OF DECKING, UNLESS
OTHERWISE NOTED OR INDICATED BY SPECIFIC PARTITION TYPES.
21. ALL OUTSIDE CMU CORNERS OF INTERIOR WALLS SHALL BE BULLNOSED,
UNLESS OTHERWISE NOTED.
22. PROVIDE ANGLED BLOCKS AND BRICKS FOR OUTSIDE CORNERS OF
MASONRY WALLS OR OTHER SPECIAL SHAPES AVAILABLE FROM
MANUFACTURER.
23. REFER TO ROOM FINISH LEGEND AND PROJECT SPECIFICATIONS FOR FINISH
REQUIREMENTS.
PULL SIDE
PUSH SIDE
1'-4"
METAL STUDS AT 16" OC (UON)
(1) LAYER 5/8" GWB BOTH SIDES
PROVIDE FIRE RATED
SEALANT BOTH SIDES FOR
ALL FIRE RATED
ASSEMBLYIES (TYP)
PROVIDE SOUND
ATTENUATION BLANKETS AT
ALL SOUND PARTITIONS
SCHEDULED CEILING
SCHEDULED BASE
NOTES:
1. PROVIDE TILE BACKER BOARD AT ALL
LOCATIONS TO RECIEVE TILE
2. SEE COMMENTS IN SCHEDULE FOR
ADDTIONAL INFORMATION
3. CONSTRUCT TOP OF WALL TO UNDERSIDE
OF HORIZONTAL FRAMING ABOVE UNLESS
OTHERWISE NOTED ON DRAWINGS.
SEE SCHED.
WIDTH
DRAWING SYMBOLS
DETAIL
IDENTIFICATI
ON
BUILDING SECTION
INDENTIFICATION
WALL SECTION
INDENTIFICATION
ELEVATION
MARKS
COLUMN
NUMBER
DOOR
NUMBER
WINDOW TYPE
REVISION NUMBER
PARTITION TYPE
DATUM or
ELEVATION MARK
CENTERLINE
1t
A101
SIM
A101
SIM
A101
SIM
A101
A101
SIM
ROOM TAG
NAME
ELEVATION
REVISION NUMBER
REFERENCE CODE
8A.1
XXXX
CURTAIN WALL or
STOREFRONT TAGCW-1
OCC:
ROOM NAME
150 SF
DETAIL NO.
DRAWING NO.
SECTION NO.
DRAWING NO.
SECTION NO.
DRAWING NO.
OPEN HEAD
DETAIL NO.
DRAWING NO.
CLOSED HEAD
SIM/OPP TAG
SIM/OPP TAG
SIM/OPP TAG
EXTERIOR INTERIOR
ROOM NAME
ROOM NUMBER
GROSS SF
OCCUPANTS
22A TOILET ACCESSORY
TAG
MATERIAL SYMBOLS
EARTH
POROUS FILL or SUB-SLAB AGGREGATE
CONCRETE
CONCRETE MASONRY UNIT (CMU)
BRICK
GYPSUM WALL AND/OR CEILING BOARD
BATT INSULATION / SOUND ATTENUATION
RIGID INSULATION
STEEL
CONTINUOUS WOOD BLOCKING
WOOD SHIM OR BLOCKING
PLYWOOD
FIRE SAFING
MORTAR NET
SPRAY FOAM INSULATION
STONE
MORTAR / GROUT
ABBREVIATIONS
CJ CONTROL JOINT
CMU CONCRETE MASONRY UNIT
CFMF COLD FORMED METAL FRAMING
DN DOWN
DWG DRAWING
EIFS EXTERIOR INSULATION AND FINISH SYSTEM
EL ELEVATION
EQ EQUAL
EJ EXPANSION JOINT
EWC ELECTRIC WATER COOLER
FD FLOOR DRAIN
FE FIRE EXTINGUISHER (BRACKET MOUNTED)
FEC FIRE EXTINGUISHER CABINET
FT FOOT or FEET
FRTW FIRE RETARDANT TREATED WOOD
GALV GALVANIZED
GSF GROSS SQUARE FEET
GWB GYPSUM WALL BOARD
HM HOLLOW METAL
HP HIGH POINT
LP LOW POINT
MAX MAXIMUM
MIN MINIMUM
MO MASONRY OPENING
N/A NOT APPLICABLE
NIC NOT IN CONTRACT
NSF NET SQUARE FEET
OC ON CENTER
OD OVERFLOW DRAIN OR OUTSIDE DIAMETER
PTD PAINT or PAINTED
PTW PRESSURE TREATED WOOD
PVC POLYVINYL CHLORIDE
RD ROOF DRAIN
REINF REINFORED OR REINFORCING
RWC RAIN WATER CONDUCTOR
SF SQUARE FEET
TOS TOP OF STEEL
TYP TYPICAL
VIF VERIFY IN FIELD
AREA OF WORK
EXISTING
PAINT
ROOM
(NOT IN
SCOPE)
D E G
EXISTING
PAINT ROOM
(NOT IN SCOPE)
102 SF
CORRIDOR
194 SF
CORRIDOR
77 SF
CORRIDOR
88 SF
TOILET /
SHOWER
AE300
33 SF
CHANGING
ROOM
'-1
C
LE
A R
'-0
'-4
CONTROL WALL
5'-2"
'-0
1'-6"
9'-10 3/8" 4'-1" 6'-8 1/8"
VIF
19'-10"
B6B6
D4
D3
A3
D6
D4
4'-2"
CLEAR
3'-0"
30" ACCESS DOOR
B6
5'-6" 3'-9"
D3
D3D3
D3
7'-0 1/2" 19'-5 1/4"
5'-4"
'-1
'-8
C
LE
A R
'-0
R .O
'-4
'-4
FF A3
F
D3
D3
'-2
'-3
'-6
/8
'-8
'-5
/2
'-5
/2
'-3
'-5
/2
'-0
/2
'-4
2 HOUR FIRE RATED
WALL ASSEMBLY
D3
B6
D3
B6
A3
D3
A3
A3A3
D3
D3
F
A3
D3
A3A3
249 SF
WOMEN'S
LOCKER
ROOM
450 SF
MEN'S
LOCKER
ROOM
BINS PROVIDED BY OWNER
CONTRACTOR TO INSTALL
A3 A3
A3
A3
A3
D3
A3
A3A3
D3
A3
D3
D3
B6
D3
A3
D6
D3
D3
AE111
'-1
'-5
'-1
4'-1"
'-7
'-1
/4
'-0
'-6
'-0
/8
5'-0 3/8"
4'-4"
13'-6"
'-9
'-1
'-4
/2
'-1
'-2
'-1
" 3'-6"
'-0
'-0
'-2
1'-0"
15'-5 3/8"
9'-4"
1'-2 3/8"
CONSTRUCT WALL TO UNDERSIDE OF
EXISTING DECK. TYP. OF ALL WALLS AS
INDICATED WITH HATCH.
METAL STUDS AT 16" OC (UON)
(1) LAYER 5/8" GWB BOTH SIDES
SEE NOTE 3
SEE NOTE 3
UNFACED BATT INSULATION
FULL DEPTH OF STUD
SCHEDULED CEILING
SCHEDULED BASE
NOTES:
1. PROVIDE TILE BACKER BOARD AT ALL
LOCATIONS TO RECEIVE TILE
2. SEE COMMENTS IN SCHEDULE FOR
ADDITIONAL INFORMATION
3. CONSTRUCT ALL PARTITIONS WITH SOUND
ISOLATION CONSTRUCTION DETAILS PER
REQUIREMENTS OF THE GYPSUM MANUAL
2012, FIGURE 9, INCLUDING ACOUSTIC
SEALANT AT PERIMETER OF ALL
PARTITIONS.
4. CONSTRUCT TOP OF WALL TO UNDERSIDE
OF HORIZONTAL FRAMING ABOVE UNLESS
OTHERWISE NOTED ON DRAWINGS.
FINISHED FLOOR
4 1/4"
SCHEDULED CEILING
SCHEDULED BASE
NOTES:
1. SEE COMMENTS IN SCHEDULE
FOR ADDITIONAL INFORMATION
FINISHED FLOOR
CONTINUOUS FIRE SAFING
INSULATION TO FILL BETWEEN
CMU & STRUCTURE ABOVE AT
METAL DECK LOCATIONS, TYP FOR
ALL FIRE RATED ASSEMBLIES
3/4" COMPRESSIBLE FILLER &
SEALANT - SAME RATING AS
PARTITION
GROUT SOLID FIRST COURSE
SEE STRUCTURAL DRAWINGS
FOR DOWELS AND REINFORCING
SEE SCHED.
WIDTH
BRACE PARTITION TO
STRUCTURE ABOVE @ 32"
O.C. UNO.
SOUND ATTENUATION
BLANKETS. EXTEND 4'-0" MIN
PAST PARTITION.
METAL STUDS AT 16" OC (UON)
(1) LAYER 5/8" GWB BOTH SIDES
SEE NOTE 3
UNFACED BATT INSULATION
FULL DEPTH OF STUD
SCHEDULED CEILING
SCHEDULED BASE
NOTES:
1. PROVIDE TILE BACKER BOARD AT ALL
LOCATIONS TO RECEIVE TILE
2. SEE COMMENTS IN SCHEDULE FOR
ADDITIONAL INFORMATION
3. CONSTRUCT ALL PARTITIONS WITH
SOUND ISOLATION CONSTRUCTION
DETAILS PER REQUIREMENTS OF THE
GYPSUM MANUAL 2012, FIGURE 9,
INCLUDING ACOUSTIC SEALANT AT
PERIMETER OF ALL PARTITIONS.
4. CONSTRUCT TOP OF WALL TO
UNDERSIDE OF HORIZONTAL FRAMING
ABOVE UNLESS OTHERWISE NOTED
ON DRAWINGS.
SEE SCHED.
WIDTH
FINISHED FLOOR
EXTEND GWB TIGHT TO
STRUCTURE ON ONE SIDE
FOR ALL SMOKE RATED
PARTITIONS
PROVIDE SEALANT FOR ALL
SMOKE RATED PARTITIONS
PROVIDE SEALANT FOR ALL
SMOKE RATED PARTITIONS
7/8" METAL FURRING
CHANNEL AT 2'-0" O.C.
SCHEDULED CEILING
SCHEDULED BASE
NOTES:
1. PROVIDE TILE BACKER BOARD AT ALL
LOCATIONS TO RECEIVE TILE
2. SEE COMMENTS IN SCHEDULE FOR
ADDITIONAL INFORMATION
3. CONSTRUCT ALL PARTITIONS WITH
SOUND ISOLATION CONSTRUCTION
DETAILS PER REQUIREMENTS OF THE
GYPSUM MANUAL 2012, FIGURE 9,
INCLUDING ACOUSTIC SEALANT AT
PERIMETER OF ALL PARTITIONS.
4. CONSTRUCT TOP OF WALL TO
UNDERSIDE OF HORIZONTAL FRAMING
ABOVE UNLESS OTHERWISE NOTED
ON DRAWINGS.
EXISTING WALL ASSEMBLY
5/8" GWB
FINISHED FLOOR
SEE NOTE 3
SEE SCHED
WIDTH
A Se rv ic e D i s a b le d Ve t e r an Owned
S m a l l B u s iness
SDVOSB
CVE
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
CONSULTANTS:
o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
1 2 3 4 5 6 87 9
97 8654321
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0700-0008
B
A
C
D
E
F
NO. DESCRIPTION DATE
PLAN
NORTH
ACTUAL
NORTH
Phone 609.695.7400
HAMILTON, N.J. 08691
1395 YARDVILLE HAMILTON SQUARE ROAD
Architecture Planning Design
SPIEZLE ARCHITECTURAL GROUP, INC.
Architecture Planning Design
Fax 609.394.2274
SPIEZLE ARCHITECTURAL GROUP, INC.
NOT FOR CONSTRUCTION - FULLY SPRINKLERED
B3 SUBMISSION
REPAIR CORROSION
CONTROL FACILITY BLDG.
JOINT BASE
McGUIRE-DIX-LAKEHURST AFB, NJ
PTFL132039
12-05-2019
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE PROFESSIONAL
ENGINEER. FLOOR PLAN AND GENERAL PLAN
INFORMATION
AE100
1/2" = 1'-0".
A1 - DOOR SWING DIAGRAM
PARTITION TYPE 'B' SCHEDULE
TYPE
MARK
STUD
SIZE
FIRE
RATING
TEST
NUMBER
STC
RATING WIDTH COMMENTS
B3 3 5/8" - - 4 7/8"
B6 6" - - 7 1/4"
1/32" = 1'-0"2
AREA OF WORK FLOOR PLAN
1/4" = 1'-0"1
FLOOR PLAN
PARTITION TYPE 'A' SCHEDULE
Type Mark
STUD
SIZE
Fire Rating
TEST
NUMBER
STC
RATING Width Description
A3 3 5/8" - - 4 1/4" 1 LAYER GWB
PARTITION TYPE CMU SCHEDULE
Type Mark Comments Fire Rating TEST NUMBER STC RATING WIDTH
4 - - 3 5/8"
8 TOOTH IN WITH
EXISTING WALL
SEE CODE PLAN - - 7 5/8"
PARTITION TYPE 'D' SCHEDULE
TYPE
MARK
STUD
SIZE
FIRE
RATING
TEST
NUMBER
STC
RATING WIDTH COMMENTS
D3 3 5/8" - - 4 7/8"
D4 4" - - 5 1/4"
D6 6" - - 7 1/4"
PARTITION TYPE 'F' SCHEDULE
TYPE
MARK
STUD
SIZE
FIRE
RATING
TEST
NUMBER
STC
RATING WIDTH COMMENTS
F 7/8" - - 1 1/2"
MEN'S
LOCKER
ROOM
WOMEN'S
LOCKER
ROOM
TOILET /
SHOWER
CORRIDOR
CORRIDOR
CHANGING
ROOM
CORRIDOR
ACT-1 8' - 0"
GYP 8' - 0"
GYP 8' - 0"
ACT-1 8' - 0"
ACT-1 8' - 0"
ACT-1 8' - 0"
ACT-1 8' - 0"
GYP 8' - 0"
ACT-1 8' - 0"
EXISTING
PAINT ROOM
ACT-1 8' - 0"
CEILING NOTES
NOTES:
1. INCLUSION OF SYMBOL IN LEGEND DOES NOT IMPLY
SCOPE OF WORK. REFER TO PLANS.
2. CONTRACTORS SHALL COORDINATE WITH ALL OTHER
TRADES PRIOR TO INSTALLATION OF FIXTURES AND
OTHER CEILING DEVICES.
3. REFER TO M/E/P DRAWINGS FOR SIZES, TYPES,
QUANTITIES AND INSTALLATION REQUIREMENTS OF
FIXTURES AND CEILING DEVICES.
4. WHERE CEILING HEIGHTS ARE BELOW WINDOW HEADS
THE CONTRACTOR SHALL PROVIDE FASCIA MOLDING OR
TRIM TO MATCH SIZE AND COLOR OF CEILING TRIM.
5. COORDINATE ALL AUDIO & VISUAL DEVICES WITH A/V
DRAWINGS. A/V EQUIPMENT SHOWN HERE, INCLUDING
PROJECTORS AND PROJECTION SCREENS ARE
DIAGRAMMATIC AND ARE SHOWN HERE TO DEPICT
ADJACENCIES WITH OTHER LIGHTING AND CEILING
DEVICES.
XXX-# 88'-88"
HEIGHT ABOVE FINISHED FLOOR
CEILING TYPE
OFFICE SPACE
MEN'S LOCKER
ROOM
PT-1
RB-1
ERF-2
WOMEN'S
LOCKER ROOM
PT-1
RB-1
ERF-2
TOILET /
SHOWER
PT-1
RB-1
ERF-2
CORRIDOR
PT-1
RB-1
ERF-2
CHANGING
ROOM
PT-1
RB-1
ERF-2
CORRIDOR
PT-1
RB-1
ERF-2
CORRIDOR
PT-1
RB-1
ERF-2
EXISTING
PAINT ROOM
PATCH EXISTING FLOORING WITH LVT-1 AS
NEEDED TO ACCOMMODATE TRENCHING
FOR UNDERSLAB PIPING.
PT-2
PT-2
PT-1 FINISH
WHERE INDICATED
ERF-1
N/A
N/A
N/A
N/A
CLEAN EXISTING EPOXY FLOOR
RB-1
ROPPE
4" x 1/8" GAUGE - TOED BASE
STONE COLD
BASE FOR ALL VCT
INTERIOR FINISH LEGEND
FINISH TYPE IDENTITY CODE MANUFACTURER / STYLE COLOR NAME / COLOR # REMARKS
LIST FINISH TYPE
HERE
ERF-2
KEY RESIN COMPANY
KEY QUARTZ B-125
BROWN
214-D
CLEAN EXISTING EPOXY FLOOR
BEFORE APPLYING NEW COATS
LVT-1
ARMSTRONG FLOORING
12"x24", LOW GLOSS
REDONDO BEACH
J6219
MATCH EXISTING FLOORING
PT-1
SHERWIN WILLIAMS
EGGSHELL FINISH
PEARLY WHITE
SW7009
FINAL COLOR APPROVAL BY OWNER
PT-2
SHERWIN WILLIAMS
PRO MAR 200, INTERIOR LATEX
WHITE
SEMI GLOSS
PROVIDE AT ALL WET WALLS
FINAL COLOR APPROVAL BY OWNER
FINISH ABBREVIATIONS
AFP ACOUSTICAL FABRIC PANELS
CPT CARPET
CT CERAMIC TILE
EX. EXISTING FINISH TO REMAIN
EXP EXPOSED
GWB GYPSUM WALLBOARD (PAINTED)
P PAINTED
PE SOLID PVC EDGING
PL PLASTIC LAMINATE
PT PAINT
RF RUBBER FLOORING
RB RUBBER BASE
SCF SEALED CONCRETE FLOOR
SS SOLID SURFACING MATERIAL
TB TACKBOARD
VRB VENTILATED RUBBER BASE
VCT VINYL COMPOSITION TILE
ERF EPOXY RESIN FLOORING
ERPT EPOXY RESIN PAINT
GENERAL FINISH NOTES:
INDICATES EXTENT OF INDICATED FINISH
ROOM NAME
A1000
WF
BF
FF
ROOM FINISH TAG
TYPICAL WALL FINISH
BASE FINISH
FLOOR FINISH
ROOM NAME
ROOM NUMBER
INDICATES CORNER GUARD
E
AE401
AE111
B6
D6
PROVIDE GWB UNDER ENTIRE ACCESS
PLATFORM. FASTEN TO HORIZONTAL
WALL BRACING. EXTEND GWB 2'-0"
MIN. IN BOTH DIRECTIONS ALONG
THE CORRIDOR.
M
IN
'-0
ACCESS
PLATFORM.
M
IN
'-9
/4
SEE STRUCTURAL DRAWINGS
FOR DETAILS AND LOCATION
PT-1 FINISH
WHERE INDICATED
ACCESS PLATFORM (SEE
STRUCTURAL FOR
DETAILS)
BUILD WALL TO UNDERSIDE
OF STRUCTURE
194 SF
CORRIDOR
RUBBER BASE
CONCRETE LEDGE
SEE FLOOR PLAN FOR WALL TYPE
LOCKER
CONTINUOUS 2X4 TREATED
WOOD BLOCKING
3"
BENT BARS
A Se rv ic e D i s a b le d Ve t e r an Owned
S m a l l B u s iness
SDVOSB
CVE
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
CONSULTANTS:
o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
1 2 3 4 5 6 87 9
97 8654321
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0700-0008
B
A
C
D
E
F
NO. DESCRIPTION DATE
PLAN
NORTH
ACTUAL
NORTH
Phone 609.695.7400
HAMILTON, N.J. 08691
1395 YARDVILLE HAMILTON SQUARE ROAD
Architecture Planning Design
SPIEZLE ARCHITECTURAL GROUP, INC.
Architecture Planning Design
Fax 609.394.2274
SPIEZLE ARCHITECTURAL GROUP, INC.
NOT FOR CONSTRUCTION - FULLY SPRINKLERED
B3 SUBMISSION
REPAIR CORROSION
CONTROL FACILITY BLDG.
JOINT BASE
McGUIRE-DIX-LAKEHURST AFB, NJ
PTFL132039
12-05-2019
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE PROFESSIONAL
ENGINEER. REFLECTED CEILING PLAN
AND FINISH PLAN
AE111
1/8" = 1'-0"1
REFLECTED CEILING PLAN
CEILING TYPE SCHEDULE
TYPE MARK DESCRIPTION
ACT-1 2x2 ACT PANEL
GYP GYPSUM BOARD CEILING
1/8" = 1'-0"2
FINISH PLAN
1/4" = 1'-0"3
ACCESS PLATFORM PLAN
1/4" = 1'-0"4
ACCESSPLATFORM SECTION
1 1/2" = 1'-0"5
TYPICAL LOCKER BASE DETAIL
Level 1 0"
Bottom of Steel 22' - 9"
AE300
AE300
'-0
18 GA. 8" METAL STUDS @ 16" O.C. HORIZONTAL
WALL BRACING. BRACE TO THE TOP OF
PARTITIONS. HANG CEILING GRID FROM
HORIZONTAL BRACING. FASTEN 1/2" GYPSUM WALL
BOARD ON TOP. DESIGN INTENT IS FOR BRACING
ONLY; DO NOT USE FOR STORAGE.
18 GA. 8" METAL STUD AT 16" O.C.
1/2" MASONRY ANCHOR AT 48" O.C.
F
1/2" GWB
18 GA. 8" METAL STUD AT 16" O.C.
1/2" GWB
OF EXISTING
STEEL SUPPORT
OF EXISTING
STEEL SUPPORT
CUT VERTICAL LEG OF ANGLE TO
ALLOW TOP HORIZONTAL LEG TO
BEAR ON LOWER SUPPORT ANGLE
OPENING
OR CURB
TYP.
TO UNDERSIDE OF
TOP FLANGE (TYP.)
" S1 "
S
NOTES:
1. FOR SIZE AND LOCATION OF OPENINGS SEE MECHANICAL DRAWINGS.
2. STEEL CONTRACTOR SHALL VERIFY ALL OPENINGS AND EXACT
LOCATIONS WITH THE TRADE CONTRACTOR REQUIRING SAID
OPENINGS PRIOR TO FABRICATION AND ERECTION OF STEEL FRAMES.
3. PROVIDE STEEL FRAMES AS SHOWN AROUND ALL REQUIRED
OPENINGS LARGER THAN 8" AT ROOF.
4. PROVIDE STEEL ANGLES ON ALL SIDES OF OPENINGS UNLESS
BEAM IS SHOWN ON PLAN. ANGLE SIZES TO BE:
FOR "S1" OR "S2" < 6'-6" L-4"x4"x5/16" FOR "S1" OR "S2" > 6'-6" L-6"x6"x3/8"
5. PROVIDE STEEL ANGLES ON ALL SIDES OF MECHANICAL CURBS UNLESS
BEAM IS SHOWN ON PLAN. ANGLE SIZES TO BE L-6"x6"x3/8".
6. FOR SIZE AND LOCATION OF MECH'L UNITS, SEE MECHANICAL DWGS.
EXISTING ROOFING
ASSEMBLY TO REMAIN
METAL COUNTERFLASHING
EXHAUST FAN
PRE-MANUFACTURERD CURB
FLASHING MEMBRANE
M
IN
EXISTING ROOF DECK TO
REMAIN
PRE-MANUFACTURED CANT
2X P.T. WOOD BLOCKING
LAP MEMBRANE FLASHING
UP AND OVER T.O. CURB
PROVIDE TIE-IN TO EXISTING ROOFING ASSEMBLY
AS TO NOT VOID EXISTING ROOF WARRANTY
STEEL ANGLE. REFER TO
TYPICAL CURB SUPPORT
DETAIL (5/A3.1)
REMOVE PORTION OF EXISTING ROOF
DECK AND ROOFING ASSEMBLY TO
ACCOMODATE INSTALLATION OF
EXHAUST FAN CURB AND DUCTWORK
GENERAL NOTE:
EXISTING ROOF IS A SBS MODIFIED ROOFING ASSEMBLY
UNDER EXISTING WARRANTY. PERFORM ALL WORK AS TO
NOT VOID EXISTING WARRANTY.
GENERAL ROOFING NOTES
1. SEE ROOF PLAN FOR DESIGNATION OF SPECIFIC 'ROOF ASSEMBLY TYPES'.
2. THE QUANTITY AND LOCATION OF ALL EXISTING AND NEW ROOFTOP EQUIPMENT INCLUDING BUT NOT
LIMITED TO MECHANICAL UNITS, ROOF AND OVERFLOW DRAINS, VENTS AND ELECTRICAL CONDUIT AND DEVICES ARE SHOWN FOR REFERENCE ONLY. THE CONTRACTOR MUST FIELD VERIFY ALL EXISTING
CONDITIONS PRIOR TO THE COMMENCEMENT OF WORK AND COORDINATE WITH NEW CONDITIONS
INDICATED UNDER BASE BIDS, ALTERNATE BIDS AND SEPARATE CONTRACT(S) WHERE APPLICABLE.
3. ROOF CRICKETS SHALL SLOPE AT A MINIMUM RATE OF 1/2" PER FOOT AND BE LOCATED IN LOW VALLEYS, BETWEEN ROOF DRAINS AND BEHIND EQUIPMENT TO DIVERT WATER AROUND CURBS, RAILS
AND OTHER EQUIPMENT SUPPORTS, WHETHER INDICATED OR NOT.
4. ALL WOOD BLOCKING AND PLYWOOD SHEATHING SHALL BE PRESERVATIVE TREATED. UNLESS
OTHERWISE NOTED, ALL PLYWOOD SHEATHING SHALL BE A MINIMUM OF 5/8" THICK.
5. WHETHER INDICATED OR NOT ON THE DRAWINGS, THE CONTRACTOR SHALL BE RESPONSIBLE FOR
FLASHING ALL ROOFTOP EQUIPMENT AND PENETRATIONS PER THE DETAILS AND/OR ROOFING
MANUFACTURER'S REQUIREMENTS, WHICHEVER IS STRICTER.
6. PROVIDE ROOF PROTECTION PADS COMPATIBLE WITH THE SPECIFIED ROOFING SYSTEM BELOW ALL POINTS OF CONTACT OF EQUIPMENT SUPPORT RAILS, DUCT SUPPORTS, PIPE CARRIERS AND OTHER
SUPPORT DEVICES WHICH DO NOT PENETRATE THE ROOF.
7. THE BUILDING MAY BE OCCUPIED DURING ROOFING REMOVAL AND REPLACEMENT. THE CONTRACTORS
WORK AND SEQUENCING SHALL BE COORDINATED WITH THE OWNER AND ARCHITECT PRIOR TO
COMMENCEMENT OF WORK.
8. FOR ALL CONNECTIONS TO EXISTING ROOFS TO REMAIN, COORDINATE WITH THE MANUFACTURER OF THE EXISTING ROOFING SYSTEM PRIOR TO THE START OF WORK TO VERIFY THE COMPATIBILITY OF ALL FLASHING METHODS, ROOFING MATERIALS AND INSTALLATION METHODS SO AS NOT TO VOID EXISTING
ROOF WARRANTIES.
9. THE CONTRACTOR IS RESPONSIBLE FOR ALL DISCONNECT, EXTENSION, TEMPORARY RELOCATION AND RECONNECTION OF UTILITIES THAT MAY BE NECESSARY TO FACILITATE THE WORK. COORDINATE ALL UTILITY INTERRUPTIONS AND SHUTDOWNS WITH THE OWNER AND ARCHITECT PER THE SPECIFICATIONS.
10. THE CONTRACTOR SHALL PURGE, DISCONNECT, RAISE AND RECONNECT EXISTING GAS PIPING AS
NECESSARY TO COMPLETE THE WORK.
11. ALL EXISTING ROOFTOP EQUIPMENT, CURBS, RAILS AND VENTS SHALL REMAIN, UNLESS OTHERWISE NOTED. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING MINIMUM CLEARANCES BETWEEN
ROOF SURFACES AND BOTTOM OF EQUIPMENT. THE CONTRACTOR SHALL BE RESPONSIBLE FOR
PROTECTING EXISTING EQUIPMENT TO REMAIN AND SHALL REPAIR/REPLACE DAMAGED EQUIPMENT
IMMEDIATELY AT NO COST TO THE OWNER.
12. LOCATIONS OF ROOF PENETRATIONS ARE DIAGRAMMATIC AND MUST BE COORDINATED WITH OTHER ASPECTS OF THE WORK. THE CONTRACTOR SHALL COORDINATE FINAL PLACEMENT OF EQUIPMENT WITH STEEL FRAMING, EXISTING EQUIPMENT AND CONDITIONS BELOW THE ROOF DECK THAT MAY INHIBIT THE INSTALLATION OF SAID EQUIPMENT FROM LOCATIONS DEPICTED IN THE DRAWINGS.
13. THE CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND DISPOSAL OF ALL HAZARDOUS MATERIALS.
REFER TO THE PROJECT MANUAL AND ABATEMENT DRAWINGS FOR ADDITIONAL INFORMATION
REGARDING REMOVAL, HANDLING AND DISPOSAL PROCEDURES.
14. REPLACE DAMAGED MATERIALS AND ASSEMBLIES IN 'LIKE KIND' LEAVING NO EVIDENCE OF PATCHING OR
REPAIRS AS DETERMINED BY THE ARCHITECT AND AT NO COST TO THE OWNER.
A Se rv ic e D i s a b le d Ve t e r an Owned
S m a l l B u s iness
SDVOSB
CVE
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
CONSULTANTS:
o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
1 2 3 4 5 6 87 9
97 8654321
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0700-0008
B
A
C
D
E
F
NO. DESCRIPTION DATE
PLAN
NORTH
ACTUAL
NORTH
Phone 609.695.7400
HAMILTON, N.J. 08691
1395 YARDVILLE HAMILTON SQUARE ROAD
Architecture Planning Design
SPIEZLE ARCHITECTURAL GROUP, INC.
Architecture Planning Design
Fax 609.394.2274
SPIEZLE ARCHITECTURAL GROUP, INC.
NOT FOR CONSTRUCTION - FULLY SPRINKLERED
B3 SUBMISSION
REPAIR CORROSION
CONTROL FACILITY BLDG.
JOINT BASE
McGUIRE-DIX-LAKEHURST AFB, NJ
PTFL132039
12-05-2019
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE PROFESSIONAL
ENGINEER. BUILDING SECTIONS AND DETAILS
AE300
1/4" = 1'-0"1
PARTIAL BUILDING SECTION
1 1/2" = 1'-0"3
SECTION DETAIL
1 1/2" = 1'-0"2
SECTION DETAIL
1/2" = 1'-0"4
TYPICAL CURB SUPPORT UNDER MECHANICAL CURB
1 1/2" = 1'-0"5
TYPICAL EXHAUST FAN DETAIL
AE401 2
AE401 7
AE401
4 6
450 SF
MEN'S
LOCKER
ROOM
249 SF
WOMEN'S
LOCKER
ROOM
102 SF
CORRIDOR
77 SF
CORRIDOR
33 SF
CHANGING
ROOM
194 SF
CORRIDOR
88 SF
TOILET /
SHOWER
'-0
'-1
/4
'-3
'-8
/2
'-8
/2
'-0
'-0
'-6
05 11
'-7
/8
'-0
1'-6 1/4"
'-6
'-0
'-0
'-0 " 1
'-0
'-6
/8
2'-0" 1'-8"
10" 3'-3" 10"
'-0
'-0
AE401
TYP
AE401
TYP
TOILET ACCESSORY LEGEND
MARK DESCRIPTION MANUFACTURER MODEL NUMBER REMARKS
SOAP DISPENSER BOBRICK B-2111
BOBRICK
COAT HOOK BOBRICK B-6827 --
BOBRICK
B-3942
COMBINATION PAPER TOWEL
AND WASTE RECEPTACLE
BOBRICK --
MIRROR (SINGLE LAVATORY)
BOBRICK
B-290 x 2436
MIRROR (FULL LENGTH)
BOBRICK
B-290 x 2472
HOOK STRIP B-232 x 24
GRAB BAR SET (WATER CLOSET) B-6806 x 36" (H) B-6806 x 42" (H) B-6806 x 18" (V)
TOILET PAPER DISPENSER BOBRICK B-2890
SANITARY NAPKIN DISPOSAL BOBRICK B-270 --
V VERTICAL MOUNTING
H HORIZONTAL MOUNTING
ACCESSIBILITY DESIGN STANDARDS
AMERICAN NATIONAL STANDARD
ICC/ANSI A117.1-2009, ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES
NEW JERSEY UNIFORM CONSTRUCTION CODE
SUBCHAPTER 7: BARRIER-FREE DESIGN
NOTES:
1. FIXTURES SHALL BE INSTALLED AS PER MANUFACTURER'S RECOMMENDATIONS AND APPLICABLE
CODES AND REGULATIONS.
2. WRAP ALL EXPOSED PIPING.
3. HEIGHT OF WATER CLOSETS ARE MEASURED FROM FINISHED FLOOR TO THE TOP OF THE SEAT.
4. DISPENSERS SHALL BE 1-1/2" MINIMUM BELOW AND 12" MINIMUM ABOVE GRAB BAR (TYP.)
5. AT FRAMED WALL ASSEMBLIES PROVIDE REINFORCING FOR SURFACE MOUNTED ACCESSORIES.
WH = WALL HYDRANT
HB = HOSE BIBB
= BARRIER-FREE ACCESSIBILITY
= INDICATES 5'-0" CLEAR
TURNING RADIUS
R= 30"
11 BENCH BRADLEY LENOX PEDESTAL VERIFY SIZE IN FIELD
CURTAIN, CURTAIN ROD, AND HOOKS BOBRICK 204-2, B-207 x 36, 204-1 --10
UTILITY SHELF BOBRICK B-239 x 34 --
13 ACCESSIBILITY SIGNAGE SEE TYPICAL DETAIL AND SPECIFICATIONS
INTERIOR SIGNAGE TYPE R
INTERIOR SIGNAGE TYPE R
DOOR AND FRAME NOTES
1. OPENING FORCE OF INTERIOR NON-RATED DOORS SHALL BE NO GREATER THAN 5 LBS.
2. OPENING FORCE OF FIRE RATED DOORS SHALL BE NO GREATER THAN 8 LBS.
3. ALL EXTERIOR GLAZING IN NON-RATED WALL AND DOOR ASSEMBLIES SHALL BE MINIMUM 1" INSULATED GLAZING. REFER TO SPECIFICATIONS FOR GLAZING TYPES.
4. PAINT ALL EXPOSED STEEL (COLOR AS SELECTED BY ARCHITECT).
5. PROVIDE COMPATIBLE FLASHING MATERIALS BETWEEN DISSIMILAR MATERIALS SUCH AS STEEL TO ALUMINUM.
6. SHIM ASSEMBLIES AS REQUIRED FOR PLUMB AND LEVEL. PROVIDE SEALANT AND BACKER RODS AT ALL JOINTS BETWEEN WINDOW SYSTEMS, DOOR FRAMES AND OTHER SURROUNDING CONSTRUCTION.
7. ALUMINUM WINDOW AND ENTRANCE FRAMES SHALL NOT BE INSTALLED I DIRECT CONTACT WITH DISSIMILAR BUILDING MATERIALS.
8. THE MINIMUM LATCH SIDE CLEARANCE BETWEEN THE EDGE OF DOOR AND ADJACENT WALL OR OBSTRUCTIONS ON PULL SIDE SHALL BE 1'-6" MINIMUM.
9. THE MINIMUM LATCH SIDE CLEARANCE BETWEEN THE EDGE OF DOOR AND ADJACENT WALL OR OBSTRUCTIONS ON PUSH SIDE SHALL BE 1'-0" MINIMUM.
10. DO NOT APPLY WALL BASE TO HOLLOW METAL OR ALUMINUM FRAMES, UNLESS OTHERWISE NOTED.
11. THE CONTRACTOR SHALL COORDINATE FOR INSTALLATION OF POWER, CONDUIT AND/OR WIRING, ETC. AT OPENINGS SCHEDULED TO RECEIVE DEVICES SUCH AS DOOR CONTACTS. CARD READERS, ELECTRIC LOCKS AND
AUTOMATIC DOOR OPENERS.
DOOR WIDTH
D O
O R H
EI
G
H T
2" 2"
HM1 F
PARTITION (PER PLANS)
HOLLOW METAL FRAME
DOOR
BOND BEAM OR OTHER
LINTEL ASSEMBLY
PARTITION
PER PLANS
HOLLOW METAL
FRAME
DOOR
SEALANT
(TYP.)
V A R
IE
S B Y
TY
PE
5/8" 2"
/1
/2
HOLLOW METAL
FRAME
MASONRY FRAME
ANCHOR
SEALANT BOTH SIDES
HOLLOW METAL
FRAME
V A R
IE
S B Y
TY
PE
/2
/2
5/8" 2"
H1
J1
H2
J2
PAVING (PITCHED
FOR DRAINAGE)
MIN.
4"
BARRIER-FREE
ALUMINUM THRESHOLD
(SET IN FULL BED OF
SEALANT)
3/8" CONTROL JOINT
WITH SEALANT
SCHEDULED FLOOR FINISH
NON-SHRINK GROUT
FLUSH
EXPANSION
JOINT COVER
SCHEDULED FLOOR
FINISH
T1 T2
SOAP
DISPENSER
PAPER
TOWEL
DISPENSER
WASTE
DISPOSAL
PAPER TOWEL
COMBO UNIT
ELECTRIC
HAND DRYER
MIRROR
(SINGLE LAV.)
MIRROR
(MULTI LAV.)
MIRROR
(FULL HEIGHT)
TOILET TISSUE
DISPENSER
SANITARY NAPKIN
DISPOSAL
GARMENT
HOOK
6"x6" ADA
STALL SIGN
S
EE
S C
H
ED
U
LE
SEE
SCHED.
SEE
SCHEDULE
SEE
SCHED.
S
EE
S C
H
ED
M A X.
H
EI
G H
T
TO
O
PE
R A B
LE
P A R
TS
'-0
FIN.
FLOOR
FIN.
FLOOR
URINAL
ACCESSIBL
E
URINAL
STANDARD
FLUSH VALVE
(TYP.)
S
TA
N D
A R D
A D
A
12" MAX. 42" MIN.
40"
M
IN
M
IN
7"-9"
TOILET
STALLS
GRAB
BARS
TOILET
PARTITION
18"
36" MIN. 6"
WALL
HUNG
LAVATORY
M
A X.
8"
11"
INSULATE
EXPOSED
PIPES
(TYP.)
ELEC. WATER
COOLER
S
TA
N D
A R D
8"
11"
M
A X.
A D
A
TRANSFER-TYPE
SHOWER COMPARTMENT
TRANSFER-TYPE
SHOWER CONTROLS
BACK WALL
36" MIN.
M
IN
S
EA
T W
A
LL
M
IN
12"
C O
N
TR
O L
W A
LL
18"
CL
M
A X.
MAX.
15"
CONTROL
WALLCONTRO
L AREA
6" 24"
GRAB
BAR
FOLD-UP
SEAT
6" 6"
6"
A RM
RW
R
RB
RG
MEN'S RESTROOM
WITH PICTOGRAM
WOMENS RESTROOM
WITH PICTOGRAM
BOYS RESTROOM
WITH PICTOGRAM
GIRLS RESTROOM
WITH PICTOGRAM
ROOM NAME / NUMBER
CONTINUOUS SEALANT (TYP.)1/2"
/4
" SOLID SURFACE BACK SPLASH
SOLID SURFACE ON 3/4" MOISTURE
RESISTANT PLYWOOD SUBSTRATE
SOLID SURFACE SIDE SPLASH
BOTH ENDS OF COUNTER
SOLID SURFACE ON 3/4" MOISTURE RESISTANT
PLYWOOD SUBSTRATE
1/4"
/2
/2
/2
/4
1"
/4
/4
SOLID SURFACE EASED EDGE PROFILE
DRIP GROOVE DETAIL AT WET LOCATIONS
BLOCKING AS REQUIRED
GRIND JOINT SMOOTH
A Se rv ic e D i s a b le d Ve t e r an Owned
S m a l l B u s iness
SDVOSB
CVE
Drawing Title Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
CONSULTANTS:
o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
1 2 3 4 5 6 87 9
97 8654321
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0700-0008
B
A
C
D
E
F
NO. DESCRIPTION DATE
PLAN
NORTH
ACTUAL
NORTH
Phone 609.695.7400
HAMILTON, N.J. 08691
1395 YARDVILLE HAMILTON SQUARE ROAD
Architecture Planning Design
SPIEZLE ARCHITECTURAL GROUP, INC.
Architecture Planning Design
Fax 609.394.2274
SPIEZLE ARCHITECTURAL GROUP, INC.
NOT FOR CONSTRUCTION - FULLY SPRINKLERED
B3 SUBMISSION
REPAIR CORROSION
CONTROL FACILITY BLDG.
JOINT BASE
McGUIRE-DIX-LAKEHURST AFB, NJ
PTFL132039
12-05-2019
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE PROFESSIONAL
ENGINEER. ENLARGED PLANS AND DOOR DETAILS
AND SCHEDULES
AE401
1/4" = 1'-0"1
ACCESSORIES FLOOR PLAN
1/4" = 1'-0"2
INTERIOR ELEVATION
1/4" = 1'-0"4
INTERIOR ELEVATION
1/4" = 1'-0"5
INTERIOR ELEVATION
1/4" = 1'-0"6
INTERIOR ELEVATION
1/4" = 1'-0"7
INTERIOR ELEVATION
1/4" = 1'-0"8
INTERIOR ELEVATION
1/4" = 1'-0"9
INTERIOR ELEVATION
1/4" = 1'-0"3
INTERIOR ELEVATION
DOOR AND FRAME SCHEDULE
NO. TO
DOOR FRAME
STOP
TYPE
HARDWAR
E SET
FIRE
RATING REMARKS
SINGLE /
PAIR
DOOR
WIDTH
DOOR
HEIGHT
DOOR
THK.
DOOR
MAT.
DOOR
TYPE
FRAME
TYPE
FRAME
MAT.
HEAD
TYPE
JAMB
TYPE
THRESHOLD
TYPE
143 CORRIDOR SINGLE 3' - 0" 7' - 2" 1 3/4" HM F HM1 HM H1 J1 4.0
145 CORRIDOR SINGLE 2' - 6" 7' - 2" 1 3/4" HM F HM1 HM H1 J1 6.0
147 CORRIDOR SINGLE 3' - 0" 7' - 2" 1 3/4" HM F HM1 HM H2 J2 2.0
152 AIRPLANE HANGER SINGLE 3' - 0" 7' - 2" 1 3/4" HM F HM1 HM H2 J2 1.0
153 CORRIDOR SINGLE 3' - 0" 7' - 2" 1 3/4" HM F HM1 HM H1 J1 3.0
176 CHANGING ROOM SINGLE 3' - 0" 7' - 2" 1 3/4" HM F HM1 HM H1 J1 4.0
181 WOMEN'S LOCKER ROOM SINGLE 3' - 0" 7' - 2" 1 3/4" HM F HM1 HM H1 J1 7.0
182 MEN'S LOCKER ROOM SINGLE 3' - 0" 7' - 2" 1 3/4" HM F HM1 HM H1 J1 7.0
185 TOILET / SHOWER SINGLE 3' - 0" 7' - 2" 1 3/4" HM F HM1 HM H1 J1 5.0
188 CORRIDOR SINGLE 3' - 0" 7' - 2" 1 3/4" HM F HM1 HM H1 J1 3.0
192 CORRIDOR SINGLE 3' - 0" 7' - 2" 1 3/4" HM F HM1 HM H1 J1 3.0
1/4" = 1'-0"13
FRAME AND DOOR TYPE
1" = 1'-0"12
HEAD AND JAMB DETAILS
1" = 1'-0"14
THRESHOLD TYPES
90 MIN
1/4" = 1'-0"11
STANDARD PLUMBING FIXTURE AND ACCESSORY MOUNTING
HEIGHTS
3" = 1'-0"
INTERIOR SIGNAGE
3" = 1'-0"15
TYPICAL DETAIL AT SINK COUNTERTOP
3" = 1'-0"16
TYPICAL DETAIL AT SINK COUNTERTOP
STRUCTURAL
ABBREVIATIONS AND NOTES
S-001
RPER
PLAN
NORTH
ACTUAL
NORTH
SPIEZLE ARCHITECTURAL GROUP, INC.SPIEZLE ARCHITECTURAL GROUP, INC.
STRUCTURAL
PLATFORM FRAMING PLAN
S-101
ACTUAL
NORTH
SPIEZLE ARCHITECTURAL GROUP, INC.SPIEZLE ARCHITECTURAL GROUP, INC.
STRUCTURAL
FLOOR RENOVATION PLAN
S-102
STRUCTURAL
SECTIONS AND DETAILS
S-501
ACTUAL
NORTH
SPIEZLE ARCHITECTURAL GROUP, INC.SPIEZLE ARCHITECTURAL GROUP, INC.
FIRE PROTECTION
LEGEND, NOTES & DETAILS
FX001
pdMR
ACTUAL
NORTH
SPIEZLE ARCHITECTURAL GROUP, INC.SPIEZLE ARCHITECTURAL GROUP, INC.
FIRE PROTECTION
FLOOR PLAN
FX101
PLUMBING
ABBREVIATIONS, GENERAL NOTES
& SYMBOLS
P-001 pdTH
PLAN
NORTH
ACTUAL
ACTUAL
NORTH
SPIEZLE ARCHITECTURAL GROUP, INC.SPIEZLE ARCHITECTURAL GROUP, INC.
PLUMBING
UNDERSLAB PIPING PLANS
P-100
ACTUAL
NORTH
SPIEZLE ARCHITECTURAL GROUP, INC.SPIEZLE ARCHITECTURAL GROUP, INC.
PLUMBING
FLOOR PLANS
P-101
DETAILS
P-501 pdTH
PLAN
NORTH
ACTUAL
RISER DIAGRAMS & SCHEDULES
P-601 pdTH
ABBREVIATIONS,
NOTES AND SYMBOLS
MC001
ARFPB
ACTUAL
NORTH
SPIEZLE ARCHITECTURAL GROUP, INC.SPIEZLE ARCHITECTURAL GROUP, INC.
MECHANICAL
DUCTWORK PLANS
DEMOLITION & NEW WORK
M-101
MECHANICAL
DETAILS
M-501
MECHANICAL
SCHEDULES
M-601
ARFPB
SPIEZLE ARCHITECTURAL GROUP, INC.SPIEZLE ARCHITECTURAL GROUP, INC.
DIAMETER
CFM IN IN BHP HP
EF-1 ROOF LOCKERS
TOILET & LOCKER
EXHAUST
905 0.25
CENTRIFUGAL DOME
STYLE
BI CURVED WHEEL 12 DIRECT 1460 0.1 0.25 1 120 1750 ELECTRONIC GREENHECK AE-12-433-A 1,2,3
NOTES:
3. ELECTRONIC SPEED CONTROL
BASIS OF DESIGN
OR APPROVED EQUAL
MOTOR ELECTRICAL
REMARKSSPEED
CONTROL
FAN
MAX
RPM
DRIVE PHASE
MARK LOCATION
TYPE
FAN
RPM
1. ROOF CURB.
NOMINAL
POWER
2. BACKDRAFT DAMPERS
4. BIRD SCREEN
ARRANGEMENT,
ROTATION, AND
DISCHARGE
FAN SCHEDULE
AREA AND/OR
BLDG SERVED
SYSTEM
AND/OR
SERVICE
AIR
FLOW
VOLT
TSP
Db Wb Db Wb
CFM CFM IN MBH MBH °F °F °F °F WATTS CONTROL VOLTS PHASE FLA MCA MCOP
AC-1
CEILING OF CORROSION
CONTROL LOCKERS
CORROSION
CONTROL LOCKERS
COOLING AND
HEATING
725 725 1 40 22.5 87.8 73.8 57.6 56.5 13.6 4" MERV 8 800 CONST VOLUME 208 3 2.8 4 15 AAON H3-ARB-8-0-161C-12F
NOTES:
1. HORIZONTAL UNIT
2. CONSTANT VOLUME, 100% OA
3. FULL DIGITAL CONTROL SYSTEM
4. UNIT THERMOSTAT WITH 7 DAY TIMECLOCK
5. MODULATING HOT GAS REHEAT AND DIGITAL HUMIDITY CONTROLS
6. TWO POSITION ELECTRIC OUTSIDE AIR DAMPER
INDOOR UNIT SPLIT SYSTEM AIR CONDITIONER ELECTRIC SCHEDULE
MARK LOCATION
AREA AND/OR
BLDG SERVED
TYPE
MIN NET
TOTAL
CAPACITY
MIN NET
SENS
CAPACITY
COOLING CAPACITY
AIR
FILTER
MARK
NO
BASIS OF DESIGN
LAT SYSTEM
EER
INDOOR FAN
TOTAL
SUPPLY
AIR
FLOW
CIRCUIT
ELECTRICAL DATA
EAT
MIN.
OUTSIDE
AIR
FLOW
EXT
STATIC
PRESSURE
FAN
POWER
CFM °F BTUH BTUH Ø" Ø" HP
GDH-1 ABOVE CEILING LOCKER ROOM
N. GAS, INDOOR, SEPERATED
COMBUSTION, POWER VENTED
725 10 75,000 60,000 4" 1" 0.02 1 115 72 MODINE DFS-75
1. PROVIDE WITH SPARK IGNITION, VERTICAL LOUVERS, THERMOSTAT, SUSPENSION KIT AND AUTOMATIC SHUTOFF VENT DAMPER.
2. INSTALL PER THE MANUFACTURES INSTALLATION INSTRUCTIONS.
3. PROVIDE ABOVE ROOF CONCENTRIC FLUE/COMBUSTION VENT, BELOW ROOF CONCENTRIC VENT ADAPTER AND B LISTED INDOOR VENT WITH DRIP LEG AND CLEANOUT AND COMBUSTION AIR PIPING.
4. 409 SS STEEL HEAT EXCHANGER AND BURNER
4. PROVIDE GAS MODULATING CONTROL PACKAGE AND SPACE AND DUCT MOUNTED TEMPERATURE SENSORS. CONTROL IS TO PROVIDE DUCT SETPOINT RESET BY SPACE TEMPERATURE.
5. PROVIDE ENABLE CONTACTS BASED ON AC UNIT OPERATING
6. CONTROL PACKAGE TO BE BACNET COMPLIANT
7. CONDENSATE CONNECTION DRAIN KIT.
NOTES:
GAS
CONNECTION
FAN MOTOR
INSTALLED
WEIGHT
LBS
BASIS OF DESIGN
PHASE VOLT
MARK LOCATION
AREA AND/OR
BLDG SERVED
TYPE
AIR
FLOW
EAT
HEATING
INPUT
THERMAL
OUTPUT
COMBUSTION AIR AND
VENT OUTLET SIZE
NATURAL GAS DUCT HEATER SCHEDULE
NOMINAL
POWER
MBH °F °F HP
ACCU-1 GRADE
CORROSION
CONTROL LOCKERS
AC-1
DIGITAL
SCROLL
41.1 410a 40 95 13.6 1 3 208 1 0.33 1 120 -----
NOTES:
AIR COOLED CONDENSING UNIT SCHEDULE (AIR CONDITIONING SERVICE)
MARK LOCATION
AREA
AND/OR
BLDG SERVED
SYSTEM
AND/OR
SERVICE
TYPE
MIN
REFRIGERATION REFRIGERANT
MAX
SUCTION
TEMP @
COMP
OA
TEMP
MIN
SYSTEM
EER
COMPRESSOR MOTOR CONDENSER FAN MOTOR
REMARKS
VOLT
1. UL-RATED STARTERS SHALL BE FURNISHED BY MANUFACTURER OF EQUIPMENT.
2. kW/TON INCLUDES CONDENSER FANS.
# COMP PHASE VOLT # FANS PHASE
IN WG IN x IN IN IN x IN
SD-1
SUPPLY
DIFFUSER
SEE
DRAWINGS
0.070 CEILING 24 x 24
SEE
DRAWINGS
SEE
DRAWINGS
20 NONE ALUMINUM WHITE TITUS TMS 9 LOUVERED FACE
NOTES:
1. SEE FLOOR PLAN FOR THROW PATTERN. 6. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR CEILING TYPE.
2. SEE DETAIL FOR DAMPER IN BRANCH DUCT SERVING EACH DIFFUSER. 7. THROW VALUE IN FEET FOR 100 FPM TERMINAL VELOCITY.
3. PROVIDE SQUARE TO ROUND ADAPTER. 8. PROVIDE FLEXIBLE DUCT WHERE SHOWN ON DRAWINGS AT DIFFUSER NECK SIZE,
4. INSTALL ALL AIR DEVICES IN ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS. 9. PROVIDE 0.5 INCH FIBERGLASS WITH VAPOR BARRIER ON BACKPAN,
5. MAX NC RATING BASED ON 10dB ROOM ABSORBTION.
FINISH
AIR DEVICE SCHEDULE (SUPPLY)
REMARKSDAMPERMOUNTING ACCESSORIES
PANEL/
FRAME
SIZE
NECK
SIZETYPE
MAX APD BASIS OF DESIGN
OR APPROVED EQUAL
NCMARK CONSTRUCTIONAIR FLOW
DUCT
SIZEMIN MAX
CFM CFM IN WG IN x IN IN x IN
EG-1
EXHAUST
REGISTER
0 175 0.060 CEILING
SEE
DRAWINGS
SEE
DRAWINGS
25 NONE WHITE TITUS 45F
EG-2
EXHAUST
REGISTER
0 800 0.006 CEILING
SEE
DRAWINGS
SEE
DRAWINGS
25 NONE WHITE TITUS PAR
NOTE:
PROVIDE SQUARE TO ROUND ADAPTER.
AIR DEVICE SCHEDULE (RETURN AND EXHAUST)
MARK TYPE
PANEL/FRAME
SIZE
NECK
SIZE
AIR FLOW MAX
APD NCMOUNTING DAMPER FINISH
BASIS OF DESIGN
OR APPROVED EQUAL
ELECTRICAL
SYMBOLS, LEGEND,
AND ABBREVIATIONS
EC001
MRMR
PLAN
NORTH
ACTUAL
NOTES
EC002
MRMR
PLAN
NORTH
ACTUAL
DEMOLITION PLAN
ED101
MRMR
PLAN
NORTH
ACTUAL
ACTUAL
NORTH
SPIEZLE ARCHITECTURAL GROUP, INC.SPIEZLE ARCHITECTURAL GROUP, INC.
ELECTRICAL
LIGHTING PLAN
EL101
MJRMJR
ACTUAL
NORTH
SPIEZLE ARCHITECTURAL GROUP, INC.SPIEZLE ARCHITECTURAL GROUP, INC.
ELECTRICAL
POWER PLAN
EP101
ACTUAL
NORTH
SPIEZLE ARCHITECTURAL GROUP, INC.SPIEZLE ARCHITECTURAL GROUP, INC.
ELECTRICAL
SIGNAL PLAN
EY101
DETAILS AND PANEL SCHEDULES
E-501
MRMR
| GI001 |
| GI001 |