Repair and Test Fuel System, Point Reyes National Seashore
Repair and Test Fuel System
Point Reyes National Seashore
STATEMENT OF WORK (SOW)
STATEMENT OF WORK
1.0 Background
2.0 Scope
3.0 Objectives
4.0 Tasks
5.0 Delivery
6.0 Government-Furnished Property
7.0 Site-Specific Safety and Health Plan
8.0 Place of Performance
9.0 Period of Performance
10.0 Area Maps
11.0 AST and PMC Fuel System Cut Sheets
1.0 Background
Point Reyes National Seashore (PRNS), located in Marin County, California, has a requirement for the repair and testing of a marine gasoline fueling system and Above Ground Storage Tank (AST). This PMC Fuelhouse Marine fuel dispensing system and Hoovervault AST is operated by the Park in support of its Visitor and Resource Protection Division’s Marine Program.
The three-year-old system consists of a 1,000-gallon AST, transfer pumps, filling/test well ports, fuel gauges and alarms, ~100’ double-wall containment supply line, and a cabinet-mounted marine dispensing unit. System currently will not pass a pressure test as required for permitting by Bay Area Air Quality Management District (BAAQMD).
System is otherwise in good operating condition.
This project will diagnose, service, repair, or replace any components needed to ensure the system is in full compliant operational condition. Vendor will ensure system is fully compliant with any Federal, State, or Local regulations regarding air quality to pass testing for permitting with BAAQMD. Vendor will provide park with a certificate or other document that facilitates permitting with regulatory agencies.
2.0 Scope
1) Diagnose, service, repair, or replace any components needed to ensure the system is in full compliant operational condition.
2) Ensure system is fully compliant with any Federal, State, or Local regulations regarding air quality to pass testing for permitting with the BAAQMD.
3) Provide Park with a certificate or other document that facilitates permitting with regulatory agencies.
3.0 Objectives
Repair equipment pressure.
Test equipment pressure as required by the BAAQMD.
Provide documentation necessary for permit application.
4.0 Tasks
Refer to the cut sheets beginning on page 5 to complete the following tasks:
A. Diagnose what is preventing the equipment from maintaining pressure.
B. Repair or replace components as needed.
C. Pressure test equipment to ensure system is fully compliant with any Federal, State, or Local regulations regarding air quality to pass testing for permitting with the BAAQMD.
D. Provide documentation necessary for permit application.
5.0 Delivery
Include any relevant product literature, maintenance guides, and schedules.
Payment will only be made for actual services rendered, as verified by the Government.
Payment requests must be submitted electronically through the U. S. Department of the Treasury's Invoice Processing Platform System (IPP) at https://www.ipp.gov/.
6.0 Government-Furnished Property
No government-furnished property is to be provided to the contractor.
7.0 Site-Specific Safety and Health Plan
Prior to work commencing on site, a site-specific safety and health plan shall be prepared covering on-site work to be performed by the contractor and all subcontractors. The prime contractor shall be responsible for development, implementation, and oversight of the site-specific plan. The level of detail provided in the site-specific safety and health plan shall be tailored to the type of work, complexity of operations to be performed, and hazards anticipated. The site-specific safety and health plan shall address, in as much detail as possible, anticipated tasks, their related hazards, and anticipated control measures.
Work performed under this contract shall comply with applicable federal, state, and local safety and occupational health laws and regulations, including adherence to any local government health orders in effect to reduce the rate of transmission of Novel Coronavirus Disease 2019 (“COVID-19”).
8.0 Place of Performance
The place of performance is located within Point Reyes National Seashore at:
1 Sacramento Landing Road Inverness, CA 94937.
The system is located on the dock at Sacramento Landing at Tomales Bay.
The GPS coordinates are: 38° 08'57'N 122° 54'19'W
Work shall coincide with Park business hours, between 7:00 am to 4:00 pm.
The site point of contact is Jeff Jewhurst, Roads Supervisor- (415) 464-5158, jeffrey_jewhurst@nps.gov.
9.0 Period of Performance
The period of performance is estimated to be between September 15, 2021 to December 15, 2021, but will be determined at time of award.
POINT REYES NATIONAL SEASHORE SACRAMENTO LANDING
AST and FUELING SYSTEM SITE MAP
Point Reyes National Seashore Headquarters
1 Bear Valley Rd Point Reyes Station, CA 94956
10.0 Site Maps
Sacramento Landing AST Fueling System
1 Sacramento Landing Road Inverness, CA 94937
Travel time between park headquarters and site is approx. 20 minutes.
Sacramento Landing AST Fueling System Site
1 Sacramento Landing Road Inverness, CA 94937
HOOVER VAULT™
FIRE RATED DOUBLE-WALL TANKS
Containment Solutions, Inc. (CSI) provides safe, aff ordable solutions for the storage of fl ammable and combustible liquids.
If you are concerned about the eff ects fuel storage has on your bottom line, look at the advantages of aboveground fi re-protected storage tanks.
Our steel Hoover Vault™ tanks meet the requirements of all national fi re codes for fi re-rated aboveground storage tanks and are labeled according to Underwriter’s Laboratories Standard 2085 “Insulated, Protected Secondary Containment”.
Vault tanks utilize patented designs with lightweight fi reproofi ng materials, applied in the interstitial space of UL 142 double-wall tanks. These materials ensure that the inner tank is protected from the eff ects of fi re. This design allows both the inner and the outer tanks to be pressure tested at the factory and in the fi eld.
In addition, the fi reproofi ng materials allow liquid to migrate through to the monitoring tube, so leaks from the inner tank are detected. Rectangular vault tanks are space-saving in design.
ADVANTAGES:
• UL 2085 listed for insulated, protected secondary containment
– Two-hour fi re rating using lightweight concrete
– True 360º “pressure testable” secondary containment
– Vehicle impact protection
– Ballistic Protection
– Built-in leak detection tube
• Meets requirements of all National Fire
Codes
– UFC Articles 52 and 79, Appendix II and Standard A-ll-F-l
– NFPA Standards 30 and 30A
– BOCA
– SBCCI
• CARB Certifi ed for Stage I and II Vapor
Recovery
• Underwriter’s Laboratories of Canada
(ULC) Listed
• 30-Year warranty
• Factory installed equipment packages:
– Motor fuel dispensing, emergency generator/fuel oil, used oil collection (others available upon request)
• Standard Tank Capacities 250 to 20,000 gallons (larger sizes up to 30,000 gallons are available)
A
11.0 AST and PMC Fuel System Cut Sheets
Comp1 Highlight
5150 Jeff erson Chemical Road • Conroe, TX 77301 • Phone: (936) 756-7731 • www.containmentsolutions.com Copyright © • Containment Solutions, Inc. • All Rights Reserved • January 2014 • Pub. No. TNK 1504F
STANDARD TANK SIZES
CAPACITY
(GALLONS) LENGTH WIDTH HEIGHT SHIPPING
WEIGHT
250 4’9” 3’7” 3’9” 3,400 LBS.
500 6’8” 4’7” 3’9” 5,400 LBS.
1,000 7’9” 5’7” 4’9” 8,500 LBS.
1,500 10’7” 5’11” 4’9” 10,250 LBS.
2,000 11’10” 6’11” 4’9” 12,500 LBS.
2,500 9’5” 6’11” 7’1” 13,100 LBS.
3,000 9’8” 7’11” 7’1” 15,800 LBS.
4,000 12’8” 7’11” 7’1” 19,000 LBS.
5,000 15’8” 7’11” 7’1” 23,700 LBS.
6,000 18’8” 7’11” 7’1” 27,000 LBS.
8,000 24’8” 7’11” 7’1” 33,450 LBS.
10,000 30’8” 7’11” 7’1” 42,600 LBS.
12,000 36’8” 7’11” 7’1” 48,750 LBS.
15,000 45’8” 7’11” 7’1” 60,400 LBS.
20,000 60’8” 7’11” 7’1” 76,900 LBS.
VAULT TANK OPTIONS
• UL 142 listed double-wall inner tank, providing triple containment
• Larger tank capacities up to 30,000 gallons
• 3,000 PSI concrete
• Stainless steel inner tanks
• Dual compartments for multi-purpose use available in all capacities
• Lifting lugs and pump mounting brackets
• Fibervault® exterior coatings
• Internal coatings compatible with aviation fuels and other chemicals
Ground Level Spill Box
Steps and Handrail Assembly
The Fuelhouse marine dispensers are designed and built to solve the unique challenges of the saltwater and freshwater marine environment while providing a clean and compact appearance. The attractive design provides the sophistication you want and the simplicity your customers appreciate. The high speed fueling capability of the Fuelhouse series saves time, and therefore, money by minimizing the time vessels occupy the fueling dock. The Fuelhouse marine dispenser is purpose built for the marine fueling environment and provides years of reliable operation.
The Fuelhouse is a listed dispenser that incorporates an internal hose reel capable of managing and protecting the long lengths of hose re-quired in many marine facili-ties. Valuable fuel dock space is saved by eliminating the need for an external reel.
The compact design mini-mizes both its footprint and height to reduce its presence on the fueling dock. With a height under 4 feet, the Fu-elhouse dispenser also im-proves safety/awareness and marina appearance by limit-ing visual obstructions.
Appearance matters. By using only high quality stainless steel, the Fuel-house marine dispenser will retain its attractive finish for many years. The stainless steel chassis is fully welded to maintain rigidity and durability throughout the life of the dispenser. A black powder-coat finish is applied to the chassis for added protection. Corrosion resistance is not limited to the exterior.
From the aluminum meter and brass valve to the fully conformal coated electronics, only components suitable for long term use in a marine environment are used for the internal hydraulic and electrical systems.
The Fuelhouse has the flexibility to operate in either a standalone or remote control application. The dispenser is compatible with most con-sole/card systems using either the standard hardwire or optional 2-wire interface. The 2-wire interface allows communication with newer con-trol devices using a RS-485 connection, enabling features such as re-mote price setting and totals retrieval.
35 & 60 GPM configurations
Liquid Controls PD Meter
1” or 1½” internal reel op-tions
Electric or spring rewind
Above or below grade supply inlet
Internal filtration
Resale accurate
Optional communications in-terface
Stainless steel enclosure
Commercial or retail elec-tronic display
Powder coated welded stainless steel chassis
Brushed finish stainless steel panels
Fuelhouse Marine Dispenser www.pmc-ga.com
Fuel Dispensing and Metering Solutions
PUMP MEASURE CONTROL
MODELS
FH-510-MA-1M – Fuelhouse dispenser with 1” stainless reel, spring rewind.
FH-510-MA-2M – Fuelhouse dispenser with 1” stainless reel, power rewind.
FH-515-MA-3M – Fuelhouse dispenser with 1-1/2” stainless reel, spring rewind.
FH-515-MA-4M – Fuelhouse dispenser with 1-1/2” stainless reel, power rewind.
PERFORMANCE
FH-510 series – 35 GPM FH-515 series – 60 GPM
· Actual delivery rates will vary, depending upon the design of the fuel system, length of hose, type of nozzle, etc.
CABINET
Chassis: Powder coated 304 stainless steel.
Panels: Brushed finish 316 stainless steel.
DISPLAYS
Six digit backlight LCD displays with UV blocking acrylic windows.
Capacities Retail Commercial
Total Sale 9999.99 9999.99 Total Volume 9999.99 N/A Unit Price 0.001– 9.999 N/A
Seven digit electromechanical non-resettable totalizer.
FILTRATION
Hydrosorb single or dual element (Dependant on flow rate) spin-on.
METER
Liquid Controls high flow, rotary motion, positive displacement meter.
SOLENOID
FH-510 Series - 1-1/2” normally closed.
FH-515 Series - 2” normally closed.
SUPPLY CONNECTION
FH-510 Series - 1-1/2” NPT.
FH-515 Series - 2” NPT.
MAXIMUM WORKING PRESSURE
50 PSI.
VOLTAGE AND FREQUENCY
120VAC/60 Hz (240VAC/50 Hz optional)
PULSE OUTPUT (standard) Programmable pulse output provided for connection to console / card access system. Selectable for money or volume pulse. Volume pulse resolution: 10 or 100 pulses per volume.
COMMUNICATIONS INTERFACE (optional) EIA-485 communications interface for connection to console / card access system.
APPROVALS
ETL Listed. — Weights and Measures sealable for retail sale of fuel.
NTEP Certificate number: 04-018
HOSE
None provided. Customer supplied hoses can be installed upon assembly.
FH-510-MA-1M – Maximum capacity – 1” x 85 feet.
FH-510-MA-2M – Maximum capacity – 1” x 130 feet.
FH-515-MA-3M – Maximum capacity – 1-1/2” x 50 feet.
FH-515-MA-4M – Maximum capacity – 1-1/2” x 85 feet.
NOZZLE COMPATABILITY
11A Style, 7H Style, and 1290 Style through 1-1/2”. Contact factory for other types.
SPECIFICATIONS
Fuelhouse Marine Dispenser