Atch 2 GPNC Heating Water System Drawings.pdf

PDF 4 MB Posted

Attached to
GPNC Replace Water Heating System Federal contract opportunity
Solicitation number
140F0121R0031
Issued by
Department of the Interior Fish and Wildlife Service

About this file

This is a solicitation for replacement of a water heating system at the Great Plains Nature Center. The project requires removal of existing HVAC boilers, pumps, valves and installation of new pumps, valves, and controls. Work includes removing old equipment, installing new hydronic pumps, specialties, and two-way control valves, as well as HVAC controls upgrades and emergency boiler connections. The federal agency is the Department of the Interior Fish and Wildlife Service.

View the file

Other files for this federal contract opportunity

Other files attached to GPNC Replace Water Heating System, newest first.
File Type Posted
Sol_140F0121R0031_Amd_0002.pdf PDF
Sol_140F0121R0031_Amd_0001.pdf PDF
Amend_0001_Atch_1_Example_Comissioning_0001.pdf PDF
Atch 4 GPNC Water Heating System DBA Det Wage Rate.pdf PDF
Sol_140F0121R0031.pdf PDF
Atch 3 GPNC Water Heating System Submittal List.pdf PDF
Atch 5 GPNC Water Heating System Past Perf Quest.doc DOC document
Atch 1 GPNC Heating Water System Specs.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Environment & Infrastructure Solutions, Inc.

4600 E. WASHINGTON STREET, SUITE 600

PHOENIX, ARIZONA 85034 / PHONE: 602-733-6000

6232 EAST 29TH ST N,

WICHITA, KS 67220

3720192002

JAY MARTIN

(615) - 333 - 0630 jay.martin@woodplc.com

WOOD PROJECT NUMBER:

PROJECT MANAGER CONTACT:

PHONE:

EMAIL:

EMILIO GONZALEZ

(602) - 733 - 6008 emilio.gonzalez@woodplc.com

MECHANICAL CONTACT:

PHONE:

EMAIL:

STEVEN KAIN

(602) - 733 - 6139 steven.kain@woodplc.com

ELECTRICAL CONTACT:

PHONE:

EMAIL:

L

I

C

E N

S

E

D

K

A

NS

A

S

P

R

O

F

E

I

O

N A L

G

26855

E

M

I

L

I

O

GO

N

Z

A

L

E

Z

07/11/19

AutoCAD SHX Text

FISH AND WILDLIFE SERVICE

AutoCAD SHX Text

UNITED STATES DEPARTMENT OF THE INTERIOR

AutoCAD SHX Text

REGION 6 ENGINEERING - DENVER, COLORADO

AutoCAD SHX Text

DESIGNED:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DRAWN:

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

SHEET 1 OF

AutoCAD SHX Text

CHECKED:

AutoCAD SHX Text

VICINITY MAP

AutoCAD SHX Text

NO SCALE

AutoCAD SHX Text

OR

AutoCAD SHX Text

RI

AutoCAD SHX Text

ME

AutoCAD SHX Text

RT

AutoCAD SHX Text

PA

AutoCAD SHX Text

DE

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text

NT

AutoCAD SHX Text

TE

AutoCAD SHX Text

IN

AutoCAD SHX Text E

AutoCAD SHX Text

TH

AutoCAD SHX Text

FISH AND WILDLIFE

AutoCAD SHX Text

SERVICE

AutoCAD SHX Text U.S.

AutoCAD SHX Text

U.S. FISH & WILDLIFE SERVICE

AutoCAD SHX Text

SERVICE

AutoCAD SHX Text

FISH AND WILDLIFE

AutoCAD SHX Text

TH

AutoCAD SHX Text

ME

AutoCAD SHX Text

RT

AutoCAD SHX Text

PA

AutoCAD SHX Text

DE

AutoCAD SHX Text

NT

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text

OR

AutoCAD SHX Text

RI

AutoCAD SHX Text

TE

AutoCAD SHX Text

IN

AutoCAD SHX Text E

AutoCAD SHX Text U.S.

AutoCAD SHX Text

APPROVAL SIGNATURES

AutoCAD SHX Text

ANY PRINT ACCOMPANYING THIS INVITATION TO BID MAY BE A REDUCED

AutoCAD SHX Text

REPRODUCTION OF THE WORKING DRAWINGS. IF LINE BELOW DOES NOT

AutoCAD SHX Text

MEASURE SIX INCHES IN LENGTH, THE INDICATED SCALES ARE TO BE

AutoCAD SHX Text

ADJUSTED ACCORDINGLY.

AutoCAD SHX Text

%%UNOTE TO BIDDERS:%%

AutoCAD SHX Text

REGIONAL ENGINEER

AutoCAD SHX Text

ASS'T. REGIONAL DIR.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

PROGRAM SUPERVISOR

AutoCAD SHX Text

FACILITIES

AutoCAD SHX Text

CULTURAL RESOURCES

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

GREAT PLAINS NATURE CENTER

AutoCAD SHX Text

SEDGWICK COUNTY

AutoCAD SHX Text

KANSAS

AutoCAD SHX Text

GREAT PLAINS NATURE CENTER HVAC HEATING WATER REPLACEMENT

AutoCAD SHX Text

EPG / SJK

AutoCAD SHX Text

TW / TM

AutoCAD SHX Text

SM / ER

AutoCAD SHX Text 06/10/19

AutoCAD SHX Text

6R-KS-1169-18-04(B)

AutoCAD SHX Text

AutoCAD SHX Text

GREAT PLAINS NATURE CENTER

AutoCAD SHX Text

GREAT PLAINS NATURE CENTER HEATING

AutoCAD SHX Text SHEET# SHEET NAME COVER SHEET M0.1 MECHANICAL LEGEND, SHEET LIST, AND ABBREVIATIONS MECHANICAL LEGEND, SHEET LIST, AND ABBREVIATIONS M0.2 MECHANICAL GENERAL NOTES MECHANICAL GENERAL NOTES M1.0 MECHANICAL DEMOLITION PLAN - CENTRAL PLANT MECHANICAL DEMOLITION PLAN - CENTRAL PLANT M2.0 MECHANICAL NEW PLAN - CENTRAL PLANT MECHANICAL NEW PLAN - CENTRAL PLANT M2.1 MECHANICAL NEW PLAN - AIR HANDLING UNITS MECHANICAL NEW PLAN - AIR HANDLING UNITS M3.0 MECHANICAL ONE LINE DIAGRAMS MECHANICAL ONE LINE DIAGRAMS M4.0 MECHANICAL DETAILS MECHANICAL DETAILS M4.1 STRUCTURAL AND ARCHITECTURAL DETAILS AND MECHANICAL SCHEDULES STRUCTURAL AND ARCHITECTURAL DETAILS AND MECHANICAL SCHEDULES M5.0 I/O SUMMARY AND CONTROL DIAGRAM I/O SUMMARY AND CONTROL DIAGRAM E0.1 ELECTRICAL SYMBOLS AND LEGEND ELECTRICAL SYMBOLS AND LEGEND E1.0 ELECTRICAL PANEL SCHEDULES AND ONE LINES ELECTRICAL PANEL SCHEDULES AND ONE LINES E2.0 ELECTRICAL DEMOLITION PLAN ELECTRICAL DEMOLITION PLAN E3.0 ELECTRICAL NEW WORK PLAN ELECTRICAL NEW WORK PLAN S1.0 STRUCTURAL DETAILSSTRUCTURAL DETAILS

AutoCAD SHX Text

WATER SYSTEM REPLACEMENT

amercer Text Box N/A amercer Text Box N/A amercer Text Box

SAFETY/IND HYGIENIST

WALL MOUNTED OSCILLATING FAN

CEILING PADDLE FAN

EXIST HOT WATER FIN TUBE UNIT TAG

(FOR 4-WAY THROW ARROWS NOT SHOWN)

DIRECTION SHOWN BY ARROWS

CEILING SUPPLY DIFFUSER W/ THROW

SEQUENCE NUMBER

LENGTH OF ACTIVE FIN TUBE

CFM

NITROGEN DIOXIDE SENSOR

CO

CARBON MONOXIDE SENSOR

DOOR LOUVER

FLEXIBLE CONNECTOR

DIRECTION OF AIR FLOW EXHAUST

HOT WATER COIL

FINTUBE DESIGNATION

MBH

SMOKE DETECTOR

TERMINAL UNIT, VARIABLE VOLUME WITH

PUMP

STARTER/DISCONNECT

ROOF VENTILATOR, EXHAUST

FLEXIBLE DUCT

SQUARE ELBOW WITH TURNING VANES

CONNECT TO EXISTING

THERMOSTAT OR THERMISTOR

MOTORIZED DAMPER, OPPOSED BLADE

MOTORIZED DAMPER, PARALLEL BLADE

FIRE DAMPER

SMOKE DAMPER

DIRECTION OF AIR FLOW

INLINE FAN

CENTRIFUGAL FAN

PROPELLER FAN

TERMINAL UNIT, VARIABLE VOLUME

UNIT HEATER

FINTUBE RADIATION AND ENCLOSURE

SUPPLY GRILLE, DIFFUSER

RETURN GRILLE, REGISTER

DIFFUSER, REGISTER OR GRILLE

SYMBOL PER ABBREVIATION LIST

FD

SD

EQUIPMENT SEQUENCE NUMBER

HUMIDISTAT

SWITCH

M

M

T

H

S

S

AUTOMATIC AIR VENT WITH ISOLATION VALVE

BOILER DRAIN VALVE W/ HOSE BIB

BALL VALVE IN VERTICAL

DN

UP

NEZV

ABBREVIATIONS

BUCKET TRAP

STEAM MONITOR

THREE-WAY AUTOMATIC CONTROL VALVE

THREE-WAY AUTOMATIC CONTROL VALVE

TWO-WAY AUTOMATIC CONTROL VALVE

TWO-WAY AUTOMATIC CONTROL VALVE

MECHANICAL SYMBOLS

COMBINATION FLOW MEASURING/

BALANCING VALVE (CIRCUIT SETTER)

GATE VALVE

GLOBE VALVE

PLUG VALVE

CHECK VALVE

SAFETY RELIEF VALVE

STRAINER W/BALL DRAIN VALVE, HOSE

BIB AND CAP (GATE VALVE FOR STEAM)

UNION AS DICTATED BY PIPE SIZE

PIPE END CAP

PRESSURE GAUGE W/BALL VALVE

(GATE VALVE AND SIPHON FOR STEAM)

THERMOMETER

TEMPERATURE/PRESSURE WELL

("PETE'S PLUG")

MANUAL AIR VENT

FLEXIBLE PIPE CONNECTION

VIBRATION ISOLATOR

PIPE GUIDE

DIRT LEG

DIRECTION OF FLOW OF PIPE

PIPE PITCH UP IN DIRECTION OF FLOW

PIPE PITCH DOWN IN DIRECTION OF FLOW

FLOAT AND THERMOSTATIC TRAP

THERMOSTATIC TRAP

PIPING SYMBOLS DUCTWORK SYMBOLS

VD

VD

VD

VD

VD

SUPPLY

EXHAUST/RETURN

VD

VD

SQUARE ELBOW

W/TURNING VANES

RADIUS ELBOW

SPLIT TAKE-OFF

W/ BRANCH

DAMPERS

BULLHEAD SPLIT

TAKE-0FF

BULLHEAD

TEE

OFFSET

VD

CEILING DIFFUSER

OR GRILLE W/

FLEXIBLE DUCT

PRESSURE REDUCING VALVE

BALL VALVE

BUTTERFLY VALVE

OS&Y VALVE

OS&Y VALVE IN VERTICAL (PLAN)

NONELECTRIC ZONE VALVE

PRESSURE SWITCH

TEMPERATURE SENSOR

FLOW SWITCH, FREEZESTAT

SUPPLY DUCT UP

SUPPLY DUCT DOWN

RISE(R) OR DROP(D)

RETURN/EXHAUST

DUCT UP

RETURN/EXHAUST

DUCT DOWN

END SWITCH

AIR FLOW SWITCH

PIPE TEE FROM TOP

PIPE TEE FROM BOTTOM

PIPE RISE

PIPE DROP

(ELECTRIC OR DDC)

(PNEUMATIC)

(ELECTRIC OR DDC)

(PNEUMATIC)

PIPE UP TO FINTUBE

RADIATION ON FLOOR ABOVE

COCK

STRAINER W/ BLOW OFF

AIR SEPARATOR

S

PRESSURE REGULATING VALVE

REDUCED PRESSURE BACKFLOW PREVENTER

FUSOMATIC VALVE

DOOR UNDERCUT

DRAWING WHERE DETAIL IS DRAWN

DETAIL NUMBER

DETAIL NUMBER

THREE WAY VALVE

FLANGE AS DICTATED BY PIPE SIZE

S

M

@ AT

(E) EXISTING

(N) NEW

A AMP

ABS ACRYLONITRILE BUTADIENE

STYRENE PLASTIC

ABV ABOVE

AC AIR CONDITIONING

AD ACCESS DOOR

ADA AMERICANS WITH DISABILITIES

ACT

ADS AIR DIRT SEPARATOR

AF AIR FILTER

AFF ABOVE FINISHED FLOOR

AFM AIR FLOW MEASURING STATION

AHU AIR HANDLING UNIT

AL ACOUSTICAL LINER

AMB AMBIENT

AP ACCESS PANEL

APD AIR PRESSURE DROP

APPROX APPROXIMATELY

AS AIR SEPARATOR

ASME AMERICAN SOCIETY OF

MECHANICAL ENGINEERS

ASSY ASSEMBLY

ATC AUTOMATIC TEMPERATURE

CONTROL

ATT ACOUSTICAL ATTENUATOR

AV AUTOMATIC VENT

AW ACID WASTE

AWV ACID WASTE VENT

B BOILER

BDD BACKDRAFT DAMPER

BHP BRAKE HORSEPOWER

BLDG BUILDING

BOT BOTTOM

BTUH BTU PER HOUR

C CENTERLINE

CA COMPRESSED AIR

CAP CAPACITY

CD CONDENSATE DRAIN

CDWR CONDENSER WATER RETURN

CDWS CONDENSER WATER SUPPLY

CDWS&R CONDENSER WATER SUPPLY &

RETURN

CF CEILING FAN

CFM CUBIC FEET PER MINUTE

CH CHILLER

CHWP CHILLED WATER PUMP

CHWR CHILLED WATER RETURN

CHWS CHILLED WATER SUPPLY

CHWS&R CHILLED WATER SUPPLY &

RETURN

CLG CEILING

CO CLEAN OUT, CARBON MONOXIDE

COL COLUMN

CONC CONCRETE

COND CONDENSATE

CONN CONNECTION

CONT CONTINUATION

CONV CONVECTOR

CP CONTROL PANEL, CONDENSATE

PUMP

CPT CONDENSATE PUMP TRAP

CSA CANADIAN STANDARDS

ASSOCIATION

CT COOLING TOWER

CU CONDENSING UNIT

CUH CABINET UNIT HEATER

CV CONTROL VALVE

Cv CONTROL VALVE RATING

CVT CONSTANT VOLUME AIR

TERMINAL

CW COLD WATER

D DRAIN

dB DECIBELS

DB DRY BULB

DC DRY COOLER

DDC DIRECT DIGITAL CONTROL

Ø, DIA DIAMETER

DIFF DIFFERENTIAL, DIFFUSER

DISCH DISCHARGE

DN DOWN

DOM DOMESTIC

DP DIFFERENTIAL PRESSURE

DWG DRAWING

DWGS DRAWINGS

E EXHAUST GRILLE

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EC ELECTRICAL CONTRACTOR

EDR EQUIVALENT DIRECT

RADIATION

EER ENERGY EFFICIENT RATIO

EF EXHAUST FAN

EFF EFFICIENCY

ELEC ELECTRIC, ELECTRICAL

ELEV ELEVATION

ENT ENTERING

EPDM ETHYLENE PROPYLENE DIENE

MEMBRANE

EQUIP EQUIPMENT

ESP EXTERNAL STATIC PRESSURE

ET EXPANSION TANK

EVAP EVAPORATOR

EWC ELECTRIC WATER COOLER

EWT ENTERING WATER TEMP

EXH EXHAUST

EXIST EXISTING

EXT EXPANSION TANK

EXP EXPANSION

F FAN, DEGREES FAHRENHEIT

FA FRESH AIR

FAI FRESH AIR INTAKE

FBG FURNISHED BY GOVERNMENT

FC FLEX CONNECTION

FCO FLOOR CLEANOUT

FD FIRE DAMPER, FLOOR DRAIN

FF FINISH FLOOR

FIX FIXTURE

FLA FULL LOAD AMPS

FLR FLOOR

FOB FLAT ON BOTTOM

FOT FLAT ON TOP

FS FLOAT SWITCH

FTR FIN TUBE RADIATION

FZ FREEZESTAT

G GAS

GA GAUGE

GAL GALLONS

GALV GALVANIZED

GC GENERAL CONTRACTOR

GP GENERAL PURPOSE

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GR GLYCOL RETURN

GRH GRAVITY RELIEF HOOD

GS GLYCOL SUPPLY

GV GATE VALVE

GSM GALVANIZED SHEET METAL

GW GREASE WASTE

GWV GREASE WASTE VENT

GYP GYPSUM WALLBOARD

HC HEATING COIL

HOA HANDS-OFF-AUTOMATIC

HW HOT WATER

HWR HOT WATER RECIRCULATED

HOR HORIZONTAL

HP HORSEPOWER, HIGH

PRESSURE

HPC HIGH PRESSURE COND

HPS HIGH PRESSURE STEAM

(16 PSI TO 150 PSI)

HR HOUR

HT HEIGHT

HUMID HUMIDIFIER, HUMIDITY

HV HEATING AND VENTILATING

UNIT

HVAC HEATING, VENTILATING AND

AIR CONDITIONING

HHW HEATING HOT WATER

HHWP HEATING HOT WATER PUMP

HHWR HEATING HOT WATER RETURN

HHWS HEATING HOT WATER SUPPLY

HHWS&R HEATING HOT WATER SUPPLY

& RETURN

HX HEAT EXCHANGER

HZ HERTZ

IBR HYDRONICS INSTITUTE

ID INSIDE DIAMETER

IN INCHES

INDIR INDIRECT WASTE

KW KILOWATT

L LENGTH, LOUVER

LAT LEAVING AIR TEMP

LD LIQUIFIED PETROLEUM

LDB LEAVING DRY BULB

LF LINEAR FEET

LG LONG

LOC LOCATION, LOCATED

LP LIQUEFIED PROPANE

LPC LOW PRESSURE COND

LPS LOW PRESSURE STEAM

(15 PSI OR LESS)

LRA LOCKED ROTOR AMPS

LVG LEAVING

LWB LEAVING WET BULB

LWT LEAVING WATER TEMP

M MECHANICAL

MANUF MANUFACTURER

MAX MAXIMUM

MAX PD MAXIMUM PRESSURE

DROP

MBH 1000 BTU PER HOUR

MBU 1000 BTU

MCA MAXIMUM CIRCUIT AMPS

MCC MOTOR CONTROL

CENTER

MD MOTORIZED DAMPER

MECH MECHANICAL

MEZZ MEZZANINE

MFG MANUFACTURER

MIN MINIMUM, MINUTES

MISC MISCELLANEOUS

mm MILLIMETERS

MNTD MOUNTED

MOCP MAXIMUM OVERCURRENT

PROTECTION

MUA MAKE-UP AIR

MUW MAKE-UP WATER

N/A NOT APPLICABLE

NATL NATURAL

NC NORMALLY CLOSED

NOISE CRITERIA

NEC NATIONAL ELECTRIC

CODE

NG NATURAL GAS

NFPA NATIONAL FIRE

PROTECTION

ASSOCIATION

NIC NOT IN CONTRACT

NO NUMBER, NORMALLY

OPEN

N02 NITROGEN DIOXIDE

NTS NOT TO SCALE

OA OUTSIDE AIR

OAI OUTSIDE AIR INTAKE

OAT OUTSIDE AIR TEMP

OBD OPPOSED BLADE DAMPER

OD OUTSIDE DIAMETER

OED OPEN ENDED DUCT

OF OVERFLOW

OS&Y OUTSIDE STEM AND YOKE

P PUMP, PITCH

PC PUMPED CONDENSATE

PD PRESSURE DROP

PF POT FEEDER

PLMB PLUMBING

PRESS PRESSURE

PRV PRESSURE REDUCING

VALVE

PSI POUNDS PER SQUARE

INCH

PSIG POUNDS PER SQUARE

INCH GAUGE

PT PRESSURE TREATED

PVC POLYVINYL CHLORIDE

TRIPLE DUTY VALVE

DEMO UP TO THIS POINT

SUPPLY

AHU

S-#

2.2

5 LF

FR-1

2.2

FLOWRATE (GPM)

KEYNOTE (NUMBER)

REVISION (LETTER)

NO2

EXISTING TO REMAIN

REMOVAL / DEMOLITION

NEW WORK

HIDDEN ITEMS

PIPE CONTINUATION

AFS

B

BUTTERFLY VALVE W/ MOTOR

BALL VALVE W/ MOTOR

BALANCING VALVE

E

S

P

S

S

T

ANGULAR GLOBE VALVE W/ MOTOR

ANGULAR GLOBE VALVE

ANGULAR GATE VALVE

TWO-WAY VALVE

NEEDLE

PIPE DOWN W/ VALVE

PIPE UP W/ VALVE

EXHAUST GRILLE, REGISTER

QTY QUANTITY

R RETURN GRILLE

RA RETURN AIR

RAD RADIATOR

RAF, RF RETURN AIR FAN

RAT RETURN AIR TEMP

REL RELIEF

REQD REQUIRED

RET RETURN

RH RELATIVE HUMIDITY

RL REFRIGERANT LIQUID

RLA RATED LOAD AMPS

RM ROOM

RPM REVOLUTIONS PER

MINUTE

RS REFRIGERANT

SUCTION

RTU ROOFTOP UNIT

S SUPPLY DIFFUSER

SA SUPPLY AIR

SCR SCREEN

SD SMOKE DAMPER

SF SQUARE FOOT

SIM SIMILAR

SMACNA SHEET METAL AND

AIR CONDITIONING

CONTRACTOR'S

NATIONAL

ASSOCIATION

SOV SHUT OFF VALVE

SP STATIC PRESSURE

SPH STATIC PRESSURE

HIGH LIMIT

SPL STATIC PRESSURE

LOW LIMIT

SPS STATIC PRESSURE

SENSOR

SQ SQUARE

SS STAINLESS STEEL

STL STEEL

SUP SUPPLY

SW SANITARY WASTE

SWD SANITARY WASTE

DRAIN

SWV SANITARY WASTE

VENT

T TEMPERATURE

SENSOR,

THERMOSTAT

TC TOTAL COOLING

TCV TEMPERATURE

CONTROL VALVE

TEMP TEMPERATURE

THK THICK, THICKNESS

TG TRANSFER GRILLE

TRANS TRANSITION

TSP TOTAL STATIC

PRESSURE

TW TEMPERED WATER

TYP TYPICAL

UH UNIT HEATER

UNO UNLESS NOTED

OTHERWISE

V VENT

VAV VARIABLE AIR

VOLUME

VD VOLUME DAMPER

VEL VELOCITY

VFD VARIABLE

FREQUENCY DRIVE

VTR VENT THROUGH

ROOF

W WIDTH, WATT

W/ WITH

WB WET BULB

WC WATER COLUMN

WCO WALL CLEANOUT

WF WALL FAN

WG WATER GAUGE

WH WATER HEATER

WMS WIRE MESH SCREEN

WPD WATER PRESSURE

DROP

· INTERNATIONAL BUILDING CODE 2015

· INTERNATIONAL PLUMBING CODE 2015

· INTERNATIONAL MECHANICAL CODE 2015

· INTERNATIONAL FUEL GAS CODE 2015

· NFPA 70 NATIONAL ELECTRICAL CODE 2014

APPLICABLE CODES

NOTE:

ABBREVIATIONS AND SYMBOLS APPLY TO

MECHANICAL DRAWINGS MARKED M# AND

PLUMBING DRAWINGS MARKED P#. HOWEVER, ALL

ABBREVIATIONS AND SYMBOLS MAY NOT BE

APPLICABLE TO THIS PARTICULAR PROJECT. THEY

ARE PROVIDED FOR GENERAL REFERENCE ONLY.

REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REFERENCES

REF NUMBER TITLE

A

PIPE TEE FROM BOTTOM W/ VALVE

F

E

D

C

B

A

5 4 3 2 19 8 7 6

0TENTHS 0 INCHES 1 2 3 54 6 7 8 9 EIGHTHS10 7010MM 20 30 40 50 60 9080 100

COPYRIGHT © 2018

AR

CH

D -2

4x

UNLESS OTHERWISE AGREED IN A WRITTEN CONTRACT BETWEEN WOOD ENVIRONMENT &

INFRASTRUCTURE SOLUTIONS, INC. AND ITS CLIENT, THIS DOCUMENT: (I) CONTAINS INFORMATION, DATA AND DESIGN THAT IS CONFIDENTIAL AND MAY NOT BE COPIED OR DISCLOSED; AND (II) MAY BE USED BY THE CLIENT ONLY IN THE CONTEXT AND FOR THE EXPRESS PURPOSE FOR WHICH IT WAS INTENDED.

ANY USE OF, OR RELIANCE ON, THIS DOCUMENT BY ANY THIRD PARTY IS AT THAT PARTY'S SOLE RISK.

Environment & Infrastructure Solutions, Inc.

4600 E. WASHINGTON STREET, SUITE 600

PHOENIX, ARIZONA 85034 / PHONE: 602-733-6000

STAMP/SEAL

DES

DRN

SCALE

PROJECT NO.

CLIENT PROJECT MGR DEPARTMENT MGR PROJECT MGR

BY DD/MM/YY SUBJECT AREA

CLIENT DWG NO.

DRAWING NO. REV

PROJECT PHASE

APP

CHK

CA

D

FI

LE

SAVED: 09-Mar-21 1:21 PM PLOTTED: 10-Mar-21 3:58 PM USER: RODRIGUEZ, BRANDY

-M0.1

6R-KS-1169-18-04(B)

- -GREAT PLAINS NATURE CENTER

HEATING WATER SYSTEM REPLACEMENT

MECHANICAL LEGEND, SHEET LIST,

AND ABBREVIATIONS

J. CROWNHOLM E. GONZALEZ J. MARTIN

3720192002

EG 04/04/19

TW 04/04/19

CV 07/05/19

EG 07/08/19

APPROVED FOR CONSTRUCTION

100% FOR CONSTRUCTION

\\P

HX

4-

FS

1\D

AT

A\

IN

FR

AS

TR

UC

TU

RE

\F

AC

ILI

TI

ES

\P

RO

JE

CT

S\

\37

U

SF

W

S

GR

EA

T

PL

AI

NS

N

AT

UR

E

CE

NT

ER

\9.

0 C

AD

D

RA

W

IN

GS

\09 -S

HE

ET

S\

HE

AT

IN

G

HO

T W

AT

ER

R

EP

LA

CE

ME

NT

\M 0.1

M

EC

HA

NI

CA

L L

EG

EN

D, S

HE

ET

LI

ST

, A

ND

A

BB

RE

VI

AT

IO

NS

.D

W G

M0.1 MECHANICAL LEGEND, SHEET LIST, AND ABBREVIATIONS

M0.2 MECHANICAL GENERAL NOTES

M1.0 MECHANICAL DEMOLITION PLAN - CENTRAL PLANT

M2.0 MECHANICAL NEW PLAN - CENTRAL PLANT

M2.1 MECHANICAL NEW PLAN - AIR HANDLING UNITS

M3.0 MECHANICAL ONE LINE DIAGRAM

M4.0 MECHANICAL AND STRUCTURAL DETAILS

M4.1 STRUCTURAL AND ARCHITECTURAL DETAILS AND MECHANICAL SCHEDULES

M5.0 I/O SUMMARY AND CONTROL DIAGRAM

MECHANICAL SHEET LIST

FM

FLOW METER

L

I

C

E N

S

E

D

K

A

NS

A

M

I

L

I

O

GO

N

Z

A

L

E

Z

07/11/19

AutoCAD SHX Text S

AutoCAD SHX Text F

AutoCAD SHX Text D

AutoCAD SHX Text

NOTE:

GENERAL NOTES

1. GENERAL NOTES, SYMBOLS LIST AND DETAILS ARE APPLICABLE TO DRAWINGS MARKED M#.

2. ON DEMOLITION PLANS EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HEAVY LINE WEIGHT WITH

HATCH, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER PLANS NEW

MECHANICAL SYSTEMS ARE SHOWN HEAVY LINE WEIGHT.

3. THE INSTALLATION OR REMOVAL OF DUCTS, PIPES AND EQUIPMENT MAY REQUIRE THE REMOVAL OF EXISTING WALLS

AND CEILINGS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING AND REPAIRING THESE WALLS AND/OR

CEILINGS SO THEY MATCH THE EXISTING WHERE NOT REPLACED UNDER ARCHITECTURAL DIVISION.

4. ALL FIXTURES AND EQUIPMENT REMOVED, AND NOT REUSED, ARE TO BE RETURNED TO CONTRACTING OFFICER FOR

FIRST RIGHT OF REFUSAL. CONTRACTOR TO DISPOSE OF PROPERLY IF CONTRACTING OFFICER DOES NOT ACCEPT.

5. INFORMATION ON THE DRAWINGS HAS BEEN ASCERTAINED FROM EXISTING DRAWINGS AND FIELD OBSERVATIONS.

THIS INFORMATION IS AS ACCURATE AS CONDITIONS WOULD ALLOW. IT IS THE RESPONSIBILITY OF THE CONTRACTOR

TO VISIT THE SITE, PRIOR TO BID, AND BECOME FAMILIAR WITH THE EXTENT OF THE REMODEL WORK REQUIRED. NO

EXTRAS WILL BE ALLOWED FOR ALTERATIONS OF A FORESEEABLE NATURE REQUIRED TO ACHIEVE THE END RESULT

AS INDICATED BY CONTRACT DOCUMENTS.

6. COORDINATE WORK OF THIS SECTION WITH THAT OF OTHER SECTIONS.

7. WORK SHALL BE COORDINATED WITH TRADES INVOLVED. OFFSETS IN PIPING AND TRANSITIONS AROUND

OBSTRUCTIONS SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE CONTRACTING OFFICER.

8. VERIFY EQUIPMENT CONNECTIONS WITH MANUFACTURER'S CERTIFIED DRAWINGS. VERIFY AND PROVIDE PIPE

TRANSITIONS TO FURNISHED EQUIPMENT. FIELD VERIFY AND COORDINATE DIMENSIONS BEFORE FABRICATION.

9. INSTALL EQUIPMENT, PIPING AND DUCTWORK AS REQUIRED TO PROVIDE A VIBRATION-FREE INSTALLATION AND TO

FACILITATE EQUIPMENT ACCESS AS REQUIRED BY EQUIPMENT MANUFACTURER.

10. CONTROL WIRE AND CONDUIT SHALL COMPLY WITH NEC AND SPECIFICATIONS.

11. INSULATE PIPING AS SPECIFIED IN PROJECT SPECIFICATIONS. PERFORM TESTS SPECIFIED BEFORE INSULATING.

12. PROVIDE CLAMPS, OFFSETS, EXPANSION JOINTS, ANCHORS AND GUIDES AS NECESSARY TO PREVENT STRESS ON

PIPING.

13. RUN PIPING LEVEL AND PARALLEL TO WALLS OR AS INDICATED IN SPECIFICATIONS.

14. DRAWINGS ARE NOT TO BE SCALED FOR DIMENSIONS. TAKE ALL DIMENSIONS FROM THE SITE, CERTIFIED EQUIPMENT

DRAWINGS AND FROM THE STRUCTURE ITSELF BEFORE FABRICATING ANY WORK, VERIFY ALL SPACE REQUIREMENTS

COORDINATING WITH OTHER TRADES, AND INSTALL THE SYSTEMS IN THE SPACE PROVIDED WITHOUT EXTRA CHARGES

TO THE CONTRACTING OFFICER.

15. THE CONTRACTING OFFICER IS NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR TO MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO PERFORM HIS WORK.

16. ALL WORK SHALL BE INSTALLED IN ACCORDANCE WITH ALL APPLICABLE STATE CODES, LOCAL CODES AND

CONTRACTING OFFICER'S STANDARDS INDICATED BY THE CONSTRUCTION DOCUMENTS.

17. ALL EXTERIOR WALL AND ROOF PENETRATIONS SHALL BE SEALED WATERTIGHT.

18. CONTRACTOR IS RESPONSIBLE FOR RAISING AND LOWERING EXISTING EQUIPMENT AND MAKING PROPER OFFSETS IN

PIPING TO AVOID CONFLICTS.

GENERAL NOTES APPLY TO MECHANICAL

DRAWINGS MARKED M#.

REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REFERENCES

REF NUMBER TITLE

F

E

D

C

B

A

5 4 3 2 19 8 7 6

0TENTHS 0 INCHES 1 2 3 54 6 7 8 9 EIGHTHS10 7010MM 20 30 40 50 60 9080 100

COPYRIGHT © 2018

AR

CH

D -2

4x

UNLESS OTHERWISE AGREED IN A WRITTEN CONTRACT BETWEEN WOOD ENVIRONMENT &

INFRASTRUCTURE SOLUTIONS, INC. AND ITS CLIENT, THIS DOCUMENT: (I) CONTAINS INFORMATION, DATA AND DESIGN THAT IS CONFIDENTIAL AND MAY NOT BE COPIED OR DISCLOSED; AND (II) MAY BE USED BY THE CLIENT ONLY IN THE CONTEXT AND FOR THE EXPRESS PURPOSE FOR WHICH IT WAS INTENDED.

ANY USE OF, OR RELIANCE ON, THIS DOCUMENT BY ANY THIRD PARTY IS AT THAT PARTY'S SOLE RISK.

Environment & Infrastructure Solutions, Inc.

4600 E. WASHINGTON STREET, SUITE 600

PHOENIX, ARIZONA 85034 / PHONE: 602-733-6000

STAMP/SEAL

DES

DRN

SCALE

PROJECT NO.

CLIENT PROJECT MGR DEPARTMENT MGR PROJECT MGR

BY DD/MM/YY SUBJECT AREA

CLIENT DWG NO.

DRAWING NO. REV

PROJECT PHASE

APP

CHK

CA

D

FI

LE

SAVED: 09-Mar-21 10:19 AM PLOTTED: 10-Mar-21 3:57 PM USER: RODRIGUEZ, BRANDY

-M0.2

6R-KS-1169-18-04(B)

- -GREAT PLAINS NATURE CENTER

HEATING WATER SYSTEM REPLACEMENT

MECHANICAL GENERAL NOTES

J. CROWNHOLM E. GONZALEZ J. MARTIN

3720192002

EG 04/04/19

TW 04/04/19

CV 07/05/19

EG 07/08/19

APPROVED FOR CONSTRUCTION

100% FOR CONSTRUCTION

\\P

HX

4-

FS

1\D

AT

A\

IN

FR

AS

TR

UC

TU

RE

\F

AC

ILI

TI

ES

\P

RO

JE

CT

S\

\37

U

SF

W

S

GR

EA

T

PL

AI

NS

N

AT

UR

E

CE

NT

ER

\9.

0 C

AD

D

RA

W

IN

GS

\09 -S

HE

ET

S\

HE

AT

IN

G

HO

T W

AT

ER

R

EP

LA

CE

ME

NT

\M 0.2

M

EC

HA

NI

CA

L G

EN

ER

AL

N

OT

ES

.D W

G

L

I

C

E N

S

E

D

K

A

NS

A

O

M

I

L

GO

Z

A

L

E

Z

07/11/19

KEY NOTES

REMOVE EXISTING BOILER AND ALL ASSOCIATED APPURTENANCES. SEE MECHANICAL ONE LINE DIAGRAM SHEET

M3.0.

REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REFERENCES

REF NUMBER TITLE

F

E

D

C

B

A

5 4 3 2 19 8 7 6

0TENTHS 0 INCHES 1 2 3 54 6 7 8 9 EIGHTHS10 7010MM 20 30 40 50 60 9080 100

COPYRIGHT © 2018

AR

CH

D -2

4x

UNLESS OTHERWISE AGREED IN A WRITTEN CONTRACT BETWEEN WOOD ENVIRONMENT &

INFRASTRUCTURE SOLUTIONS, INC. AND ITS CLIENT, THIS DOCUMENT: (I) CONTAINS INFORMATION, DATA AND DESIGN THAT IS CONFIDENTIAL AND MAY NOT BE COPIED OR DISCLOSED; AND (II) MAY BE USED BY THE CLIENT ONLY IN THE CONTEXT AND FOR THE EXPRESS PURPOSE FOR WHICH IT WAS INTENDED.

ANY USE OF, OR RELIANCE ON, THIS DOCUMENT BY ANY THIRD PARTY IS AT THAT PARTY'S SOLE RISK.

Environment & Infrastructure Solutions, Inc.

4600 E. WASHINGTON STREET, SUITE 600

PHOENIX, ARIZONA 85034 / PHONE: 602-733-6000

SCALE:

N

O

R

T

H

EXP

(E)

ADS

(E)

HOT WATER HEATER(E)

B

(E)

B

(E)

B

(E)

B

(E)

HHWP

(E)

HHWP

(E)

UH

D

(E)

SCALE:

N O

R T

H

KEY PLAN

N.T.S.

PF

B

(E)

B

(E)

B

(E)

B

(E)

(E)

L

(E)

L

(E)

LOWHIGH

REMOVE EXISTING EXPANSION TANK AND ALL ASSOCIATED APPURTENANCES. SEE MECHANICAL ONE LINE

DIAGRAM SHEET M3.0.

REMOVE EXISTING AIR DIRT SEPARATOR AND ALL ASSOCIATED APPURTENANCES. SEE MECHANICAL

DEMOLITION ONE LINE DIAGRAM SHEET M3.0.

REMOVE EXISTING PUMP AND ALL ASSOCIATED APPURTENANCES. SEE MECHANICAL ONE LINE DIAGRAM SHEET

M3.0.

REMOVE EXISTING POT FEEDER AND ALL ASSOCIATED APPURTENANCES. SEE MECHANICAL ONE LINE DIAGRAM

SHEET M3.0.

6 REMOVE EXISTING BOILER CONTROL PANEL AND ALL ASSOCIATED APPURTENANCES.

REMOVE EXISTING NATURAL GAS PIPING DOWN TO BOILER AND CAP AT MAIN. SEE MECHANICAL ONE LINE

DIAGRAM SHEET M3.0.

(TYPICAL OF 4)

8 REMOVE EXISTING HHWS/HHWR PIPE AS SHOWN. SEE MECHANICAL ONE LINE DIAGRAM SHEET M3.0.

REMOVE EXISTING MAIN BOILER FLUE UP THROUGH ROOF AND ALL FLUE BRANCHES TO EACH BOILER. SEE

STRUCTURAL DETAILS 12/M4.0, 1/M4.1, 2/M4.1, AND 3/M4.1.

GAS

METER(E)

MECHANICAL DEMOLITION PLAN - CENTRAL PLANT

1/2"=1'

STAMP/SEAL

DES

DRN

SCALE

PROJECT NO.

CLIENT PROJECT MGR DEPARTMENT MGR PROJECT MGR

BY DD/MM/YY SUBJECT AREA

CLIENT DWG NO.

DRAWING NO. REV

PROJECT PHASE

APP

CHK

CA

D

FI

LE

SAVED: 09-Mar-21 10:23 AM PLOTTED: 10-Mar-21 3:54 PM USER: RODRIGUEZ, BRANDY

-M1.0

6R-KS-1169-18-04(B)

- -GREAT PLAINS NATURE CENTER

HEATING WATER SYSTEM REPLACEMENT

MECHANICAL DEMOLITION PLAN - CENTRAL PLANT

J. CROWNHOLM E. GONZALEZ J. MARTIN

3720192002

EG 04/04/19

TW 04/04/19

CV 07/05/19

EG 07/08/19

APPROVED FOR CONSTRUCTION

100% FOR CONSTRUCTION

\\P

HX

4-

FS

1\D

AT

A\

IN

FR

AS

TR

UC

TU

RE

\F

AC

ILI

TI

ES

\P

RO

JE

CT

S\

\37

U

SF

W

S

GR

EA

T

PL

AI

NS

N

AT

UR

E

CE

NT

ER

\9.

0 C

AD

D

RA

W

IN

GS

\09 -S

HE

ET

S\

HE

AT

IN

G

HO

T W

AT

ER

R

EP

LA

CE

ME

NT

\M 1.0

M

EC

HA

NI

CA

L D

EM

OL

IT

IO

N

PL

AN

CE

NT

RA

L P

LA

NT

.D W

G

GENERAL NOTES

1. CONTRACTOR SHALL COORDINATE EQUIPMENT DEMOLITION WITH THE USFWS AND CONSTRUCTION MANAGER. THE

CONTRACTOR SHALL DEVELOP A PHASE AND RIGGING PLAN FOR APPROVAL BY THE USFWS AND CONSTRUCTION

MANAGER.

2. CONTRACTOR SHALL COORDINATE PROPER DISPOSAL OF REMOVED EQUIPMENT WITH USFWS REGARDING

RECYCLING / SCRAPPING OF DEMOLISHED MATERIALS. CONTRACTOR TO PROVIDE APPROPRIATE TRASH / RECYCLING

CANISTERS FOR DEBRIS COLLECTION.

3. PROPER EVACUATION AND DECOMMISSIONING OF MECHANICAL SYSTEMS TO BE DEMOLISHED MUST BE DONE PRIOR

TO REMOVAL OF EQUIPMENT. ALL REMOVED SYSTEMS MUST BE DEMOLISHED WITHOUT CAUSING DANGER TO THE

SITE, OCCUPANTS OR ENVIRONMENT.

4. DISMANTLE EQUIPMENT IN SECTIONS AS REQUIRED FOR REMOVAL FROM TIGHT SPACES. DOUBLE DOORS IN SPACE

TO BE USED FOR EQUIPMENT REMOVAL.

L

I

C

E N

S

E

D

K

A

NS

A

E

M

I

L

Z

A

L

E

Z

07/11/19

REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REFERENCES

REF NUMBER TITLE

F

E

D

C

B

A

5 4 3 2 19 8 7 6

0TENTHS 0 INCHES 1 2 3 54 6 7 8 9 EIGHTHS10 7010MM 20 30 40 50 60 9080 100

COPYRIGHT © 2018

AR

CH

D -2

4x

UNLESS OTHERWISE AGREED IN A WRITTEN CONTRACT BETWEEN WOOD ENVIRONMENT &

INFRASTRUCTURE SOLUTIONS, INC. AND ITS CLIENT, THIS DOCUMENT: (I) CONTAINS INFORMATION, DATA AND DESIGN THAT IS CONFIDENTIAL AND MAY NOT BE COPIED OR DISCLOSED; AND (II) MAY BE USED BY THE CLIENT ONLY IN THE CONTEXT AND FOR THE EXPRESS PURPOSE FOR WHICH IT WAS INTENDED.

ANY USE OF, OR RELIANCE ON, THIS DOCUMENT BY ANY THIRD PARTY IS AT THAT PARTY'S SOLE RISK.

Environment & Infrastructure Solutions, Inc.

4600 E. WASHINGTON STREET, SUITE 600

PHOENIX, ARIZONA 85034 / PHONE: 602-733-6000

SCALE:

N O

R T

H

KEY PLAN

N.T.S.

HOT WATER HEATER(E)

UH

D

(E)

SCALE:

KEY NOTES

PROVIDE NEW BOILER AND ALL ASSOCIATED APPURTENANCES ON EXISTING HOUSEKEEPING PAD. INSTALL PER

MANUFACTURER'S RECOMMENDATIONS. SEE SCHEDULE, DETAIL AND MECHANICAL ONE LINE DIAGRAM SHEET M3.0.

ADS

B

HHWP

CONNECT NEW NATURAL GAS PIPE TO EXISTING NATURAL GAS AS SHOWN. SEE MECHANICAL ONE LINE

DIAGRAM SHEET M3.0.

PROVIDE CPVC CONCENTRIC VENT KIT UP THROUGH ROOF. CONNECT TO BOILER FRESH AIR

AND EXHAUST AIR LOCATIONS.

GAS

METER(E)

PROVIDE EXPANSION TANK ON EXISTING HOUSEKEEPING PAD WHERE SHOWN. INSTALL PER

MANUFACTURER'S RECOMMENDATIONS. SEE SCHEDULE, DETAIL AND MECHANICAL ONE LINE DIAGRAM

SHEET M3.0.

PROVIDE AIR SEPARATOR WHERE SHOWN. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.

SEE SCHEDULE, DETAIL AND MECHANICAL ONE LINE DIAGRAM SHEET M3.0.

PROVIDE INLINE PUMP ON EXISTING HOUSEKEEPING PAD WHERE SHOWN. INSTALL PER

MANUFACTURER'S RECOMMENDATIONS. SEE SCHEDULE, DETAIL AND MECHANICAL ONE LINE

DIAGRAM SHEET M3.0.

PROVIDE POT FEEDER ON EXISTING HOUSEKEEPING PAD WHERE SHOWN. INSTALL PER

MANUFACTURER'S RECOMMENDATIONS. SEE SCHEDULE, DETAIL AND MECHANICAL ONE LINE

DIAGRAM SHEET M3.0.

PROVIDE TEMPERATURE CONTROL VALVE WHERE SHOWN. INSTALL PER MANUFACTURER'S

RECOMMENDATIONS. SEE SCHEDULE AND MECHANICAL ONE LINE DIAGRAM SHEET M3.0.

CONNECT NEW HYDRONIC HEATING WATER RETURN AND SUPPLY PIPE TO EXISTING HYDRONIC

HEATING WATER RETURN AND SUPPLY PIPE AS SHOWN.

PROVIDE EMERGENCY 4 INCH HYDRONIC HEATING WATER CONNECTIONS WITH ISOLATION VALVE

AND CAP WHERE SHOWN.

EXP

TCV

HBP

6 (N)

(N)

(N)

(N)

(N)

B

1 (N)

B

1 (N)

B

1 (N)

L

(E)

L

(E)

LOWHIGH

9 9 9 9

MECHANICAL ROOM NEW PLAN

1/4"=1'

N

O

R

T

H

STAMP/SEAL

DES

DRN

SCALE

PROJECT NO.

CLIENT PROJECT MGR DEPARTMENT MGR PROJECT MGR

BY DD/MM/YY SUBJECT AREA

CLIENT DWG NO.

DRAWING NO. REV

PROJECT PHASE

APP

CHK

CA

D

FI

LE

SAVED: 09-Mar-21 10:27 AM PLOTTED: 10-Mar-21 3:53 PM USER: RODRIGUEZ, BRANDY

-M2.0

6R-KS-1169-18-04(B)

- -GREAT PLAINS NATURE CENTER

HEATING WATER SYSTEM REPLACEMENT

MECHANICAL NEW PLAN - CENTRAL PLANT

J. CROWNHOLM E. GONZALEZ J. MARTIN

3720192002

EG 04/04/19

TW 04/04/19

CV 07/05/19

EG 07/08/19

APPROVED FOR CONSTRUCTION

100% FOR CONSTRUCTION

\\P

HX

4-

FS

1\D

AT

A\

IN

FR

AS

TR

UC

TU

RE

\F

AC

ILI

TI

ES

\P

RO

JE

CT

S\

\37

U

SF

W

S

GR

EA

T

PL

AI

NS

N

AT

UR

E

CE

NT

ER

\9.

0 C

AD

D

RA

W

IN

GS

\09 -S

HE

ET

S\

HE

AT

IN

G

HO

T W

AT

ER

R

EP

LA

CE

ME

NT

\M 2.0

M

EC

HA

NI

CA

L N

EW

P

LA

N

- C

EN

TR

AL

P

LA

NT

.D

W G

PF

5(N)

HHWP

4(N)

GENERAL NOTES

1. CONTRACTOR SHALL COORDINATE EQUIPMENT INSTALLATION WITH THE USFWS AND CONSTRUCTION

MANAGER. THE CONTRACTOR SHALL DEVELOP A PHASING AND RIGGING PLAN FOR APPROVAL BY THE

USFWS AND CONSTRUCTION MANAGER.

2. CONTRACTOR SHALL FIELD VERIFY ALL SIZES, DIMENSIONS, ROUTES OF EGRESS AND ENTRY, AND

LOCATIONS SHOWN ON DESIGN DRAWINGS PRIOR TO BID AND CONSTRUCTION START.

VFD

HHWP1

12 (N)

VFD

HHWP2

12 (N)

FMS

11(N)

PROVIDE FLOW MEASURING STATION WHERE SHOWN. INSTALL PER MANUFACTURER'S

RECOMMENDATIONS. SEE SCHEDULE AND MECHANICAL ONE LINE DIAGRAM SHEET M3.0.

PROVIDE VARIABLE FREQUENCY DRIVE WHERE SHOWN. INSTALL PER MANUFACTURER'S

RECOMMENDATIONS. SEE SCHEDULE AND ELECTRICAL PLANS.

L

I

C

E N

S

E

D

K

A

NS

A

E

M

I

L

Z

A

L

E

T

UH-D

T

AHU-7

H

AHU-7

KEY NOTES

REPLACE EXISTING TEMPERATURE CONTROL VALVE AND INTEGRATE WITH EXISTING

BUILDING AUTOMATION SYSTEM. SEE SCHEDULE AND DETAILS.

REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REFERENCES

REF NUMBER TITLE

F

E

D

C

B

A

5 4 3 2 19 8 7 6

0TENTHS 0 INCHES 1 2 3 54 6 7 8 9 EIGHTHS10 7010MM 20 30 40 50 60 9080 100

COPYRIGHT © 2018

AR

CH

D -2

4x

UNLESS OTHERWISE AGREED IN A WRITTEN CONTRACT BETWEEN WOOD ENVIRONMENT &

INFRASTRUCTURE SOLUTIONS, INC. AND ITS CLIENT, THIS DOCUMENT: (I) CONTAINS INFORMATION, DATA AND DESIGN THAT IS CONFIDENTIAL AND MAY NOT BE COPIED OR DISCLOSED; AND (II) MAY BE USED BY THE CLIENT ONLY IN THE CONTEXT AND FOR THE EXPRESS PURPOSE FOR WHICH IT WAS INTENDED.

ANY USE OF, OR RELIANCE ON, THIS DOCUMENT BY ANY THIRD PARTY IS AT THAT PARTY'S SOLE RISK.

Environment & Infrastructure Solutions, Inc.

4600 E. WASHINGTON STREET, SUITE 600

PHOENIX, ARIZONA 85034 / PHONE: 602-733-6000

SCALE:

N O

R T

H

KEY PLAN

N.T.S.

STAMP/SEAL

DES

DRN

SCALE

PROJECT NO.

CLIENT PROJECT MGR DEPARTMENT MGR PROJECT MGR

BY DD/MM/YY SUBJECT AREA

CLIENT DWG NO.

DRAWING NO. REV

PROJECT PHASE

APP

CHK

CA

D

FI

LE

SAVED: 09-Mar-21 12:33 PM PLOTTED: 10-Mar-21 3:51 PM USER: RODRIGUEZ, BRANDY

-M2.1

6R-KS-1169-18-04(B)

- -GREAT PLAINS NATURE CENTER

HEATING WATER SYSTEM REPLACEMENT

MECHANICAL NEW PLAN - AIR HANDLING UNITS

J. CROWNHOLM E. GONZALEZ J. MARTIN

3720192002

EG 04/04/19

TW 04/04/19

CV 07/05/19

EG 07/08/19

APPROVED FOR CONSTRUCTION

100% FOR CONSTRUCTION

\\P

HX

4-

FS

1\D

AT

A\

IN

FR

AS

TR

UC

TU

RE

\F

AC

ILI

TI

ES

\P

RO

JE

CT

S\

\37

U

SF

W

S

GR

EA

T

PL

AI

NS

N

AT

UR

E

CE

NT

ER

\9.

0 C

AD

D

RA

W

IN

GS

\09 -S

HE

ET

S\

HE

AT

IN

G

HO

T W

AT

ER

R

EP

LA

CE

ME

NT

\M 2.1

M

EC

HA

NI

CA

L N

EW

P

LA

N

- M

EC

HA

NI

CA

L R

OO

MS

.D W

G

AHU

(E)

AHU

(E)

AHU

(E)

AHU

(E)

AHU

(E)

AHU

(E)

AHU

(E)

AHU

(E)

4" HHWS&R

2" HHWS&R

1" HHWS&R

2" HHWS&R

4" HHWS&R

3/4" HHWS&R

1" HHWS&R

2" HHWS&R

1 1/2" HHWS&R

2" HHWS&R

1 1/4" HHWS&R

1 1/4" HHWS&R

1 1/2" HHWS&R

1 1/2" HHWS&R

2" HHWS&R

5/8" HHWS&R

20"x60"(E)

28"Ø(E)

30"Ø(E)

20"x40"(E)

18"x10"(E)

60"x60"(E)

60"x12"(E)

28"Ø(E)

60"x10"(E)

60"x10"(E)

DUCT SILENCER(E)

CONTROL AIR COMPRESSOR(E)

REFRIGERATED AIR DRYER(E)

UNIT HEATER (E)

(TYP OF 3)

UNIT HEATER(E)

2" HHWS&R(E)

1/2" HHWS&R(E)

2 1/2" HHWS&R(E)

4" HHWS&R(E)

96"x42" OSA LOUVER(E)

24"x36"(E)

24"x48"(E)

48"x14"(E)

24"x18"(E)

UNIT HEATER(E)

26"x12"(E)

24"x18"(E)

SCALE:

N

O

R

T

H

MECHANICAL NEW PLAN - AHU-3,5,6

3/16"=1'

SCALE:

N

O

R

T

H

MECHANICAL NEW PLAN - AHU-1,2

3/16"=1'

SCALE:

N

O

R

T

H

MECHANICAL NEW PLAN - AHU-7,8

3/16"=1'

SCALE:

N

O

R

T

H

MECHANICAL NEW PLAN - AHU-4

3/16"=1'

28"Ø(E)

GENERAL NOTES

1. CONTRACTOR SHALL COORDINATE EQUIPMENT INSTALLATION WITH THE USFWS AND

CONSTRUCTION MANAGER. THE CONTRACTOR SHALL DEVELOP A PHASING AND RIGGING

PLAN FOR APPROVAL BY THE USFWS AND CONSTRUCTION MANAGER.

2. CONTRACTOR SHALL FIELD VERIFY ALL SIZES, DIMENSIONS, ROUTES OF EGRESS AND

ENTRY, AND LOCATIONS SHOWN ON DESIGN DRAWINGS PRIOR TO BID AND CONSTRUCTION

START.

L

I

C

E N

S

E

D

K

A

NS

A

O

E

M

I

L

Z

A

L

E

REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REFERENCES

F

E

D

C

B

A

5 4 3 2 19 8 7 6

0TENTHS 0 INCHES 1 2 3 54 6 7 8 9 EIGHTHS10 7010MM 20 30 40 50 60 9080 100

COPYRIGHT © 2018

AR

CH

D -2

4x

UNLESS OTHERWISE AGREED IN A WRITTEN CONTRACT BETWEEN WOOD ENVIRONMENT &

INFRASTRUCTURE SOLUTIONS, INC. AND ITS CLIENT, THIS DOCUMENT: (I) CONTAINS INFORMATION, DATA AND DESIGN THAT IS CONFIDENTIAL AND MAY NOT BE COPIED OR DISCLOSED; AND (II) MAY BE USED BY THE CLIENT ONLY IN THE CONTEXT AND FOR THE EXPRESS PURPOSE FOR WHICH IT WAS INTENDED.

ANY USE OF, OR RELIANCE ON, THIS DOCUMENT BY ANY THIRD PARTY IS AT THAT PARTY'S SOLE RISK.

Environment & Infrastructure Solutions, Inc.

4600 E. WASHINGTON STREET, SUITE 600

PHOENIX, ARIZONA 85034 / PHONE: 602-733-6000

SCALE:

NATURAL GAS DEMOLITION ONE LINE DIAGRAM

N.T.S.

SCALE:

HEATING HOT WATER DEMOLITION ONE LINE DIAGRAM

N.T.S.

SCALE:

NATURAL GAS NEW ONE LINE DIAGRAM

N.T.S.

SCALE:

HEATING HOT WATER NEW ONE LINE DIAGRAM

N.T.S.

2 1/2" NG(E)

TO GAS METER

ADS

B

B

HOT WATER HEATER(E)

1 1/4" NG(E)

(TYP OF 8)

B

B

B

B

B

B

B

B

B

B

B

B

B

B

HHWP

HHWP

PF

EXP

REMOVE UP TO BALL VALVE

DOWNSTREAM OF PRESSURE

REGULATING VALVE.

1" HHWS(E)

2 1/2" NG(E) 2 1/2" NG(E) 1" NG(E)

1 1/2" NG(E)

(TYP OF 4)

1" MUW(E)

4" HHWS(E)

4" HHWR(E)

4" HHWS(E)

3/4" HHWS(E)

4" HHWS(E)

1 1/4" HHWS&R(E)

(TYPICAL OF 8)

1 1/4" HHWS&R(E)

(TYPICAL OF 8)

4" HHWR(E)

4" HHWS(E)

4" HHWS&R(E)

2 1/2" NG(E)

TO GAS METER

HOT WATER HEATER(E)

2 1/2" NG(E) 2 1/2" NG(E)

1" NG(E)

B

B

B

B

1 1/2" NG(N)

TYPICAL OF 4

1" MUW(N)

EXP

HHWP

HHWP

PF

B

B

B

B

TCV

HBP

ADS

1 1/2" HHWS(N)

4" HHWS(N)

4" HHWR(N)

4" HHWS(N)

4" HHWS(N)

3/4" HHWS(N)

4" HHWS(N)

3/4" HHWS(N)

1 1/4" HHWS&R(N)

(TYPICAL OF 4)

4" HHWR(N)

FROM BALL VALVE

DOWNSTREAM OF

PRESSURE REGULATING

VALVE

STAMP/SEAL

DES

DRN

SCALE

PROJECT NO.

CLIENT PROJECT MGR DEPARTMENT MGR PROJECT MGR

BY DD/MM/YY SUBJECT AREA

CLIENT DWG NO.

DRAWING NO. REV

PROJECT PHASE

APP

CHK

CA

D

FI

LE

SAVED: 09-Mar-21 12:33 PM PLOTTED: 10-Mar-21 3:49 PM USER: RODRIGUEZ, BRANDY

-M3.0

6R-KS-1169-18-04(B)

- -GREAT PLAINS NATURE CENTER

HEATING WATER SYSTEM REPLACEMENT

MECHANICAL ONE LINE DIAGRAMS

J. CROWNHOLM E. GONZALEZ J. MARTIN

3720192002

EG 04/04/19

TW 04/04/19

CV 07/05/19

EG 07/08/19

APPROVED FOR CONSTRUCTION

100% FOR CONSTRUCTION

\\P

HX

4-

FS

1\D

AT

A\

IN

FR

AS

TR

UC

TU

RE

\F

AC

ILI

TI

ES

\P

RO

JE

CT

S\

\37

U

SF

W

S

GR

EA

T

PL

AI

NS

N

AT

UR

E

CE

NT

ER

\9.

0 C

AD

D

RA

W

IN

GS

\09 -S

HE

ET

S\

HE

AT

IN

G

HO

T W

AT

ER

R

EP

LA

CE

ME

NT

\M 3.0

M

EC

HA

NI

CA

L O

NE

LI

NE

D

IA

GR

AM

S.

DW

G

2" HHWS(N)

FMS

TCV

B4

TCV

B3

TCV

B2

TCV

B1

L

I

C

E N

S

E

D

K

A

NS

A

M

I

L

I

O

GO

N

Z

A

L

E

Z

07/11/19

REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REFERENCES

F

E

D

C

B

A

5 4 3 2 19 8 7 6

0TENTHS 0 INCHES 1 2 3 54 6 7 8 9 EIGHTHS10 7010MM 20 30 40 50 60 9080 100

COPYRIGHT © 2018

AR

CH

D -2

4x

UNLESS OTHERWISE AGREED IN A WRITTEN CONTRACT BETWEEN WOOD ENVIRONMENT &

INFRASTRUCTURE SOLUTIONS, INC. AND ITS CLIENT, THIS DOCUMENT: (I) CONTAINS INFORMATION, DATA AND DESIGN THAT IS CONFIDENTIAL AND MAY NOT BE COPIED OR DISCLOSED; AND (II) MAY BE USED BY THE CLIENT ONLY IN THE CONTEXT AND FOR THE EXPRESS PURPOSE FOR WHICH IT WAS INTENDED.

ANY USE OF, OR RELIANCE ON, THIS DOCUMENT BY ANY THIRD PARTY IS AT THAT PARTY'S SOLE RISK.

Environment & Infrastructure Solutions, Inc.

4600 E. WASHINGTON STREET, SUITE 600

PHOENIX, ARIZONA 85034 / PHONE: 602-733-6000

SCALE: N.T.S.

POT FEEDER DETAIL

BALL VALVE (TYP)

POT FEEDER

REMOVABLE SCREW

TOP WITH GASKET

UNION (TYP)

FLOW INDICATOR

3/4" TO PUMP

SUCTION

3/4" FROM PUMP

DISCHARGE

3/4" DRAIN W/ HOSE

END AND CAP

SCALE: N.T.S.

AIR SEPARATOR DETAIL

4" EXISTING

HOUSEKEEPING PAD

SCALE: N.T.S.

EXPANSION TANK DETAIL

4" THICK EXISTING

HOUSEKEEPING PAD

NOTE:

SEE ONE LINE DIAGRAM

FOR PIPE SIZING.

SCALE: N.T.S.

PIPE INSULATION DETAIL

SCALE: N.T.S.

VENT THRU ROOF DETAIL

CONCENTRIC

SCALE: N.T.S.

AUTOMATIC AIR VENT DETAIL

SCALE: N.T.S.

PIPE SUPPORT DETAIL

AIR INTAKE

UP TO ROOF

SAFETY RELIEF VALVE

ISOLATION VALVE (TYPICAL)

VENT UP TO ROOF

WITH VENT CAP

V-STRAINS WITH

BLOW OFF

SEE NOTE 1

NOTES:

1. TERMINATE ALL DRAINS AT ADJACENT FLOOR SINK.

2. SEE TYPICAL GAS CONNECTION DETAIL 1/M4.0.

CONDENSATE NEUTRALIZATION KIT

HHWR

HHWS (FACTORY PROVIDED,

FIELD INSTALLED)

SEE NOTE 1

SEE NOTE 2

SCALE: N.T.S.

BOILER DETAIL

DIELECTRIC UNION

GAS COCK

GAS SUPPLY LINE

6'' DIRT LEG (MIN.)

APPLIANCE

ANGLED TRIPLE

DUTY VALVE

FLUSH

LINE

DRAIN CONNECTION

SPLIT

COUPLER

PIPE HANGER (TYP.)

RECOMMENDED FIELD

PRESSURE GAUGE PIPING

ARRANGEMENT

SUCTION

GUIDE

NEOPRENE

ISOLATION PAD

PIPE SUPPORT

PET COCK

(TYP.)

SYSTEM INLET

SYSTEM OUTLET

HANGERS SUPPORT THE WEIGHT

OF THE FILLED PIPING, PUMPS

AND FITTINGS

2'' OR 3''

HEIGHT ABOVE

PAD

SCALE: N.T.S.

TYPICAL GAS CONNECTION DETAIL

SCALE: N.T.S.

FLOOR SADDLE SUPPORT DETAIL

BLADDER TYPE

EXPANSION TANK

TO MAKEUP

WATER ASSEMBLY

TO AIR SEPARATOR

INSULATION NOTES (INTERIOR):

SHALL BE NONCOMBUSTIBLE, RIGID MOLDED

WITH MINIMUM K VALUE OF 0.24 @ 75F, ASTM

C547, MAX. MOISTURE ABSORPTION OF 0.2%

BY VOL., AND VAPOR BARRIER LAP ADHESIVE

COMPATIBLE WITH INSULATION.

REGULATORY REQUIREMENT:

INSULATION SHALL CONFORM TO A MAXIMUM

FLAME SPREAD/SMOKE DEVELOPED RATING

OF 25/50 IN ACCORDANCE WITH ASTM E84,

NFPA 255 & UL 723.

1-1/2" INSULATION

(MIN.)

JACKET

PIPE

HIGH CAPACITY

AUTO AIR VENT

TO EXT AND

MUW ASSEMBLY

BALL VALVE

RETURN FROM

SYSTEM

FULL SIZE DRAIN

TO NEAREST

FLOOR SINK OR

DRAIN

TO PUMP

SUCTION

FULL SIZE DRAIN

TO F.S.

AIR AND DIRT

SEPARATOR

VENT

APPLY CAULKING

AT PENETRATION

OF FLASHING

ROOFING UP AND

OVER FLASHING

ROOF

ELBOW (FIELD SUPPLIED)

C O

M B

U S

T I O

N

A I R

V E

N T

COMBUSTION AIR

INTAKE

STORM COLLAR

UL LISTED SHEET

METAL FLASHING

STRAP (FIELD

SUPPLIED)

PROVIDE FIRE COLLAR AROUND FLUE

PIPES AT RATED ROOF PENETRATIONS.

TEST COCK

FLOAT TYPE AIR VENT

ARMSTRONG

MODEL 1-AV 3/4" CONN.

3/4" DIA. BALL VALVE

JAMESBURY CLINCHER

TYPE 2111

3/4" FROM PIPE VENTED

HIGH POINTS

INSULATED PIPE

WITH VAPOR BARRIER

18" LONG 16 GAUGE

PIPE SHIELD

CLEVIS PIPE HANGER

250 LBS MAX

PRECAST HOLLOW

CORE SLAB

PLATE WASHER

1/4"x5"x5"

FLOOR TOPPING

ALL THREAD THRU

CONCRETE FLANK.

1/2"Ø THREADED ROD

90° SECTION OF RIGID

INSULATION MIN. 12" LONG

(TYP. FOR ALL PIPING)

4" EXISTING

HOUSEKEEPING PAD

FLOOR

TEMPERATURE CONTROL VALVE

BOILER

INLINE PUMP

INLINE PUMP WITH

STAMP/SEAL

DES

DRN

SCALE

PROJECT NO.

CLIENT PROJECT MGR DEPARTMENT MGR PROJECT MGR

BY DD/MM/YY SUBJECT AREA

CLIENT DWG NO.

DRAWING NO. REV

PROJECT PHASE

APP

CHK

CA

D

FI

LE

SAVED: 09-Mar-21 1:23 PM PLOTTED: 10-Mar-21 3:40 PM USER: RODRIGUEZ, BRANDY

-M4.0

6R-KS-1169-18-04(B)

- -GREAT PLAINS NATURE CENTER

HEATING WATER SYSTEM REPLACEMENT

MECHANICAL DETAILS

J. CROWNHOLM E. GONZALEZ J. MARTIN

3720192002

EG 04/04/19

TW 04/04/19

CV 07/05/19

EG 07/08/19

APPROVED FOR CONSTRUCTION

100% FOR CONSTRUCTION

\\P

HX

4-

FS

1\D

AT

A\

IN

FR

AS

TR

UC

TU

RE

\F

AC

ILI

TI

ES

\P

RO

JE

CT

S\

\37

U

SF

W

S

GR

EA

T

PL

AI

NS

N

AT

UR

E

CE

NT

ER

\9.

0 C

AD

D

RA

W

IN

GS

\09 -S

HE

ET

S\

HE

AT

IN

G

HO

T W

AT

ER

R

EP

LA

CE

ME

NT

\M 4.0

M

EC

HA

NI

CA

L D

ET

AI

LS

.D

W G

SCALE: N.T.S.

LARGE COIL PIPING DIAGRAM (2-WAY)

STRAINER W/ BALL

VALVE, HOSE END

AND THREADED

2-WAY

CONTROL

VALVE

CALIBRATED

BALANCING

VALVE (TYP.)

UNION OR FLANGE, DIELECTRIC

FITTINGS AS REQUIRED (TYP.)

SHUT-OFF VALVE

THERMOMETER (TYP.)

SUPPLY

RETURN

MANUAL AIR VENT W/ FULL SIZE

DRAIN TO DRAIN PAN (TYP.)

COIL

'PETE'S' TEST

PLUG (TYP.)

COIL

COIL CONDENSATE DRAIN

PAN (INSULATED)

OPEN VENT

TRAP. SEE DETAIL

COIL CONDENSATE DRAIN.

SEE MECHANICAL PLANS

'PETE'S' TEST

PLUG (TYP.)

NOTES:

1. PROVIDE CONDENSATE DRAIN PIPING

AND TRAP ON COOLING COILS ONLY.

FLEXIBLE

CONNECTOR-STAINLESS

STEEL HOSE W/ STAINLESS

STEEL OUTER BRAID (TYP.)

SCALE: N.T.S.

SMALL COOLING COIL PIPING DIAGRAM (2-WAY)

COPPER

PIPE

2-WAY CONTROL NOT

REQUIRED FOR FC-9, 21,

22, 35, 36, 49, 50, 56, 64, 74, 75

BALL VALVE (TYP.)

DIELECTRIC UNION

OR DIELECTRIC FLANGE

PLENUM-RATED HOSE W/ STAINLESS

STEEL OUTER BRAID (TYP.)

COIL CONDENSATE

DRAIN PAN (INSULATED)

STRAINER

STEEL

PIPE

MANUAL AIR VENT W/ FULL

SIZE DRAIN TO DRAIN PAN

FAN COIL

OPEN VENT

TRAP-SEE DETAIL

COIL CONDENSATE

DRAIN-SEE DETAIL

UNION (TYP.)

AUTOMATIC

BALANCING VALVE

L

I

C

E N

S

E

D

K

A

NS

A

M

I

L

I

O

GO

N

Z

A

L

E

Z

07/11/19

AutoCAD SHX Text

NG

AutoCAD SHX Text

CHWR

AutoCAD SHX Text

CHWS

REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REFERENCES

F

E

D

C

B

A

5 4 3 2 19 8 7 6

0TENTHS 0 INCHES 1 2 3 54 6 7 8 9 EIGHTHS10 7010MM 20 30 40 50 60 9080 100

COPYRIGHT © 2018

AR

CH

D -2

4x

UNLESS OTHERWISE AGREED IN A WRITTEN CONTRACT BETWEEN WOOD ENVIRONMENT &

INFRASTRUCTURE SOLUTIONS, INC. AND ITS CLIENT, THIS DOCUMENT: (I) CONTAINS INFORMATION, DATA AND DESIGN THAT IS CONFIDENTIAL AND MAY NOT BE COPIED OR DISCLOSED; AND (II) MAY BE USED BY THE CLIENT ONLY IN THE CONTEXT AND FOR THE EXPRESS PURPOSE FOR WHICH IT WAS INTENDED.

ANY USE OF, OR RELIANCE ON, THIS DOCUMENT BY ANY THIRD PARTY IS AT THAT PARTY'S SOLE RISK.

Environment & Infrastructure Solutions, Inc.

4600 E. WASHINGTON STREET, SUITE 600

PHOENIX, ARIZONA 85034 / PHONE: 602-733-6000

SCALE: 1"=1'

TYPICAL INFILL FRAMING

SCALE: 1 1/2" = 1'

TYPICAL INFILL FRAMING

SCALE: 3" = 1'

INFILL FRAMING CONNECTION DETAIL

NEW MODIFIED MEMBRANE

EXTEND OVER THE EXISTING

ROOFING MEMBRANE AS SHOWN

EXISTING ROOFING MEMBRANE

EXISTING ROOF INSULATION

EXISTING METAL DECK

L6" X 6" X 1/4" VERTICAL ATTACH

TO TOP AND BOTTOM CHORD

OF EXISTING ROOF JOIST

EXISTING ROOF JOINT

NEW INSULATION TO MATCH

EXISTING STAGGER ALL JOINS.

FASTEN PER SPECIFCATIONS

NEW METAL DECK INFILL

TO MATCH EXISTING METAL

DECK F.V. (MIN 6'-0" SPAN

RATING)

L4" X 4" X 1/4"

NEW INSULATION TO

MATCH EXISTING. STAGGER

ALL JOINTS. FASTEN PER

SPECIFICATION

OVERLAP AND ATTACH TO EXISTING METAL

DECK / STRUCTURE. WELD OR MECHANICALLY

FASTEN (MATCH EXISTING)

L4" X 4" X 1/4" SHOWN DASHED

TOP CHORD

OF EXISTING

ROOF JOIST

BOTTOM CHORD OF

EXISTING ROOF JOIST

L6" X 6" X 1/4" SHOWN DASHED

L6" X 6" X 1/4"

BOTTOM CHORD OF

EXISTING ROOF JOIST

(TOP CHORD SIMILAR)

STAMP/SEAL

DES

DRN

SCALE

PROJECT NO.

CLIENT PROJECT MGR DEPARTMENT MGR PROJECT MGR

BY DD/MM/YY SUBJECT AREA

CLIENT DWG NO.

DRAWING NO. REV

PROJECT PHASE

APP

CHK

CA

D

FI

LE

SAVED: 09-Mar-21 1:32 PM PLOTTED: 10-Mar-21 3:39 PM USER: RODRIGUEZ, BRANDY

-M4.1

6R-KS-1169-18-04(B)

- -GREAT PLAINS NATURE CENTER

HEATING WATER SYSTEM REPLACEMENT

STRUCTURAL AND ARCHITECTURAL DETAILS

AND MECHANICAL SCHEDULES

J. CROWNHOLM E. GONZALEZ J. MARTIN

3720192002

EG 04/04/19

TW 04/04/19

CV 07/05/19

EG 07/08/19

APPROVED FOR CONSTRUCTION

100% FOR CONSTRUCTION

\\P

HX

4-

FS

1\D

AT

A\

IN

FR

AS

TR

UC

TU

RE

\F

AC

ILI

TI

ES

\P

RO

JE

CT

S\

\37

U

SF

W

S

GR

EA

T

PL

AI

NS

N

AT

UR

E

CE

NT

ER

\9.

0 C

AD

D

RA

W

IN

GS

\09 -S

HE

ET

S\

HE

AT

IN

G

HO

T W

AT

ER

R

EP

LA

CE

ME

NT

\M 4.1

S

TR

UC

TU

RA

L A

ND

A

RC

HI

TE

CT

UR

AL

D

ET

AI

LS

A

ND

M

EC

HA

NI

CA

L S

CH

ED

UL

ES

.D W

G

(2) L4" X 4" X 1/4"

L4" X 4" X 1/4" (TYP)

EXISTING METAL DECK, SEE PLAN

L4" X 4" X 1/4" (TYP)

JOINT SPACING VERIFY IN FIELD

NOTES:

1. UNIT TO BE SHOP ASSEMBLED

AND FIELD WELDED TO JOIST.

2. SEE ARCHITECTURAL AND

MECHANICAL DRAWINGS FOR

SIZE AND LOCATION OF

OPENINGS.

SCALE: 1 1/2" = 1'

IN EXISTING CONSTRUCTION

ROOF OPENING DETAIL

L

I

C

E N

S

E

D

K

A

NS

A

M

I

L

I

O

GO

N

Z

A

L

E

Z

07/11/19

REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REFERENCES

F

E

D

C

B

A

5 4 3 2 19 8 7 6

0TENTHS 0 INCHES 1 2 3 54 6 7 8 9 EIGHTHS10 7010MM 20 30 40 50 60 9080 100

COPYRIGHT © 2018

AR

CH

D -2

4x

UNLESS OTHERWISE AGREED IN A WRITTEN CONTRACT BETWEEN WOOD ENVIRONMENT &

INFRASTRUCTURE SOLUTIONS, INC. AND ITS CLIENT, THIS DOCUMENT: (I) CONTAINS INFORMATION, DATA AND DESIGN THAT IS CONFIDENTIAL AND MAY NOT BE COPIED OR DISCLOSED; AND (II) MAY BE USED BY THE CLIENT ONLY IN THE CONTEXT AND FOR THE EXPRESS PURPOSE FOR WHICH IT WAS INTENDED.

ANY USE OF, OR RELIANCE ON, THIS DOCUMENT BY ANY THIRD PARTY IS AT THAT PARTY'S SOLE RISK.

Environment & Infrastructure Solutions, Inc.

4600 E. WASHINGTON STREET, SUITE 600

PHOENIX, ARIZONA 85034 / PHONE: 602-733-6000

BHHWSTAI

BHHWRTAI

MHHWTEMPAI

AO

BLR1-SDI

BLR1-SP

DO BLR1-C

AI

HHW-DP

DI HHWBYPVLV-S

DO HHWBYPVLV-C

HHWF-GPMAI

AI BLR1-%

BLR1EWT AI

BLR2EWT AI

DIBLR1VLV-S

DOBLR1VLV-C

BLR1LWTAI

BLR2LWT

DIBLR2VLV-S

DOBLR2VLV-C

AO

HWP1-S DI

HWP1SPEED

DOHWP1-C

HWP2-S

HWP2SPEED

HWP2-C

AI HHWBYPVLV-%

SCALE: N.T.S.

CENTRAL PLANT - HEATING WATER CONTROL DIAGRAM

AO

DI

DO

AI

BLR3EWT AI

BLR3LWT

DIBLR3VLV-S

DOBLR3VLV-C

AI

BLR4EWT AI

BLR4LWT

DIBLR4VLV-S

DOBLR4VLV-C

AI

AO

BLR2-SDI

BLR2-SP

DO BLR2-C

AI BLR2-%

AO

BLR3-SDI

BLR3-SP

DO BLR3-C

AI BLR3-%

AO

BLR4-SDI

BLR1-SP

DO BLR4-C

AI BLR1-%

S

T

S

T

S

T

S

T

S

T

S

T

S

T

S

T

S

T

S

T

S

T

STAMP/SEAL

DES

DRN

SCALE

PROJECT NO.

CLIENT PROJECT MGR DEPARTMENT MGR PROJECT MGR

BY DD/MM/YY SUBJECT AREA

CLIENT DWG NO.

DRAWING NO. REV

PROJECT PHASE

APP

CHK

CA

D

FI

LE

SAVED: 09-Mar-21 1:46 PM PLOTTED: 10-Mar-21 3:37 PM USER: RODRIGUEZ, BRANDY

-M5.0

6R-KS-1169-18-04(B)

- -GREAT PLAINS NATURE CENTER

HEATING WATER SYSTEM REPLACEMENT

I/O SUMMARY AND CONTROL DIAGRAM

J. CROWNHOLM E. GONZALEZ J. MARTIN

3720192002

EG 04/04/19

TW 04/04/19

CV 07/05/19

EG 07/08/19

APPROVED FOR CONSTRUCTION

100% FOR CONSTRUCTION

\\P

HX

4-

FS

1\D

AT

A\

IN

FR

AS

TR

UC

TU

RE

\F

AC

ILI

TI

ES

\P

RO

JE

CT

S\

\37

U

SF

W

S

GR

EA

T

PL

AI

NS

N

AT

UR

E

CE

NT

ER

\9.

0 C

AD

D

RA

W

IN

GS

\09 -S

HE

ET

S\

HE

AT

IN

G

HO

T W

AT

ER

R

EP

LA

CE

ME

NT

\M 5.0

IO

S

UM

MA

RY

A

ND

C

ON

TR

OL

D

IA

GR

AM

.D

W G

L

I

C

E N

S

E

D

K

A

NS

A

M

I

L

I

O

GO

N

Z

A

L

E

Z

07/11/19

AutoCAD SHX Text

DP

ABBREVIATIONS

A AMPS

HP HORSEPOWER

KW KILOWATTS

KWH KILOWATT HOUR

V VOLTS

AC ALTERNATING CURRENT

DC DIRECT CURRENT

UNO UNLESS NOTED OTHERWISE

AFF ABOVE FINISHED FLOOR

KV THOUSAND VOLTS

KVA KILOVOLT-AMPERES

MVA MEGAVOLT-AMPERES

AIC AMPS INTERRUPTING CAPACITY

MCP MOTOR CIRCUIT PROTECTOR

HMCP HIGH CAPACITY MOTOR CIRCUIT PROTECTOR

TMCB THERMAL MAGNETIC CIRCUIT BREAKER

VCB VACUUM CIRCUIT BREAKER

CPT CONTROL POWER TRANSFORMER

FU FUSE

TB TERMINAL BLOCK

W WATTS

AM AMMETER

VM VOLTMETER

MPR MULTI-PURPOSE OR MOTOR PROTECTION RELAY

AWG AMERICAN WIRE GAUGE

KCMIL THOUSANDS OF CIRCULAR MILLS

OL MOTOR OVERLOADS, THERMAL OR ELECTRONIC

PLC PROGRAMMABLE LOGIC CONTROLLER

EXIT LIGHT WITH ARROW

EXIT LIGHT - DOUBLE DIRECTED

EXIT LIGHT - SINGLE DIRECTED

FLOOD LIGHT - TWIN

EMERGENCY LIGHT

EXIT LIGHT

LIGHT POLE

WALKWAY LIGHT

RECESSED SURFACE LIGHT

SINGLE FLOOD LIGHT

3-WAY WALL SWITCH

4-WAY WALL SWITCH

DIMMER SWITCH

RECESSED1X4_EMERGENCY

SINGLE SWITCH

(3) -A FU

N

30A/3P

F DISCONNECT WITH RATINGS

STARTER WITH DISCONNECT

EQUIPMENT_CONNECTION

FLEX_CONDUIT_2

HOME RUN

J-BOX

MOTOR

MOTOR

PANEL

PUSH BUTTON DOUBLE

PUSH BUTTON EMERGENCY

PUSH BUTTON SINGLE

RECEPTACLE DUPLEX

RECEPTACLE QUAD

RECEPTACLE SINGLE

RECEPTACLE SPECIAL

SEAL OFF

WIREMOLD

CONDUCTORS IN CONDUIT, LONG

LINES HOT, SHORT LINES

NEUTRAL, GROUND NOT SHOWN

BUT REQUIRED

PLAN DRAWING SYMBOLS - ELECTRICAL DEVICES PLAN DRAWING SYMBOLS - LIGHTING AND SWITCHES SINGLE LINE DRAWING SYMBOLS

CIRCUIT BREAKER, DRAW OUT STYLE,

MEDIUM VOLTAGE

FUSED VACUUM CONTACTOR/STARTER,

DRAW OUT STYLE, 5KV

TRANSFORMER

DELTA CONNECTION

GROUNDED WYE CONNECTION

RESISTANCE GROUNDED CONNECTION

ANSI DEVICE OR RELAY FUNCTION

51G SHOWN AS REFERENCE ONLY

CURRENT TRANSFORMER, GROUND

TYPE

CURRENT TRANSFORMER, PHASE

POTENTIAL TRANSFORMER

BATTERY BANK

CAPACITOR OR CAPACITOR BANK

FUSED CUTOUT, POLE MOUNTED

FUSE

BUSSED THROAT CONNECTION OR BUS

DUCT

MEDIUM VOLTAGE CABLE STRESS CONE

TERMINATION KIT

LIGHTNING ARRESTOR

SAFETY SWITCH, 600V MAXIMUM

BI-METALLIC MOTOR OVERLOADS

CIRCUIT BREAKER, 600V MAXIMUM

GROUND CONNECTION

CONTACT, NORMALLY CLOSED

CONTACT, NORMALLY OPEN

INDICATES FUNCTIONAL INTERLOCKING

OF EQUIPMENT

SURGE ARRESTOR

51G

CURRENT TRANSFORMER, PHASE

MULTI-RATIO

LIGHTING OR SMALL POWER

DISTRIBUTION PANEL

MOTOR WITH

HORSEPOWER LISTED

MISCELLANEOUS ELECTRICAL LOAD

WITH DEMAND KVA LISTED

KVA

KVA

CURRENT TRANSFORMER

POLARITY MARK

LOR

SS

RTD

MSH

VSH

ES

VOLT METER

AMMETER

LOCAL-OFF-REMOTE SELECTOR SWITCH

START - STOP PUSHBUTTON

RESISTANCE TEMPERATURE DEVICE

MOTOR SPACE HEATER

HIGH VIBRATION SWITCH

EMERGENCY STOP PUSHBUTTON

VFD

VARIABLE FREQUENCY DRIVE W/DISCONNECT

ELECTRICAL SHEET LIST

E0.1 ELECTRICAL ABBREVIATIONS, LEGEND, SYMBOLS AND GENERAL NOTES

E1.0 ELECTRICAL PANEL SCHEDULES AND ONE LINE DIAGRAMS

E2.0 ELECTRICAL DEMOLITION PLAN - CENTRAL PLANT

E3.0 ELECTRICAL NEW PLAN - CENTRAL PLANT

REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REFERENCES

REF NUMBER TITLE

F

E

D

C

B

A

5 4 3 2 19 8 7 6

0TENTHS 0 INCHES 1 2 3 54 6 7 8 9 EIGHTHS10 7010MM 20 30 40 50 60 9080 100

COPYRIGHT © 2018

AR

CH

D -2

4x

UNLESS OTHERWISE AGREED IN A WRITTEN CONTRACT BETWEEN WOOD ENVIRONMENT &

INFRASTRUCTURE SOLUTIONS, INC. AND ITS CLIENT, THIS DOCUMENT: (I) CONTAINS INFORMATION, DATA AND DESIGN THAT IS CONFIDENTIAL AND MAY NOT BE COPIED OR DISCLOSED; AND (II) MAY BE USED BY THE CLIENT ONLY IN THE CONTEXT AND FOR THE EXPRESS PURPOSE FOR WHICH IT WAS INTENDED.

ANY USE OF, OR RELIANCE ON, THIS DOCUMENT BY ANY THIRD PARTY IS AT THAT PARTY'S SOLE RISK.

Environment & Infrastructure Solutions, Inc.

4600 E. WASHINGTON STREET, SUITE 600

PHOENIX, ARIZONA 85034 / PHONE: 602-733-6000

STAMP/SEAL

DES

DRN

SCALE

PROJECT NO.

CLIENT PROJECT MGR DEPARTMENT MGR PROJECT MGR

BY DD/MM/YY SUBJECT AREA

CLIENT DWG NO.

DRAWING NO. REV

PROJECT PHASE

APP

CHK

CA

D

FI

LE

SAVED: 09-Mar-21 10:51 AM PLOTTED: 10-Mar-21 4:03 PM USER: RODRIGUEZ, BRANDY

-E0.1

6R-KS-1169-18-04(B)

- -GREAT PLAINS NATURE CENTER

HEATING WATER SYSTEM REPLACEMENT

ELECTRICAL ABBREVIATIONS, LEGEND,

SYMBOLS AND GENERAL NOTES

J. CROWNHOLM S. KAIN J. MARTIN

3720192002

NTS

SJK -

SJK 19/03/19

T. RAFFIN 10/07/19

T. RAFFIN 10/07/19

APPROVED FOR CONSTRUCTION

100% FOR CONSTRUCTION

\\P

HX

4-

FS

1\D

AT

A\

IN

FR

AS

TR

UC

TU

RE

\F

AC

ILI

TI

ES

\P

RO

JE

CT

S\

\37

U

SF

W

S

GR

EA

T

PL

AI

NS

N

AT

UR

E

CE

NT

ER

\9.

0 C

AD

D

RA

W

IN

GS

\09 -S

HE

ET

S\

HE

AT

IN

G

HO

T W

AT

ER

R

EP

LA

CE

ME

NT

\E 0.1

-E

LE

CS

YM

BO

LS

AN

DL

EG

EN

D.

DW

G

AutoCAD SHX Text

AutoCAD SHX Text S

AutoCAD SHX Text

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text D

AutoCAD SHX Text S

AutoCAD SHX Text E

J

REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REFERENCES

F

E

D

C

B

A

5 4 3 2 19 8 7 6

0TENTHS 0 INCHES 1 2 3 54 6 7 8 9 EIGHTHS10 7010MM 20 30 40 50 60 9080 100

COPYRIGHT © 2018

AR

CH

D -2

4x

UNLESS OTHERWISE AGREED IN A WRITTEN CONTRACT BETWEEN WOOD ENVIRONMENT &

INFRASTRUCTURE SOLUTIONS, INC. AND ITS CLIENT, THIS DOCUMENT: (I) CONTAINS INFORMATION, DATA AND DESIGN THAT IS CONFIDENTIAL AND MAY NOT BE COPIED OR DISCLOSED; AND (II) MAY BE USED BY THE CLIENT ONLY IN THE CONTEXT AND FOR THE EXPRESS PURPOSE FOR WHICH IT WAS INTENDED.

ANY USE OF, OR RELIANCE ON, THIS DOCUMENT BY ANY THIRD PARTY IS AT THAT PARTY'S SOLE RISK.

Environment & Infrastructure Solutions, Inc.

4600 E. WASHINGTON STREET, SUITE 600

PHOENIX, ARIZONA 85034 / PHONE: 602-733-6000

STAMP/SEAL

DES

DRN

SCALE

PROJECT NO.

CLIENT PROJECT MGR DEPARTMENT MGR PROJECT MGR

BY DD/MM/YY SUBJECT AREA

CLIENT DWG NO.

DRAWING NO. REV

PROJECT PHASE

APP

CHK

CA

D

FI

LE

SAVED: 09-Mar-21 10:53 AM PLOTTED: 10-Mar-21 4:02 PM USER: RODRIGUEZ, BRANDY

-E1.0

6R-KS-1169-18-04(B)

- -GREAT PLAINS NATURE CENTER

HEATING WATER SYSTEM REPLACEMENT

ELECTRICAL PANEL SCHEDULES AND

ONE LINE DIAGRAMS

J. CROWNHOLM S. KAIN J. MARTIN

3720192002

NTS

SJK -

SJK 19/03/19

T. RAFFIN 10/07/19

T. RAFFIN 10/07/19

APPROVED FOR CONSTRUCTION

100% FOR CONSTRUCTION

\\P

HX

4-

FS

1\D

AT

A\

IN

FR

AS

TR

UC

TU

RE

\F

AC

ILI

TI

ES

\P

RO

JE

CT

S\

\37

U

SF

W

S

GR

EA

T

PL

AI

NS

N

AT

UR

E

CE

NT

ER

\9.

0 C

AD

D

RA

W

IN

GS

\09 -S

HE

ET

S\

HE

AT

IN

G

HO

T W

AT

ER

R

EP

LA

CE

ME

NT

\E 1.0

-E

LE

CP

AN

EL

SC

HE

DU

LE

SA

ND

ON

EL

IN

ES

.D

W G

PANEL "B2" SCHEDULE - AS FOUND

PANEL "B2" SCHEDULE - REVISED FOR NEW WORK

PANEL SCHEDULE AND 1-LINE NOTES:

1. CIRCUIT BREAKER, CONDUCTOR, AND LOAD HAVE ALL CHANGED FROM "AS-FOUND"

CONDITION. NEW CONDUCTORS SHALL BE NEC TYPE THWN, STRANDED COPPER.

2. HWP'S ARE REDUNDANT. ONLY ONE HWP WILL RUN AT ANY TIME. THIS IS WHY LOADS

IN CIRCUITS 16/18/20 ARE LISTED AS ZERO VOLT-AMPS. HWP'S SHALL BE

INTERLOCKED EITHER HARD WIRED OR THROUGH THE FACILITY CONTROL SYSTEM

SUCH THAT THEY CANNOT OPERATE CONCURRENTLY.

3. LOAD CHANGED FROM FOUR BOILERS TO TWO BOILERS. REVISE PANEL SCHEDULE

TO MATCH. LOAD CHANGED ACCORDINGLY. CIRCUIT BREAKERS AND CONDUCTORS

ARE UNCHANGED.

4. LOADS SHOWN IN "AS-FOUND" SCHEDULE ARE BASED UPON EXISTING DRAWINGS

AND A SITE INSPECTION. WHILE THERE MAY BE MINOR DISCREPANCIES IN INDIVIDUAL

CIRCUITS, ENGINEER IS SATISFIED THAT THE OVERALL PANEL LOAD IS ACCURATE.

SEE GENERAL NOTE 2.

GENERAL NOTES:

1. CHANGES TO THE "AS-FOUND" CONDITION ARE DENOTED BY REVISION

CLOUDS. NOTES ASSOCIATED WITH THE REVISED CIRCUITS DESCRIBE

THE CHANGES.

2. PRIOR TO BEGINNING WORK, CONTRACTOR SHALL MEASURE AND

RECORD THE PANEL "B2" FEEDER AMPS WITH BOTH CWP AND HWP

PUMPS RUNNING. AFTER INSTALLATION OF THE HWP VFD'S,

CONTRACTOR SHALL AGAIN MEASURE AND RECORD THE PANEL "B2"

FEEDER AMPS WITH ONLY ONE OF THE HWP'S RUNNING. DELIVER THE

MEASUREMENTS TO THE CONTRACTING OFFICER AND NOTIFY

ENGINEER IF EITHER OF THESE READINGS EXCEEDS 160 AMPS.

REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REFERENCES

F

E

D

C

B

A

5 4 3 2 19 8 7 6

0TENTHS 0 INCHES 1 2 3 54 6 7 8 9 EIGHTHS10 7010MM 20 30 40 50 60 9080 100

COPYRIGHT © 2018

AR

CH

D -2

4x

UNLESS OTHERWISE AGREED IN A WRITTEN CONTRACT BETWEEN WOOD ENVIRONMENT &

INFRASTRUCTURE SOLUTIONS, INC. AND ITS CLIENT, THIS DOCUMENT: (I) CONTAINS INFORMATION, DATA AND DESIGN THAT IS CONFIDENTIAL AND MAY NOT BE COPIED OR DISCLOSED; AND (II) MAY BE USED BY THE CLIENT ONLY IN THE CONTEXT AND FOR THE EXPRESS PURPOSE FOR WHICH IT WAS INTENDED.

ANY USE OF, OR RELIANCE ON, THIS DOCUMENT BY ANY THIRD PARTY IS AT THAT PARTY'S SOLE RISK.

Environment & Infrastructure Solutions, Inc.

4600 E. WASHINGTON STREET, SUITE 600

PHOENIX, ARIZONA 85034 / PHONE: 602-733-6000

SCALE:

STAMP/SEAL

DES

DRN

SCALE

PROJECT NO.

CLIENT PROJECT MGR DEPARTMENT MGR PROJECT MGR

BY DD/MM/YY SUBJECT AREA

CLIENT DWG NO.

DRAWING…