Atch 2 GPNC Heating Water System Drawings.pdf
PDF 4 MB Posted
- Attached to
- GPNC Replace Water Heating System Federal contract opportunity
- Solicitation number
- 140F0121R0031
About this file
This is a solicitation for replacement of a water heating system at the Great Plains Nature Center. The project requires removal of existing HVAC boilers, pumps, valves and installation of new pumps, valves, and controls. Work includes removing old equipment, installing new hydronic pumps, specialties, and two-way control valves, as well as HVAC controls upgrades and emergency boiler connections. The federal agency is the Department of the Interior Fish and Wildlife Service.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140F0121R0031_Amd_0002.pdf | ||
| Sol_140F0121R0031_Amd_0001.pdf | ||
| Amend_0001_Atch_1_Example_Comissioning_0001.pdf | ||
| Atch 4 GPNC Water Heating System DBA Det Wage Rate.pdf | ||
| Sol_140F0121R0031.pdf | ||
| Atch 3 GPNC Water Heating System Submittal List.pdf | ||
| Atch 5 GPNC Water Heating System Past Perf Quest.doc | DOC document | |
| Atch 1 GPNC Heating Water System Specs.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Environment & Infrastructure Solutions, Inc.
4600 E. WASHINGTON STREET, SUITE 600
PHOENIX, ARIZONA 85034 / PHONE: 602-733-6000
6232 EAST 29TH ST N,
WICHITA, KS 67220
3720192002
JAY MARTIN
(615) - 333 - 0630 jay.martin@woodplc.com
WOOD PROJECT NUMBER:
PROJECT MANAGER CONTACT:
PHONE:
EMAIL:
EMILIO GONZALEZ
(602) - 733 - 6008 emilio.gonzalez@woodplc.com
MECHANICAL CONTACT:
PHONE:
EMAIL:
STEVEN KAIN
(602) - 733 - 6139 steven.kain@woodplc.com
ELECTRICAL CONTACT:
PHONE:
EMAIL:
L
I
C
E N
S
E
D
K
A
NS
A
S
P
R
O
F
E
I
O
N A L
G
26855
E
M
I
L
I
O
GO
N
Z
A
L
E
Z
07/11/19
AutoCAD SHX Text
FISH AND WILDLIFE SERVICE
AutoCAD SHX Text
UNITED STATES DEPARTMENT OF THE INTERIOR
AutoCAD SHX Text
REGION 6 ENGINEERING - DENVER, COLORADO
AutoCAD SHX Text
DESIGNED:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DRAWN:
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
SHEET 1 OF
AutoCAD SHX Text
CHECKED:
AutoCAD SHX Text
VICINITY MAP
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
OR
AutoCAD SHX Text
RI
AutoCAD SHX Text
ME
AutoCAD SHX Text
RT
AutoCAD SHX Text
PA
AutoCAD SHX Text
DE
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text
NT
AutoCAD SHX Text
TE
AutoCAD SHX Text
IN
AutoCAD SHX Text E
AutoCAD SHX Text
TH
AutoCAD SHX Text
FISH AND WILDLIFE
AutoCAD SHX Text
SERVICE
AutoCAD SHX Text U.S.
AutoCAD SHX Text
U.S. FISH & WILDLIFE SERVICE
AutoCAD SHX Text
SERVICE
AutoCAD SHX Text
FISH AND WILDLIFE
AutoCAD SHX Text
TH
AutoCAD SHX Text
ME
AutoCAD SHX Text
RT
AutoCAD SHX Text
PA
AutoCAD SHX Text
DE
AutoCAD SHX Text
NT
AutoCAD SHX Text F
AutoCAD SHX Text O
AutoCAD SHX Text
OR
AutoCAD SHX Text
RI
AutoCAD SHX Text
TE
AutoCAD SHX Text
IN
AutoCAD SHX Text E
AutoCAD SHX Text U.S.
AutoCAD SHX Text
APPROVAL SIGNATURES
AutoCAD SHX Text
ANY PRINT ACCOMPANYING THIS INVITATION TO BID MAY BE A REDUCED
AutoCAD SHX Text
REPRODUCTION OF THE WORKING DRAWINGS. IF LINE BELOW DOES NOT
AutoCAD SHX Text
MEASURE SIX INCHES IN LENGTH, THE INDICATED SCALES ARE TO BE
AutoCAD SHX Text
ADJUSTED ACCORDINGLY.
AutoCAD SHX Text
%%UNOTE TO BIDDERS:%%
AutoCAD SHX Text
REGIONAL ENGINEER
AutoCAD SHX Text
ASS'T. REGIONAL DIR.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
PROGRAM SUPERVISOR
AutoCAD SHX Text
FACILITIES
AutoCAD SHX Text
CULTURAL RESOURCES
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
GREAT PLAINS NATURE CENTER
AutoCAD SHX Text
SEDGWICK COUNTY
AutoCAD SHX Text
KANSAS
AutoCAD SHX Text
GREAT PLAINS NATURE CENTER HVAC HEATING WATER REPLACEMENT
AutoCAD SHX Text
EPG / SJK
AutoCAD SHX Text
TW / TM
AutoCAD SHX Text
SM / ER
AutoCAD SHX Text 06/10/19
AutoCAD SHX Text
6R-KS-1169-18-04(B)
AutoCAD SHX Text
AutoCAD SHX Text
GREAT PLAINS NATURE CENTER
AutoCAD SHX Text
GREAT PLAINS NATURE CENTER HEATING
AutoCAD SHX Text SHEET# SHEET NAME COVER SHEET M0.1 MECHANICAL LEGEND, SHEET LIST, AND ABBREVIATIONS MECHANICAL LEGEND, SHEET LIST, AND ABBREVIATIONS M0.2 MECHANICAL GENERAL NOTES MECHANICAL GENERAL NOTES M1.0 MECHANICAL DEMOLITION PLAN - CENTRAL PLANT MECHANICAL DEMOLITION PLAN - CENTRAL PLANT M2.0 MECHANICAL NEW PLAN - CENTRAL PLANT MECHANICAL NEW PLAN - CENTRAL PLANT M2.1 MECHANICAL NEW PLAN - AIR HANDLING UNITS MECHANICAL NEW PLAN - AIR HANDLING UNITS M3.0 MECHANICAL ONE LINE DIAGRAMS MECHANICAL ONE LINE DIAGRAMS M4.0 MECHANICAL DETAILS MECHANICAL DETAILS M4.1 STRUCTURAL AND ARCHITECTURAL DETAILS AND MECHANICAL SCHEDULES STRUCTURAL AND ARCHITECTURAL DETAILS AND MECHANICAL SCHEDULES M5.0 I/O SUMMARY AND CONTROL DIAGRAM I/O SUMMARY AND CONTROL DIAGRAM E0.1 ELECTRICAL SYMBOLS AND LEGEND ELECTRICAL SYMBOLS AND LEGEND E1.0 ELECTRICAL PANEL SCHEDULES AND ONE LINES ELECTRICAL PANEL SCHEDULES AND ONE LINES E2.0 ELECTRICAL DEMOLITION PLAN ELECTRICAL DEMOLITION PLAN E3.0 ELECTRICAL NEW WORK PLAN ELECTRICAL NEW WORK PLAN S1.0 STRUCTURAL DETAILSSTRUCTURAL DETAILS
AutoCAD SHX Text
WATER SYSTEM REPLACEMENT
amercer Text Box N/A amercer Text Box N/A amercer Text Box
SAFETY/IND HYGIENIST
WALL MOUNTED OSCILLATING FAN
CEILING PADDLE FAN
EXIST HOT WATER FIN TUBE UNIT TAG
(FOR 4-WAY THROW ARROWS NOT SHOWN)
DIRECTION SHOWN BY ARROWS
CEILING SUPPLY DIFFUSER W/ THROW
SEQUENCE NUMBER
LENGTH OF ACTIVE FIN TUBE
CFM
NITROGEN DIOXIDE SENSOR
CO
CARBON MONOXIDE SENSOR
DOOR LOUVER
FLEXIBLE CONNECTOR
DIRECTION OF AIR FLOW EXHAUST
HOT WATER COIL
FINTUBE DESIGNATION
MBH
SMOKE DETECTOR
TERMINAL UNIT, VARIABLE VOLUME WITH
PUMP
STARTER/DISCONNECT
ROOF VENTILATOR, EXHAUST
FLEXIBLE DUCT
SQUARE ELBOW WITH TURNING VANES
CONNECT TO EXISTING
THERMOSTAT OR THERMISTOR
MOTORIZED DAMPER, OPPOSED BLADE
MOTORIZED DAMPER, PARALLEL BLADE
FIRE DAMPER
SMOKE DAMPER
DIRECTION OF AIR FLOW
INLINE FAN
CENTRIFUGAL FAN
PROPELLER FAN
TERMINAL UNIT, VARIABLE VOLUME
UNIT HEATER
FINTUBE RADIATION AND ENCLOSURE
SUPPLY GRILLE, DIFFUSER
RETURN GRILLE, REGISTER
DIFFUSER, REGISTER OR GRILLE
SYMBOL PER ABBREVIATION LIST
FD
SD
EQUIPMENT SEQUENCE NUMBER
HUMIDISTAT
SWITCH
M
M
T
H
S
S
AUTOMATIC AIR VENT WITH ISOLATION VALVE
BOILER DRAIN VALVE W/ HOSE BIB
BALL VALVE IN VERTICAL
DN
UP
NEZV
ABBREVIATIONS
BUCKET TRAP
STEAM MONITOR
THREE-WAY AUTOMATIC CONTROL VALVE
THREE-WAY AUTOMATIC CONTROL VALVE
TWO-WAY AUTOMATIC CONTROL VALVE
TWO-WAY AUTOMATIC CONTROL VALVE
MECHANICAL SYMBOLS
COMBINATION FLOW MEASURING/
BALANCING VALVE (CIRCUIT SETTER)
GATE VALVE
GLOBE VALVE
PLUG VALVE
CHECK VALVE
SAFETY RELIEF VALVE
STRAINER W/BALL DRAIN VALVE, HOSE
BIB AND CAP (GATE VALVE FOR STEAM)
UNION AS DICTATED BY PIPE SIZE
PIPE END CAP
PRESSURE GAUGE W/BALL VALVE
(GATE VALVE AND SIPHON FOR STEAM)
THERMOMETER
TEMPERATURE/PRESSURE WELL
("PETE'S PLUG")
MANUAL AIR VENT
FLEXIBLE PIPE CONNECTION
VIBRATION ISOLATOR
PIPE GUIDE
DIRT LEG
DIRECTION OF FLOW OF PIPE
PIPE PITCH UP IN DIRECTION OF FLOW
PIPE PITCH DOWN IN DIRECTION OF FLOW
FLOAT AND THERMOSTATIC TRAP
THERMOSTATIC TRAP
PIPING SYMBOLS DUCTWORK SYMBOLS
VD
VD
VD
VD
VD
SUPPLY
EXHAUST/RETURN
VD
VD
SQUARE ELBOW
W/TURNING VANES
RADIUS ELBOW
SPLIT TAKE-OFF
W/ BRANCH
DAMPERS
BULLHEAD SPLIT
TAKE-0FF
BULLHEAD
TEE
OFFSET
VD
CEILING DIFFUSER
OR GRILLE W/
FLEXIBLE DUCT
PRESSURE REDUCING VALVE
BALL VALVE
BUTTERFLY VALVE
OS&Y VALVE
OS&Y VALVE IN VERTICAL (PLAN)
NONELECTRIC ZONE VALVE
PRESSURE SWITCH
TEMPERATURE SENSOR
FLOW SWITCH, FREEZESTAT
SUPPLY DUCT UP
SUPPLY DUCT DOWN
RISE(R) OR DROP(D)
RETURN/EXHAUST
DUCT UP
RETURN/EXHAUST
DUCT DOWN
END SWITCH
AIR FLOW SWITCH
PIPE TEE FROM TOP
PIPE TEE FROM BOTTOM
PIPE RISE
PIPE DROP
(ELECTRIC OR DDC)
(PNEUMATIC)
(ELECTRIC OR DDC)
(PNEUMATIC)
PIPE UP TO FINTUBE
RADIATION ON FLOOR ABOVE
COCK
STRAINER W/ BLOW OFF
AIR SEPARATOR
S
PRESSURE REGULATING VALVE
REDUCED PRESSURE BACKFLOW PREVENTER
FUSOMATIC VALVE
DOOR UNDERCUT
DRAWING WHERE DETAIL IS DRAWN
DETAIL NUMBER
DETAIL NUMBER
THREE WAY VALVE
FLANGE AS DICTATED BY PIPE SIZE
S
M
@ AT
(E) EXISTING
(N) NEW
A AMP
ABS ACRYLONITRILE BUTADIENE
STYRENE PLASTIC
ABV ABOVE
AC AIR CONDITIONING
AD ACCESS DOOR
ADA AMERICANS WITH DISABILITIES
ACT
ADS AIR DIRT SEPARATOR
AF AIR FILTER
AFF ABOVE FINISHED FLOOR
AFM AIR FLOW MEASURING STATION
AHU AIR HANDLING UNIT
AL ACOUSTICAL LINER
AMB AMBIENT
AP ACCESS PANEL
APD AIR PRESSURE DROP
APPROX APPROXIMATELY
AS AIR SEPARATOR
ASME AMERICAN SOCIETY OF
MECHANICAL ENGINEERS
ASSY ASSEMBLY
ATC AUTOMATIC TEMPERATURE
CONTROL
ATT ACOUSTICAL ATTENUATOR
AV AUTOMATIC VENT
AW ACID WASTE
AWV ACID WASTE VENT
B BOILER
BDD BACKDRAFT DAMPER
BHP BRAKE HORSEPOWER
BLDG BUILDING
BOT BOTTOM
BTUH BTU PER HOUR
C CENTERLINE
CA COMPRESSED AIR
CAP CAPACITY
CD CONDENSATE DRAIN
CDWR CONDENSER WATER RETURN
CDWS CONDENSER WATER SUPPLY
CDWS&R CONDENSER WATER SUPPLY &
RETURN
CF CEILING FAN
CFM CUBIC FEET PER MINUTE
CH CHILLER
CHWP CHILLED WATER PUMP
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CHWS&R CHILLED WATER SUPPLY &
RETURN
CLG CEILING
CO CLEAN OUT, CARBON MONOXIDE
COL COLUMN
CONC CONCRETE
COND CONDENSATE
CONN CONNECTION
CONT CONTINUATION
CONV CONVECTOR
CP CONTROL PANEL, CONDENSATE
PUMP
CPT CONDENSATE PUMP TRAP
CSA CANADIAN STANDARDS
ASSOCIATION
CT COOLING TOWER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CV CONTROL VALVE
Cv CONTROL VALVE RATING
CVT CONSTANT VOLUME AIR
TERMINAL
CW COLD WATER
D DRAIN
dB DECIBELS
DB DRY BULB
DC DRY COOLER
DDC DIRECT DIGITAL CONTROL
Ø, DIA DIAMETER
DIFF DIFFERENTIAL, DIFFUSER
DISCH DISCHARGE
DN DOWN
DOM DOMESTIC
DP DIFFERENTIAL PRESSURE
DWG DRAWING
DWGS DRAWINGS
E EXHAUST GRILLE
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EC ELECTRICAL CONTRACTOR
EDR EQUIVALENT DIRECT
RADIATION
EER ENERGY EFFICIENT RATIO
EF EXHAUST FAN
EFF EFFICIENCY
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATION
ENT ENTERING
EPDM ETHYLENE PROPYLENE DIENE
MEMBRANE
EQUIP EQUIPMENT
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
EVAP EVAPORATOR
EWC ELECTRIC WATER COOLER
EWT ENTERING WATER TEMP
EXH EXHAUST
EXIST EXISTING
EXT EXPANSION TANK
EXP EXPANSION
F FAN, DEGREES FAHRENHEIT
FA FRESH AIR
FAI FRESH AIR INTAKE
FBG FURNISHED BY GOVERNMENT
FC FLEX CONNECTION
FCO FLOOR CLEANOUT
FD FIRE DAMPER, FLOOR DRAIN
FF FINISH FLOOR
FIX FIXTURE
FLA FULL LOAD AMPS
FLR FLOOR
FOB FLAT ON BOTTOM
FOT FLAT ON TOP
FS FLOAT SWITCH
FTR FIN TUBE RADIATION
FZ FREEZESTAT
G GAS
GA GAUGE
GAL GALLONS
GALV GALVANIZED
GC GENERAL CONTRACTOR
GP GENERAL PURPOSE
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GR GLYCOL RETURN
GRH GRAVITY RELIEF HOOD
GS GLYCOL SUPPLY
GV GATE VALVE
GSM GALVANIZED SHEET METAL
GW GREASE WASTE
GWV GREASE WASTE VENT
GYP GYPSUM WALLBOARD
HC HEATING COIL
HOA HANDS-OFF-AUTOMATIC
HW HOT WATER
HWR HOT WATER RECIRCULATED
HOR HORIZONTAL
HP HORSEPOWER, HIGH
PRESSURE
HPC HIGH PRESSURE COND
HPS HIGH PRESSURE STEAM
(16 PSI TO 150 PSI)
HR HOUR
HT HEIGHT
HUMID HUMIDIFIER, HUMIDITY
HV HEATING AND VENTILATING
UNIT
HVAC HEATING, VENTILATING AND
AIR CONDITIONING
HHW HEATING HOT WATER
HHWP HEATING HOT WATER PUMP
HHWR HEATING HOT WATER RETURN
HHWS HEATING HOT WATER SUPPLY
HHWS&R HEATING HOT WATER SUPPLY
& RETURN
HX HEAT EXCHANGER
HZ HERTZ
IBR HYDRONICS INSTITUTE
ID INSIDE DIAMETER
IN INCHES
INDIR INDIRECT WASTE
KW KILOWATT
L LENGTH, LOUVER
LAT LEAVING AIR TEMP
LD LIQUIFIED PETROLEUM
LDB LEAVING DRY BULB
LF LINEAR FEET
LG LONG
LOC LOCATION, LOCATED
LP LIQUEFIED PROPANE
LPC LOW PRESSURE COND
LPS LOW PRESSURE STEAM
(15 PSI OR LESS)
LRA LOCKED ROTOR AMPS
LVG LEAVING
LWB LEAVING WET BULB
LWT LEAVING WATER TEMP
M MECHANICAL
MANUF MANUFACTURER
MAX MAXIMUM
MAX PD MAXIMUM PRESSURE
DROP
MBH 1000 BTU PER HOUR
MBU 1000 BTU
MCA MAXIMUM CIRCUIT AMPS
MCC MOTOR CONTROL
CENTER
MD MOTORIZED DAMPER
MECH MECHANICAL
MEZZ MEZZANINE
MFG MANUFACTURER
MIN MINIMUM, MINUTES
MISC MISCELLANEOUS
mm MILLIMETERS
MNTD MOUNTED
MOCP MAXIMUM OVERCURRENT
PROTECTION
MUA MAKE-UP AIR
MUW MAKE-UP WATER
N/A NOT APPLICABLE
NATL NATURAL
NC NORMALLY CLOSED
NOISE CRITERIA
NEC NATIONAL ELECTRIC
CODE
NG NATURAL GAS
NFPA NATIONAL FIRE
PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NO NUMBER, NORMALLY
OPEN
N02 NITROGEN DIOXIDE
NTS NOT TO SCALE
OA OUTSIDE AIR
OAI OUTSIDE AIR INTAKE
OAT OUTSIDE AIR TEMP
OBD OPPOSED BLADE DAMPER
OD OUTSIDE DIAMETER
OED OPEN ENDED DUCT
OF OVERFLOW
OS&Y OUTSIDE STEM AND YOKE
P PUMP, PITCH
PC PUMPED CONDENSATE
PD PRESSURE DROP
PF POT FEEDER
PLMB PLUMBING
PRESS PRESSURE
PRV PRESSURE REDUCING
VALVE
PSI POUNDS PER SQUARE
INCH
PSIG POUNDS PER SQUARE
INCH GAUGE
PT PRESSURE TREATED
PVC POLYVINYL CHLORIDE
TRIPLE DUTY VALVE
DEMO UP TO THIS POINT
SUPPLY
AHU
S-#
2.2
5 LF
FR-1
2.2
FLOWRATE (GPM)
KEYNOTE (NUMBER)
REVISION (LETTER)
NO2
EXISTING TO REMAIN
REMOVAL / DEMOLITION
NEW WORK
HIDDEN ITEMS
PIPE CONTINUATION
AFS
B
BUTTERFLY VALVE W/ MOTOR
BALL VALVE W/ MOTOR
BALANCING VALVE
E
S
P
S
S
T
ANGULAR GLOBE VALVE W/ MOTOR
ANGULAR GLOBE VALVE
ANGULAR GATE VALVE
TWO-WAY VALVE
NEEDLE
PIPE DOWN W/ VALVE
PIPE UP W/ VALVE
EXHAUST GRILLE, REGISTER
QTY QUANTITY
R RETURN GRILLE
RA RETURN AIR
RAD RADIATOR
RAF, RF RETURN AIR FAN
RAT RETURN AIR TEMP
REL RELIEF
REQD REQUIRED
RET RETURN
RH RELATIVE HUMIDITY
RL REFRIGERANT LIQUID
RLA RATED LOAD AMPS
RM ROOM
RPM REVOLUTIONS PER
MINUTE
RS REFRIGERANT
SUCTION
RTU ROOFTOP UNIT
S SUPPLY DIFFUSER
SA SUPPLY AIR
SCR SCREEN
SD SMOKE DAMPER
SF SQUARE FOOT
SIM SIMILAR
SMACNA SHEET METAL AND
AIR CONDITIONING
CONTRACTOR'S
NATIONAL
ASSOCIATION
SOV SHUT OFF VALVE
SP STATIC PRESSURE
SPH STATIC PRESSURE
HIGH LIMIT
SPL STATIC PRESSURE
LOW LIMIT
SPS STATIC PRESSURE
SENSOR
SQ SQUARE
SS STAINLESS STEEL
STL STEEL
SUP SUPPLY
SW SANITARY WASTE
SWD SANITARY WASTE
DRAIN
SWV SANITARY WASTE
VENT
T TEMPERATURE
SENSOR,
THERMOSTAT
TC TOTAL COOLING
TCV TEMPERATURE
CONTROL VALVE
TEMP TEMPERATURE
THK THICK, THICKNESS
TG TRANSFER GRILLE
TRANS TRANSITION
TSP TOTAL STATIC
PRESSURE
TW TEMPERED WATER
TYP TYPICAL
UH UNIT HEATER
UNO UNLESS NOTED
OTHERWISE
V VENT
VAV VARIABLE AIR
VOLUME
VD VOLUME DAMPER
VEL VELOCITY
VFD VARIABLE
FREQUENCY DRIVE
VTR VENT THROUGH
ROOF
W WIDTH, WATT
W/ WITH
WB WET BULB
WC WATER COLUMN
WCO WALL CLEANOUT
WF WALL FAN
WG WATER GAUGE
WH WATER HEATER
WMS WIRE MESH SCREEN
WPD WATER PRESSURE
DROP
· INTERNATIONAL BUILDING CODE 2015
· INTERNATIONAL PLUMBING CODE 2015
· INTERNATIONAL MECHANICAL CODE 2015
· INTERNATIONAL FUEL GAS CODE 2015
· NFPA 70 NATIONAL ELECTRICAL CODE 2014
APPLICABLE CODES
NOTE:
ABBREVIATIONS AND SYMBOLS APPLY TO
MECHANICAL DRAWINGS MARKED M# AND
PLUMBING DRAWINGS MARKED P#. HOWEVER, ALL
ABBREVIATIONS AND SYMBOLS MAY NOT BE
APPLICABLE TO THIS PARTICULAR PROJECT. THEY
ARE PROVIDED FOR GENERAL REFERENCE ONLY.
REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REFERENCES
REF NUMBER TITLE
A
PIPE TEE FROM BOTTOM W/ VALVE
F
E
D
C
B
A
5 4 3 2 19 8 7 6
0TENTHS 0 INCHES 1 2 3 54 6 7 8 9 EIGHTHS10 7010MM 20 30 40 50 60 9080 100
COPYRIGHT © 2018
AR
CH
D -2
4x
UNLESS OTHERWISE AGREED IN A WRITTEN CONTRACT BETWEEN WOOD ENVIRONMENT &
INFRASTRUCTURE SOLUTIONS, INC. AND ITS CLIENT, THIS DOCUMENT: (I) CONTAINS INFORMATION, DATA AND DESIGN THAT IS CONFIDENTIAL AND MAY NOT BE COPIED OR DISCLOSED; AND (II) MAY BE USED BY THE CLIENT ONLY IN THE CONTEXT AND FOR THE EXPRESS PURPOSE FOR WHICH IT WAS INTENDED.
ANY USE OF, OR RELIANCE ON, THIS DOCUMENT BY ANY THIRD PARTY IS AT THAT PARTY'S SOLE RISK.
Environment & Infrastructure Solutions, Inc.
4600 E. WASHINGTON STREET, SUITE 600
PHOENIX, ARIZONA 85034 / PHONE: 602-733-6000
STAMP/SEAL
DES
DRN
SCALE
PROJECT NO.
CLIENT PROJECT MGR DEPARTMENT MGR PROJECT MGR
BY DD/MM/YY SUBJECT AREA
CLIENT DWG NO.
DRAWING NO. REV
PROJECT PHASE
APP
CHK
CA
D
FI
LE
SAVED: 09-Mar-21 1:21 PM PLOTTED: 10-Mar-21 3:58 PM USER: RODRIGUEZ, BRANDY
-M0.1
6R-KS-1169-18-04(B)
- -GREAT PLAINS NATURE CENTER
HEATING WATER SYSTEM REPLACEMENT
MECHANICAL LEGEND, SHEET LIST,
AND ABBREVIATIONS
J. CROWNHOLM E. GONZALEZ J. MARTIN
3720192002
EG 04/04/19
TW 04/04/19
CV 07/05/19
EG 07/08/19
APPROVED FOR CONSTRUCTION
100% FOR CONSTRUCTION
\\P
HX
4-
FS
1\D
AT
A\
IN
FR
AS
TR
UC
TU
RE
\F
AC
ILI
TI
ES
\P
RO
JE
CT
S\
\37
U
SF
W
S
GR
EA
T
PL
AI
NS
N
AT
UR
E
CE
NT
ER
\9.
0 C
AD
D
RA
W
IN
GS
\09 -S
HE
ET
S\
HE
AT
IN
G
HO
T W
AT
ER
R
EP
LA
CE
ME
NT
\M 0.1
M
EC
HA
NI
CA
L L
EG
EN
D, S
HE
ET
LI
ST
, A
ND
A
BB
RE
VI
AT
IO
NS
.D
W G
M0.1 MECHANICAL LEGEND, SHEET LIST, AND ABBREVIATIONS
M0.2 MECHANICAL GENERAL NOTES
M1.0 MECHANICAL DEMOLITION PLAN - CENTRAL PLANT
M2.0 MECHANICAL NEW PLAN - CENTRAL PLANT
M2.1 MECHANICAL NEW PLAN - AIR HANDLING UNITS
M3.0 MECHANICAL ONE LINE DIAGRAM
M4.0 MECHANICAL AND STRUCTURAL DETAILS
M4.1 STRUCTURAL AND ARCHITECTURAL DETAILS AND MECHANICAL SCHEDULES
M5.0 I/O SUMMARY AND CONTROL DIAGRAM
MECHANICAL SHEET LIST
FM
FLOW METER
L
I
C
E N
S
E
D
K
A
NS
A
M
I
L
I
O
GO
N
Z
A
L
E
Z
07/11/19
AutoCAD SHX Text S
AutoCAD SHX Text F
AutoCAD SHX Text D
AutoCAD SHX Text
NOTE:
GENERAL NOTES
1. GENERAL NOTES, SYMBOLS LIST AND DETAILS ARE APPLICABLE TO DRAWINGS MARKED M#.
2. ON DEMOLITION PLANS EXISTING MECHANICAL SYSTEMS TO BE REMOVED ARE SHOWN HEAVY LINE WEIGHT WITH
HATCH, EXISTING MECHANICAL SYSTEMS TO REMAIN ARE SHOWN LIGHT LINE WEIGHT. ON ALL OTHER PLANS NEW
MECHANICAL SYSTEMS ARE SHOWN HEAVY LINE WEIGHT.
3. THE INSTALLATION OR REMOVAL OF DUCTS, PIPES AND EQUIPMENT MAY REQUIRE THE REMOVAL OF EXISTING WALLS
AND CEILINGS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING AND REPAIRING THESE WALLS AND/OR
CEILINGS SO THEY MATCH THE EXISTING WHERE NOT REPLACED UNDER ARCHITECTURAL DIVISION.
4. ALL FIXTURES AND EQUIPMENT REMOVED, AND NOT REUSED, ARE TO BE RETURNED TO CONTRACTING OFFICER FOR
FIRST RIGHT OF REFUSAL. CONTRACTOR TO DISPOSE OF PROPERLY IF CONTRACTING OFFICER DOES NOT ACCEPT.
5. INFORMATION ON THE DRAWINGS HAS BEEN ASCERTAINED FROM EXISTING DRAWINGS AND FIELD OBSERVATIONS.
THIS INFORMATION IS AS ACCURATE AS CONDITIONS WOULD ALLOW. IT IS THE RESPONSIBILITY OF THE CONTRACTOR
TO VISIT THE SITE, PRIOR TO BID, AND BECOME FAMILIAR WITH THE EXTENT OF THE REMODEL WORK REQUIRED. NO
EXTRAS WILL BE ALLOWED FOR ALTERATIONS OF A FORESEEABLE NATURE REQUIRED TO ACHIEVE THE END RESULT
AS INDICATED BY CONTRACT DOCUMENTS.
6. COORDINATE WORK OF THIS SECTION WITH THAT OF OTHER SECTIONS.
7. WORK SHALL BE COORDINATED WITH TRADES INVOLVED. OFFSETS IN PIPING AND TRANSITIONS AROUND
OBSTRUCTIONS SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE CONTRACTING OFFICER.
8. VERIFY EQUIPMENT CONNECTIONS WITH MANUFACTURER'S CERTIFIED DRAWINGS. VERIFY AND PROVIDE PIPE
TRANSITIONS TO FURNISHED EQUIPMENT. FIELD VERIFY AND COORDINATE DIMENSIONS BEFORE FABRICATION.
9. INSTALL EQUIPMENT, PIPING AND DUCTWORK AS REQUIRED TO PROVIDE A VIBRATION-FREE INSTALLATION AND TO
FACILITATE EQUIPMENT ACCESS AS REQUIRED BY EQUIPMENT MANUFACTURER.
10. CONTROL WIRE AND CONDUIT SHALL COMPLY WITH NEC AND SPECIFICATIONS.
11. INSULATE PIPING AS SPECIFIED IN PROJECT SPECIFICATIONS. PERFORM TESTS SPECIFIED BEFORE INSULATING.
12. PROVIDE CLAMPS, OFFSETS, EXPANSION JOINTS, ANCHORS AND GUIDES AS NECESSARY TO PREVENT STRESS ON
PIPING.
13. RUN PIPING LEVEL AND PARALLEL TO WALLS OR AS INDICATED IN SPECIFICATIONS.
14. DRAWINGS ARE NOT TO BE SCALED FOR DIMENSIONS. TAKE ALL DIMENSIONS FROM THE SITE, CERTIFIED EQUIPMENT
DRAWINGS AND FROM THE STRUCTURE ITSELF BEFORE FABRICATING ANY WORK, VERIFY ALL SPACE REQUIREMENTS
COORDINATING WITH OTHER TRADES, AND INSTALL THE SYSTEMS IN THE SPACE PROVIDED WITHOUT EXTRA CHARGES
TO THE CONTRACTING OFFICER.
15. THE CONTRACTING OFFICER IS NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS OR TO MEANS, METHODS, TECHNIQUES, CONSTRUCTION SEQUENCES, OR PROCEDURES REQUIRED TO PERFORM HIS WORK.
16. ALL WORK SHALL BE INSTALLED IN ACCORDANCE WITH ALL APPLICABLE STATE CODES, LOCAL CODES AND
CONTRACTING OFFICER'S STANDARDS INDICATED BY THE CONSTRUCTION DOCUMENTS.
17. ALL EXTERIOR WALL AND ROOF PENETRATIONS SHALL BE SEALED WATERTIGHT.
18. CONTRACTOR IS RESPONSIBLE FOR RAISING AND LOWERING EXISTING EQUIPMENT AND MAKING PROPER OFFSETS IN
PIPING TO AVOID CONFLICTS.
GENERAL NOTES APPLY TO MECHANICAL
DRAWINGS MARKED M#.
REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REFERENCES
REF NUMBER TITLE
F
E
D
C
B
A
5 4 3 2 19 8 7 6
0TENTHS 0 INCHES 1 2 3 54 6 7 8 9 EIGHTHS10 7010MM 20 30 40 50 60 9080 100
COPYRIGHT © 2018
AR
CH
D -2
4x
UNLESS OTHERWISE AGREED IN A WRITTEN CONTRACT BETWEEN WOOD ENVIRONMENT &
INFRASTRUCTURE SOLUTIONS, INC. AND ITS CLIENT, THIS DOCUMENT: (I) CONTAINS INFORMATION, DATA AND DESIGN THAT IS CONFIDENTIAL AND MAY NOT BE COPIED OR DISCLOSED; AND (II) MAY BE USED BY THE CLIENT ONLY IN THE CONTEXT AND FOR THE EXPRESS PURPOSE FOR WHICH IT WAS INTENDED.
ANY USE OF, OR RELIANCE ON, THIS DOCUMENT BY ANY THIRD PARTY IS AT THAT PARTY'S SOLE RISK.
Environment & Infrastructure Solutions, Inc.
4600 E. WASHINGTON STREET, SUITE 600
PHOENIX, ARIZONA 85034 / PHONE: 602-733-6000
STAMP/SEAL
DES
DRN
SCALE
PROJECT NO.
CLIENT PROJECT MGR DEPARTMENT MGR PROJECT MGR
BY DD/MM/YY SUBJECT AREA
CLIENT DWG NO.
DRAWING NO. REV
PROJECT PHASE
APP
CHK
CA
D
FI
LE
SAVED: 09-Mar-21 10:19 AM PLOTTED: 10-Mar-21 3:57 PM USER: RODRIGUEZ, BRANDY
-M0.2
6R-KS-1169-18-04(B)
- -GREAT PLAINS NATURE CENTER
HEATING WATER SYSTEM REPLACEMENT
MECHANICAL GENERAL NOTES
J. CROWNHOLM E. GONZALEZ J. MARTIN
3720192002
EG 04/04/19
TW 04/04/19
CV 07/05/19
EG 07/08/19
APPROVED FOR CONSTRUCTION
100% FOR CONSTRUCTION
\\P
HX
4-
FS
1\D
AT
A\
IN
FR
AS
TR
UC
TU
RE
\F
AC
ILI
TI
ES
\P
RO
JE
CT
S\
\37
U
SF
W
S
GR
EA
T
PL
AI
NS
N
AT
UR
E
CE
NT
ER
\9.
0 C
AD
D
RA
W
IN
GS
\09 -S
HE
ET
S\
HE
AT
IN
G
HO
T W
AT
ER
R
EP
LA
CE
ME
NT
\M 0.2
M
EC
HA
NI
CA
L G
EN
ER
AL
N
OT
ES
.D W
G
L
I
C
E N
S
E
D
K
A
NS
A
O
M
I
L
GO
Z
A
L
E
Z
07/11/19
KEY NOTES
REMOVE EXISTING BOILER AND ALL ASSOCIATED APPURTENANCES. SEE MECHANICAL ONE LINE DIAGRAM SHEET
M3.0.
REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REFERENCES
REF NUMBER TITLE
F
E
D
C
B
A
5 4 3 2 19 8 7 6
0TENTHS 0 INCHES 1 2 3 54 6 7 8 9 EIGHTHS10 7010MM 20 30 40 50 60 9080 100
COPYRIGHT © 2018
AR
CH
D -2
4x
UNLESS OTHERWISE AGREED IN A WRITTEN CONTRACT BETWEEN WOOD ENVIRONMENT &
INFRASTRUCTURE SOLUTIONS, INC. AND ITS CLIENT, THIS DOCUMENT: (I) CONTAINS INFORMATION, DATA AND DESIGN THAT IS CONFIDENTIAL AND MAY NOT BE COPIED OR DISCLOSED; AND (II) MAY BE USED BY THE CLIENT ONLY IN THE CONTEXT AND FOR THE EXPRESS PURPOSE FOR WHICH IT WAS INTENDED.
ANY USE OF, OR RELIANCE ON, THIS DOCUMENT BY ANY THIRD PARTY IS AT THAT PARTY'S SOLE RISK.
Environment & Infrastructure Solutions, Inc.
4600 E. WASHINGTON STREET, SUITE 600
PHOENIX, ARIZONA 85034 / PHONE: 602-733-6000
SCALE:
N
O
R
T
H
EXP
(E)
ADS
(E)
HOT WATER HEATER(E)
B
(E)
B
(E)
B
(E)
B
(E)
HHWP
(E)
HHWP
(E)
UH
D
(E)
SCALE:
N O
R T
H
KEY PLAN
N.T.S.
PF
B
(E)
B
(E)
B
(E)
B
(E)
(E)
L
(E)
L
(E)
LOWHIGH
REMOVE EXISTING EXPANSION TANK AND ALL ASSOCIATED APPURTENANCES. SEE MECHANICAL ONE LINE
DIAGRAM SHEET M3.0.
REMOVE EXISTING AIR DIRT SEPARATOR AND ALL ASSOCIATED APPURTENANCES. SEE MECHANICAL
DEMOLITION ONE LINE DIAGRAM SHEET M3.0.
REMOVE EXISTING PUMP AND ALL ASSOCIATED APPURTENANCES. SEE MECHANICAL ONE LINE DIAGRAM SHEET
M3.0.
REMOVE EXISTING POT FEEDER AND ALL ASSOCIATED APPURTENANCES. SEE MECHANICAL ONE LINE DIAGRAM
SHEET M3.0.
6 REMOVE EXISTING BOILER CONTROL PANEL AND ALL ASSOCIATED APPURTENANCES.
REMOVE EXISTING NATURAL GAS PIPING DOWN TO BOILER AND CAP AT MAIN. SEE MECHANICAL ONE LINE
DIAGRAM SHEET M3.0.
(TYPICAL OF 4)
8 REMOVE EXISTING HHWS/HHWR PIPE AS SHOWN. SEE MECHANICAL ONE LINE DIAGRAM SHEET M3.0.
REMOVE EXISTING MAIN BOILER FLUE UP THROUGH ROOF AND ALL FLUE BRANCHES TO EACH BOILER. SEE
STRUCTURAL DETAILS 12/M4.0, 1/M4.1, 2/M4.1, AND 3/M4.1.
GAS
METER(E)
MECHANICAL DEMOLITION PLAN - CENTRAL PLANT
1/2"=1'
STAMP/SEAL
DES
DRN
SCALE
PROJECT NO.
CLIENT PROJECT MGR DEPARTMENT MGR PROJECT MGR
BY DD/MM/YY SUBJECT AREA
CLIENT DWG NO.
DRAWING NO. REV
PROJECT PHASE
APP
CHK
CA
D
FI
LE
SAVED: 09-Mar-21 10:23 AM PLOTTED: 10-Mar-21 3:54 PM USER: RODRIGUEZ, BRANDY
-M1.0
6R-KS-1169-18-04(B)
- -GREAT PLAINS NATURE CENTER
HEATING WATER SYSTEM REPLACEMENT
MECHANICAL DEMOLITION PLAN - CENTRAL PLANT
J. CROWNHOLM E. GONZALEZ J. MARTIN
3720192002
EG 04/04/19
TW 04/04/19
CV 07/05/19
EG 07/08/19
APPROVED FOR CONSTRUCTION
100% FOR CONSTRUCTION
\\P
HX
4-
FS
1\D
AT
A\
IN
FR
AS
TR
UC
TU
RE
\F
AC
ILI
TI
ES
\P
RO
JE
CT
S\
\37
U
SF
W
S
GR
EA
T
PL
AI
NS
N
AT
UR
E
CE
NT
ER
\9.
0 C
AD
D
RA
W
IN
GS
\09 -S
HE
ET
S\
HE
AT
IN
G
HO
T W
AT
ER
R
EP
LA
CE
ME
NT
\M 1.0
M
EC
HA
NI
CA
L D
EM
OL
IT
IO
N
PL
AN
CE
NT
RA
L P
LA
NT
.D W
G
GENERAL NOTES
1. CONTRACTOR SHALL COORDINATE EQUIPMENT DEMOLITION WITH THE USFWS AND CONSTRUCTION MANAGER. THE
CONTRACTOR SHALL DEVELOP A PHASE AND RIGGING PLAN FOR APPROVAL BY THE USFWS AND CONSTRUCTION
MANAGER.
2. CONTRACTOR SHALL COORDINATE PROPER DISPOSAL OF REMOVED EQUIPMENT WITH USFWS REGARDING
RECYCLING / SCRAPPING OF DEMOLISHED MATERIALS. CONTRACTOR TO PROVIDE APPROPRIATE TRASH / RECYCLING
CANISTERS FOR DEBRIS COLLECTION.
3. PROPER EVACUATION AND DECOMMISSIONING OF MECHANICAL SYSTEMS TO BE DEMOLISHED MUST BE DONE PRIOR
TO REMOVAL OF EQUIPMENT. ALL REMOVED SYSTEMS MUST BE DEMOLISHED WITHOUT CAUSING DANGER TO THE
SITE, OCCUPANTS OR ENVIRONMENT.
4. DISMANTLE EQUIPMENT IN SECTIONS AS REQUIRED FOR REMOVAL FROM TIGHT SPACES. DOUBLE DOORS IN SPACE
TO BE USED FOR EQUIPMENT REMOVAL.
L
I
C
E N
S
E
D
K
A
NS
A
E
M
I
L
Z
A
L
E
Z
07/11/19
REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REFERENCES
REF NUMBER TITLE
F
E
D
C
B
A
5 4 3 2 19 8 7 6
0TENTHS 0 INCHES 1 2 3 54 6 7 8 9 EIGHTHS10 7010MM 20 30 40 50 60 9080 100
COPYRIGHT © 2018
AR
CH
D -2
4x
UNLESS OTHERWISE AGREED IN A WRITTEN CONTRACT BETWEEN WOOD ENVIRONMENT &
INFRASTRUCTURE SOLUTIONS, INC. AND ITS CLIENT, THIS DOCUMENT: (I) CONTAINS INFORMATION, DATA AND DESIGN THAT IS CONFIDENTIAL AND MAY NOT BE COPIED OR DISCLOSED; AND (II) MAY BE USED BY THE CLIENT ONLY IN THE CONTEXT AND FOR THE EXPRESS PURPOSE FOR WHICH IT WAS INTENDED.
ANY USE OF, OR RELIANCE ON, THIS DOCUMENT BY ANY THIRD PARTY IS AT THAT PARTY'S SOLE RISK.
Environment & Infrastructure Solutions, Inc.
4600 E. WASHINGTON STREET, SUITE 600
PHOENIX, ARIZONA 85034 / PHONE: 602-733-6000
SCALE:
N O
R T
H
KEY PLAN
N.T.S.
HOT WATER HEATER(E)
UH
D
(E)
SCALE:
KEY NOTES
PROVIDE NEW BOILER AND ALL ASSOCIATED APPURTENANCES ON EXISTING HOUSEKEEPING PAD. INSTALL PER
MANUFACTURER'S RECOMMENDATIONS. SEE SCHEDULE, DETAIL AND MECHANICAL ONE LINE DIAGRAM SHEET M3.0.
ADS
B
HHWP
CONNECT NEW NATURAL GAS PIPE TO EXISTING NATURAL GAS AS SHOWN. SEE MECHANICAL ONE LINE
DIAGRAM SHEET M3.0.
PROVIDE CPVC CONCENTRIC VENT KIT UP THROUGH ROOF. CONNECT TO BOILER FRESH AIR
AND EXHAUST AIR LOCATIONS.
GAS
METER(E)
PROVIDE EXPANSION TANK ON EXISTING HOUSEKEEPING PAD WHERE SHOWN. INSTALL PER
MANUFACTURER'S RECOMMENDATIONS. SEE SCHEDULE, DETAIL AND MECHANICAL ONE LINE DIAGRAM
SHEET M3.0.
PROVIDE AIR SEPARATOR WHERE SHOWN. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
SEE SCHEDULE, DETAIL AND MECHANICAL ONE LINE DIAGRAM SHEET M3.0.
PROVIDE INLINE PUMP ON EXISTING HOUSEKEEPING PAD WHERE SHOWN. INSTALL PER
MANUFACTURER'S RECOMMENDATIONS. SEE SCHEDULE, DETAIL AND MECHANICAL ONE LINE
DIAGRAM SHEET M3.0.
PROVIDE POT FEEDER ON EXISTING HOUSEKEEPING PAD WHERE SHOWN. INSTALL PER
MANUFACTURER'S RECOMMENDATIONS. SEE SCHEDULE, DETAIL AND MECHANICAL ONE LINE
DIAGRAM SHEET M3.0.
PROVIDE TEMPERATURE CONTROL VALVE WHERE SHOWN. INSTALL PER MANUFACTURER'S
RECOMMENDATIONS. SEE SCHEDULE AND MECHANICAL ONE LINE DIAGRAM SHEET M3.0.
CONNECT NEW HYDRONIC HEATING WATER RETURN AND SUPPLY PIPE TO EXISTING HYDRONIC
HEATING WATER RETURN AND SUPPLY PIPE AS SHOWN.
PROVIDE EMERGENCY 4 INCH HYDRONIC HEATING WATER CONNECTIONS WITH ISOLATION VALVE
AND CAP WHERE SHOWN.
EXP
TCV
HBP
6 (N)
(N)
(N)
(N)
(N)
B
1 (N)
B
1 (N)
B
1 (N)
L
(E)
L
(E)
LOWHIGH
9 9 9 9
MECHANICAL ROOM NEW PLAN
1/4"=1'
N
O
R
T
H
STAMP/SEAL
DES
DRN
SCALE
PROJECT NO.
CLIENT PROJECT MGR DEPARTMENT MGR PROJECT MGR
BY DD/MM/YY SUBJECT AREA
CLIENT DWG NO.
DRAWING NO. REV
PROJECT PHASE
APP
CHK
CA
D
FI
LE
SAVED: 09-Mar-21 10:27 AM PLOTTED: 10-Mar-21 3:53 PM USER: RODRIGUEZ, BRANDY
-M2.0
6R-KS-1169-18-04(B)
- -GREAT PLAINS NATURE CENTER
HEATING WATER SYSTEM REPLACEMENT
MECHANICAL NEW PLAN - CENTRAL PLANT
J. CROWNHOLM E. GONZALEZ J. MARTIN
3720192002
EG 04/04/19
TW 04/04/19
CV 07/05/19
EG 07/08/19
APPROVED FOR CONSTRUCTION
100% FOR CONSTRUCTION
\\P
HX
4-
FS
1\D
AT
A\
IN
FR
AS
TR
UC
TU
RE
\F
AC
ILI
TI
ES
\P
RO
JE
CT
S\
\37
U
SF
W
S
GR
EA
T
PL
AI
NS
N
AT
UR
E
CE
NT
ER
\9.
0 C
AD
D
RA
W
IN
GS
\09 -S
HE
ET
S\
HE
AT
IN
G
HO
T W
AT
ER
R
EP
LA
CE
ME
NT
\M 2.0
M
EC
HA
NI
CA
L N
EW
P
LA
N
- C
EN
TR
AL
P
LA
NT
.D
W G
PF
5(N)
HHWP
4(N)
GENERAL NOTES
1. CONTRACTOR SHALL COORDINATE EQUIPMENT INSTALLATION WITH THE USFWS AND CONSTRUCTION
MANAGER. THE CONTRACTOR SHALL DEVELOP A PHASING AND RIGGING PLAN FOR APPROVAL BY THE
USFWS AND CONSTRUCTION MANAGER.
2. CONTRACTOR SHALL FIELD VERIFY ALL SIZES, DIMENSIONS, ROUTES OF EGRESS AND ENTRY, AND
LOCATIONS SHOWN ON DESIGN DRAWINGS PRIOR TO BID AND CONSTRUCTION START.
VFD
HHWP1
12 (N)
VFD
HHWP2
12 (N)
FMS
11(N)
PROVIDE FLOW MEASURING STATION WHERE SHOWN. INSTALL PER MANUFACTURER'S
RECOMMENDATIONS. SEE SCHEDULE AND MECHANICAL ONE LINE DIAGRAM SHEET M3.0.
PROVIDE VARIABLE FREQUENCY DRIVE WHERE SHOWN. INSTALL PER MANUFACTURER'S
RECOMMENDATIONS. SEE SCHEDULE AND ELECTRICAL PLANS.
L
I
C
E N
S
E
D
K
A
NS
A
E
M
I
L
Z
A
L
E
T
UH-D
T
AHU-7
H
AHU-7
KEY NOTES
REPLACE EXISTING TEMPERATURE CONTROL VALVE AND INTEGRATE WITH EXISTING
BUILDING AUTOMATION SYSTEM. SEE SCHEDULE AND DETAILS.
REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REFERENCES
REF NUMBER TITLE
F
E
D
C
B
A
5 4 3 2 19 8 7 6
0TENTHS 0 INCHES 1 2 3 54 6 7 8 9 EIGHTHS10 7010MM 20 30 40 50 60 9080 100
COPYRIGHT © 2018
AR
CH
D -2
4x
UNLESS OTHERWISE AGREED IN A WRITTEN CONTRACT BETWEEN WOOD ENVIRONMENT &
INFRASTRUCTURE SOLUTIONS, INC. AND ITS CLIENT, THIS DOCUMENT: (I) CONTAINS INFORMATION, DATA AND DESIGN THAT IS CONFIDENTIAL AND MAY NOT BE COPIED OR DISCLOSED; AND (II) MAY BE USED BY THE CLIENT ONLY IN THE CONTEXT AND FOR THE EXPRESS PURPOSE FOR WHICH IT WAS INTENDED.
ANY USE OF, OR RELIANCE ON, THIS DOCUMENT BY ANY THIRD PARTY IS AT THAT PARTY'S SOLE RISK.
Environment & Infrastructure Solutions, Inc.
4600 E. WASHINGTON STREET, SUITE 600
PHOENIX, ARIZONA 85034 / PHONE: 602-733-6000
SCALE:
N O
R T
H
KEY PLAN
N.T.S.
STAMP/SEAL
DES
DRN
SCALE
PROJECT NO.
CLIENT PROJECT MGR DEPARTMENT MGR PROJECT MGR
BY DD/MM/YY SUBJECT AREA
CLIENT DWG NO.
DRAWING NO. REV
PROJECT PHASE
APP
CHK
CA
D
FI
LE
SAVED: 09-Mar-21 12:33 PM PLOTTED: 10-Mar-21 3:51 PM USER: RODRIGUEZ, BRANDY
-M2.1
6R-KS-1169-18-04(B)
- -GREAT PLAINS NATURE CENTER
HEATING WATER SYSTEM REPLACEMENT
MECHANICAL NEW PLAN - AIR HANDLING UNITS
J. CROWNHOLM E. GONZALEZ J. MARTIN
3720192002
EG 04/04/19
TW 04/04/19
CV 07/05/19
EG 07/08/19
APPROVED FOR CONSTRUCTION
100% FOR CONSTRUCTION
\\P
HX
4-
FS
1\D
AT
A\
IN
FR
AS
TR
UC
TU
RE
\F
AC
ILI
TI
ES
\P
RO
JE
CT
S\
\37
U
SF
W
S
GR
EA
T
PL
AI
NS
N
AT
UR
E
CE
NT
ER
\9.
0 C
AD
D
RA
W
IN
GS
\09 -S
HE
ET
S\
HE
AT
IN
G
HO
T W
AT
ER
R
EP
LA
CE
ME
NT
\M 2.1
M
EC
HA
NI
CA
L N
EW
P
LA
N
- M
EC
HA
NI
CA
L R
OO
MS
.D W
G
AHU
(E)
AHU
(E)
AHU
(E)
AHU
(E)
AHU
(E)
AHU
(E)
AHU
(E)
AHU
(E)
4" HHWS&R
2" HHWS&R
1" HHWS&R
2" HHWS&R
4" HHWS&R
3/4" HHWS&R
1" HHWS&R
2" HHWS&R
1 1/2" HHWS&R
2" HHWS&R
1 1/4" HHWS&R
1 1/4" HHWS&R
1 1/2" HHWS&R
1 1/2" HHWS&R
2" HHWS&R
5/8" HHWS&R
20"x60"(E)
28"Ø(E)
30"Ø(E)
20"x40"(E)
18"x10"(E)
60"x60"(E)
60"x12"(E)
28"Ø(E)
60"x10"(E)
60"x10"(E)
DUCT SILENCER(E)
CONTROL AIR COMPRESSOR(E)
REFRIGERATED AIR DRYER(E)
UNIT HEATER (E)
(TYP OF 3)
UNIT HEATER(E)
2" HHWS&R(E)
1/2" HHWS&R(E)
2 1/2" HHWS&R(E)
4" HHWS&R(E)
96"x42" OSA LOUVER(E)
24"x36"(E)
24"x48"(E)
48"x14"(E)
24"x18"(E)
UNIT HEATER(E)
26"x12"(E)
24"x18"(E)
SCALE:
N
O
R
T
H
MECHANICAL NEW PLAN - AHU-3,5,6
3/16"=1'
SCALE:
N
O
R
T
H
MECHANICAL NEW PLAN - AHU-1,2
3/16"=1'
SCALE:
N
O
R
T
H
MECHANICAL NEW PLAN - AHU-7,8
3/16"=1'
SCALE:
N
O
R
T
H
MECHANICAL NEW PLAN - AHU-4
3/16"=1'
28"Ø(E)
GENERAL NOTES
1. CONTRACTOR SHALL COORDINATE EQUIPMENT INSTALLATION WITH THE USFWS AND
CONSTRUCTION MANAGER. THE CONTRACTOR SHALL DEVELOP A PHASING AND RIGGING
PLAN FOR APPROVAL BY THE USFWS AND CONSTRUCTION MANAGER.
2. CONTRACTOR SHALL FIELD VERIFY ALL SIZES, DIMENSIONS, ROUTES OF EGRESS AND
ENTRY, AND LOCATIONS SHOWN ON DESIGN DRAWINGS PRIOR TO BID AND CONSTRUCTION
START.
L
I
C
E N
S
E
D
K
A
NS
A
O
E
M
I
L
Z
A
L
E
REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REFERENCES
F
E
D
C
B
A
5 4 3 2 19 8 7 6
0TENTHS 0 INCHES 1 2 3 54 6 7 8 9 EIGHTHS10 7010MM 20 30 40 50 60 9080 100
COPYRIGHT © 2018
AR
CH
D -2
4x
UNLESS OTHERWISE AGREED IN A WRITTEN CONTRACT BETWEEN WOOD ENVIRONMENT &
INFRASTRUCTURE SOLUTIONS, INC. AND ITS CLIENT, THIS DOCUMENT: (I) CONTAINS INFORMATION, DATA AND DESIGN THAT IS CONFIDENTIAL AND MAY NOT BE COPIED OR DISCLOSED; AND (II) MAY BE USED BY THE CLIENT ONLY IN THE CONTEXT AND FOR THE EXPRESS PURPOSE FOR WHICH IT WAS INTENDED.
ANY USE OF, OR RELIANCE ON, THIS DOCUMENT BY ANY THIRD PARTY IS AT THAT PARTY'S SOLE RISK.
Environment & Infrastructure Solutions, Inc.
4600 E. WASHINGTON STREET, SUITE 600
PHOENIX, ARIZONA 85034 / PHONE: 602-733-6000
SCALE:
NATURAL GAS DEMOLITION ONE LINE DIAGRAM
N.T.S.
SCALE:
HEATING HOT WATER DEMOLITION ONE LINE DIAGRAM
N.T.S.
SCALE:
NATURAL GAS NEW ONE LINE DIAGRAM
N.T.S.
SCALE:
HEATING HOT WATER NEW ONE LINE DIAGRAM
N.T.S.
2 1/2" NG(E)
TO GAS METER
ADS
B
B
HOT WATER HEATER(E)
1 1/4" NG(E)
(TYP OF 8)
B
B
B
B
B
B
B
B
B
B
B
B
B
B
HHWP
HHWP
PF
EXP
REMOVE UP TO BALL VALVE
DOWNSTREAM OF PRESSURE
REGULATING VALVE.
1" HHWS(E)
2 1/2" NG(E) 2 1/2" NG(E) 1" NG(E)
1 1/2" NG(E)
(TYP OF 4)
1" MUW(E)
4" HHWS(E)
4" HHWR(E)
4" HHWS(E)
3/4" HHWS(E)
4" HHWS(E)
1 1/4" HHWS&R(E)
(TYPICAL OF 8)
1 1/4" HHWS&R(E)
(TYPICAL OF 8)
4" HHWR(E)
4" HHWS(E)
4" HHWS&R(E)
2 1/2" NG(E)
TO GAS METER
HOT WATER HEATER(E)
2 1/2" NG(E) 2 1/2" NG(E)
1" NG(E)
B
B
B
B
1 1/2" NG(N)
TYPICAL OF 4
1" MUW(N)
EXP
HHWP
HHWP
PF
B
B
B
B
TCV
HBP
ADS
1 1/2" HHWS(N)
4" HHWS(N)
4" HHWR(N)
4" HHWS(N)
4" HHWS(N)
3/4" HHWS(N)
4" HHWS(N)
3/4" HHWS(N)
1 1/4" HHWS&R(N)
(TYPICAL OF 4)
4" HHWR(N)
FROM BALL VALVE
DOWNSTREAM OF
PRESSURE REGULATING
VALVE
STAMP/SEAL
DES
DRN
SCALE
PROJECT NO.
CLIENT PROJECT MGR DEPARTMENT MGR PROJECT MGR
BY DD/MM/YY SUBJECT AREA
CLIENT DWG NO.
DRAWING NO. REV
PROJECT PHASE
APP
CHK
CA
D
FI
LE
SAVED: 09-Mar-21 12:33 PM PLOTTED: 10-Mar-21 3:49 PM USER: RODRIGUEZ, BRANDY
-M3.0
6R-KS-1169-18-04(B)
- -GREAT PLAINS NATURE CENTER
HEATING WATER SYSTEM REPLACEMENT
MECHANICAL ONE LINE DIAGRAMS
J. CROWNHOLM E. GONZALEZ J. MARTIN
3720192002
EG 04/04/19
TW 04/04/19
CV 07/05/19
EG 07/08/19
APPROVED FOR CONSTRUCTION
100% FOR CONSTRUCTION
\\P
HX
4-
FS
1\D
AT
A\
IN
FR
AS
TR
UC
TU
RE
\F
AC
ILI
TI
ES
\P
RO
JE
CT
S\
\37
U
SF
W
S
GR
EA
T
PL
AI
NS
N
AT
UR
E
CE
NT
ER
\9.
0 C
AD
D
RA
W
IN
GS
\09 -S
HE
ET
S\
HE
AT
IN
G
HO
T W
AT
ER
R
EP
LA
CE
ME
NT
\M 3.0
M
EC
HA
NI
CA
L O
NE
LI
NE
D
IA
GR
AM
S.
DW
G
2" HHWS(N)
FMS
TCV
B4
TCV
B3
TCV
B2
TCV
B1
L
I
C
E N
S
E
D
K
A
NS
A
M
I
L
I
O
GO
N
Z
A
L
E
Z
07/11/19
REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REFERENCES
F
E
D
C
B
A
5 4 3 2 19 8 7 6
0TENTHS 0 INCHES 1 2 3 54 6 7 8 9 EIGHTHS10 7010MM 20 30 40 50 60 9080 100
COPYRIGHT © 2018
AR
CH
D -2
4x
UNLESS OTHERWISE AGREED IN A WRITTEN CONTRACT BETWEEN WOOD ENVIRONMENT &
INFRASTRUCTURE SOLUTIONS, INC. AND ITS CLIENT, THIS DOCUMENT: (I) CONTAINS INFORMATION, DATA AND DESIGN THAT IS CONFIDENTIAL AND MAY NOT BE COPIED OR DISCLOSED; AND (II) MAY BE USED BY THE CLIENT ONLY IN THE CONTEXT AND FOR THE EXPRESS PURPOSE FOR WHICH IT WAS INTENDED.
ANY USE OF, OR RELIANCE ON, THIS DOCUMENT BY ANY THIRD PARTY IS AT THAT PARTY'S SOLE RISK.
Environment & Infrastructure Solutions, Inc.
4600 E. WASHINGTON STREET, SUITE 600
PHOENIX, ARIZONA 85034 / PHONE: 602-733-6000
SCALE: N.T.S.
POT FEEDER DETAIL
BALL VALVE (TYP)
POT FEEDER
REMOVABLE SCREW
TOP WITH GASKET
UNION (TYP)
FLOW INDICATOR
3/4" TO PUMP
SUCTION
3/4" FROM PUMP
DISCHARGE
3/4" DRAIN W/ HOSE
END AND CAP
SCALE: N.T.S.
AIR SEPARATOR DETAIL
4" EXISTING
HOUSEKEEPING PAD
SCALE: N.T.S.
EXPANSION TANK DETAIL
4" THICK EXISTING
HOUSEKEEPING PAD
NOTE:
SEE ONE LINE DIAGRAM
FOR PIPE SIZING.
SCALE: N.T.S.
PIPE INSULATION DETAIL
SCALE: N.T.S.
VENT THRU ROOF DETAIL
CONCENTRIC
SCALE: N.T.S.
AUTOMATIC AIR VENT DETAIL
SCALE: N.T.S.
PIPE SUPPORT DETAIL
AIR INTAKE
UP TO ROOF
SAFETY RELIEF VALVE
ISOLATION VALVE (TYPICAL)
VENT UP TO ROOF
WITH VENT CAP
V-STRAINS WITH
BLOW OFF
SEE NOTE 1
NOTES:
1. TERMINATE ALL DRAINS AT ADJACENT FLOOR SINK.
2. SEE TYPICAL GAS CONNECTION DETAIL 1/M4.0.
CONDENSATE NEUTRALIZATION KIT
HHWR
HHWS (FACTORY PROVIDED,
FIELD INSTALLED)
SEE NOTE 1
SEE NOTE 2
SCALE: N.T.S.
BOILER DETAIL
DIELECTRIC UNION
GAS COCK
GAS SUPPLY LINE
6'' DIRT LEG (MIN.)
APPLIANCE
ANGLED TRIPLE
DUTY VALVE
FLUSH
LINE
DRAIN CONNECTION
SPLIT
COUPLER
PIPE HANGER (TYP.)
RECOMMENDED FIELD
PRESSURE GAUGE PIPING
ARRANGEMENT
SUCTION
GUIDE
NEOPRENE
ISOLATION PAD
PIPE SUPPORT
PET COCK
(TYP.)
SYSTEM INLET
SYSTEM OUTLET
HANGERS SUPPORT THE WEIGHT
OF THE FILLED PIPING, PUMPS
AND FITTINGS
2'' OR 3''
HEIGHT ABOVE
PAD
SCALE: N.T.S.
TYPICAL GAS CONNECTION DETAIL
SCALE: N.T.S.
FLOOR SADDLE SUPPORT DETAIL
BLADDER TYPE
EXPANSION TANK
TO MAKEUP
WATER ASSEMBLY
TO AIR SEPARATOR
INSULATION NOTES (INTERIOR):
SHALL BE NONCOMBUSTIBLE, RIGID MOLDED
WITH MINIMUM K VALUE OF 0.24 @ 75F, ASTM
C547, MAX. MOISTURE ABSORPTION OF 0.2%
BY VOL., AND VAPOR BARRIER LAP ADHESIVE
COMPATIBLE WITH INSULATION.
REGULATORY REQUIREMENT:
INSULATION SHALL CONFORM TO A MAXIMUM
FLAME SPREAD/SMOKE DEVELOPED RATING
OF 25/50 IN ACCORDANCE WITH ASTM E84,
NFPA 255 & UL 723.
1-1/2" INSULATION
(MIN.)
JACKET
PIPE
HIGH CAPACITY
AUTO AIR VENT
TO EXT AND
MUW ASSEMBLY
BALL VALVE
RETURN FROM
SYSTEM
FULL SIZE DRAIN
TO NEAREST
FLOOR SINK OR
DRAIN
TO PUMP
SUCTION
FULL SIZE DRAIN
TO F.S.
AIR AND DIRT
SEPARATOR
VENT
APPLY CAULKING
AT PENETRATION
OF FLASHING
ROOFING UP AND
OVER FLASHING
ROOF
ELBOW (FIELD SUPPLIED)
C O
M B
U S
T I O
N
A I R
V E
N T
COMBUSTION AIR
INTAKE
STORM COLLAR
UL LISTED SHEET
METAL FLASHING
STRAP (FIELD
SUPPLIED)
PROVIDE FIRE COLLAR AROUND FLUE
PIPES AT RATED ROOF PENETRATIONS.
TEST COCK
FLOAT TYPE AIR VENT
ARMSTRONG
MODEL 1-AV 3/4" CONN.
3/4" DIA. BALL VALVE
JAMESBURY CLINCHER
TYPE 2111
3/4" FROM PIPE VENTED
HIGH POINTS
INSULATED PIPE
WITH VAPOR BARRIER
18" LONG 16 GAUGE
PIPE SHIELD
CLEVIS PIPE HANGER
250 LBS MAX
PRECAST HOLLOW
CORE SLAB
PLATE WASHER
1/4"x5"x5"
FLOOR TOPPING
ALL THREAD THRU
CONCRETE FLANK.
1/2"Ø THREADED ROD
90° SECTION OF RIGID
INSULATION MIN. 12" LONG
(TYP. FOR ALL PIPING)
4" EXISTING
HOUSEKEEPING PAD
FLOOR
TEMPERATURE CONTROL VALVE
BOILER
INLINE PUMP
INLINE PUMP WITH
STAMP/SEAL
DES
DRN
SCALE
PROJECT NO.
CLIENT PROJECT MGR DEPARTMENT MGR PROJECT MGR
BY DD/MM/YY SUBJECT AREA
CLIENT DWG NO.
DRAWING NO. REV
PROJECT PHASE
APP
CHK
CA
D
FI
LE
SAVED: 09-Mar-21 1:23 PM PLOTTED: 10-Mar-21 3:40 PM USER: RODRIGUEZ, BRANDY
-M4.0
6R-KS-1169-18-04(B)
- -GREAT PLAINS NATURE CENTER
HEATING WATER SYSTEM REPLACEMENT
MECHANICAL DETAILS
J. CROWNHOLM E. GONZALEZ J. MARTIN
3720192002
EG 04/04/19
TW 04/04/19
CV 07/05/19
EG 07/08/19
APPROVED FOR CONSTRUCTION
100% FOR CONSTRUCTION
\\P
HX
4-
FS
1\D
AT
A\
IN
FR
AS
TR
UC
TU
RE
\F
AC
ILI
TI
ES
\P
RO
JE
CT
S\
\37
U
SF
W
S
GR
EA
T
PL
AI
NS
N
AT
UR
E
CE
NT
ER
\9.
0 C
AD
D
RA
W
IN
GS
\09 -S
HE
ET
S\
HE
AT
IN
G
HO
T W
AT
ER
R
EP
LA
CE
ME
NT
\M 4.0
M
EC
HA
NI
CA
L D
ET
AI
LS
.D
W G
SCALE: N.T.S.
LARGE COIL PIPING DIAGRAM (2-WAY)
STRAINER W/ BALL
VALVE, HOSE END
AND THREADED
2-WAY
CONTROL
VALVE
CALIBRATED
BALANCING
VALVE (TYP.)
UNION OR FLANGE, DIELECTRIC
FITTINGS AS REQUIRED (TYP.)
SHUT-OFF VALVE
THERMOMETER (TYP.)
SUPPLY
RETURN
MANUAL AIR VENT W/ FULL SIZE
DRAIN TO DRAIN PAN (TYP.)
COIL
'PETE'S' TEST
PLUG (TYP.)
COIL
COIL CONDENSATE DRAIN
PAN (INSULATED)
OPEN VENT
TRAP. SEE DETAIL
COIL CONDENSATE DRAIN.
SEE MECHANICAL PLANS
'PETE'S' TEST
PLUG (TYP.)
NOTES:
1. PROVIDE CONDENSATE DRAIN PIPING
AND TRAP ON COOLING COILS ONLY.
FLEXIBLE
CONNECTOR-STAINLESS
STEEL HOSE W/ STAINLESS
STEEL OUTER BRAID (TYP.)
SCALE: N.T.S.
SMALL COOLING COIL PIPING DIAGRAM (2-WAY)
COPPER
PIPE
2-WAY CONTROL NOT
REQUIRED FOR FC-9, 21,
22, 35, 36, 49, 50, 56, 64, 74, 75
BALL VALVE (TYP.)
DIELECTRIC UNION
OR DIELECTRIC FLANGE
PLENUM-RATED HOSE W/ STAINLESS
STEEL OUTER BRAID (TYP.)
COIL CONDENSATE
DRAIN PAN (INSULATED)
STRAINER
STEEL
PIPE
MANUAL AIR VENT W/ FULL
SIZE DRAIN TO DRAIN PAN
FAN COIL
OPEN VENT
TRAP-SEE DETAIL
COIL CONDENSATE
DRAIN-SEE DETAIL
UNION (TYP.)
AUTOMATIC
BALANCING VALVE
L
I
C
E N
S
E
D
K
A
NS
A
M
I
L
I
O
GO
N
Z
A
L
E
Z
07/11/19
AutoCAD SHX Text
NG
AutoCAD SHX Text
CHWR
AutoCAD SHX Text
CHWS
REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REFERENCES
F
E
D
C
B
A
5 4 3 2 19 8 7 6
0TENTHS 0 INCHES 1 2 3 54 6 7 8 9 EIGHTHS10 7010MM 20 30 40 50 60 9080 100
COPYRIGHT © 2018
AR
CH
D -2
4x
UNLESS OTHERWISE AGREED IN A WRITTEN CONTRACT BETWEEN WOOD ENVIRONMENT &
INFRASTRUCTURE SOLUTIONS, INC. AND ITS CLIENT, THIS DOCUMENT: (I) CONTAINS INFORMATION, DATA AND DESIGN THAT IS CONFIDENTIAL AND MAY NOT BE COPIED OR DISCLOSED; AND (II) MAY BE USED BY THE CLIENT ONLY IN THE CONTEXT AND FOR THE EXPRESS PURPOSE FOR WHICH IT WAS INTENDED.
ANY USE OF, OR RELIANCE ON, THIS DOCUMENT BY ANY THIRD PARTY IS AT THAT PARTY'S SOLE RISK.
Environment & Infrastructure Solutions, Inc.
4600 E. WASHINGTON STREET, SUITE 600
PHOENIX, ARIZONA 85034 / PHONE: 602-733-6000
SCALE: 1"=1'
TYPICAL INFILL FRAMING
SCALE: 1 1/2" = 1'
TYPICAL INFILL FRAMING
SCALE: 3" = 1'
INFILL FRAMING CONNECTION DETAIL
NEW MODIFIED MEMBRANE
EXTEND OVER THE EXISTING
ROOFING MEMBRANE AS SHOWN
EXISTING ROOFING MEMBRANE
EXISTING ROOF INSULATION
EXISTING METAL DECK
L6" X 6" X 1/4" VERTICAL ATTACH
TO TOP AND BOTTOM CHORD
OF EXISTING ROOF JOIST
EXISTING ROOF JOINT
NEW INSULATION TO MATCH
EXISTING STAGGER ALL JOINS.
FASTEN PER SPECIFCATIONS
NEW METAL DECK INFILL
TO MATCH EXISTING METAL
DECK F.V. (MIN 6'-0" SPAN
RATING)
L4" X 4" X 1/4"
NEW INSULATION TO
MATCH EXISTING. STAGGER
ALL JOINTS. FASTEN PER
SPECIFICATION
OVERLAP AND ATTACH TO EXISTING METAL
DECK / STRUCTURE. WELD OR MECHANICALLY
FASTEN (MATCH EXISTING)
L4" X 4" X 1/4" SHOWN DASHED
TOP CHORD
OF EXISTING
ROOF JOIST
BOTTOM CHORD OF
EXISTING ROOF JOIST
L6" X 6" X 1/4" SHOWN DASHED
L6" X 6" X 1/4"
BOTTOM CHORD OF
EXISTING ROOF JOIST
(TOP CHORD SIMILAR)
STAMP/SEAL
DES
DRN
SCALE
PROJECT NO.
CLIENT PROJECT MGR DEPARTMENT MGR PROJECT MGR
BY DD/MM/YY SUBJECT AREA
CLIENT DWG NO.
DRAWING NO. REV
PROJECT PHASE
APP
CHK
CA
D
FI
LE
SAVED: 09-Mar-21 1:32 PM PLOTTED: 10-Mar-21 3:39 PM USER: RODRIGUEZ, BRANDY
-M4.1
6R-KS-1169-18-04(B)
- -GREAT PLAINS NATURE CENTER
HEATING WATER SYSTEM REPLACEMENT
STRUCTURAL AND ARCHITECTURAL DETAILS
AND MECHANICAL SCHEDULES
J. CROWNHOLM E. GONZALEZ J. MARTIN
3720192002
EG 04/04/19
TW 04/04/19
CV 07/05/19
EG 07/08/19
APPROVED FOR CONSTRUCTION
100% FOR CONSTRUCTION
\\P
HX
4-
FS
1\D
AT
A\
IN
FR
AS
TR
UC
TU
RE
\F
AC
ILI
TI
ES
\P
RO
JE
CT
S\
\37
U
SF
W
S
GR
EA
T
PL
AI
NS
N
AT
UR
E
CE
NT
ER
\9.
0 C
AD
D
RA
W
IN
GS
\09 -S
HE
ET
S\
HE
AT
IN
G
HO
T W
AT
ER
R
EP
LA
CE
ME
NT
\M 4.1
S
TR
UC
TU
RA
L A
ND
A
RC
HI
TE
CT
UR
AL
D
ET
AI
LS
A
ND
M
EC
HA
NI
CA
L S
CH
ED
UL
ES
.D W
G
(2) L4" X 4" X 1/4"
L4" X 4" X 1/4" (TYP)
EXISTING METAL DECK, SEE PLAN
L4" X 4" X 1/4" (TYP)
JOINT SPACING VERIFY IN FIELD
NOTES:
1. UNIT TO BE SHOP ASSEMBLED
AND FIELD WELDED TO JOIST.
2. SEE ARCHITECTURAL AND
MECHANICAL DRAWINGS FOR
SIZE AND LOCATION OF
OPENINGS.
SCALE: 1 1/2" = 1'
IN EXISTING CONSTRUCTION
ROOF OPENING DETAIL
L
I
C
E N
S
E
D
K
A
NS
A
M
I
L
I
O
GO
N
Z
A
L
E
Z
07/11/19
REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REFERENCES
F
E
D
C
B
A
5 4 3 2 19 8 7 6
0TENTHS 0 INCHES 1 2 3 54 6 7 8 9 EIGHTHS10 7010MM 20 30 40 50 60 9080 100
COPYRIGHT © 2018
AR
CH
D -2
4x
UNLESS OTHERWISE AGREED IN A WRITTEN CONTRACT BETWEEN WOOD ENVIRONMENT &
INFRASTRUCTURE SOLUTIONS, INC. AND ITS CLIENT, THIS DOCUMENT: (I) CONTAINS INFORMATION, DATA AND DESIGN THAT IS CONFIDENTIAL AND MAY NOT BE COPIED OR DISCLOSED; AND (II) MAY BE USED BY THE CLIENT ONLY IN THE CONTEXT AND FOR THE EXPRESS PURPOSE FOR WHICH IT WAS INTENDED.
ANY USE OF, OR RELIANCE ON, THIS DOCUMENT BY ANY THIRD PARTY IS AT THAT PARTY'S SOLE RISK.
Environment & Infrastructure Solutions, Inc.
4600 E. WASHINGTON STREET, SUITE 600
PHOENIX, ARIZONA 85034 / PHONE: 602-733-6000
BHHWSTAI
BHHWRTAI
MHHWTEMPAI
AO
BLR1-SDI
BLR1-SP
DO BLR1-C
AI
HHW-DP
DI HHWBYPVLV-S
DO HHWBYPVLV-C
HHWF-GPMAI
AI BLR1-%
BLR1EWT AI
BLR2EWT AI
DIBLR1VLV-S
DOBLR1VLV-C
BLR1LWTAI
BLR2LWT
DIBLR2VLV-S
DOBLR2VLV-C
AO
HWP1-S DI
HWP1SPEED
DOHWP1-C
HWP2-S
HWP2SPEED
HWP2-C
AI HHWBYPVLV-%
SCALE: N.T.S.
CENTRAL PLANT - HEATING WATER CONTROL DIAGRAM
AO
DI
DO
AI
BLR3EWT AI
BLR3LWT
DIBLR3VLV-S
DOBLR3VLV-C
AI
BLR4EWT AI
BLR4LWT
DIBLR4VLV-S
DOBLR4VLV-C
AI
AO
BLR2-SDI
BLR2-SP
DO BLR2-C
AI BLR2-%
AO
BLR3-SDI
BLR3-SP
DO BLR3-C
AI BLR3-%
AO
BLR4-SDI
BLR1-SP
DO BLR4-C
AI BLR1-%
S
T
S
T
S
T
S
T
S
T
S
T
S
T
S
T
S
T
S
T
S
T
STAMP/SEAL
DES
DRN
SCALE
PROJECT NO.
CLIENT PROJECT MGR DEPARTMENT MGR PROJECT MGR
BY DD/MM/YY SUBJECT AREA
CLIENT DWG NO.
DRAWING NO. REV
PROJECT PHASE
APP
CHK
CA
D
FI
LE
SAVED: 09-Mar-21 1:46 PM PLOTTED: 10-Mar-21 3:37 PM USER: RODRIGUEZ, BRANDY
-M5.0
6R-KS-1169-18-04(B)
- -GREAT PLAINS NATURE CENTER
HEATING WATER SYSTEM REPLACEMENT
I/O SUMMARY AND CONTROL DIAGRAM
J. CROWNHOLM E. GONZALEZ J. MARTIN
3720192002
EG 04/04/19
TW 04/04/19
CV 07/05/19
EG 07/08/19
APPROVED FOR CONSTRUCTION
100% FOR CONSTRUCTION
\\P
HX
4-
FS
1\D
AT
A\
IN
FR
AS
TR
UC
TU
RE
\F
AC
ILI
TI
ES
\P
RO
JE
CT
S\
\37
U
SF
W
S
GR
EA
T
PL
AI
NS
N
AT
UR
E
CE
NT
ER
\9.
0 C
AD
D
RA
W
IN
GS
\09 -S
HE
ET
S\
HE
AT
IN
G
HO
T W
AT
ER
R
EP
LA
CE
ME
NT
\M 5.0
IO
S
UM
MA
RY
A
ND
C
ON
TR
OL
D
IA
GR
AM
.D
W G
L
I
C
E N
S
E
D
K
A
NS
A
M
I
L
I
O
GO
N
Z
A
L
E
Z
07/11/19
AutoCAD SHX Text
DP
ABBREVIATIONS
A AMPS
HP HORSEPOWER
KW KILOWATTS
KWH KILOWATT HOUR
V VOLTS
AC ALTERNATING CURRENT
DC DIRECT CURRENT
UNO UNLESS NOTED OTHERWISE
AFF ABOVE FINISHED FLOOR
KV THOUSAND VOLTS
KVA KILOVOLT-AMPERES
MVA MEGAVOLT-AMPERES
AIC AMPS INTERRUPTING CAPACITY
MCP MOTOR CIRCUIT PROTECTOR
HMCP HIGH CAPACITY MOTOR CIRCUIT PROTECTOR
TMCB THERMAL MAGNETIC CIRCUIT BREAKER
VCB VACUUM CIRCUIT BREAKER
CPT CONTROL POWER TRANSFORMER
FU FUSE
TB TERMINAL BLOCK
W WATTS
AM AMMETER
VM VOLTMETER
MPR MULTI-PURPOSE OR MOTOR PROTECTION RELAY
AWG AMERICAN WIRE GAUGE
KCMIL THOUSANDS OF CIRCULAR MILLS
OL MOTOR OVERLOADS, THERMAL OR ELECTRONIC
PLC PROGRAMMABLE LOGIC CONTROLLER
EXIT LIGHT WITH ARROW
EXIT LIGHT - DOUBLE DIRECTED
EXIT LIGHT - SINGLE DIRECTED
FLOOD LIGHT - TWIN
EMERGENCY LIGHT
EXIT LIGHT
LIGHT POLE
WALKWAY LIGHT
RECESSED SURFACE LIGHT
SINGLE FLOOD LIGHT
3-WAY WALL SWITCH
4-WAY WALL SWITCH
DIMMER SWITCH
RECESSED1X4_EMERGENCY
SINGLE SWITCH
(3) -A FU
N
30A/3P
F DISCONNECT WITH RATINGS
STARTER WITH DISCONNECT
EQUIPMENT_CONNECTION
FLEX_CONDUIT_2
HOME RUN
J-BOX
MOTOR
MOTOR
PANEL
PUSH BUTTON DOUBLE
PUSH BUTTON EMERGENCY
PUSH BUTTON SINGLE
RECEPTACLE DUPLEX
RECEPTACLE QUAD
RECEPTACLE SINGLE
RECEPTACLE SPECIAL
SEAL OFF
WIREMOLD
CONDUCTORS IN CONDUIT, LONG
LINES HOT, SHORT LINES
NEUTRAL, GROUND NOT SHOWN
BUT REQUIRED
PLAN DRAWING SYMBOLS - ELECTRICAL DEVICES PLAN DRAWING SYMBOLS - LIGHTING AND SWITCHES SINGLE LINE DRAWING SYMBOLS
CIRCUIT BREAKER, DRAW OUT STYLE,
MEDIUM VOLTAGE
FUSED VACUUM CONTACTOR/STARTER,
DRAW OUT STYLE, 5KV
TRANSFORMER
DELTA CONNECTION
GROUNDED WYE CONNECTION
RESISTANCE GROUNDED CONNECTION
ANSI DEVICE OR RELAY FUNCTION
51G SHOWN AS REFERENCE ONLY
CURRENT TRANSFORMER, GROUND
TYPE
CURRENT TRANSFORMER, PHASE
POTENTIAL TRANSFORMER
BATTERY BANK
CAPACITOR OR CAPACITOR BANK
FUSED CUTOUT, POLE MOUNTED
FUSE
BUSSED THROAT CONNECTION OR BUS
DUCT
MEDIUM VOLTAGE CABLE STRESS CONE
TERMINATION KIT
LIGHTNING ARRESTOR
SAFETY SWITCH, 600V MAXIMUM
BI-METALLIC MOTOR OVERLOADS
CIRCUIT BREAKER, 600V MAXIMUM
GROUND CONNECTION
CONTACT, NORMALLY CLOSED
CONTACT, NORMALLY OPEN
INDICATES FUNCTIONAL INTERLOCKING
OF EQUIPMENT
SURGE ARRESTOR
51G
CURRENT TRANSFORMER, PHASE
MULTI-RATIO
LIGHTING OR SMALL POWER
DISTRIBUTION PANEL
MOTOR WITH
HORSEPOWER LISTED
MISCELLANEOUS ELECTRICAL LOAD
WITH DEMAND KVA LISTED
KVA
KVA
CURRENT TRANSFORMER
POLARITY MARK
LOR
SS
RTD
MSH
VSH
ES
VOLT METER
AMMETER
LOCAL-OFF-REMOTE SELECTOR SWITCH
START - STOP PUSHBUTTON
RESISTANCE TEMPERATURE DEVICE
MOTOR SPACE HEATER
HIGH VIBRATION SWITCH
EMERGENCY STOP PUSHBUTTON
VFD
VARIABLE FREQUENCY DRIVE W/DISCONNECT
ELECTRICAL SHEET LIST
E0.1 ELECTRICAL ABBREVIATIONS, LEGEND, SYMBOLS AND GENERAL NOTES
E1.0 ELECTRICAL PANEL SCHEDULES AND ONE LINE DIAGRAMS
E2.0 ELECTRICAL DEMOLITION PLAN - CENTRAL PLANT
E3.0 ELECTRICAL NEW PLAN - CENTRAL PLANT
REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REFERENCES
REF NUMBER TITLE
F
E
D
C
B
A
5 4 3 2 19 8 7 6
0TENTHS 0 INCHES 1 2 3 54 6 7 8 9 EIGHTHS10 7010MM 20 30 40 50 60 9080 100
COPYRIGHT © 2018
AR
CH
D -2
4x
UNLESS OTHERWISE AGREED IN A WRITTEN CONTRACT BETWEEN WOOD ENVIRONMENT &
INFRASTRUCTURE SOLUTIONS, INC. AND ITS CLIENT, THIS DOCUMENT: (I) CONTAINS INFORMATION, DATA AND DESIGN THAT IS CONFIDENTIAL AND MAY NOT BE COPIED OR DISCLOSED; AND (II) MAY BE USED BY THE CLIENT ONLY IN THE CONTEXT AND FOR THE EXPRESS PURPOSE FOR WHICH IT WAS INTENDED.
ANY USE OF, OR RELIANCE ON, THIS DOCUMENT BY ANY THIRD PARTY IS AT THAT PARTY'S SOLE RISK.
Environment & Infrastructure Solutions, Inc.
4600 E. WASHINGTON STREET, SUITE 600
PHOENIX, ARIZONA 85034 / PHONE: 602-733-6000
STAMP/SEAL
DES
DRN
SCALE
PROJECT NO.
CLIENT PROJECT MGR DEPARTMENT MGR PROJECT MGR
BY DD/MM/YY SUBJECT AREA
CLIENT DWG NO.
DRAWING NO. REV
PROJECT PHASE
APP
CHK
CA
D
FI
LE
SAVED: 09-Mar-21 10:51 AM PLOTTED: 10-Mar-21 4:03 PM USER: RODRIGUEZ, BRANDY
-E0.1
6R-KS-1169-18-04(B)
- -GREAT PLAINS NATURE CENTER
HEATING WATER SYSTEM REPLACEMENT
ELECTRICAL ABBREVIATIONS, LEGEND,
SYMBOLS AND GENERAL NOTES
J. CROWNHOLM S. KAIN J. MARTIN
3720192002
NTS
SJK -
SJK 19/03/19
T. RAFFIN 10/07/19
T. RAFFIN 10/07/19
APPROVED FOR CONSTRUCTION
100% FOR CONSTRUCTION
\\P
HX
4-
FS
1\D
AT
A\
IN
FR
AS
TR
UC
TU
RE
\F
AC
ILI
TI
ES
\P
RO
JE
CT
S\
\37
U
SF
W
S
GR
EA
T
PL
AI
NS
N
AT
UR
E
CE
NT
ER
\9.
0 C
AD
D
RA
W
IN
GS
\09 -S
HE
ET
S\
HE
AT
IN
G
HO
T W
AT
ER
R
EP
LA
CE
ME
NT
\E 0.1
-E
LE
CS
YM
BO
LS
AN
DL
EG
EN
D.
DW
G
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text E
J
REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REFERENCES
F
E
D
C
B
A
5 4 3 2 19 8 7 6
0TENTHS 0 INCHES 1 2 3 54 6 7 8 9 EIGHTHS10 7010MM 20 30 40 50 60 9080 100
COPYRIGHT © 2018
AR
CH
D -2
4x
UNLESS OTHERWISE AGREED IN A WRITTEN CONTRACT BETWEEN WOOD ENVIRONMENT &
INFRASTRUCTURE SOLUTIONS, INC. AND ITS CLIENT, THIS DOCUMENT: (I) CONTAINS INFORMATION, DATA AND DESIGN THAT IS CONFIDENTIAL AND MAY NOT BE COPIED OR DISCLOSED; AND (II) MAY BE USED BY THE CLIENT ONLY IN THE CONTEXT AND FOR THE EXPRESS PURPOSE FOR WHICH IT WAS INTENDED.
ANY USE OF, OR RELIANCE ON, THIS DOCUMENT BY ANY THIRD PARTY IS AT THAT PARTY'S SOLE RISK.
Environment & Infrastructure Solutions, Inc.
4600 E. WASHINGTON STREET, SUITE 600
PHOENIX, ARIZONA 85034 / PHONE: 602-733-6000
STAMP/SEAL
DES
DRN
SCALE
PROJECT NO.
CLIENT PROJECT MGR DEPARTMENT MGR PROJECT MGR
BY DD/MM/YY SUBJECT AREA
CLIENT DWG NO.
DRAWING NO. REV
PROJECT PHASE
APP
CHK
CA
D
FI
LE
SAVED: 09-Mar-21 10:53 AM PLOTTED: 10-Mar-21 4:02 PM USER: RODRIGUEZ, BRANDY
-E1.0
6R-KS-1169-18-04(B)
- -GREAT PLAINS NATURE CENTER
HEATING WATER SYSTEM REPLACEMENT
ELECTRICAL PANEL SCHEDULES AND
ONE LINE DIAGRAMS
J. CROWNHOLM S. KAIN J. MARTIN
3720192002
NTS
SJK -
SJK 19/03/19
T. RAFFIN 10/07/19
T. RAFFIN 10/07/19
APPROVED FOR CONSTRUCTION
100% FOR CONSTRUCTION
\\P
HX
4-
FS
1\D
AT
A\
IN
FR
AS
TR
UC
TU
RE
\F
AC
ILI
TI
ES
\P
RO
JE
CT
S\
\37
U
SF
W
S
GR
EA
T
PL
AI
NS
N
AT
UR
E
CE
NT
ER
\9.
0 C
AD
D
RA
W
IN
GS
\09 -S
HE
ET
S\
HE
AT
IN
G
HO
T W
AT
ER
R
EP
LA
CE
ME
NT
\E 1.0
-E
LE
CP
AN
EL
SC
HE
DU
LE
SA
ND
ON
EL
IN
ES
.D
W G
PANEL "B2" SCHEDULE - AS FOUND
PANEL "B2" SCHEDULE - REVISED FOR NEW WORK
PANEL SCHEDULE AND 1-LINE NOTES:
1. CIRCUIT BREAKER, CONDUCTOR, AND LOAD HAVE ALL CHANGED FROM "AS-FOUND"
CONDITION. NEW CONDUCTORS SHALL BE NEC TYPE THWN, STRANDED COPPER.
2. HWP'S ARE REDUNDANT. ONLY ONE HWP WILL RUN AT ANY TIME. THIS IS WHY LOADS
IN CIRCUITS 16/18/20 ARE LISTED AS ZERO VOLT-AMPS. HWP'S SHALL BE
INTERLOCKED EITHER HARD WIRED OR THROUGH THE FACILITY CONTROL SYSTEM
SUCH THAT THEY CANNOT OPERATE CONCURRENTLY.
3. LOAD CHANGED FROM FOUR BOILERS TO TWO BOILERS. REVISE PANEL SCHEDULE
TO MATCH. LOAD CHANGED ACCORDINGLY. CIRCUIT BREAKERS AND CONDUCTORS
ARE UNCHANGED.
4. LOADS SHOWN IN "AS-FOUND" SCHEDULE ARE BASED UPON EXISTING DRAWINGS
AND A SITE INSPECTION. WHILE THERE MAY BE MINOR DISCREPANCIES IN INDIVIDUAL
CIRCUITS, ENGINEER IS SATISFIED THAT THE OVERALL PANEL LOAD IS ACCURATE.
SEE GENERAL NOTE 2.
GENERAL NOTES:
1. CHANGES TO THE "AS-FOUND" CONDITION ARE DENOTED BY REVISION
CLOUDS. NOTES ASSOCIATED WITH THE REVISED CIRCUITS DESCRIBE
THE CHANGES.
2. PRIOR TO BEGINNING WORK, CONTRACTOR SHALL MEASURE AND
RECORD THE PANEL "B2" FEEDER AMPS WITH BOTH CWP AND HWP
PUMPS RUNNING. AFTER INSTALLATION OF THE HWP VFD'S,
CONTRACTOR SHALL AGAIN MEASURE AND RECORD THE PANEL "B2"
FEEDER AMPS WITH ONLY ONE OF THE HWP'S RUNNING. DELIVER THE
MEASUREMENTS TO THE CONTRACTING OFFICER AND NOTIFY
ENGINEER IF EITHER OF THESE READINGS EXCEEDS 160 AMPS.
REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REV REVISION / ISSUE DESCRIPTION DRN CHK APP APP APP APPDDMMYY REFERENCES
F
E
D
C
B
A
5 4 3 2 19 8 7 6
0TENTHS 0 INCHES 1 2 3 54 6 7 8 9 EIGHTHS10 7010MM 20 30 40 50 60 9080 100
COPYRIGHT © 2018
AR
CH
D -2
4x
UNLESS OTHERWISE AGREED IN A WRITTEN CONTRACT BETWEEN WOOD ENVIRONMENT &
INFRASTRUCTURE SOLUTIONS, INC. AND ITS CLIENT, THIS DOCUMENT: (I) CONTAINS INFORMATION, DATA AND DESIGN THAT IS CONFIDENTIAL AND MAY NOT BE COPIED OR DISCLOSED; AND (II) MAY BE USED BY THE CLIENT ONLY IN THE CONTEXT AND FOR THE EXPRESS PURPOSE FOR WHICH IT WAS INTENDED.
ANY USE OF, OR RELIANCE ON, THIS DOCUMENT BY ANY THIRD PARTY IS AT THAT PARTY'S SOLE RISK.
Environment & Infrastructure Solutions, Inc.
4600 E. WASHINGTON STREET, SUITE 600
PHOENIX, ARIZONA 85034 / PHONE: 602-733-6000
SCALE:
STAMP/SEAL
DES
DRN
SCALE
PROJECT NO.
CLIENT PROJECT MGR DEPARTMENT MGR PROJECT MGR
BY DD/MM/YY SUBJECT AREA
CLIENT DWG NO.
DRAWING…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .