Atch 2_Drawings.pdf
PDF 11 MB Posted
- Attached to
- Transformer Replacement, Ames Federal contract opportunity
- Solicitation number
- 12639524Q0094
About this file
This file provides details for a federal solicitation from the Department of Agriculture Animal and Plant Health Inspection Service Marketing and Regulatory Programs Business Services. Solicitation number 12639524Q0094 seeks proposals to replace transformers at a location in Ames, Iowa. Offerors should review the attached drawings in Atch 2_Drawings.pdf to understand the scope of work. Proposals are due by the date specified in the full solicitation document. The opportunity is set aside for small businesses.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Questions and answers.docx | DOCX document | |
| 12639524Q0094-0001.pdf | ||
| Atch 3_Larson Spec for Information Only.pdf | ||
| FYI ONLY_Quotation Larson_redacted.pdf | ||
| Atch 1_SOW Building 403 transformer replacement.docx | DOCX document | |
| Atch 4_Federal Construction Wage Rates Story County.pdf | ||
| 12639524Q0094.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Location Coordinator:Contracting Officer Rep.:Contracting Officer:Engineering Project Manager:
Task
Order #:
Drawing Title:PROJECT TITLE:
FEU Project #:
Drawing Number:
Agricultural Research Service U.S. Department of Agriculture
NCAH
1920 Dayton Avenue Ames, Iowa 50010
Revision:
Client:
Sheet: Of
Designer:
Date:
Date:
Ben A'Hearn TBD Brandon Keith
Building 403 Transformer Replacement
Title Page
2/21/2024
Brandon Keith P01
24016 1 7
Building 403 transformer replacement
UNITED STATES DEPARTMENT OF AGRICULTURE
AGRICULTURE RESEARCH SERVICE
NATIONAL CENTERS FOR ANIMAL HEALTH
INDEX OF DRAWINGS
P02
Title Page
Transformer Basin Details
P03
P04
Construction Area Detail
P01
Name Plates/Photos
P06
Switchgear One Lines
Existing Transformer Details
P07 New Transformer Specification
P05
Construction Area, Building 403
Attachment 2
Order #:
Drawing Title:PROJECT TITLE:
FEU Project #:
Drawing Number:
Agricultural Research Service U.S. Department of Agriculture
NCAH
1920 Dayton Avenue Ames, Iowa 50010
Revision:
Client:
Sheet: Of
Designer:
Date:
Date:
Ben A'Hearn TBD Brandon Keith
Building 403 Transformer Replacement
Transformer Basin Details
2/21/2024
Brandon Keith P02
24016 2 7
TRANSFORMER PAD DETAIL
NO SCALE
Contractor shall be responsible for containment basin size based on the size of the new 75 kVA transformer and liquid contained within.
3" cast iron pipe with self closing gate valve. Drain Valve to be positioned as to allow complete drainage of rainwater from basin without pooling. Drain shall be located at lowest point.
Transformer Pad and Basin Detail
FOR REFERENCE ONLY
Order #:
Drawing Title:PROJECT TITLE:
FEU Project #:
Drawing Number:
Agricultural Research Service U.S. Department of Agriculture
NCAH
1920 Dayton Avenue Ames, Iowa 50010
Revision:
Client:
Sheet: Of
Designer:
Date:
Date:
Ben A'Hearn TBD Brandon Keith
Building 403 Transformer Replacement
Construction Area Details
2/21/2024
Brandon Keith P03
24016 3 7
Building403
Existing transformer at building 403, to be replaced.
13.8 Switchgear
13.8KV Feeder to Building 403
NORTH
Order #:
Drawing Title:PROJECT TITLE:
FEU Project #:
Drawing Number:
Agricultural Research Service U.S. Department of Agriculture
NCAH
1920 Dayton Avenue Ames, Iowa 50010
Revision:
Client:
Sheet: Of
Designer:
Date:
Date:
Ben A'Hearn TBD Brandon Keith
Building 403 Transformer Replacement
Name Plates/Photos
2/21/2024
Brandon Keith P04
24016 4 7
Existing 112.5kVA transformer (To Be replaced) Existing Arc Flash Label
Order #:
Drawing Title:PROJECT TITLE:
FEU Project #:
Drawing Number:
Agricultural Research Service U.S. Department of Agriculture
NCAH
1920 Dayton Avenue Ames, Iowa 50010
Revision:
Client:
Sheet: Of
Designer:
Date:
Date:
Ben A'Hearn TBD Brandon Keith
Building 403 Transformer Replacement
Switchgear One lines
2/21/2024
Brandon Keith P05
24016 5 7
Order #:
Drawing Title:PROJECT TITLE:
FEU Project #:
Drawing Number:
Agricultural Research Service U.S. Department of Agriculture
NCAH
1920 Dayton Avenue Ames, Iowa 50010
Revision:
Client:
Sheet: Of
Designer:
Date:
Date:
Ben A'Hearn TBD Brandon Keith
Building 403 Transformer Replacement
Existing Transformer Details
2/21/2024
Brandon Keith P06
24016 6 7
403 transformer 112.5kVA
97 gallons of oil
84.00 in
.0 in
To Be Replaced with new 75kVA transformer
Order #:
Drawing Title:PROJECT TITLE:
FEU Project #:
Drawing Number:
Agricultural Research Service U.S. Department of Agriculture
NCAH
1920 Dayton Avenue Ames, Iowa 50010
Revision:
Client:
Sheet: Of
Designer:
Date:
Date:
Ben A'Hearn TBD Brandon Keith
Building 403 Transformer Replacement
New Transformer Specification
2/21/2024
Brandon Keith P07
24016 7 7
MT-PML-R7-3P-DMP-75KVA-YT-LT-DF-A6-BB-CZ-2B4-M1 Pad Mount Transformer Ratings Transformer Type: Pad Mounted, Compartmental-Type Meets/Exceeds DOE 2016 Efficiency Ratings Transformer Configuration: Liquid Filled Pad Mounted Meets/Exceeds CSA Efficiency Ratings Transformer Feed Type: Loop Feed Complies with ANSI / IEEE C57.12.00 Operation: Step-Down Operation (Not Approved for Step-Up) Complies with ANSI / IEEE C57 12.28 Phase: Three Phase Complies with ANSI / IEEE C57 12.29 Capacity: 75 KVA Complies with ANSI / IEEE C57 12.34 Vector Group: DYN1 Complies with ANSI / IEEE C57 12.35 Primary Voltage: 13800V Complies with ANSI / IEEE C57.12.70 Primary Voltage Switch: N/A Complies with ANSI / IEEE C57.12.110 Primary Voltage Class: 15 kV Class Complies with ANSI / IEEE C57.12.131 Primary Phasor: Delta Complies with ANSI / IEEE C62.11 Primary BIL: 95 KV Complies with ANSI / IEEE C62.22 Secondary Voltage: 208Y/120 Complies with ANSI / IEEE 386 Secondary Voltage Class: 1.2 kV Class Complies with ANSI / IEEE C2 Secondary Phasor: Wye-N Complies with ANSI / IEEE C37.47 Secondary BIL: 30 KV Complies with ANSI Z535.4 Frequency: 60 Hz Complies with ASTM D3487 Temperature Rise: 65°C Complies with ASTM D6871 Insulation Rating: Class E Insulation - 120°C, 248°F Complies with NEMA 260-1996 Cooling Class: KNAN; Self-Cooled Complies with 10 CFR Part 431 Forced Air (Fans): None Complies with CSA C2.1-06 Tap Changer: 5-position Tap Changer Complies with CSA C50 Tap Qty: (2) FCAN Above Taps, (2) FCBN Below Taps Complies with CSA C88 Tap %: 2.5% Complies with CSA C88.1 Tap Changer Switch Rating: 200-Amp, 15 kV Complies with CSA C88-16 Tap Changer Switch Location: High Voltage (HV) [Left Side] Front Compartment Complies with CSA C227.4 Impedance: 1.0-5.0% Typical, Target 2.70-5% Complies with CSA C227.5 Primary Connection Type: Dead Front Complies with CSA C802-3 Primary Termination Arrangement: V Terminal Arrangement Complies with CSA C802.1 Primary Termination: Externally Clamped Well Bushings w/ Removable Studs, 200A Load Break Elbows w/ Inserts Primary Connection Qty: (6) Primary Connections for use w/ Elbow Connectors Features Primary Parking Stand Qty: (6) Welded Brackets for Installing Accessory Parking Stand Bushings
Pentahead Bolt Entry Assembly
Primary Bushing Rating: 15 kV Class, 95 kV BIL, 200A, Load Break, IEEE 386 Color Red High-Fire Point Insulating Fluid Primary Neutral Connection: Primary HO Neutral Internally Bonded to Tank Non-PCB Insulating Fluid Primary Surge Arrestors: (3) High Voltage Elbow Surge Arrestors, Included Tamper Proof Housing Primary Surge Arrestor Voltage Rating: 18 kV Class Elbow Arrestor Hinged Front Compartment Doors, Pad Lockable Primary Surge Arrestor MCOV Rating: 15.3 kVrms NEMA 3R Wiring Compartment Primary Over Current Protection (OCP): Bayonet Expulsion Fuse in series w/ Partial- Range Current-Limiting Fuse
Hot Stick Included, HV Door Mount
Primary Over Current Protection Method: Fused, Oil-Immersed Primary Over Current Protection Holder: Bayonet Fuse Holder w/ Flapper Valve and External Drip Shield
Efficiency %: 98.70%
Primary Grounding Provisions: (1) NEMA Ground Bar attached to tank via (2) Welded Ground Bungs in HV Cabinet
Based on transformer operating at 50% of namep base kVA.
Secondary Connection Type: Live Front Secondary Termination Arrangement: Staggered Terminal Arrangement Load Losses Based on 85°C Reference Temp.
Secondary Connections: NEMA Spade Terminals, 4-Hole Spade, Externally Clamped, Accepts up to (4) Double Lug connections with (2) cables per side of Spade connector
No Load Loss (in watts): +/- 190W
Secondary Connection Qty: (4) Externally Clamped One-Piece Epoxy Bushings Copper Threaded Studs
Full Load Loss (in watts) at 100%: +/- 950W
Secondary Connection Supports: N/A Total Load Loss (in watts) at 100%: +/- 1,140W Secondary Over Current Protection (OCP): N/A Secondary Neutral Connection: Secondary X2 Neutral Grounded to Tank via 1/2”-13 UNC Tapped Hole, 7/16” Deep Bung & Copper Ground Strap
Total Losses at 55°C LL Temp.& 20°C NL Tem
Secondary Grounding Provisions: (1) NEMA Ground Bar attached to tank via (2) Welded Ground Bungs in LV Cabinet
Total Load Loss (in watts) at 50%: +/- 413W
Metering Current Transformer (CT): N/A Note: Losses offered are typical only, not gua
Metering Panel: N/A Auxiliary Control Panel : N/A Labeling:
Load Break Switch: 4-Position Load Break Switch Externally Stencilled (Painted) KVA Rating Load Break Switch Qty: (1) Externally Stencilled (Painted) Voltage Rating Load Break Switch Rating: 200-Amp, 15 kV External Non-PCB Label Load Break Switch Location: High Voltage (HV) Front Compartment External Warning & Danger Label Efficiency Standard(s): Meets DOE 2016 Standards, Meets CSA Standards Meets ANSI/IEEE Standards
External Barcode Label
K-Factor Rating (Harmonic Mitigation): K-1 (Standard) Internal Busing & Accessory Labeling Pulse Drive Rating: N/A Stainless Steel Riveted Nameplate Insulation Fluid: Biodegradable Natural Vegetable Oil Ester Insulating Fluid - Non-PCB Fluid Fluid (Oil) Capacity*: 75 Gallons Factory Tests:
Fluid (Oil) Weight*: 575 lb Winding Resistance Test Liquid Level Indicator: Analog Dial Gauge Insulation Resistance Test Temperature Indicator: Analog Dial Gauge Voltage Ratio Error Test Pressure/Vacuum Indicator: Analog Dial Gauge Short-circuit Impedance Test Pressure Relief Device: Included, Automatic Action No-load Loss (Wattage) Test Fault Indicator: N/A Load Loss (Wattage) Test Gas Sampler Valve: Included, Schrader Valve Induced Voltage Withstand Test Fill Valve: 1" NPT Port w/ Removable Bolt Plug Separate Source Voltage Withstand Test Fill Valve Location: Front Compartment Pressure Integrity Test Test Drain Valve: 1" NPT Port w/ 5/8" NPT Sampler Valve Drain Valve Location: Front Compartment Shipping:
Winding Material: Copper Shipped on pallet on open flatbed Ambient Temperature Rating: 40°C Palletized on Wooden Pallet w/ Skid Pockets Ambient Operating Temperature Range: -40°C to +40°C (-50°F to +104°F) Pallet Skid Facing Outward Sides of Truck
Sound Level: 51 dBA Note: Crated shipping in lieu of palletizing can be done upon request for an additional fee
Elevation (Altitude): 3300ft (1000 meters) Above Sea Level Core Material: Grain Oriented Steel Tank Material: Coated Steel Cabinet Material: Coated Steel Base Platform Material: Coated Steel Portability: Lifting lugs, provisions for jacking under base, w/ base construction suitable for using rollers or skidding Housing Type: Compartmental Air-Filled Cabinet w/ Locking Doors, HV Compartment Left, LV Compartment Right, Steel Barrier Separation, HV Door Spring-Loaded Release Pin in LV Compartment Enclosure Rating: NEMA 3R Weatherproof Wiring Cabinet, Sealed Tank Seismic Rating: Yes Paint Type: Weatherproof and UV Resistant Epoxy Coating and Undercoating Finish Color: Munsell™ 7.0 GY 3.29/1.5 Bell Green Mounting: Pad Mounted Conduit Opening: Bottom Feed Underground Entry/Exit HV Compartment Base Wireway Dimensions*: 20"-W x 5"-D LV Compartment Base Wireway Dimensions*: 16"-W x 5"-D MV/LV Compartment Cabinet Depth*: 20"-D Tank Cover Access Handhole: N/A
Dimensions*: 61"-W x 43"-D x 69"-H
Dry Weight (w/o Oil)*: 730 lb
Total Weight (Liquid Filled)*: 2,160 lb
New Transformer Specification (Or Approved Equivalent)
File details come from the government source that posted it. Updated .