Ascend704-ElectricalDrawings.pdf
PDF 21 MB Posted
- Attached to
- Ascend704 Managed Network & NOC
- Solicitation number
- 76-20260714
- Issued by
- North Carolina
About this file
This file is an electrical design drawing and legend for the Ascend704 Entrepreneurship Center project at South Piedmont Community College in Monroe, North Carolina. The document provides comprehensive electrical specifications and symbol definitions for the new facility construction, prepared by L.B. Smith and Associates, P.A. under North Carolina License C-0503. The electrical design follows 2018 NCECC and ASHRAE 90.1 energy code standards, with interior lighting power specified at 32,524 watts against an allowable 50,738 watts, and exterior lighting power specified at 5,036 watts against an allowable 8,897 watts. The project includes detailed luminaire schedules, fixture specifications, mounting heights, and control systems across multiple floor plans covering power distribution, fire alarm systems, data networks, security systems, and sound masking installations. The drawings encompass a multi-sheet set including floor plans for first floor, second floor, and high roof areas, along with riser diagrams and detailed equipment specifications.
The electrical design incorporates advanced building systems including emergency lighting with battery backup, ground fault protection systems, audio/video intercoms, CCTV security cameras, fire alarm systems with addressable modules, access control panels, occupancy sensors, dimming controls, and data/voice outlets for telecommunications. Mounting height specifications are provided for all wall-mounted and ceiling-mounted devices, with general notes requiring compliance with NEC, NFPA codes, and all local building codes. The contractor is responsible for coordination with mechanical, plumbing, and architectural trades; shop drawing submissions prior to installation; and adherence to manufacturer specifications. A one-year warranty from substantial completion is required for all materials and work, with all equipment to be UL-listed and labeled. The project includes provisions for seismic restraint, fire-rated ceiling assemblies, and phased construction sequencing with temporary service connections as needed to maintain the project schedule.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFQ# 76-20260714 Ascend704 Managed Network & NOC.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2018 APPENDIX B
BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS
ELECTRICAL DESIGN
ELECTRICAL SUMMARY
ELECTRICAL SYSTEM AND EQUIPMENT
Method of Compliance: Energy Code Performance X Prescriptive
ASHRAE 90.1 Performance Prescriptive
Lighting schedule (each fixture type) lamp type required in fixture Refer to Luminaire Schedule, Sheet E-002 number of lamps in fixture Refer to Luminaire Schedule, Sheet E-002 ballast type used in the fixture Refer to Luminaire Schedule, Sheet E-002 number of ballasts in fixture Refer to Luminaire Schedule, Sheet E-002 total wattage per fixture Refer to Luminaire Schedule, Sheet E-002 total interior wattage specified vs. allowed (whole building or space by space)
32,524 watts specified 50,738 watts allowed total exterior wattage specified vs. allowed
5,036 watts specified 8,897 watts allowed
Additional Efficiency Package Options
(When using the 2018 NCECC; not required for ASHRAE 90.1)
C406.2 More Efficient HVAC Equipment Performance
X C406.3 Reduced Lighting Power Density
C406.4 Enhanced Digital Lighting Controls
C406.5 On-Site Renewable Energy
C406.6 Dedicated Outdoor Air System
C406.7 Reduced Energy Use in Service Water Heating
C
SD
SD
BL
P
UON
EM
CFOI
OFOI
CFCI
OFCI
T C/S
J
DESCRIPTION
DP
S
S
X
S
S 3
S D
SK
PC
S
S 4
S
U
SL
N
OS
OS
SPL
IL
GROUND FAULT PROTECTED DUPLEX WITH WEATHER-
PROOF "WHILE IN USE" TYPE DIE-CAST METAL
COVERPLATE WITH LOCKABLE ENCLOSURE AT
OUTLET - SEE SPECIFICATIONS
WP
ER
ELECTRIC WATER COOLER RECEPTACLE:
COORDINATE EXACT LOCATION WITH PLUMBING
CONTRACTOR TO CONCEAL OUTLET(S) BEHIND
COOLER, PROVIDE MULTIPLE RECEPTACLES WHERE
REQUIRED BY MANUFACTURER, PROVIDE READILY
ACCESSIBLE DEAD FRONT GFCI DEVICE AT 18"
ADJACENT TO WATER COOLER FOR PROTECTION OF
WATER COOLER RECEPTACLE(S)
EWC
AUDIO/VIDEO INTERCOM STATION: MASTER WITH
SELECTIVE DOOR CONTROLS, POWER SUPPLIES & DOOR
RELAY CONTACTS AS REQUIRED FOR OPERATION OF
ANY DOOR IN THE SYSTEM AND VIEWING OF ANY
AUDIO/VIDEO INTERCOM REMOTE ON THE SYSTEM.
AIPHONE#AX-MV W/DESK STAND - COLOR BY ARCHITECT.
SAME AS ''IM'' EXCEPT WALL MOUNTED W
DOOR RELEASE PUSH-PLATE / INFRA-RED OPERATOR
STATION. PROVIDE ANY ADDITIONAL ROUGH-IN FOR
''EMERGENCY RELEASE'' OPERATOR STATIONS AS
REQUIRED.
DOOR RELEASE CARD READER STATION. PROVIDE
ANY ADDITIONAL ROUGH-IN FOR ''EMERGENCY
RELEASE'' OPERATOR STATIONS AS REQUIRED.
AUTOMATIC DOOR CONNECTION (MAY ALSO HAVE
ELECTRIC STRIKE/MAG-LOCK/ELECTRIFIED PANIC
CONNECTION - SEE ARCHITECTURAL HARDWARE
SPECIFICATIONS)
2-GANG DEEP FLOORBOX, COMBO POWER/DATA/AV
BASIS OF DESIGN: HUBBELL FB4233
B
SS
KEYED, LOCKED PULL STATION : DOUBLE ACTION.
STATION SHALL ONLY BE OPERABLE VIA KEY IN
POSSESSION OF STAFF.
CDCARBON MONOXIDE DUCT DETECTOR
POWER SUPPLY/CONTROL FOR AUDIO/VISUAL DEVICES
SAME AS ''CR'' EXCEPT MULLION MOUNT M
SLASH THROUGH ANY DEVICE INDICATES MOUNTING
ABOVE COUNTERTOP 4" ABOVE BACKSPLASH, OR AT 46"
WHERE NO COUNTER IS PRESENT
CCTV CAMERA: CEILING MOUNT DOME
''DOG-HOUSE'' TYPE TWIN DUPLEX RECEPTACLE
WITH ONE DUPLEX RECEPTACLE ON BOTH SIDES
AUDIO/VIDEO INTERCOM STATION: REMOTE WITH
FLUSH-MTD S.S. ENCLOSURE. AIPHONE #AX-DVF.
SVS
VS
LV
PILOT LIGHT SWITCH (ILLUMINATED WHEN LOAD IS ON)
ILLUMINATED HANDLE LIGHT SWITCH (ILLUMINATED
WHEN LOAD IS OFF)
EMERGENCY AUTOMATIC TRANSFER SWITCH
FOR LIGHTING CONTROLS (REFER TO DETAIL)
FILLED CENTER BAR INDICATES INTEGRAL GROUND
FAULT PROTECTION (GFCI)
GANG RECEPTACLE IN COMBINATION WITH SWITCH
(PROVIDE DIVIDER IF LIGHTING CIRCUIT IS 277V)
NON-REVERSING MOTOR STARTER SNAP SWITCH
CONTRACTOR FURNISHED OWNER INSTALLED
CONTRACTOR FURNISHED CONTRACTOR INSTALLED
OWNER FURNISHED OWNER INSTALLED
OWNER FURNISHED CONTRACTOR INSTALLED
FLUSH MOUNTED REMOTE ALARM INDICATING
STATION/TEST SWITCH
CONNECTION TO SPRINKLER TAMPER
SWITCH WITH ADDRESSABLE MODULE
CONNECTION TO SPRINKLER FLOW
SWITCH WITH ADDRESSABLE MODULE
PHOTO-ELECTRIC SMOKE DETECTOR FOR PATIENT
ROOM MONITORING (SEE RISER)
PHOTO-ELECTRIC SMOKE DETECTOR
MAIN CONTROL PANEL CENTRAL PROCESSING
UNIT (CPU)
DOOR ALARM/POSITION SWITCH
TELEVISION SYSTEM OUTLET WITH DUPLEX
RECEPTACLE, COORDINATE LOCATION WITH WALL
BRACKET WHERE APPLICABLE
SURGICAL LIGHT INTENSITY CONTROL
LIGHT SWITCH:GENERAL PURPOSE
AS NOTED
AS NOTED
LIGHT SWITCH FOR UNDER-CABINET LIGHTS
6'-6'' TO
TOP
46" TO
LEVER
46" TO
LEVER
PULL STATION : DOUBLE ACTION
AUDIO-ONLY NOTIFICATION APPLIANCE
VISUAL-ONLY NOTIFICATION APPLIANCE
AUDIO/VISUAL NOTIFICATION APPLIANCE
BELL / LIGHT
BELL ONLY
HEAT DETECTOR
CARBON MONOXIDE ALARM: SINGLE STATION
W/SOUNDER BASE
CARBON MONOXIDE AUDIO/VISUAL NOTIFICATION
APPLIANCE
DOOR HOLDER : WALL TYPE
DOOR HOLDER : CLOSURE TYPE
DUCT SMOKE DETECTOR
PRESSURE SWITCH
REMOTE L.C.D. FIRE ALARM ANNUNCIATOR
POST INDICATOR VALVE
ISOLATION MODULE
H.V.A.C. SMOKE DAMPER CONNECTION
UNLESS OTHERWISE NOTED
INDICATES EMERGENCY POWER
SURFACE PLUG-MOLD
SPECIAL OUTLETS
HD
ABV CLG
CM
F
DH
ABV DOOR DH
ABV CLG DD
FS
TS
PS
46"
I
ZONE ADDRESSABLE MODULE Z
SM
ABBREVIATIONS
DESCRIPTION
XLSL
STRIP FIXTURE
CROSS-HATCHING INDICATES LIGHT IS POWERED
FROM THE EMERGENCY-CRITICAL BRANCH
PARALLEL-HATCHING INDICATES LIGHT IS POWERED
FROM THE EMERGENCY-LIFE SAFETY BRANCH
PANEL FURNITURE
POWER OUTLETS
SIMPLEX RECEPTACLE
DUPLEX RECEPTACLE-SAFETY TYPE,
TAMPER-RESISTANT
DUPLEX RECEPTACLE
QUADRUPLEX RECEPTACLE
JUNCTION BOX, CEILING OR WALL
VOLTAGE/1PH RECEPTACLE, AS NOTED
VOLTAGE/3PH RECEPTACLE, AS NOTED
SS INDICATES SURGE SUPPRESION TYPE OUTLET(S)
EXAM LIGHT SWITCH
NIGHT LIGHT SWITCH WITH CONSTANTLY
ILLUMINATED HANDLE
DIMMER SWITCH
THREE-WAY SWITCH
FOUR-WAY SWITCH
KEYED SWITCH
OCCUPANCY OR VACANCY SENSOR SWITCH
OCCUPANCY OR VACANCY SENSOR, CEILING MOUNT
LOW VOLTAGE MOMENTARY SWITCH
PHOTO-CELL AS NOTED
SURGICAL/EXAM LIGHT
EXIT LIGHT (CEILING, END, WALL MOUNT)
LIGHTING
REFER TO LUMINAIRE SCHEDULE FOR EXACT FIXTURE
SPECIFICATIONS, MOUNTING HEIGHTS, ETC.
SPECIAL VIDEO SYSTEM SIGNAL INPUT
SECURITY INTERCOM
SECURITY ACCESS CONTROL
SECURITY CCTV VIDEO SURVEILLANCE
CCTV CAMERA: WALL MOUNT DOME
CCTV POWER SUPPLIES/CONTROL PANEL 46"
DOOR
FRAME
DESCRIPTION
WALL, CLG
80"
CLG
CLG
CLG
WALL
54"
46"
46"
46"
46"
46"
46"
46"
46"
46"
46"
46"
46"
46"
1'-6"
1'-6"
1'-6"
1'-6"
46"
1'-6"
1'-6"
ON CNTR.
2'-2"
CLG
AS NOTED
18''
46"
46"
CLG
46"
46"
CLG
7'-0"
S
S
FLOOR
S
S
S M
TELEVISION SPLITTERS/AMPLIFIERS/DISTRIBUTION
TELEVISION
46" TV-HE
D R
A W
IN
G
S Y
M B
O L
SURFACE OR SUSPENDED CEILING FIXTURE (SLASH
INDICATES RECESSED)
POLE MOUNTED AREA LIGHT
EMERGENCY BATTERY WALL-PACK
WALL MOUNT FIXTURE ,
FLOODLIGHT
V
A
F
F K
F
GRAPHICS DISPLAY TERMINAL
RI
INDICATES VANDAL-PROOF POLYCARBONATE COVER,
VANDAL PROOF COVERS SHALL BE UL LISTED FOR USE
WITH THE SPECIFIC DEVICE THEY ARE PROTECTING
PC
80"
CLG
WALL
WALL
7'-6''
FIREMAN'S PHONE JACK FP
ADDRESSABLE RELAY MODULE R
WALL
ACCESS CONTROL PANEL 46"
46"
1-GANG DEEP FLOORBOX, POWER ONLY
BASIS OF DESIGN: HUBBELL FB4133
FLOOR
FIRE RATED POKE-THRU FLOOR BOX, COORDINATE
EXACT COVER REQUIREMENTS WITH ARCHITECTURAL
FINISHES, DEVICES AS SCHEDULED
BASIS OF DESIGN: HUBBELL S1R4PTFIT
DESCRIPTION
K
DB
DB
WP
DOORBELL PUSHBUTTON STATION, PROVIDE COMPLETE
WITH TRANSFORMER (MOUNT ABOVE CEILING IN
CORRIDOR NEAR PUSH-BUTTON) AND ALL
ACCESSORIES, POWER FROM NEAREST AVAILABLE 120V
NORMAL POWER GENERAL RECEPTACLE CIRCUIT,
NUTONE OR EQUAL
DOORBELL AUDIO/VISUAL STATION, PROVIDE PROVIDE
CONNECTION TO PUSHBUTTON STATION IN AREA.
COORDINATE EXACT AUDIO SOUND (CHIME, BUZZER,
ETC.) DESIRED WITH OwNER/ARCHITECT, NUTONE OR
EQUAL
PLUMBING FIXTURE ELECTRIC EYE TRANSFORMER
CONNECTION. TRANSFORMER SHALL BE 120V-24V.
MOUNT ABOVE SUSPENDED ACCESSIBLE CEILING IN J-
BOX. PROVIDE ADDITIONAL TRANSFORMERS OF SAME
TYPE AS/IF NEEDED
PROVIDE CONNECTION TO HAND DRYER (SEE
ARCHITECTURAL SPECIFICATIONS)
VERIFY WITH
ARCHITECT
C
INDICATES MOUNTING ABOVE COUNTER-TOP,
2" ABOVE BACKSPLASH, NO HIGHER THAN 48''
WG
WIREGUARD - PROVIDE MANUFACTURER'S
SPECIFIC GUARD FOR DEVICE NOTED
BOX ON ANY DEVICE INDICATES SURFACE MOUNTED
BACKBOX/WIREMOLD
CONDUIT CONCEALED IN WALLS OR IN CEILING
SPACE: ARROW(S) INDICATE(S) HOME RUN & #
OF CIRCUITS: HASHMARKS INDICATE # OF
CONDUCTORS. DASHED LINE INDICATES
CONDUIT BELOW FLOOR.
WIREWAY WITH REMOVABLE COVER (SIZE AS NOTED)
PANELBOARD, SURFACE OR FLUSH MOUNTED,
HATCHING INDICATES EMERGENCY
EQUIPMENT TAG, REFER TO EQUIPMENT SCHEDULE
MECHANICAL EQUIPMENT DESIGNATOR
(SEE MECH. SCHEDULES)
EQUIPMENT HARDWIRE CONNECTION (SEE DETAIL)
KITCHEN EQUIPMENT OUTLET COUPLING
CONNECTION (SEE DETAIL)
AS SHOWN
AS SHOWN
AS NOTED
AS SHOWN
MISCELLANEOUS
DISCONNECT SWITCH
MAGNETIC STARTER
MAGNETIC COMBINATION STARTER
ENCLOSED FLUSH MTD. CIRCUIT BREAKER
WEATHERPROOF - NEMA-3R, WET LOCATION LISTED.
PROVIDE COVERS, RATINGS, ETC, AS SUITABLE FOR
OUTDOORS.
TRENCH DUCT (SIZE AS NOTED)
PUSHBUTTON STATION
FLEXIBLE CONDUIT
TRANSFORMER
TAGGED NOTE
REVISION TAG
WIRE BASKET CABLE TRAY, SIZE AS NOTED
LOW VOLTAGE CABLE PATH
5'-0"
5'-0"
5'-0"
5'-0"
46"
46"
7'-6''
6'-6'' TO TOP
XPEXPLOSION PROOF - PROVIDE WIRING METHODS,
ENCLOSURES, RATINGS, ETC. AS SUITABLE FOR
HAZARDOUS LOCATION.
SURGE PROTECTION DEVICE
GENERATOR ANNUNCIATOR PANEL - SEE
SPECIFICATIONS
46"
THERMOSTAT PROVIDED BY MECHANICAL
CONTRACTOR, ELECTRICAL CONTRACTOR SHALL
PROVIDE BACK-BOX CONDUIT STUB-UP, REFER TO
MECHANICAL DRAWINGS FOR LOCATIONS
PANEL FURNITURE DUPLEX RECEPTACLE. PROVIDE
ALL WIRING AS REQUIRED, COORDINATE EXACT
INSTALLATION REQUIREMENTS AND LOCATIONS WITH
OWNER'S PANEL FURNITURE VENDOR
PANEL FURNITURE DATA/VOICE OUTLET. PROVIDE ALL
WIRING AS REQUIRED, COORDINATE EXACT
INSTALLATION REQUIREMENTS AND LOCATIONS WITH
OWNER'S PANEL FURNITURE VENDOR
POWER CONNECTION TO PANEL FURNITURE, PROVIDE
SEAL-TIGHT CONDUIT CONNECTION FROM RECESSED
WALL BOX TO PANEL FURNITURE, PROVIDE FINAL
CONNECTIONS TO PANEL FURNITURE AS REQUIRED BY
PANEL FURNITURE VENDOR
1'-6"
COMBINATION POWER AND LOW VOLTAGE CONNECTION
TO PANEL FURNITURE, PROVIDE SEAL-TIGHT CONDUIT
CONNECTION FROM RECESSED WALL BOX TO PANEL
FURNITURE, PROVIDE FINAL CONNECTIONS TO PANEL
FURNITURE AS REQUIRED BY PANEL FURNITURE
VENDOR
PPPOWER POLE AS NOTED
SECURITY
MOTION DETECTOR CLG
SWITCHES
MOMENTARY CONTACT SWITCH
HAND-OFF-AUTO 3-POSTION SWITCH
TIMER SWITCH
S MC
S HOA
S T
46"
46"
46"
KEYPAD STATION. SURFACE-MOUNTED BOTTOM
AT 60'' AFF - (SEE SPECIFICATIONS)
SV
S
SPAGING SPEAKER: WALL
PAGING SPEAKER W/ VOLUME CONTROL
PAGING SPEAKER: CEILING CLG
CLG
8'-0"
OVERHEAD PAGING
VANDAL PROOF / WEATHERPROOF WALL
MOUNTED PAGING SPEAKER. QUAM VP1
EXTERIOR VANDAL PROOF / WEATHERPROOF WALL
MOUNTED PAGING SPEAKER, SHALL BE PAINTED
COLOR SELECTED BY ARCHITECT/OWNER. QUAM VP6
SEE
FLOOR
PLANS
SEE
FLOOR
PLANS
S
S
EXT.
FIRE ALARM
WP
E,EMINDICATES EMERGENCY POWER
SURFACE WIRE-MOLD
KP
MD
GEN-A
SPD
J
J
SEC-A
GDT
NAC
CC
CC
CR
DA
IM
IR
PP
CR
AD
IM
PIV
FAA
FACP
IDC
J
T
FP
D R
A W
M B
O L
D R
A W
M B
O L
D R
A W
M B
O L
AS SHOWNLADDER CABLE TRAY, SIZE AS NOTED
AS SHOWNSOLID BOTTOM CABLE TRAY, SIZE AS NOTED
EQUIP-1
PLUMBING FIXTURE SOLENOID VALVE/ELECTRIC EYE
SENSOR CONNECTION. COORDINATE EXACT
CONNECTION REQUIREMENTS WITH MANUFACTURER.
GROUND
NEUTRAL
PHASE
FIREMAN'S KNOX BOX CONNECTION KB
REMOTE FIRE ALARM ANNUNCIATOR W/ MICROPHONE 54" FAAM
WALL, CLG
WALL, CLG V
A
F, CM
INDICATES CHIME AUDIBLE NOTIFACTION CH
DEVICE USED FOR ELEVATOR CONTROL EL
FIRE ALARM CONTROL EXTENDER EXT
4'-6''
TRANSPONDER CABINET 46" TRAN
BE , BR
PROJECTED BEAM SMOKE DETECTOR; EMITTER
(BE) AND RECEIVER (BR)
FLOOR
AV
AUDIO/VISUAL SYSTEM OUTLET, REFER TO
ASSOCIATED DETAIL 5/E303 FOR ADDITIONAL
INFORMATION
COMBINATION POWER AND DATA OUTLET LOCATION,
REFER TO ASSOCIATED DETAIL 6/E303 FOR
ADDITIONAL INFORMATION
1'-6"
1'-6"
FF
DEAD FRONT GFCI DEVICE, LABEL AND INSTALL IN
READILY ACCESSIBLE LOCATION
FILLED OUTER BARS INDICATES INTEGRAL INTEGRAL
USB OUTLETS IN ADDITION TO POWER RECEPTACLES
1'-6"
, J
VARIABLE FREQUENCY DRIVE 5'-0"
CIRCLE ON ANY DEVICE INDICATES DEVICE FED FROM
STUB UP CONDUIT
MOTOR CONNECTION, REFER TO EQUIPMENT
CONNECTION SCHEDULE
DUPLEX RECEPTACLE, CEILING MOUNTED CLG
#D
WIRELESS ACCESS POINT WITH PROVISIONS FOR (1
DATA OUTLET FOR ANTENNA. PROVIDE A COMPLETE
DATA OUTLET WITH FACEPLATE ABOVE CEILING,
MOUNTED AT AN ACCESSIBLE HEIGHT NO MORE THAN
24" ABOVE CEILING. AT EACH OUTLET, PROVIDE A 20'
COIL OF CABLE AHEAD OF THE OUTLET FOR
ADJUSTMENT OF FINAL OUTLET LOCATION. THE
CONTRACTOR SHALL COORDINATE EXACT LOCATIONS
WITH THE OWNER AND ADJUST OUTLET LOCATIONS AT
SUBSTANTIAL COMPLETION TO ACCOMMODATE
OWNER'S WAP LOCATIONS. WAP'S ARE OWNER-
FURNISHED, OWNER-INSTALLED
WAP
DATA OUTLET : NUMBER BESIDE OUTLET
INDICATES NUMBER OF DATA JACKS
DATA / VOICE
1'-6"
CONDUIT UP
CONDUIT DOWN
GROUND BUS BAR ON INSULATED STANDOFFS 2'-0''
AS SHOWNBUS DUCT, AMPERAGES AS NOTED
M O
U N
T
IN
G H
E
IG
H T
(T O
C E
N T
E R
O F
B O
X
M O
U N
T
IN
G H
E
IG
C E
N T
E R
O F
B O
X
M O
U N
T
IN
G H
E
IG
C E
N T
E R
O F
B O
X
M O
U N
T
IN
G H
E
IG
C E
N T
E R
O F
B O
X
WIRELESS ACCESS POINT WITH PROVISIONS FOR (1
DATA OUTLET FOR ANTENNA. PROVIDE A COMPLETE
DATA OUTLET WITH FACEPLATE ABOVE CEILING,
MOUNTED AT AN ACCESSIBLE HEIGHT NO MORE THAN
24" ABOVE CEILING. AT EACH OUTLET, PROVIDE A 20'
COIL OF CABLE AHEAD OF THE OUTLET FOR
ADJUSTMENT OF FINAL OUTLET LOCATION. THE
CONTRACTOR SHALL COORDINATE EXACT LOCATIONS
WITH THE OWNER AND ADJUST OUTLET LOCATIONS AT
SUBSTANTIAL COMPLETION TO ACCOMMODATE
OWNER'S WAP LOCATIONS. WAP'S ARE OWNER-
FURNISHED, OWNER-INSTALLED
WAP
HD
SOUND MASKING LOUDSPEAKER
BASIS OF DESIGN: BIAMP Qt ACTIVE EMITTER SM
DOOR HARDWARE POWER SUPPLY 46" PWR
T
AUDIO/VISUAL SYSTEM OUTLET, REFER TO
ASSOCIATED DETAIL 4/E303 FOR ADDITIONAL
INFORMATION
J
HDMI OUTLET, REFER TO ASSOCIATED DETAIL 11/E303
FOR ADDITIONAL INFORMATION HDMI
ROOM SCHEDULER
RS
60"
SAME AS "RS" EXCEPT MULLION MOUNTED
RS
60" M
2-GANG DEEP FLOORBOX, POWER ONLY
BASIS OF DESIGN: HUBBELL FB4233
FLOOR
D A
T E
R E
V
IS
IO
N
S
CHECKED BY
DRAWN BY
DATE
SCALE
S H E E T
T
IT
L E
P R O J E C T
N A M E
O W N E R
L O C A T
IO
N
S C O
P R O J E C T
N U M B E R
P R O J E C T
N U M B E R
-2
-0
A
.0
M
O N
R O
E N
O R
T H
C A
R O
L
IN
A
S O
U T
H P
IE
D
M O
N T
C O
M M
U N
IT
Y
C O
L L E
G E
C E
N T
E R
F O
R E
N T
R E
P R
E N
E U
R S
H
IP
AS NOTED
FOR
CONSTRUCTION
NC LICENSE C-0503 CMTA #223.089
LEAD DESIGN PROFESSIONAL
LARRY B. SMITH, JR., P.E.
L.B. SMITH AND ASSOCIATE, P.A.
(704) 289-5168 lbsjr@lbsmithpa.com
N
S
EHP BORE.
043650
E Y
E
T
SEAL
HTRON
ORAC
ANLI
E
EENIGN R
RP
OISSEFO LAN
E L E
C T
R
IC
A L L
E G
E N
D A
N D
N O
T E
S
FEB. 26, 2025
JCT
SER
E-001
10/17/2025
GENERAL NOTES (LEGEND):
A. EACH CONTRACTOR, PROPOSER, SUPPLIER AND/OR MANUFACTURER SHALL REFER TO ALL DOCUMENTS PERTAINING TO THIS PROJECT AND COORDINATE ACCORDINGLY SO AS TO ENSURE ADEQUACY OF FIT, COMPLIANCE WITH SPECIFICATIONS, PROPER VOLTAGE AND CURRENT CHARACTERISTICS TO AVOID CONFLICT
WITH ANY OTHER BUILDINGS SYSTEMS. VERIFY SAME WITH SHOP DRAWINGS.
B. ADDITIONAL ELECTRICAL REQUIREMENTS MAY BE SHOWN ON PLANS FROM OTHER DISCIPLINES IN THIS SET. IT IS THE CONTRACTOR’S RESPONSIBILITY TO REVIEW ALL PLANS AND SPECIFICATIONS FOR A COMPLETE
UNDERSTANDING OF THE PROJECT REQUIREMENTS.
C. WORK SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF ALL LOCAL, STATE, AND NATIONAL CODES.
INCLUDING BUT NOT LIMITED TO NFPA 70 (NEC), NFPA 72, INTERNATIONAL BUILDING CODES, ETC. IN ADDITION, OBSERVE ALL APPLICABLE RULES AND REGULATIONS THAT MAY APPLY TO THE WORK UNDER THIS CONTRACT FROM CITY, COUNTY, LOCAL, STATE, FEDERAL, MUNICIPALITY, UTILITY COMPANY, OSHA, ETC.
D. CONTRACTOR SHALL FOLLOW SEISMIC RESTRAINT AND DESIGN REQUIREMENTS CONTAINED IN LATEST ADOPTED STATE AND INTERNATIONAL BUILDING CODES, WITH ALL AMENDMENTS AS ADOPTED BY THE CURRENT LEGISLATION. REFER TO ELECTRICAL AND STRUCTURAL SPECIFICATIONS FOR ADDITIONAL INFORMATION.
E. ADVISE THE ENGINEER OF ANY CONFLICTS, ERRORS, OMISSIONS, ETC. AT LEAST TEN DAYS PRIOR TO BID DATE, TO
ALLOW CLARIFICATION BY WRITTEN ADDENDUM.
F. WHERE CONFLICTS ARE FOUND BETWEEN DRAWINGS, DETAILS, OR SPECIFICATIONS, THE MORE STRINGENT
REQUIREMENT SHALL APPLY. NOTIFY ARCHITECT OF DISCREPANCY IN WRITING.
G. DEVIATION FROM SPECIFICATIONS OR PLANS REQUIRES PRIOR WRITTEN APPROVAL FROM THE ENGINEERS AND
MUST BE SUBMITTED IN WRITING NO LATER THAN TEN DAYS PRIOR TO THE BID DATE.
H. ALL ELECTRICAL COMPONENTS OR EQUIPMENT SHALL BE LISTED AND LABELED BY UNDERWRITER'S LABORATORIES OR OTHER APPROVED LISTING AGENCY. APPROVAL AND LABELING OF INDIVIDUAL COMPONENTS ON AN ASSEMBLY IS NOT ACCEPTABLE AS MEETING THIS REQUIREMENT, UNLESS WAIVED BY THE ENGINEER IN
WRITING.
I. ALL MATERIALS FURNISHED AND ALL WORK INSTALLED SHALL COMPLY WITH THE CURRENT EDITION OF THE NATIONAL ELECTRICAL CODES, NATIONAL FIRE CODES OF THE NATIONAL FIRE PROTECTION ASSOCIATION, THE REQUIREMENTS OF LOCAL UTILITY COMPANIES, AND WITH THE REQUIREMENTS OF ALL GOVERNMENTAL AGENCIES OR DEPARTMENTS HAVING JURISDICTION. IF ANY CONFLICTS OR DISCREPANCIES OCCUR THE MOST STRINGENT
SHALL APPLY.
J. MOUNTING HEIGHTS FOR WALL MOUNTED DEVICES INDICATED ABOVE FINISHED FLOOR ARE TO CENTER OF DEVICE UNO. MOUNTING HEIGHTS TO CEILING SUSPENDED DEVICES ARE TO BOTTOM OF DEVICE UNO. WHERE MOUNTING HEIGHTS ARE NOT INDICATED OR ARE IN CONFLICT WITH ANY OTHER BUILDING SYSTEM, CONTACT THE ENGINEER BEFORE AFFECTING INSTALLATION. REFER ALSO TO ARCHITECTURAL INTERIOR AND EXTERIOR ELEVATIONS, CEILING HEIGHTS AND OTHER DETAILS OF THESE DOCUMENTS, AS APPLICABLE.
K. DO NOT SCALE FROM DRAWINGS, AS PRINTING DISTORTS SCALE. WORK SHALL BE LAID OUT FROM DIMENSIONED
DRAWINGS, OR DIMENSIONS SUPPLIED TO THE CONTRACTOR.
L. REFER TO ARCHITECTURAL WALL ELEVATIONS (WHERE GIVEN) FOR HEIGHTS AND MOUNTING RELATIONSHIP OF OUTLETS AND FURNITURE, CASEWORK, AND/OR EQUIPMENT. ADDITIONAL OUTLETS MAY BE SHOWN ON
ARCHITECTURAL DRAWINGS AND SHALL BE INCLUDED IN THE CONTRACT.
M. FLUSH OR PEDESTAL TYPE FLOOR OUTLETS/BOXES, AS INDICATED ON PLAN, SHALL BE LOCATED BY DIMENSIONS PROVIDED BY THE ARCHITECT, UNLESS OTHERWISE SHOWN ON PLANS. IF IN DOUBT, CONTACT THE ENGINEER
PRIOR TO ROUGHING-IN ANY WORK.
N. INSTALL EQUIPMENT, MATERIALS, ETC. IN STRICT ACCORDANCE WITH MANUFACTURER’S RECOMMENDATIONS AND DIRECTIONS. IF IN CONFLICT WITH THE DESIGN INDICATED IN CONTRACT DOCUMENTS, ADVISE THE ENGINEER
PRIOR TO INSTALLATION FOR CLARIFICATION.
O. THE CONSTRUCTION MANAGER, GENERAL CONTRACTOR, OR WHOMEVER HOLDS THE PRIME CONTRACT(S) FOR THIS CONSTRUCTION IS RESPONSIBLE FOR THE COORDINATION, APPEARANCE, SCHEDULING AND TIMELINESS OF THE WORK OF ALL TRADES, CONTRACTORS, SUPPLIERS, INSTALLERS, ETC. POOR OR UNTIMELY WORK ON THE PART OF ANY SUBCONTRACTOR SHALL BE RESOLVED BY THE PARTY WHO ENGAGED THEM ON THIS PROJECT.
P. THE PURPOSE AND INTENT OF ALL OF THE DOCUMENTS PERTAINING TO THIS PROJECT IS TO PROVIDE A COMPLETE, FUNCTIONAL, SAFE, LIKE-NEW FACILITY. ANYTHING LESS SHALL BE UNACCEPTABLE.
Q. ALL SYSTEMS, EQUIPMENT AND MATERIALS ARE TO BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER. WORK NOT MEETING THIS CRITERION SHALL BE REMOVED AND REINSTALLED SATISFACTORILY. FINAL DETERMINATION OF
THE ACCEPTABILITY OF THE QUALITY OF WORK RESIDES WITH THE ENGINEER
R. ALL WORK, MATERIALS, EQUIPMENT, ETC. SHALL BE FULLY GUARANTEED FOR ONE FULL CALENDAR YEAR FROM THE DATE OF SUBSTANTIAL COMPLETION AS DOCUMENTED BY THE ENGINEER, UNLESS LONGER WARRANTY
PERIODS FOR EQUIPMENT ARE SPECIFIED.
S. ALL WORK SHALL BE CONCEALED UNLESS SPECIFICALLY INDICATED TO BE EXPOSED, OR REQUIRED TO BE EXPOSED. IF IN DOUBT, CONTACT THE ENGINEER FOR CLARIFICATIONS PRIOR TO INSTALLING ANY SUCH WORK.
T. UNLESS OTHERWISE SPECIFIED OR INDICATED, ALL EQUIPMENT AND/OR MATERIALS WITHIN OCCUPIED SPACES OR EXPOSED TO VIEW ON THE BUILDING EXTERIOR SHALL BE PRIMED AND FINISHED SO AS TO COMPLEMENT ADJACENT SURFACE, UNLESS OTHERWISE NOTED. COORDINATE WORK AND COLORS WITH ARCHITECT.
U. WHERE PENETRATING ROOFING MEMBRANE OR OTHER MATERIALS USED FOR WEATHERPROOFING THE BUILDING, MAKE SUCH PENETRATION IN A WAY THAT WILL NOT VOID OR DIMINISH THE ROOFING WARRANTY OR INTEGRITY IN ANYWAY. COORDINATE ALL SUCH PENETRATIONS WITH THE ROOFING MANUFACTURER AND ARCHITECT.
V. CEILING-MOUNTED ELECTRICAL DEVICES SHALL BE CENTERED IN 2'X2' CEILING TILE AND INSTALLED CENTERED ON
2' DIMENSION OF 2'X4' TILE AND ON CENTERLINE OR A QUARTER POINT ON 4' DIMENSION.
W. PROVIDE DETAILED SHOP DRAWINGS TO ENGINEER PRIOR TO PURCHASING OR INSTALLING ANY EQUIPMENT DEVIATIONS IN SIZES, CAPACITIES, FIT, FINISH, ETC. FOR EQUIPMENT FROM THAT PRIME SPECIFIED SHALL BE THE RESPONSIBILITY OF THE PURCHASER OF THAT EQUIPMENT. ANY PROVISIONS REQUIRED TO ACCOMMODATE A DEVIATION, WHETHER APPROVED BY THE ENGINEER OR NOT, SHALL BE THE RESPONSIBILITY OF THE PURCHASER.
X. WHERE FIRE-RATED CEILING ASSEMBLIES ARE NOTED, PROVIDE UL-LISTED FIRE-RATED GYPSUM BOARD OR PRE- MANUFACTURED ENCLOSURES ABOVE LUMINAIRES, CEILING DEVICES, ETC. IN OR ON CEILING, AS REQUIRED TO
MAINTAIN CEILING RATINGS.
Y. DO NOT RECESS PANELBOARD TUBS OR OTHER FLUSH-MOUNTED EQUIPMENT IN WALLS THAT HAVE A FIRE
RATING. NO INSTALLATION SHALL DIMINISH OR VOID FIRE RESISTIVE RATINGS IN ANYWAY.
Z. COORDINATE THE LOCATION OF DRAINS, ELECTRICAL OUTLETS, GAS OUTLETS, ETC. WITH ALL CASEWORK, KITCHEN EQUIPMENT, MECHANICAL ROOM EQUIPMENT, ETC. PRIOR TO COMMENCING INSTALLATION. WORK NOT SO COORDINATED SHALL BE REMOVED AND PROPERLY INSTALLED AT THE EXPENSE OF THE RESPONSIBLE
CONTRACTOR(S).
AA. ALL OFFSETS, TURNS, FITTINGS, TRIM, DETAIL, ETC. MAY NOT BE INDICATED, BUT SHALL BE PROVIDED AS REQUIRED. ADDITIONAL ALLOWANCES SHALL BE INCLUDED FOR SAME AT EACH PROPOSER’S DISCRETION.
BB. INSTALL NO PIPING, CONDUIT, DUCTWORK, ETC. IN A LOCATION OR IN A MANNER WHICH WILL ALLOW FREEZING OR
THE COLLECTION OF CONDENSATION THEREON. IF IN DOUBT, CONTACT THE ENGINEER.
CC. ALL WIRING SYSTEMS SHALL BE INSTALLED WITH A MINIMUM OF SPLICES. CONDUCTORS, WHETHER SINGLE OR MULTI-PAIR, SHALL BE INSTALLED CONTINUOUS INSOFAR AS POSSIBLE FROM TERMINAL POINT TO TERMINAL POINT.
DD. NO CONDUIT, SUPPORTS, ETC. SHALL BE RUN THROUGH ACCESS CLEARANCES OF EQUIPMENT BY OTHER TRADES
(I.E. VAV BOXES). COORDINATE WITH ALL TRADES PRIOR TO CONSTRUCTION.
EE. ALL SUPPORTS FOR EQUIPMENT, DEVICES OR FIXTURES SHALL BE UNIQUE, DIRECTLY FROM THE BUILDING STRUCTURE. DO NOT SUPPORT WORK FROM OTHER TRADES EQUIPMENT OR SUPPORTS WITHOUT WRITTEN
PERMISSION FROM THE ENGINEER AND CONSENT OF THE OTHER TRADE, IN WRITING.
FF. WHERE BACKBOXES ARE LOCATED IN THE SAME VERTICAL CHANNEL/STUD SPACE ON OPPOSITE SIDES OF THE SAME WALL, PROVIDE SOUND-INSULATING PUTTY AROUND BOXES AS REQUIRED TO ELIMINATE SOUND
TRANSMISSION FROM ROOM TO ROOM.
GG. JUNCTION BOXES LOCATED ABOVE ACCESSIBLE CEILINGS SHALL BE LOCATED NO MORE THAN 36” ABOVE CEILING LEVEL. LABEL EACH BOX IN AREA OF WORK WITH A PERMANENT MARKER OR IN ACCORDANCE WITH
SPECIFICATIONS, WHICHEVER IS MORE STRINGENT.
HH. ANY VIBRATING, OSCILLATING OR OTHER NOISE OR MOTION PRODUCING EQUIPMENT SHALL BE ISOLATED FROM SURROUNDING SYSTEMS IN AN APPROVED MANNER. NOISY OR STRUCTURALLY DAMAGING INSTALLATIONS SHALL BE SATISFACTORILY REPLACED OR REPAIRED AT THE INSTALLING CONTRACTORS' EXPENSE. THE FINAL DECISION ON THE SUITABILITY OF A PARTICULAR INSTALLATION'S ACCEPTABILITY SHALL BE THAT OF THE ENGINEER.
II. CHECK ALL THREE PHASE MOTORS WITH A PHASE ROTATION METER, PRIOR TO PLACING IN SERVICE.
JJ. ALL ITEMS HAVING KEYED LOCKS/OPERATORS SHALL HAVE CORED LOCKS/OPERATORS. ALL KEYING SHALL MATCH THE OWNER'S EXISTING KEY-WAYS. COORDINATE EXACT REQUIREMENTS WITH OWNER PRIOR TO CONSTRUCTION.
KK. NOISY WORK, WORK OUTSIDE CONSTRUCTION BARRIERS, WORK IN OCCUPIED AREAS, ETC. SHALL BE PERFORMED AFTER HOURS OR ON WEEKENDS. COORDINATE EXACT SCHEDULING WITH FACILITY PRIOR TO CONSTRUCTION.
LL. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING REQUIRED FOR HIS WORK. ALL CUTTING AND PATCHING SHALL BE IN ACCORDANCE WITH THE ARCHITECT'S STANDARDS FOR SUCH WORK.
MM. THE CONTRACTOR IS RESPONSIBLE FOR ALL UTILITY COMPANY FEES, CASH CONTRIBUTIONS OR OTHER COSTS THAT THE UTILITY COMPANY MAY REQUIRE TO COMPLETE THEIR WORK. (ELECTRIC, TELEPHONE, TELEVISION, DATA, ETC.).
NN. ALL CONTRACTORS SHALL EXERCISE EXTREME CARE IN THE COURSE OF THEIR WORK SO AS TO ENSURE THAT THEY DO NOT INTERRUPT ANY EXISTING SERVICE OR SUB-SERVICE FOR SAFETY PURPOSES. PAY PARTICULAR ATTENTION TO THIS PRECAUTION RELATIVE TO NATURAL GAS AND ELECTRICAL LINES. VERIFY THE LOCATION, SIZE, TYPE, ETC. OF EACH UNDERGROUND OR OVERHEAD UTILITY. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH ALL FEDERAL, STATE AND/OR LOCAL RULES, REGULATIONS, STANDARD AND SAFETY REQUIREMENTS.
UTILITIES SHALL BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE MUNICIPALITY OR UTILITY COMPANY
STANDARDS. IN ALL CASES, THE MOST STRINGENT REQUIREMENT SHALL APPLY.
OO. INTERRUPTION OF ANY EXISTING SERVICES SHALL BE COORDINATED WITH THE OWNER, GENERAL CONTRACTOR, UTILITY COMPANY AS NECESSARY, AND THE ARCHITECT, AT LEAST TWO WEEKS IN ADVANCE OF ANTICIPATED INTERRUPTION. A SCHEDULE FOR THESE OUTAGES SHALL BE DEVELOPED AND AGREED UPON BETWEEN THE PARTIES MENTIONED TO AVOID UNNECESSARY INCONVENIENCE TO THE OWNER OR ANY AFFECTED PARTY. NOTIFY THE UTILITY COMPANY OF ANY ANTICIPATED SERVICES REQUIRED TWO WEEKS IN ADVANCE, IN WRITING. IF UTILITY
COMPANY REQUIRES A LONGER NOTIFICATION PERIOD, SO PROVIDE.
PP. WHERE INTERRUPTING AN EXISTING UTILITY OR SERVICE DELIBERATELY OR ACCIDENTALLY, THE RESPONSIBLE CONTRACTOR SHALL WORK CONTINUOUSLY AS NEEDED TO RESTORE SAME, PROVIDING PREMIUM TIME AS
NEEDED.
QQ. AS APPLICABLE, REFER TO ARCHITECTURAL PHASING PLANS AND PHASING BOUNDARIES ON THESE DRAWINGS FOR SEQUENCING OF WORK, FULL EXTENT OF AREAS INVOLVED, EXTENT OF CEILING WORK, ETC. PROVIDE TEMPORARY CONNECTIONS FOR CIRCUITS AND WORK AS REQUIRED TO MAINTAIN SEQUENCE OF THE WORK FROM PHASE TO PHASE. PROVIDE ALL REQUIRED INCREMENTAL INSPECTIONS, CERTIFICATIONS, ETC. AND ALL
TEMPORARY SERVICES AS REQUIRED BY OWNER TO ACCOMPLISH THE PHASING PLAN.
NO SCALE
ELECTRICAL LEGEND
ELECTRICAL SHEET LIST
Sheet Number Sheet Name
E-001 ELECTRICAL LEGEND AND NOTES
E-002 LUMINAIRE SCHEDULE
E-100 ELECTRICAL SITE PLAN
E-101A FLOOR PLAN - FIRST FLOOR - AREA A - POWER
E-101B FLOOR PLAN - FIRST FLOOR - AREA B - POWER
E-102A FLOOR PLAN - SECOND FLOOR - AREA A - POWER
E-102B FLOOR PLAN - SECOND FLOOR - AREA B - POWER
E-103A FLOOR PLAN - HIGH ROOF - AREA A - POWER
E-111A FLOOR PLAN - FIRST FLOOR - AREA A - FIRE ALARM
E-111B FLOOR PLAN - FIRST FLOOR - AREA B - FIRE ALARM
E-112A FLOOR PLAN - SECOND FLOOR - AREA A - FIRE ALARM
E-112B FLOOR PLAN - SECOND FLOOR - AREA B - FIRE ALARM
E-121A FLOOR PLAN - FIRST FLOOR - AREA A - DATA NETWORKS
E-121B FLOOR PLAN - FIRST FLOOR - AREA B - DATA NETWORKS
E-122A FLOOR PLAN - SECOND FLOOR - AREA A - DATA NETWORKS
E-131A FLOOR PLAN - FIRST FLOOR - AREA A - SECURITY
E-131B FLOOR PLAN - FIRST FLOOR - AREA B - SECURITY
E-132A FLOOR PLAN - SECOND FLOOR - AREA A - SECURITY
E-132B FLOOR PLAN - SECOND FLOOR - AREA B - SECURITY
E-141A FLOOR PLAN - FIRST FLOOR - AREA A - SOUND MASKING
E-141B FLOOR PLAN - FIRST FLOOR - AREA B - SOUND MASKING
E-142A FLOOR PLAN - SECOND FLOOR - AREA A - SOUND MASKING
E-142B FLOOR PLAN - FIRST FLOOR - AREA B - SOUND MASKING
E-151A FLOOR PLAN - FIRST FLOOR - AREA A - LIGHTING
E-151B FLOOR PLAN - FIRST FLOOR - AREA B - LIGHTING
E-152A FLOOR PLAN - SECOND FLOOR - AREA A - LIGHTING
E-152B FLOOR PLAN - SECOND FLOOR - AREA B - LIGHTING
E-153 FIRST FLOOR PLAN - LIGHTING CONTROL ZONES
E-154 SECOND FLOOR PLAN - LIGHTING CONTROL ZONES
E-161 FLOOR PLAN - FIRST FLOOR - INTERCONNECTION
E-162 FLOOR PLAN - SECOND FLOOR - INTERCONNECTION
E-201 ENLARGED PLANS
E-301 POWER RISER DIAGRAM
E-302 DETAILS AND DIAGRAMS
E-303 DETAILS AND DIAGRAMS
E-304 DETAILS AND DIAGRAMS
E-305 DETAILS AND DIAGRAMS
E-306 TELECOM DETAILS AND DIAGRAMS
E-307 TELECOM DETAILS AND DIAGRAMS
E-308 TELECOM DETAILS AND DIAGRAMS
E-309 TELECOM DETAILS AND DIAGRAMS
E-310 AV BLOCK DIAGRAMS
E-311 AV BLOCK DIAGRAMS
E-312 AV BLOCK DIAGRAMS
E-313 AV EQUIPMENT LISTS
E-401 ELECTRICAL EQUIPMENT SCHEDULES
E-402 ELECTRICAL EQUIPMENT SCHEDULES
/1
/2
A V
F L
O O
R B
O X
R E
V
IS
IO
N
S
/1
/2
A S
I
120V LIGHTING
BRANCH CIRCUIT
POWER
1/2'' EMT
PROVIDE NEMA-1 ENCLOSURE
ABOVE CEILING FOR LOW
VOLTAGE POWER SUPPLY.
MOUNT ENCLOSURE TO WALL
ABOVE LAY-IN CEILING.
LED LIGHT STRIP.
NOTCH BOTTOM OF
CABINET FRAME AS
REQUIRED FOR
CONTINUOUS RUNS.
PROVIDE GROMMET FOR
24V WIRING AT WALL
PENETRATION.
SECURELY FASTEN LED STRIP TO
BOTTOM OF CABINET WITH 3M
ADHESIVE. ALSO PROVIDE PLASTIC
MOUNTING CLIPS EVERY 6'' ON CENTER.
24V WIRING
SUPPORTED
FROM CABINET
NOTES
A. PROVIDE LED STRIPS WITH ALL 24V FITTINGS REQUIRED.
B. LOW VOLTAGE POWER SUPPLY SHALL REQUIRE 120V HARDWIRED CONNECTION.
C. PROVIDE LINE VOLTAGE VACANCY SENSOR SWITCH FOR TYPE ''UC'' LIGHTING.
VACANCY
SENSOR
SWITCH
($VS)
UPPER
CABINET
LOWER
CABINET
UPPER
CABINET
WIRE
STRAP
D A
T E
R E
V
IS
IO
N
S
CHECKED BY
DRAWN BY
DATE
SCALE
S H E E T
T
IT
L E
P R O J E C T
N A M E
O W N E R
L O C A T
IO
N
S C O
P R O J E C T
N U M B E R
P R O J E C T
N U M B E R
-2
-0
A
.0
M
O N
R O
E N
O R
T H
C A
R O
L
IN
A
S O
U T
H P
IE
D
M O
N T
C O
M M
U N
IT
Y
C O
L L E
G E
C E
N T
E R
F O
R E
N T
R E
P R
E N
E U
R S
H
IP
AS NOTED
FOR
CONSTRUCTION
NC LICENSE C-0503 CMTA #223.089
LEAD DESIGN PROFESSIONAL
LARRY B. SMITH, JR., P.E.
L.B. SMITH AND ASSOCIATE, P.A.
(704) 289-5168 lbsjr@lbsmithpa.com
N
S
EHP BORE.
043650
E Y
E
T
SEAL
HTRON
ORAC
ANLI
E
EENIGN R
RP
OISSEFO LAN
L U
M
IN
A
IR
E S
C H
E D
U L E
FEB. 26, 2025
JCT
SER
E-002
10/17/2025
LUMINAIRE SCHEDULE
TYPE DESCRIPTION BASIS OF DESIGN EQUAL MANUFACTURERS MOUNTING LAMPS / CCT
MINIMUM
LUMENS
MAXIMUM
WATTAGE VOLTAGE REMARKS
EMC RECESSED CONCEALED HEAD LED EMERGENCY
BATTERY LIGHT, FLUSH DOOR, WHITE FINISH
CONCEALITE F5 LED8 90 SD EMERGI-LITE,
LIGHTALARMS, DUAL-LITE
CEILING LED 30 277
EMP PENDANT MOUNT CONCEALED HEAD LED
EMERGENCY BATTERY LIGHT, SURFACE HOUSING
CONCEALITE F5 LED8 90 SD SM CF EMERGI-LITE,
LIGHTALARMS, DUAL-LITE
PENDANT LED 30 277 HOUSING COLOR TO BE SELECTED BY
ARCHITECT.
EMW WALL MOUNT LED EMERGENCY BATTERY
LIGHTING UNIT
LITHONIA ELM4L (COLOR) UVOLT LTP EMERGI-LITE,
LIGHTALARMS, DUAL-LITE
WALL LED 640 11 277
L1 LINEAR LED DIRECT / INDIRECT LIGHT, NOMINAL
1.9" W x 4" H x 72" L, FLUSH OPAL ACRYLIC LENS, WHITE FINISH
CORONET #LS1
UPDN-6'-0"-35-HIGH-UNV-DB-W-ACTB15-FL-NA-NA-ST
D
ACUITY, ZUMTOBEL,
NEO-RAY, FINELITE
CEILING
SUSPENDED
LED 3500K 7292 45 277 AIRCRAFT CABLE SUSPENSION
L2 RECESSED ROUND OPEN DOWNLIGHT, 6"
APERTURE, 0-10V DIMMING TO 10%
LITHONIA LDN6 35/20 L06 AR LSS TRW MVOLT GZ10 COOPER, CURRENT-HLI,
SIGNIFY
CEILING LED 3500K 2000 22 277
L2E SAME AS TYPE 'L2' WITH BACKUP BATTERY AND
EMERGENCY TRANSFER RELAY.
LITHONIA LDN6 35/20 L06 AR LSS TRW MVOLT GZ10
E10WCP
COOPER, CURRENT-HLI,
SIGNIFY
CEILING LED 3500K 2000 22 277
L3 CYLINDER DOWNLIGHT, 4" APERTURE, 0-10V
DIMMING TO <1%
LITHONIA LDN4CYL 35/20 L04 AR LSS MVOLT EZ1
ACC DWHG
COOPER, CURRENT-HLI,
SIGNIFY
CEILING
SUSPENDED
LED 3500K 2000 22 277
L4 LED STRIP, 4' LONG, ROUNDED ACRYLIC LENS,
WHITE HOUSING
WILLIAMS 75R-4-L50/835-VBY-2-DRV-UNV COOPER, CURRENT-HLI,
SIGNIFY
CHAIN HUNG LED 3500K 4867 33 277
L5 WALL MOUNTED LED SCONCE, DIMMABLE TRIAC ESTILUZ A-3722 TANGO NOON WALL, VIBIA
WALL LED 2700K 850 10 120 COLOR TO BE SELECTED BY ARCHITECT
L6 WALL MOUNTED LED DIRECT/INDIRECT SCONCE. OCL FR1-S1SC-13-WF-BKP-2LED1/35K-UNV-DM0 DELTALIGHT VISION, WALL LED 3500K 2750 35 277
L7 RECESSED LINEAR LED, 1.5" APERTURE WIDTH,
TRIMLESS, FLUSH LENS
CORONET
#LSR1-4-35-HIGH-UNV-DB-W-NT-FL-NA-NA-NA
ACUITY, NEO-RAY, ALCON RECESSED LED 3500K 3752 30 277
L9 ASYMMETRIC LED COVE LIGHT. STANDARD
UPLIGHT DIFFUSER. INSTALL IN PRE-BUILT COVE.
CORONET
EZ-C-VARIES-35-LOW-UNV-DB.1%-W-COVE-SD-NA-N
A-NA
LITECONTROL, ELLIPTIPAR,
IO
SURFACE -
COVE
LED 3500K 400/FT <varies> 277 WITH REMOTE DRIVERS, 0-10V DIMMABLE TO <1%
L10 2' x 4' LAY-IN VOLUMETRIC LED LUMINAIRE, WHITE
TRIM, CENTER BASKET SQUARE RIBBED ACRYLIC
DIFFUSER
LITHONIA 2BLT4 RB 60L SDP MVOLT GZ1 LP835 WH COOPER, CURRENT-HLI,
SIGNIFY
LAY-IN LED 3500K 6083 47 277
L11 RECESSED LINEAR LED, 3.5" APERTURE WIDTH,
DROPPED REVEAL LENS
ALW
LP3.5RTDL-TGRID-S6-HI/90/3500K-V01-EXT-N-COLOR
-UNV
ACUITY, NEO-RAY, ALCON RECESSED LED 3500K 6600 76 277
L12 RECESSED 3-HEAD MULTIPLE ADJUSTABLE LED
DOWNLIGHT, MEDIUM DISTRIBUTION, WHITE
FINISH, SOFTENING LENS.
3G LIGHTING
3G-RC3-3000-H90-35K-40D-UNV-D01-WT-WG-WH-NC-
SF
EUROFASE, CSL RECESSED LED 3500K 7431 94 277
L15 ILLUMINATED SCONCE WITH CUSTOM LASER CUT
SIGNAGE, DIMMABLE TRIAC. MOUNT 72" AFF TO
CENTER OF GLOBE.
ESTILUZ A-3720-26 BLK-LASER CUT SIGNAGE OXYGEN, LIGHTOLOGY WALL LED 2700K 870 12 120 CUSTOM SIGNAGE - DETERMINED DURING
SUBMITTAL REVIEW - ROOM NAME AND
NUMBER
L16 SUSPENDED LED LINEAR DIRECT/INDIRECT, 12'
LONG
ALW
LP2UUS-S12-HI/80/3500K-V01-EXT/R-LOW/80/3500K-V
01-EXT/R-SW-UNV
ACUITY, NEO-RAY, FINELITE CEILING
SUSPENDED
LED 3500K 23040 85 277 AIRCRAFT CABLE SUSPENSION
L17 SUSPENDED LINEAR LED DIRECT/INDIRECT
MODULAR LUMINAIRE ASSEMBLY WITH CURVED
CORNER SECTIONS, OPAL ACRYLIC LENSES.
DELRAY DOS CURVE SERIES HAFELE, CEILING
SUSPENDED
LED 3500K 866/FT <varies> 277 AIRCRAFT CABLE SUSPENSION. HOUSING
COLOR TO BE SELECTED BY ARCHITECT.
L18 PENDANT-MOUNTED LINEAR LED, MULTI-CELL,
1.25" APERTURE WIDTH, BLACK HOUSING, MATTE
SILVER BEVEL, CANOPY MOUNTED DRIVER
USAI MPD08-27H1-35KS-50-BL-SM-PD3-UNV-D6E &
PXC-95-BL
CORONET PENDANT LED 3500K 1914 27 277 8-CELLS, 50-DEGREE BEAM. SUSPEND FLUSH
WITH BOTTOM OF WOOD CEILING.
L20 LED WALL LIGHT, DIRECT/INDIRECT, 2' LONG.
MOUNT OVER MIRROR.
WILLIAMS
WMAUD-2-L20/835U/L20/835D-AF-DIMU/DIMD-UNV
COOPER, CURRENT-HLI,
SIGNIFY
WALL LED 3500K 3868 33 277
L24 WALL-MOUNTED ENCLOSED AND GASKETED LED
LUMINAIRE, FROSTED ACRYLIC LENS, FIBERGLASS
HOUSING
WILLIAMS 96-4-L40/835-HAFR-DRV-UNV COOPER, CURRENT-HLI,
SIGNIFY
WALL LED 3500K 4000 30 277
L25 2' x 4' LAY-IN FLAT PANEL LED LUMINAIRE, WHITE
TRIM
LITHONIA CPX 2X4 AL08 SWW7 M2 COOPER, CURRENT-HLI,
SIGNIFY
LAY-IN LED 3500K 6048 51 277 RATED NSF/ANSI STANDARD 2.
L26 WALL-MOUNTED OUTDOOR LED WALLPACK, CAST
ALUMINUM HOUSING, GLASS LENS
LITHONIA TWX2 LED P1 40K MVOLT COLOR COOPER, CURRENT-HLI,
SIGNIFY
WALL LED 4000K 3250 23 277 HOUSING COLOR TO BE SELECTED BY
ARCHITECT.
L27 WALL OR MULLION-MOUNTED OUTDOOR LED
EMERGENCY EGRESS LUMINAIRE, INTEGRAL
EMERGENCY BATTERY PACK, BUTTON
PHOTOCELL
LUMINAIRE LED BLD 24IN NODIM 20W 40K 277 DP
(COLOR) EMB310 PC
MULE, SIGNTEX WALL OR
MULLION
LED 4000K 2006 23 277 HOUSING COLOR TO BE SELECTED BY
ARCHITECT.
L28 OUTDOOR LED CYLINDER DOWNLIGHT, 6"
APERTURE
METEOR ASII6-40-358-UNV-STV-60-XXX-STD-ST2 COOPER, CURRENT-HLI,
SIGNIFY
CEILING
PENDANT
LED 3500K 5155 44 277 3/8" PENDANT STEM. HOUSING COLOR TO BE
SELECTED BY ARCHITECT.
L29 WALL-MOUNTED OUTDOOR LED LUMINAIRE,
VANDAL RESISTANT, FULL CUTOFF
LUMINAIRE LED BLD 24IN MIN1 20W 40K 277 DP
(COLOR)
MULE, SIGNTEX WALL LED 4000K 2006 23 277 HOUSING COLOR TO BE SELECTED BY
ARCHITECT. MATCH TYPE L27.
OL2 POLE-ARM-MOUNTED LED AREA LIGHT, 25-FOOT
POLE, IES TYPE 4 WIDE CUTOFF DISTRIBUTION,
WITH TWO LUMINAIRES MOUNTED 180 DEGREES
APART.
BEACON VP-2-320L-185-4K8-4W-UNV-A-COLOR;
POLE: AAL SSA-A-25-50-B-2-B3-COLOR
ACUITY, COOPER, PHILIPS POLE LED 4000K 27000 x2 370 277 HOUSING AND POLE COLOR TO BE SELECTED
BY ARCHITECT. PROVIDE CONCRETE POLE
BASE PER DETAIL.
OL3 VANDAL RESISTANT LED BOLLARD LIGHT, FLAT
TOP CYLINDER, 42" TALL, EXTERNAL LOUVERS.
KIM VRB3/20L4KUV/(COLOR) ACUITY, COOPER, PHILIPS CONCRETE
BASE
LED 4000K 1005 25 277 FINISH COLOR TO BE SELECTED BY
ARCHITECT.
OL4 FLUSH IN GRADE LED WALLWASHER UPLIGHT.
ALUMINUM TRIM, FLAT, CLEAR TEMPERED GLASS
LENS.
HYDREL IGF6 A LED P1 80CRI 40K MVOLT WWD 0T
FLC 34B ZT DNA
CURRENT, COOPER INGRADE LED 4000K 1154 17 277
OL5 GROUND MOUNTED LED FLOODLIGHT, WIDE
FLOOD RECTANGULAR (6X5) BEAM SPREAD,
VANDAL GUARD, DARK BRONZE FINISH, INTEGRAL
SLIPFITTER, TENON BASE MOUNT
LITHONIA DSXF1 LED P1 40K WFR MVOLT IS VG
DDBXD & AFTM DDBXD
COOPER, CURRENT-HLI,
SIGNIFY
CONCRETE
BASE
LED 4000K 3089 22 277
UC UNDERCABINET LED STRIP WITH MOUNTING
CHANNEL AND DIFFUSING LENS. SEE DETAIL.
PROLUME RIA-##H-835-F115 MOSS, LUMINII, Q-TRAN UNDER
CABINET
LED 3500K 136/FT 18 120 REMOTE MOUNTED POWER SUPPLY
X1 LED EXIT SIGN, EDGE LIT RED LETTERS, SINGLE
FACE, CLEAR PANEL, BRUSHED ALUMINUM
RECESSED HOUSING
LITHONIA EDGR 1 R EL SURE-LITES, EMERGI-LITE,
DUAL-LITE
UNIVERSAL LED PER CODE 5 277
X2 LED EXIT SIGN, EDGE LIT RED LETTERS, DOUBLE
FACE, MIRROR PANEL, BRUSHED ALUMINUM
RECESSED HOUSING
LITHONIA EDGR 2 RMR EL SURE-LITES, EMERGI-LITE,
DUAL-LITE
CEILING LED PER CODE 5 277
XW LED EXIT SIGN, EDGE LIT RED LETTERS, SINGLE
FACE, CLEAR PANEL, BRUSHED ALUMINUM
RECESSED HOUSING
LITHONIA EDGR 1 R EL WM SURE-LITES, EMERGI-LITE,
DUAL-LITE
WALL LED PER CODE 5 277
XWP WEATHERPROOF LED EXIT SIGN, BLACK STENCIL
FACE, RED LETTERS, BLACK PAINTED ALUMINUM
HOUSING
LITHONIA LV S 1 R 120/277 EL N CW SURE-LITES, EMERGI-LITE,
DUAL-LITE
WALL LED PER CODE 5 277
LUMINAIRE REFERENCE IMAGES
TYPE L1 TYPE L2, L2E TYPE L3
TYPE L9
TYPE L17TYPE L12
TYPE L20
TYPE L15
TYPE EMC, EMP TYPE EMW
TYPE L10
TYPE L4
TYPE L24 TYPE L25 TYPE L26 TYPE L27, L29
TYPE X1, X2, XWTYPE L28
TYPE OL1, OL2 TYPE OL3
TYPE L5
TYPE L6 TYPE L7 TYPE L11
TYPE L16
TYPE OL4
TYPE L18
TYPE OL5
TYPE XWP
NO SCALE
LIGHT FIXTURE TYPE ''UC'' INSTALLATION DETAIL
TYPE UC
/1
/2
A S
I
TS
D
D
APPR
OX
OP
EN
S
TO
RA
GE
OP
EN
S
TO
RA
GE
A P P R O X
G V
S
W V
W V
H
Y
D
H
Y
D
H
DTS
OL2
(1LA-17)
OL2
(1LA-17)
OL2
(1LA-17)
OL2
(1LA-17)
L.P.
L.P.
L.P.L.P.L.P.L.P.
L.P.
P.P.
P.P.
NEW POWER
SERVICE DROP
POLE
NEW OVERHEAD
POWER LINE BY
DUKE ENERGY
EXISTING
POWER POLE
ELECTRICAL
MANHOLE
'EMH1'
EXISTING PAD-
MOUNTED
TRANSFORMER
RELOCATE
OL2
(1LA-17)
OL2
(1LA-17)
OL2
(1LA-17)
PAD-MOUNTED
TRANSFORMER
2 @6" SCH. 40 PVC CONDUITS,
CONCRETE-ENCASED
1 @6" SCH. 40 PVC CONDUIT,
CONCRETE-ENCASED. SEE
4/E-305 FOR DETAIL (SIMILAR).
MDF ROOM
EXISTING
TELECOM
BOX
ELECTRICAL
ROOM
480/277V, 3-PH, 4W
UNDERGROUND SERVICE.
SEE POWER RISER DIAGRAM.
(4) GROUND-MOUNTED
FLOODLIGHTS
(5) GROUND-MOUNTED
FLOODLIGHTS
P.P.
WP WP
FOR BFP
ENCLOSURE
HEATERS
2" E.C. TO
MDF ROOM
TYPICAL: IN ADDITION TO BRANCH
CIRCUIT, PROVIDE 2" E.C. TO EACH
LIGHT POLE FOR FUTURE LOW
VOLTAGE WIRING TO CAMERAS OR
OTHER DEVICES
PB
PB
PB
PB
PB
TYPICAL PULL BOX, FLUSH IN
GROUND. QUANTITY AND
LOCATIONS AS REQUIRED.
2 @ 4" E.C.
2 @ 4" E.C.
PB
EXIST. DATA VAULT
(APPROX. LOCATION)
2 @ 4" E.C.
2 @ 4" E.C.
MAIN CAMPUS
MDF LOCATION
THRU WALL JUST
ABOVE FOOTING
OVERHEAD
2 @ 4" E.C.
AREA UNDER
CONSTRUCTION
EXISTING BUILDING "A"
TURN CONDUIT UP
INTO PRIMARY
COMPARTMENT
EXISTING AREA LIGHT
WITH 25' METAL POLE
ON CONCRETE BASE
OL3
(1LA-19)
OL3
(1LA-19)
OL3
(1LA-19)
OL3
(1LA-19)
OL3
(1LA-19)
OL3
(1LA-19)
OL3
(1LA-19)
OL3
(1LA-19)
OL3
(1LA-19)
OL3
(1LA-19)
1PAB-22
1PAB-23
L4
L4
L4
L4
L4 L4 L4
(TYP)
L6
L5
OL5
(1LA-16)
OL5
(1LA-16)
5'-0"
E Q
E Q
E Q
E Q
(TYP)
L7
E-201
(3) IN-GRADE
UPLIGHTS
EQ
8'-0
" 8'-0 8'-0
" EQ
5'-0"
OL5
(1LA-16)
L7 TAMPER SWITCH AND LOW-
TEMP HEAT DETECTOR IN FIRE
PROTECTION BFP ENCLOSURE
F.H. TAMPER
SWITCH
E-305
U1
1 @6" SCH. 40 PVC
CONDUIT, CONCRETE-
ENCASED
OL3
(1LA-19)
OL3
(1LA-19)
OL3
(1LA-19)
OL3
(1LA-19)
OL3
(1LA-19)
TRUE
NORTH
P L
A N
N O
R T
H
D A
T E
R E
V
IS
IO
N
S
CHECKED BY
DRAWN BY
DATE
SCALE
S H E E T
T
IT
L E
P R O J E C T
N A M E
O W N E R
L O C A T
IO
N
S C O
P R O J E C T
N U M B E R
P R O J E C T
N U M B E R
-2
-0
A
.0
M
O N
R O
E N
O R
T H
C A
R O
L
IN
A
S O
U T
H P
IE
D
M O
N T
C O
M M
U N
IT
Y
C O
L L E
G E
C E
N T
E R
F O
R E
N T
R E
P R
E N
E U
R S
H
IP
AS NOTED
FOR
CONSTRUCTION
NC LICENSE C-0503 CMTA #223.089
LEAD DESIGN PROFESSIONAL
LARRY B. SMITH, JR., P.E.
L.B. SMITH AND ASSOCIATE, P.A.
(704) 289-5168 lbsjr@lbsmithpa.com
N
S
EHP BORE.
043650
E Y
E
T
SEAL
HTRON
ORAC
ANLI
E
EENIGN R
RP
OISSEFO LAN
E L E
C T
R
IC
A L S
IT
E
P L A
N
FEB. 26, 2025
JCT
SER
E-100
10/17/2025
SCALE: 1" = 30'-0"
ELECTRICAL SITE PLAN
KEYNOTES
L4 SEE DETAIL 2/E-305 FOR POLE LIGHT INSTALLATION
REQUIREMENTS.
L5 PROVIDE NEW CONCRETE BASE AND INSTALLATION MATCHING
EXISTING POLE LIGHTS. REFER TO DETAIL 2/E-305 FOR CONCRETE
BASE CONSTRUCTION. EXTEND EXISTING UNDERGROUND BRANCH
CIRCUIT TO NEW LOCATION.
L6 PROVIDE CONCRETE BASE FOR BOLLARD LIGHT PER DETAIL 5/E-305.
L7 PROVIDE CONCRETE BASE FOR FLOODLIGHT PER DETAIL 3/E-305.
U1 PRECAST CONCRETE MANHOLE, MINIMUM INTERIOR 6'W X 6'L X 7'H,
WITH 36" DIAMETER TOP ACCESS OPENING, 24" X 24" KNOCKOUT ON
EACH WALL (TOP AND BASE), WALL INSERTS FOR CABLE RACKING,
SUMP WITH COVER, RECESSED PULLING IRONS (FOUR IN BASE
SECTION FLOOR). PROVIDE MASONRY COLLAR AND AASHTO
H-20/HS-20 TRAFFIC RATED CAST IRON ROUND COVER AND FRAME.
PROVIDE COVER WITH STANDARD "ELECTRIC" LOGO.
/1
/2
A S
I
J
R /L
R /L
T
T
AV
AV
T
T
T
TT
M
J
J
J
J J
J
M
D
C
B
A
E
F
H
1 2 4 5 6 73 7.1 9
I
J
K
3.1 4.1
H.1
E.1
F.1
STORAGE
MDF
ELEV
ELEV
ELECTRICAL
OFFICE
BUSINESS CENTER SUITE
MEDIUM MEETING
PROJECT ROOM
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
WELLNESS
PHONE
PHONE
PHONE
119PANTRY/ DRY STOR.
JAN.
142MEN'S
WOMEN'S
COMMUNITY MANAGER
COPY/ PRINT
STAIR
ST2
SECURITY
STAIR
ST1
BREAK-OUT SPACE
248 SF
SOCIAL COMMONS SEATING
INDOORS
PHONE
PHONE
PHONE
PASS-THRU COFFEE
PROJECT ROOM
OFFICE
OFFICE
OFFICE
OFFICE
ADMIN OFFICE
MEDIUM MEETING
664 SF
MEDIUM MEETING
641 SF
CORRIDOR
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
SUITE
331 SF
PROJECT ROOM
179 SF
OPEN COLLABORATION
LOBBY
CORRIDOR
CORRIDOR
CORRIDOR
TEAM WORK
CORRIDOR
RISER
OFFICE
MDP
1MA
1LA
1PA
1MA
SHARED OFFICE
SOCIAL COMMONS
WP
E-201
E-201
EWC
EWC
36"
36"
E-201
WP
T-1PA
1PAA
1PA-4
1PA-4
1PA-4
1PA-4
1PA-4
1PA-5
1PA-5
2PA-2
1PA-5
1PA-5
1PA-5
1PA-5
1PA-6
1PA-6 1PA-6
1PA-7
1PA-7
1PA-7
1PA-7
1PA-8
1PA-8
1PA-8 1PA-8
1PA-8 1PA-9
1PA-9
1PA-9
1PA-9
1PA-10
1PA-101PA-10
1PA-10
1PB-10
1PB-10
1PB-12
1PB-7
1PA-11
1PB-7
1PA-10
1PB-10
1PB-12
1PBA-9
1PB-10
1PB-5
1PB-5
1PB-5
1PB-10
1PB-8
1PB-8 1PB-8
1PB-8
1PA-11
1PA-11 1PA-11 1PA-11 1PA-11
1PA-12
1PA-12 1PA-13
1PA-13
1PA-131PA-12
1PA-12
1PA-13
1PA-14
1PA-15
1PA-13 1PA-16 1PA-16
1PA-161PAB-26
1PAB-25
1PA-16
1PA-16
1PA-17
1PA-17
1PA-16
1PA-18
1PA-18
1PA-18
1PA-18
1PA-18
1PA-18
1PA-18
1PA-19
1PA-19
1PA-19
1PA-20
1PA-20
1PA-20
1PA-21 1PA-21
1PA-21
1PA-21
1PA-21
1PA-211PAA-51PAA-41PAA-21PAA-1,3
1PA-22
1PA-22
1PA-22 1PA-22
1PA-22
1PA-23
1PA-23
1PA-23
1PA-23
1PAA-9
1PAA-9 1PAA-9
1PAA-2
1PAA-37 1PA-25
1PAA-7
1PAA-2
1PAA-2
1PA-24 1PA-29,31 1PA-27
1PAA-7
1PAA-7
1PAA-7
1PAA-6
1PAA-6
1PAA-6 1PAA-6 1PAA-6
1PAA-6
1PAA-9
1PAA-8
1PAA-8
1PAA-8
1PAA-8
1PAA-11
1PAA-11 1PAA-11
1PAA-11
1PAA-10
1PAA-10
1PAA-10
1PAA-10
1PAA-13
1PAA-13
1PAA-13
1PAA-13
1PAA-15
1PAA-12
1PAA-12
1PAA-12
1PAA-12 1PAA-15
1PAA-15
1PAA-15
1PAA-15
1PAA-14
1PAA-14
1PAA-14
1PAA-14
1PAA-14
1PAA-14
1PAA-17
1PAA-17
1PAA-17
1PAA-17
1PAA-17
1PAA-16
1PAA-16
1PAA-16
1PAA-16
1PAA-18
1PAA-18
1PAA-18
1PAA-18
1PB-12 1PB-12
1PAA-19 1PAA-19
1PAB
E-121A
1PAA-35 1PAA-35
1PAB-24
1PAB-24
1PAA-36
1PAA-32
1PB-6
1PB-61PB-6
1PB-6
1PB-6
1PB-6
1PB-3
1PB-3
1PB-3
1PB-81PB-8
1PB-12
1PB-12
1PB-12
1PB-9
1PB-14
1PB-11
1PB-16
1PB-16
1PB-16
1PB-16
1PB-20
1PB-20
1PB-20
1PB-20
1PBA-16
1PBA-16
1PBA-20
SOCIAL COMMONS SUPPORT
125A
P1
WH-1
DS-VAV-1-01
(1MA-2)
DS-VAV-1-02
(1MA-4)
DS-VAV-1-03
(1MA-6)
DS-VAV-1-04
(1MA-7)
DS-VAV-1-05
(1MA-8)
DS-VAV-1-07
(1MA-10)
DS-VAV-1-11
(1MA-17)
DS-VAV-1-12
(1MA-18)
DS-VAV-1-13
(1MA-19)
DS-VAV-1-15
(1MA-21)
1PAA-6 1PAA-34
DS-VAV-1-16
(1MA-22)
DS-VAV-1-14
(1MA-20)
DS-VAV-1-17
(1MA-23)
DS-VAV-1-18
(1MA-24)
DS-VAV-1-19
(1MA-25)
DS-VAV-1-10
(1MA-16)
DS-VAV-1-09
(1MA-12,14)
DS-VAV-1-08
(1MA-11,13,15)
DS-VAV-1-06
(1MA-9)
DS-WH-1
(1MA-1,3,5)
EH-2
EH-3
EH-1
DS-VAV-3-19
(1MB-25,27)
DS-VAV-3-01
(1MB-1)
DS-VAV-3-03
(1MB-3)
DS-VAV-3-05
(1MB-5)
(1MA-26)
(1MA-27)
(1MA-28)
LCP1A
SP-1
1PA-26
P1
1PAB-28
1PAB-30
P1
1PAB-271PAB-29
HWRP-1
DS-HWRP-1
(1PAB-32)
E100A
E100B
E126
P9
1PAB-34
P9
P9
1PAB-31
1PAB-33
1PA-5
WP
FOR
SPRINKLER
BELL
EF-4
1PAB-36
1PAB-35
1PA-33
72"
1PA-35
AREA A
AREA B
TRUE
NORTH
P L
A N
N O
R T
H
WALL RATING LEGEND
NON-RATED PARTITION
1 HOUR FIRE BARRIER
D A
T E
R E
V
IS
IO
N
S
CHECKED BY
DRAWN BY
DATE
SCALE
S H E E T
T
IT
L E
P R O J E C T
N A M E
O W N E R
L O C A T
IO
N
S C O
P R O J E C T
N U M B E R
P R O J E C T
N U M B E R
-2
-0
A
.0
M
O N
R O
E N
O R
T H
C A
R O
L
IN
A
S O
U T
H P
IE
D
M O
N T
C O
M M
U N
IT
Y
C O
L L E
G E
C E
N T
E R
F O
R E
N T
R E
P R
E N
E U
R S
H
IP
AS NOTED
FOR
CONSTRUCTION
NC LICENSE C-0503 CMTA #223.089
LEAD DESIGN PROFESSIONAL
LARRY B. SMITH, JR., P.E.
L.B. SMITH AND ASSOCIATE, P.A.
(704) 289-5168 lbsjr@lbsmithpa.com
N
S
EHP B
ORE.
043650
E Y
E
T
SEAL
HTRO
N
ORAC
AN
LI
E
EENIGN R
R
P
OISSEFO
L
AN
F L O
O R
P L A
N
F
IR
S T
F L O
O R
A
R E
A A
P
O W
E R
FEB. 26, 2025
JCT
SER
E-101A
5/29/2026
:KEYNOTES
P1 FOR HAND DRYER INTEGRATED IN WASH BAR. COORDINATE
RECEPTACLE LOCATION WITH WASH BAR INSTALLATION
INSTRUCTIONS.
P9 MOTOR-OPERATED DOOR PAIR. PROVIDE 120V POWER AND ALL
REQUIRED CONTROL WIRING AND CONNECTIONS TO DOOR
OPERATORS AND ACTUATION DEVICES. COORDINATE LOCATIONS OF
DOOR ACTUATION DEVICES WITH ARCHITECT. ALL WIRING SHALL BE
IN CONCEALED CONDUIT.
SCALE: 1/8" = 1'-0"
FIRST FLOOR AREA A - POWER
/1
/2
S C
O c o m m e n ts
/1
/2
A V
F L
O O
R B
O X
R E
V
IS
IO
N
S
/1
/2
A S
I
/1
/2
A S
I
.5
/2
/2
E Q
U
IP
M E
N T
C H
A N
G E
J
J
J
R /L
R /L
R/L
R /L
R /L
R/L J
R/L J
R/L R/L
AV
AV
T T
T T
T T
J
J
M
J J
J
D
C
B
A
E
F
7.1 9
I
J
K
11 12 12.110.1 13 14 15
F.2
D.1
H.1
E.1
F.1
SECURITY
STAIR
ST1
SERVICE HALL
FULL CONFERENCE HALL
BREAK-OUT SPACE
248 SF
SOCIAL COMMONS SEATING
INDOORS
OUTDOOR CAFE SEATING
ADMIN OFFICE
MEDIUM MEETING
664 SF
MEDIUM MEETING
641 SF
CORRIDOR
PREFUNCTION
SUITE
331 SF
PROJECT ROOM
179 SF
OPEN COLLABORATION
CORRIDOR
BREAK-OUT SPACE
247 SF
BREAK-OUT SPACE
209 SF
BREAK-OUT SPACE
226 SF
CONF. CENTER ENTRY
LOADING DOCK
CORRIDOR
ELECTRICAL
DRY STORAGE
CATERING KITCHEN
FAMILY
IDF
JAN
WOMEN'S
MEN'S
COATS
CORRIDOR
WALK-IN REF
1PB
1PBC
1MB
E W
C
E W
C
E-201
P P
P
P
P
PP
P1
P1
WP
AV ROOM
160A
WP
1MBA-2,4,6
30A, 3P, FPN,
NEMA 3R
TRASH COMPACTOR
REMOTE POWER
PACK (480V, 3-PH)
WP
1PB-2
1PB-2
1PB-4
1PB-4
1PB-4
1PB-4
1PA-10
1PA-10
1PA-10
1PA-10
1PB-10
1PB-10
1PB-12
1PB-7
1PA-11
1PB-7
1PA-10
1PB-10
1PB-12
1PBA-9
1PB-20
1PBA-9
1PB-10
1PB-5
1PB-5
1PB-5
1PB-10
1PB-8
1PB-8 1PB-8
1PB-8
1PAA-14
1PAA-14
1PAA-14
1PAA-14
1PAA-14
1PAA-14
1PAA-17
1PAA-17
1PAA-17
1PAA-17
1PAA-17
1PAA-16
1PAA-16
1PAA-16
1PAA-16
1PAA-18
1PAA-18
1PAA-18
1PAA-18
1PB-12 1PB-12
1PBA
1PB-6
1PB-61PB-6
1PB-6
1PB-6
1PB-6
1PB-3
1PB-3
1PB-3
1PB-81PB-8
1PB-12
1PB-12
1PB-12
1PB-9
1PB-14
1PB-11 1PB-11
1PB-11
1PB-11
1PB-11
1PB-11PROJECTION
SCREEN
PROJECTION
SCREEN
PROJECTION
SCREEN
PROJECTION
SCREEN
PROJECTION
SCREENPROJECTION
SCREEN
PROJECTION
SCREEN
1PB-16
1PB-16
1PB-16
1PB-16
1PB-16
1PB-16 1PB-16
1PB-13
1PB-13
1PB-18 1PB-18 1PB-18 1PB-18
1PB-15 1PB-15 1PB-15 1PB-15
1PB-20
1PB-20
1PB-20
1PB-20
1PB-17
1PB-22 1PB-22 1PB-22 1PB-22
1PB-19 1PB-19 1PB-19 1PB-19
1PB-24 1PB-24
1PB-24
1PB-24
1PB-24
1PB-21
1PB-25 1PB-25
1PB-25 1PB-25
1PB-28 1PB-28
1PB-28 1PB-28
1PB-23 1PB-23
1PB-23 1PB-23
1PB-26 1PB-26
1PB-26 1PB-26
1PBA-1
1PBA-1
1PBA-1
1PBA-1
1PBA-1
1PBA-1
1PBA-1
1PBA-2
1PBA-2
1PBA-3 1PBA-3 1PBA-3 1PBA-3
1PBA-4 1PBA-4 1PBA-4 1PBA-4
1PBA-5
1PBA-5
1PBA-5
1PBA-5
1PBA-5
1PBA-6
1PBA-7 1PBA-7 1PBA-7 1PBA-7
1PBA-8 1PBA-8 1PBA-8 1PBA-8
1PBA-9 1PBA-9
1PBA-9 1PBA-91PBA-10 1PBA-10
1PBA-11 1PBA-11 1PBA-12 1PBA-13 1PBA-13
1PBA-12 1PBA-14
1PBA-14
1PBA-141PBA-14
1PBA-14
1PBA-16
1PBA-16
1PBA-16
1PBA-18
1PBA-18
1PBA-18
1PBA-18
1PBA-16
1PBA-16 1PBA-18
1PBA-18
1PBA-20
1PBA-20
1PBA-15
1PBA-15
1PBA-15
1PBA-17
1PBA-17
1PBA-17
1PBA-17 1PBA-17
1PBA-19
1PBA-19
1PBA-21
1PBA-19
1PBA-19
1PBA-21
1PBA-22
1PBA-24
1PBA-26
1PBA-22
1PBA-231PBA-23
1PBA-25
1PBA-25
1PBA-25
1PBA-25
1PBA-25
1PBA-25
1PBA-31 1PBA-29
DOOR DOOR
WH-2
DS-VAV-1-19
(1MA-25)
DS-VAV-1-10
(1MA-16)
DS-VAV-1-09
(1MA-12,14)
EH-1
DS-VAV-3-19
(1MB-25,27)
DS-VAV-3-18
(1MB-28,30)
DS-VAV-3-01
(1MB-1)
DS-VAV-3-02
(1MB-2)
DS-VAV-3-03
(1MB-3)
DS-VAV-3-04
(1MB-4)
DS-VAV-3-05
(1MB-5)
DS-VAV-3-06
(1MB-6,8)
DS-VAV-3-07
(1MB-7,9)
DS-VAV-3-08
(1MB-10)
DS-VAV-3-09
(1MB-11)
DS-VAV-3-10
(1MB-12,14,16)
DS-VAV-3-11
(1MB-13)
DS-VAV-3-12
(1MB-18)
DS-VAV-3-13
(1MB-15)
DS-VAV-3-14
(1MB-20,22)
DS-VAV-3-15
(1MB-17,19)
DS-VAV-3-16
(1MB-24,26)
DS-VAV-3-17
(1MB-21,23)
EH-4
EH-5
(1MA-26)
DS-EH-5
(1MBA-13,15,17)
DS-EH-4
(1MBA-8,10,12)
DS-WH-2
(1MBA-7,9,11)
1MBA
1PMB
HWRP-2
DS-HWRP-2
(1PBA-27)
E-121B
E-121B
1PBB
E126
E150A E150B
P9 P9
1PBA-30 1PBA-32
P9
1PAB-34
1PBA-14
WP
TRUE
NORTH
P L
A N
N O
R T
H
AREA A
AREA B
WALL RATING LEGEND
NON-RATED PARTITION
1 HOUR FIRE BARRIER
D A
T E
R E
V
IS
IO
N
S
CHECKED BY
DRAWN BY
DATE
SCALE
S H E E T
T
IT
L E
P R O J E C T
N A M E
O W N E R
L O C A T
IO
N
S C O
P R O J E C T
N U M B E R
P R O J E C T
N U M B E R
-2
-0
A
.0
M
O N
R O
E N
O R
T H
C A
R O
L
IN
A
S O
U T
H P
IE
D
M O
N T
C O
M M
U N
IT
Y
C O
L L E
G E
C E
N T
E R
F O
R E
N T
R E
P R
E N
E U
R S
H
IP
AS NOTED
FOR
CONSTRUCTION
NC LICENSE C-0503 CMTA #223.089
LEAD DESIGN PROFESSIONAL
LARRY B. SMITH, JR., P.E.
L.B. SMITH AND ASSOCIATE, P.A.
(704) 289-5168 lbsjr@lbsmithpa.com
N
S
EHP BORE.
043650
E Y
E
T
SEAL
HTRON
ORAC
ANLI
E
EENIGN R
RP
OISSEFO LAN
F L O
O R
P L A
N
F
IR
S T
F L O
O R
A
R E
A B
P
O W
E R
FEB. 26, 2025
JCT
SER
E-101B
10/17/2025
SCALE: 1/8" = 1'-0"
FIRST FLOOR AREA B - POWER
:KEYNOTES
P1 FOR HAND DRYER INTEGRATED IN WASH BAR. COORDINATE
RECEPTACLE LOCATION WITH WASH BAR INSTALLATION
INSTRUCTIONS.
P9 MOTOR-OPERATED DOOR PAIR. PROVIDE 120V POWER AND ALL
REQUIRED CONTROL WIRING AND CONNECTIONS TO DOOR
OPERATORS AND ACTUATION DEVICES. COORDINATE LOCATIONS OF
DOOR ACTUATION DEVICES WITH ARCHITECT. ALL WIRING SHALL BE
IN CONCEALED CONDUIT.
/1
/2
A V
F L
O O
R B
O X
R E
V
IS
IO
N
S
/1
/2
A S
I
T
T
T
D
C
B
A
E
F
H
1 2 4 5 6 73 7.1 9
I
J
K
3.1 4.1
H.1
E.1
F.1
JAN.
MEN'S
WOMEN'S
IDF
SEMINAR ROOM
826 SF
LARGE SUITE
382 SF
SMALL SUITE
160 SF
SMALL SUITE
162 SF
OFFICE
PHONE
PHONE
OFFICE
MEDIUM MEETING
315 SF
SHARED OFFICE
SHARED OFFICE
OFFICE
OFFICE
OFFICE
PHONE
PHONE
PHONE
PHONE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
PROJECT ROOM
OFFICE
OFFICE
OFFICE
OFFICE
STAIR
ST2
COWORKING NON-RESERVED
COWORKING- RESERVED
PODCAST
CASUAL MEETING
351 SF
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
PHONE
OFFICE
OFFICE
SMALL SUITE
STAIR
ST1
PHONE
PHONE
QUIET NOOK
OFFICE
PROJECT ROOM
CORRIDOR
CORRIDOR
CORRIDOR
LANDING
CORRIDOR
WET BAR GALLEY
CORRIDOR
ELEV.
ELEV
ELEC.
STOR.
258B
LARGE SUITE
381 SF
CORRIDOR
CORRIDOR
CORRIDOR
E-122A
EWC
EWC
WP
WP
2MA
2LA
2PA
+60"
+32"
P1
P1
2PAA
T-2PA
1PA-2
2PAA-1
2PAA-1
2PAA-1
2PAA-4
2PAB-7
2PAB-6
2PA-3
2PA-3
2PA-4
2PA-4
2PA-5
2PA-9
2PA-10
2PA-11 2PA-12
2PA-11
2PA-12
2PA-13
2PA-14
2PA-14
2PA-15
2PA-15
2PA-17
2PA-16
2PAA-13
2PAA-13
2PAA-14
2PA-23 2PA-23
2PA-23
2PA-25
2PA-25
2PA-25
2PA-22
2PA-22 2PA-22
2PA-19
2PA-19 2PA-18
2PA-18
2PA-17
2PA-28
2PA-27
2PA-28
2PA-28
2PA-28
2PAA-19 2PAA-19
2PAA-20
2PAA-18
2PAA-18 2PAA-22 2PAA-23
2PAA-232PAA-22 2PAA-24
2PAA-24 2PAA-25
2PAA-25
2PA-3
2PA-4
2PA-4
2PA-5
2PA-5
2PA-5
2PA-6
2PA-6
2PA-6
2PAA-15
2PAA-15
2PAA-16
2PA-5
2PA-6
2PA-10
2PA-92PA-9
2PA-7
2PA-7
2PA-7 2PA-8 2PA-8 2PA-8
2PA-8
2PA-8
2PA-8
2PA-82PA-7
2PA-7
2PA-7
2PAA-4
2PA-7
2PA-11
2PA-11
2PA-12
2PA-13
2PA-13
2PA-13
2PA-14
2PA-14
2PA-15
2PA-15
2PA-16 2PA-16
2PA-16
2PAA-4
2PAA-13
2PAA-14
2PAA-14
2PA-24
2PA-24
2PA-24
2PA-24
2PA-24
2PA-24
2PA-21
2PA-20 2PA-18
2PA-18
2PA-17
2PA-29
2PAA-29
2PAA-28
2PAA-29
2PAA-29
2PAA-28
2PAA-282PAA-282PAA-21
2PAA-21
2PAA-21
2PAA-21
2PAA-20
2PAA-20
2PAA-21
2PAA-19
2PAA-19
2PAA-20
2PAA-22
2PAA-22
2PAA-23 2PAA-24
2PAA-23 2PAA-24 2PAA-26
2PAA-252PAA-18
2PAA-18
2PA-26
2PA-6
2PAA-15 2PAA-16 2PAA-16
2PAA-15 2PAA-17 2PAA-17
2PA-10
2PA-27
2PAB-4 2PAB-4
2PAB-4 2PAB-2
2PAB-2 2PAB-2
2PAB-5 2PAB-3
2PAB-5 2PAB-5 2PAB-3
2PAB-3
2PAA-29
2PAB-1
2PAB-12PAB-1
2PAA-28
STOR.
259B
2PA-17
2PA-12
2PA-9
2PA-29
2PA-28
2PA-292PA-27
2PA-30
LOCATE IN HOISTWAY
AS DIRECTED BY
ELEVATOR INSTALLER
2PAA-1
2PAA-2
2PAA-3
2PAA-3
E-201
2PAA-17
2PAA-21
2PAA-27
2PAA-27
PROJECT ROOM
2PAB-10
2PAB-11
DS-VAV-2-01
(2MA-1)
DS-VAV-2-02
(2MA-2)
DS-VAV-2-03
(2MA-3)
DS-VAV-2-04
(2MA-4)
DS-VAV-2-05
(2MA-5)
DS-VAV-2-06
(2MA-6)
DS-VAV-2-07
(2MA-7)
DS-VAV-2-08
(2MA-8)
DS-VAV-2-09
(2MA-9)
DS-VAV-2-10
(2MA-10)
DS-VAV-2-11
(2MA-11)
DS-VAV-2-12
(2MA-12,14)
DS-VAV-2-13
(2MA-13,15)
DS-VAV-2-14
(2MA-16,18)
DS-VAV-2-15
(2MA-17)
DS-VAV-2-16
(2MA-19,21)
DS-VAV-2-17
(2MA-20,22)
DS-VAV-2-18
(2MA-23)
DS-VAV-2-19
(2MA-24)
SUSPEND FROM
STRUCTURE,
8'-0" AFF
2PMA
T-2PMA
2PAB
DS-T-2PA
(MDP-10)
COORDINATE ELEVATOR
CONTROLLER LOCATION WITH
ELEVATOR SHOP DRAWINGS
ELEVATOR MAIN POWER
DISCONNECT SWITCH.
REFER TO DETAIL 7/E-302.
LCP2A
2PAB-9
2PAB-8
ELEVATOR CAR 120V CIRCUIT
DISCONNECT SWITCH
AC-6
P8
TRUE
NORTH
P L
A N
N O
R T
H
AREA A
AREA B
WALL RATING LEGEND
NON-RATED PARTITION
1 HOUR FIRE BARRIER
D A
T E
R E
V
IS
IO
N
S
CHECKED BY
DRAWN BY
DATE
SCALE
S H E E T
T
IT
L E
P R O J E C T
N A M E
O W N E R
L O C A T
IO
N
S C O
P R O J E C T
N U M B E R
P R O J E C T
N U M B E R
-2
-0
A
.0
M
O N
R O
E N
O R
T H
C A
R O
L
IN
A
S O
U T
H P
IE
D
M O
N T
C O
M M
U N
IT
Y
C O
L L E
G E
C E
N T
E R
F O
R E
N T
R E
P R
E N
E U
R S
H
IP
AS NOTED
FOR
CONSTRUCTION
NC LICENSE C-0503 CMTA #223.089
LEAD DESIGN PROFESSIONAL
LARRY B. SMITH, JR., P.E.
L.B. SMITH AND ASSOCIATE, P.A.
(704) 289-5168 lbsjr@lbsmithpa.com
N
S
EHP BORE.
043650
E Y
E
T
SEAL
HTRON
ORAC
ANLI
E
EENIGN R
RP
OISSEFO LAN
F L O
O R
P L A
N
S E
C O
N D
F L O
O R
A
R E
A A
P
O W
E R
FEB. 26, 2025
JCT
SER
E-102A
10/17/2025
SCALE: 1/8" = 1'-0"
SECOND FLOOR AREA A - POWER
:KEYNOTES
P1 FOR HAND DRYER INTEGRATED IN WASH BAR. COORDINATE
RECEPTACLE LOCATION WITH WASH BAR INSTALLATION
INSTRUCTIONS.
P8 SPLIT-SYSTEM AIR CONDITIONING INDOOR UNIT, 208V, 1-PH,
POWERED FROM OUTDOOR UNIT. PROVIDE LOCAL MOTOR-RATED
DISCONNECT SWITCH IF NONE IS INCLUDED WITH UNIT, AND
PROVIDE POWER AND CONTROL WIRING PER MANUFACTURER'S
INSTALLATION…