APPENDIX B - BACNET QC Checklist.doc

DOC document 99 KB Posted

Attached to
HVAC CONTROLLER SYSTEM AND INSTALLATION Federal contract opportunity
Solicitation number
N6426720Q0176
Issued by
Department of the Navy Naval Sea Systems Command

About this file

This document contains a quality control checklist template for Bacnet control systems and a solicitation for an HVAC controller system and installation.

The quality control checklist outlines 14 items to verify for pre-construction, post-construction, and closeout submittals, including confirming all DDC hardware is numbered on drawings, software supports ASHRAE 135, training has been conducted, and as-built drawings accurately represent the installed system.

The solicitation seeks quotes for an HVAC controller system and installation at the Naval Surface Warfare Center in Corona, California. Interested parties must attend a mandatory site visit on August 27, 2020 and submit required documents by August 15. Quotes are due September 2, 2020. The award will be made to the responsible offeror whose conforming quote is most advantageous based on evaluation criteria in sections L and M. Offerors must be registered in SAM and attend the site visit to be considered for award.

View the file

Other files for this federal contract opportunity

Other files attached to HVAC CONTROLLER SYSTEM AND INSTALLATION, newest first.
File Type Posted
N642620Q0176 Answers.pdf PDF
CDRLs.zip ZIP file
APPENDIX A - DIVISION 01 - GENERAL REQUIREMENTS.pdf PDF
MINIMUM_5512_REQUIREMENTS.docx DOCX document
SECNAV_5512_1_11787_APPROVED_AC_PASS_ID_FORM_05282014.pdf PDF
N6426720Q0176 Redact.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

APPENDIX A

QC CHECKLIST: BACNET

This checklist is not all-inclusive of the requirements of this specification and should not be interpreted as such.

This checklist is for (check one:)

Pre-Construction QC Checklist Submittal
(Items 1-2)
Post-Construction QC Checklist Submittal
(Items 1-6)
Close-out QC Checklist Submittal
(Items 1-14)

Initial and date each item in the spaces provided verifying that each requirement has been met.

Items verified for Pre-Construction, Post-Construction and Closeout QC Checklists Submittal:

Item
Initial
Date
1
All DDC Hardware (nodes) are numbered on Control System

Schematic Drawings.

2
M&C software supports, and ASHRAE 135. M&C software is BTL Listed as a B-AWS.

Items verified for Post-Construction and Closeout QC Checklist Submittal:

Item
Initial
Date
3
Communication between the M&C software and ASHRAE 135 field control systems uses only ASHRAE 135.
4
Connections to non-ASHRAE field control systems are via a Gateway from the field control system to ASHRAE 135 or via a UMCS supported protocol without the use of a hardware Gateway.
5
Computer workstations and servers are installed as shown on the UMCS Riser Diagram.
6
Training schedule and course attendee lists have been developed and coordinated with shops and submitted.

Items verified for Closeout QC Checklists Submittal:

Item
Initial
Date
7
All points in field control systems have been discovered and are available at the M&C software.
8
All software has been licensed to the Government
9
M&C software monitoring displays have been created for all building systems, including all override and display points indicated on Points Schedule drawings.
10
Final As-built Drawings accurately represent the final installed system.
11
Default trends have been set up (per Points Schedule drawings).
12
Scheduling has been configured at the M&C Software (per Occupancy Schedule drawing).
13
O&M Instructions have been completed and submitted.
14
Basic Operator and Advanced Training courses have been completed.

(QC Representative Signature) (Date)

Section 23 09 23 Appendix Page 2