Responses to questions about solicitation AG-4329-S-16-0001
View the file
Other files
| File | Type | Posted |
|---|---|---|
| USDA_Byron_Building_1_Final_Environmental_Report.pdf | ||
| AG-4329-S-16-0001.pdf | ||
| Flooring_DIAGRAM.pdf | ||
| RFQ_Remidation_Byron_SOW.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Gaytan, Juan - ARS
To: Gaytan, Juan - ARS Subject: RE: Remediation of flooring, AG-4329-S-16-001
Questions Asked.
1) What will the completion percentage of the 2nd floor be when turned over to the asbestos contractor?
98%
2) Will the 2nd floor HVAC be de‐energized? Yes
3) Will the building be vacant? 1st floor will be occupied during normal working hours. Work scheduled on
2nd floor, space will be cleaned and vacant to allow 2nd floor to be sealed at one time.
4) Will the ceilings systems (new grids and acoustical tiles) be completely installed? Yes
5) The Owner will need to provide adequate electricity for the abatement procedures. Vendor may use exiting receptacles on 2nd floor for power supply. Plenty of 120V, very limited 240V.
6) Access is needed for exhausting negative air outside the building. Contractor may use existing door to outside at send floor north east end of building, stair well to 1st floor from 2nd may be used at east end of building. Windows in labs and offices may be removed to allow air to be vented as needed.
7) Which method, PCM or TEM, will be used for air clearance testing? PCM will be done daily. TEM will be done at completion for the clearance testing.
8) Is this an unrestricted or small business set aside? This is a Total small business set aside
9) Environmental report file is not working? Attachment has been uploaded again