Atch_2_-_Drawings.pdf

PDF 2 MB Posted

Attached to
Fire Cache Fire Sprinkler and Alarm System Upgrade Federal contract opportunity
Solicitation number
AG-04GG-S-17-0010
Issued by
Department of Agriculture Forest Service R6-Pacific Northwest Region

About this file

Drawings

View the file

Other files for this federal contract opportunity

Other files attached to Fire Cache Fire Sprinkler and Alarm System Upgrade, newest first.
File Type Posted
SF-30_-_Amd_2_-_AG-04GG-S-17-0010_.pdf PDF
HVAC_Upgrade_As-Builts.pdf PDF
Conformed_AG-04GG-S-17-0010_Amd_0001.pdf PDF
Site_Visit_Handout.pdf PDF
Minutes_from_site_visit.pdf PDF
SF-30_-_Amd_1_-_AG-04GG-S-17-0010.pdf PDF
Balance_Report_2014-01-24.pdf PDF
Atch_3_-_Wage_Decision_OR170025.pdf PDF
Atch_1_-_Specifications.pdf PDF
AG-04GG-S-17-0010.pdf PDF
Atch_5_Past_Performance_Data_Sheet.docx DOCX document
Atch_4_Fire_clauses_r6-fs-6300-52.pdf PDF
Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REDMOND AIR CENTER FIRE CACHE

FIRE SPRINKLER AND ALARM SYSTEM

UPGRADE

Case, Lowe and Hart, Inc.

2484 Washington Blvd. Ste 510

Ogden, Utah 84401

DRAWING INDEX

G001 Title Sheet FP101 Fire Sprinkler Demolition Plan − Cache Warehouse FP102 Schematic Fire Sprinkler Plan − Cache Warehouse FP103 Fire Alarm Demolition Plan − Cache Warehouse FP104 Fire Alarm Plan − Cache Warehouse

Protection Consultants, Inc.

1199 S Main Street #101

Centerville, Utah 84014

U. S. Department of Agriculture

FOREST SERVICE

Pacific Northwest Region Six Engineering

DESCHUTES NATIONAL FOREST

17674

RPE

S R

OF

ER ES

L E

K

V

NI J. E W

IS

EG

I

T

D

SIONA

L

IGNE

NEER

OREGON

14,R.

A

M

1 99 5

Case, Lowe & Hart, Inc. 2484 Washington Blvd.

Suite 510 Ogden, Utah 84401

801.399.5821 Fax 801.399.0728 www.clhae.com

SHEET OF 5

DRAWN BY:

CHECKED BY:

REDMOND AIR CENTER FIRE

CACHE FIRE SPRINKLER AND

ALARM SYSTEM UPGRADE

DESCHUTES

PACIFIC NORTHWEST

DISTRICT RANGER

ISSUE INFORMATION

PROJECT NO:

CAD DWG FILE:

DESIGNED BY:

15072

F0REST SUPERVISOR

FOREST ENGINEER

DATE

DATE

DATE

AGRICULTURE

The Pacific Northwest Region

FOREST SERVICE

UNITED STATES

DEPARTMENT

OF

PROJECT TEAM

Protection Consultants, Inc.

1199 S. Main Street #101 Centerville, Utah 84014

801.295.6070 Fax 801.677.0000

NATIONAL FOREST

REGION 6

NOV 01, 2016

MARK DATE DESCRIPTION

G001

Title Sheet

K.J.L.

J.A.C., J.M.S.

K.J.L.

G001.DWG

11/01/16

FIRE SPRINKLER DEMO KEY NOTES

CONNECTED TO NEW RISER.

CONNECTION PIPING MAY REMAIN TO BE

MAIN DRAIN (IF 2") AND FIRE DEPARTMENT

PIPING BACK TO 6" FLANGE ABOVE FLOOR SLAB.

VALVES GAUGES AND APPURTENANCES. REMOVE

DEMOLISHED. REMOVE ALL PIPING, FITTINGS,

EXISTING FIRE SPRINKLER RISER TO BE

SUPPORTS AND BRACES.

DEMOLISHED. REMOVE PIPING, FITTINGS, PIPE

EXISTING 2-1/2" FEED AND CROSS MAINS TO BE

AND PIPE SUPPORTS.

DEMOLISHED. REMOVE PIPING, FITTINGS, SPRINKLERS

SPRINKLERS PROTECTING WAREHOUSE AREA TO BE

EXISTING 1-1/4" BRANCH LINES AND UPRIGHT FIRE

FEED MAIN (SEE SHEET FP102).

CONNECT PIPING TO NEW FIRE SPRINKLER RISER OR

PROTECTING EAST OFFICE/WORK AREAS TO REMAIN.

EXISTING FIRE SPRINKLERS AND BRANCH LINES

FP101

FP101.DWG

2-1/2" 2-1/2" 2-1/2" 2-1/2"

2-1/2"

2-1/2"2-1/2"2-1/2"2-1/2"

1 0

FIRE SPRINKLER DEMOLITION PLAN - CACHE WAREHOUSE

1/8" = 1’-0" 4’ 8’ 16’

Cache Warehouse Demolition Plan -

Fire Sprinkler

PUMP REPAIR

PUMP REPAIR

W A

R E

H O

U S

E

TOOL MAINTENANCE

MECHANICAL

PAINTING

OVEN REPAIR MEN

WOMEN

OFFICE

OFFICE

OFFICE

OFFICE

Case, Lowe & Hart, Inc. 2484 Washington Blvd.

Suite 510 Ogden, Utah 84401

801.399.5821 Fax 801.399.0728 www.clhae.com

SHEET OF

DRAWN BY:

CHECKED BY:

DESCHUTES

PACIFIC NORTHWEST

DESCRIPTION

DISTRICT RANGER

ISSUE INFORMATION

PROJECT NO:

CAD DWG FILE:

DESIGNED BY:

MARK DATE

F0REST SUPERVISOR

FOREST ENGINEER

DATE

DATE

DATE

AGRICULTURE

The Pacific Northwest Region

FOREST SERVICE

UNITED STATES

DEPARTMENT

OF

PROJECT TEAM

Protection Consultants, Inc.

1199 S. Main Street #101 Centerville, Utah 84014

801.295.6070 Fax 801.677.0000

NATIONAL FOREST

REGION 6

GTJ

BAJ

GTJ

11/01/16

15072

ALARM SYSTEM UPGRADE

CACHE FIRE SPRINKLER AND

REDMOND AIR CENTER FIRE

11/01/16

3 3

FIRE SPRINKLER KEY NOTES

FIRE SPRINKLER GENERAL NOTES

FLOW: 804 GPM

RESIDUAL PRESSURE 122 PSI

STATIC PRESSURE: 148 PSI

FLOW TEST AND FIRE PUMP SUBMITTAL DATA) IS:

PUMP DISCHARGE FLANGE (BASED ON OCT 2014

FIRE PROTECTION WATER SUPPLY AVAILABLE AT

FROM ADJACENT FIRE PUMP HOUSE TO REMAIN.

REMOTE, FREE STANDING POST INDICATOR VALVE

EXISTING 6" FIRE PROTECTION WATER SUPPLY WITH

SHEET.

WATER FLOW SWITCH. SEE RISER DETAIL ON THIS

VALVE, 2" MAIN DRAIN, PRESSURE GAUGES AND

NEW, 6" FIRE SPRINKLER RISER WITH RISER CHECK

SHEET.

TO RISER. SEE FIRE SPRINKLER RISER DETAIL ON THIS

CHECK VALVE WITH AUTOMATIC BALL DRIP FROM FDC

RISER CHECK VALVE. INSTALL NEW 4" PIPING AND

FDC TO NEW FIRE SPRINKLER RISER DOWNSTREAM OF

CONNECTION (FDC) TO REMAIN. CONNECT EXISTING

EXISTING, 2-WAY, WALL MOUNTED FIRE DEPARTMENT

MAIN.

PROTECTING OFFICE/WORK AREAS TO NEW 6" FEED

CONNECT EXISTING PIPING FOR FIRE SPRINKLERS

INSTALLED THROUGHOUT WAREHOUSE AREA.

WAREHOUSE AREA TO SUPPLY NEW FIRE SPRINKLERS

INSTALL NEW 6" FEED MAIN FROM NEW RISER TO

REMAIN.

OFFICE/WORK AREAS EAST OF WAREHOUSE TO

EXISTING FIRE SPRINKLERS/PIPING PROTECTING

PLATFORMS.

SPACES IN WAREHOUSE AND BELOW STORAGE

ON PLANS) TO PROTECT BELOW CEILING OF OFFICE

INSTALL ADDITIONAL FIRE SPRINKLERS (NOT SHOWN

SPRINKLERS.

MULTIPLE ROW RACKS WITHOUT IN-RACK FIRE

COMMODITY STORED ON SINGLE, DOUBLE OR

HIGH STORAGE OF NON-ENCAPSULATED CLASS IV

16.2.1.3.3.2 AND FIGURE 16.2.1.3.2(D) CURVE C FOR 15’

BASED ON THE REQUIREMENTS OF NFPA 13 TABLE

PROVIDE 500 GPM HOSE ALLOWANCE). DESIGN IS

SYSTEM LACKS SUFFICIENT VOLUME AT RAC TO

HOSE ALLOWANCE IS REQUIRED (REDMOND WATER

DENSITY OF 0.385 GPM/SQ FT OVER 2,000 SQ FT. NO

HYDRAULIC DESIGN AREA #1. MINIMUM DISCHARGE

1.

C. USFS DESIGN STANDARDS

2013 EDITION

B. NFPA 13 INSTALLATION OF FIRE SPRINKLER SYSTEMS

A. INTERNATIONAL BUILDING/FIRE CODES (2015 EDITIONS)

FOLLOWING CODES AND STANDARDS:

COMPLY WITH THE APPLICABLE PROVISIONS OF THE

THE FIRE SPRINKLER SYSTEM SHALL BE DESIGNED TO

2.

HAVING JURISDICTION.

CALCULATIONS AND OBTAIN APPROVAL FROM AUTHORITY

SPRINKLER SYSTEM, PREPARE SHOP DRAWINGS, HYDRAULIC

CONDITIONS, DEVELOP THE FINAL DESIGN FOR FIRE

SHALL BE RESPONSIBLE TO FIELD VERIFY EXISTING

BUILDING CONDITIONS. THE FIRE SPRINKLER CONTRACTOR

MUST BE ADJUSTED WHERE REQUIRED TO MATCH ACTUAL

OTHER FIRE PROTECTION EQUIPMENT ARE APPROXIMATE AND

SHOWN ON THESE DRAWINGS FOR SPRINKLERS, PIPING AND

THIS DRAWING IS CONCEPTUAL IN NATURE. THE LOCATIONS

THE DESIGN OF THE FIRE SPRINKLER SYSTEM CONTAINED ON

3.

ACCORDANCE WITH THE DRAWINGS AND SPECIFICATIONS.

2013 EDITION, REDMOND FIRE DEPARTMENT AND SHALL BE IN

DESIGN SHALL MEET THE REQUIREMENTS OF IBC, IFC, NFPA 13

REDMOND AIR CENTER IN REDMOND, OR. THE SYSTEM

PROTECT ALL AREAS OF CACHE WARESHOUSE AT THE

FUNCTIONAL A NEW WET-PIPE FIRE SPRINKLER ZONE TO

PERFORM ALL WORK AND OPERATIONS TO INSTALL AND MAKE

FURNISH ALL MATERIALS, EQUIPMENT AND SUPPLIES AND

4.

COVERAGE PER SPRINKLER SHALL BE 100 SQ FT.

ORIFICE (K-11.2) HIGH TEMPERATURE RATED. MAXIMUM

FIRE SPRINKLERS IN WAREHOUSE SHALL BE EXTRA LARGE

5.

DRAWINGS

BY THE FIRE ALARM SYSTEM. REFER TO FIRE ALARM

CONTROL VALVES AND FLOW SWITCHES SHALL BE PROVIDED

OFF-PREMISE SUPERVISION OF ALL FIRE SPRINKLER SYSTEM

6.

SYSTEMS.

AND/OR FM APPROVED FOR USE IN FIRE PROTECTION

OF THE FIRE SPRINKLER SYSTEM SHALL BE U.L. LISTED

ALL DEVICES AND MATERIALS USED FOR THE INSTALLATION

7.

SHALL BE DOMESTIC, BLACK STEEL, SCHEDULE 40 PIPING.

CONFORMING TO ANSI/ASTM A53, ASTM A135 OR A795. PIPING

NEW FIRE SPRINKLER PIPING SHALL BE STEEL PIPE

8.

C. PLAIN END FITTINGS MAY NOT BE USED.

GASKETED VICTAULIC STYLE FITTINGS AND COUPLINGS.

JOINED WITH CUT/ROLL GROOVED JOINTS USING RUBBER

B. PIPING 2-1/2" AND LARGER IN NOMINAL DIAMETER SHALL BE

AND COUPLINGS.

JOINED WITH THREADED JOINTS USING CAST IRON FITTINGS

A. PIPING 2" AND SMALLER IN NOMINAL DIAMETER SHALL BE

FITTINGS:

9.

PIPE AND MAXIMUM 15’-0" BETWEEN HANGERS.

1-1/2" AND LARGER: MINIMUM ONE HANGER PER LENGTH OF

OF PIPE AND MAXIMUM 12’-0" BETWEEN HANGERS.

1-1/4" AND SMALLER PIPE: MINIMUM ONE HANGER PER LENGTH

HANGERS:

10.

CROSS MAINS.

ALL FIRE SPRINKLER SYSTEM RISERS, FEED MAINS AND

INSTALL SWAY BRACING IN ACCORDANCE WITH NFPA 13 ON

SWAY BRACING:

11.

FABRICATING OR INSTALLING ANY EQUIPMENT.

ENGINEER AND THE GOVERNMENT PRIOR TO ORDERING,

WITH NFPA 13 FOR REVIEW AND APPROVAL TO THE PROJECT

DRAWINGS AND HYDRAULIC CALCULATIONS IN ACCORDANCE

CONTRACTOR SHALL PREPARE AND SUBMIT COMPLETE SHOP

12.

FOREST SERVICE AND REDMOND FIRE DEPARTMENT.

TESTING SHALL BE WITNESSED AND APPROVED BY THE US

ANDRECOMMENDED BY EQUIPMENT MANUFACTURERS. ALL

COMMISSIONING REQUIRED BY NFPA 13, NFPA 20 AND NFPA 72

CONTRACTOR SHALL PERFORM ALL TESTING AND

1 01/8" = 1’-0" 4’ 8’ 16’

PUMP REPAIR

PUMP REPAIR

W A

R E

H O

U S

E

TOOL MAINTENANCE

MECHANICAL

PAINTING

OVEN REPAIR MEN

WOMEN

OFFICE

OFFICE

OFFICE

OFFICE

FP102

SCHEMATIC FIRE SPRINKLER PLAN - CACHE WAREHOUSE Cache Warehouse Sprinkler Plan - Schematic Fire

D

567891011121314

15 16 17 18 19 20 21 22 23 24 25 26 27 28

29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52

103 106

108 113

4" 4" 4" 4" 4" 4" 4" 4" 4" 4" 4" 4" 4" 4" 4" 4" 4" 4" 4" 4" 4" 4" 4" 4" 1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

1- 1/ x

1’

3" 3" 3" 3" 3" 3" 3" 3" 3" 3" 3" 3" 3" 3" 3" 3" 3" 3" 3" 3" 3" 3" 3"

FIRE SPRINKLER RISER SCHEMATIC

D

NO SCALE

SUPPLY FROM PUMP HOUSE TO REMAIN

EXISTING 6" FIRE PROTECTION WATER

TO REMAIN

EXISTING 6" FLANGE ABOVE FLOOR SLAB

WITHIN 24" OF FLOOR

NEW 6" RISER WITH FLEXIBLE COUPLING

OUTLET AND PRESSURE GAUGES.

RISER CHECK VALVE WITH MAIN DRAIN

PIPING MAY BE REUSED.

BUILDING EXTERIOR. EXISTING DISCHARGE

2" MAIN DRAIN. EXTEND DISCHARGE TO

12 SPRINKLERS

SPARE SPRINKLER CABINET. STOCK WITH

4" SWING CHECK VALVE

DRAINAGE

DRIP AT LOW POINT OF PIPING FOR

BE REUSED. PROVIDE 1/2" AUTO BALL

DEPT. CONNECTION. EXISTING FDC MAY

4" OUT TO 2-1/2" X 2-1/2" X 4" FIRE

HYDRAULIC DESIGN INFORMATION PLACARD

VANE TYPE WATER FLOW SWITCH

PIPING.

THROUGH 2" MAIN DRAIN DISCHARGE

DISCHARGE TO EXTERIOR OF BUILDING

PRESSURE RELIEF VALVE. EXTEND

VALVE WITH 1/2" ORIFICE AND BUILT-IN

AGF MODEL 3011 INSPECTOR’S TEST

6" SUPPLY TO FIRE SPRINKLER SYSTEM

FP102.DWG

Case, Lowe & Hart, Inc. 2484 Washington Blvd.

Suite 510 Ogden, Utah 84401

801.399.5821 Fax 801.399.0728 www.clhae.com

SHEET OF

DRAWN BY:

CHECKED BY:

DESCHUTES

PACIFIC NORTHWEST

DESCRIPTION

DISTRICT RANGER

ISSUE INFORMATION

PROJECT NO:

CAD DWG FILE:

DESIGNED BY:

MARK DATE

F0REST SUPERVISOR

FOREST ENGINEER

DATE

DATE

DATE

AGRICULTURE

The Pacific Northwest Region

FOREST SERVICE

UNITED STATES

DEPARTMENT

OF

PROJECT TEAM

Protection Consultants, Inc.

1199 S. Main Street #101 Centerville, Utah 84014

801.295.6070 Fax 801.677.0000

NATIONAL FOREST

REGION 6

GTJ

BAJ

GTJ

11/01/16

15072

ALARM SYSTEM UPGRADE

CACHE FIRE SPRINKLER AND

REDMOND AIR CENTER FIRE

11/01/16

1’-0" BD

1’-0" BD

2’-6" BD

2’-6" BD

2’-6" BD2’-6" BD

AND FACP.

SWITCH AND ALL WIRING BETWEEN FLOW SWITCH

SWITCH TO BE DEMOLISHED. REMOVE FLOW

EXISTING FIRE SPRINKLER RISER WITH WATER FLOW

FACP.

BETWEEN FIRE SUPPRESSION SYSTEM CONTROLS AND

REMOVE ALL WIRING, J-BOXES, CONDUIT AND WIRING

EXISTING FIRE ALARM SYSTEM TO BE DEMOLISHED.

FIRE SUPPRESSION SYSTEM CONTROLS FROM

TO REMAIN. DISCONNECT ACTIVATION RELAYS OF

EXISTING FIRE SUPPRESSION SYSTEM IN FUME HOOD

SAMPLING TUBE, J-BOXES, CONDUIT AND WIRING.

DEMOLISHED. REMOVE DETECTOR, HOUSING,

EXISTING DUCT MOUNTED SMOKE DETECTOR TO BE

NEW FIRE ALARM SYSTEM (SEE SHEET FP104).

AND FAN CONTROLS MAY REMAIN TO BE REUSED FOR

BETWEEN RELAY AND FACP. WIRING BETWEEN RELAY

DEMOLISHED. REMOVE RELAY AND ALL WIRING

EXISTING RELAY FOR FAN SHUTDOWN TO BE

FIRE ALARM DEMOLITION KEY NOTES

SYSTEM HAS BEEN INSTALLED AND TESTED.

SYSTEM TO OCCUR ONLY AFTER NEW FIRE ALARM

PHASE DEMOLITION OF EXISTING FIRE ALARM

BOXES (EXCEPT AS NOTED BELOW) AND WIRING.

NOTIFICATION APPLIANCES, CONDUIT, JUNCTION

POWER SUPPLIES, INITIATING DEVICES,

ENTIRETY. REMOVE ALL CONTROL EQUIPMENT,

CONVENTIONAL FCI) TO BE DEMOLISHED IN ITS

EXISTING FIRE ALARM SYSTEM (6 ZONE

PULL STATION (SEE SHEET FP104).

PRESENT) MAY REMAIN IF REUSED TO MOUNT NEW

AND WIRING. J-BOXES AND CONDUIT (WHERE

DEMOLISHED. REMOVE DEVICE, J-BOXES, CONDUIT

EXISTING FIRE ALARM PULL STATION TO BE

PRESENT) AND WIRING.

DEMOLISHED. REMOVE DEVICE, J-BOX, CONDUIT (IF

EXISTING SMOKE OR HEAT DETECTOR TO BE

ALARM SYSTEM (SEE SHEET FP104).

CONTROLS MAY REMAIN TO BE REUSED FOR NEW FIRE

FACP. WIRING BETWEEN RELAY AND EXHAUST FAN

REMOVE RELAY AND ALL WIRING BETWEEN RELAY AND

VERIFIED BY CONTRACTOR) TO BE DEMOLISHED.

(PURPOSE OF RELAY IS ASSEUME AND SHALL BE

EXISTING RELAY FOR EXHAUST FAN ACTIVATION

NOTIFICATION APPLIANCE (SEE SHEET FP104).

PRESENT) MAY REMAIN IF REUSED TO MOUNT NEW

AND WIRING. J-BOXES AND CONDUIT (WHERE

DEMOLISHED. REMOVE DEVICE, J-BOXES, CONDUIT

EXISTING FIRE ALARM NOTIFICATION APPLIANCE TO BE

1 01/8" = 1’-0" 4’ 8’ 16’

PUMP REPAIR

PUMP REPAIR

W A

R E

H O

U S

E

TOOL MAINTENANCE

MECHANICAL

PAINTING

OVEN REPAIR MEN

WOMEN

OFFICE

OFFICE

OFFICE

OFFICE

FIRE ALARM DEMOLITION PLAN - CACHE WAREHOUSE

FP103

Cache Warehouse Demolition Plan -

Fire Alarm

F

SD

SD

M

R

R

FP103.DWG

STORAGE

F A

P S

F A

C P

Case, Lowe & Hart, Inc. 2484 Washington Blvd.

Suite 510 Ogden, Utah 84401

801.399.5821 Fax 801.399.0728 www.clhae.com

SHEET OF

DRAWN BY:

CHECKED BY:

DESCHUTES

PACIFIC NORTHWEST

DESCRIPTION

DISTRICT RANGER

ISSUE INFORMATION

PROJECT NO:

CAD DWG FILE:

DESIGNED BY:

MARK DATE

F0REST SUPERVISOR

FOREST ENGINEER

DATE

DATE

DATE

AGRICULTURE

The Pacific Northwest Region

FOREST SERVICE

UNITED STATES

DEPARTMENT

OF

PROJECT TEAM

Protection Consultants, Inc.

1199 S. Main Street #101 Centerville, Utah 84014

801.295.6070 Fax 801.677.0000

NATIONAL FOREST

REGION 6

GTJ

BAJ

GTJ

11/01/16

15072

ALARM SYSTEM UPGRADE

CACHE FIRE SPRINKLER AND

REDMOND AIR CENTER FIRE

11/01/16

9 9

FIRE ALARM KEY NOTES

SIGNAL.

ACTIVATION OF WATER FLOW SWITCH AS A FIRE ALARM

WATER FLOW SWITCH TO NEW FACP. PROGRAM

ADDRESSABLE MONITOR MODULE AND CONNECT

SWITCH (INCLUDING 2 SETS OF CONTACTS). INSTALL

NEW FIRE SPRINKLER RISER WITH WATER FLOW

ADMINISTRATION BUILDING AS REQUIRED.

REVISE FACP PROGRAMMING OF EXISTING FACP IN

ADMINISTRATION BUILDING. ADD MODULES AND

SUPERVISORY AND TROUBLE SIGNALS TO FACP IN

ALARM SYSTEM SHALL RELAY FIRE ALARM,

COMPATIBLE WITH NEW FIRE ALARM SYSTEM. FIRE

FUNCTIONAL (NO SHORTS OR GROUND FAULTS) AND IF

BURIED CONDUIT MAY BE RE-USED IF COMPLETELY

SUPPRESSION PER NFPA 70. EXISTING WIRING IN

BUILDINGS. PROVIDE TRANSIENT VOLTAGE

WIRING IN EXISTING BURIED CONDUIT BETWEEN

ADJACENT ADMINISTRATION BUILDING. INSTALL

CACHE WAREHOUSE TO EXISTING SIMPLEX FACP IN

PROVIDE CIRCUITS TO CONNECT NEW FACP IN FIRE

FACP.

10.4.4. DETECTOR SHALL BE LISTED COMPATIBLE WITH

CONTROL EQUIPMENT IN ACCORDANCE WITH NFPA 72

INSTALL SMOKE DETECTOR ABOVE FIRE ALARM

AS A FIRE ALARM SIGNAL.

PROGRAM ACTIVATION OF FIRE SUPPRESSION SYSTEM

SUPPRESSION SYSTEM CONTROLS TO NEW FACP.

MODULE AND CONNECT ACTIVATION RELAY OF FIRE

TO REMAIN. INSTALL ADDRESSABLE MONITOR

EXISTING FIRE SUPPRESSION SYSTEM IN FUME HOOD

DEMOLISHED (SEE SHEET FP103) MAY BE REUSED.

CONTROLS AND EXISTING FIRE ALARM RELAY TO BE

BUILDING. CONTROL WIRING BETWEEN HVAC

MOUNTED OR SPOT TYPE SMOKE DETECTOR IN

FAN SHUTDOWN UPON ACTUATION OF ANY DUCT

EXCESS OF 2,000 CFM. PROGRAM RELAY TO INITIATE

OF ALL AIR HANDLING SYSTEMS WITH A CAPACITY IN

INSTALL ADDRESSABLE RELAY TO INITIATE SHUTDOWN

LEVEL.

MEZZANINE TO PROVIDE VISIBLE ALARM ON MEZZANINE

INSTALL STROBE ON ROOF DECK ABOVE STORAGE

ABOVE GRADE ON WEATHER-PROOF BACK BOX.

FOR EXTERIOR USE AND SHALL BE MOUNTED AT 10’-0"

AREAS. NOTIFICATION APPLIANCES SHALL BE LISTED

AUDIBLE AND VISIBLE ALARMS FOR EXTERIOR WORK

FIRE ALARM NOTIFICATION APPLIANCES TO PROVIDE

FOR SIGNIFICANT OCCUPANT LOAD. INSTALL EXTERIOR

SEASONAL WORK AREAS AND HAVE THE POTENTIAL

PORTIONS OF BUILDING EXTERIOR ARE USED AS

SPRINKLER RISER.

CONTACTS OF WATER FLOW SWITCH ON FIRE

POWER SUPPLY SWITCHED THROUGH NORMALLY OPEN

WATER FLOW ALARM. CONNECT BELL TO 120 VAC

FIRE DEPARTMENT CONNECTION TO PROVIDE LOCAL

INSTALL 10" ELECTRIC BELL ABOVE FIRE SPRINKLER

FIRE ALARM GENERAL NOTES

1.

2.

D. NFPA 72 2013 EDITION

C. NFPA 70 2015 EDITION

B. INTERNATIONAL FIRE CODE (IFC) - 2015 EDITION

A. INTERNATIONAL BUILDING CODE (IBC) - 2015 EDITION

APPLICABLE CODES AND STANDARDS:

3.

4.

5.

6.

7.

8.

9.

11.

POWER.

PROVIDE A MINIMUM OF 5 MINUTES OF ALARM

STANDBY POWER WITH AN ADIDTIONAL RESERVE TO

72. SIZE BATTERIES TO PROVIDE 24 HOURS OF

BATTERIES) POWER SUPPLY PER NFPA 70 AND NFPA

AND SECONDARY (24VDC USING TWO 12 VDC

INSTALL NEW PRIMARY (120 VAC) POWER SUPPLY

LOCATION OF EXISTING FACP TO BE DEMOLISHED.

PANEL (FACP). SURFACE MOUNT ON WALL AT

NEW SIMPLEX, ADDRESSABLE FIRE ALARM CONTROL

POWER.

PROVIDE A MINIMUM OF 5 MINUTES OF ALARM

STANDBY POWER WITH AN ADIDTIONAL RESERVE TO

72. SIZE BATTERIES TO PROVIDE 24 HOURS OF

BATTERIES) POWER SUPPLY PER NFPA 70 AND NFPA

AND SECONDARY (24VDC USING TWO 12 VDC

INSTALL NEW PRIMARY (120 VAC) POWER SUPPLY

SUPPLIES TO BE DETERMINED BY CONTRACTOR.

REQUIRED NUMBER AND LOCATION OF POWER

REQUIRED POWER CANNOT BE SUPPLIED BY FACP.

NOTIFICATION APPLIANCES IN BUILDING WHERE

AS REQUIRED TO PROVIDE 24 VDC POWER TO

INSTALL NOTIFICATION APPLIANCE POWER SUPPLIES

RELAY MAY BE REUSED.

BETWEEN EXHAUST FAN CONTROLS AND FIRE ALARM

VERIFIED BY CONTRACTOR). CONTROL WIRING

ACTIVATION OF WAREHOUSE EXHAUST FANS (TO BE

DEMOLISHED. FUNCTION OF RELAY IS ASSUMED TO BE

FIRE ALARM RELAY AT THIS LOCATION TO BE

INSTALL ADDRESSABLE RELAY TO REPLACE EXISTING

AFF.

SURFACE MOUNT ON WALL AT APPROXIMATELY 54"

AND ALLOW CONTROL OF FIRE ALARM SYSTEM.

INSTALL ANNUNCIATOR PANEL TO DISPLAY STATUS

MAY BE REUSED.

WIRING BETWEEN SOLENOID AND FIRE ALARM RELAY

DETECTOR OR FLOW SWITCH IN BUILDING. CONTROL

OPERATE SOLENOID UPON ACTUATION OF ANY

NEW ADDRESSABLE RELAY AND PROGRAM RELAY TO

SUPPLY TO BOILER. REPLACE EXISTING RELAY WITH

CONTRACTOR) TO ACTIVATE SOLENOID ON GAS

(LOCATION UNKNOWN - TO BE DETERMINED BY

EXISTING FIRE ALARM SYSTEM INCLUDES RELAY

10.

OF IBC, IFC AND NFPA 72.

ALARM SYSTEM SHALL COMPLY WITH ALL APPLICABLE PROVISIONS

ADMINISTRATION BUILDING. DESIGN AND INSTALLATION OF FIRE

CONNECTION TO EXISTING SIMPLEX FACP IN ADJACENT

SIMPLEX FIRE ALARM SYSTEM IN CACHE WAREHOUSE AND

OF EXISTING FIRE ALARM SYSTEM AND INSTALLATION OF NEW

SCOPE OF WORK: WORK SHALL INCLUDE COMPLETE DEMOLITION

WITH THE NEW FIRE ALARM CONTROL PANEL (FACP).

SYSTEMS. ALL INITIATING DEVICES SHALL BE LISTED COMPATIBLE

BE UL LISTED AND/OR FM APPROVED FOR USE IN FIRE PROTECTION

DEVICES USED FOR THE FIRE ALARM SYSTEM INSTALLATION SHALL

QUALITY ASSURANCE: ALL NEW EQUIPMENT, MATERIAL AND

THE CONSTRUCTION DOCUMENTS REQUIREMENTS OF NFPA 72.

INSTALLING ANY EQUIPMENT. SUBMITTALS SHALL CONFORM TO

JURISDICTION FOR REVIEW/APPROVAL PRIOR TO ORDERING OR

AND SUBMIT SHOP DRAWINGS TO ALL AUTHORITIES HAVING

SUBMITTALS: FIRE ALARM SYSTEM CONTRACTOR SHALL PREPARE

FOR RELAY TO OFF-PREMISE MONITORING STATION.

EXISTING SIMPLEX FACP IN ADJACENT ADMINISTRATION BUILDING

SYSTEM PROVIDES OFF-PREMISE NOTIFICATION OF STATUS TO

REQUIREMENTS FOR PROTECTED PREMISE FIRE ALARM SYSTEMS.

SYSTEM TYPE: FIRE ALARM SYSTEM SHALL MEET THE

EQUIVALENT AS PER NFPA 70 ARTICLE 760.

BE FPL (FIRE POWER LIMITED) WITH 300V INSULATION OR

COMPOUND. ALL WIRING USED IN THE FIRE ALARM SYSTEM SHALL

PARTITIONS SHALL BE FIRE STOPPED WITH A SUITABLE CAULKING

FLEXIBLE CONDUIT. ALL PENETRATIONS THROUGH RATED

GROUNDS. ALL WIRING SHALL BE INSTALLED IN RIGID, EMT OR

SHALL BE NEW. WIRING SHALL BE FREE OF OPENS, SHORTS AND

WIRING/CONDUIT: ALL WIRING (UNLESS OTHERWISE NOTED)

B CIRCUITS.

APPLIANCE CIRCUITS SHALL MEET THE REQUIREMENTS FOR CLASS

MEET THE REQUIREMENTS FOR CLASS A CIRCUITS. NOTIFICATION

WIRING STYLES (PER NFPA 72): INITIATING DEVICE CIRCUITS SHALL

MARKED AND IDENTIFIED AS "FIRE ALARM CIRCUIT".

MECHANICALLY PROTECTED AND SHALL BE PERMANENTLY

PANEL (EXISTING MAY BE REUSED). CIRCUIT SHALL BE

BRANCH CIRCUIT (20 AMP) FROM NEARBY POWER DISTRIBUTION

CONTROL EQUIPEMNT SHALL BE PROVIDED BY A DEDICATED

POWER: PRIMARY POWER SUPPLY TO NEW FIRE ALARM

F. DUCT MOUNTED SMOKE DETECTORS

E. FIRE SUPPRESSION SYSTEM IN FUME HOOD

D. FIRE SPRINKLER WATER FLOW SWITCH

INSTALLATION OF SMOKE DETECTORS

C. HEAT DETECTORS: INSTALL IN AREAS NOT SUITABLE FOR

INDICATED

ALARM CONTROL EQUIPMENT AND THROUGHOUT BUILDING AS

B. SMOKE DETECTORS: INSTALL SMOKE DETECTOR ABOVE FIRE

A. MANUAL PULL STATION

INITIATING DEVICES:

MAINTENANCE PERSONNEL AND REDMOND FIRE DEPARTMENT.

WITNESSED BY PROJECT ENGINEER, US FOREST SERVICE

ACCEPTANCE TESTS REQUIRED BY NFPA 72. TESTING SHALL BE

TESTING: CONTRACTOR SHALL SCHEDULE AND PERFORM ALL

NEW FIRE ALARM SYSTEM HAS BEEN INSTALLED AND TESTED.

DEMOLITION OF EXISTING FIRE ALARM SYSTEM TO OCCUR AFTER

BUILDING THROUGHOUT DURATION OF PROJECT. PHASE

PHASING: FIRE ALARM PROTECTION SHALL BE PROVIDED FOR

12.

ALL DETECTORS THAT MAY BE REQUIRED ARE SHOWN ON PLANS.

THE PHYSICAL CONFIGURATION OF THE EXISTING BUILDING. NOT

MEETING THE REQUIREMENTS OF NFPA 72 AND CONFORMING TO

NUMBER AND LOCATION OF DETECTORS FOR 100% COVERAGE

FIRE ALARM CONTRACTOR IS RESPONSIBLE FOR DETERMINING

1 01/8" = 1’-0" 4’ 8’ 16’

PUMP REPAIR

PUMP REPAIR

W A

R E

H O

U S

E

TOOL MAINTENANCE

MECHANICAL

PAINTING

OVEN REPAIR MEN

WOMEN

OFFICE

OFFICE

OFFICE

OFFICE

F

SD

SD

M

R

R

FP104.DWG

STORAGE

FAPS

FACP

Cache Warehouse Fire Alarm Plan -

FP104

FIRE ALARM PLAN - CACHE WAREHOUSE

FIRE ALARM CONTROL PANEL

SMOKE DETECTOR

FIRE ALARM PULL STATION

FIRE SPRINKLER WATER FLOW SWITCH

MONITOR MODULE

FAPS

FACP FIRE ALARM NOTIFICATION APPLIANCE POWER SUPPLY

F

M

R

SD DUCT MOUNTED SMOKE DETECTOR WITH HOUSING

FIRE ALARM CONTROL RELAY

R

N

N

R

N

N

WALL MOUNT HORN/STROBE ON EXISTING J-BOX

WALL MOUNT HORN/STROBE ON NEW J-BOX

CEILING MOUNT HORN/STROBE ON EXISTING J-BOX

CEILING MOUNT HORN/STROBE ON NEW J-BOX

CEILING OR WALL MOUNT STROBE ON NEW J-BOX

BACK BOX

WALL MOUNT HORN/STROBE ON NEW WEATHER-PROOF

EXTERIOR WATER FLOW BELL

N

30CD

NN

75CD75CD

N

75CD

N75CD

R

75CD

R

75CD

N

110CD

R

115CD

115CD

R

115CD

N

115CD

N

115CD

N

115CD

N

110CD

R

110CD

N

110CD

R

15CD

N

R

110CD

15CD

N

N

15CD

R

30CD

N

30CD

R

15CD

R

15CD

15CD

N

N

15CD

R

30CD

R

75CD

75CD

R

75CD

N

R

75CD

M

75CD

R

R

15CD

BELOW PLATFORM

DETECTORS ABOVE AND

OFFICE CEILING

DETECTOR BELOW

ROOF DECK

DETECTOR ON

ROOF DECK

DETECTOR ON

STORAGE PLATFORM

DETECTOR BELOW

A N

N

OFFICE CEILING

DETECTOR BELOW

R

H

H

H

H

H

H

ANN FIRE ALARM ANNUNCIATOR PANEL

HEAT DETECTOR

Case, Lowe & Hart, Inc. 2484 Washington Blvd.

Suite 510 Ogden, Utah 84401

801.399.5821 Fax 801.399.0728 www.clhae.com

SHEET OF

DRAWN BY:

CHECKED BY:

DESCHUTES

PACIFIC NORTHWEST

DESCRIPTION

DISTRICT RANGER

ISSUE INFORMATION

PROJECT NO:

CAD DWG FILE:

DESIGNED BY:

MARK DATE

F0REST SUPERVISOR

FOREST ENGINEER

DATE

DATE

DATE

AGRICULTURE

The Pacific Northwest Region

FOREST SERVICE

UNITED STATES

DEPARTMENT

OF

PROJECT TEAM

Protection Consultants, Inc.

1199 S. Main Street #101 Centerville, Utah 84014

801.295.6070 Fax 801.677.0000

NATIONAL FOREST

REGION 6

GTJ

BAJ

GTJ

11/01/16

15072

ALARM SYSTEM UPGRADE

CACHE FIRE SPRINKLER AND

REDMOND AIR CENTER FIRE

11/01/16

G001 - Title Sheet
FP101
FP102
FP103
FP104