RFB-04-27 DJJ-KCH Fire Alarm Replacement Campus Wide
Solicitation number
RFB 785 2600000648 4
Issued by
Kentucky

About this file

This is Addendum 3 to RFB-04-27 for the Kentucky Department of Juvenile Justice (DJJ) Fire Alarm Replacement Campus Wide project. The addendum provides clarifications and modifications to the original request for bids regarding the installation of a campus-wide fire alarm system at the Kentucky Children's Home (KCH) facility. The document addresses specific technical questions and requirements submitted by potential bidders, including clarifications on existing fire alarm system components, equipment specifications, installation procedures, and coordination with facility operations. Key modifications include adjustments to scope items, clarification of responsibilities between the contractor and DJJ, and additional technical specifications for the fire alarm replacement project. The addendum ensures that all bidders have consistent and accurate information regarding project requirements prior to submitting their proposals.

The addendum emphasizes the importance of bidder compliance with all specifications outlined in the original RFB and previous addenda. It provides technical guidance on system compatibility, testing requirements, and documentation standards that must be met throughout the project. The document clarifies the evaluation criteria and ensures that bids are evaluated fairly based on complete and accurate project specifications. All bidders must acknowledge receipt of Addendum 3 in their bid submissions to be considered responsive to the solicitation.

View the file

Other files

File Type Posted
Final_RFB_785_2600000648_2_SO_FORM.PDF PDF
Final_RFB_785_2600000648_3_SO_FORM.PDF PDF
Final_RFB_785_2600000648_4_SO_FORM.PDF PDF
Final_RFB_785_2600000648_1_SO_FORM.PDF PDF
Addendum 2.pdf PDF
Addendum 1.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COMMONWEALTH OF KENTUCKY

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

INVITATION TO BID NO: RFB-04-27

FOR: Fire Alarm Replacement Campus Wide Kentucky Children's Home Department of Juvenile Justice Lyndon, Kentucky

DATE: July 10, 2026

RFB-785-2600000648

ADDENDUM NO. Three (3)

BIDDER SHALL CONFORM TO THE FOLLOWING CHANGES AS SAME SHALL BECOME BINDING

UPON THE CONTRACT TO BE ISSUED IN RESPONSE TO THIS INVITATION TO BID.

Item 1: Refer to attached addendum for all additions, deletions, and/or changes to specifications and/or drawings.

END OF ADDENDUM

Invitation to Bid No. RFB-04-27 For: Fire Alarm Replacement Campus Wide Kentucky Children's Home Department of Juvenile Justice Lyndon, Kentucky

Janis Wilhoite, Statewide Procurement Analyst II Division of Engineering and Contract Administration

KHC Fire Alarm Replacement Campus Wide Addendum #2 July 10, 2026

Addendum Items (Questions and Responses):

1. Question: Can existing cabling be re-used for the new system?

Response: No, all cabling shall be new.

2. Question: Will a planned temporary fire alarm impairment for up to a set number of calendar days (~5) be permitted with prior notice and an approved fire watch, or is maintaining the existing system until the new system is online a hard requirement? The latter will greatly increase the effort and cost.

Response: No, all buildings with the exception of the Chapel will remain occupied.

3. Question: Is Fire-Lite and acceptable fire alarm manufacturer?

Response: No, please use the listed manufacturers in the specifications and addendum.

4. Question: On the contract documents under Division 28 Section 283100 11.8 “All electrical work is to be constructed and installed in accordance with plans and specifications which have been approved in their entirety and/or reflect any changes requested by the state fire marshal, as applicable or required. Electrical work shall not commence until such plans are in the hands of the electrical contractor. This seems to say as built drawings require an approval by the state fire marshal. Is that correct? And if so what time frame?

Response: An as built set of drawings reflecting any changes made during construction as well as any changes made from the permitting drawings are to be provided upon completion of construction.

5. Question: On sheet E301, PIV is not shown on plans. It appears to be locked and monitored electronically. Can you confirm if it needs to be monitored electronically and if so who is responsible for replacing the PIV Switch if it is non-functional as it appears that the box is currently damaged?

Response: The contractor is responsible for providing new connections to all building

PIV devices as well as monitoring these. If the existing PIV switch is damaged it is not the responsibility of the contractor to replace this.

6. Question: Will after work hours be permitted upon request?

Response: No, Work hours are from 8AM to 4PM. No weekends or state holidays or overtime.

7. Question: Is a fire watch required only for buildings that are occupied, or is it also required for unoccupied buildings? Additionally, who will be responsible for providing and managing the fire watch—the Owner or the Contractor?

Response: Fire watch is required for all buildings. The contractor is responsible for providing the fire watch per NFPA, State HBC and the Fire Marshal’s Office requirements.

8. Question: What are the permitted working hours for each building? Could you please identify which buildings are currently occupied and which are unoccupied?

Additionally, is after-hours or weekend work allowed for this project, and if so, are there any specific restrictions or timeframes that we should be aware of Response: Work hours are from 8AM to 4PM with no weekends or state holidays or overtime. All buildings are occupied with the exception of the Chapel.

9. Question: Who is responsible for the Elevator permit and re-inspection fees? Is there a specific elevator contractor required or under contract for the facility?

Response: The contractor shall include the elevator recertification price in their bid. DC elevator has serviced the Everett and Johnson Breckenridge buildings.

10. Question: First floor of the Chapel there is an existing beam smoke detector, and the drawings only show 4 existing smoke detectors to demo however there are not 4 existing smoke detectors in the chapel. Can we reuse or replace the existing beam smoke detector in lieu of installing 4 new detectors at the top of the high ceiling?

Response: It is acceptable to replace the existing beam detectors provided all NFPA and code requirements are met.

Addendum Items:

1. General:

a. The electrical set of the current ongoing renovation for the DJJ Lyndon

Building has been included for reference only as requested.

2. Rice Building Drawings:

a. Drawings E500D, E500F, E501D, E501F, E502D and E502F have been updated to include the correct floor plan.

3. General:

a. For clarification, the contractor shall include all new conduit/raceway and wiring for each new/replaced device in their bid.

RTA DATE

DECA LOG #

A&E FILE NO.

MLRCHECKED BY

DRAWN BY

DRAWING DATE

DRAWING INFORMATION

FRANKFORT, KENTUCKY

DIVISION OF ENGINEERING

DEPARTMENT FOR FACILITIES MANAGEMENT

FINANCE AND ADMINISTRATION CABINET

COMMONWEALTH OF KENTUCKY

DRAWING NO.

ACCOUNT NO.

PHASE

LEA

VDLF25

DECA REVIEWED

FOR INTENT ONLY

10411 Meeting Street

Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmtaegrs.com

RTA

05/04/2026

07/10/26

KCH Fire Alarm Replacement Campus Wide, DJJ Lyndon

523-CAW7-KC12-00

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text

AutoCAD SHX Text

COMMUNICATION

AutoCAD SHX Text

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text

AutoCAD SHX Text

MECH.

AutoCAD SHX Text

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text

AutoCAD SHX Text

MECH. ROOM

AutoCAD SHX Text

AutoCAD SHX Text

BREAK ROOM

AutoCAD SHX Text

AutoCAD SHX Text

DINING ROOM

AutoCAD SHX Text

AutoCAD SHX Text

RESTROOM

AutoCAD SHX Text

AutoCAD SHX Text

STAIRWAY

AutoCAD SHX Text

AutoCAD SHX Text

ELEV. LOBBY

AutoCAD SHX Text

AutoCAD SHX Text

ELEV. EQUIP. ROOM

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

GENERAL DEMOLITION NOTES :

AutoCAD SHX Text A. THICK DOTTED LINES INDICATE ITEMS FOR REMOVAL(U.O.N.) AND THIN SOLID THICK DOTTED LINES INDICATE ITEMS FOR REMOVAL(U.O.N.) AND THIN SOLID LINES INDICATE EXISTING ITEMS TO REMAIN. B. THE CONTRACTOR SHALL MAINTAIN THE CONTINUITY OF EXISTING CIRCUITS THAT THE CONTRACTOR SHALL MAINTAIN THE CONTINUITY OF EXISTING CIRCUITS THAT CONTAIN DEVICES OR EQUIPMENT THAT ARE TO REMAIN. WHEN DEMOLITION OF AN ELECTRICAL DEVICE (OR CIRCUIT) IS INDICATED ON THE DRAWINGS: THE CONTRACTOR SHALL ENSURE THAT OTHER DEVICES OR EQUIPMENT "UPSTREAM" OR "DOWNSTREAM"ON THE CIRCUITS SHALL REMAIN IN "PRE-DEMOLITION" WORKING ORDER. "LEFT-OVER" CIRCUIT BREAKERS SHALL REMAIN, BE SWITCHED TO OFF POSITION, AND BE LABELED AS SPARES IN THEIR PANELS. PROVIDE NEW TYPE WRITTEN DIRECTORIES FOR ALL PANELS AFFECTED. C. LOCATIONS OF DEVICES, CONNECTIONS, ETC., INDICATED ON THIS DRAWING WERE LOCATIONS OF DEVICES, CONNECTIONS, ETC., INDICATED ON THIS DRAWING WERE TAKEN FROM VARIOUS SOURCES. THEY ARE DIAGRAMMATIC ONLY AND ARE SUBJECT TO VARIATION FROM EXISTING CONDITIONS. CERTAIN EXISTING ELEMENTS MAY NOT BE INDICATED AT ALL. THE CONTRACTOR PROPOSING TO DO ANY PART OF THE WORK INDICATED HEREON SHALL VISIT THIS SITE AND DETERMINE TO HIS SATISFACTION THAT THEY MAY COMPLETE ALL WORK REQUIRED FOR THE BID WHICH HE PROPOSES. D. COORDINATE DISPOSAL OF ALL FIXTURES, DEVICES, ETC. (INDICATED FOR COORDINATE DISPOSAL OF ALL FIXTURES, DEVICES, ETC. (INDICATED FOR DEMOLITION) WITH OWNER. E. CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING WALLS AS REQUIRED CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING WALLS AS REQUIRED WHERE NEW FLUSH MOUNTED DEVICES ARE BEING REMOVED. F. CONTRACTOR SHALL PATCH AND REPAIR DUCTWORK AS REQUIRED WHEREVER CONTRACTOR SHALL PATCH AND REPAIR DUCTWORK AS REQUIRED WHEREVER DUCT SMOKE DETECTORS ARE BEING REMOVED OR INSTALLED. G. SOME EXISTING SIMPLEX PULL STATIONS AND NOTIFICATION DEVICES SERVE THE SOME EXISTING SIMPLEX PULL STATIONS AND NOTIFICATION DEVICES SERVE THE DURESS ALARM SYSTEM AND ARE NOT A PART OF THE EXISTING FIRE ALARM SYSTEM. CONTRACTOR SHALL VERIFY THAT ALL DEVICES TO BE REMOVED ARE A PART OF THE FIRE ALARM SYSTEM. H. CONTRACTOR SHALL STORE, PROTECT AND TURN OVER ALL REMOVED SMOKE CONTRACTOR SHALL STORE, PROTECT AND TURN OVER ALL REMOVED SMOKE DETECTORS, NOTIFICATION DEVICES AND FACP COMPONENTS TO OWNER.

AutoCAD SHX Text

TAGGED NOTES :

AutoCAD SHX Text

1. NOT USED.NOT USED.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DESCRIPTION OF REVISIONS

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

REVISION HISTORY OF THIS DRAWING

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DESCRIPTION OF REVISIONS

AutoCAD SHX Text

RICE - BASEMENT - DEMOLITION

AutoCAD SHX Text

SCALE: 3/16'' = 1'-0"

AutoCAD SHX Text E500D

AutoCAD SHX Text

AutoCAD SHX Text E500D

AutoCAD SHX Text

RICE - BASEMENT - DEMOLITION

A&E FILE NO.

MLRCHECKED BY

DRAWN BY

DRAWING DATE

DRAWING INFORMATION

FRANKFORT, KENTUCKY

DIVISION OF ENGINEERING

DEPARTMENT FOR FACILITIES MANAGEMENT

FINANCE AND ADMINISTRATION CABINET

COMMONWEALTH OF KENTUCKY

DRAWING NO.

ACCOUNT NO.

PHASE

LEA

VDLF25

DECA REVIEWED

FOR INTENT ONLY

10411 Meeting Street

Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmtaegrs.com

RTA

05/04/2026

07/10/26

KCH Fire Alarm Replacement Campus Wide, DJJ Lyndon

523-CAW7-KC12-00

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text

AutoCAD SHX Text

COMMUNICATION

AutoCAD SHX Text

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text

AutoCAD SHX Text

MECH.

AutoCAD SHX Text

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text

AutoCAD SHX Text

MECH. ROOM

AutoCAD SHX Text

AutoCAD SHX Text

BREAK ROOM

AutoCAD SHX Text

AutoCAD SHX Text

DINING ROOM

AutoCAD SHX Text

AutoCAD SHX Text

RESTROOM

AutoCAD SHX Text

AutoCAD SHX Text

STAIRWAY

AutoCAD SHX Text

AutoCAD SHX Text

ELEV. LOBBY

AutoCAD SHX Text

AutoCAD SHX Text

ELEV. EQUIP. ROOM

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text

EL

AutoCAD SHX Text

EL

AutoCAD SHX Text

EL

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text

CM

AutoCAD SHX Text

CM

AutoCAD SHX Text

CM

AutoCAD SHX Text

CM

AutoCAD SHX Text

CM

AutoCAD SHX Text

CM

AutoCAD SHX Text

CM

AutoCAD SHX Text

CM

AutoCAD SHX Text

CM

AutoCAD SHX Text

CM

AutoCAD SHX Text

CM

AutoCAD SHX Text

CM

AutoCAD SHX Text

CM

AutoCAD SHX Text

CM

AutoCAD SHX Text

CM

AutoCAD SHX Text

CM

AutoCAD SHX Text

CM

AutoCAD SHX Text

CM

AutoCAD SHX Text

CM

AutoCAD SHX Text

CM

AutoCAD SHX Text

CM

AutoCAD SHX Text

CM

AutoCAD SHX Text

CM

AutoCAD SHX Text

CM

AutoCAD SHX Text

GENERAL POWER/SYSTEMS NOTES :

AutoCAD SHX Text A. REFER TO THE ARCHITECT'S REFLECTED CEILING PLANS, ELEVATIONS, AND REFER TO THE ARCHITECT'S REFLECTED CEILING PLANS, ELEVATIONS, AND CASEWORK DETAILS FOR EXACT LOCATIONS OF ALL WALL AND CEILING MOUNTED ELECTRICAL DEVICES. B. CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, AS INDICATED ON CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, AS INDICATED ON THE FLOOR PLANS, WITH A MAXIMUM OF THREE (3) BRANCH CIRCUITS PER HOMERUN. EACH BRANCH CIRCUIT SHALL BE PROVIDED WITH A DEDICATED NEUTRAL CONDUCTOR. DEDICATED NEUTRAL CONDUCTORS SHALL BE CONSIDERED CURRENT CARRYING. IF ADDITIONAL CONDUCTORS ARE RAN IN THE SAME CONDUIT WITH THOSE INDICATED, CONTRACTOR SHALL DERATE ALL CURRENT CARRYING CONDUCTORS PER NEC 310.15(B)(3), AND UPSIZE CONDUIT AS REQUIRED PER NEC 300.17 AND ANNEX C. MULTIWIRE BRANCH CIRCUITS AS DEFINED IN NEC 100/210.4(CIRCUITS SHARING A COMMON NEUTRAL CONDUCTOR) SHALL NOT BE PERMITTED. C. IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES, SWITCHES, IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES, SWITCHES, ETC. IN AREA OF CONSTRUCTION. PROVIDE CLEAR ADHESIVE LABELS WITH BLACK LETTERING. IN HEALTHCARE FACILITIES, ENGRAVE EMERGENCY DEVICE COVERPLATES IN PATIENT CARE AREAS. MARK INSIDES OF ALL DEVICE BOXES WITH PANEL AND CIRCUIT NUMBERS. D. RECEPTACLES THAT ARE CONTROLLED BY AN AUTOMATIC MEANS SUCH AS RECEPTACLES THAT ARE CONTROLLED BY AN AUTOMATIC MEANS SUCH AS OCCUPANCY SENSOR OR ENERGY MANAGEMENT SYSTEM SHALL BE MARKED IN ACCORDANCE WITH NEC 406.3(E). E. LOCATIONS OF ELECTRICAL CONNECTIONS AND LOCAL DISCONNECTS SHALL BE LOCATIONS OF ELECTRICAL CONNECTIONS AND LOCAL DISCONNECTS SHALL BE COORDINATED WITH MECHANICAL AND PLUMBING CONTRACTORS TO ENSURE ACCESS AND WORKING CLEARANCE IS MAINTAINED PER NEC. NOTIFY OTHER TRADES OF REQUIRED CLEARANCE AREAS TO AVOID ROUTING OF OTHER SYSTEMS IN THESE AREAS. DO NOT INSTALL ELECTRICAL EQUIPMENT OVER EQUIPMENT NAMEPLATES OR ACCESS PANELS OR THROUGH ACCESS/MAINTENANCE CLEARANCES OF EQUIPMENT BY OTHER TRADES. F. REFER TO "SYSTEM INSTALLATION MATRIX" (ON SYSTEMS LEGEND SHEET) AND REFER TO "SYSTEM INSTALLATION MATRIX" (ON SYSTEMS LEGEND SHEET) AND SPECIFICATIONS FOR CONTRACTOR REQUIREMENTS OF EACH SYSTEM. G. THE CONTRACTOR SHALL ROUTE ALL "SYSTEM CONDUIT STUB-UPS" TO THE THE CONTRACTOR SHALL ROUTE ALL "SYSTEM CONDUIT STUB-UPS" TO THE NEAREST CORRIDOR CABLING PATH (SEE "STUB-UP" DETAILS). REFER TO CABLING PATH INSTALLATION DETAIL FOR ADDITIONAL REQUIREMENTS. H. CONTRACTOR SHALL PAINT ALL SYSTEMS CONDUIT STUB-UPS LIGHT BLUE FOR CONTRACTOR SHALL PAINT ALL SYSTEMS CONDUIT STUB-UPS LIGHT BLUE FOR SYSTEMS CABLING INTO THE CORRIDOR CABLING PATH. PROVIDE PULL STRINGS IN ALL NEW CONDUIT RUNS FOR SYSTEM CABLING INSTALLATION.

AutoCAD SHX Text

TAGGED NOTES :

AutoCAD SHX Text

1. NOT USED.NOT USED.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DESCRIPTION OF REVISIONS

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

REVISION HISTORY OF THIS DRAWING

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DESCRIPTION OF REVISIONS

AutoCAD SHX Text

RICE - BASEMENT - NEW WORK

AutoCAD SHX Text

SCALE: 3/16'' = 1'-0"

AutoCAD SHX Text E500F

AutoCAD SHX Text

AutoCAD SHX Text E500F

RICE - BASEMENT - NEW WORK

A&E FILE NO.

MLRCHECKED BY

DRAWN BY

DRAWING DATE

DRAWING INFORMATION

FRANKFORT, KENTUCKY

DIVISION OF ENGINEERING

DEPARTMENT FOR FACILITIES MANAGEMENT

FINANCE AND ADMINISTRATION CABINET

COMMONWEALTH OF KENTUCKY

DRAWING NO.

ACCOUNT NO.

PHASE

LEA

VDLF25

DECA REVIEWED

FOR INTENT ONLY

10411 Meeting Street

Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmtaegrs.com

RTA

05/04/2026

07/10/26

KCH Fire Alarm Replacement Campus Wide, DJJ Lyndon

523-CAW7-KC12-00

AutoCAD SHX Text

GENERAL DEMOLITION NOTES :

AutoCAD SHX Text A. THICK DOTTED LINES INDICATE ITEMS FOR REMOVAL(U.O.N.) AND THIN SOLID THICK DOTTED LINES INDICATE ITEMS FOR REMOVAL(U.O.N.) AND THIN SOLID LINES INDICATE EXISTING ITEMS TO REMAIN. B. THE CONTRACTOR SHALL MAINTAIN THE CONTINUITY OF EXISTING CIRCUITS THAT THE CONTRACTOR SHALL MAINTAIN THE CONTINUITY OF EXISTING CIRCUITS THAT CONTAIN DEVICES OR EQUIPMENT THAT ARE TO REMAIN. WHEN DEMOLITION OF AN ELECTRICAL DEVICE (OR CIRCUIT) IS INDICATED ON THE DRAWINGS: THE CONTRACTOR SHALL ENSURE THAT OTHER DEVICES OR EQUIPMENT "UPSTREAM" OR "DOWNSTREAM"ON THE CIRCUITS SHALL REMAIN IN "PRE-DEMOLITION" WORKING ORDER. "LEFT-OVER" CIRCUIT BREAKERS SHALL REMAIN, BE SWITCHED TO OFF POSITION, AND BE LABELED AS SPARES IN THEIR PANELS. PROVIDE NEW TYPE WRITTEN DIRECTORIES FOR ALL PANELS AFFECTED. C. LOCATIONS OF DEVICES, CONNECTIONS, ETC., INDICATED ON THIS DRAWING WERE LOCATIONS OF DEVICES, CONNECTIONS, ETC., INDICATED ON THIS DRAWING WERE TAKEN FROM VARIOUS SOURCES. THEY ARE DIAGRAMMATIC ONLY AND ARE SUBJECT TO VARIATION FROM EXISTING CONDITIONS. CERTAIN EXISTING ELEMENTS MAY NOT BE INDICATED AT ALL. THE CONTRACTOR PROPOSING TO DO ANY PART OF THE WORK INDICATED HEREON SHALL VISIT THIS SITE AND DETERMINE TO HIS SATISFACTION THAT THEY MAY COMPLETE ALL WORK REQUIRED FOR THE BID WHICH HE PROPOSES. D. COORDINATE DISPOSAL OF ALL FIXTURES, DEVICES, ETC. (INDICATED FOR COORDINATE DISPOSAL OF ALL FIXTURES, DEVICES, ETC. (INDICATED FOR DEMOLITION) WITH OWNER. E. CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING WALLS AS REQUIRED CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING WALLS AS REQUIRED WHERE NEW FLUSH MOUNTED DEVICES ARE BEING REMOVED. F. CONTRACTOR SHALL PATCH AND REPAIR DUCTWORK AS REQUIRED WHEREVER CONTRACTOR SHALL PATCH AND REPAIR DUCTWORK AS REQUIRED WHEREVER DUCT SMOKE DETECTORS ARE BEING REMOVED OR INSTALLED. G. SOME EXISTING SIMPLEX PULL STATIONS AND NOTIFICATION DEVICES SERVE THE SOME EXISTING SIMPLEX PULL STATIONS AND NOTIFICATION DEVICES SERVE THE DURESS ALARM SYSTEM AND ARE NOT A PART OF THE EXISTING FIRE ALARM SYSTEM. CONTRACTOR SHALL VERIFY THAT ALL DEVICES TO BE REMOVED ARE A PART OF THE FIRE ALARM SYSTEM. H. CONTRACTOR SHALL STORE, PROTECT AND TURN OVER ALL REMOVED SMOKE CONTRACTOR SHALL STORE, PROTECT AND TURN OVER ALL REMOVED SMOKE DETECTORS, NOTIFICATION DEVICES AND FACP COMPONENTS TO OWNER.

AutoCAD SHX Text

TAGGED NOTES :

AutoCAD SHX Text

1. NOT USED.NOT USED.

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

MECH.

AutoCAD SHX Text

MENS RR.

AutoCAD SHX Text

WOMENS RR.

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

CONFERENCE ROOM

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

COPY

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text

ELEVATOR LOBBY

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

HALL

AutoCAD SHX Text

CORRIDOR

AutoCAD SHX Text

UPPER LANDING

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DESCRIPTION OF REVISIONS

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

REVISION HISTORY OF THIS DRAWING

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DESCRIPTION OF REVISIONS

AutoCAD SHX Text

RICE - FIRST FLOOR - DEMOLITION

AutoCAD SHX Text

SCALE: 3/16'' = 1'-0"

AutoCAD SHX Text E501D

AutoCAD SHX Text

AutoCAD SHX Text E501D

RICE - FIRST FLOOR - DEMOLITION

A&E FILE NO.

MLRCHECKED BY

DRAWN BY

DRAWING DATE

DRAWING INFORMATION

FRANKFORT, KENTUCKY

DIVISION OF ENGINEERING

DEPARTMENT FOR FACILITIES MANAGEMENT

FINANCE AND ADMINISTRATION CABINET

COMMONWEALTH OF KENTUCKY

DRAWING NO.

ACCOUNT NO.

PHASE

LEA

VDLF25

DECA REVIEWED

FOR INTENT ONLY

10411 Meeting Street

Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmtaegrs.com

RTA

05/04/2026

07/10/26

KCH Fire Alarm Replacement Campus Wide, DJJ Lyndon

523-CAW7-KC12-00

AutoCAD SHX Text

GENERAL POWER/SYSTEMS NOTES :

AutoCAD SHX Text A. REFER TO THE ARCHITECT'S REFLECTED CEILING PLANS, ELEVATIONS, AND REFER TO THE ARCHITECT'S REFLECTED CEILING PLANS, ELEVATIONS, AND CASEWORK DETAILS FOR EXACT LOCATIONS OF ALL WALL AND CEILING MOUNTED ELECTRICAL DEVICES. B. CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, AS INDICATED ON CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, AS INDICATED ON THE FLOOR PLANS, WITH A MAXIMUM OF THREE (3) BRANCH CIRCUITS PER HOMERUN. EACH BRANCH CIRCUIT SHALL BE PROVIDED WITH A DEDICATED NEUTRAL CONDUCTOR. DEDICATED NEUTRAL CONDUCTORS SHALL BE CONSIDERED CURRENT CARRYING. IF ADDITIONAL CONDUCTORS ARE RAN IN THE SAME CONDUIT WITH THOSE INDICATED, CONTRACTOR SHALL DERATE ALL CURRENT CARRYING CONDUCTORS PER NEC 310.15(B)(3), AND UPSIZE CONDUIT AS REQUIRED PER NEC 300.17 AND ANNEX C. MULTIWIRE BRANCH CIRCUITS AS DEFINED IN NEC 100/210.4(CIRCUITS SHARING A COMMON NEUTRAL CONDUCTOR) SHALL NOT BE PERMITTED. C. IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES, SWITCHES, IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES, SWITCHES, ETC. IN AREA OF CONSTRUCTION. PROVIDE CLEAR ADHESIVE LABELS WITH BLACK LETTERING. IN HEALTHCARE FACILITIES, ENGRAVE EMERGENCY DEVICE COVERPLATES IN PATIENT CARE AREAS. MARK INSIDES OF ALL DEVICE BOXES WITH PANEL AND CIRCUIT NUMBERS. D. RECEPTACLES THAT ARE CONTROLLED BY AN AUTOMATIC MEANS SUCH AS RECEPTACLES THAT ARE CONTROLLED BY AN AUTOMATIC MEANS SUCH AS OCCUPANCY SENSOR OR ENERGY MANAGEMENT SYSTEM SHALL BE MARKED IN ACCORDANCE WITH NEC 406.3(E). E. LOCATIONS OF ELECTRICAL CONNECTIONS AND LOCAL DISCONNECTS SHALL BE LOCATIONS OF ELECTRICAL CONNECTIONS AND LOCAL DISCONNECTS SHALL BE COORDINATED WITH MECHANICAL AND PLUMBING CONTRACTORS TO ENSURE ACCESS AND WORKING CLEARANCE IS MAINTAINED PER NEC. NOTIFY OTHER TRADES OF REQUIRED CLEARANCE AREAS TO AVOID ROUTING OF OTHER SYSTEMS IN THESE AREAS. DO NOT INSTALL ELECTRICAL EQUIPMENT OVER EQUIPMENT NAMEPLATES OR ACCESS PANELS OR THROUGH ACCESS/MAINTENANCE CLEARANCES OF EQUIPMENT BY OTHER TRADES. F. REFER TO "SYSTEM INSTALLATION MATRIX" (ON SYSTEMS LEGEND SHEET) AND REFER TO "SYSTEM INSTALLATION MATRIX" (ON SYSTEMS LEGEND SHEET) AND SPECIFICATIONS FOR CONTRACTOR REQUIREMENTS OF EACH SYSTEM. G. THE CONTRACTOR SHALL ROUTE ALL "SYSTEM CONDUIT STUB-UPS" TO THE THE CONTRACTOR SHALL ROUTE ALL "SYSTEM CONDUIT STUB-UPS" TO THE NEAREST CORRIDOR CABLING PATH (SEE "STUB-UP" DETAILS). REFER TO CABLING PATH INSTALLATION DETAIL FOR ADDITIONAL REQUIREMENTS. H. CONTRACTOR SHALL PAINT ALL SYSTEMS CONDUIT STUB-UPS LIGHT BLUE FOR CONTRACTOR SHALL PAINT ALL SYSTEMS CONDUIT STUB-UPS LIGHT BLUE FOR SYSTEMS CABLING INTO THE CORRIDOR CABLING PATH. PROVIDE PULL STRINGS IN ALL NEW CONDUIT RUNS FOR SYSTEM CABLING INSTALLATION.

AutoCAD SHX Text

TAGGED NOTES :

AutoCAD SHX Text

1. NOT USED.NOT USED.

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

MECH.

AutoCAD SHX Text

MENS RR.

AutoCAD SHX Text

WOMENS RR.

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

CONFERENCE ROOM

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

COPY

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text

ELEVATOR LOBBY

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

HALL

AutoCAD SHX Text

CORRIDOR

AutoCAD SHX Text

UPPER LANDING

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text F

AutoCAD SHX Text

EL

AutoCAD SHX Text

CM

AutoCAD SHX Text

CM

AutoCAD SHX Text

CM

AutoCAD SHX Text

CM

AutoCAD SHX Text

CM

AutoCAD SHX Text

CM

AutoCAD SHX Text

CM

AutoCAD SHX Text

CM

AutoCAD SHX Text

CM

AutoCAD SHX Text

CM

AutoCAD SHX Text

CM

AutoCAD SHX Text F

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DESCRIPTION OF REVISIONS

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

REVISION HISTORY OF THIS DRAWING

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DESCRIPTION OF REVISIONS

AutoCAD SHX Text

RICE - FIRST FLOOR - NEW WORK

AutoCAD SHX Text

SCALE: 3/16'' = 1'-0"

AutoCAD SHX Text E501F

AutoCAD SHX Text

AutoCAD SHX Text E501F

RICE - FIRST FLOOR - NEW WORK

A&E FILE NO.

MLRCHECKED BY

DRAWN BY

DRAWING DATE

DRAWING INFORMATION

FRANKFORT, KENTUCKY

DIVISION OF ENGINEERING

DEPARTMENT FOR FACILITIES MANAGEMENT

FINANCE AND ADMINISTRATION CABINET

COMMONWEALTH OF KENTUCKY

DRAWING NO.

ACCOUNT NO.

PHASE

LEA

VDLF25

DECA REVIEWED

FOR INTENT ONLY

10411 Meeting Street

Prospect, Kentucky 40059 502 326.3085 f 502 326.2691 www.cmtaegrs.com

RTA

05/04/2026

07/10/26

KCH Fire Alarm Replacement Campus Wide, DJJ Lyndon

523-CAW7-KC12-00

AutoCAD SHX Text

GENERAL DEMOLITION NOTES :

AutoCAD SHX Text A. THICK DOTTED LINES INDICATE ITEMS FOR REMOVAL(U.O.N.) AND THIN SOLID THICK DOTTED LINES INDICATE ITEMS FOR REMOVAL(U.O.N.) AND THIN SOLID LINES INDICATE EXISTING ITEMS TO REMAIN. B. THE CONTRACTOR SHALL MAINTAIN THE CONTINUITY OF EXISTING CIRCUITS THAT THE CONTRACTOR SHALL MAINTAIN THE CONTINUITY OF EXISTING CIRCUITS THAT CONTAIN DEVICES OR EQUIPMENT THAT ARE TO REMAIN. WHEN DEMOLITION OF AN ELECTRICAL DEVICE (OR CIRCUIT) IS INDICATED ON THE DRAWINGS: THE CONTRACTOR SHALL ENSURE THAT OTHER DEVICES OR EQUIPMENT "UPSTREAM" OR "DOWNSTREAM"ON THE CIRCUITS SHALL REMAIN IN "PRE-DEMOLITION" WORKING ORDER. "LEFT-OVER" CIRCUIT BREAKERS SHALL REMAIN, BE SWITCHED TO OFF POSITION, AND BE LABELED AS SPARES IN THEIR PANELS. PROVIDE NEW TYPE WRITTEN DIRECTORIES FOR ALL PANELS AFFECTED. C. LOCATIONS OF DEVICES, CONNECTIONS, ETC., INDICATED ON THIS DRAWING WERE LOCATIONS OF DEVICES, CONNECTIONS, ETC., INDICATED ON THIS DRAWING WERE TAKEN FROM VARIOUS SOURCES. THEY ARE DIAGRAMMATIC ONLY AND ARE SUBJECT TO VARIATION FROM EXISTING CONDITIONS. CERTAIN EXISTING ELEMENTS MAY NOT BE INDICATED AT ALL. THE CONTRACTOR PROPOSING TO DO ANY PART OF THE WORK INDICATED HEREON SHALL VISIT THIS SITE AND DETERMINE TO HIS SATISFACTION THAT THEY MAY COMPLETE ALL WORK REQUIRED FOR THE BID WHICH HE PROPOSES. D. COORDINATE DISPOSAL OF ALL FIXTURES, DEVICES, ETC. (INDICATED FOR COORDINATE DISPOSAL OF ALL FIXTURES, DEVICES, ETC. (INDICATED FOR DEMOLITION) WITH OWNER. E. CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING WALLS AS REQUIRED CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING WALLS AS REQUIRED WHERE NEW FLUSH MOUNTED DEVICES ARE BEING REMOVED. F. CONTRACTOR SHALL PATCH AND REPAIR DUCTWORK AS REQUIRED WHEREVER CONTRACTOR SHALL PATCH AND REPAIR DUCTWORK AS REQUIRED WHEREVER DUCT SMOKE DETECTORS ARE BEING REMOVED OR INSTALLED. G. SOME EXISTING SIMPLEX PULL STATIONS AND NOTIFICATION DEVICES SERVE THE SOME EXISTING SIMPLEX PULL STATIONS AND NOTIFICATION DEVICES SERVE THE DURESS ALARM SYSTEM AND ARE NOT A PART OF THE EXISTING FIRE ALARM SYSTEM. CONTRACTOR SHALL VERIFY THAT ALL DEVICES TO BE REMOVED ARE A PART OF THE FIRE ALARM SYSTEM. H. CONTRACTOR SHALL STORE, PROTECT AND TURN OVER ALL REMOVED SMOKE CONTRACTOR SHALL STORE, PROTECT AND TURN OVER ALL REMOVED SMOKE DETECTORS, NOTIFICATION DEVICES AND FACP COMPONENTS TO OWNER.

AutoCAD SHX Text

TAGGED NOTES :

AutoCAD SHX Text

1. NOT USED.NOT USED.

AutoCAD SHX Text

MECH. RM.

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

MECH. RM.

AutoCAD SHX Text

MENS RR.

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

OFFICE

AutoCAD SHX Text

WOMENS RR.

AutoCAD SHX Text

ELEV. LOBBY

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DESCRIPTION OF REVISIONS

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

REVISION HISTORY OF THIS DRAWING

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DESCRIPTION OF REVISIONS

AutoCAD SHX Text

RICE - SECOND FLOOR - DEMOLITION

AutoCAD SHX Text

SCALE: 3/16'' = 1'-0"

AutoCAD SHX Text E502D

AutoCAD SHX Text

AutoCAD SHX Text E502D

RICE - SECOND FLOOR - DEMOLITION

C

SD

SD

BL

P

UON

EM

CFOI

OFOI

CFCI

OFCI

T

ANALOG CLOCK

C/S

J

DESCRIPTION

DP

S

S

X

S

S 3

S D

SK

PC

S

S 4

S

U

SL

N

OS

OS

SPL

IL

GROUND FAULT PROTECTED DUPLEX WITH WEATHER-

PROOF "WHILE IN USE" TYPE DIE-CAST METAL

COVERPLATE WITH LOCKABLE ENCLOSURE AT

OUTLET - SEE SPECIFICATIONS

WP

ER

ELECTRIC WATER COOLER RECEPTACLE:

COORDINATE EXACT LOCATION WITH PLUMBING

CONTRACTOR TO CONCEAL OUTLET(S) BEHIND

COOLER, PROVIDE MULTIPLE RECEPTACLES WHERE

REQUIRED BY MANUFACTURER, PROVIDE READILY

ACCESSIBLE DEAD FRONT GFCI DEVICE AT 18"

ADJACENT TO WATER COOLER FOR PROTECTION OF

WATER COOLER RECEPTACLE(S)

EWC

AUDIO/VIDEO INTERCOM STATION: MASTER WITH

SELECTIVE DOOR CONTROLS, POWER SUPPLIES & DOOR

RELAY CONTACTS AS REQUIRED FOR OPERATION OF

ANY DOOR IN THE SYSTEM AND VIEWING OF ANY

AUDIO/VIDEO INTERCOM REMOTE ON THE SYSTEM.

AIPHONE#AX-MV W/DESK STAND - COLOR BY ARCHITECT.

SAME AS ''IM'' EXCEPT WALL MOUNTED W

DOOR CONNECTION. PROVIDE ALL CONDUIT, JUNCTION

BOXES, CABLING, POWER, ETC. AS REQUIRED FOR NEW

DOOR CONTROLS. REFER TO SECURITYS DRAWINGS

FOR FURTHER REQUIREMENTS

DOOR RELEASE CARD READER STATION. PROVIDE

ANY ADDITIONAL ROUGH-IN FOR ''EMERGENCY

RELEASE'' OPERATOR STATIONS AS REQUIRED.

AUTOMATIC DOOR CONNECTION (MAY ALSO HAVE

ELECTRIC STRIKE/MAG-LOCK/ELECTRIFIED PANIC

CONNECTION - SEE ARCHITECTURAL HARDWARE

SPECIFICATIONS)

FLOORBOX, COMBINATION POWER AND LOW

VOLTAGE, REFER TO FLOORBOX SCHEDULE

B

SS

KEYED, LOCKED PULL STATION : DOUBLE ACTION.

STATION SHALL ONLY BE OPERABLE VIA KEY IN

POSSESSION OF STAFF.

CDCARBON MONOXIDE DUCT DETECTOR

POWER SUPPLY/CONTROL FOR AUDIO/VISUAL DEVICES

SAME AS ''CR'' EXCEPT MULLION MOUNT M

SLASH THROUGH ANY DEVICE INDICATES MOUNTING

ABOVE COUNTERTOP 4" ABOVE BACKSPLASH, OR AT 46"

WHERE NO COUNTER IS PRESENT

OVERHEAD PROJECTOR: PROVIDE DUPLEX

RECEPTACLE, ONE DATA, HDMI, 3.5mm AUDIO, AND

VGA OUTLET ON (3) PLATES

CCTV CAMERA: CEILING MOUNT DOME

WP

''DOG-HOUSE'' TYPE TWIN DUPLEX RECEPTACLE

WITH ONE DUPLEX RECEPTACLE ON BOTH SIDES

AUDIO/VIDEO INTERCOM STATION: REMOTE WITH

FLUSH-MTD S.S. ENCLOSURE. AIPHONE #AX-DVF.

SVS

VS

LV

PILOT LIGHT SWITCH (ILLUMINATED WHEN LOAD IS ON)

ILLUMINATED HANDLE LIGHT SWITCH (ILLUMINATED

WHEN LOAD IS OFF)

EMERGENCY AUTOMATIC TRANSFER SWITCH

FOR LIGHTING CONTROLS (REFER TO DETAIL)

FILLED CENTER BAR INDICATES INTEGRAL GROUND

FAULT PROTECTION (GFCI)

GANG RECEPTACLE IN COMBINATION WITH SWITCH

(PROVIDE DIVIDER IF LIGHTING CIRCUIT IS 277V)

NON-REVERSING MOTOR STARTER SNAP SWITCH

CONTRACTOR FURNISHED OWNER INSTALLED

CONTRACTOR FURNISHED CONTRACTOR INSTALLED

OWNER FURNISHED OWNER INSTALLED

OWNER FURNISHED CONTRACTOR INSTALLED

FLUSH MOUNTED REMOTE ALARM INDICATING

STATION/TEST SWITCH

CONNECTION TO SPRINKLER TAMPER

SWITCH WITH ADDRESSABLE MODULE

CONNECTION TO SPRINKLER FLOW

SWITCH WITH ADDRESSABLE MODULE

PHOTO-ELECTRIC SMOKE DETECTOR FOR PATIENT

ROOM MONITORING (SEE RISER)

PHOTO-ELECTRIC SMOKE DETECTOR

MAIN CONTROL PANEL CENTRAL PROCESSING

UNIT (CPU)

DOOR ALARM/POSITION SWITCH

DOOR POWER SUPPLY

DOOR DELAYED EGRESS/ELECTRIFIED PANIC

MECHANISM

TELEVISION SYSTEM OUTLET WITH DUPLEX

RECEPTACLE, COORDINATE LOCATION WITH WALL

BRACKET WHERE APPLICABLE

SURGICAL LIGHT INTENSITY CONTROL

LIGHT SWITCH:GENERAL PURPOSE

AS NOTED

AS NOTED

LIGHT SWITCH FOR UNDER-CABINET LIGHTS

6'-6'' TO

TOP

46" TO

LEVER

46" TO

LEVER

DESCRIPTION

PULL STATION : DOUBLE ACTION

AUDIO-ONLY NOTIFICATION APPLIANCE

VISUAL-ONLY NOTIFICATION APPLIANCE

AUDIO/VISUAL NOTIFICATION APPLIANCE

BELL / LIGHT

BELL ONLY

HEAT DETECTOR

CARBON MONOXIDE ALARM: SINGLE STATION

W/SOUNDER BASE

CARBON MONOXIDE AUDIO/VISUAL NOTIFICATION

APPLIANCE

DOOR HOLDER : WALL TYPE

DOOR HOLDER : CLOSURE TYPE

DUCT SMOKE DETECTOR

PRESSURE SWITCH

REMOTE L.C.D. FIRE ALARM ANNUNCIATOR

POST INDICATOR VALVE

ISOLATION MODULE

H.V.A.C. SMOKE DAMPER CONNECTION

UNLESS OTHERWISE NOTED

INDICATES EMERGENCY POWER

ELAPSED TIMER

SURFACE PLUG-MOLD

SPECIAL OUTLETS

HD

ABV CLG

CM

F

DH

ABV DOOR DH

ABV CLG DD

FS

TS

PS

46"

I

ZONE ADDRESSABLE MODULE Z

SM

ABBREVIATIONS

DESCRIPTION

XLSL

STRIP FIXTURE

CROSS-HATCHING INDICATES LIGHT IS POWERED

FROM THE EMERGENCY-CRITICAL BRANCH

PARALLEL-HATCHING INDICATES LIGHT IS POWERED

FROM THE EMERGENCY-LIFE SAFETY BRANCH

PANEL FURNITURE

POWER OUTLETS

SIMPLEX RECEPTACLE

DUPLEX RECEPTACLE-SAFETY TYPE,

TAMPER-RESISTANT

DUPLEX RECEPTACLE

QUADRUPLEX RECEPTACLE

JUNCTION BOX, CEILING OR WALL

VOLTAGE/1PH RECEPTACLE, AS NOTED

VOLTAGE/3PH RECEPTACLE, AS NOTED

SS INDICATES SURGE SUPPRESION TYPE OUTLET(S)

EXAM LIGHT SWITCH

NIGHT LIGHT SWITCH WITH CONSTANTLY

ILLUMINATED HANDLE

DIMMER SWITCH

THREE-WAY SWITCH

FOUR-WAY SWITCH

KEYED SWITCH

OCCUPANCY OR VACANCY SENSOR SWITCH

OCCUPANCY OR VACANCY SENSOR, CEILING MOUNT

LOW VOLTAGE MOMENTARY SWITCH

PHOTO-CELL AS NOTED

SURGICAL/EXAM LIGHT

EXIT LIGHT (CEILING, END, WALL MOUNT)

CLOCKS

ET

LIGHTING

REFER TO LUMINAIRE SCHEDULE FOR EXACT FIXTURE

SPECIFICATIONS, MOUNTING HEIGHTS, ETC.

SPECIAL VIDEO SYSTEM SIGNAL INPUT

SECURITY PANIC ALARM

SECURITY INTERCOM

SECURITY ACCESS CONTROL

SECURITY CCTV VIDEO SURVEILLANCE

PANIC ALARM BUTTON

PANIC ALARM ANNUNCIATOR

PANIC ALARM POWER SUPPLY CABINET

DOOR RELEASE KEYSWITCH STATION

DOOR RELEASE KEYPAD STATION

MOTION SENSOR DOOR CONTROL

REMOTE DOOR RELEASE PUSH-BUTTON

CCTV CAMERA: WALL MOUNT DOME

CCTV POWER SUPPLIES/CONTROL PANEL 46"

46"

DOOR

FRAME

ABV DOOR

8" ACT

DESCRIPTION

WALL, CLG

80"

CLG

CLG

CLG

WALL

54"

46"

46"

46"

46"

46"

46"

46"

46"

46"

46"

46"

46"

46"

1'-6"

1'-6"

1'-6"

1'-6"

46"

1'-6"

1'-6"

ON CNTR.

2'-2"

CLG

AS NOTED

46"

46"

18''

46"

46"

CLG

46"

6'-0''

46"

46"

CEIL.

CLG

7'-0"

S

CLG

S

FLOOR

S

S

S M

TELEVISION SPLITTERS/AMPLIFIERS/DISTRIBUTION

TELEVISION

46" TV-HE

D R

A W

IN

G

S

Y M

B O

L

AMBER STROBE 80''

SURFACE OR SUSPENDED CEILING FIXTURE (SLASH

INDICATES RECESSED)

POLE MOUNTED AREA LIGHT

EMERGENCY BATTERY WALL-PACK

WALL MOUNT FIXTURE ,

FLOODLIGHT

V

A

F

F K

F

GRAPHICS DISPLAY TERMINAL

RI

INDICATES VANDAL-PROOF POLYCARBONATE COVER,

VANDAL PROOF COVERS SHALL BE UL LISTED FOR USE

WITH THE SPECIFIC DEVICE THEY ARE PROTECTING

PC

80"

CLG

WALL

WALL

7'-6''

FIREMAN'S PHONE JACK FP

ADDRESSABLE RELAY MODULE R

WALL

ACCESS CONTROL POWER SUPPLIES/CONTROL PANEL 46"

46"

ABV CLG

ELECTRIC STRIKE AT LATCH

MAGNETIC LOCK(S) ABV DOOR

INDICATES EXTERIOR CAMERA RATED FOR

CONDITIONS, WET LOCATION LISTED, WITH

AUXILLARY HEATER

PTZINDICATES CAMERA WITH PAN/TILT/ZOOM FUNCTION

FLOORBOX, POWER ONLY, AS SCHEDULED FLOOR

FIRE RATED POKE-THRU FLOOR BOX, COORDINATE

EXACT COVER REQUIREMENTS WITH ARCHITECTURAL

FINISHES, DEVICES AS SCHEDULED

DESCRIPTION

K

DB

DB

WP

DOORBELL PUSHBUTTON STATION, PROVIDE COMPLETE

WITH TRANSFORMER (MOUNT ABOVE CEILING IN

CORRIDOR NEAR PUSH-BUTTON) AND ALL

ACCESSORIES, POWER FROM NEAREST AVAILABLE 120V

NORMAL POWER GENERAL RECEPTACLE CIRCUIT,

NUTONE OR EQUAL

DOORBELL AUDIO/VISUAL STATION, PROVIDE PROVIDE

CONNECTION TO PUSHBUTTON STATION IN AREA.

COORDINATE EXACT AUDIO SOUND (CHIME, BUZZER,

ETC.) DESIRED WITH OwNER/ARCHITECT, NUTONE OR

EQUAL

PLUMBING FIXTURE ELECTRIC EYE TRANSFORMER

CONNECTION. TRANSFORMER SHALL BE 120V-24V.

MOUNT ABOVE SUSPENDED ACCESSIBLE CEILING IN J-

BOX. PROVIDE ADDITIONAL TRANSFORMERS OF SAME

TYPE AS/IF NEEDED

PROVIDE CONNECTION TO HAND DRYER (SEE

ARCHITECTURAL SPECIFICATIONS)

VERIFY WITH

ARCHITECT

C

INDICATES MOUNTING ABOVE COUNTER-TOP,

2" ABOVE BACKSPLASH, NO HIGHER THAN 48''

WG

WIREGUARD - PROVIDE MANUFACTURER'S

SPECIFIC GUARD FOR DEVICE NOTED

BOX ON ANY DEVICE INDICATES SURFACE MOUNTED

BACKBOX/WIREMOLD

CONDUIT CONCEALED IN WALLS OR IN CEILING

SPACE: ARROW(S) INDICATE(S) HOME RUN & #

OF CIRCUITS: HASHMARKS INDICATE # OF

CONDUCTORS. DASHED LINE INDICATES

CONDUIT BELOW FLOOR.

WIREWAY WITH REMOVABLE COVER (SIZE AS NOTED)

PANELBOARD, SURFACE OR FLUSH MOUNTED,

HATCHING INDICATES EMERGENCY

EQUIPMENT TAG, REFER TO EQUIPMENT SCHEDULE

MECHANICAL EQUIPMENT DESIGNATOR

(SEE MECH. SCHEDULES)

EQUIPMENT HARDWIRE CONNECTION (SEE DETAIL)

KITCHEN EQUIPMENT OUTLET COUPLING

CONNECTION (SEE DETAIL)

AS SHOWN

AS SHOWN

AS NOTED

AS SHOWN

MISCELLANEOUS

DISCONNECT SWITCH

MAGNETIC STARTER

MAGNETIC COMBINATION STARTER

ENCLOSED FLUSH MTD. CIRCUIT BREAKER

WEATHERPROOF - NEMA-3R, WET LOCATION LISTED.

PROVIDE COVERS, RATINGS, ETC, AS SUITABLE FOR

OUTDOORS.

TRENCH DUCT (SIZE AS NOTED)

PUSHBUTTON STATION

FLEXIBLE CONDUIT

TRANSFORMER

TAGGED NOTE

REVISION TAG

WIRE BASKET CABLE TRAY, SIZE AS NOTED

LOW VOLTAGE CABLE PATH

5'-0"

5'-0"

5'-0"

5'-0"

46"

46"

7'-6''

6'-6'' TO TOP

XPEXPLOSION PROOF - PROVIDE WIRING METHODS,

ENCLOSURES, RATINGS, ETC. AS SUITABLE FOR

HAZARDOUS LOCATION.

SURGE PROTECTION DEVICE

GENERATOR ANNUNCIATOR PANEL - SEE

SPECIFICATIONS

46"

THERMOSTAT PROVIDED BY MECHANICAL

CONTRACTOR, ELECTRICAL CONTRACTOR SHALL

PROVIDE BACK-BOX CONDUIT STUB-UP, REFER TO

MECHANICAL DRAWINGS FOR LOCATIONS

PANEL FURNITURE DUPLEX RECEPTACLE. PROVIDE

ALL WIRING AS REQUIRED, COORDINATE EXACT

INSTALLATION REQUIREMENTS AND LOCATIONS WITH

OWNER'S PANEL FURNITURE VENDOR

PANEL FURNITURE DATA/VOICE OUTLET. PROVIDE ALL

WIRING AS REQUIRED, COORDINATE EXACT

INSTALLATION REQUIREMENTS AND LOCATIONS WITH

OWNER'S PANEL FURNITURE VENDOR

POWER CONNECTION TO PANEL FURNITURE, PROVIDE

SEAL-TIGHT CONDUIT CONNECTION FROM RECESSED

WALL BOX TO PANEL FURNITURE, PROVIDE FINAL

CONNECTIONS TO PANEL FURNITURE AS REQUIRED BY

PANEL FURNITURE VENDOR

1'-6"

COMBINATION POWER AND LOW VOLTAGE CONNECTION

TO PANEL FURNITURE, PROVIDE SEAL-TIGHT CONDUIT

CONNECTION FROM RECESSED WALL BOX TO PANEL

FURNITURE, PROVIDE FINAL CONNECTIONS TO PANEL

FURNITURE AS REQUIRED BY PANEL FURNITURE

VENDOR

C A

B L

IN

G

/C O

N D

U C

T O

R S

O

F O

I

C A

B L

IN

G /C

O N

D U

C T

O R

S

O F

C I

C A

B L

IN

G

/C O

N D

U C

T O

R S

C

F C

I

IT

E

M U

S E

D O

N P

R O

J E

C T

D E

V

IC

E S

O

F C

I

D E

V

IC

E S

C

F C

I

SYSTEM D

E

V

IC

E S

O

F O

I

RF

SECURITY: PANIC ALARM

SECURITY: ACCESS CONTROL

SECURITY: INTERCOM

SECURITY: CCTV

PATIENT ROOM MOTION DETECTION

SYSTEM

RESPONSIBILITY

MATRIX

OVERHEAD PAGING

FIRE ALARM

TELEVISION

DATA PROCESSING

TELEPHONE

LOCAL SOUND

TELEMETRY

RF TRACKER

PATIENT DOOR TOP LIGATURE ALARM

NURSE CALL

SYSTEM RESPONSIBILITY GENERAL NOTES:

A. REFER TO VENDOR DRAWINGS FOR COMPLETE SCOPE OF WORK RELATING TO

VENDOR-FURNISHED EQUIPMENT. ALL WORK INDICATED ON VENDOR DRAWINGS

SHALL BE INCLUDED BY THE CONTRACTOR.

B. REFER TO ARCHITECTURAL DOOR HARDWARE SPECIFICATIONS FOR ACCESS

CONTROL DEVICE SPECIFICATIONS AND FURTHER REQUIREMENTS.

C. PROVIDE BACKBOXES AND CONDUIT WITH PULL-STRINGS FOR ALL SYSTEMS.

CONTRACTOR SHALL VERIFY BACKBOX SIZES, CONDUIT, ETC. AND EXACT

INSTALLATION LOCATIONS/REQUIREMENTS WITH SUCCESSFUL VENDORS OF ALL

SYSTEMS PRIOR TO CONSTRUCTION.

D. AT ALL SYSTEMS EQUIPMENT CABINET/TERMINAL BOARD LOCATIONS,

CONTRACTOR SHALL PROVIDE SIZE AND NUMBER OF CONDUIT STUB-OUTS TO

CABLE PATHS AS REQUIRED BY SYSTEM VENDORS, TERMINATE CONDUITS AT

CABINETS/ON BACKBOARDS AS REQUIRED. COORDINATE EXACT REQUIREMENTS

WITH APPROPRIATE VENDORS PRIOR TO CONSTRUCTION.

E. REFER TO SPECIFICATIONS FOR REQUIREMENTS APPLICABLE TO ALL SYSTEMS

INCLUDING CABLING, CABLE MANAGEMENT, INSTALLATION, GROUNDING, TESTING,

LABELING, ETC.

F. WHERE INDICATED AS CFCI, THE CONTRACTOR SHALL PROVIDE THE SYSTEM

COMPLETE, INCLUDING ALL ROUGH-INS, CABLING, DEVICES, POWER, ETC. THE

CONTRACTOR SHALL CONTACT THE LISTED VENDOR FOR PRICING PRIOR TO BID.

ALL SYSTEMS SHALL MATCH EXISTING FACILITY STANDARDS AND BE FULLY

COMPATIBLE WITH ANY EXISTING SYSTEMS. ALL SYSTEM VENDORS SHALL

COORDINATE EXACT SYSTEM REQUIREMENTS WITH OWNER PRIOR TO BID. NEW

COMPONENTS SHALL BE INTERCONNECTED WITH EXISTING SYSTEMS WHERE

POSSIBLE. ALL NEW SYSTEM DESIGNS AND PROGRAMMING SHALL BE

COORDINATED WITH THE OWNER PRIOR TO ORDERING. ALL PROGRAMMING SHALL

BE INCLUDED AS REQUIRED BY THE OWNER. PROVIDE 4 HOURS OF TRAINING FOR

EACH SYSTEM.

PPPOWER POLE AS NOTED

84''

DIGITAL CLOCK: SINGLE FACE

DIGITAL CLOCK: DUAL FACE

CLOCK SYSTEM HEAD END

84''

84''

84''

SECURITY INTRUSION DETECTION

MOTION DETECTOR CLG

MOTION DETECTOR KEYPAD CONTROLLER 46"

SECURITY SYSTEM HEAD END 46"

SWITCHES

MOMENTARY CONTACT SWITCH

HAND-OFF-AUTO 3-POSTION SWITCH

TIMER SWITCH

S MC

S HOA

S T

46"

46"

46"

M

SV

S

S

V

1'-6''

46"PAGING SYSTEM AMPLIFIER/TUNER CABINET

PAGING MICROPHONE

WALL VOLUME CONTROL

PAGING SPEAKER: WALL

PAGING SPEAKER W/ VOLUME CONTROL

PAGING SPEAKER: CEILING CLG

CLG

8'-0"

46"

OVERHEAD PAGING

VANDAL PROOF / WEATHERPROOF WALL

MOUNTED PAGING SPEAKER. QUAM VP1

EXTERIOR VANDAL PROOF / WEATHERPROOF WALL

MOUNTED PAGING SPEAKER, SHALL BE PAINTED

COLOR SELECTED BY ARCHITECT/OWNER. QUAM VP6

RECESSED WALL MOUNTED PAGING SPEAKER

DUKANE 5A606 SPEAKER. ATLAS 417-8WD

WALL MOUNTED PAGING HORN

CALL INITIATION STATION

LCD WALL DISPLAY

8'-0"

9'-0"

SEE

FLOOR

PLANS

SEE

FLOOR

PLANS

46"

S

H

S

S

C

LD

R

EXT.

FIRE ALARM

WP

RADIOLOGY EQUIPMENT

SECURITY INTRUSION DETECTION

PHYSIOLOGICAL/TELEMETRY MONITORING

E,EMINDICATES EMERGENCY POWER

SYSTEM

SYMBOL

PUSH-TO-EXIT BUTTON 46"

SURFACE WIRE-MOLD

PE

PA

MK

MD

SEC-M

2DC

DC

CLOCK

GEN-A

SPD

J

J

ML

ES

SEC-A

GDT

AS

NAC

CC

CC

CR

RR

DP

DA

IM

KP

IR

KS

MS

DC

CR

DS

AD

IM

PIV

FAA

FACP

SEC-P

PA

PB

SEC-C

J

T

FP

D R

A W

M

B O

L

D R

A W

M

B O

L

D R

A W

M

B O

L

AS SHOWNLADDER CABLE TRAY, SIZE AS NOTED

AS SHOWNSOLID BOTTOM CABLE TRAY, SIZE AS NOTED

EQUIP-1

PLUMBING FIXTURE SOLENOID VALVE/ELECTRIC EYE

SENSOR CONNECTION. COORDINATE EXACT

CONNECTION REQUIREMENTS WITH MANUFACTURER.

GROUND

NEUTRAL

PHASE

FIREMAN'S KNOX BOX CONNECTION KB

REMOTE FIRE ALARM ANNUNCIATOR W/ MICROPHONE 54" FAAM

WALL, CLG

WALL, CLG V

A

F

CM

INDICATES CHIME AUDIBLE NOTIFACTION CH

DEVICE USED FOR ELEVATOR CONTROL EL

FIRE ALARM CONTROL EXTENDER EXT

4'-6''

TRANSPONDER CABINET 46" TRAN

BE , BR

PROJECTED BEAM SMOKE DETECTOR; EMITTER

(BE) AND RECEIVER (BR)

FLOOR

AV

AUDIO/VISUAL SYSTEM OUTLET WITH DUPLEX

RECEPTACLE, REFER TO ASSOCIATED DETAIL FOR

ADDITIONAL INFORMATION

1'-6"

COMBINATION POWER AND DATA OUTLET LOCATION,

REFER TO ASSOCIATED DETAIL FOR ADDITIONAL

INFORMATION

1'-6"

COMBINATION POWER AND DATA OUTLET LOCATION,

GFCI DUPLEX RECEPTACLE, REFER TO ASSOCIATED

DETAIL FOR ADDITIONAL INFORMATION

1'-6"

1'-6"

FF

DEAD FRONT GFCI DEVICE, LABEL AND INSTALL IN

READILY ACCESSIBLE LOCATION

FILLED OUTER BARS INDICATES INTEGRAL INTEGRAL

USB OUTLETS IN ADDITION TO POWER RECEPTACLES

1'-6"

, J

VARIABLE FREQUENCY DRIVE 5'-0"

CIRCLE ON ANY DEVICE INDICATES DEVICE FED FROM

STUB UP CONDUIT

MOTOR CONNECTION, REFER TO EQUIPMENT

CONNECTION SCHEDULE

DUPLEX RECEPTACLE, CEILING MOUNTED CLG

PAY

#D/#V

#D

INTERMEDIATE DISTRIBUTION FRAME - REFERENCE

DATA SYSTEM SCHEMATICS AND DETAILS FOR

ADDITIONAL REQUIREMENTS

MAIN DISTRIBUTION FRAME - REFERENCE DATA

SYSTEM SCHEMATICS AND DETAILS FOR ADDITIONAL

REQUIREMENTS

WIRELESS ACCESS POINT WITH PROVISIONS FOR (1

DATA OUTLET FOR ANTENNA. PROVIDE A COMPLETE

DATA OUTLET WITH FACEPLATE ABOVE CEILING,

MOUNTED AT AN ACCESSIBLE HEIGHT NO MORE THAN

24" ABOVE CEILING. AT EACH OUTLET, PROVIDE A 20'

COIL OF CABLE AHEAD OF THE OUTLET FOR

ADJUSTMENT OF FINAL OUTLET LOCATION. THE

CONTRACTOR SHALL COORDINATE EXACT LOCATIONS

WITH THE OWNER AND ADJUST OUTLET LOCATIONS AT

SUBSTANTIAL COMPLETION TO ACCOMMODATE

OWNER'S WAP LOCATIONS. WAP'S ARE OWNER-

FURNISHED, OWNER-INSTALLED

TELECOMMUNICATIONS SYSTEM BACKBOARD. PROVIDE

96''H x 3/4''D FIRE-RETARDENT PLYWOOD BACKBOARD

WITH TWO (2) COATS OF NON-C0NDUCTIVE, FIRE-

RETARDANT LIGHT GRAY PAINT, #3/0 TO GROUND BAR AT

MAIN SERVICE SWITCHBOARD, 30-PT GROUND BAR AND

A 6'-0'', #3 AWG PIGTAIL AT BACKBOARD. INSTALL BOARD

AT 2' AFF. (LENGTH OF BOARD AS INDICATED ON FLOOR

PLAN)

WAP

DATA OUTLET : NUMBER BESIDE OUTLET

INDICATES NUMBER OF DATA JACKS

VOICE OUTLET : NUMBER BESIDE OUTLET

INDICATES NUMBER OF VOICE JACKS

COMBINATION OUTLET : NUMBER BESIDE OUTLET

INDICATES NUMBER OF DATA/VOICE JACKS

TELEMETRY ANTENNA

RF TRACKER ANTENNA

DATA / VOICE

AS REQ'D.OUTLET (VOICE ONLY) : PAYPHONE TYPE

1'-6"

1'-6"

1'-6"

CLG

CLG

#V

MDF

IDF

TEL

CONDUIT UP

CONDUIT DOWN

GROUND BUS BAR ON INSULATED STANDOFFS 2'-0''

AS SHOWNBUS DUCT, AMPERAGES AS NOTED

M O

U N

T

H E

IG

H

T

T O

N T

E R

O F

B O

X

M O

U N

T

IG

H

T

N T

E R

O F

B O

X

M O

U N

T

IG

H

T

N T

E R

O F

B O

X

M O

U N

T

IG

H

T

N T

E R

O F

B O

X

PROVIDE FIRE ALARM CONNECTION TO DOOR INDICATED

SA COORDINATED WITH SECURITY VENDOR.

FDDOOR

DBDURESS BUTTON

ARCHITECTSK E R S E Y A N D K E R S E Y

RTA DATE

DECA LOG #

A&E FILE NO.

CHECKED BY

DRAWN BY

DRAWING DATE

DRAWING INFORMATION

DRAWING NO.

AS BUILT DATE

PHASE

DATEDESCRIPTION OF REVISIONS

REVISION HISTORY OF THIS DRAWING

DATEDESCRIPTION OF REVISIONS

FRANKFORT, KENTUCKY

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

KENTUCKY DEPARTMENT OF JUVENILE JUSTICE

FINANCE AND ADMINISTRATION CABINET

COMMONWEALTH OF KENTUCKYACCOUNT NO(S).

Fax 502 585 2728 kerseyandkersey.com

Louisville, KY 40204

Tel 502 583 0094

839 East Gray Street Suite 207

Lexington, KY 40507

201 West Short Street Commiskey, IN 47227

Tel 812 873 1287

9307 West 1000 North

Tel 859 303 8439

LOUISVILLE, KENTUCKY LEXINGTON, KENTUCKY MADISON, INDIANA

DJJ - LYNDON RENOVATION

8711 LAGRANGE ROAD

LOUISVILLE, KY

2259 / 2361

523-CBOB-LY-0000

523-CAEC-JF-01-00

DJJ Lyndon Facilities:

DJJ Control Room:

CONFORMED SET 11-15-24

/1 /2

:0

:2

P

M

E100

ELECTRICAL LEGEND

06/07/2024

RTA

GTJ/GTH

MLR

NO SCALE

ELECTRICAL LEGEND

GENERAL NOTES (LEGEND):

A. EACH CONTRACTOR, PROPOSER, SUPPLIER AND/OR MANUFACTURER SHALL REFER TO ALL DOCUMENTS PERTAINING TO THIS PROJECT AND COORDINATE ACCORDINGLY SO AS TO ENSURE ADEQUACY OF FIT, COMPLIANCE WITH SPECIFICATIONS, PROPER VOLTAGE AND CURRENT CHARACTERISTICS TO AVOID CONFLICT

WITH ANY OTHER BUILDINGS SYSTEMS. VERIFY SAME WITH SHOP DRAWINGS.

B. ADDITIONAL ELECTRICAL REQUIREMENTS MAY BE SHOWN ON PLANS FROM OTHER DISCIPLINES IN THIS SET. IT IS THE CONTRACTOR’S RESPONSIBILITY TO REVIEW ALL PLANS AND SPECIFICATIONS FOR A COMPLETE

UNDERSTANDING OF THE PROJECT REQUIREMENTS.

C. WORK SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF ALL LOCAL, STATE, AND NATIONAL CODES.

INCLUDING BUT NOT LIMITED TO NFPA 70 (NEC), NFPA 72, INTERNATIONAL BUILDING CODES, ETC. IN ADDITION, OBSERVE ALL APPLICABLE RULES AND REGULATIONS THAT MAY APPLY TO THE WORK UNDER THIS CONTRACT FROM CITY, COUNTY, LOCAL, STATE, FEDERAL, MUNICIPALITY, UTILITY COMPANY, OSHA, ETC.

D. CONTRACTOR SHALL FOLLOW SEISMIC RESTRAINT AND DESIGN REQUIREMENTS CONTAINED IN LATEST ADOPTED STATE AND INTERNATIONAL BUILDING CODES, WITH ALL AMENDMENTS AS ADOPTED BY THE CURRENT LEGISLATION. REFER TO ELECTRICAL AND STRUCTURAL SPECIFICATIONS FOR ADDITIONAL INFORMATION.

E. ADVISE THE ENGINEER OF ANY CONFLICTS, ERRORS, OMISSIONS, ETC. AT LEAST TEN DAYS PRIOR TO BID DATE, TO

ALLOW CLARIFICATION BY WRITTEN ADDENDUM.

F. WHERE CONFLICTS ARE FOUND BETWEEN DRAWINGS, DETAILS, OR SPECIFICATIONS, THE MORE STRINGENT

REQUIREMENT SHALL APPLY. NOTIFY ARCHITECT OF DISCREPANCY IN WRITING.

G. DEVIATION FROM SPECIFICATIONS OR PLANS REQUIRES PRIOR WRITTEN APPROVAL FROM THE ENGINEERS AND

MUST BE SUBMITTED IN WRITING NO LATER THAN TEN DAYS PRIOR TO THE BID DATE.

H. ALL ELECTRICAL COMPONENTS OR EQUIPMENT SHALL BE LISTED AND LABELED BY UNDERWRITER'S LABORATORIES OR OTHER APPROVED LISTING AGENCY. APPROVAL AND LABELING OF INDIVIDUAL COMPONENTS ON AN ASSEMBLY IS NOT ACCEPTABLE AS MEETING THIS REQUIREMENT, UNLESS WAIVED BY THE ENGINEER IN

WRITING.

I. ALL MATERIALS FURNISHED AND ALL WORK INSTALLED SHALL COMPLY WITH THE CURRENT EDITION OF THE NATIONAL ELECTRICAL CODES, NATIONAL FIRE CODES OF THE NATIONAL FIRE PROTECTION ASSOCIATION, THE REQUIREMENTS OF LOCAL UTILITY COMPANIES, AND WITH THE REQUIREMENTS OF ALL GOVERNMENTAL AGENCIES OR DEPARTMENTS HAVING JURISDICTION. IF ANY CONFLICTS OR DISCREPANCIES OCCUR THE MOST STRINGENT

SHALL APPLY.

J. MOUNTING HEIGHTS FOR WALL MOUNTED DEVICES INDICATED ABOVE FINISHED FLOOR ARE TO CENTER OF DEVICE UNO. MOUNTING HEIGHTS TO CEILING SUSPENDED DEVICES ARE TO BOTTOM OF DEVICE UNO. WHERE MOUNTING HEIGHTS ARE NOT INDICATED OR ARE IN CONFLICT WITH ANY OTHER BUILDING SYSTEM, CONTACT THE ENGINEER BEFORE AFFECTING INSTALLATION. REFER ALSO TO ARCHITECTURAL INTERIOR AND EXTERIOR ELEVATIONS, CEILING HEIGHTS AND OTHER DETAILS OF THESE DOCUMENTS, AS APPLICABLE.

K. DO NOT SCALE FROM DRAWINGS, AS PRINTING DISTORTS SCALE. WORK SHALL BE LAID OUT FROM DIMENSIONED

DRAWINGS, OR DIMENSIONS SUPPLIED TO THE CONTRACTOR.

L. REFER TO ARCHITECTURAL WALL ELEVATIONS (WHERE GIVEN) FOR HEIGHTS AND MOUNTING RELATIONSHIP OF OUTLETS AND FURNITURE, CASEWORK, AND/OR EQUIPMENT. ADDITIONAL OUTLETS MAY BE SHOWN ON

ARCHITECTURAL DRAWINGS AND SHALL BE INCLUDED IN THE CONTRACT.

M. FLUSH OR PEDESTAL TYPE FLOOR OUTLETS/BOXES, AS INDICATED ON PLAN, SHALL BE LOCATED BY DIMENSIONS PROVIDED BY THE ARCHITECT, UNLESS OTHERWISE SHOWN ON PLANS. IF IN DOUBT, CONTACT THE ENGINEER

PRIOR TO ROUGHING-IN ANY WORK.

N. INSTALL EQUIPMENT, MATERIALS, ETC. IN STRICT ACCORDANCE WITH MANUFACTURER’S RECOMMENDATIONS AND DIRECTIONS. IF IN CONFLICT WITH THE DESIGN INDICATED IN CONTRACT DOCUMENTS, ADVISE THE ENGINEER

PRIOR TO INSTALLATION FOR CLARIFICATION.

O. THE CONSTRUCTION MANAGER, GENERAL CONTRACTOR, OR WHOMEVER HOLDS THE PRIME CONTRACT(S) FOR THIS CONSTRUCTION IS RESPONSIBLE FOR THE COORDINATION, APPEARANCE, SCHEDULING AND TIMELINESS OF THE WORK OF ALL TRADES, CONTRACTORS, SUPPLIERS, INSTALLERS, ETC. POOR OR UNTIMELY WORK ON THE PART OF ANY SUBCONTRACTOR SHALL BE RESOLVED BY THE PARTY WHO ENGAGED THEM ON THIS PROJECT.

P. THE PURPOSE AND INTENT OF ALL OF THE DOCUMENTS PERTAINING TO THIS PROJECT IS TO PROVIDE A COMPLETE, FUNCTIONAL, SAFE, LIKE-NEW FACILITY. ANYTHING LESS SHALL BE UNACCEPTABLE.

Q. ALL SYSTEMS, EQUIPMENT AND MATERIALS ARE TO BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER. WORK NOT MEETING THIS CRITERION SHALL BE REMOVED AND REINSTALLED SATISFACTORILY. FINAL DETERMINATION OF

THE ACCEPTABILITY OF THE QUALITY OF WORK RESIDES WITH THE ENGINEER

R. ALL WORK, MATERIALS, EQUIPMENT, ETC. SHALL BE FULLY GUARANTEED FOR ONE FULL CALENDAR YEAR FROM THE DATE OF SUBSTANTIAL COMPLETION AS DOCUMENTED BY THE ENGINEER, UNLESS LONGER WARRANTY

PERIODS FOR EQUIPMENT ARE SPECIFIED.

S. ALL WORK SHALL BE CONCEALED UNLESS SPECIFICALLY INDICATED TO BE EXPOSED, OR REQUIRED TO BE EXPOSED. IF IN DOUBT, CONTACT THE ENGINEER FOR CLARIFICATIONS PRIOR TO INSTALLING ANY SUCH WORK.

T. UNLESS OTHERWISE SPECIFIED OR INDICATED, ALL EQUIPMENT AND/OR MATERIALS WITHIN OCCUPIED SPACES OR EXPOSED TO VIEW ON THE BUILDING EXTERIOR SHALL BE PRIMED AND FINISHED SO AS TO COMPLEMENT ADJACENT SURFACE, UNLESS OTHERWISE NOTED. COORDINATE WORK AND COLORS WITH ARCHITECT.

U. WHERE PENETRATING ROOFING MEMBRANE OR OTHER MATERIALS USED FOR WEATHERPROOFING THE BUILDING, MAKE SUCH PENETRATION IN A WAY THAT WILL NOT VOID OR DIMINISH THE ROOFING WARRANTY OR INTEGRITY IN ANYWAY. COORDINATE ALL SUCH PENETRATIONS WITH THE ROOFING MANUFACTURER AND ARCHITECT.

V. CEILING-MOUNTED ELECTRICAL DEVICES SHALL BE CENTERED IN 2'X2' CEILING TILE AND INSTALLED CENTERED ON

2' DIMENSION OF 2'X4' TILE AND ON CENTERLINE OR A QUARTER POINT ON 4' DIMENSION.

W. PROVIDE DETAILED SHOP DRAWINGS TO ENGINEER PRIOR TO PURCHASING OR INSTALLING ANY EQUIPMENT DEVIATIONS IN SIZES, CAPACITIES, FIT, FINISH, ETC. FOR EQUIPMENT FROM THAT PRIME SPECIFIED SHALL BE THE RESPONSIBILITY OF THE PURCHASER OF THAT EQUIPMENT. ANY PROVISIONS REQUIRED TO ACCOMMODATE A DEVIATION, WHETHER APPROVED BY THE ENGINEER OR NOT, SHALL BE THE RESPONSIBILITY OF THE PURCHASER.

X. WHERE FIRE-RATED CEILING ASSEMBLIES ARE NOTED, PROVIDE UL-LISTED FIRE-RATED GYPSUM BOARD OR PRE- MANUFACTURED ENCLOSURES ABOVE LUMINAIRES, CEILING DEVICES, ETC. IN OR ON CEILING, AS REQUIRED TO

MAINTAIN CEILING RATINGS.

Y. DO NOT RECESS PANELBOARD TUBS OR OTHER FLUSH-MOUNTED EQUIPMENT IN WALLS THAT HAVE A FIRE

RATING. NO INSTALLATION SHALL DIMINISH OR VOID FIRE RESISTIVE RATINGS IN ANYWAY.

Z. COORDINATE THE LOCATION OF DRAINS, ELECTRICAL OUTLETS, GAS OUTLETS, ETC. WITH ALL CASEWORK, KITCHEN EQUIPMENT, MECHANICAL ROOM EQUIPMENT, ETC. PRIOR TO COMMENCING INSTALLATION. WORK NOT SO COORDINATED SHALL BE REMOVED AND PROPERLY INSTALLED AT THE EXPENSE OF THE RESPONSIBLE

CONTRACTOR(S).

AA. ALL OFFSETS, TURNS, FITTINGS, TRIM, DETAIL, ETC. MAY NOT BE INDICATED, BUT SHALL BE PROVIDED AS REQUIRED. ADDITIONAL ALLOWANCES SHALL BE INCLUDED FOR SAME AT EACH PROPOSER’S DISCRETION.

BB. INSTALL NO PIPING, CONDUIT, DUCTWORK, ETC. IN A LOCATION OR IN A MANNER WHICH WILL ALLOW FREEZING OR

THE COLLECTION OF CONDENSATION THEREON. IF IN DOUBT, CONTACT THE ENGINEER.

CC. ALL WIRING SYSTEMS SHALL BE INSTALLED WITH A MINIMUM OF SPLICES. CONDUCTORS, WHETHER SINGLE OR MULTI-PAIR, SHALL BE INSTALLED CONTINUOUS INSOFAR AS POSSIBLE FROM TERMINAL POINT TO TERMINAL POINT.

DD. NO CONDUIT, SUPPORTS, ETC. SHALL BE RUN THROUGH ACCESS CLEARANCES OF EQUIPMENT BY OTHER TRADES

(I.E. VAV BOXES). COORDINATE WITH ALL TRADES PRIOR TO CONSTRUCTION.

EE. ALL SUPPORTS FOR EQUIPMENT, DEVICES OR…