Addenda 1.pdf
PDF 6 MB Posted
- Solicitation number
- C6CF2D66-C8D6-4C04-AC8D-A20EB5779428
- Issued by
- Schenectady County, Schenectady City, New York
About this file
The document provided is Addenda 1 related to a state and local contract opportunity issued by the New York State Office for People with Developmental Disabilities (OPWDD) for the Building 9D Window Glass Replacement project located at 500 Balltown Rd, Schenectady, NY. The project involves the replacement of 16 windows measuring 5'7"x1'7.75", 10 windows measuring 3'7.25"x1'7.75", and 9 windows measuring 2'9"x1'7.5". The solicitation was issued on 2/23/24 with bids due by 3/8/24 at 1PM. Attendance at the mandatory site visit scheduled for 3/1/24 at 9AM is required. The awarded vendor must confirm all measurements before ordering the windows.
The Addenda also includes an asbestos inspection report which indicated that while some window caulking contained trace amounts of asbestos, the materials were in fair condition. There are no Minority/Women-owned Business Enterprise (MWBE) goals required for this single activity project, though the overall MWBE goal for the agency is provided. Prevailing wages must be paid as this is a New York State public works project.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Appendix A.pdf | ||
| Bid Documents.pdf | ||
| COVID Safety Plan.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
KATHY HOCHUL
Governor
KERRI E. NEIFELD
Commissioner
WILLOW BAER
Executive Deputy Commissioner
Developmental Disabilities Business Office
500 Balltown Road, Schenectady, NY 12304 │ TEL: 518-388-3648, FAX: 518-347-3451│www.opwdd.ny.gov
March 6, 2024
Addenda 1
Building 9D Window Glass Replacement 500 Balltown Rd Schenectady, NY 12304
Solicitation Date: 2/23/24 Bid Due Date: 3/8/24 – 1PM Date of update: 3/6/24
Good afternoon, Below is the answers to questions submitted that should be considered when submitting your estimates.
1) Please provide a schedule for window replacements to include size and qty of each type.
a. The size and quantity are as follows:
i. 16 of 5’7’’x1’7.75’’
ii. 10 of 3’7.25’’x1’7.75’’
iii. 9 of 2’9’’x1’7.5’’
b. We have a schematic of the facility and the windows needing replacement. We have attached the upper floors. The right side of the schematic is the “D” wing and the area we a focusing on to replace the windows.
c. The awarded vendor must confirm measurements before ordering.
2) Are windows glazed from the interior or exterior?
a. There is no Glazing, these are aluminum insert windows or double pane windows.
3) Are there any concerns about hazardous materials (e.g. asbestos, PCB, lead)?
a. The ACM report is attached.
4) Are WMBE goals incorporated in this project? Bid docs say yes - site visit mentioned they are not. As this is a single activity, even if the awarded contractor is a WMBE, the goals noted cannot be met for all categories.
a. There is a general goal, but not required. Our overall goal is listed in the Contract Reporter Ad.
Please be sure any estimates include this information.
Please let us know if there are any questions.
Sincerely, Samantha J Lewandowski Samantha J Lewandowski Office Assistant 3 NYS Office for People with Developmental Disabilities psespurchasing@opwdd.ny.gov 518-388-3648 http://www.opwdd.ny.gov/ mailto:psespurchasing@opwdd.ny.gov
5'-9" V.I.F
11'-7 1/4" V.I.F 17'-3" V.I.F
8'-7 1/2" V.I.F
'-7
/4
" V .I.
F
'-7
/4
" V .I.
F
5' -9
V.
I.F
5' -9
V.
I.F
FLOOR
TYPE A TYPE B TYPE C TYPE D
SHT
1 SECOND FLOOR PLAN
SCALE: FULL (1/8" = 1'-0")
SHT
1 WINDOW TYPES
SCALE: FULL (3/16" = 1'-0")
revise all dimensions confirm 73 3/8" +/-window does not exist confirm this 'upper window ' for replacement (maybe was the other side of wing?)
unsure if window exists here. to be confirmed window schedule here (qtys/type)
Environmental Consulting & Management Services • Health & Safety Training • Laboratory Services
December 19, 2022
John Mclear
Capital District DDSO
500 Balltown Road
Schenectady, New York 12304
RE: Windows – Bldg 9
OD Heck 500 Balltown Road
Schenectady, NY 12304
Spectrum Project # 22-645
Dear Mr. Mclear:
Spectrum Environmental Associates, Inc. (Spectrum) is submitting this letter and attached documentation as our final report for the above referenced asbestos bulk sampling project.
Mr. Nate Martin (AH # 21-04856), Spectrum’s inspector of record for this project, collected six
(6) samples of suspect asbestos containing materials on December 13, 2022 as requested by
Nathan Pannone of DDSO. All of the samples were sent to AmeriSci under proper chain of custody record for asbestos analysis.
The inspection and sampling were performed in accordance with generally accepted industry practices and applicable state and federal regulations including, but not limited to; NYS-DOL
Industrial Code Rule 56, USEPA – Title 40 CFR Part 763 “AHERA”, USEPA Title 40 CFR Part
61 “NESHAP” and OSHA – Title 29 CFR Part 1926.1101 “Construction Standard”. The bulk samples were analyzed by an independent laboratory approved by the New York State
Department of Health (NYS-DOH) Environmental Laboratory Approval Program (ELAP).
According to USEPA and New York State Department of Labor - Industrial Code Rule 56 (NYS
ICR 56) an asbestos containing material contains more than one percent (1%) of asbestos by weight. Analytical results indicating less than 1% or a “trace” means the material may be treated as non-asbestos. OSHA does require that an employer not expose its workers above the PEL and therefore specific training, work practices and/or respiratory protection may need to be consideration when handling materials that are less than one percent.
In the attached table, results are provided of the materials requested to be sampled. Any other materials that may be disturbed should be assumed to contain asbestos until properly assessed and/or sampled in accordance with applicable regulations.
Windows – Bldg 9
Date Sampled: December 13, 2022
This report is for the exclusive use of Capital District DDSO, its successors and/or assigns. This report and its contents represent confidential information and should not be duplicated without the expressed permission of Capital District DDSO, its successors and/or assigns.
Should you have any questions concerning the collection and/or the analytical results presented in this report, please do not hesitate to contact our office at (518) 346-6374.
Sincerely, Robert J DeRuyter
Robert J. DeRuyter
VP of Operations
Cc: file
Attachments: Sample Summary Table
Photographs
Sample Location Drawing/Map
Laboratory Results with Chain of Custody
Licensure and Certification
Limitations:
The following limitation/conditions were noted as part of the survey:
OSHA requires that an employer not expose its workers above the PEL and therefore specific training, work practices and/or respiratory protection may need to be a consideration when handling materials that are less than one percent.
The sampling was limited to the request material(s) and location(s) by the client.
If materials not sampled in the survey are uncovered during renovation/demolition, per
ICR56 work should stop and those materials should be assessed before work continues. Also per ICR 56, a copy of the survey report should be submitted to the local agency issuing the demolition permit and a copy should be kept on site during the demolition phase of the project.
This report reflects the conditions found at the date and time of the inspection(s). Conditions of the area and materials may change due to external events, forces or influences. Re-inspection of the area may be required prior to the start of any work if an extended period of time has passed or if disturbances have occurred.
All asbestos locations on drawings are approximate. All quantities are estimated and must be field verified prior to use as part of a bidding document. Materials may extend or be hidden behind or within other materials or structural members. Any contractor or other user of this report is required to physically confirm the quantities and verify measurements of materials to be removed, to be bid for removal, or for any other purpose. Contractors are responsible to physically visit the site and confirm all quantities for bidding purposes.
Sample Summary Table
Quantities of identified ACM are estimates only and should be field verified prior to bid by the contractor or confirmed as part of an RFP or design specification. Please see the limitation listed above.
Asbestos % by PLM* - please refer to the PLM Bulk Asbestos Report for the method used.
Definitions:
NAD – No Asbestos Detected
NA – Not Analyzed
NA1 – (SOF-V) and (SM-V) must be analyzed by ELAP 198.8 or equivalent effective 5/6/16
NA2 – Insufficient Material for Preparation N/A – Not Applicable (quantities are not provided for negative materials)
TBD – To Be Determined (quantification was not possible as the scope of work was not provided)
NA/PS – Not Analyzed / Positive Stop
All asbestos locations on drawings are approximate. All quantities are estimated and must be field verified prior to use as part of a bidding document. Materials may extend or be hidden behind or within other materials or structural members. Any contractor or other user of this report is required to physically confirm the quantities and verify measurements of materials to be removed, to be bid for removal, or for any other purpose. Contractors are responsible to physically visit the site and confirm all quantities for bidding purposes.
Material Location Asbestos % by PLM* Asbestos % by TEM Condition
Window Caulking Windows of 9NE NAD Chrysotile Trace Fair
Window Caulking Windows of 9NE NAD Chrysotile Trace Fair
Window Caulking Windows of 9NW NAD Chrysotile < 1.0% Fair
Window Caulking Windows of 9NW NAD Chrysotile Trace Fair
Window Caulking Windows of 9SW NAD Chrysotile < 1.0% Fair
Window Caulking Windows of 9SW NAD Chrysotile < 1.0% Fair
None of the materials tested were positive for asbestos according to
New York State Department of Labor - Industrial Code Rule 56 (NYS ICR 56)
Asbestos Inspection Photo Album of Windows Bldg 9 by
Spectrum Environmental Associates, Inc.
Date of Inspection: December 13, 2022 bderuyter Text Box 22-645 (12-13-22) Windows Bldg 9 Limited Bulk Sample Locations - NTS
AmeriSci New York
117 EAST 30TH ST.
NEW YORK, NY 10016
TEL: (212) 679-8600 • FAX: (212) 679-3114
12/14/22 AmeriSci Job # 222122175 12/17/22
ELAP # 11480 1 2
22-645; 500 Balltown Road, Building 9
PLM Bulk Asbestos Report Date Received Date Examined
RE:
ofPage
P.O. # Spectrum Environmental Associates, Inc.
P.O.Box 1024
Schenectady, NY 12301
Attn: Bill Massman
Asbestos Present Total % AsbestosClient No. / HGA Lab No.
Location:
Analyst Description:
Asbestos Types:
Other Material:
No1 222122175-01 NAD Windows Of 9NE, Window Caulking1
White, Homogeneous, Non-Fibrous, Bulk Material
Non-fibrous 32.7%
(by NYS ELAP 198.6) by Khaalid W. Perine on 12/17/22
Location:
Analyst Description:
Asbestos Types:
Other Material:
No2 222122175-02 NAD Windows Of 9NE, Window Caulking1
White, Homogeneous, Non-Fibrous, Bulk Material
Non-fibrous 20.5%
(by NYS ELAP 198.6) by Khaalid W. Perine on 12/17/22
Location:
Analyst Description:
Asbestos Types:
Other Material:
No3 222122175-03 NAD Windows Of 9NW, Window Caulking2
Beige, Homogeneous, Non-Fibrous, Bulk Material
Non-fibrous 33.5%
(by NYS ELAP 198.6) by Khaalid W. Perine on 12/17/22
Location:
Analyst Description:
Asbestos Types:
Other Material:
No4 222122175-04 NAD Windows Of 9NW, Window Caulking2
Beige, Homogeneous, Non-Fibrous, Bulk Material
Non-fibrous 36.4%
(by NYS ELAP 198.6) by Khaalid W. Perine on 12/17/22
Location:
Analyst Description:
Asbestos Types:
Other Material:
No5 222122175-05 NAD Windows Of 9SW, Window Caulking3
White/Beige, Homogeneous, Non-Fibrous, Bulk Material
Non-fibrous 29.9%
(by NYS ELAP 198.6) by Khaalid W. Perine on 12/17/22
See Reporting notes on last page
AmeriSci Job #: 222122175 Page 2 of 2
22-645; 500 Balltown Road, Building 9
PLM Bulk Asbestos Report Client Name: Spectrum Environmental Associates, Inc.
Asbestos Present Total % AsbestosClient No. / HGA Lab No.
Location:
Analyst Description:
Asbestos Types:
Other Material:
No6 222122175-06 NAD Windows Of 9SW, Window Caulking3
White/Beige, Homogeneous, Non-Fibrous, Bulk Material
Non-fibrous 28.1%
(by NYS ELAP 198.6) by Khaalid W. Perine on 12/17/22
Reporting Notes:
*NAD/NSD =no asbestos detected; NA =not analyzed; NA/PS=not analyzed/positive stop, (SOF-V) = Sprayed On Fireproofing containing Vermiculite;
(SM-V) = Surfacing Material containing Vermiculite; PLM Bulk Asbestos Analysis using Leicia, Model DMEP Pol Scope, Microscope, Serial #: 13595, by Appd E to Subpt E, 40 CFR 763 quantified by either CVES or 400 pt ct as noted for each analysis (NVLAP 200546-0), ELAP PLM Method 198.1 for NY friable samples, which includes the identification and quantitation of vermiculite, or ELAP 198.6 for NOB samples, or EPA 400 pt ct by EPA 600- M4-82-020 (NY ELAP Lab 11480); Note:PLM is not consistently reliable in detecting asbestos in floor coverings and similar non-friable organically bound materials. NAD or Trace results by PLM are inconclusive, TEM is currently the only method that can be used to determine if this material can be considered or treated as non asbestos-containing in NY State (also see EPA Advisory for floor tile, FR 59,146,38970,8/1/94) National Institute of Standards and Technology Accreditation requirements mandate that this report must not be reproduced except in full without the approval of the lab.This PLM report relates ONLY to the items tested. RI Cert AAL-094, CT Cert PH-0186, Mass Cert AA000054, NJ Lab ID #NY031.
____________END OF REPORT___________
Analyzed by: Khaalid W. Perine Date: 12/17/2022
Reviewed by: Marik Peysakhov
Client Name:
222122175
Spectrum Environmental Associates, Inc.
22-645; 500 Balltown Road, Building 9
AmeriSci Job #: Page 1 of 1
Table I Summary of Bulk Asbestos Analysis Results
Client Sample#
Sample Weight (gram)
Heat Sensitive
Organic %
Acid Soluble
Inorganic %
Insoluble Non-Asbestos
Inorganic %
HG
Area ** Asbestos % by
PLM/DS
** Asbestos % by
TEM
AmeriSci Sample #
01 1 1 0.132 37.5 29.8 32.6 NAD Chrysotile Trace
Windows Of 9NE, Window CaulkingLocation:
02 2 1 0.200 30.6 48.9 20.4 NAD Chrysotile Trace
Windows Of 9NE, Window CaulkingLocation:
03 3 2 0.226 24.0 42.4 33.3 NAD Chrysotile <1.0
Windows Of 9NW, Window CaulkingLocation:
04 4 2 0.158 28.0 35.6 36.3 NAD Chrysotile Trace
Windows Of 9NW, Window CaulkingLocation:
05 5 3 0.218 25.5 44.6 29.7 NAD Chrysotile <1.0
Windows Of 9SW, Window CaulkingLocation:
06 6 3 0.244 18.4 53.5 27.9 NAD Chrysotile <1.0
Windows Of 9SW, Window CaulkingLocation:
**Quantitative Analysis (Semi/Full); Bulk Asbestos Analysis - PLM by Appd E to Subpt E, 40 CFR 763 or NYSDOH ELAP 198.1 for New York friable samples or NYSDOH ELAP 198.6 for New York NOB samples;
TEM (Semi/Full) by EPA 600/R-93/116 (or NYSDOH ELAP 198.4; for New York samples). Analysis using Hitachi, Model H7000-Noran 7 System, Microscope, Serial #: 747-05-06. NAD = no asbestos detected during a quantitative analysis; NA = not analyzed; Trace = <1%; (SOF-V) = Sprayed On Fireproofing containing Vermiculite; (SM-V) = Surfacing Material containing Vermiculite; Quantitation for beginning weights of <0.1 grams should be considered as qualitative only; Qualitative Analysis: Asbestos analysis results of "Present" or "NVA = No Visible Asbestos" represents results for Qualitative PLM or TEM Analysis only (no accreditation coverage available from any regulatory agency for qualitative analyses): NVLAP (PLM) 200546-0, NYSDOH ELAP Lab 11480, NJ Lab ID #NY031.
Warning Note: PLM limitation, only TEM will resolve fibers <0.25 micrometers in diameter. TEM bulk analysis is representative of the fine grained matrix material and may not be representative of non-uniformly dispersed debris for which PLM evaluation is recommended (i.e. soils and other heterogenous materials).
Analyzed by: Marik Peysakhov Date: 12/18/2022
Reviewed by: Marik Peysakhov
New York State – Department of Labor Division of Safety and Health License and Certificate Unit State Campus, Building 12
Albany, NY 12240
ASBESTOS HANDLING LICENSE
Spectrum Environmental Associates, Inc.
P.O. Box 1024
Schenectady, NY 12301
FILE NUMBER: 99-0129
LICENSE NUMBER: 29081
LICENSE CLASS: RESTRICTED
DATE OF ISSUE: 02/02/2022
EXPIRATION DATE: 02/28/2023
Duly Authorized Representative – William L Massmann:
This license has been issued in accordance with applicable provisions of Article 30 of the Labor Law of New York State and of the New York State Codes, Rules and Regulations (12 NYCRR Part 56). It is subject to suspension or revocation for a (1) serious violation of state, federal or local laws with regard to the conduct of an asbestos project, or (2) demonstrated lack of responsibility in the conduct of any job involving asbestos or asbestos material.
This license is valid only for the contractor named above and this license or a photocopy must be prominently displayed at the asbestos project worksite. This license verifies that all persons employed by the licensee on an asbestos project in New York State have been issued an Asbestos Certificate, appropriate for the type of work they perform, by the New York State Department of Labor.
Amy Phillips, Director SH 432 (8/12) For the Commissioner of Labor
| Addenda 1 - CD23054-Building 9D Window Glass Replacement.pdf |
| BLDG09 Second Floor_working Drawings-Window Plan.pdf |
| Sheets and Views |
| Window Plan |
22-645 DDSO Bldg 9 Windows Limited Bulk Report.pdf
File details come from the government source that posted it. Updated .