ACM.WellsCurtice.WholeHouse.pdf
PDF 3 MB Posted
- Solicitation number
- 2138854
- Issued by
- Oneida County, New York
About this file
This is a Comprehensive Regulated Building Materials Inspection Report prepared by LaBella Associates, D.P.C. for the New York State Office for People with Developmental Disabilities regarding a residential property located at 5580 Wells Curtice Road in Canandaigua, New York. The inspection, conducted on February 12, 2020, by certified inspector Chris Enright, identified suspect regulated building materials including asbestos-containing materials (ACM) and lead-based paint (LBP) that may require abatement or removal prior to or during renovation. The inspection involved visual examination of interior, exterior, and roofing systems, collection of bulk samples for laboratory analysis using Polarized Light Microscopy and Transmission Electron Microscopy, and field testing using X-ray fluorescence (XRF) procedures. A total of 32 asbestos bulk samples and 87 lead XRF readings were collected from various locations throughout the building, including basement areas, multiple rooms, exterior components, and roofing materials.
The inspection results confirmed the presence of asbestos-containing material in one sample: black roofing cement located around silver roof vents, containing 18% chrysotile asbestos with an estimated 10 square feet requiring attention. The report notes that no tested painted or glazed materials were found to contain lead above the EPA action level threshold of 1.0 mg/cm², though lead was detected at low concentrations in vinyl cove base, stair tread, and ceramic tiles. The inspection identified significant limitations, including that only readily accessible materials were sampled and that destructive investigation was limited due to the building's operational status as an occupied residential group home. The report recommends that if future building renovations occur, previously inaccessible areas including floor surfaces and wall/ceiling cavities should be re-investigated using destructive sampling techniques to identify potential hidden regulated materials.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFQ.pdf | ||
| SOW.pdf | ||
| CP-FL-H2668-20260820_Roof_Replacement_WELLS_CURTICE.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
300 State Street, Suite 201 | Rochester, NY 14614 | p 585-454-6110 | f 585-454-3066 www.labellapc.com
Comprehensive
Regulated Building Materials Inspection
Location:
Residential House
5580 Wells Curtice Road
Canandaigua, New York 14424
Prepared for:
NYS Office for People with Developmental Disabilities
6666 Babcock Hollow Road
Bath, New York 14810
LaBella Project No. 2200856
March 2020
Table of Contents
Page No.
I. Project Description 1
II. Inspection Procedures 1
III. Inspection Limitations 1
IV. Inspection Results 2
V. Observations & Cautionary Statements 3
Asbestos Bulk Sample Summary Table T-1
Appendix A – Inspection Fact Sheet FS-1
Appendix B – Sample Location Drawing
Appendix C – Inspection Photos
Appendix D – Laboratory Analytical Reports
Appendix E – Licenses and Certifications
1 1
I. PROJECT DESCRIPTION
In accordance with current regulations, LaBella Associates, D.P.C. (LaBella) conducted a
Comprehensive Regulated Building Materials (RBM) Inspection of the residential property located at
5580 Wells Curtice Road in Canandaigua, New York. The objective was to identify suspect RBMs, such as Asbestos-Containing Materials (ACM) and Lead-Based Paint (LBP) which may require abatement or removal prior to or during renovation due to applicable regulations.
Materials and locations understood to be impacted by this project were determined from information provided by NYS Office for People with Developmental Disabilities.
II. INSPECTION PROCEDURES
The following procedures were used to obtain the data for this Report:
A. Existing documentation was requested for review. No record drawings or documentation of previously completed inspections were made available.
B. A visual inspection of the interior, exterior and roofing system of the building was conducted to identify visible and accessible sources of the above referenced suspect RBMs.
Photographs captured during this inspection are attached in Appendix C.
C. Bulk samples of accessible RBMs were collected and submitted for laboratory analysis.
D. Asbestos samples were submitted for laboratory analysis. Preliminary Polarized Light
Microscopy analyses of non-friable, organically bound (NOB) materials were performed by
LaBella Laboratories, a NYSDOH accredited laboratory, to determine the presence and percentage of asbestos in each sample. Transmission electron microscopy analyses of NOB materials, if necessary, were performed by AMA Laboratories.
E. Suspect painted or glazed materials were spot checked in the field using XRF testing procedures for the presence of lead.
F. Results of the laboratory analyses, field testing and the visual on-site inspection were compiled and summarized.
III. INSPECTION LIMITATIONS
This inspection was conducted in accordance with generally accepted environmental engineering practices for this region. Collection of bulk samples of suspect RBMs was limited to those materials readily accessible using hand tools or hand-held power tools. Homogeneous materials were identified and located based on visual observation from readily accessible points. The data derived from representative samples of any given homogeneous material represent conditions that apply only at that particular location. Inspection protocol and methodology requires that sample data be used to draw conclusions about the entire homogeneous area, but such conclusions may not necessarily apply to the general Site as a whole. No sub-surface investigations were performed to
2 2 determine the possible presence of regulated materials on or in the immediate vicinity of the Site.
LaBella makes no other warranty or representation, either expressed or implied, nor is one intended to be included as part of its services, proposals, contracts or reports. No inspection can wholly eliminate the uncertainty regarding the potential for undiscovered RBMs. The Work performed by
LaBella is intended to reduce, but not eliminate, uncertainty regarding the potential for RBMs at the
Site. This inspection report is not intended to be a bid document for an abatement scope of work.
This report is intended to satisfy the requirements of NYS Code Rule 56-5 for inspections.
IV. INSPECTION RESULTS
Asbestos-Containing Materials (ACMs) Based on laboratory analyses of bulk samples collected, the following material was determined to contain greater than 1% asbestos. However, the following table does not include all of the materials sampled during this inspection; for a full list of materials sampled see the Asbestos Bulk Sample
Summary Table immediately following this report.
Type of Material
Typical Location
Estimated
Amount1
Friability
Condition
Black Roofing Cement Around Silver Roof Vents 10 SF Non-Friable Good
Lead – Based Paint Several representative interior and exterior painted and glazed surfaces such as door components, window components, walls, etc. were observed and tested for the presence of lead-based paint using XRF testing procedures. In accordance with Environmental Protection Agency (EPA) protocols, no tested materials were found to contain lead above the action level threshold of 1.0 mg/cm2.
However, additional lead-based materials may exist within the property. Therefore, any Contractor performing work on the property shall be responsible for determining the quantity, location and condition of materials not tested during this inspection.
The buildings and spaces inspected for this project do not include or comprise residential spaces applicable to the requirements of EPA lead-based paint management regulations. Therefore, EPA
40 Code of Federal Regulations (CFR) 745: Lead-Based Paint Renovation, Repair and Painting
(RRP) Program Rule and HUD requirements do not apply. However, lead was detected at low concentrations in a variety of building materials (i.e., vinyl cove base, stair tread, and ceramic tiles).
Renovation and demolition contractors should be informed of the presence of lead for OSHA compliance considerations.
For purposes of reading this report, and understanding which wall or component in a particular space was sampled, walls were assigned the letters A, B, C, or D. The wall labeled as “A” is the address side of the building; walls B, C, and D will follow clockwise in succession.
1 For general reference only: Estimated amounts of confirmed ACM listed above were obtained through field observations made during site visits. Quantities are approximations and LaBella assumes no responsibility if used for bidding.
3 3
V. OBSERVATIONS AND CAUTIONARY STATEMENTS
Vermiculite
Vermiculite has been used as loose insulation in attics, walls, CMU block, and as a component of plaster, fireproofing and other building materials. The NYS Department of Health considers
Vermiculite to be an asbestos-containing material, and that building materials containing more than
10% Vermiculite should be treated as asbestos-containing.
Vermiculite was not observed in spaces and materials inspected for this project. However, destructive investigation of wall cavities was not conducted, and therefore the presence or extent of this material’s application throughout the building was not determined.
Cautionary measures should be taken during construction, renovation, and demolition to ensure that proper steps are taken if Vermiculite is discovered in previously inaccessible locations. If
Vermiculite is discovered, work should be stopped immediately to address the issue and prevent the uncontrolled release and distribution of an asbestos-containing material.
Potentially Hidden/Inaccessible RBMs
As stated earlier, collection of bulk samples of suspect RBMs was limited to those materials readily accessible. Since the building is occupied and in operation as a residential group home open to the public, destructive sampling techniques were limited in order to minimize disruption to residents and damage to building components.
Although this inspection was conducted in a manner consistent with recognized professional practices, the potential does exist for additional RBMs to be located in the following inaccessible areas because of the operational constraints mentioned above:
On floor surfaces potentially covered by multiple layers of building materials such as, laminates, plywood, floor tile, etc.
Inside wall and/or ceiling cavities
If future building renovations are to take place, it is recommended that the above areas/materials be re-investigated using destructive sampling techniques as necessary, in order to identify and sample currently hidden/inaccessible suspect RBMs that could potentially be discovered during building renovation.
Asbestos Bulk Sample
Summary Table
Asbestos Bulk Sample Summary Table
Comprehensive Regulated Building Materials Inspection
5580 Wells Curtice Road
Canandaigua, New York 14424
Items in Bold are Confirmed ACM
T-1 LaBella Project 2200856
Sample #
Sample Location
Results %
Asbestos
1A Red Firestop Basement Storage, Around Wall Penetrations None Detected
1B Red Firestop Basement Storage, Around Wall Penetrations None Detected
2A Gray Duct Mastic Basement Storage, On Ductwork None Detected
2B Gray Duct Mastic Basement Storage, On Ductwork None Detected
3A White/Gray Sheet Vinyl Basement Stairwell, Top Landing None Detected
3B White/Gray Sheet Vinyl Basement Stairwell, Top Landing None Detected
4A Tan Sheet Vinyl Mastic Basement Stairwell, Top Landing None Detected
4B Tan Sheet Vinyl Mastic Room 104, Floor None Detected
5A Gray Stair Tread Basement Stairwell, On Stairs None Detected
5B Gray Stair Tread Basement Stairwell, On Stairs None Detected
6A White Mastic Basement Stairwell, On Stairs None Detected
6B White Mastic Basement Stairwell, On Stairs None Detected
7A Tan Cove Molding Mastic Basement Stairwell, Wall Base None Detected
7B Tan Cove Molding Mastic Room 104, Wall Base None Detected
8A Gray Drywall Basement Stairwell, Wall None Detected
8B Gray Drywall Room 106, Wall None Detected
9A White Joint Compound Basement Stairwell, Wall None Detected
9B White Joint Compound Garage, Wall None Detected
9C White Joint Compound Room 101, Wall None Detected
9D White Joint Compound Room 149, Wall None Detected
9E White Joint Compound Room 137, Ceiling None Detected
9F White Joint Compound Room 114, Wall None Detected
9G White Joint Compound Room 110, Ceiling None Detected
10A Multi/Gray Sheet Vinyl Room 104, Floor None Detected
10B Multi/Gray Sheet Vinyl Room 104, Floor None Detected
T-2
Asbestos
11A Gray Grout Room 106, Floor None Detected
11B Gray Grout Room 150, Floor None Detected
12A Gray Ceramic Tile Cement Room 106, Floor None Detected
12B Gray Ceramic Tile Cement Room 150, Floor None Detected
13A White Grout Room 106, Cove Base None Detected
13B White Grout Janitor’s Closet, 4 Feet Up Wall None Detected
14A Tan Ceramic Tile Mastic Room 106, Cove Base None Detected
14B Tan Ceramic Tile Mastic Janitor’s Closet, 4 Feet Up Wall None Detected
15A White/Gray Sheet Vinyl Janitor’s Closet, Floor None Detected
15B White/Gray Sheet Vinyl Room 157, Floor None Detected
16A Tan/Gray Sheet Vinyl Room 153, Floor None Detected
16B Tan/Gray Sheet Vinyl Room 134, Floor None Detected
17A Blue/Gray Sheet Vinyl Room 112, Floor None Detected
17B Blue/Gray Sheet Vinyl Room 112, Floor None Detected
18A Pink/Gray Sheet Vinyl Room 145, Floor None Detected
18B Pink/Gray Sheet Vinyl Room 145, Floor None Detected
19A Yellow/Gray Sheet Vinyl Room 145, Closet Floor None Detected
19B Yellow/Gray Sheet Vinyl Room 145, Closet Floor None Detected
20A White/Gray Sheet Vinyl Room 109, Floor None Detected
20B White/Gray Sheet Vinyl Room 109, Floor None Detected
21A Tan Tar Paper Room 143, Floor Under Hardwood None Detected
21B Tan Tar Paper Room 143, Floor Under Hardwood None Detected
22A Gray Grout Room 101, Floor None Detected
22B Gray Grout Room 101, Floor None Detected
23A Gray Ceramic Tile Cement Room 150, Behind Wall Tile None Detected
T-3
Asbestos
23B Gray Ceramic Tile Cement Room 150, Behind Wall Tile None Detected
24A Black Window Glazing
Compound
Room 101, Around Glass
Window Pane of Interior Window None Detected
24B Black Window Glazing
Compound
Room 155, Around Glass
Window Pane of Interior Window None Detected
25A White Sink Coating Room 104, Under Sink None Detected
25B White Sink Coating Room 109, Under Sink None Detected
26A Gray Window Glazing
Compound
Around Glass Window Panes of
Exterior Sidelight Windows None Detected
26B Gray Window Glazing
Compound
Around Glass Window Panes of
Exterior Windows None Detected
27A Black Window Glazing
Compound
Around Glass Window Panes of
Exterior Windows None Detected
27B Black Window Glazing
Compound
Around Glass Window Panes of
Exterior Sidelight Windows None Detected
28A White Caulk Along Exterior Metal Trim None Detected
28B White Caulk Along Exterior Metal Trim None Detected
29A Gray Caulk Around Exterior Pipe Penetration None Detected
29B Gray Caulk Around Exterior Pipe Penetration None Detected
30A Black Roofing Cement Around Roof Vents None Detected
30B Black Roofing Cement Around Silver Roof Vents Chrysotile 18%
31A Black Caulk Around Roof Pipe Penetrations
(PVC)
None Detected
31B Black Caulk Around Roof Pipe Penetrations
(PVC)
None Detected
32A Gray/Black Roof Shingle Roof None Detected
32B Gray/Black Roof Shingle Roof None Detected
Appendix A
Inspection Fact Sheet
FS-1
Inspection Fact Sheet
Name and Address of Building/Structure
Residential House
Name and Address of Building/Structure Owner
NYS Office for people with Developmental Disabilities
6666 Babcock Hollow Road
Bath, New York 14810
Name and Address of Owner’s Agent
LaBella Associates, D.P.C.
300 State Street, Suite 201
Rochester, New York 14614
Name of the Firm & Person Conducting the Inspection
Chris Enright (NYSDOL Cert. #06-08603)
Date the Inspection Was Conducted
February 12, 2020
Appendix B
Sample Location Drawing
Boiler Room
Electrical Room
Storage Room
Stairwell
Project Number: 2200856
Wells Curtice IRA House
5580 Wells Curtice Road, Canandaigua NY
Basement Bulk Samples
A
BD
C
2A,B
1A,B
Confirmed ACM Bold and Underlined Project Number: 2200856
Wells Curtice IRA House
5580 Wells Curtice Road, Canandaigua NY
Interior/Exterior Bulk Samples
Roofing Samples
4B 7B 10A,B 25A
9B
8B 11A 12A 13A 14A
9D
21A,B
9G
11B 12B 23A,B
17A,B
18A,B 19A,B
20A,B 25B
9C 22A,B 24A
13B 14B 15A
9E
9F
16B 16A
24B
3A,B 4A 5A,B 6A,B 7A 8A 9A
15B
27A,B
29A,B
32A
30B 31A
31B 32B
30A
26B 28B
26A 28A
A
B D
C
Appendix C
Inspection Photos
Photo 1
Black asbestos-containing roof cement located along the silver roof vents
Appendix D
Laboratory Analytical
Reports
XRF Lead Sampling Summary Table
LaBella Project No. 2200857
I = Intact Condition. No visible damage or deterioration
P = Poor Condition. Paint is chipped, peeling, or otherwise damaged
Reading No. Location (Room) Wall (A, B, C D) &
Structure Substrate Color XRF Result
1 Calibration Check ----- ----- ----- PASS
2 Basement Stairwell A, Wall Drywall White 0.00
3 Basement Stairwell A, Wall Base Vinyl Black 0.00
4 Basement Stairwell A, Door Case Metal Cream 0.00
5 Basement Stairwell A, Door Metal Cream 0.00
6 Basement Stairwell A Stringer Wood White 0.00
7 Basement Stairwell Stair Riser Wood White 0.00
8 Basement Stairwell Stair Tread Vinyl Gray 0.04
9 Basement Stairwell A, Handrail Wood Brown 0.00
10 Basement Storage A, Wall Drywall White 0.00
11 Basement Storage A, Wall Base Vinyl Black 0.00
12 Basement Storage C, Wall CMU White 0.00
13 Basement Storage Ceiling Drywall White 0.00
14 Basement Storage I-Beam Metal White 0.00
15 Basement Storage Support Beam Metal Red 0.00
16 Basement Storage Pipe Metal Black 0.00
17 Electrical Room A, Wall CMU White 0.00
18 Electrical Room A, Wall Metal Gray 0.00
19 Electrical Room B, Wall Wood Black 0.00
20 Boiler Room A, Wall CMU White 0.00
21 Boiler Room A, Wall Metal Red 0.00
22 Boiler Room Ceiling, I-Beam Metal White 0.00
23 Boiler Room Support Beam Metal Red 0.00
24 Room 104 A, Wall Drywall Green 0.00
25 Room 104 A, Wall Base Vinyl Green 0.08
Reading No. Location (Room) Wall (A, B, C D) &
Structure Substrate Color XRF Result
26 Room 104 D, Wall Counter Wood Tan 0.00
27 Room 101 A, Wall Door Metal Blue 0.00
28 Room 101 A, Side Light Window Wood White 0.00
29 Room 101 B, Wall Drywall Gray 0.00
30 Room 101 C, Door Case Metal White 0.00
31 Room 101 B, Wall Door Metal Blue/gray 0.00
32 Room 101 Floor Ceramic Red 0.00
33 Room 106 A, Wall Drywall Tan 0.00
34 Room 106 A, Wall Base Ceramic Pink 0.00
35 Room 106 Floor Ceramic Pink 0.00
36 Room 106 Sink Porcelain White 0.00
37 Room 106 Toilet Porcelain White 0.00
38 Janitor’s Closet D, Wall Ceramic White 0.00
39 Room 157 A, Wall Drywall White 0.00
40 Room 157 Door Wood Brown 0.00
41 Room 155 A, Wall Drywall White 0.00
42 Room 155 A, Wall Base Vinyl Tan 0.00
43 Room 155 C, Wall Wood White 0.00
44 Room 155 D, Wall Drywall Green 0.00
45 Room 153 A, Wall Drywall Blue 0.00
46 Room 153 A, Wall Base Wood Brown 0.00
47 Room 150 A, Wall Drywall Lavender 0.00
48 Room 150 A, Wall Base Ceramic White 0.00
49 Room 150 Floor Ceramic White 0.00
50 Room 150 A, Wall Ceramic Blue/gray 0.01
Reading No. Location (Room) Wall (A, B, C D) &
Structure Substrate Color XRF Result
51 Room 147 A, Toilet Porcelain White 0.00
52 Room 147 B, Wall Ceramic Tan 0.00
53 Room 145 A, Wall Drywall Gray 0.00
54 Room 145 A, Wall Base Vinyl Tan 0.00
55 Room 143 A, Wall Drywall Brown 0.00
56 Room 143 A, Door Wood Brown 0.00
57 Room 143 A, Wall Door Frame Metal White 0.00
58 Room 134 A, Wall Drywall Brown 0.00
59 Room 133 C, Wall Drywall Tan 0.00
60 Room 133 C, Wall Base Vinyl Brown 0.00
61 Room 133 B, Window Case Wood Brown 0.00
62 Room 132 C, Window Case Wood White 0.00
63 Room 132 A, Wall Vinyl Cream 0.00
64 Room 111 C, Wall Drywall Yellow 0.00
65 Room 111 C, Wall Base Vinyl Tan 0.00
66 Room 125 B, Wall Drywall Tan 0.00
67 Room 128 B, Wall Drywall White 0.00
68 Room 116 B, Wall Ceramic Yellow 0.00
69 Room 116 Floor Ceramic Gray 0.00
70 Room 114 B, Wall Ceramic White 0.00
71 Room 114 C, Sink Porcelain White 0.00
72 Room 114 C, Toilet Porcelain White 0.00
73 Room 114 A, Wall Drywall Brown 0.00
74 Room 114 Floor Ceramic Breen 0.00
75 Room 137 B, Wall Drywall Blue 0.00
Reading No. Location (Room) Wall (A, B, C D) &
Structure Substrate Color XRF Result
76 Room 137 B, Door 2 Casing Wood White 0.00
77 Room 109 A, Wall Drywall Tan 0.00
78 Room 110 A, Wall Drywall Green 0.00
79 Room 120 A, Wall Drywall Purple 0.00
80 Room 120 Floor Wood Brown 0.00
81 Room 120 A, Wall Drywall White 0.00
82 Garage D, Door Metal Gray 0.00
83 Exterior A, Window Sash Metal White 0.00
84 Exterior A, Window Shutter Wood Maroon 0.00
85 Exterior A, Window Casing Wood White 0.00
86 Exterior B, Window Casing Wood White 0.00
87 Calibration Check ----- ----- ----- PASS
Appendix E
Licenses and Certifications
New York State – Department of Labor Division of Safety and Health License and Certificate Unit State Campus, Building 12
Albany, NY 12240
ASBESTOS HANDLING LICENSE
Suite 201 300 State Street
Rochester, NY 14614
FILE NUMBER: 99-1172
LICENSE NUMBER: 29278
LICENSE CLASS: RESTRICTED
DATE OF ISSUE: 02/06/2020
EXPIRATION DATE: 02/28/2021
Duly Authorized Representative – Greg Senecal:
This license has been issued in accordance with applicable provisions of Article 30 of the Labor Law of New York State and of the New York State Codes, Rules and Regulations (12 NYCRR Part 56). It is subject to suspension or revocation for a (1) serious violation of state, federal or local laws with regard to the conduct of an asbestos project, or (2) demonstrated lack of responsibility in the conduct of any job involving asbestos or asbestos material.
This license is valid only for the contractor named above and this license or a photocopy must be prominently displayed at the asbestos project worksite. This license verifies that all persons employed by the licensee on an asbestos project in New York State have been issued an Asbestos Certificate, appropriate for the type of work they perform, by the New York State Department of Labor.
Eileen M. Franko, Director SH 432 (8/12) For the Commissioner of Labor
Labella Associates, D.P.C.
has fulfilled the requirements of the Toxic Substances Control Act (TSCA) Section 402, and has received certification to conduct lead-based paint activities pursuant to 40 CFR Part 745.226
All EPA Administered Lead-based Paint Activities Program States, Tribes and Territories
This certification is valid from the date of issuance and expires September 26, 2021
Certification #
LBP-2226-1
Issued On
September 04, 2018
Michelle Price, Chief
Lead, Heavy Metals, and Inorganics Branch
File details come from the government source that posted it. Updated .