Project: Aaon Unit Location: Beaufort, NC Replacement Unit
Qty 1 Aaon Packaged Unit - Model: RN-060 Supply Air: 7,000 CFM (2" ESP) | Outdoor Air (OA): 7,000 CFM
208/3/60 | MCA: 372 A | MOCP: 450 A
Refrigerant Style: R-410A Scroll Compressor Unit Configuration: Air-Cooled Condenser with 6-Row High Efficiency Evaporator Coil Cooling/Heat Pump Staging: 4 Stage - Four stage cooling unit or four stage cooling and four stage heat pump heating unit without auxiliary heat.
Heat Type: Electric Heat Heat Staging: Modulating/SCR Electric - 0-10V Control Signal Return/Outside Air Section: Motorized 100% Outside Air Dampers, No Return Air OA Control: 2 Position Actuator Pre-Filters: Metal Mesh Outside Air Pre-Filter Unit Filter: 4” Pleated Unit Filter - MERV 8 Refrigeration Options: Polymer E-Coated Modulating Hot Gas Reheat + Hot Gas Bypass Lead Outside Air or Preheat Configuration: None Controls Vendor: WattMaster Orion VCC-X Controls System + Integrated BACnet MSTP Options Included: Start-Up | Polymer E-Coated Evap & Cond Coils | Phase & Brown Out Protection | Non-Fused Disconnect
| GFI Outlet | Compressor Isolation Valves | Sight Glass | remote Safety Shutdown Terminals | Clogged Filter Switch | Magnehelic Gauge
2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094 AAONEcat32 Ver. 4.288 (SN: 5408304-)
A
B
C
D
A
B
C
A
B
C
A
B
RN-060-8-A-BB14-1AA:M000-U0B-KDH-BBC-0RQ0HBF-00-0000000VB
Tag: RTU# 1
Job Information Unit Information
Job Name: Approx. Op./Ship Weights:
Job Number: Supply CFM/ESP:
Site Altitude:
Refrigerant
Final Filter FV / Qty:
Outside CFM:
Ambient Temperature:
5531 / 5531 lbs. (±5%) 7000 / 2 in. wg.
145.83 fpm / 24
95 ºF DB / 78 ºF WB
Static Pressure
External: Economizer:
Evaporator: Heating:
Filters Clean: Cabinet:
Dirt Allowance Re-Heat Coil:
Total:
0.00 in. wg.
0.02 in. wg.
0.09 in. wg.
2.00 in. wg.
0.11 in. wg.
0.02 in. wg.
0.35 in. wg. 0.01 in. wg.
2.61 in. wg.
Cooling Section Heating Section
Gross Net Total Capacity:
Sensible Capacity:
Latent Capacity:
Mixed Air Temp:
Entering Air Temp:
Lv Air Temp (Coil):
Lv Air Temp (Unit) Supply Air Fan:
SA Fan RPM / Width:
Evaporator Coil:
Evaporator Face Velocity:
629.56 615.82 MBH
331.03 317.30 MBH
298.52 MBH
95.00 ºF DB 78.00 ºF WB
95.00 ºF DB 78.00 ºF WB
49.11 ºF DB 48.91 ºF WB
50.90 ºF DB 49.71 ºF WB
1 x 245D @ 4.95 BHP 1384 / 5.560"
43.8 ft² / 6 Rows / 12 FPI
160.0 fpm
PreHeat Type: Std (No Preheat)
Heating Type:
Heating CFM:
Total Capacity:
OA Temp:
RA Temp:
Entering Air Temp:
Leaving Air Temp:
Input:
Heater Qty:
Electric Heat FLA:
Electric Heat
410.2 MBH
26.0 ºF DB / 22.0 ºF WB
75.0 ºF DB / 62.0 ºF WB
26.0 ºF DB / 22.0 ºF WB
80.3 ºF DB / 51.3 ºF WB
8 x 15.0 kW 333.6
Re-Heat Coil:
Capacity: 158 MBH
LA DB / WB: 70.00 ºF / 57.58 ºF
RH: 47%
Rating Information
Cooling Capacity (MBH): 630.0 Cooling EER: 10.5 Cooling IEER: 12.3 Rated in accordance with AHRI 340/360
Application EER @ Op. Conditions: 10.3
Electrical Data
Rating: Minimum Circuit Amp:
Unit FLA: Maximum Overcurrent:
208/3/60 372 364 450
Qty HP VAC Phase RPM FLA RLA Compressor 1: 4 208 3 51.3 Condenser Fans: 6 0.75 208 3 1080 3.4 Supply Fan: 1 10.00 208 3 1760 30.8
Cabinet Sound Power Levels*
Octave Bands: 63 125 250 500 1000 2000 4000 8000 Discharge LW(dB): 89 87 90 94 90 86 81 76 Return LW(dB): 75 71 70 64 64 58 46 35 *Sound power levels are given for informational purposes only. The sound levels are not guaranteed.
Unit Rating
A
B
C
B
C
A
B
A
B
Job Name: Unit Submittal For:
Job Number: Unit Submittal Date:
Base Option Description
R Series Roof Top Unit
N Generation Ninth Generation
060 Unit Size Sixty
8 Voltage 208V/3Ø/60Hz
A Interior Protection Interior Corrosion Protection
B Refrigerant Style R-410A
B Unit Configuration Air-Cooled Cond. + 6 Row Evap. Coil
1 Coil Coating Polymer E-Coated Evap. and Cond. Coils
4 Cooling/Heat Pump Staging 4 Stage
1 Heating Type Electric Heat
A Heating Designation Heat A - 120.1 kW
A Heating Staging Modulating/SCR Electric - 0-10V Control Signal
Feature Option Description
M 1A. RA/OA Section Motorized 100% Outside Air Dampers - No RA Opening
0 1B. RA/EA Blower Configuration Standard - None
0 1C. RA/EA Blower Standard - None
0 1D. RA/EA Blower Motor Standard - None
U 2. OA Control 2 Position Actuator
0 3. Heat Options Standard
B 4. Maintenance Options 115V Convenience Outlet - Factory Wired
K 5A. SA Blower Configuration 1 Blower + Premium Efficiency TEFC Motor + 1 VFD
D 5B. SA Blower 24'' Direct Drive Backward Curved Plenum
H 5C. SA Motor 10 hp - 1760 rpm
B 6A. Pre Filter Type Metal Mesh OA Pre Filter
B 6B. Unit Filter Type 4" Pleated - 30% Eff
C 6C. Filter Options Clogged Filter Switch + Magnehelic Gauge
0 7. Refrigeration Control Standard - Adj Comp. Cooling Lock Out Through Unit Controls
R 8. Refrigeration Options HGB Lead + Polymer E-Coated MHGR
Q 9. Refrigeration Accessories VFD Condenser Fan - Head Pressure Control + Sight Glass + Compressor Isolation Valves
0 10. Power Options Standard Power Block
H 11. Safety Options Remote Safety Shutdown Terminals
B 12. Controls Phase & Brown Out Protection
F 13. Special Controls Make Up Air Unit Controller - CV Cool + CV Heat
0 14A. Outside Air Configuration Standard - None
0 14B. Preheat Sizing Standard - None
0 15. Glycol Percent Water or No WSHP
0 16. Interior Cabinet Options Standard - Double Wall + R-13 Foam Insulation + Stainless Steel Drain Pan
0 17. Exterior Cabinet Options Standard
0 18. Customer Code Standard
0 19. Code Options Standard - ETL U.S.A. Listing
0 20. Crating Standard
0 21. Water-Cooled Cond. Standard - None
V 22. Control Vendors VCC-X Controls + Integrated BACnet MSTP
B 23. Type Standard - Includes AAON Gray Paint
Unit Submittal
A
B
C
B
C
A
B
A
B
Job Name: VCCX For:
Job Number: VCCX Date:
Hardware Included For VCCX Controller
Part # Included Parts Assigned Channel BACnet Point
ASM01698 VCCX2 CONTROLLER
V13050 OSA Temp/Hum Sensor EBUS2 communicating sensor AI:16,AI:17,AI:18,AI:19 R82890 Supply Temp Sensor - Field Installed VCCX control point AI 3 AI:9
Supply Fan Control Signal 0-10VDC VCCX control point AO 1 AI:22 Economizer VCCX control point AO 2 AI:30 Modulated Heating (0-10VDC) VCCX control point AO 3 AI:35
R62330 Proof of Air Flow VCCX control point BI 1 BI:6 R64580 Dirty Filter Sensor VCCX control point BI 2 BI:25
Safety Shut Down VCCX control point BI 8 BI:26 Supply Fan Configured Relay point BI:63 Heat 1 Configured Relay Point BI:64 Heat 2 Configured Relay Point BI:65 Heat 3 Configured Relay Point BI:66 Heat 4 Configured Relay Point BI:67
ASM02201 DIGITAL REFRIGERATION MODULE 1
V38391 Suction Pressure Sensor A RSMD 1 point SP-1 AI:48 V38410 Discharge Pressure Sensor A RSMD 1 point HP-1 AI:50 V38410 Discharge Pressure Sensor C RSMD 1 point HP-2 AI:55
Modulated Condenser Signal CD RSMD 1 point AOut1 AI:44 Modulated Condenser Signal AB RSMD 1 point AOut1 BI:
Comp Status Input A RSMD 1 point BI1 Comp Status Input C RSMD 1 point BI2 BI:79 Emergency Shutdown RSMD 1 point BI4 BI:81,82 Condenser Enable AB RSMD 1 Fixed Relay point BI:78,BI:85 Condenser Enable CD RSMD 1 Fixed Relay point BI:86 Comp Enable A RSMD 1 Fixed Relay point AI:46 Comp Enable C RSMD 1 Fixed Relay point BI:77,BI:84
ASM02201 DIGITAL REFRIGERATION MODULE 2
V38410 Discharge Pressure Sensor B RSMD 2 point HP-1 AI:50 V38410 Discharge Pressure Sensor D RSMD 2 point HP-2 AI:55
Comp Status Input B RSMD 2 point BI1 Comp Status Input D RSMD 2 point BI2 BI:79 Emergency Shutdown RSMD 2 point BI4 BI:81,82 Comp Enable B RSMD 2 Fixed Relay point AI:46 Comp Enable D RSMD 2 Fixed Relay point BI:77,BI:84
ASM01670 MODULATING HOT GAS REHEAT MODULE
Reheat HGR Valve MHGRV-X AI:42 Reheat 2 Position HGR Valve Enable MHGRV-X
VCCX Components
JOB INFORMATION: WHEEL SPECIFICATION:
Job Name: Max RPM:
Job Tag: Diameter x Qty:
Rep Firm: CFM:
Date: Tip Speed:
Inertia:
2,000
24.5 in. x 1
8,877 FPM
10 WR²
OPERATING CONDITIONS: MOTOR SELECTION:
Air Flow: Rated HP / Bypass:
Static Pressure: Frame Size:
Relief Dampers DP: Nominal RPM:
VAC/PH/HZ:
TSP: Efficiency Site Altitude: Enclosure Type:
TSP @ Sea Level: Max Inertial Load:
7,000 CFM 10 / No
2.61 in. Wg. 215T
0.00 in. Wg. 1760
208/3/60
2.61 in. Wg. Premium / 0.917
10.00 Ft TEFC
2.61 in. Wg. 82 WR²
*Please Contact Factory.
FAN PERFORMANCE: FAN SOUND POWER (Inlet/Outlet):
RPM: Octave Band: (Re 10^-12 watts)
BHP: 1 2 3 4 5 6 7 8
Efficiency:
In/Out Velocity:
Plenum Out Velocity: SOUND POWER A-Weighted: 91 / 96 dB
Max Duct SP with Blocked Airway: 3.3 in. Wg. @ 1384 rpm
4.95 58.2% 88 87 86 85 84 83 80 78
2141/2357 FPM 89 87 90 95 93 89 85 80
79 FPM
RPM
BHP
SYSTEM
Efficiency
SP Surge
CFM Min
Supply Fan Model: 245D @ 1384 RPM and 100% Width Design Conditions: 7000 CFM @ 2.61" SP
CFM x 1000 109876543210
S P
B H
P
40%
20%
0%
RPM: 1384
BHP: 4.95
EFFICIENCY: 58.16
24.5" STAR Plenum