A06-Specifications.pdf

PDF 678 KB Posted

Attached to
WI-GENOA NFH-COLDWATER NORTH BLDG
Solicitation number
140F0221R0007
Issued by

About this file

This document package includes specifications for a construction project and a related federal solicitation. The specifications call for rehabilitation work at the Coldwater North Building at the Genoa National Fish Hatchery in Wisconsin, including removing existing structures, constructing new reinforced concrete raceways and a headwall tank, installing a concrete floor and exterior slabs, and connecting new PVC piping. The work also includes erosion control, earthwork, aggregate base installation, geotextile fabric, seeding, reinforcing steel, cast-in-place concrete, miscellaneous metals, and a trench drain system. The related solicitation is for this same scope of work at the Genoa NFH Coldwater North Building and was issued by the Department of the Interior Fish and Wildlife Service.

View the file

Other files

File Type Posted
A06-Drawings.pdf PDF
NoticetoOfferors.pdf PDF
BidBondForm.pdf PDF
safety checklist.pdf PDF
B03-DOLWageDetermination.pdf PDF
CPARS Notice.pdf PDF
PPQ.docx DOCX document
Sol_140F0221R0007.pdf PDF
19-FS-014_BIDSCH.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

UNITED STA , �F THE INTERIOR

FISH 1ND�I SERVICE

MID � � .3

lnfrastruct0-re .. t Division

Station Name/ Address:

Project Name/Number:

5600 Am\rica d. W€st�uite 990 Bloo ingt N"ss437-1458

U.S.

FISH & WILDLIFE

SERVICE

GENOA NATIONAL FISH HATCHERY

S 5631 State Highway 35, Genoa Wisconsin, 54632

COLDWATER NORTH BUILDING REHAB

19-FS-014

PROJECT MANUAL

Page J – 1

PART III, SECTION J

LIST OF DOCUMENTS, EXHIBITS, AND OTHER ATTACHMENTS

INDEX

TECHNICAL PROVISIONS/SPECIFICATIONS

DIVISION 1 - GENERAL REQUIREMENTS

SECTION 01100 SUMMARY OF THE WORK

SECTION 01310 PROJECT COORDINATION

SECTION 01330 SUBMITTALS

SECTION 01420 DEFINITIONS AND STANDARDS

SECTION 01770 PROJECT CLOSEOUT

DIVISION 2 - SITE WORK

SECTION 02050 EROSION CONTROL

SECTION 02200 EARTHWORK

SECTION 02224 AGGREGATE BASE COURSE

SECTION 02270 GEOTEXTILE FABRIC

SECTION 02668 DRAIN PIPING

SECTION 02930 SEEDING

DIVISIONS 3-16 - NOT USED

SECTION 03210 REINFORCING STEEL

SECTION 03300 CAST-IN-PLACE CONRETE

DIVISIONS 4 - NOT USED

SECTION 05120 MISCELLANEOUS METALS

SECTION 05050 TRENCH DRAIN

DIVISIONS 6-16 - NOT USED

Page J – 2

ATTACHMENTS

PRECONSTRUCTION SAFETY CHECKLIST

SUBMITTAL REGISTER

DRAWINGS

Drawing Number Description Sheet

3F-WS-126-521 Vicinity Map/Drawing Index 1 of 8 3F-WS-126-522 Demolition Plan 2 of 8 3F-WS-126-523 Building Floor Plan 3 of 8 3F-WS-126-524 Concrete Raceway Details 4 of 8 3F-WS-126-525 Concrete Raceway Reinf. Details 5 of 8 3F-WS-126-526 Concrete Headbox Details 6 of 8 3F-WS-126-527 Concrete Headbox Reinf. Details 7 of 8 3F-WS-126-528 Details 8 of 8

DIVISION 1 SECTION 01100

GENERAL REQUIREMENTS SUMMARY OF THE WORK

01100-1

A. General

1. Project Title: Coldwater North Quarantine Building /

Raceway Rehabilitation.

2. All applicable Sections of the Federal Acquisition Regulations (FAR) and Division 1 apply to each Section of this Technical Specification (Division 2 through 16).

3. Payment for work done under this contract shall be made in accordance with the lump sum and unit price bid therefore in the Bidding Schedule, and in accordance with subsequent addenda, Change Orders, and/or Extra Work Orders.

B. Work and Payment Under This Contract

1. The work in this contract is listed below. Measurement and payment shall include but not be limited to furnishing materials, labor, and equipment for work defined below.

Base Bid

Raceway Rehabilitation: Work includes removal of 2 existing fiberglass raceway structures and a headwall tank inside a 30’ x 90’ metal building, construction of two new 6’ wide x 62’long reinforced concrete raceways and 8’x 14’ headwall tank structure, laying new reinforced 6” thick concrete floor and exterior concrete building slabs, cutting exiting and installing new PVC piping to 2 new reinforced concrete raceways and 4 existing 16’ x 3’ fiberglass raceway tanks and work to include all mobilization, demobilization, excavation, laying of plastic foundation fabric, soil and gravel backfill, compaction and testing, surveying and layout for piping and floor slope drainage, miscellaneous work required for removal and replacement of metal building foam insulation necessary for concrete floor construction, and removal and trucking of all waste material to off-site location.

01100-2

Payment for this item shall be made lump sum per unit item bid.

C. Location And Inspection Of Site

1. The site of the work is located at the Genoa National Fish Hatchery near Genoa, Wisconsin. The mailing address is shown on the Solicitation, Offer, and Award (Standard Form 1442) as attached to this Invitation.

The Hatchery Manager may be contacted for further information at the above referenced address or by telephone at (608) 689-2605.

2. All prospective bidders, contractors, subcontractors, and related persons are encouraged to visit the site of the proposed work and to assess the location and extent of the work prior to submitting bids. Persons may inspect the work site by contacting the Hatchery Manager.

D. Specifications and Drawings for Construction

1. The successful bidder will be provided, upon request, up to 2 sets of additional full size prints of the contract drawings as necessary for execution of this contract.

These drawings will be provided at no additional cost to the successful bidder/quoter.

2. Exact location of all affected utilities will be the responsibility of the contractor. Drawings may not completely show all utilities. Site verification is required in addition to contacting any local authorities and utility companies to determine exact locations of utilities.

3. In case of difference between drawings and specifications, the specifications shall govern.

E. Work Not Included In This Contract

1. All items indicated "NIC" on drawings or specifications are items not included in this contract.

01100-3

2. Work in place is generally shown as "Existing" on the

Contract Drawings.

3. Work to be performed under other contracts and not included as part of this contract is generally shown as "By Others" on the Contract Drawings.

F. Items Provided By The Government

1. Work to be accomplished by the Government or manufactured items to be provided by the Government are generally shown as "By Government" on the Contract Drawings.

G. Engineering Services

1. The Government has established a benchmark for this project. The drawings relate the project to this benchmark. From this benchmark the Contractor shall furnish and place all stakes, marks, and templates required for the performance and completion of the work.

Any benchmarks disturbed or removed during construction shall be reset by the Contractor at their expense.

H. Temporary Facilities

1. Maintain and restore all government roads, service areas, and utilities used to pre-construction condition.

I. Site Access and Right of Way

1. The construction access limits on Government property will be established by the Government and the Contractor shall be responsible for complying with these limits and governing all work accordingly. All temporary access roads shall be removed following work completion unless directed otherwise by the Contracting Officer.

2. All bidders are reminded that they are responsible for contacting the local entity such as township, county, or state having jurisdiction in the project vicinity to

01100-4 insure bidders/quoters are aware of any requirements of the local entity. These requirements are between the entity and the bidder. Load limits and other restrictions shall be obeyed. If the Contractor proposes to cross private property, permission must be obtained from the owner to use private property or roads in the conduct of the work.

3. Work scheduled on Saturdays, Sundays, Federal Holidays or other than normal working hours shall be approved in advance by the Government.

J. Safety - In addition to FAR 52.236-13 Accident Prevention

1. Contractor shall fill out and submit the “Preconstruction Safety Checklist” to the Contraction Officer (CO) prior to beginning construction.

2. The contractor shall designate a safety officer to ensure a safe work site. The safety officer shall perform daily work site inspections to assure compliance with all safety regulations and standards.

3. The Contractor’s Safety Plan shall be available on-site.

The Contractor shall provide Material Safety Data Sheets (MSDS) for all hazardous materials brought on-site. MSDS shall be made available in a conspicuous location.

4. All equipment and work activities shall comply with OSHA

Regulations and all accidents incidental to work performed under this contract shall be reported in accordance with OSHA reporting requirements.

Additionally a copy of the accident report shall be provided to the Contracting Officer.

5. The Contractor shall provide and install barricades, signs, or other warning devices to delineate the construction area and restrict public access to the construction site. Follow the Manual of Uniform Traffic Control Devices (MUTCD).

01100-5

6. Provide at least one non-freezing-type fire extinguisher in each workshop and shed used for storage of materials on the premises. Place in location readily accessible to workers.

7. Provide at least on non-freezing type fire extinguisher of the appropriate class for each group of workers performing flammable operations.

8. Provide and maintain a basic first aid kit for use of workers.

(a) Provide first aid supply commensurate with size of project and provide items necessary for first aid treatment of all injuries. The first aid supply shall include items identified on the Material Safety Data Sheets (MSDS) and be placed in applicable locations.

(b) Advise all workers of the location of first aid supplies.

(c) Post telephone numbers of nearest hospital or ambulance service and fire station in conspicuous location. Advise all workers of location of telephone numbers.

9. Provide necessary Personnel Protective Equipment (PPE) as identified by MSDS and OSHA regulations. Provide documentation workers have been trained in use of PPE prior to individual use.

(END OF SECTION 01100)

DIVISION 1 SECTION 01310

GENERAL REQUIREMENTS PROJECT COORDINATION

01310-1

A. Jobsite Administration - Superintendence, Subcontract administration and Quality Control, is the responsibility of the Contractor.

1. Final decisions relative to items in conflict shall be made by the Contracting Officer.

2. The Government shall have the authority to temporarily suspend the work for such time as necessary because of the failure on the part of the Contractor to perform any of the provisions of the contract, and no extension of contract performance time will be allowed for such suspensions. Resumption of work will not be permitted until the Government determines that the defi-ciencies in performance, which caused the temporary suspension, have been corrected.

3. The Contractor shall notify the Engineer at least ten

(10) days prior to the anticipated date of completion of all work specified herein. Upon completion of the work, the Engineer shall proceed with the final inspection which shall be completed as promptly as practicable.

The time required for such inspection and for performing any corrective work shall be included in the contract performance time.

B. Modification/Change Order procedures

1. In the event of the need for a change order, the Contractor will receive a letter requesting a price quote for proposed changes to the contract.

2. For evaluation purposes, the Contractor's quote shall be broken down to show the costs of labor and materials for each proposed category of work included with the change, along with the total cost for Contractor's overhead, profit, and bond for the proposed changes.

3. All contract time extensions required as a result of a proposed change must be justified and supported in detail at the time of the proposal.

DIVISION 1 SECTION 01310

GENERAL REQUIREMENTS PROJECT COORDINATION

01310-2

C. Preconstruction Conference

1. Soon after award of the Contract and prior to commencing construction, the Contractor and any subcontractors shall attend a preconstruction conference with representatives of the Government. Timely notification of the meeting will be given to the Contractor. Time, date, and place of the conference will be determined by the Contracting Officer. Requirements pertaining to con-tract administration, construction operations and the project schedule will be discussed. The project schedule shall be in accordance with Section 01330.

2. The Preconstruction Safety Checklist must be submitted for review and completion during the Preconstruction Conference.

D. Progress Meetings

1. Periodic general project meetings will be conducted with a representative of the Contractor at the project site or by telephone by the Government's representative for the purpose of coordinating, expediting, and assessing the work progress.

2. The Contractor shall provide reports of progress on the project, discuss the work schedule for the coming period, and present all conflicts, discrepancies or other difficulties for resolution. A record of discussions and decisions will be prepared by the Government and distributed to those attending and others affected.

(END OF SECTION 01310)

DIVISION 1 SECTION 01330

GENERAL REQUIREMENTS SUBMITTALS

01330-1

A. General Refer to submittal register or technical specifications for all submittals required.

When specifically requested by the Government representative, the Contractor shall provide copies of manufacturer's literature containing detailed specifications and performance data or shop drawings fully describing the items and written installation instructions and/or recommendations for review and approval prior to accomplishing equipment installation.

B. Submittal Register:

1. A submittal register, listing all items requiring submittals under this solicitation, is provided as an attachment to this document. The Contractor shall provide all required submittals to the Engineer within 21 days of award except for items noted otherwise on the submittal register.

2. Furnish four copies of all required submittals. Three copies will be retained by the Government. One copy will be returned to the Contractor.

3. The approval of submittals shall not relieve the contractor to comply with the terms and conditions of the contract drawings and specifications. The contractor shall be responsible to determine correct dimension, design, connection, detail and satisfactory construction of all work.

C. Project Schedule: Contractor shall provide as required by

Federal Acquisition Regulation (FAR) clauses. *

D. Price Breakdown - Lump Sum Items: Contractor shall provide as required by FAR clauses. *

E. Subcontractor's List

Submit a list of subcontractors who will be working on the project.

DIVISION 1 SECTION 01330

GENERAL REQUIREMENTS SUBMITTALS

01330-2

F. Submittal of Progress Payment Certificate: Contractor shall provide as required by FAR clauses. *

G. Guarantees, Warranties And Certificates -Refer to Section

01770.

H. Operating And Maintenance Instruction - Refer to Section

01770

I. Delivery Tickets

1. The Contractor shall submit to the Government's on site representative, one legible copy of each delivery ticket for all material delivered to the construction site.

2. The delivery ticket shall show brand name, catalog number, and number of items received.

J. Waste Manifests

4. The Contractor shall submit copies of all waste manifests.

5. Manifests shall state type of waste (i.e., construction debris, hazardous asbestos, etc.), location of disposal, landfill designation, EPA registration of landfill, and EPA registration for transportation of any hazardous wastes.

* The applicable FAR clauses will be provided in full text to the resultant contractor at the pre-construction conference.

(END OF SECTION 01330)

DIVISION 1 SECTION 01420

GENERAL REQUIREMENTS DEFINITIONS AND STANDARDS

01420-1

A. Regulatory Requirements

1. All work shall be accomplished in strict accordance with the regulations, codes, and laws in effect at the time the work is performed for the location where it is to be performed.

B. Means and Methods

1. Means and methods used in the performance of this contract must be in accordance with all applicable Federal Acquisition Regulations in addition to OSHA regulations, 29 Code of Federal Regulations, acceptable industry practices as recognized by societies, associations, building codes, manufacturers’ specifications and any applicable state safety and health requirements.

C. Permits

1. All permits required to support construction activities such as road permits for oversize, overweight vehicles and equipment, bridge permits, and utility hookup permits, shall be obtained and paid for by the Contractor.

(END OF SECTION 01420)

DIVISION 1 SECTION 01770

GENERAL REQUIREMENTS PROJECT CLOSEOUT

01770-1

A. Manufacturer's Specifications

1. The installation of manufactured products and equipment, together with all associated parts, shall be in conformance with the manufacturer's recommendations, and code requirements. All installations shall be complete and ready for immediate use, and every essential part required for proper operation of the manufacturer's equipment shall be provided. Following the completion of the work under this contract, all installed equipment shall be tested for proper operation and compliance with the contract.

B. Final Inspection

1. The Contractor shall request a final inspection in writing at least ten (10) days prior to the anticipated date of completion.

2. Work will not be considered ready for final inspection until all the work has been completed and the Contractor has certified that all items are properly operating and in strict compliance with all contract terms and conditions.

3. The Contractor or the project supervisor shall be at the job site during the final inspection.

C. Tests

1. Submit reports of all tests to the Contracting Officer prior to final payment.

D. Record Drawings

DIVISION 1 SECTION 01770

GENERAL REQUIREMENTS PROJECT CLOSEOUT

01770-2

The Contractor shall provide and maintain in proper order and in good, clean condition, in the field or the Refuge office or at the project site, one (1) complete set of full size prints of all drawings. On this set, with red pencil or ink, the Contractor will neatly inscribe all changes in work. At time of final acceptance, and prior to final payment, these corrected prints will be presented to the Engineer. The Contractor will note all data and changes on these record drawings in sufficient detail and clarity to provide information necessary for preparation of "as built" drawings by the Government.

E. Guarantees, Warranties and Certificates

1. The Contractor will submit all guarantees, warranties and certificates to the government prior to final payment.

2. The Government requires a 100% warranty for a period of one full year after final acceptance. Items of work found defective during the warranty period will be replaced at no cost to the Government and the warranty for that particular part of the work shall automatically extend for one full year beyond the completion date of repairs.

3. If a manufacturer or supplier offers a guarantee in excess of the one year requirement outlined herein, then the longer guarantee period will apply for those particular items.

(END OF SECTION 01770)

DIVISION 2 SECTION 02050

SITE WORK EROSION CONTROL FENCING

02050-1

1. The requirements of this section shall govern the work necessary to place the silt fence required for erosion control.

2. Submittal: The contractor shall submit all materials and dimensions used for the silt fencing including wood stakes, geo-textile fabric, silt screen or other miscellaneous components of the silt fence.

B. Material

The geo-textile fabric shall conform to the following characteristics or be a substitute provided by Contractor and approved by the Engineer:

TEST METHOD VALUE

Min. Grab Strength ASTM D 4632 120 Lbs Machine Direction

Min. Grab Strength ASTM D 4632 100 Lbs Cross Machine Direction

Max. Apparent Opening Size ASTM D 4751 No. 30

Minimum Permittivity ASTM D 4491 0.05, s-1

Minimum Ultraviolet stability ASTM D 4355 70%

C. Execution

1. The Contractor shall provide that during all periods of shipment and storage the silt fence fabric shall be protected from the direct sunlight, ultra-violet rays, temperature greater than 140 degress F and any mud, DIVISION 2 SECTION 02050

SITE WORK EROSION CONTROL FENCING

02050-2 debris, or damaging material. Any defective fabric not acceptable to the Engineer shall not be used. The fabric shall remain in a heavy duty protective covering prior to installation.

2. The silt fence shall protect silt from entering pond areas around the building site.

3. Construction and excavation work shall not be started until the silt fence has been installed.

(END OF SECTION 02050)

DIVISION 2 SECTION 02200

SITE WORK EARTHWORK

02200-1

1. The requirements of this section shall govern the earthwork necessary for grade and sub-grade preparation for the placement of the raceways, headwall, and floor slab to include all excavation, grading, supply and compaction of fill and gravel material, and the removal of all deleterious excavated material.

2. The Contractor shall take reasonable precautions to protect natural plant growth outside of the construction limits against damage from construction operations. The Contractor shall box, pad or fence existing trees or utilities and place silt fencing as appropriate to limit damage to pond areas which may be subject to damage from construction operations.

3. The Contractor shall determine the exact locations of all affected utilities and structures prior to commencing construction and shall govern construction operations in a manner that will prevent damage to them.

4. Submittals: The Contractor shall submit compaction tests for all subgrades. The tests shall be made by an independent testing laboratory and all tests shall be paid for by the Contractor.

a. In-place field density tests of the sub-grade shall be tested for compliance with these specifications in accordance with ASTM Standards. Tests which do not meet the density standards shall be repeated after the material has been re-compacted.

Compaction shall not be less than 100% Standard Proctor for subgrades.

b. All density tests shall be in accordance with ASTM Standards for standard proctor maximum dry density specified and within -1 to +3 percent of the soils optimum moisture content.

c. Density Tests Quantities:

DIVISION 2 SECTION 02200

SITEWORK EARTHWORK

1. Base Bid Item Testing - A minimum of 16 tests shall be taken and the locations of those tests shall be at the discretion of the Government Inspector.

1. Existing gravel base and soil materials shall be excavated to a depth necessary to allow placement of the aggregate base under all concrete structures and concrete floor slab areas as shown on the contract drawings and as described herein. Gravel and soil materials removed shall be stockpilied for later reuse if they meet aggregate base requirements.

2. All waste materials encountered or excavated from designated areas shall be removed from the site at the Contractor's expense and disposed of according to local and state code requirements.

3. Following excavation of existing soil and/or base material, the sub-grade shall be tested for density.

Areas not meeting the required density requirements shall be re-compacted. Compaction shall not be less than 100% Standard Proctor for subgrades under all concrete structures and floor slab areas.

2. Grading of the sub-grade shall be smoothed and trimmed and shall be free of depressions or lumps, to a tolerance of 0.1 foot. Sub-grade shall be sloped as shown on the contract drawings. The sub-grade shall be maintained in a smooth condition until the aggregate or fill has been placed.

(END OF SECTION 02200)

DIVISION 2 SECTION 02270

SITEWORK GEOTEXTILE FABRIC

02270-1 necessary to place the geotextile fabric. Geotextile fabric shall be used in conjunction with riprap for erosion protection at pre-cast concrete end section outlets.

2. Submittal: The brand geotextile fabric to be used shall be accepted on the following basis: The Contractor shall furnish the Engineer a mill certificate or affidavit signed by a legally authorized official from the company manufacturing the fabric. The mill certificate or affidavit shall attest that the fabric meets the requirements stated in these specifications.

The filter fabric shall be pervious sheet, woven or non-woven, resistant to deterioration in soil construction applications. The filter fabric shall contain stabilizers and/or inhibitors to make the filaments resistant to deterioration due to ultra-violet and heat exposure. The filter fabric shall provide an Equivalent Opening Size (EOS) no finer than U.S. Standard Sieve No. 100 and no coarser than U.S. Standard Sieve No. 70. EOS shall be measured in accordance with CW-02215 (Corps of Engineers, November, 1977). The fabric Grab Tensile Strength (ASTM D- 1682) shall exceed 250 pounds in any principal direction.

The fabric puncture Strength (ASTM D-751) shall exceed 120 psi. The burst strength (ASTM D-751) shall exceed 400 psi.

1. The Contractor shall provide that during all periods of shipment and storage the filter fabric material shall be protected from the direct sunlight, ultra-violet rays, temperature greater than 140ΕF and any mud, debris, or damaging material. The fabric shall remain in a heavy duty protective covering prior to

02270-2 installation.

2. Fabric strips shall be placed so as to provide a minimum overlap of three (3) feet. The fabric shall be protected at all times during installation and construction. Damaged fabric shall be replaced, except that holes or tears of not larger than two (2) feet in any direction and not closer than two (2) feet to an edge may be covered with a patch two (2) feet larger than the hole. The fabric shall be covered within 3 days of placement.

(END OF SECTION 02270)

02270-1 necessary to place the geotextile fabric. Geotextile fabric shall be laid below all concrete foundation gravel.

2. Submittal: The brand geotextile fabric to be used shall be accepted on the following basis: The Contractor shall furnish the Engineer a mill certificate or affidavit signed by a legally authorized official from the company manufacturing the fabric. The mill certificate or affidavit shall attest that the fabric meets the requirements stated in these specifications.

The filter fabric shall be pervious sheet, woven or non-woven, resistant to deterioration in soil construction applications. The filter fabric shall contain stabilizers and/or inhibitors to make the filaments resistant to deterioration due to ultra-violet and heat exposure. The filter fabric shall provide an Equivalent Opening Size (EOS) no finer than U.S. Standard Sieve No. 100 and no coarser than U.S. Standard Sieve No. 70. EOS shall be measured in accordance with CW-02215 (Corps of Engineers, November, 1977). The fabric Grab Tensile Strength (ASTM D-1682) shall exceed 250 pounds in any principal direction. The fabric puncture Strength (ASTM D-751) shall exceed 120 psi. The burst strength (ASTM D-751) shall exceed 400 psi.

1. The Contractor shall provide that during all periods of shipment and storage the filter fabric material shall be protected from the direct sunlight, ultra-violet rays, temperature greater than 140 degrees F and any mud, debris, or damaging material. The f abric shall remain in a heavy duty protective covering prior to installation.

02270-2

2. Fabric strips shall be placed so as to provide a minimum overlap of three (3) feet. The fabric shall be protected at all times during installation and construction. Damaged fabric shall be replaced, except that holes or tears of not larger than two (2) feet in any direction and not closer than two (2) feet to an edge may be covered with a patch two (2) feet larger than the hole. The fabric shall be covered within 3 days of placement.

(END OF SECTION 02270)

DIVISION 2 SECTION 02668

SITE WORK DRAIN PIPING

02668-1

1. This work in this section includes installing new PVC pipe for the new concrete raceway structures. This piping will connect to the existing PVC drain piping as shown on the contract drawings.

2. The Contractor shall provide all labor, materials, tools and equipment necessary to install the piping as shown on the contract drawings or specified herein.

3. Related Sections:

Section 02220: Earthwork

4. Submittals: Submit manufacturers specification and data sheets for all PVC pipe, and fittings.

B. Materials

1. Pipe: 8 inch, PVC (Polyvinyl Chloride), ASTM D 1785, Schedule 40.

2. Fittings: Schedule 40 socket-type, solvent cement joint; or elastomeric gasketed joint.

3. Solvent Cement: ASTM D 2564.

4. Gaskets: ASTM F 477, elastomeric seal.

1. General:

a. The raceway supply and drain lines shall be connected to existing 8-inch diameter PVC pipe that runs to existing ponds.

b. Verify locations of any existing underground utilities prior to trenching. If damaged by the Contractor restore in an approved manner at no

02668-2 expense to the Government.

c. Dimensions shown on the drawings are approximate only. The contractor shall verify all piping geometry in the field and shall be responsible for ensuring proper alignment and fit of all piping consistent with the drawings.

d. Field measure critical dimensions and do not fabricate or cut materials to length until such measurements are made.

2. Preparation of Buried Pipe Foundation:

a. Grade trench bottom to provide a smooth, firm, stable, and rock-free foundation throughout the length of the piping.

b. Remove unstable, soft, and unsuitable materials at the surface upon which pipes are to be laid and backfill with aggregate specified in Section 02224 and as shown on the drawings.

c. Shape bottom of trench to fit bottom of piping.

Fill unevenness with tamped backfill. Dig bell holes at each pipe joint to relieve the bells of all loads and to ensure continuous bearing of the pipe barrel on the foundation.

3. Installation of Pipe and Fittings:

a. Pipe: Install PVC, Schedule 40 socket-type, solvent cement or elastomeric gasketed fittings in accordance with manufacturer's installation instructions.

b. Set pipe at elevations shown on the drawings.

c. All piping shall be run as direct as possible, avoiding unnecessary offsets.

02668-3

d. Routes and Grades: Route piping in general locations indicated and in an orderly manner to connect with existing lines.

e. All piping connections shall be made within the building footprint area.

(END OF SECTION 02668)

DIVISION 2 SECTION 02930

SITEWORK SEEDING

02930-1 necessary to seed areas disturbed by construction operations around the Coldwater North Building.

2. All disturbed dike embankment / pond slope areas not receiving gravel replacement shall be reseeded.

3. Preparation of Ground for Seeding: The seedbed shall consist of a minimum of 4-inch depth of loosed friable soil free of refuse, stumps, large roots, rocks over 2 inches in diameter, brush, weeds, or other material which would be detrimental to the proper development of vegetative growth. It shall be capable of supporting normal vegetation. It shall not be taken form a source known to contain any of the noxious weeds listed within these specifications.

4. Seedbed shall have a pH value of 6.2 to 7.4 Testing for pH value shall be performed by the contractor to determine if the seedbed meets these requirements. If necessary, the Contractor shall add agricultural limestone to the seedbed in order to bring the pH within the specified range. Results of the pH tests before and after application of agricultual limestone shall be submitted to the Engineer. (See submittals below.)

5. Seasonal Limitations: For seeding, the normal planting season shall be from April 15th through October 15th.

Seeding at times other than the normal seasonal dates will be allowed only after prior approval by the Engineer. Seeding shall not be done during windy weather or when the ground is excessively wet, frozen, or otherwise untillable.

6. Submittals: The Contractor shall submit certification that the seed mixture meets these specifications.

02930-2

1. Agricultural Limestone shall conform to the following:

a. Fineness (percent passing the No. 8 sieve) shall be no less than 80.0.

b. The total neutralizing value (calcium carbonate equivalent) shall be no less than 80.0.

c. The product of the two factors (fineness times calcium carbonate equivalent) shall be no less than 7200.

2. Fertilizer: Fertilizer shall be free flowing and suitable for application with approved equipment.

Bagged fertilizer shall bear the name, trademark, and warranty of the producer, and the contents and their proportions. A fertilizer in the proportions of 12-12- 12 shall be used for areas to be seeded.

3. Seed: Seed used for general seeding shall be Wisconsin

DOT seed mixture No. 60. The seed shall be furnished in the quantities required and shall be furnished full-tagged and delivered in properly designated packages or bags as directed. Seed shall conform to the following requirements:

a. Seed shall have a minimum purity of 98% and 85% germination.

b. Seed shall contain none of these noxious weeds:

Canada Thistle, Field Bindweed, Johnson Grass, Perennial Peppergrass, Perennial Sow Thistle, Quack Grass, or Wild Garlic.

d. Seed shall be purchased from sources of supply that have been sampled and tested in accordance with the methods and procedures prescribed by the current edition of Rules for Testing Seeds published by the

02930-3

Association of Official Seed Analysis and found to be satisfactory. This report is required before seed is sown. Such test report shall be no more than one year old at the time seed is used and then shall be subject to approval.

d. Mulch: Mulch for seeding may consist of straw, excelsior mulch, wood cellulose fiber mulch, or other material approved by the Engineer. All mulch shall be reasonable free from noxious weeds.

C. Excecution

1. Fertilizer and agricultural limestone: Fertilizer and agricultural limestone shall be spread uniformly and shall be mixed into the top 2 inches of soils with a disk harrow, rotary tiller or other approved equipment.

Fertilizer shall be applied at a rate of five hundred pounds per acre on all areas to be seeded.

2. Seed: Seed may be drilled in (not to be covered more than 1/2 inch) or mixed with water and the mixture sprayed over the area to be seeded. An approved mechanical method which will place the seed in direct contact with the soil may be used. In places inaccessible to mechanical equipment, or where the area to be seeded is small, a hand operated cyclone seeded or other approved equipment may be used.

a. Leguminous seeds, unless otherwise specified, shall be inoculated with a culture. The culture shall be mixed with sufficent water to distribute it thouroughly. The seed shall be wet thoroughly with the solution and allowed to dry sufficiently to be in condition for to be in condition for sowing.

Inoculated seed shall be sown within 30 hours after treatment. Where seeding is to be done by hydraulic methods, the inoculant may be added to the water in the spray tank.

02930-4

3. Mulch: Mulching material shall be applied to all seeded areas and shall be applied in a continuous blanket at the rate of 2 tons (air dry weight) per acre except, wood celulose fiber mulch shall be applied at the rate of 3/4 ton (air dry weight) per acre. The percent of moisture in the mulch shall not exceed 50%, except that in wood cellulose fiber mulch the moisture percent shall not exceed 15%. Only wood cellulose fiber will be used for mulch if the hydro-seeing method of application is used. Any of the other application methods may utilize any of the mulch materials in these specifications. The mulching material shall be maintained in place satisfactorily until final completion and acceptance of the contract.

b. Other suitable methods may be used if approved by the Project Engineer.

(END OF SECTION 02930)

DIVISION 3 SECTION 03210

CONCRETE REINFORCING STEEL

03210-1

1. All concrete reinforcing steel will be fabricated and placed in accordance with the "Manual of Standard Practice" by the Concrete Reinforcing Steel Institute (CRSI), 228 North LaSalle Street, Chicago, Illinois 60601. Fabrication and placement will also be in accordance with these specifications and as shown on the contract drawings.

2. Submittal: The Contractor shall furnish mill certificates and shop drawings for the reinforcing steel used. The mill certificate shall include all descriptive material information pertaining to the reinforcing steel. The shop drawings shall show all dimensions and connection details.

1. Reinforcing steel shall conform to the requirements of ASTM A-615, latest revision.

a. All bars No. 4 or larger shall be Grade 60.

b. All bars used on this project shall be epoxy coated in conformance with AASHTO M 284.

2. Bar chairs and other similar devices used to support reinforcing steel shall be items of standard manufacture, sized to support the reinforcement to the dimensions shown on the contract drawings and of adequate strength to resist displacement when placing concrete.

Reinforcing bars shall be set to proper elevation by the use of metal chairs. The use of wood blocks, mortar blocks or other materials is prohibited.

DIVISION 3 SECTION 03210

CONCRETE REINFORCING STEEL

03210-2

1. Store steel reinforcement in an orderly manner above ground on platforms, skids, or other supports. Where possible, store reinforcement steel above the extreme high water elevation.

2. All reinforcing steel shall be securely tied in place, supported and spaced so that it will not be displaced while placing concrete.

3. The dimensions as shown on the contract drawings, indicate the clear distance from the edge of the main reinforcement to the concrete surface. The concrete covering of stirrups, spacer bars and similar secondary reinforcements may be reduced by the diameter of such bars.

4. Lap requirements will be as shown on the contract drawings or as specified in the latest edition of ACI standard 318.

5. Bar placement tolerance shall be as follows:

a. Between bars: ¼-inch (plus or minus).

b. Vertical position of bars in slabs and walls:

1/2-inch (plus or minus).

6. Subject to the approval of the Engineer, reinforcement bars may be shifted or bent in the field where necessary to avoid openings, pipes, embedded items and other obstructions.

7. The Contractor will notify the designated Government

Inspector when the reinforcing is in place and prior to the placement of forms so that the reinforcing can be inspected.

(END OF SECTION 03210)

DIVISION 3 SECTION 03300

CONCRETE CAST-IN-PLACE CONCRETE

03300-1

1. All concrete work not specifically covered by these specifications shall conform to ACI Standard Building Code Requirements for Reinforced Concrete (ACI 318-77).

2. Testing. The Contractor shall:

a. Perform appropriate laboratory tests including compression tests of cylinders, air content and slump tests to substantiate mix designs. Two (2) copies of certified testing laboratory reports shall be furnished the Government as soon as possible after the test has been completed. One copy of the cylinder test results shall be sent directly to the Engineer from the testing laboratory and one copy to the Government Inspector. The tests will clearly indicate the mix proportions used, test results, and certify compliance with these specifications.

b. The Contractor shall take the following minimum number of tests to assure compliance with contract requirements:

Test Material Frequency

Air Content

(ASTM C-2311)

Concrete One for each day's pour or as directed by the Engineer.

Slump

(ASTM C-143)

Concrete One per truck for each day's pour, or as directed by the Engineer.

Strength*

(ASTM C-31,

make & cure;

ASTM C-39,

test cylinders)

Concrete One cylinder per truck and at least one (1) set of three (3) for each day's pour.

03300-2

* Test one (1) cylinder at 7 days and two (2) cylinders at 28 days.

3. Submittals: The proportions of all components of the concrete mix shall be by weight and shall be submitted for approval prior to placement of any concrete. The approved mix design and supplier shall not be changed throughout concrete placement unless a new mix design and supplier are approved.

1. Cement shall be Portland Cement, Type I, IA, III, or IIIA conforming to the requirements of ASTM C-150.

2. Water shall be clean and free from deleterious amounts of acids, oil, alkalis, and organic materials, and conform to ASTM C-109.

3. All aggregates shall conform to the requirements of ASTM

C-33. The aggregate particles shall be clean, hard, unweathered, and uncoated.

a. Fine aggregate shall be natural sand conforming to the requirements of ASTM C-33.

b. Coarse aggregates shall be crushed stone or washed gravel conforming to the grading requirements of ASTM C-33, size No. 67, 3/4 to No. 4.

4. The concrete mix design shall conform to the following criteria:

a. Water/Cement Ratio - 0.43 (max).

b. Compressive Strength - 4500 psi @ 28 days (min).

c. Air Content - 5 to 8%.

d. Air Entraining Admixture - ASTM C-260.

e. Slump - 2 to 4 inches.

5. Admixtures

03300-3

a. Air entraining admixture shall be added if Type I or

III cement is used and shall conform to ASTM C-260.

An air-entraining admixture which has been in storage for longer than 6 months or which has been subject to freezing shall not be used.

b. Fly ash, if used, shall be Class C or Class F, conforming to ASTM 618, latest revision. Fly ash will be limited to no more than 15%, by weight, of the total cementitious material.

c. No other admixtures shall be used unless approved in writing by the Engineer. Calcium chloride will not be acceptable under any conditions.

6. Curing compound shall be a resin base liquid concrete curing compound, ASTM C-309, Type 1, with fugitive dye to provide uniformity of application and 95% or more re-tention of mixing water for seven (7) days or more.

Compound must be compatible with all applied finishes designated for use.

7. Polyethylene film for curing concrete shall be non-staining, white in color, minimum 0.004 of an inch in thickness and shall conform to the requirements of ASTM C-171.

1. General: Unless otherwise specified herein, concrete materials, mixing, and placing shall conform to require-ments of ACI 304, "Recommended Practice for Measuring, Mixing and Placing Concrete".

2. Concrete Mix:

a. The concrete mix design shall conform to the "Recom-mended Practice for Selecting Proportions for Con-crete (ACI 211.1)" by the American Concrete Institute.

b. The Contractor may use, at his own option, ready-mix concrete provided the concrete mix meets the above requirements and the requirements of ASTM C-94. The

03300-4

Engineer shall have access to the batch plant during all batching operations.

3. Anchor Bolts and Expansion Bolts:

a. The Contractor will set all anchor bolts precisely with templates and maintain bolt positions during concreting operations. Anchor bolts and expansion bolts shall be standard manufactured items intended for the use shown. Bolts, nuts, washers and appurtenant items shall be galvanized unless other-wise noted. Bolts shall be furnished with cut washers.

4. Pipe Sleeves and Embedded Items:

a. Before placing any concrete, the Contractor will determine that all embedded metal pipe sleeves, anchors, anchor slots, anchor bolts, wedge inserts, concrete inserts and similar items are firmly secured and fastened in place.

5. Expansion joints and control joints

a. Expansion joints and control joints shall be as shown on the contract drawings. Control joints shall be saw-cut or tooled to a depth of 1/4 the slab the slab thickness and caulked. Expansion joints shall be as detailed on the drawings.

6. Placing Concrete

a. The Contractor will deliver with each load of "ready mixed concrete" to be incorporated in the work, an inspection or delivery ticket giving the class of concrete or proportions of the mix, time of departure and any other pertinent data. Only loads which arrive in a satisfactory condition and which carry an inspection of delivery ticket will be incorporated into the work.

b. The Contractor will deliver and place concrete in the work within one (1) hour subsequent to the charging

03300-5 into the mixing drum, regardless of whether such mixing drum is part of a central plant or a transit mixer. This time shall be appropriately decreased when air temperatures are unusually high or the ingredients are such that an unusually quick time of set or loss of plasticity will occur, or during cold weather when loss of heat occurs to such an extent that the concrete will not be of the proper tempera-ture when placed in the forms.

c. Retempering of partially hardened concrete will not be permitted.

d. Addition of water to ready-mixed concrete at the site will be allowed only with approval of the Engineer and only if the maximum water-cement ratio and the maximum slump are not exceeded.

e. The Contractor will convey concrete from mixer to forms as rapidly as practicable and by methods which will prevent segregation or loss of ingredients, will deposit the concrete as nearly as practicable in its final position, and will use chutes such that the concrete slides in the chute and does not flow.

Where a vertical drop greater than 5 feet is neces-sary, the Contractor will place the concrete through an elephant trunk or similar device to prevent segregation.

f. The Contractor will place concrete before the initial set has occurred, and in no event after it has contained its water content for more than one (1) hour. The concrete will be placed on clean, damp surfaces, free from water, or upon properly consol-idated fills, but never upon soft mud, dry porous earth, or frozen ground.

g. The Contractor will deposit continuously and as rapidly as practicable until the unit of operation is completed.

h. The Contractor will consolidate all concrete by vibration so that the concrete is thoroughly worked around the reinforcement, around embedded items, and

03300-6 into corners of forms, eliminating all air or stone pockets which may cause honeycombing, pitting, or planes of weakness. Mechanical vibrators with a minimum frequency of 7000 revolutions per minute, operated by competent workmen will be used.

i. In joining fresh concrete to concrete that has already set, the Contractor will remove all loose and foreign materials from set concrete, scrub with wire brooms and thoroughly clean the set concrete, and will moisten existing surfaces when the new concrete is placed.

j. Concrete in vertical members shall have been in place at least four (4) hours before concrete in horizon-tal, or vertical members resting thereon, is placed.

7. Weather Conditions:

a. Protection - The Contractor will:

(1) Provide adequate protection against rain, sleet and snow before and during placement and finish-ing of concrete.

(2) Provide adequate protective measures to maintain the temperature of the concrete as specified.

(3) Keep a thermometer on the job site at all times to record temperature.

b. Cold Weather Concreting - The Contractor will:

(1) Not place concrete when the atmospheric tempera-ture is below 40°F or when the concrete is likely to be subjected to freezing temperatures within 24 hours after it has been deposited unless adequate temporary heating is provided. In no case shall concrete be exposed to freezing temperature for 72 hours after placing.

(2) Maintain concrete temperature not less than 50°F nor more than 80°F for the first three (3) days

03300-7 after placing, and protect from freezing for the next five (5) days.

(3) Use no frozen materials or materials containing ice in concrete.

(4) Use no salt or other chemicals to prevent freezing.

(5) Perform all cold weather concreting in accor-dance with ACI 306, "Recommended Practice for Cold Weather Concreting".

c. Hot Weather Protection - The Contractor will:

(1) Not place concrete when the atmospheric tempera-ture is above 90°.

(2) Maintain concrete temperature not less than 50°F nor more than 90°F for the first three (3) days after placing, and protect from temperatures over 90°F for the next five (5) days.

(3) Thoroughly wet dry porous surfaces immediately prior to concreting.

(4) Perform all hot weather concreting in accordance with ACI 305, "Recommended Practice for Hot Weather Concreting".

8. Repairing and Patching - The Contractor will:

a. Remove and replace at no additional cost, any con-crete not formed as shown on plans, concrete out of alignment, surfaces beyond required tolerances, or defective surfaces which cannot be properly repaired or patched, including any concrete failing to meet the strength requirements.

b. Clean, dampen, and fill all bolt and tie holes and other similar defects, with patching concrete immedi-ately after removing forms.

03300-8

c. Remove to sound concrete all bulges, projections, honeycomb and all other defects in exposed concrete, and patch. Thickness of patch: 1-inch, minimum.

Cut the perimeter edges of all areas to receive patching mix perpendicular to the surface or under-cut. Feather-edge patches will not be allowed. Do all patching before concrete is thoroughly dry.

9. Curing - The Contractor will:

a. Protect concrete from premature drying. Provide temporary housing, covering, or other protection used in curing and keep in place and intact a minimum of 24 hours after artificial heating or cooling has been discontinued. Institute curing measures within two

(2) hours of finishing operations.

b. Keep concrete continuously moist for seven (7) days, and prevent rapid drying at the end of the curing period. Curing may be accomplished by one of the following methods.

(1) Use curing compounds conforming to ASTM

Specification C 309-5B, Type I. Do not use compounds on any surface which will receive additional concrete.

(2) Use non-staining polyethylene film and keep all joints weighted to prevent wind penetration.

10. Finishing:

a. A rubbed finish shall be given to all exposed walls above finish ground line. Fins and other projections shall be carefully removed and damaged places re-paired. After all required patching, cleaning, and correction of major imperfections have been completed, the concrete surface shall be rubbed with cement or carborundum bricks and water, leaving the surface uniformly smooth and clean.

b. Slabs - The Contractor will slope all concrete slabs in a manner to prevent the collection of water.

03300-9

1. Slabs and horizontal surfaces shall have a steel trowel finish unless specifically otherwise specified or directed by the Engineer.

2. All high areas shall be refloated to a uniform, smooth granular texture.

3. The finish surface shall be free of any trowel marks, uniform in texture and appearance. Floor surfaces not sloped as shown on the drawings shall be planed to a tolerance not to exceed 1/8-inch in 10 feet in any direction. Any surface defects of sufficient magnitude shall be removed by grinding.

c. Spreading dry cement for finishing will not be permitted.

11. Backfilling:

a. Walls shall not be backfilled for a minimum of ten

(10) days after placement, or until the concrete has reached 70% of its 28-day compressive strength as determined by cylinder break tests.

(END OF SECTION 03300)

DIVISION 5 SECTION 05120

METALS MISCELLANEOUS METALS

05120-1

1. Work in this section includes the installation of all screen slots, channels, and…