89503220QWA000224

x x

1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted ; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGEMENT TO BE

RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR

OFFER. If by virtue of this amendment you desire to change an offer already submitted , such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

x

LOVELAND CO 80539-8986

RMR

5555 E. CROSSROADS BLVD

ROCKY MOUNTAIN REGIONAL OFFICE

US DOE/WESTERN AREA POWER

WAPA (RMR)

04/23/20200001

13. THIS ITEM ONLY APPLIES TO MODIFICATION OF CONTRACTS/ORDERS. IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

12. ACCOUNTING AND APPROPRIATION DATA (If required) is not extended.is extended, Items 8 and 15, and returning

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended , by one of the following methods: (a) By completing

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

FACILITY CODE CODE

10B. DATED (SEE ITEM 13)

10A. MODIFICATION OF CONTRACT/ORDER NO.

9B. DATED (SEE ITEM 11)

9A. AMENDMENT OF SOLICITATION NO.

CODE

8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code)

7. ADMINISTERED BY (If other than Item 6)CODE 6. ISSUED BY

PAGE OF PAGES

4. REQUISITION/PURCHASE REQ. NO.3. EFFECTIVE DATE2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO. (If applicable)

1. CONTRACT ID CODE

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

04/23/2020

CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority) appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

E. IMPORTANT: Contractor is not is required to sign this document and return __________________ copies to the issuing office.

ORDER NO. IN ITEM 10A.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

The purpose of this amendment is to answer vendor questions. The following action is taken:

1. The due date for submission of quotes is hereby extended from April 30, 2020 at 2:00 pm

MT to May 6, 2020 at 2:00 pm MT.

2. Vendor Questions and answers:

Q. What is the Finish Requirement for the Generator Stand? Should it be painted or galvanized?

A. Painted or powdercoat black

Continued ...

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)15A. NAME AND TITLE OF SIGNER (Type or print)

15C. DATE SIGNED 16B. UNITED STATES OF AMERICA 15B. CONTRACTOR/OFFEROR 16C. DATE SIGNED

(Signature of person authorized to sign) (Signature of Contracting Officer)

Eileen R. Ray

STANDARD FORM 30 (REV. 11/2016)

Prescribed by GSA FAR (48 CFR) 53.243

Previous edition unusable

Except as provided herein, all terms and conditions of the document referenced in Item 9 A or 10A, as heretofore changed, remains unchanged and in full force and effect .

04/23/2020 Signature on File

ITEM NO. SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT

NAME OF OFFEROR OR CONTRACTOR

2 3

CONTINUATION SHEET

REFERENCE NO. OF DOCUMENT BEING CONTINUED PAGE OF

(A) (B) (C) (D) (E) (F)

89503220QWA000224/0001

Q. Can the Contracting Officer clarify what is required for a "varmint shield". Assume it relates as noted to the flat plate support platform for the Generator and Load Bank, but is there also a requirement for screening around the base of the Generator Stand to keep small animals or birds from nesting under the generator.

A. A 3/16” plate between the generator base and the stand

Q. It was noted the Vendor can pre-drill holes for the Generator Standing Mounting, but no other holes. We assume this refers to the stand mounting holes to anchor the stand to the GFE concrete foundation. It would be better for the installation crew to have pre-drilled anchor bolt holes in the stand leg mounting plates. We can provide an anchor bolt template and dimensions, which would allow an exact placement of the anchor bolts in the concrete, and eliminate the need to field drill holes. Please advise if pre-drilled anchor bolt holes are acceptable for ease of installation.

A. No holes are required, and we prefer to drill all holes on site to avoid any possible variations in the bolt position placement by the concrete contractor.

A. We have not found a factory designed stand that meets the Solicitation requirements. We propose to have our Structural Engineering Firm, ECS Engineers, located in Casper, Wyoming provide an engineered design and Shop Drawings, submitted for review and approval prior to fabrication.

Please advise if this is an acceptable alternative to a factory designed and fabricated generator stand.

A. The previous installations were provided by the factory, and because of wind load, snow load, and seismic rating, the proposed alternative is not acceptable. Warranty of the genset will be dependent on the stand rating for this site.

(see coordinates in spec).

Q. In email conversation with one of our generator suppliers (Kohler), it seems that the

Continued ...

NSN 7540-01-152-8067 OPTIONAL FORM 336 (4-86)

Sponsored by GSA

FAR (48 CFR) 53.110

ITEM NO. SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT

NAME OF OFFEROR OR CONTRACTOR

3 3

CONTINUATION SHEET

REFERENCE NO. OF DOCUMENT BEING CONTINUED PAGE OF

(A) (B) (C) (D) (E) (F)

89503220QWA000224/0001

written specification for your solicitation

89503220QWA000224, Generator Replacement, Casper, WY does not make sense to them. The specified

Cummins seems to be a residential model, and in order to meet the altitude requirements, they will have to go an industrial generator. Also, our supplier has said a load bank does not come with residential generators. Please clarify the requirements.

A. This is a brand name or equal, Cummins C20N6 with a built in load bank, (see 1.A.1. in specification). The requirement for this site has been technically researched and the determination made that the brand or equal will be sufficient for the size and reliability as well as the requirement for a load bank with a microprocessor to avoid wet-stacking the genset.