This is a fabricated pre-engineered precast concrete structure specification for a 12' x 20' precast concrete building prepared for the Department of Assets & Infrastructure in Pennsylvania. The specification document outlines the requirements for a pre-fabricated shelter to be installed at the Coroner's Office located within the Public Safety Training Campus in Eagleville, PA. The building will serve as a mausoleum for unclaimed cremains and will feature faux brick exterior finish to match the main building's architectural style. The structure is to be supplied by an EASI-SET brand manufacturer or approved equivalent and delivered to a prepared concrete foundation with a short concrete sidewalk connecting it to the parking area. Pre-bid information will be posted through the Bonfire/Euna portal, and all submissions and questions must be submitted through this same online system.

The specification requires the precast concrete building producer to be a plant-certified member of the National Precast Concrete Association (NPCA), The Precast/Prestressed Concrete Institute (PCI), or equivalent organization. The building design must comply with ACI-318-11, ASCE/SEI 7-10, IBC 2012, and other referenced standards, with design loads specified for either Case 1 (Typical) or Case 2 (Heavy) conditions. Materials must include 5000 PSI minimum 28-day compressive strength steel-reinforced concrete, ASTM A615 grade 60 reinforcing steel, and post-tensioned roof and floor panels using a proprietary second-generation design. The building will be equipped with double 3'-0" x 6'-8" insulated metal doors with comprehensive hardware specifications, including stainless steel hinges, deadbolts, and handles meeting ANSI standards. The exterior finish shall feature an architectural precast concrete brick pattern imprinted in the form, finished with water-based acrylic stain in brick red color, and all exterior joints must be sealed with DOW CORNING 790 silicone sealant to ensure a watertight design.

View the file

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FABRICATED PRE-ENGINEERED PRECAST CONCRETE STRUCTURE SPECIFICATION

12’ x 20’ PRECAST CONCRETE BUILDING

PRE-ASSEMBLED

SECTION 1 – GENERAL

1.1 WORK INCLUDED

Contractor shall furnish a precast concrete transportable building to be delivered and placed on foundation in accordance with manufacturer’s recommendations. Precast building to be EASI-SET® brand as manufactured by a licensed producer of Easi-Set Buildings, or approved equal. Building shall be provided by manufacturer with all necessary openings as specified by contractor in conformance with manufacturer’s structural requirements.

1.2 REFERENCES

A. ACI-318-11: Building Code Requirements for Structural Concrete and Commentary

B. ASCE/SEI 7-10: Minimum Design Loads for Buildings and Other Structures

C. IBC 2012: International Building Code

D. PCI Design Handbook, 7th Edition

E. Concrete Reinforcing Institute, Manual of Standard Practice

F. UL-752 (Test Method level 5) for bullet resistance certified by a military approved laboratory.

1.3 SYSTEM DESCRIPTION

DESIGN REQUIREMENTS

A. Building Dimensions: As shown on drawings

Design case to be selected to correspond to the design criteria indicated in the aforementioned codes for the geographical location of the project or as specified.

CASE 1: Typical

B. Design Loads:

1. Seismic Design Category ‘C’, Risk Design Category II

2. Roof Live Load (Snow) – 30 PSF

3. Floor Live Load – 150 PSF

4. Wind Loading* – 115 MPH

*Design loads relate to precast components only, not accessories (i.e. doors, windows, vents, etc.)

CASE 2: Heavy

C. Design Loads:

1. Seismic Design Category ‘D’, Risk Design Category III

2. Roof Live Load (Snow) – 60 PSF

3. Floor Live Load – 250 PSF

4. Wind Loading* – 165 MPH *Design loads relate to precast components only, not accessories (i.e. doors, windows, vents, etc.)

D. Roof: Roof panel shall have a peak in the center of 12-foot direction and shall slope ½” to each side. The roof shall extend a minimum of 2 ½” beyond the wall panel on each side and have a turndown design which extends ½” below the top edge of the wall panels to prevent water migration into the building along top of wall panels. Roof shall also have an integral architectural ribbed edge.

E. Roof, floor, and wall panels must each be produced as single component monolithic panels. No roof, floor, or vertical wall joints will be allowed, except at corners and along perimeter. Wall panels shall be set on top of floor panel.

F. Floor panel must have ½” step-down around the entire perimeter to prevent water migration into the building along the bottom of wall panels.

1.4 SUBMITTALS

A. Engineering calculations that are designed and sealed by a professional engineer, licensed to practice in the state where the project is located, shall be submitted for approval.

B. Manufacturers’ product literature shall be provided for any plumbing, electrical, and miscellaneous installed fixtures demonstrating compliance with these specifications.

1.5 QUALITY ASSURANCE

A. The precast concrete building producer shall be a plant-certified member of either the National Precast Concrete Association (NPCA), The Precast/Prestressed Concrete Institute (PCI), or equal.

B. No alternate building designs to the building will be allowed unless pre-approved by the owner.

SECTION 2 – PRODUCTS

2.1 MATERIALS

A. Concrete: Steel-reinforced, 5000 PSI minimum 28-day compressive strength, air-entrained (ASTM C260).

B. Reinforcing Steel: ASTM A615, grade 60 unless otherwise specified.

Welded Wire Fabric: ASTM 185, Grade 65

C. Post-tensioning Strand: 41K Polystrand CP50, ½” 270 KSI Seven-Wire strand, enclosed within a greased plastic sheath (ASTM A416). Roof and floor each shall be post-tensioned by a proprietary, second generation design using a single, continuous tendon.

Said tendon is placed in the concrete slab to form a perimeter loop starting from one corner of the slab to a point where the cable entered the slab. The tendon then turns 90 degrees and follows the cable member(s) in the periphery to a point midway along the “X” axis of the concrete building panel and then turns 90 degrees along the “Y” axis of the concrete building panel. This bisects the concrete building panel and crosses the opposite parallel portion of the cable member and exits from an adjacent side of the concrete building panel. This creates a cable pattern with no less than 2.5 parallel cables in any direction. To ensure a watertight design, no alternate methods shall be substituted for the post-tensioning.

D. Sealant: All joints between panels shall be caulked on the exterior and interior surface of the joints. Caulking shall be DOW CORNING 790 silicone sealant or equal. Exterior caulk reveal to be 3/8”x 3/4” deep so that sides of the joint are parallel for proper caulk adhesion. Back of the joint to be taped with bond breaking tape to ensure adhesion of caulk to parallel sides of joint and not the back.

E. Vents: Two screened aluminum vents to be cast in rear wall. Vents shall be SUNVENT

INDUSTRIES Model FL-164 or equal.

F. Panel Connections: All panels shall be securely fastened together with 3/8” thick steel brackets. Steel is to be of structural quality, hot-rolled carbon complying with ASTM A36 and hot dipped galvanized after fabrication. All fasteners to be ½” diameter bolts complying with ASTM A325 for carbon steel bolts. Cast-in anchors used for panel connections to be Dayton-Superior F-63 coil inserts, or equal. All inserts for corner connections must be secured directly to form before casting panels. No floating-in of connection inserts shall be allowed.

2.2 ACCESSORIES

A. Doors and Frames: Shall comply with Steel Door Institute “Recommended Specifications for Standard Steel Doors and Frames” (SDI-100) and as herein specified. All door and frame galvanizing shall be in accordance with ASTM A924 and A653, A60 minimum coating thickness.

1. The buildings shall be equipped with double 3’-0” x 6’-8” x 1-3/4” thick insulated, 18 gauge, metal doors with 16-gauge frames (to meet wall thickness). Doors to have flush top cap. 12 gauge flat astragals shall be applied to the active leaf to protect against the elements or forced opening. Doors and frames shall be factory bonderized and painted with one coat of rust inhibitive primer and one finish coat of enamel paint; color to be BOLT BROWN unless specified otherwise.

2. Doors and frames shall meet SDI standard Level 2, 1¾” heavy duty.

Manufacturers: Republic, Steelcraft, Ceco, Black Mountain, Pioneer, Curries, Mesker, MPI, Door components or equal

B. Door Hardware:

1. Pull Handle: Shall meet requirements of ANSI A156.2. Shall be thru bolt attached and constructed of a minimum ¾” diameter stainless pull handle sized 8” center to center with a stainless backer plate, minimum 0.053” on both sides.

Approved manufacturers: Design Hardware, Don-Jo, or equal

2. Hinges: Shall comply with ANSI A156.1 and be of the ball bearing, non-removable pin type (3 per door minimum). Hinges shall be 4 ½” x 4 ½” US26D (652) brushed chrome finish. Manufacturer shall provide a lifetime limited warranty.

Approved manufacturers: Design Hardware, or equal

3. Deadbolt: Commercial Grade Deadbolt conforming to ANSI 156.5 furnished with a 2 ¼” face plate and a 1” projecting deadbolt with hardened steel pins. Dead bolts shall be UL and ADA approved. Finish shall be US26D (626) brushed chrome finish. Manufacturer shall provide a lifetime limited warranty.

Approved manufacturers: Design Hardware, Dorma, or equal

4. Surface Bolt: 8” Surface bolt UL listed. Finish US26D (626) brushed chrome finish. (2 per inactive leaf) Approved manufacturers: Don-Jo, Design Hardware, or equal

6. Threshold: Bumper Seal type threshold with a maximum 1” rise to prevent water intrusion. Thresholds shall be approved for UL 10B suitable for use with fire doors rated up to three hours.

Approved manufacturers: National Guard Products or equal

7. Overhead Door Holder: Heavy duty surface mounted hold open device with hold open/stop angle of 85 to 110 degrees. Construction shall be stainless steel. Finish US32D

(630) satin stainless steel finish.

Approved manufacturers: ABH, Rockwood, or equal

8. Drip Cap: Aluminum drip cap with minimum projection of 2 ½” shall be furnished.

Approved Manufacturers: Design Hardware, National Guard Products, or equal

9. Door Stop: ANSI 156.16 approved wall mounted door stop with keeper constructed of a corrosion resistant cast brass material. Finish US26D (626) brushed chrome finish.

Approved manufacturers: Don-Jo, Rockwood, or equal

2.3 FINISHES

A. Interior of Building: Smooth form finish on all interior panel surfaces unless exterior finish is produced using a form liner, then smooth hand-troweled finish.

B. Exterior of Building: (Standard) Architectural precast concrete brick finish: Finish must be imprinted in top face of panel while in form using an open grid impression tool similar to EASI-BRICK®, or equal. Finished brick size shall be 2 3/8” x 7 5/8” with vertical steel float or light broom finish. Joints between each brick must be 3/8” wide x 3/8” deep. Back of joint shall be concave to simulate a hand-tooled joint. Each brick face shall be coated with the following water-based acrylic, water repellent penetrating concrete stain: 1) Canyon Tone stain by United Coatings, 2) Sherwin Williams (H&C concrete stain) or equal. Stain shall be applied per manufacturer’s recommendation. Joints shall be kept substantially free of stain to maintain a gray concrete color. Stain color shall be BRICK RED unless specified otherwise.

SECTION 3 – EXECUTION

3.1 SITE PREPARATION (MANUFACTURER’S RECOMMENDATION)

Work under this section relates to placement of the building on the prepared foundation and site.

A. Building shall bear fully on a crushed stone base per the foundation design.

B. The crushed stone base shall be kept within the confines of the soil or perimeter form. Do not allow the base to become unconfined so that it may wash, erode, or otherwise be undermined.

C. Provide positive drainage for the fill, pad or slab as required.

Pre-Bid Meeting A. Pre Bid information will be posted at a later date thru Bonifre/Euna site messaging via

Public notice for this solicitation.

Submissions and Communication

A. All submissions must be submitted thru Bonfire/Euna portal for this solicitation.

B. All questions must be submitted thru the Bonfire/Euna portal for this solicitation utilizing the public Q&A portion of the messaging system.

Coroner Maus Shelter Spec _SOW
C. IBC 2012: International Building Code
D. PCI Design Handbook, 7th Edition
A. The precast concrete building producer shall be a plant-certified member of either the National Precast Concrete Association (NPCA), The Precast/Prestressed Concrete Institute (PCI), or equal.

2026-03-13 Coroner Mausoleum Grading Permit Plans-Issued for Bid