80KSC021R0029 J-I Pad 39B Outrigger Guidelines.pdf
PDF 278 KB Posted
- Attached to
- Mobile Launcher 1 (ML-1) Emergency Egress System (EES) Conveyance Federal contract opportunity
- Solicitation number
- 80KSC021R0029
About this file
This file provides guidelines and drawings for outrigger pads to support a mobile launcher at Kennedy Space Center. It also describes a federal contract opportunity for installation of an emergency egress conveyance system on Mobile Launcher 1.
The opportunity solicitation is for implementation of all tasks to install a new conveyance system, including structural modifications, fabrication and installation of platforms, modification to existing structures, basket assemblies, a PLC-based safety control system, braking system, wire ropes, hoisting and control systems. The scope also includes testing, verification and validation of the new and modified installations. The solicitation number is 80KSC021R0029 and is issued by the National Aeronautics and Space Administration Kennedy Space Center for installation on Mobile Launcher 1. Requests for controlled documents require verification of vendor certification by the Defense Logistics Agency Joint Certification Program.
View the file
Other files for this federal contract opportunity
Show all 17
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P.T.C.R. BUILDING
SUBSTRUCTURE INFLUENCE ZONE
(RED)
CRAWLER WAY - CATACOMBS
STRUCTURE (BLUE)
APRON SLAB (GREEN)
GENERAL NOTES:
1. ALL PADS SHALL HAVE ADEQUATE STIFFNESS TO DISTRIBUTE OUTRIGGER LOADS UNIFORMLY
ACROSS THE ENTIRE PAD AREA
2. PADS SHALL SIT FLAT ON CONCRETE SURFACE, STACK DISTRIBUTION PADS OVER COMPLIANT
MATERIAL SUCH AS PLYWOOD OR HARD RUBBER PAD TO ACCOMODATE SURFACE UNEVENNESS
3. MAINTIAN A MINIMUM 5'-0" CLEAR AREA AROUND OUTRIGGER PADS, UON
4. NO RESTRICTION ON OUTRIGGER LOADS <30 KIP, MINIMUM 2'X2' CRANE FEET AND 8'-0" c.c. SPACING
(USE OF MINIMUM DISTRIBUTION PAD RECOMMENDED)
5. GRATING SURFACES HAVE NOT BEEN EVALUATED, AVOID OUTRIGGER LOADING
6. FOR STEEL PADS, CONSIDER PLACING PLYWOOD SHEET BETWEEN FLOAT AND PLATE TO REDUCE
POTENTIAL FOR SLIDING
7. FOR OPERATIONS EXCEEDING THESE GENERAL GUIDELINES, SUBMIT DESIRED OPERATION TO
TOSC ANALYSIS FOR CASE-BY-CASE REVIEW
MAX OUTRIGGER REACTION
260 KIP
200 KIP
160 KIP
130 KIP
100 KIP
75 KIP
50 KIP
MIN DISTRIBUTION AREA
10'X10'
8'X8' 7'X7' 6'X6' 5'X5' 4'X4' 3'X3'
MAX OUTRIGGER REACTION
260 KIP
140 KIP
75 KIP
MIN DISTRIBUTION AREA
4'X4' 3'X3' 2'X2'
MAX OUTRIGGER REACTION
80 KIP
70 KIP
50 KIP
MIN DISTRIBUTION AREA
6'X6' 4'X4' 3'X3'
H.P.G. STORAGE BATTERY AREA
SUBSTRUCTURE INFLUENCE ZONE
(RED)
12'-0"
'-0
'-0
12'-0"
12'-0"
'-0
'-0
CRANE OUTRIGGER GUIDLINES PAD B SURFACE
7/18/2019 FOR PRELIMINARY USE
8/9/2019 INITIAL RELEASE
MAINTAIN A MINIMUM 12'-0" CLEAR AREA
AROND OUTRIGGER PADS IN
SUBSTRUCTURE INFLUENCE ZONES