This document is a Q&A related to solicitation 70Z08124QELIZ0014 for the Base Elizabeth City Fire Alarm Panel Replacement project. The solicitation requires the contractor to replace the existing Notifier NFS-320 Fire Alarm Control Panels for Hangars HMF-1 and HMF-2 with new Notifier NFS-320 Control Panels, including installing new batteries and re-routing the 120VAC wiring. The contractor must conduct programming, pre-testing of all devices, and final testing with the USCG Inspector, with all work covered under a one-year warranty. The solicitation is a 100% small business set-aside using NAICS code 561621, with a site visit requirement and a bid submission deadline of NOON Eastern Time on August 15, 2024. Questions must be submitted in writing by NOON on August 12, 2024. The Q&A document addresses specific details such as the need to test all devices, the presence of foam releasing panels, and the potential need for a lift during troubleshooting.

View the file

Other files

File Type Posted
HMF 1 AND HMF 2 Building Fire Alarm SOW.docx DOCX document
DOL Eciyt.pdf PDF
SF-1449 Clauses and Provisions .docx DOCX document
70Z08124QELIZ0014- 1442.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Q and A for contract RFQ# 70Z08124QELIZ0014 - Base Elizabeth City Fire Alarm Panel Replacement

1. Would all devices need to be tested (including the foam releasing panels)? Yes, per NFPA standards because all the devices report to the Main Fire Alarm Panel. This function needs to be tested.

2. Are both HMF Hangers have releasing control panels connected to Flame Detectors? Yes

3. Will a lift be needed? Possible, for trouble shooting.