DEPARTMENT OF HOMELAND SECURITY

UNITED STATES COAST GUARD

BASE MIAMI BEACH

SPECIFICATIONS

To

Stationary Generator

General: United States Coast Guard Base Miami Beach is accepting proposals for qualified individuals or firms to provide a 100kW stationary tier 3 generator with aluminum enclosure and double walled aluminum fuel tank.

Location:

Coast Guard Base Miami Beach 100 MacArthur Causeway Miami Beach, FL 33139

III. Coast Guard Contracting Officers Representative: The Contractor shall contact the COR to coordinate all construction efforts onboard Coast Guard Facilities.

LT Steven Becker
Steven.A.Becker@uscg.mil
786-447-7394
CWO Jose A. Calderon
Jose.A.Calderon@uscg.mil
305-535-4547

Specifications: Contractor shall provide a replacement generator that meets the the following specifications:

1. Provide a 100kW stationary Tier 3 compliant diesel generator.

2. Diesel engine shall be liquid cooled and 4 cycle.

3. Generator shall have an aluminum sound attenuated enclosure compliant with UL220 and powder coated.

4. Generator shall have sub base fuel tank that is double walled aluminum or stainless steel and a capacity of at least 150gallons and with leak detection and fuel level gauges.

5. Aluminum sub base configured with forklift pockets.

6. Entire exterior shall be powder coated.

7. Generator shall be configured with selector switch and capability to provide 120/240v, 120/208v, and 277/480v.

8. Generator shall have 400AMP rated CAM docking station with disconnect protection and 120/240v, 120/208v, and 277/480v female connectors with covers.

9. Generator shall have set of covered single phase receptacles: 4 x 20 Amp duplex receptacles and 2 x 50 Amp 250v receptacles. All to be breaker protected.

10. Generator shall have automatic shutdown for: low oil pressure, high coolant temperature, and over crank.

11. Generator shall have an emergency stop button.

12. Generator shall include starting batteries with installed battery charger and 20A 120v receptacle for charger.

13. Coolant system shall have shutoff valves for maintenance.

14. Coolant shall be corrosion resistant.

15. Radiator shall include an overflow bottle.

16. Generator shall be full load factory tested.

17. Generator shall be start up and building load tested.

18. Warranty Period: Generator shall come with a minimum 2 year / 1,500 hour warranty.

19. All work must be approved by the Contracting Officer’s Representative.

Questions and Answers:

Q. First is the multi-voltage selector, usually this is found on mobile units. The only way for us to accomplish this is the purchase of a mobile unit and mount it securely at the location.

-Coast Guard is requesting a generator with an aluminum sound attenuated enclosure (see: SOW, section VIII part 3) with an aluminum sub base with forklift pockets allowing us to move it from its stationary location for any emergency event (see: SOW, section VIII part 5).

Second is the fuel tank. I don’t know of anyone that offers stainless or aluminum tanks on there system. We have the double walled, and have always lasted the life of the generator. In our quote, we will have to quote with exception.

-Due to the salt air environment on the island, Coast Guard is requesting a sub base fuel tank that is double walled aluminum or stainless steel and a capacity of at least 150 gallons and with leak detection and fuel level gauges (see: SOW, section VIII part 4).

Third is a question about connectivity. Is this generator going to supply l back-up power to a building and optional plugs. It appears that you might want to just power a panel with outlets for different cords to be connected at option.

This generator will be suppling back up power to a building. Coast Guard is requesting 400AMP rated CAM docking station with disconnect protection with female connector with covers to tie into the emergency panel (see: SOW, section VIII part 8). We are also looking for the option with duplex receptacles. (see: SOW, section VIII, part 9)

If it is to do both a building and the optional voltages to a panel with voltage selection, then a 2 way through switch would be needed to ensure the building always received the correct voltage.

image1.jpeg