Automatic Transfer Switch 1200 A

AUTOMATIC TRANSFER SWITCH

PART 1 GENERAL

1.1 SUMMARY

A This section includes the following items from a single supplier:

1. Automatic transfer switch

2. Related Accessories as specified

B Products Furnished or Supplied but not installed

C Products Installed but not furnished or supplied

D Related Requirements

1. It is the intent of this specification to secure an automatic transfer switch that has been prototype tested, factory built, production-tested, and site-tested together with all accessories necessary for a complete installation as shown on the plans and drawings and specified herein.

2. Any exceptions to the published specifications shall be subject to the approval of the engineer and submitted minimum 10 days prior to the closing of the bid with a line by line summary description of all the items of compliance, any items that have been are omitted or have been taken exception to, and a complete description of all deviations.

3. It is the intent of this specification to secure an automatic transfer switch that has been tested during design verification, in production, and at the final job site. The automatic transfer switch will be a commercial design and will be complete with all of the necessary accessories for complete installation as shown on the plans, drawings, and specifications herein. The equipment supplied shall meet the requirements of the National Electrical Code and applicable local codes and regulations.

4. All equipment shall be new and of current production by an international, power system manufacturer of generators, transfer switches, and paralleling switchgear. The manufacturer shall be a supplier of a complete and coordinated system. There will be single-source responsibility for warranty, parts, and service through a factory-authorized representative with factory-trained technicians.

1.2 PRICE AND PAYMENT PROCEDURES

A Allowances

B Unit Prices

C Alternates or Alternatives

D Measurement and Payment

1.3 REFERENCES

A Abbreviations and Acronyms

B Definitions

C Reference Standards

1.4 ADMINISTRATIVE REQUIREMENTS

A Coordination

B Pre-installation Meeting

C Sequencing

D Scheduling

1.5 SUBMITTALS

A Action Submittals

1. Product Data a The submittal shall include specification sheets showing all standard and optional accessories to be supplied; schematic wiring diagrams, dimension drawings, and interconnection diagrams identifying by terminal number each required interconnection between the generator set, the transfer switch, and the remote annunciator panel if it is included elsewhere in these specifications.

2. Shop Drawings

3. Samples

B Informational Submittal

1. Certificates

2. Test and Evaluation Reports

3. Manufacturer’s Instruction

4. Source Quality Control Submittals

5. Field or Site Quality Control

6. Manufacturer’s Report

7. Special Procedure Submittal

8. Qualification Statement

C Closeout Submittals

1. Maintenance Contracts

2. Operation And Maintenance Data

3. Bonds

4. Warranty Documentation

5. Record Documentation

6. Software

D Maintenance Material Submittals

1. Literature

2. Spare Parts

3. Extra Stock Materials

4. Tools

1.6 Quality Assurance

A Regulatory Agency

1. The automatic transfer switch shall conform to the requirements of the following codes and standards:

a UL 1008 - Standard for Transfer Switch Equipment b IEC 947-6-1 Low-voltage Switchgear and Control gear; Multifunction equipment;

Automatic Transfer Switching EquipmentEN55011, Limits and Methods of Measurement of Radio Interference Characteristics of Industrial, Scientific and Medical Equipment.

c NFPA 70 - National Electrical Code d NFPA 99 - Essential Electrical Systems for Health Care Facilities e NFPA 110 - Emergency and Standby Power Systems f IEEE Standard 446 - IEEE Recommended Practice for Emergency and Standby Power

Systems for Commercial and Industrial Applications g NEMA Standard ICS 10-2005, Electromechanical AC Transfer Switch Equipment.

h EN61000-4-4 Fast Transient Immunity Severity Level 4 i EN61000-4-5 Surge Immunity Class 4 (voltage sensing and programmable inputs only) j IEEE 472 (ANSI C37.90A) Ring Wave Test k IEC Specifications for EMI/EMC Immunity (CISPR 11, IEC 1000-4-2, IEC 1000-4-3, IEC 1000-4-4, IEC 1000-4-5, IEC 1000-4-6, IEC 1000-4-8, IEC 1000-4-11) l CSA C22.2 No. 178 certification

2. Qualifications a The automatic transfer switch shall be produced by a manufacturer who is ISO 9001 certified for the design, development, production and service of its complete product line.

b A manufacturer who has produced this type of equipment for a period of at least 10 years and who maintains a service organization available twenty-four hours a day throughout the year shall produce the automatic transfer switch.

3. Manufacturers a The automatic transfer switch shall be furnished by a single manufacturer who shall be responsible for the design, coordination, and testing of the complete system. The entire system shall be installed as shown on the plans, drawings, and specifications herein.

b The manufacturer shall maintain a national service organization of employing personnel located throughout the contiguous United States. The Service center’s personnel must be factory trained and must be on call 24 hours a day, 365 days a year.

c The manufacturer shall maintain records of each switch, by serial number, for a minimum of 20 years.

4. Suppliers

5. Fabricators

6. Installers/ Applicators/ Erectors

7. Testing Agencies

8. Licensed Professional

9. Certificates

10. Preconstruction testing

11. Field and Site Samples

12. Mock-ups

1.7 Delivery, Storage, and Handling

A Delivery and Acceptance Requirements

B Storage and Handling Requirements

C Packaging Waste Management

1.8 Field or Site Conditions

A Ambient Conditions

1. Automatic transfer switch shall operate in the following conditions without any damage to the unit or its loads.

a Ambient Temperature: -4 to 158 Degrees F b Relative Humidity: 5% to 95% noncondensing

B Existing Conditions

1.9 Warranty or Bond

A Manufacturer’s Warranty

1. The ATS shall include a standard warranty covering five (5) years to guarantee against defective material and workmanship in accordance with the manufacturer's published warranty from the date of initial startup. Labor and travel charges for the third, fourth, and fifth years are not covered by this warranty.

2. The ATS manufacturer and its distributor shall maintain a 24-hour parts and service organization. This organization shall regularly engage in maintenance contract programs to perform preventive maintenance and service on equipment similar to that specified. A service agreement shall be available and shall include system operation under simulated operating conditions; adjustment to the generator set, transfer switch, and switchgear controls as required, and certification in the owner's maintenance log of repairs made and functional tests performed on all systems.

B Special Warranty

C Extended Correction Period

PART 2 PRODUCTS

2.1 Owner-Furnished or Owner-Supplied

A New Products

B Existing Products

2.2 Equipment

A Equipment

1. Furnish and install an automatic transfer switches system(s) with 3-Pole / 4-Wire, Solid Neutral, 1200 Amps, 208V/60Hz. Each automatic transfer shall consist of an inherently double throw power transfer switch mechanism and a microprocessor controller to provide automatic operation.

All transfer switches and controllers shall be the products of the same manufacturer.

B Manufacturer

1. Automatic transfer switches shall be Kohler Service Entrance Rated - Programmed Transition

(KEP)/KEP-DCTC-1200SPK or approved equivalent. Any alternate shall be submitted for approval to the consulting engineer at least 10 days prior to bid date. Alternate bids shall include a line-by-line clarification of the specification marked with "D" for deviation; "E" for exception, and "C" for comply.

C Construction

D Enclosure

1. The ATS shall be furnished in a NEMA 3R enclosure.

2. All standard door mounted switches and indicating LEDs shall be integrated into a flush-mounted, interface membrane or equivalent in the enclosure door for easy viewing & replacement. The panel shall be capable of having a manual locking feature to allow the user to lockout all membrane mounted control switches to prevent unauthorized tampering. This cover shall be mounted with hinges and have a latch that may be padlocked. The membrane panel shall be suitable for mounting by others when furnished on open type units.

2.3 Description

A Regulatory Requirements

B Sustainability Characteristics

2.4 Performance / Design Criteria

A Capacities

2.5 Operation

A Operators

B Controls

1. A four line, 20 character LCD display and dynamic 4 button keypad shall be an integral part of the controller for viewing all available data and setting desired operational parameters.

Operational parameters shall also be available for viewing and control through the communications interface port or USB. The following parameters shall only be adjustable via a password protected programming on the controller:

a Nominal line voltage and frequency b Single or three phase sensing c Operating parameter protection d Transfer operating mode configuration (Standard transition, Programmed transition, or Closed transition)

C Voltage and Frequency

1. Voltage (all phases) and frequency on both the normal and emergency sources shall be continuously monitored, with the following pickup, dropout, and trip setting capabilities (values shown as % of nominal unless otherwise specified):

a Parameter Dropout/Trip Pickup/Reset b Under voltage 75 to 98% 85 to 100% c Over voltage 106 to 135% 95 to 100% of trip d Under frequency 95 to 99% 80 to 95% e Over frequency 01 to 115% 105 to 120% f Voltage unbalance 5 to 20% 3 to 18%

2. Repetitive accuracy of all settings shall be within ± 0.5% over an operating temperature range of -

20°C to 70°C.

3. An adjustable dropout time for transient voltage and frequency excursions shall be provided. The time delays shall be 0.1 to 9.9 seconds for voltage and .1 to 15 seconds for frequency.

4. Voltage and frequency settings shall be field adjustable in 1% increments either locally with the display and keypad, remotely via the communications interface port or USB.

5. The controller shall be capable of sensing the phase rotation of both the normal and emergency sources. The source shall be considered unacceptable if the phase rotation is not the preferred rotation selected (ABC or BAC). Unacceptable phase rotation shall be indicated on the LCD; the service required LED and the annunciation through the communication protocol and dry contacts.

In addition, the phase rotation sensing shall be capable of being disabled, if required.

6. The controller shall be capable of detecting a single phasing condition of a source, even though a voltage may be regenerated by the load. This condition is a loss of phase and shall be considered a failed source.

7. Source status screens shall be provided for both normal & emergency to provide digital readout of voltage on all 3 phases (phase to phase and phase to neutral), frequency, and phase rotation.

D Time Delays

E Additional Features

F Operation Sequence

2.6 Materials

2.7 Assembly or Fabrication

A Factory Assembly

B Shop Fabrication

C Assembly or Fabrication Tolerances

2.8 Mixes

2.9 Finishes

A Primer Materials

B Finish Materials

C Shop Finishing Materials

2.10 Accessories

2.11 Source Quality Control

A Test and Inspection

1. Upon request, the manufacturer shall provide a notarized letter certifying compliance with all of the requirements of this specification including compliance with the above codes and standards.

The certification shall identify, by serial number(s), the equipment involved. No exceptions to the specifications, other than those stipulated at the time of the submittal, shall be included in the certification.

2. The ATS manufacturer shall be certified to ISO 9001 International Quality Standard and the manufacturer shall have third party certification verifying quality assurance in design/development, production, installation and servicing in accordance with ISO 9001.

B Non-Conforming Work

C Manufacturer’s Services

D Coordination of Other Tests and Inspections

PART 3 EXECUTION

3.1 Installers

A Installer List

B Substitution Limitations

3.2 Examination

A Verification of Conditions

B Pre-installation Testing

C Evaluation and Assessment

3.3 Preparation

A Protection of In-place Condition

B Surface Preparation

C Demolition/ Removal

3.4 Installation

A Special Techniques

B Interface with Other Work

C System Integration

D Tolerances

3.5 Repair/ Restoration

3.6 Reinstallation

3.7 Field or Site Quality Control

A Field or Site Tests and Inspection

B Non-Conforming Work

C Manufacturer’s Services

3.8 System Startup

3.9 Adjusting

3.10 Cleaning

A Waste Management

3.11 Closeout Activities

A Demonstration

B Training

3.12 Protection

3.13 Maintenance

3.14 Attachments

END OF SECTION