6-Bluffdale ES Kitchen HVAC 100 Combined.pdf
PDF 5 MB Posted
- Attached to
- IFB - Make-Up-Air Replacement Bluffdale Elementary School State and local contract opportunity
- Solicitation number
- 26DB02
- Issued by
- Salt Lake County, Utah
About this file
This file contains design and construction documents for the Bluffdale Elementary School Kitchen HVAC replacement project, prepared by Olsen & Peterson Consulting Engineers (Mechanical), Reaveley Engineers (Structural), and Resolut Group (Electrical) for Jordan School District. The project scope involves replacing the existing make-up air unit (MAU-1) serving the kitchen area at 14323 S 2700 W, Bluffdale, Utah 84065. The new system includes a Greenheck indirect natural gas-fired make-up air unit with 4,400 CFM capacity, a Carrier rooftop unit (RT-1) with 1,600 MBH heating capacity and 3,013 MBH gross cooling capacity, two Mitsubishi split air conditioning systems (AC-1 for heating and cooling, AC-2 for cooling only), new ductwork with supply and return air lines, control panels, and thermostats. The construction documents include detailed mechanical plans, reflected ceiling plans, mechanical schedules, mechanical details for ductwork and equipment installation, plumbing plans for condensate drainage and water supply, and electrical plans for power distribution and controls. A structural memorandum confirms the existing roof structure adequately supports the new mechanical equipment weighing 2,236 pounds with the addition of reinforcing steel angles at bearing locations.
Pricing, payment terms, performance schedules, and contractual conditions are not included in these design documents. The project location is at an elevation of 4,250 feet in Bluffdale, Utah, and the design incorporates R-454B refrigerant in accordance with current standards. All equipment is specified to be UL-listed and ARI-certified where applicable, with specific provisions for MERV 8 or MERV 13 filter upgrades, BACnet-compatible controls for building management system integration, and coordination requirements among mechanical, electrical, plumbing, and structural trades during installation. The electrical work includes extending circuits from existing panels (F(E) and J(E)) with appropriately sized conductors and overcurrent protection, while maintaining existing fire alarm system integration through Nelson Fire Systems.
View the file
Other files for this state and local contract opportunity
| File | Type | Posted |
|---|---|---|
| 4-Attachment A - JSD Standard Terms Conditions.pdf | ||
| 3-Attachment F - URS Post-Retired Verification Form.pdf | ||
| 1-Vendor Information Sheet - 02.26.2025.pdf | ||
| 2-Attachment B - Boycott Statement - 09.pdf | ||
| 5-Bluffdale ES Kitchen HVAC Bid Specifications.pdf | ||
| 7-26DB02 - IFB - Bluffdale Make Up Air Replacement.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet No.
Pr oj ec t T itl e
Sh ee t T itl e
JA
N
. 2
XX
X
D at e:
Pr oj ec t N o.
D ra w n:
C he ck ed
4 JP
PR
O
PO
SE
D N
EW
C
O N
ST
R
U C
TI
O
N F
O R
S
W , B
LU
FF
D A
LE
, U
TA
H
B
LU
FF
D
A
LE
E S
K
IT
C H
EN
H
VA
C
TS
TI
TL
E
SH
EE
T
N
JANUARY 5, 2026
SITE ADDRESS
DRAWING INDEXVICINITY MAPCONSULTANTS
OLSEN & PETERSON CONSULTING ENGINEERS - MECHANICAL
14 East 2700 South Salt Lake City, Utah 84115 Phone: (801) 486-4646
GENERAL
TS TITLE SHEET
MECHANICAL
M101 M201 M501 M601
MECHANICAL PLAN
REFLECTED CEILING PLAN
MECHANICAL SCHEDULES
MECHANICAL DETAILS
BLUFFDALE
ELEMENTARY
SCHOOL
BLUFFDALE ELEMENTARY SCHOOL KITCHEN HVAC UPGRADE
14323 S 2700 W
BLUFFDALE, UTAH 84065
REAVELY ENGINEERS - STRUCTURAL
250 East 200 South #1000 Salt Lake City, Utah 84111 Phone: (801) 486-3883
ELECTRICAL
E001 E002 E101
ELECTRICAL TITLE SHEET
ELECTRICAL SCHEDULES AND NOTES
FIRST FLOOR ELECTRICAL PLAN
STRUCTURAL
S100 STRUCTURAL DETAILS
RESOLUT GROUP - ELECTRICAL
181 East 5600 South Suite 200 Murray, Utah 84107 Phone: (801) 530-3148
STORAGE
KITCHEN
OFFICE
FREEZER
ELEC.
RECEIVING
JAN./OFFICE
LOCKER
TOILET
CAN WASH
MULTI PURPOSE
MULTI PURPOSE
SERVING
T
STORAGE
KITCHEN
SERVING
OFFICE
FREEZER
ELEC.
RECEIVING
JAN./OFFICE
LOCKER
TOILET
CAN WASH
MULTI PURPOSE
MULTI PURPOSE
G-1
G-1
T
RT-1
AC-1
(INDOOR)
AC-1
AC-1
(INDOOR)
AC-1
AC-2
(INDOOR)
AC-2
(ALT-1)
(ALT-1)
(ON ROOF)(ON ROOF)
(ON ROOF)
30"x20" 24"x20" 20"x16" 16"x8"
14"Ø
14"x12"
10"Ø
14"x12"
24"x12"
14"x8" 24"x8"
T
25 T
7 7
T26
10"Ø
10"Ø
30 30
REFERENCE NOTES
1 DISCONNECT SUPPLY DUCTWORK, CONTROLS, WIRING, PIPING,
AND REMOVE EXISTING GAS/EVAP MAKE-UP AIR UNIT AND CURB
COMPLETE.
APPROXIMATE LOCATION OF EXISTING SUPPLY DUCTWORK TO
REMAIN.
EXISTING ROOF MOUNTED FREEZER CONDENSER TO REMAIN.
EXISTING ROOF MOUNTED EXHAUST FAN AND EXHAUST
DUCTWORK TO REMAIN.
PROVIDE HEAT SENSOR IN KITCHEN HOOD. PLACE IN A CENTRAL
LOCATION.
REMOVE EXISTING THERMOSTAT AND RELATED WIRING &
CONTROLS.
REBALANCE EXISTING DIFFUSER TO CFM SHOWN.
NEW RETURN AIR GRILLE.
NEW LINED RETURN AIR DUCT. COORDINATE WITH EXISTING
STRUCTURE AND ALL TRADES.
NEW WALL MOUNTED HEATING/COOLING THERMOSTAT TO
CONTROL MAU-1.
NEW MAU/EF CONTROL PANEL. SEE DETAIL 3/M601.
CONNECT SUPPLY OUTLET OF MAU-1 WITH EXISTING SUPPLY
DUCTWORK AT ROOF DECK.
NEW RETURN DUCT AND SUPPLY DUCT DROPS THRU EXISTING
ROOF DECK. COORDINATE WITH EXISTING STRUCTURE. PROVIDE
ANGLE IRON STEEL FRAMING AT OPENING.
CONNECT EXISTING GAS LINE AND WATER LINE FROM PREVIOUS
UNIT TO NEW MAU. FIELD COORDINATE SIZE AND LOCATION. SEE
DETAIL 1/M602.
PROVIDE GAS TO RT-1. SEE DETAIL 2/M601 FOR CONNECTION
DETAIL.
PROVIDE NEW ROOF INSULATION, ROOFING, CURB & ROOF DECK
AS REQUIRED FOR COMPLETE INSTALLATION.
DISCONNECT DUCT AT THIS LOCATION, AND CAP.
REMAINING DUCT RUN AND DIFFUSERS TO BE ABANDONED IN
PLACE.
REMOVE ROOFING IN THIS AREA A MINIMUM OF 3' FROM THE
EDGE OF THE NEW CURB. SEE NEW WORK.
HIGH EFFICIENCY TAKE OFF (HETO).
TURNING VANES (TYP).
FLEX DUCT. MAXIMUM LENGTH 5'-0".
NEW MANUAL BALANCING DAMPER.
CONNECT TO EXISTING DUCT AT APPROXIMATELY THIS
LOCATION.
HARD WIRED HEATING-COOLING THERMOSTAT.
HARD WIRED COOLING THERMOSTAT.
PROVIDE NEW ROOFING FOR CURB AND A MINIMUM OF 3' OUT
FROM THE EDGE OF THE NEW CURB.
REMOVE EXISTING DUCTS AND DIFFUSERS COMPLETE.
COORDINATE WITH NEW WORK.
DUCT TO RUN ABOVE CEILING. COORDINATE WITH EXISTING
CONDITIONS (TYP).
NEW 24" X 24" HINGED CEILING ACCESS PANEL. PANEL TO BE
BRIGHT WHITE.
NORTH
MECHANICAL PLAN
SCALE: 1/4" = 1'-0"
NORTH
MECHANICAL DEMOLITION PLAN
SCALE: 1/4" = 1'-0"
Sheet No.
Pr oj ec t T itl e
Sh ee t T itl e
JA
N
. 2
XX
X
D at e:
Pr oj ec t N o.
D ra w n:
C he ck ed
4 JP
PR
O
PO
SE
D N
EW
C
O N
ST
R
U C
TI
O
N F
O R
S
W , B
LU
FF
D A
LE
, U
TA
H
B
LU
FF
D
A
LE
E S
K
IT
C H
EN
H
VA
C
M
EC
H A
N
IC
A L
PL
A
N
M101
KITCHEN
OFFICE
FREEZER
ELEC.
RECEIVING
JAN./OFFICE
LOCKER
TOILET
CAN WASH
MULTI PURPOSE
MULTI PURPOSE
SERVING
1 1
STORAGE
KITCHEN
SERVING
OFFICE
FREEZER
ELEC.
RECEIVING
JAN./OFFICE
LOCKER
TOILET
CAN WASH
MULTI PURPOSE
MULTI PURPOSE
T
AC-1
(INDOOR)
AC-1
AC-1
(INDOOR)
AC-1
AC-2
(INDOOR)
AC-2
(ALT-1)
(ALT-1)
(ON ROOF)(ON ROOF)
(ON ROOF)
REFERENCE NOTES
1 REMOVE EXISTING DIFFUSER COMPLETE (TYP).
EXISTING KITCHEN HOOD TO REMAIN.
EXISTING DIFFUSER TO BE REMOVED AND REINSTALLED INTO
NEW CEILING.
EXISTING GRILLE TO REMAIN (TYP).
REMOVE EXISTING HARD LID CEILING IN THIS AREA. COORDINATE
WITH MECHANICAL CONTRACTOR.
TEMPORARILY REMOVE ALL EXISTING CEILING MOUNTED LIGHT.
COORDINATE WITH ELECTRICAL DRAWINGS (TYP).
REINSTALL ALL EXISTING CEILING MOUNTED LIGHT FIXTURES.
COORDINATE WITH ELECTRICAL DRAWINGS (TYP).
EXISTING CEILING TO REMAIN (TYP).
CONDENSATE DRAIN TO RUN BELOW CEILING (TYP).
EXISTING FIRE SPRINKLER TO REMAIN (TYP).
INSTALL NEW FIRE SPRINKLER HEADS IN NEW CEILING (TYP).
NEW HARD LID CEILING, MATCH EXISTING CEILING.
NEW 24" X 24" CEILING ACCESS PANEL PROVIDED BY
MECHANICAL CONTRACTOR. (TYP)
EXISTING GAS PIPING WITH SOLENOID SWITCH, TO REMAIN,
DROPS BELOW CEILING AT APPROXIMATELY THIS LOCATION.
NORTH
CEILING MECHANICAL PLAN
SCALE: 1/4" = 1'-0"
NORTH
CEILING DEMOLITION PLAN
SCALE: 1/4" = 1'-0"
Sheet No.
Pr oj ec t T itl e
Sh ee t T itl e
JA
N
. 2
XX
X
D at e:
Pr oj ec t N o.
D ra w n:
C he ck ed
4 JP
PR
O
PO
SE
D N
EW
C
O N
ST
R
U C
TI
O
N F
O R
S
W , B
LU
FF
D A
LE
, U
TA
H
B
LU
FF
D
A
LE
E S
K
IT
C H
EN
H
VA
C
R
EF
LE
C
TE
D
C
EI
LI
N
G P
LA
N
CEILING TO BE REMOVED AND REPLACED.
REMOVE AND REINSTALL ALL ELECTRICAL AND
OTHER FIXTURES AS NECESSARY.
EXISTING CEILING TO BE LEFT INTACT AS MUCH
AS POSSIBLE.
M201 oj ec t T itl e
Sh ee t T itl e
JA
N
. 2
XX
X
D at e:
Pr oj ec t N o.
D ra w n:
C he ck ed
4 JP
PR
O
PO
SE
D N
EW
C
O N
ST
R
U C
TI
O
N F
O R
S
W , B
LU
FF
D A
LE
, U
TA
H
B
LU
FF
D
A
LE
E S
K
IT
C H
EN
H
VA
C
M
EC
H A
N
IC
A L
SC
H
ED
U
LE
S
ROOFTOP UNIT SCHEDULE
MODEL & MANUFACTURERPOWEROATEATTEMP RISETYPE
HEATING CAPACITY GROSS COOLING CAPACITY
ESPCFMSYMBOL
FAN
MOTOR
B.H.P. STAGES
MOPSEER2 WEIGHT
LBS.UNIT DIMENSIONSROOM
MBH
SENSIBLE
MBH
TOTAL
OUTPUT
MBH
INPUT
MBHO.A.
MIN
208/3/60
MCA
208/3/60
RT-1 1600 1"KITCHEN 0.96 1
NATURAL
GAS 24 3013.446.62 36.13 70729.2 74 L x 47 W x 33 H9679.543.253.6278
NECK SIZETYPESYMBOL AIR PATTERN
DIFFUSER SCHEDULE
LOCATION MAKE & MODEL
LOCATION
GRILLE & REGISTER SCHEDULE
SIZESYMBOL TYPE MAKE & MODEL
(1)
NOTES:
(1) COLOR SHALL BE BRIGHT WHITE.
(2) PROVIDE FRAME FOR MOUNTING IN GYP-BOARD CEILING.
NOTES:
(1) COLOR TO BE BRIGHT WHITE
(2) PROVIDE FRAME FOR MOUNTING IN GYP-BOARD CEILING.
G-1 CEILING RETURN AIR PRICE 53524"x24" (2)
10" DIA 4 - WAYCEILING PRICE LCMD
(2)
SUPPLY
REFRIGERANT LIQUID PIPING RL
REFRIGERANT SUCTION PIPING RS
BALL VALVE
UNION
CHECK VALVE
PIPING DROP
PIPING RISE
TTEMPERATURE SENSOR
DIFFUSER
RETURN GRILLE
FLEXIBLE DUCT (MAX 5'-0")
TURNING VANES
BALANCING DAMPER
SUPPLY DUCT RISE
SUPPLY DUCT DROP
ROUND DUCT RISE
ROUND DUCT DROP
RETURN/EXHAUST DUCT RISE
RETURN/EXHAUST DUCT DROP
H.E.T. WITH BALANCING DAMPER
DUCT WITH FLEX DUCT TO DIFFUSER
DUCT TO DIFFUSER
CARRIER
48FEDA053A5-8B1C0
MECHANICAL EQUIPMENT SCHEDULE
(1)(2)(3)(4)(5)
& 120/1/60 208/3/60
NOTES:
(1) PROVIDE HINGED ACCESS DOORS, 100% OUTDOOR AIR ECONOMIZER PACKAGE WITH BUILT-IN 100% RELIEF AIR, 18" HIGH FACTORY ROOF CURB, UNPOWERED WEATHERPROOF GFI CONVENIENCE OUTLET, AND ALL CONTROLS FOR AUTOMATIC OPERATION (WITH ABILITY FOR BMS ENABLE/DISABLE AND MONITORING WITH BACNET). UNIT SHALL BE U.L. LISTED, ARI CERTIFIED AND AGA APPROVED. DOWN DISCHARGE.
(2) COOLING CAPACITY BASED ON 45 DEG. F. S.S.T., 80 DEG. F. db TEMP, 67 DEG. F. wb TEMP. AND 98 DEG. F.O.A. TEMP; HEATING BASED ON 0 DEGREES AMBIENT.
(3) UNITS SHALL BE COMPLETE WITH 2" MERV 8 FILTERS, ABLE TO UPGRADE TO MERV 13 WITH NO CHANGES TO FILTER RACK.
(4) UNITS SHALL USE R-454B REFRIGERANT.
(5) CAPACITIES BASED ON 4250 FT. ELEVATION.
MECHANICAL LEGEND
INDOOR UNIT: HEATING/COOLING, WALL MOUNTED, HORIZONTAL DISCHARGE,
385 CFM, 12,200 BTUH NOMINAL COOLING AT 95°F O.A. TEMP, 80°F D.B. & 67°F W.B. 18,000
BTUH TOTAL HEATING CAPACITY AT 17°F O.A. TEMP, 70°F D.B. & 43°F W.B., MCA=16,
208/230/1/60 MOTOR TO BE UL LISTED. UNIT TO BE COMPLETE WITH CLEANABLE FILTER,
CONDENSATE PUMP, CHECK & EXPANSION VALVE KIT, PRE-CHARGED LINE SET, DRIP PAN AND
DRAIN CONNECTION. PROVIDE WALL MOUNTED THERMOSTAT WITH NIGHT SET BACK.
THERMOSTAT SHALL BE HARD WIRED TO UNIT.
UNIT DIM: 46"W x 12"D x 14.5H
WEIGHT: 46
SEER2 : 21
MANUFACTURER: MITSUBISHI
MODEL: PKA-AL12NL
OUTDOOR UNIT: AIR COOLED, HORIZONTAL DISCHARGE, INVERTER COMPRESSOR, UNIT TO BE
MOUNTED ON ROOF. 12,000 BTUH TOTAL COOLING CAPACITY AT 95°F O.A. TEMP, 80°F
D.B. & 67°F W.B., 20,000 BTUH TOTAL HEATING CAPACITY AT 17°F O.A. TEMP, 70°F D.B. & 60°F
W.B., MCA=16, 208/230/1/60.
AND ALL CONTROLS FOR AUTOMATIC OPERATION. CONTRACTOR TO PROVIDE A
ROOF CURB 18" ABOVE FINISHED ROOF LEVEL. R454B REFRIGERANT.
UNIT DIM: 37.5W x 14"D x 37"H
WEIGHT: 155
MANUFACTURER: MITSUBISHI
MODEL: PUZ-AK12NL
AC-1
HSPF2 : 10
(INDOOR)
AC-1
(OUTDOOR)
UNIT TO BE COMPLETE WITH CRANKCASE HEATER, AMBIENT CONTROL KIT TO 0°F,
12" DIA 4 - WAYCEILING PRICE LCMD
(2)
SUPPLY
G-2 CEILING SUPPLY AIR PRICE 10SS48"x12" (2)
4400 1.25" YES DOWN 420.8 340.8 3 H.P. GREENHECK IGX-P120-H32-MF-N
MAKE-UP AIR UNIT SCHEDULE
MODEL & MANUFACTURER
MBH OUTPUTMBH INPUT EFFICIENCY
NATURAL GAS - HEATING CAPACITY
ESPCFMSYMBOL EVAP
SECTION
FLOW
CONFIG
MOTOR HP/
VOLTAGE
SIZE L"xW"xH"
WEIGHT/ LBS
NOTES:
(1) INDIRECT NATURAL GAS FIRED.
(2) FAN CFM AT PROJECT ALTITUDE
(3) 14" FACTORY ROOF CURB, FACTORY DISCONNECT, RAIN HOOD, AND HAIL GUARDS.
(4) FACTORY UN-POWERED 20 AMP@ 120/1/60 CONVENIENCE OUTLET.
(1)(2)(3)(4)
KITCHEN
AREA SERVED
MAU-1 80% 208/3/60
139-3/4"L x 41-3/8"W x 43-7/8"H
1500 LBS-- 17.3 A 25 A
MCAFLA MOCP
D-1
CFM
D-2
CFM
(1)
M501
INDOOR UNIT: COOLING ONLY, WALL MOUNTED, HORIZONTAL DISCHARGE,
775 CFM, 24,000 BTUH NOMINAL COOLING AT 95°F O.A. TEMP, 80°F D.B. & 67°F W.B.
MCA=16,
208/230/1/60 MOTOR TO BE UL LISTED. UNIT TO BE COMPLETE WITH CLEANABLE FILTER,
CHECK & EXPANSION VALVE KIT, PRE-CHARGED LINE SET, DRIP PAN AND
DRAIN CONNECTION. PROVIDE WALL MOUNTED THERMOSTAT WITH NIGHT SET BACK.
THERMOSTAT SHALL BE HARD WIRED TO UNIT.
UNIT DIM: 36"W x 9.5"D x 12"H
WEIGHT: 28LB
SEER2 : 21.1
MANUFACTURER: MITSUBISHI
MODEL: PKA-AK24NL
OUTDOOR UNIT: AIR COOLED, HORIZONTAL DISCHARGE, INVERTER COMPRESSOR, UNIT TO BE
MOUNTED ON ROOF. 24,000 BTUH TOTAL COOLING CAPACITY AT 95°F O.A. TEMP, 80°F
D.B. & 67°F W.B., MCA=16, 208/230/1/60.
AND ALL CONTROLS FOR AUTOMATIC OPERATION. CONTRACTOR TO PROVIDE A
ROOF CURB 18" ABOVE FINISHED ROOF LEVEL. R454B REFRIGERANT.
UNIT DIM: 34"W x 12"D x 24"H
WEIGHT: 100LB
MANUFACTURER: MITSUBISHI
MODEL: PUY-AH24NL
AC-2
(INDOOR)
AC-2
(OUTDOOR)
UNIT TO BE COMPLETE WITH CRANKCASE HEATER, AMBIENT CONTROL KIT TO 0°F,
(ALT-01)
(ALT-01)
oj ec t T itl e
Sh ee t T itl e
JA
N
. 2
XX
X
D at e:
Pr oj ec t N o.
D ra w n:
C he ck ed
4 JP
PR
O
PO
SE
D N
EW
C
O N
ST
R
U C
TI
O
N F
O R
S
W , B
LU
FF
D A
LE
, U
TA
H
B
LU
FF
D
A
LE
E S
K
IT
C H
EN
H
VA
C
NOTE: VERIFY EXACT
REQUIREMENTS WITH
ROOFING CONTRACTOR
KEEP AS SHORT
AS POSSIBLE
(3 FEET MAX)
PIPE RISE FROM
MAIN. SEE PLAN
FOR SIZE
EXISTING ROOF
FLASHING FLANGE
VENT FLASHING RAIN
COLLAR WITH CLAMP
CAULKING (TYPICAL)
6" V
ER
TI
C
AL
SEDIMENT TRAP-
SAME SIZE AS DROP
FLEXIBLE GAS
CONNECTOR.
18" MAX.
GROUND JOINT
UNION
MANUAL MAIN
SHUT-OFF VALVE
PIPING TO BE
SAME SIZE AS
UNIT INLET.
CONNECT TO
ROOFTOP
EQUIPMENT
PLUGGED TEE
GAS REGULATOR
ROOFTOP UNIT GAS
M601SCALE: NTS
LINE CONNECTION DETAIL
EXHAUST FAN &
MAKE-UP AIR UNIT
UP MENU
DOWN ENTER
DATE/TIME
MAKE-UP AIR UNIT
MANUFACTURER
LCD USER INTERFACE
MUST BE CAPABLE OF MAU
& FAN ON/OFF, HEATING,
FAN-ONLY, COOLING AND
MAU ADJUSTABLE SUPPLY
AIR TEMPERATURE
(TYPICAL)
NOTES: LOCATE BOX
WHERE SHOWN ON PLANS.
COORDINATE WITH OWNER.
STAINLESS STEEL,
SURFACE MOUNTED,
LOCKABLE, HINGED
CONTROL BOX
INDICATOR LIGHT
(TYPICAL)
MAKE-UP AIR
(MAU-1)
EXISTING HOOD
EXHAUST FAN
NEW MAKE-UP AIR UNIT AND EXISTING KITCHEN
M601SCALE: NTS
EXHAUST CONTROL PANEL DETAIL - MAIN KITCHEN
G
PROVIDE NEOPRENE
PADS
GAS INLET
EXTERIOR DUCT INSULATION.
18" MIN.
CONNECT DUCT TO EXISTING
SUPPLY DUCT.
GAS RISE INSIDE CURB.
FLASH AT PENETRATION.
PROVIDE VALVE
MAKE-UP AIR UNIT DETAIL
FLASH WATER-TIGHT.
EQUIPMENT BASE/CURB. ALL
PIPING SHALL RISE THRU CURB.
ANCHOR UNIT TO CURB WITH
FOUR 1/2" BOLTS
EXISTING 1/2" COLD
WATER FROM BLDG.
MAKE-UP AIR UNIT
WATER INLET PROVIDE
BALL VALVE WITH DRAIN
DOWNSTREAM OF
SOLENOID
INTAKE HOOD
DO NOT LINE MAKE-UP AIR DUCTWORK
EXISTING 1-1/2" DRAIN
TO SERVICE SINK. SEE
DETAIL 2/P601.
BALL TYPE SHUT OFF VALVE
M601
VOLUME DAMPER
WITH LOCKING
QUADRANT
MINIMUM DUCT HEIGHT = BRANCH
DUCT DIAMETER + 4"
M
NEOPRENE GASKET SEAL
RECTANGULAR
S.A. DUCT
APPLY SEALANT
ALL AROUND
SUPPLY AIR DUCT
HIGH EFFICIENCY DUCT TAKE-
OFF WITH BALANCING DAMPER
& LOCKING QUADRANT
CEILING DIFFUSER
SECURE FLEX DUCT WITH 3 EA.
SHEET METAL SCREWS, TWO
WRAPS OF ALUMINUM TAKE AND
A TYTON CINCH BAND AT INNER
AND OUTER FLEX
WIRE REINFORCED
INSULATED FLEXIBLE
DUCT WITH VAPOR
BARRIER
5'-0" MAXIMUM LENGTH
TYTON DRAWBAND AT
INNER AND OUTER FLEX
OVER 2-WRAPS OF
ALUMINUM TAPE
CEILING
M6.1
WRAP ALL RIGID DUCT
E/ FOIL FACED 1.1/2"
FIBERGLASS DUCT WRAP
5'-0" MAXIMUM FLEX
DUCT LENGTHFASTEN RIGID DUCT
TO SPIN-IN WITH
SHEET METAL SCREWS
#10 X 3/4" SELF TAPPING
CADMIUM PLATED SCREWS.
NO POP RIVETS ALLOWED
INSULATED SHEET
METAL DUCT
HIGH EFFICIENCY TAKE-OFF
WITH BALANCING DAMPER
AND LOCKING QUADRANT
(OPERATOR OUTSIDE
OF INSULATION WRAP)
ATTACH FLEX DUCT TO
RIGID DUCT SECTIONS
WITH TYTON CINCH BANDS
HANGER
STRAPS
1" MIN.
M6.1
FLEX DUCT AND DIFFUSER DETAIL 4
M601
HIGH EFFICIENCY TAKE-OFF DETAIL 5
M601
DUCT HANGER/CONNECTION DETAIL 6
M601
OUTDOOR
CONDENSING
UNIT
3/4" TREATED PLYWOOD
ON TOP OF RAILS
3/4" STEEL STOVE BOLT IN
RECESS W/ 2" WASHER
INDIVIDUAL REFRIGERANT
PIPING AND CONDUIT FLASHING
1 PIECE 22 GAUGE GALV. SHEET
METAL PANS OVER TOP OF BASE.
ALL JOINTS, SEAMS, AND FLASHINGS
SHALL BE SOLDERED
PROVIDE NEOPRENE PADS
WHERE UNIT SITS ON PLATFORM
NOTE:
PROVIDE EQUIPMENT BASE AT OUTDOOR CONDENSING
UNITS. ANCHOR BASE SECURELY TO STRUCTURE AND
EQUIPMENT TO BASE. BASE SHALL BE LARGE ENOUGH
FOR ALL UTILITIES TO RISE THRU BASE. COVER OVER
BASE SHALL BE ONE PIECE WATER RIGHT TURNED OVER
EDGES, FLASH AT UTILITIES
ANCHOR C.U.
SECURELY TO CURB.
(4-PLACES)
TREATED WOOD RAILS TO
FORM A CONTINUOUS
CURB. BOLT EACH SECTION
TO ROOF IN 3 PLACES
ROOF FLASHING
12" CLEAR MIN.
EXISTING
ROOF LINE
ROOF STRUCTURE
DRILL THRU ROOF
STRUCTURE & BOLT
DOWN EQUIPMENT
RAIL
3/4" NUT & 3"
DIA. WASHER
ROOF INSULATION
D
3/4" CONDENSATE DRAIN
PUMPED UP FOR AC-1,
DRAINING EXPOSED FOR AC-2
ANCHOR UNIT
SECURELY
TO WALL
CEILINGCEILING
EXISTING
ROOF
PROVIDE NEOPRENE PADS
18" MIN. CLEAR
REFRIGERANT PIPING
(OUTDOOR)
(INDOOR UNIT)
AC-2
AC-1
AC-1
AC-2
M601
AC-1 AND AC-2 OUTDOOR 7
M601
ROOM SPLIT SYSTEM UNIT 8
M601
PACKAGED ROOF-TOP UNIT DETAIL
UNIT TO BE INSTALLED LEVEL.
SHIM UNDER ROOF CURB
MOUNTING AS NECESSARY
INSTALL NEOPRENE
GASKET BETWEEN UNIT &
ROOF CURB FRAME
ROOF FLASHING BY
GENERAL CONT
18" CLEAR MINIMUMROOF LINE
24" HIGH MANUFACTURERS
INSULATED AND PRE-FABRICATED
ROOF CURB
ROOF OPENINGS TO BE SIZED FOR DUCT
PENETRATIONS. COORDINATE OPENINGS WITH
STRUCTURAL ENGINEER (TYP)
CONDENSATE DRAIN LINE
W/ P-TRAP TO ROOF
OUTSIDE AIR INTAKE W/
WEATHER HOOD
LOCKING ACCESS
DOOR (TYP)
R.A. S.A.
INSTALL SEISMIC RESTRAINT
BRACKETS PER MFGR
INSTRUCTIONS (TYP)
RELIEF AIR OPENING
W/ WEATHER HOOD
SUPPLY AIR DUCTWORK. SEE PLAN FOR SIZE
ATC CONTROL
WIRING CONDUIT
POWER WIRING
CONDUIT
THROUGH THE
BASE RTU UTILITY
PLATE
RETURN AIR DUCTWORK. SEE PLAN FOR SIZE
THROUGH THE
BASE UTILITIES
WATER TIGHT
FITTINGS (TYP)
THROUGH THE BASE
UTILITY PLATE - PLAN VIEW
CONSISTENT AND LEVEL 4"
CONCRETE REQUIRED IN CURB BASE
M601NOT TO SCALE
EXISTING DW
EXHAUST FAN
GAS LINE TO RUN BELOW ROOF
G
M601
M
EC
H A
N
IC
A L
D
ET
A
IL
S
KITCHEN
OFFICE
FREEZER
ELEC.
RECEIVING
JAN./OFFICE
LOCKER
TOILET
CAN WASH
MULTI PURPOSE
MULTI PURPOSE
SERVING
STORAGE
SERVING
OFFICE
FREEZER
ELEC.
RECEIVING
JAN./OFFICE
LOCKER
TOILET
CAN WASH
MULTI PURPOSE
MULTI PURPOSE
RT-1
AC-1
(INDOOR)
AC-1
AC-1
(INDOOR)
AC-1
AC-2
(INDOOR)
AC-2
(ALT-1)
(ALT-1)
(ON ROOF)(ON ROOF)
(ON ROOF)
3/4"
D
1"
G-4OZ
1"
D
D
P601
REFERENCE NOTES
1 DEMO EXISTING GAS LINE BACK FROM UNIT FAR ENOUGH TO
MAKE NEW CONNECTION TO NEW MAU UNIT.
CONNECT EXISTING GAS LINE AND WATER LINE FROM PREVIOUS
UNIT TO NEW MAU. FIELD COORDINATE SIZE AND LOCATION. SEE
DETAILS 1/P601 AND 2/M601.
RUN PIPING ABOVE EXISTING CEILING.
PIPING TO RUN EXPOSED, BELOW CEILING, WITH NO PUMP, AND
DROP AT THIS LOCATION T0 4" AFF, PENETRATE WALL,
DISCHARGE TO CAN WASH ROOM FLOOR (ALT-1).
TERMINATE CONDENSATE DRAIN INDIRECT.
PROVIDE GAS TO RT-1. SEE DETAIL 2/M601 FOR CONNECTION
DETAIL.
CONDENSATE TO RUN EXPOSED, BELOW CEILING, WITH NO
PUMP.
EXISTING GAS PIPING TO REMAIN.
TIE INTO EXISTING GAS AT THIS LOCATION.
NORTH
PLUMBING PLAN
SCALE: 1/4" = 1'-0"
NORTH
PLUMBING DEMOLITION PLAN
SCALE: 1/4" = 1'-0"
Sheet No.
Pr oj ec t T itl e
Sh ee t T itl e
JA
N
. 2
XX
X
D at e:
Pr oj ec t N o.
D ra w n:
C he ck ed
4 JP
PR
O
PO
SE
D N
EW
C
O N
ST
R
U C
TI
O
N F
O R
S
W , B
LU
FF
D A
LE
, U
TA
H
B
LU
FF
D
A
LE
E S
K
IT
C H
EN
H
VA
C
PL
U
M B
IN
G
P
LA
N
P101 oj ec t T itl e
Sh ee t T itl e
JA
N
. 2
XX
X
D at e:
Pr oj ec t N o.
D ra w n:
C he ck ed
4 JP
PR
O
PO
SE
D N
EW
C
O N
ST
R
U C
TI
O
N F
O R
S
W , B
LU
FF
D A
LE
, U
TA
H
B
LU
FF
D
A
LE
E S
K
IT
C H
EN
H
VA
C
P601
NOTE: SOLENOID POSITIONS SHOWN ARE FOR WINTER DRAIN DOWN.
SUPPLY LINE
SUMP OVERFLOW 3/4"
SUMP DRAIN 3/4"
SUMP DRAIN SOLENOID
(NORMALLY OPEN)
SUPPLY LINE DRAIN SOLENOID
(NORMALLY OPEN)
SUPPLY SOLENOID
(NORMALLY CLOSED)
TRAP
DRAIN TO BUILDING
MAU-1
FLASH PIPE
PENETRATIONS
SEPERATELY
NEW ROOFING
SEAL COLD WATER PENETRATION WATER TIGHT.
MAKE UP WATER AND DRAIN SOLENOID DETAIL 1
P601NOT TO SCALE
PL
U
M B
IN
G
D
ET
A
IL
S
EV EV
DO
M
TV
J
P#
FB PT
#-a
LC
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
CO
0 cd
0 cd
0 cd
0 cd
0 cd
DH
DCL
F S
D
R
0 cd
XXX
XXXX
XX
F
X X
X W
A P
W A
P X
X
N
XX XX
NVR
DC
DC
XX
J
P#
#-a
X##
TC
T
X
X
X
X
D##
0 cd
WS
CR
D
X
X
X
X
X
X
X
X
X
X
X
F
F
F
XX
EXIT SIGNAGE
SHADING & ARROWS INDICATE FACES &
DIRECTIONAL CHEVRONS
WALL-MOUNTED FIXTURES, TYPICAL
(VARIOUS SYMBOLS)
LINEAR, CEILING MOUNTED LIGHT FIXTURE
(VARIOUS DIMENSIONS, DOTS INDICATE PENDANT
MOUNT)
RECESSED DOWNLIGHT FIXTURE
CHEVRON INDICATES WALL WASH
DIRECTIONAL LIGHT, TRACK OR FLOOD LIGHT
LINEAR LIGHT, TAPE LIGHT
LIGHTING FIXTURE SYMBOLS LEGEND
NOTE:
1. SWITCH IDS ARE UNIQUE PER SPACE.
2. A SWITCH WITHOUT A TAGGED ID CONTROLS ALL LIGHTING FIXTURES WITHIN A SPACE.
3. ID TAGS MAY BE USED ON CONTROL DEVICES OTHER THAN SWITCHES, SUCH AS OCCUPANCY
SENSORS OR CONTACTORS.
4. ABSENCE OF A SWITCH DESIGNATION ON A LIGHTING FIXTURE INDICATES FIXTURE IS
CONTROLLED BY THE ONLY SWITCH IN THE SPACE.
5. AN "x" IN PLACE OF THE SWITCH DESIGNATION INDICATES UNSWITCHED.
a
SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES
CEILING
CEILING
AS NOTED
AS NOTED
WALL/CEILING
WALL/CEILING
1, 2
1, 2
1, 3, 5, 12
1, 3, 5, 12
POWER SYMBOLS LEGEND
SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES
S
WALL MOUNTED RECEPTACLE
SWITCHED RECEPTACLE
EMERGENCY RECEPTACLE
GROUND FAULT RECEPTACLE
RECEPTACLE MODIFIERS:
##": HEIGHT AFF OC
WP: WEATHERPROOF IN-USE
COVER
T: TAMPER-PROOF
U: RECEPTACLE WITH USB OUTLET
G: GROUND FAULT
18"
18"
D Q SP
18"
18"
RECEPTACLE (SPECIFIC HEIGHT)
ISOLATED GROUND RECEPTACLE
GENERAL NOTE
B
18"
SWITCH MODIFIERS:
K: KEYED
T: TIMER
M: MANUAL STARTER THERMAL
OVERLOAD SWITCH
EMERGENCY POWER OFF PUSH BUTTON
DOOR OPENER PUSH PLATE
ELECTRICAL POWER METER
FUSED DISCONNECT SWITCH
TOMBSTONE RECEPTACLE*
CORD REEL, DEVICE VARIES
CORD DROP, DEVICE VARIES
MULTI-OUTLET ASSEMBLY
FILLED SQUARES INDICATE 120V OUTLET
OPEN SQUARES INDICATE WITH USB
SINGLE / DUAL PORT ELECTRICAL VEHICLE
CHARGER
POWER POLE
NON-FUSED DISCONNECT SWITCH
MAGNETIC STARTER
MAGNETIC STARTER WITH FUSED DISCONNECT
POWER RELAY
PUSHBUTTON
TRANSFORMER:
SEE SINGLE-LINE DIAGRAM FOR DESCRIPTION &
REQUIREMENTS.
TX
7, 25
EMERGENCY EGRESS LIGHT FIXTURE CEILING 1, 2, 4
CRITICAL EGRESS LIGHT FIXTURE CEILING 1, 2, 4
GENERAL LEGEND
SYMBOL DESCRIPTION NOTES
SOLID ARCHED LINES INDICATE UNSWITCHED
POWER CIRCUITING
DASHED ARCHED LINES INDICATE SWITCHED
POWER CIRCUITING
ONE CIRCUIT, HOME RUN TO PANEL
SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES
4" CONCRETE
BASE
MAIN DISTRIBUTION PANEL 6'-6" TO TOP
FLUSH PANELBOARD 6'-6" TO TOP
SURFACE PANELBOARD 6'-6" TO TOP
TWO CIRCUITS, HOME RUN TO PANEL -
THREE CIRCUITS, HOME RUN TO PANEL -
CONDUIT RUN CONCEALED IN FLOOR OR GROUND -
CONDUIT RUN CONCEALED IN WALL OR CEILING -
CONDUIT UP -
CONDUIT DOWN -
CONDUIT STUB LOCATION CAP CONDUIT
CONDUIT / CIRCUIT CONTINUATION -
GROUND BUS BAR
CABLE TRAY
SOLID BOTTOM
LADDER
BASKET
MOUNTING
AS NOTED
8+18"
EQUIPMENT CEILING RACK
EQUIPMENT CABINET/RACK
EQUIPMENT 2-POST CABINET/RACK
TELEPHONE DEMARCATION BOARD +18" 25
AS NOTED 18, 25
SEE SPEC.
AS NOTED 18, 25
SEE SPEC.
CEILING
EXISTING --
DEMO --
TEMPORARY --
NEW --
CONDUIT
OHP: OVERHEAD POWER SERVICE
UGP: UNDERGROUND POWER
SERVICE
UGF: UNDERGROUND FIBER
SERVICE
TEL: TELEPHONE SERVICE
POWER DISTRIBUTION EQUIPMENT SYMBOLS
CIRCULAR, CEILING MOUNTED LIGHT FIXTURE
CENTER DOT INDICATES PENDANT
CEILING 1, 2, 4
CONTROLLED RECEPTACLE +18" OR AS
NOTED
SPD PROTECTED RECEPTACLE +18" OR AS
NOTED
TIME CLOCK +60" -
NOT IN CONTRACT --
MAGNETIC STARTER WITH BREAKER DISCONNECT
CEILING MOUNTED RECEPTACLE CEILING
TV BACKBOX FLAT PANEL
HEIGHT +12"
EMERGENCY LIGHTING UNIT, INTEGRAL BATTERY WALL/CEILING 1
CW W: WALL C: CEILING
LIGHTING TAGS LEGEND
NOTES:
1. HATCHED FILL INDICATES DISTRIBUTION PANEL OR
SWITCHBOARD.
2. SOLID FILL INDICATES BRANCH PANEL OR LOAD CENTER.
3. DASHED BOX INDICATES CODE-REQUIRED CLEARANCE
(WIDTH & DEPTH).
4. DOOR INDICATES FRONT OF RECESSED PANEL.
H P
1A
LP
1A
M D
P
SB1
POWER TAGS LEGEND
GENERAL LEGEND
SYMBOL DESCRIPTION NOTESMOUNTING
KEYNOTE
ROOM NAME & NUMBER
DIAGRAM TAG
MATCH LINE TAG
ROOM NAME & NUMBER W/ ZONE I.D.
JUNCTION BOX
x
EXIT SIGNAGE WITH AUXILIARY HEAD
SHADING & ARROWS INDICATE FACES &
DIRECTIONAL CHEVRONS
AS NOTED
S: SIMPLEX D: DUPLEX
Q: FOURPLEX SP: SPECIAL PURPOSE
FLOOR BOX / POKE-THRU
- SEE SCHEDULE FOR TYPE INFORMATION
AREA LIGHT POLE & FIXTURE
POST-TOP LIGHT POLE & FIXTURE
BOLLARD LIGHT
ARROWS INDICATE DIRECTION
SWITCH
SWITCH MODIFIERS:
3: 3-WAY
4: 4-WAY
K: KEYED
D: DIMMING
T: TIMER
P: SWITCH W/ PILOT LIGHT
CONCRETE
BASE
CONCRETE
BASE
CONCRETE
BASE
LIGHTING CONTROL SYMBOLS
SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES
46"
1, 14
REFER TO DIA
1, 14
REFER TO DIA
1, 14
REFER TO DIA
6, 7
STEP LIGHT FIXTURE AS NOTED 1
IN-GRADE LIGHT FIXTURE AS NOTED 1
MOMENTARY CONTACT SWITCH 46" 6, 7
LOW VOLTAGE WALL STATION
(SUBSCRIPT INDICATES CONFIGURATION)
46" 6, 7
CEILING FAN CEILING -
LIGHTING CONTACTOR
LIGHTING CONTROL TOUCH SCREEN
WALL
46"
SENSORS/SWITCHES:
PC: PHOTO-ELECTRIC CONTROL
OS: OCCUPANCY SENSOR SWITCH
DL: DAYLIGHT HARVESTING SENSOR
AS NOTED 6, 7, 28
6,7
SWITCH PACKS:
AP: AUXILIARY PACK
PP: POWER PACK
ABOVE
CEILING
6, 28
CONTROL:
RC: DIGITAL ROOM CONTROLLER
(SUBSCRIPT = NUMBER OF RELAYS)
EP: EMERGENCY LIGHTING CONTROL
UNIT
ABOVE
CEILING
REFER TO DIA
AND SPEC
FIRE ALARM SYMBOLS LEGEND
SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES
+94" WALL /
CEILING OR AS
NOTED
7, 29AUDIBLE ANNUNCIATION
(BLANK): HORN
LF: LOW FREQUENCY HORN
SP: SPEAKER
FB: FIRE BELL
+48" 8, 29MANUAL PULL STATION
+94" WALL /
CEILING OR AS
NOTED
7, 29VISIBLE ANNUNCIATION, CANDELA AS INDICATED
(BLANK): CLEAR STROBE
B: BLUE STROBE
A: AMBER STROBE
+94" WALL /
CEILING OR AS
NOTED
7, 29AUDIBLE/VISIBLE ANNUNCIATION, CANDELA AS
INDICATED
(BLANK): CLEAR STROBE
B: BLUE STROBE
A: AMBER STROBE
LF: LOW FREQUENCY HORN
SP: SPEAKER
+94" WALL /
CEILING OR AS
NOTED
7, 29REMOTE INDICATOR w/ TEST SWITCH
CEILING 29SMOKE DETECTOR
CEILING 29HEAT DETECTOR
CEILING 29CARBON MONOXIDE DETECTOR
CEILING 29BEAM DETECTOR
T: TRANSMITTER
R: RECEIVER
CEILING 29COMBINATION DETECTOR (UP TO THREE)
CEILING 29DUCT SMOKE DETECTOR
DUCT 29FIRE/SMOKE DAMPER
AS INDICATEDDOOR HOLDER
AS INDICATED 29DOOR CLOSER
+48" 8, 29FIRE SERVICE PHONE
29ADDRESSABLE MODULE
AIM: ADDRESSABLE INPUT MODULE
AOM: ADDRESSABLE OUTPUT MODULE
AIO: ADDRESSABLE INPUT/OUTPUT
+48" 8, 21, 29FIRE ALARM CONTROL UNIT
EVAC: VOICE EVACUATION CONTROL
PANEL
FAA: FIRE ALARM ANNUNCIATOR
FACP: FIRE ALARM CONTROL PANEL
FATC: FIRE ALARM TERMINAL CABINET
NACP: NOTIFICATION APPLIANCE
CIRCUIT PANEL
FAMN: FIRE ALARM MASS
NOTIFICATION PANEL
TW: TWO WAY COMMUNICATION
INTERCOM
TWZ: TWO WAY COMMUNICATION
CONTROLLER
8, 29SUPERVISORY or INTERFACE DEVICE
PIV: POST INDICATOR VALVE
PS: PRESSURE SWITCH
R: NON-ADDRESSABLE RELAY
VS: VALVE SUPERVISORY SWITCH
FS: FLOW SWITCH
TS: TAMPER SWITCH
WF: WATER FLOOD SENSOR
CW W: WALL C: CEILING
DATA NETWORK SYMBOLS LEGEND
SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES
DATA OUTLET (SINGLE CABLE) 18" WALL/
FLOOR/CEILING
DATA OUTLET (TWO CABLES) 18" WALL/
FLOOR/CEILING
DATA OUTLET (THREE CABLES) 18" WALL/
FLOOR/CEILING
SERIES-X COAXIAL CABLE OUTLET
DISTRIBUTED ANTENNA SYSTEM (DAS)
PUBLIC SAFETY AND/OR
CELLULAR/COMMERCIAL
ANT: ANTENNA
BDA: BI-DIRECTIONAL AMPLIFIER
SPL: SPLITTER
VIA: VIA
108" WALL,
CEILING,
ABOVE
CEILING, OR AS
NOTED
WIRELESS ACCESS POINT* 96" WALL/
CEILING
W F C W: WALL F: FLOOR C: CEILING
SECURITY SYMBOLS LEGEND
SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES
VIDEO SURVEILLANCE CAMERA
SEE CAMERA SURVEILLANCE TYPE SCHEDULE
NVR: NETWORK VIDEO RECORDER/SERVER
WS: SECURITY WORKSTATION
ACCESS CONTROL DOOR CONTACT / WINDOW
SWITCH
SPECIALIZED SWITCH / CONTACT
(GARAGE DOOR, ROOF ACCESS DOOR / HATCH)
AS NOTED 14, 17
DOOR /
WINDOW JAMB
INTRUSION DETECTION:
AS: ALARM AND/OR STROBE
DP: DOOR/WINDOW CONTACT
GB: GLASS BREAK DETECTOR
MD: MOTION DETECTOR
PI: POP-IT MODULE
SC: SMOKE & C/O DETECTOR COMBO
SH: SMOKE & HEAT DETECTOR COMBO
ACCESS CONTROL:
DH: MAGNETIC DOOR HOLD OPENER
EC: ELECTRIFIED EXIT RIM DEVICE
EL: ELECTRIFIED DOOR LOCK
ES: ELECTRIFIED DOOR STRIKE
ML: ELECTROMAGNETIC LOCK
(MAG LOCK)
RX: REQUEST TO EXIT MOTION
7, 15, 17
CW
CW W: WALL C: CEILING
W: WALL C: CEILING
INTRUSION DETECTION SYSTEM:
KP: KEYPAD (ARM/DISARM)
ACCESS CONTROL SYSTEM:
CR: CARD READER
BR: BIOMETRIC READER
ICR: INTEGRATED CARD READER
KCR: CARDREADER W/ KEYPAD
OTHER:
INT: IP TWO-WAY AUDIO & VIDEO
INTERCOM
KS: KEY OVERRIDE SWITCH
18" WALL/
FLOOR/CEILING
CW W: WALL C: CEILING
EQUIPMENT SYSTEM PANELS
ACS: ACCESS CONTROL PANEL
IDS: INTRUSION DETECTION PANEL
PSP: POWER SUPPLY PANEL
RP#: LIGHTING PANEL
DAS: DISTRIBUTED ANTENNA SYSTEM
ERCCS: FIRST RESPONDERS RADIO SYSTEM
CATV: CABLE TV CONTENT EQUIPMENT
CEILING
CEILING
+46"
+46"
+46"
+72"
+60"
+60"
+60"
+60"
AS NOTED
+46"
18, 25
SEE SPEC.
7, 22
7, 25
7, 25
7, 25
7, 25
7, 25
Space
Space
XX
A a
7, 15, 17
DOOR JAMB,
OR AS NOTED
+46" OR
DOOR JAMB
FIXTURE ID (UPPERCASE UNDERLINED LETTER)
PANEL ID (NUMBERS & UPPERCASE LETTERS) - CIRCUIT NUMBER
RELAY ID (UPPERCASE LETTERS)
FIXTURE CONTROL ZONE ID (LOWERCASE LETTER)
#: INDICATES SWITCH TYPE
LOWERCASE LETTER: INDICATES SWITCH ID
DEVICES WITH A CHEVRON INDICATE TO
COORDINATE WITH MILLWORK PRIOR TO ROUGH-IN.
B
ELEVATION TAG. HATCHED AREA INDICATES
WHICH WALL, NUMBER INDICATES VIEW, AND
CENTER NUMBER INDICATES WHICH SHEET.
REVISION CLOUD DELTA. SHOWN WITH CLOUD
AND INDICATES A CHANGE PER THE TITLE BLOCK.
TAG FOR MECHANICAL, KITCHEN, AND SHOP
DEVICES. REFER TO SCHEDULES FOR INFO.
EF-XX
HICKS
BRIAN
No. 7709037-2202
G
IN
E E R
ONA
O F
E
SS
I
R
UT
AH
TE OF
S T A
P
L EN
PROJECT
NO:DRAWN BY:
CHK'D BY:
DATE:
T H
IS
P
R
IN
T I
S I
N C
O L
O R
T h is d ra w in g i s t h e c o p y ri g h te d p ro p e rt y o f R e s o lu t G ro u p
U n a u th o ri z e d d u p lic a ti o n p u b lic a ti o n o r d is tr ib u ti o n i s tr ic tl y p ro h ib it e d
U s e o f th is d ra w in g i s a t th e u s e r' s o w n r is k a n d
R e s o lu t G ro u p d is c la im s a n y l ia b il it y f o r d a m a g e s o r lo s s e s a ri s in g f ro m i ts u s e
A
BCDEFGHIJKLMN
ABCDEFGHIJKLMN
01/05/2026
250962
/5
/2
:3
:2
A M
A u to d e s k D o c s /2
-J
S D
B lu ff d a le
E S
M A
U R e p la c e m e n t/
J S
D B lu ff d a le E
S M
A U
R e p la c e m e n t_
E L E
C v
.r v t
01/05/2026
BR
ES
ELECTRICAL
TITLE SHEET
E001
B L U
F F
D A
L E
E S
K
IT
C H
E N
H V
A C
S
W
B lu ff d a le U
T
B
LU
F F
D A
LE
E
S K
IT
C
H E
N H
V A
C
ELECTRICAL ABBREVIATIONS INDEX
ABBREV. DESCRIPTION
A AMPS
AC ALTERNATING CURRENT
ACLG ABOVE CEILING
ADC ANALOG-TO-DIGITAL
CONVERTER
AF AMP FRAME
AFC AVAILABLE FAULT CURRENT
AFCI ARC FAULT CIRCUIT
INTERRUPTER
AFF / A.F.F. ABOVE FINISH FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AIC AMPS INTERRUPTING CAPACITY
AL ALUMINUM
ALT ALTERNATE
AM AMPS METER
AMP AMPERE
AMPL AMPLIFIER
ANN ANNUNCIATOR
AOE AUDIO-OVER-ETHERNET
APPROX APPROXIMATELY
AQ-STAT AQUASTAT
ARCH ARCHITECT, ARCHITECTURAL
AS AMP SWITCH
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIOVISUAL
AWG AMERICAN WIRE GAUGE
BATT BATTERY
BC BARE COPPER
BD BOARD
BFC BELOW FINISHED CEILING
BFG BELOW FINISHED GRADE
BLDG BUILDING
BMS BUILDING MANAGEMENT
SYSTEM
BPM BEATS-PER-MINUTE
C, CND CONDUIT
C.O. CONDUIT ONLY
C/W COMPLETE WITH
CAB CABINET
CAT CATEGORY CABLE
CAT# CATALOG
CATB COMMUNITY ANTENNA
TELEVISION
CATV CABLE TELEVISION
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CF CREST FACTOR
CKT CIRCUIT
CLG CEILING
CMPR COMPRESSOR
CNTR CONTRACTOR
CO CONDUIT ONLY
CODEC CODER-DECORDER
COMB COMBINATION
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR CONTINUOUS
CONV CONVECTOR
CP CIRCULATING PUMP
CRT COMPUTER TERMINAL
CT CURRENT TRANSFORMER
CU COPPER
CV CONSTANT VOLTAGE
DAC DIGITAL-TO-ANALOG
CONVERTER
DB DECIBEL
DBFS DB REF. FULL SCALE
DBM DB REF. 0.001 WATT
DBU DB REF. 0.775 V
DBV DB REF. 1 V
DC DIRECT CURRENT
DCP DOMESTIC CIRCULATING PUMP
DED DEDICATED
DEPT DEPARTMENT
DET DETAIL
DFA DROP FROM ABOVE
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DPR DAMPER
DR DYNAMIC RANGE
DS DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
EG EMERGENCY GENERATOR
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
ELU EMERGENCY LIGHTING UNIT
EM EMERGENCY/EGRESS BATTERY
EMI ELECTRO-MAGNETIC
INTERFERENCE
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
ENT ELEC. NON-METAL. TUBING
EP ELECTRIC PNEUMATIC
EQUIP EQUIPMENT
ER EXISTING TO BE RELOCATED
ES SOURCE VOLTAGE
EWC ELECTRIC WATER COOLER
FA FIRE ALARM
FABP FIRE ALARM BOOSTER PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOT CANDLE
FCU FAN COIL UNIT
FIR FINITE IMPULSE RESPONSE
FILTER
FIXT FIXTURE
FLR FLOOR
FLUOR FLUORESCENT
FMC FLEXIBLE METAL CONDUIT
FU FUSE
FUDS FUSE SAFETY DISCONNECT
SWITCH
GA GAUGE
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEC GRND. ELEC. COND. AT SES
GEN GENERATOR
GFCI GROUND FAULT CURRENT
INTERRUPTER
GFI GROUND FAULT INTERRUPTER
GFP GROUND FAULT PROTECTOR
GND GROUND
ABBREV. DESCRIPTION
GRC GALVANIZED RIGID CONDUIT
GYP BD GYPSUM BOARD
HOA HAND-OFF-AUTOMATIC SWITCH
HORIZ HORIZONTAL
HP HORSE POWER
HPF HIGH POWER FACTOR
HT HEIGHT
HTG HEATING
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING & AIR
CONDITIONING
HZ HERTZ
I/W INTERLOCK WITH
IC INTERRUPTING CAPACITY
IFC INTERNATIONAL FIRE CODE
IG ISOLATED GROUND
IIR INFINITE IMPULSE RESPONSE
FILTER
IMC INTERMEDIATE METALLIC
CONDUIT
INCAND INCANDESCENT
IR INFRARED
IT TOTAL CURRENT
J-BOX JUNCTION BOX
KCMIL 1000 CIRCULAR MILS (MCM)
KHZ THOUSANDS OF HZ
KV KILOVOLT
KVA KILOVOLT AMPERES
KVAR KILOVARS
KW KILOWATT
KWH KILOWATT HOUR
LCS C-WEIGHTED SLOW SOUND
LEVEL
LEQ EQUIVALENT SOUND LEVEL
LFMC LIQUID-TIGHT FLEX.
METAL. COND.
LFNC LIQUID-TIGHT FLEX. NON-METAL.
COND.
LOC LOCATE OR LOCATION
LP, SPL SOUND PRESSURE LEVEL
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LU LOUDNESS UNIT METERING
LUFS LOUDNESS UNIT FULL SCALE
LV LOW VOLTAGE
M/C MOMENTARY CONTACT
MAC MEDIA ACCESS CONTROL
MAG.S MAGNETIC STARTER
MAX MAXIMUM
MB MAIN BUS
MC MECHANICAL CONTRACTOR
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCM 1000 CIRCULAR MILLS
MDC MAIN DISTRIBUTION CENTER
MDP MAIN DISTRIBUTION PANEL
MEP MECHANICAL, ELECTRICAL, AND
PLUMBING
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT
SWITCH
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MMS MANUAL MOTOR STARTER
MNF MANUFACTURER
MOA MULTI-OUTLET ASSEMBLY
MSBD MAIN SWITCHBOARD
MSP MOTOR STARTER PANELBOARD
MSS MOTOR STARTER SWITCH
MTG MOUNTING
MTR MOTOR
MTS MANUAL TRANSFER SWITCH
N NEW
N.I.C. NOT IN CONTRACT
N/A NOT APPLICABLE
N1 NEMA 1
N3R NEMA 3R
NAC NOTIFICATION APPLIANCE
CIRCUIT PANEL
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECT.
MANUFAC. ASSOC.
NFDS NON-FUSED SAFETY
DISCONNECT SWITCH
NFPA NATIONAL FIRE PROTECTION
ASSOC.
NL NIGHT LIGHT, BYPASS LOCAL
SWITCHING
NO NORMALLY OPENED
NPF NORMAL POWER FACTOR
NTS NOT TO SCALE
NVR NETWORK VIDEO RECORDER
OC ON CENTER
OH OVERHEAD
OL OVERLOADS
OS & Y OUTSIDE SCREW & YOKE
OSI OPEN SYSTEM INTEGRATION
PA PASCAL
PB PUSHBUTTON
PBB PRIMARY BONDING BUSBAR
PC PLUMBING CONTRACTOR
PCM PULSE CODE MODULATION
PDU POWER DISTRIBUTION UNIT
PE PNEUMATIC ELECTRIC
PED PEDESTAL
PF POWER FACTOR
PFR PHASE FAILURE RELAY
PIV POST INDICATING VALVE
PLEN PLENUM
PNL PANEL
POC POINT OF CONNECTION
POE POWER OVER ETHERNET
POS POINT OF SALE
PP POWER POLE
PPM PEAK PROGRAM METER
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PSI POUNDS-PER-SQUARE-INCH
PT POTENTIAL TRANSFORMER
PTP POINT TO POINT
PTZ PAN, TILT, AND ZOOM
ABBREV. DESCRIPTION
PVC POLYVINYL CHLORIDE CONDUIT
PWR POWER
QUAN QUANTITY
R RESISTANCE
RECEP, RECPT RECEPTACLE
REQ,REQD REQUIRED
REX REQUEST TO EXIT
RF RADIO FREQUENCY
RFM ROOF MOUNTED
RL LOAD RESISTANCE
RLA RATED LOAD AMPS
RM ROOM
RMC RIGID METALLIC CONDUIT
RMP ROCKY MOUNTAIN POWER
RMS ROOT MEAN SQUARE
RNC RIGID NON-METALLIC COND.
RPM ROTATIONS-PER-MINUTE
RS SOURCE RESISTANCE
RT TOTAL RESISTANCE
RTU ROOF TOP UNIT
RX RECEIVER
S/N SOLID NEUTRAL
S/S STOP/START PUSHBUTTONS
SBB SECONDARY BONDING BUSBAR
SBG SUPPLEMENTARY BONDING
GRID
SBJ SYSTEM BONDING JUMPER
SC SURFACE CONDUIT
SCA SHORT CIRCUIT AMPERES
SDI SERIAL DIGITAL INTERFACE
SE SERVICE ENTRANCE
SEC SECONDARY
SES SMOKE EVACUATION SYSTEM
SHT SHEET
SIM SIMILAR
SLD SINGLE-LINE DIAGRAM
SNR SIGNAL-TO-NOISE RATIO
SP SPARE
SPDIF SONY PHILLIPS DIGITAL
INTERFACE
SPEC SPECIFICATIONS
SPKR LOUDSPEAKER
SPL SOUND PRESSURE LEVEL
SPP SINGLE-POINT POWER
SR SURFACE RACEWAY
SS SELECTOR SWITCH
SSW SELECTOR SWITCH
STA STATION
STD STANDARD
STP SHIELDED TWISTED PAIR
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
SYM SYMMETRICAL
SYS SYSTEM
TBB TELECOMMUNICATIONS
BONDING BACKBONE
TBC TELECOMMUNICATIONS
BONDING CONDUCTOR
TC TEMP. CONTROL CONTR.
TEL TELEPHONE
TERM TERMINAL
TL TWIST LOCK
TR TAMPER RESISTANT
T-STAT THERMOSTAT
TTB TELEPHONE TERMINAL BOARD
TTC TELEPHONE TERMINAL CABINET
TV TELEVISION
TVTC TELEVISION TERMINAL
TX TRANSMITTER
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTED POWER
SUPPLY
UT UNDERGROUND TELEPHONE
UTIL UTILITY
UTP UNSHIELDED TWISTED PAIR
UV ULTRAVIOLET
V VOLT (KV-KILOVOLT)
VA VOLT/AMPS
VA/R, VAR VOLT-AMPS/REACTIVE
VAC VOLTS ALTERNATING CURRENT
VDC VOLTS DC CURRENT
VDT VIDEO DISPLAY TERMINAL
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VI VOLUME INDICATOR
VIF VERIFY IN FIELD
VM VOLT METER
VOL VOLUME
VU VOLUME UNIT
W WATTS
W/ WITH
W/O WITHOUT
WG WIRE GUARD
WH WATTHOUR METER
WP WEATHERPROOF/NEMA 3R
XFMR TRANSFORMER
XFMR SW SW TRANSFER SWITCH
XFR TRANSFER
XL X-CONNECTOR LOCKING
XLR X-CONNECTOR LOCKING
RUBBERIZED
XP EXPLOSION PROOF
XR EXISTING TO BE REMOVED
1P ONE-POLE
2P TWO-POLE
3P THREE-POLE
4P FOUR-POLE
∠ ANGLE
& AND
@ AT
° DEGREE
▲ DELTA
', FT FOOT, FEET
", IN INCH, INCHES
# NUMBER
Ω, OHM UNIT OF ELECTRICAL
RESISTANCE
Ø, PH PHASE
℄, CTR CENTER LINE, CENTER
P PLATE
SYMBOL LEGEND GENERAL NOTES
1. SOLID BOX AROUND DEVICE INDICATES INSTALLED IN FLOOR. DASHED BOX AROUND DEVICE
INDICATES INSTALLED IN CEILING.
2. WALL DEVICES NOTED WITH A CHEVRON INDICATE TO COORDINATE WITH MILLWORK SHOP
DRAWINGS & ELEVATIONS FOR HEIGHT.
3. TYPICAL SYMBOL SCHEDULE. SOME SYMBOLS MAY NOT BE USED IN THIS SET OF DRAWINGS.
4. REFER TO LUMINAIRE SCHEDULE FOR FIXTURE TYPES, MOUNTING REQUIREMENTS, WATTAGE
& DETAILS.
5. WIRE LIGHT FIXTURE FROM ADJACENT JUNCTION BOX.
6. CONNECT NEAREST UN-SWITCHED HOT CONDUCTOR TO EMERGENCY BALLAST.
7. LIGHT FIXTURES ARE SCALED WITHIN THE DRAWINGS BASED ON ACTUAL DIMENSIONS.
8. REFER TO DRAWINGS FOR DIRECTIONAL ARROWS.
9. SUBSCRIPT INDICATES FIXTURES TO BE CONTROLLED.
10. HEIGHT MEASURED TO CENTER LINE OF THE BOX FROM THE FINISHED FLOOR.
11. HEIGHT MEASURED TO TOP OF THE BOX FROM FINISHED FLOOR.
12. NEMA TYPE 'ND' NON-FUSED UNLESS NOTED 'F' (FUSED). USE HEAVY DUTY (HD) DEVICE FOR
480 VOLT.
13. SIZE TO THE EQUIPMENT BEING CONTROLLED.
14. PROVIDE H.O.A. & S.S. PUSHBUTTONS AS REQUIRED.
15. DOUBLE ARROWS INDICATES A DOUBLE FACE UNIT.
16. FOR WATER COOLER LOCATION, REFER TO DIAGRAM R002. FOR ALL OTHER LOCATIONS,
MOUNT AT +16" TO BOTTOM OF BOX FROM FINISHED FLOOR, OR AS NOTED.
17. ARROWS SHOWN ON DEVICE INDICATE AIMING DIRECTION.
18. COORDINATE WITH DOOR HARDWARE SUPPLIER.
19. MOUNT ON TRACK OF OVERHEAD DOOR, 6" FROM TOP OF DOOR, UNLESS OVERHEAD DOOR IS
A ROLL UP DOOR, THEN MOUNT PER MANUFACTURER'S INSTRUCTIONS.
20. INSTALL DEVICES PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
21. DASHED LINE INDICATES EQUIPMENT CLEARANCES. ARROW INDICATES FRONT OF RACK.
22. HEIGHT MEASURED TO BOTTOM OF THE DEVICE FROM FINISHED FLOOR.
23. PROVIDE MUD RING &/OR BOX COVER APPROPRIATE FOR DEVICE/FIXTURE SERVED.
24. REFER TO DIAGRAMS, ELEVATIONS, & SCHEDULES FOR CUSTOM ROUGH-IN REQUIREMENTS.
25. ROUGH-IN TO BE HORIZONTAL.
26. REFER TO MANUFACTURER'S RECOMMENDED CABLE REQUIREMENTS FOR EXACT CABLE
REQUIRED.
27. FOLLOW BICSI STANDARDS FOR CABLE ROUTING & DISTANCES.
28. SUBSCRIPT INDICATES NEMA CONFIGURATION.
29. USE A 4" X 4" BOX WITH A MUD RING TO MATCH THE DEVICE & INSTALLATION.
30. USE WITH POWER PACK.
31. PROVIDE UL LISTED DEVICE COMPATIBLE WITH THE FIRE ALARM PANEL/SYSTEM.
32. CAMERA TYPES ARE INDICATED INSIDE THE CAMERA SYMBOL.
GENERAL SYMBOLS LEGEND
SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES
EQUIPMENT CEILING RACK CEILING 18, 25, SEE
SPEC.
EQUIPMENT CABINET/RACK AS NOTED 18, 25, SEE
SPEC.
EQUIPMENT 2-POST CABINET/RACK AS NOTED 18, 25, SEE
SPEC.
TELEPHONE DEMARCATION BOARD +18" 25
ELECTRICAL SHEET LIST
E001 ELECTRICAL TITLE SHEET
E002 ELECTRICAL SCHEDULES & NOTES
E101 FIRST FLOOR ELECTRICAL PLAN
EXISTING SYSTEMS INFORMATION AND VENDOR CONTRACTS
(INCLUDE WITHIN BID)
FIRE ALARM SYSTEM - HONEYWELL FCI 7200 SERIES
COMPANY
CONTACT
CELL PHONE NO.
OFFICE PHONE NO.
EXTEND EXISTING FIRE ALARM INTIATION/NOTIFICATION CIRCUITS TO ACCOMMODATE NEW FIRE ALARM DEVICES AS REQUIRED. MATCH SYSTEM WIRING. UPDATE
PROGRAMMING.
NELSON FIRE SYSTEMS
OFFICE
801-468-8300
OFFICE@NELSONFIRE.COM
801-468-8300
REVISIONS
MARK DATE DESCRIPTION
HICKS
BRIAN
No. 7709037-2202
G
IN
E E R
ONA
O F
E
SS
I
R
UT
AH
TE OF
S T A
P
L EN
PROJECT
NO:DRAWN BY:
CHK'D BY:
DATE:
T H
IS
P
R
IN
T I
S I
N C
O L
O R
T h is d ra w in g i s t h e c o p y ri g h te d p ro p e rt y o f R e s o lu t G ro u p
U n a u th o ri z e d d u p lic a ti o n p u b lic a ti o n o r d is tr ib u ti o n ic tl y p ro h ib it e d
U s e o f th is d ra w in g i s a t th e u s e r' s o w n r is k a n d
R e s o lu t G ro u p d is c la im s a n y l ia b il it y f o r d a m a g e s o r lo s s e s a ri s in g f ro m i ts u s e
A
BCDEFGHIJKLMN
ABCDEFGHIJKLMN
01/05/2026
250962
/5
/2
:3
:2
A M
A u to d e s k D o c s /2
-J
S D
B lu ff d a le
E S
M A
U R e p la c e m e n t/
J S
D B lu ff d a le E
S M
A U
R e p la c e m e n t_
E L E
C v
.r v t
01/05/2026
BR
ES
ELECTRICAL
SCHEDULES &
NOTES
E002
B L U
F F
D A
L E
E S
K
IT
C H
E N
H V
A C
S
W
B lu ff d a le U
T
B
LU
F F
D A
LE
E
S K
IT
C
H E
N H
V A
C
ELECTRICAL DEMOLITION NOTES
1. REFERENCE & COORDINATION
A. REFER TO ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR DEMOLITION AND
CONSTRUCTION PHASES. COORDINATE ALL ELECTRICAL WORK WITH GENERAL
CONSTRUCTION REQUIREMENTS, DOOR RELOCATIONS, AND WALL MODIFICATIONS.
2. DEVICE & FIXTURE REMOVAL
A. DISCONNECT AND REMOVE ALL ELECTRICAL DEVICES, SWITCHES, AND LIGHTING
FIXTURES IN DEMOLITION AREAS UNLESS NOTED OTHERWISE.
B. REMOVE ALL CONDUIT/WIRING IN WALLS SCHEDULED FOR DEMOLITION (SHOWN
DASHED) BACK TO THE LAST ACTIVE DEVICE.
C. WHERE NEW WALLS INTERSECT EXISTING ONES, REMOVE ANY AFFECTED DEVICES,
BOXES, OR BACK BOXES.
3. CIRCUIT CONTINUITY & SYSTEM MODIFICATIONS
A. FURNISH AND INSTALL CONDUIT, WIRING, AND/OR COMMUNICATIONS/DATA CABLING AS
NECESSARY TO MAINTAIN CONTINUITY OF FEEDERS, BRANCH CIRCUITS, AND SYSTEMS
SERVING DEVICES OR EQUIPMENT TO REMAIN.
B. RECONNECT, RELOCATE, AND/OR REWIRE EXISTING DEVICES, FIXTURES, OR EQUIPMENT
AS REQUIRED TO AVOID CONSTRUCTION CONFLICTS AND ENSURE PROPER OPERATION.
4. EQUIPMENT OUTSIDE WORK AREA
A. LEAVE ALL EQUIPMENT IN NON-REMODELED AREAS IN WORKING CONDITION. RESTORE
ANY INTERRUPTED FEEDERS, BRANCH CIRCUITS, OR SYSTEMS TO FULL OPERATION.
5. RACEWAYS & WIRING
A. EXISTING RACEWAYS MAY BE REUSED IF THEY MEET CURRENT CODE, SPECIFICATIONS,
AND PROJECT INTENT. VERIFY THEIR INTEGRITY BEFORE REUSE.
B. CONCEAL RACEWAYS AND WIRING IN EXISTING WALLS, CEILINGS, AND FLOORS UNLESS
OTHERWISE INDICATED. USE SURFACE METAL RACEWAY ONLY WHERE EXPLICITLY
NOTED.
C. REMOVE ALL UNUSED RACEWAYS, CONDUCTORS, BOXES, DEVICES, AND EQUIPMENT
NOT INTENDED FOR REUSE.
6. LIGHTING FIXTURE HANDLING
A. REMOVE FIXTURES NOT TO BE REUSED AND EITHER RETAIN FOR THE OWNER OR
DISPOSE OF PROPERLY. STORE REUSABLE FIXTURES IN CARTONS AND LABEL CLEARLY.
7. COVER PLATES
A. PROVIDE BLANK COVER PLATES ON ALL UNUSED OPENINGS.
8. PENETRATIONS
A. DO NOT PENETRATE STRUCTURAL ELEMENTS (FLOORS, WALLS, CEILINGS, ROOFS, ETC.)
UNLESS SPECIFICALLY PERMITTED IN THE CONSTRUCTION DOCUMENTS.
NOTE 4: EC TO VERIFY BREAKER AMPCITY. PROVIDE NEW BREAKERS AS NEEDED TO MATCH OCP SHOWN IN SCHEDULE BELOW.
NOTE 3: ALL EQUIPMENT TO BE RATED FOR THE ENVIRONMENT FOR WHICH IT IS INSTALLED.
NOTE 2: OVERCURRENT PROTECTION DEVICE (OCPD) SHOWN IS LOCATED AT POWER PANEL. ALL FUSING TO BE SIZED IN ACCORDANCE WITH FUSE MFR RECOMMENDATION FOR MOTOR NAME PLATE RATING.
NOTE 1: PER 250.122(A), EQUIPMENT GROUND IS NOT REQUIRED TO BE LARGER THAN THE PHASE CONDUCTOR
GENERAL NOTES
CC - CONTROL CONTRACTOR
MC - MECHANICAL CONTRACTOR (DIVISION 23)
EC - ELECTRICAL CONTRACTOR (DIVISION 26)
RESPONSIBILTY LEGEND:
MECHANICAL EQUIPMENT SCHEDULE
IDENTITY INFORMATION ELECTRICAL LOAD INFORMATION OCP CIRCUIT INFORMATION STARTER CONTROL DISCONNECT
INTERLOCK NOTES
TYPE ID INSTANCE ID
DESCRIPTION VOLTAGE PHASE MOTOR POWER APPARENT POWER REAL POWER FLA MCA TYPE OCP
PHASE CONDUCTORS NEUTRAL CONDUCTOR GROUND CONDUCTOR CONDUIT SIZE
TYPE FURNISH INSTALL TYPE FURNISH INSTALL TYPE FURNISH INSTALL
SETS NO. SIZE TYPE NEUTRAL SIZE TYPE SIZE TYPE SIZE
ACO - 1 AIR CONTITIONING (OUTSIDE CONDENSER) 208 V 1 0.00 hp 2.7 kVA 2.4 kW 12.8 A 16 A (Motor) Inverse Time Breaker 20 A 1 2 12 Cu Yes 12 Cu 12 Cu 3/4" CC CC FUSED EC EC PROVIDE WIRING FROM OUTDOOR TO INDOOR UNIT PER MANUFACTURER REQUIREMENTS
ACO - 1 AIR CONTITIONING (OUTSIDE CONDENSER) 208 V 1 0.00 hp 2.7 kVA 2.4 kW 12.8 A 16 A (Motor) Inverse Time Breaker 20 A 1 2 12 Cu Yes 12 Cu 12 Cu 3/4" CC CC FUSED EC EC PROVIDE WIRING FROM OUTDOOR TO INDOOR UNIT PER MANUFACTURER REQUIREMENTS
ACO - 2 AIR CONTITIONING (OUTSIDE CONDENSER) 208 V 1 0.00 hp 3.7 kVA 3.3 kW 17.6 A 22 A (Motor) Inverse Time Breaker 30 A 1 2 10 Cu Yes 10 Cu 10 Cu 3/4" CC CC FUSED EC EC PROVIDED UNDER ALTERNATE #1
MAU - 1 MAKE UP AIR UNIT 208 V 3 0.00 hp 5.0 kVA 4.5 kW 13.8 A 17.3 A (Motor) Inverse Time Breaker 25 A 1 3 12 Cu Yes 12 Cu 10 Cu 3/4" MAGNETIC STARTERSTARTER EC EC CC CC FUSED EC EC PROVIDE 120V GFCI SERVICE RECEPTACLE
RT - 1 ROOF TOP UNIT 208 V 3 0.00 hp 6.0 kVA 5.4 kW 16.7 A 20.9 A (Motor) Inverse Time Breaker 30 A 1 3 10 Cu Yes 10 Cu 10 Cu 3/4" CC CC FUSED EC EC PROVIDE POWER TO MANUFACTURER PROVIDED WEATHERPROOF GFCI
REVISIONS
MARK DATE DESCRIPTION
NOTES:
TOTAL EST. DEMAND CURRENT: 25.9 A
TOTAL CONN. CURRENT: 25.9 A
TOTAL EST. DEMAND: 9,346 VA
TOTAL CONN. LOAD: 9,346 VA
Other 9,346 VA 100.00% 9,346 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
AIC RATING: UTILITY AMPS RMS SYSM.
22.8 A 38 A 18.3 A AMPS/PHASE 9,346 VA
2662 4493 2190 TOTAL (VA) CONNECTED LOAD TOTAL
EXISTING 20 A 1 -- 41 0 VA 360 VA 42 #12 1 20 A MAU CONTROL PANEL, KITCHEN 124
39 1,331 VA 1,331 VA 40
AC-1, JAN./OFFICE 117 20 A 2 #12
37 1,331 VA 1,331 VA 38
#12 2 20 A AC-1, OFFICE 114
SPARE 20 A 1 -- 35 0 VA 1,830 VA 36
SPARE 20 A 1 -- 33 0 VA 1,830 VA 34
#10 2 30 A AC-2. STORAGE 120
SPARE 20 A 1 -- 31 0 VA 0 VA 32 -- 1 20 A EXISTING
EXISTING 20 A 1 -- 29 0 VA 0 VA 30 -- 1 20 A EXISTING
EXISTING 20 A 1 -- 27 0 VA 0 VA 28 -- 1 20 A EXISTING
SPARE 20 A 1 -- 25 0 VA 0 VA 26 -- 1 20 A EXISTING
EXISTING 20 A 1 -- 23 0 VA 0 VA 24 -- 1 20 A EXISTING
EXISTING 20 A 1 -- 21 0 VA 0 VA 22 -- 1 20 A EXISTING
EXISTING 20 A 1 -- 19 0 VA 0 VA 20 -- 1 20 A EXISTING
EXISTING 20 A 1 -- 17 0 VA 0 VA 18 -- 1 20 A EXISTING
EXISTING 20 A 1 -- 15 0 VA 0 VA 16 -- 1 20 A EXISTING
EXISTING 20 A 1 -- 13 0 VA 0 VA 14 -- 1 20 A EXISTING
EXISTING 20 A 1 -- 11 0 VA 0 VA 12 -- 1 20 A EXISTING
EXISTING 20 A 1 -- 9 0 VA 0 VA 10 -- 1 20 A EXISTING
EXISTING 20 A 1 -- 7 0 VA 0 VA 8 -- 1 20 A EXISTING
EXISTING 20 A 1 -- 5 0 VA 0 VA 6 -- 1 20 A EXISTING
EXISTING 20 A 1 -- 3 0 VA 0 VA 4 -- 1 20 A EXISTING
SPARE 20 A 1 -- 1 0 VA 0 VA 2 -- 1 20 A EXISTING
ITEM AMPS POLE
WIRE
SIZE
CIR.
NO. A B C A B C
CIR.
NO.
WIRE
SIZE POLE AMPS ITEM
BRANCH BREAKERS
SPD
BUSSING: Do Not Use; Use Current Rating ISO GROUND
MOUNTING: Do Not Use; Use Installation Type MAIN DISC. TRIP: MLO 200% NEUTRAL
FED FROM: MAIN DISC. TYPE: MLO DOOR-IN-DOOR
LOCATION: MAINS/BUS AMPS: 225 LUGS: MLO
PANEL: F(E) TYPE: Do Not Use; Use... VOLTS: 208Y/120 PHASE: 3 WIRES: 4
PANELBOARD SCHEDULE
NOTES:
TOTAL EST. DEMAND CURRENT: 31 A
TOTAL CONN. CURRENT: 31 A
TOTAL EST. DEMAND: 11,172 VA
Receptacle - General 180 VA 100.00% 180 VA TOTAL CONN. LOAD: 11,172 VA
Other 11,010 VA 100.00% 11,010 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
AIC RATING: UTILITY AMPS RMS SYSM.
30.6 A 30.6 A 31.9 A AMPS/PHASE 11,172 VA
3670 3670 3833 TOTAL (VA) CONNECTED LOAD TOTAL
MAU SERVICE GFCI, ROOF 20 A 1 #12 41 180 VA 0 VA 42 -- 1 20 A EXISTING
EXISTING 20 A 1 -- 39 0 VA 0 VA 40 -- 1 20 A EXISTING
EXISTING 20 A 1 -- 37 0 VA 0 VA 38 -- 1 20 A EXISTING
EXISTING 20 A 1 -- 35 0 VA 0 VA 36 -- 1 20 A EXISTING
EXISTING 20 A 1 -- 33 0 VA 0 VA 34 -- 1 20 A EXISTING
EXISTING 20 A 1 -- 31 0 VA 0 VA 32 -- 1 20 A EXISTING
29 2,008 VA 0 VA 30 -- 1 20 A EXISTING
27 2,008 VA 0 VA 28 -- 1 20 A EXISTINGRT-1, KITCHEN 124 30 A 3 #10
25 2,008 VA 0 VA 26 -- 1 20 A EXISTING
23 1,662 VA 0 VA 24 -- 1 20 A EXISTING
21 1,662 VA 0 VA 22 -- 1 20 A EXISTINGMAU-1, RECEIVING 118 25 A 3 #10
19 1,662 VA 0 VA 20 -- 1 20 A EXISTING
EXISTING 20 A 1 -- 17 0 VA 0 VA 18 -- 1 20 A EXISTING
EXISTING 20 A 1 -- 15 0 VA 0 VA 16 -- 1 20 A EXISTING
SPARE 20 A 1 -- 13 0 VA 0 VA 14 -- 1 20 A EXISTING
EXISTING 20 A 1 -- 11 0 VA 0 VA 12 -- 1 20 A EXISTING
SPARE 20 A 1 -- 9 0 VA 0 VA 10 -- 1 20 A EXISTING
EXISTING 20 A 1 -- 7 0 VA 0 VA 8 -- 1 20 A EXISTING
SPARE 20 A 1 -- 5 0 VA 0 VA 6 -- 1 20 A EXISTING
EXISTING 20 A 1 -- 3 0 VA 0 VA 4 -- 1 20 A EXISTING
EXISTING 20 A 1 -- 1 0 VA 0 VA 2 -- 1 20 A EXISTING
ITEM AMPS POLE
WIRE
SIZE
CIR.
NO. A B C A B C
CIR.
NO.
WIRE
SIZE POLE AMPS ITEM
BRANCH BREAKERS
SPD
BUSSING: Do Not Use; Use Current Rating ISO GROUND
MOUNTING: Do Not Use; Use Installation Type MAIN DISC. TRIP: MLO 200% NEUTRAL
FED FROM: MAIN DISC. TYPE: MLO DOOR-IN-DOOR
LOCATION: MAINS/BUS AMPS: 225 LUGS: MLO
PANEL: J(E) TYPE: Do Not Use; Use... VOLTS: 208Y/120 PHASE: 3 WIRES: 4
PANELBOARD SCHEDULE
KITCHEN
SERVING
OFFICE
FREEZER
ELEC.
RECEIVING
JAN./OFFICE
LOCKER
TOILET
CAN WASH
MULTI PURPOSE
MULTI PURPOSE
2 3
15 cd
F
T
T
T
T
AIM
STORAGE
KITCHEN
SERVING
OFFICE
FREEZER
ELEC.
RECEIVING
JAN./OFFICE
LOCKER
TOILET
CAN WASH
MULTI PURPOSE
MULTI PURPOSE
2 3
F
F F
T
T
15 cd
F
J
J
J
T
T
AIM
AIM
D4
D1
D2
D3
EXISTING MAU
ON ROOF
EXISTING EXHAUST FAN
(ON ROOF)
D3 EXISTING EXHAUST FAN
(ON ROOF)
D3 EXISTING EXHAUST FAN
(ON ROOF)
D6D6
D6
D6
D6
D6D6
D6 D6
D6
EXISTING FREEZER CONDENSER
(ON ROOF)
J(E)
F(E)
D7
J(E)
F(E) F(E)- 34,36
ACO-2
ALT-1
WP
WP
ON ROOF
J(E)- 19,21,23
MAU-1
F(E)- 37,39
ACO-1
WP
F(E)- 38,40
ACO-1
WP
E2
J(E)- 25,27,29
RT-1
WP
ON ROOF
WP
ON ROOF
AC-1
E1
AC-1
E1
AC-2
(ALT-1)
E1
E2
E2
E2 E2 E2
E2
E2
E2E2
E2
MAU CONTROL
E3
E3 E3
E3
E3
F(E)-42
J(E)-41
EXISTING EXHAUST FAN
(ON ROOF)
EXISTING FREEZER CONDENSER
(ON ROOF)
WP
ON ROOF
EXISTING EXHAUST FAN
(ON ROOF)
EXISTING EXHAUST FAN
(ON ROOF)
DEMARK POINT
E4
E5
F2
F2
HICKS
BRIAN
No. 7709037-2202
G
IN
E E R
ONA
O F
E
SS
I
R
UT
AH
TE OF
S T A
P
L EN
PROJECT
NO:DRAWN BY:
CHK'D BY:
DATE:
T H
IS
P
R
IN
T I
S I
N C
O L
O R
T h is d ra w in g i s t h e c o p y ri g h te d p ro p e rt y o f R e s o lu t G ro u p
U n a u th o ri z e d d u p lic a ti o n p u b lic a ti o n o r d is tr ib u ti o n ic tl y p ro h ib it e d
U s e o f th is d ra w in g i s a t th e u s e r' s o w n r is k a n d
R e s o lu t G ro u p d is c la im s a n y l ia b il it y f o r d a m a g e s o r lo s s e s a ri s in g f ro m i ts u s e
A
BCDEFGHIJKLMN
ABCDEFGHIJKLMN
01/05/2026
250962
/5
/2
:3
:2
A M
A u to d e s k D o c s /2
-J
S D
B lu ff d a le
E S
M A
U R e p la c e m e n t/
J S
D B lu ff d a le E
S M
A U
R e p la c e m e n t_
E L E
C v
.r v t
01/05/2026
BR
ES
FIRST FLOOR
ELECTRICAL
PLAN
E101
B L U
F F
D A
L E
E S
K
IT
C H
E N
H V
A C
S
W
B lu ff d a le U
T
B
LU
F F
D A
LE
E
S K
IT
C
H E
N H
V A
C
KEYNOTES
D1 EXISTING MAU TO BE DEMOLISHED. DIV. 26 IS TO DISCONNECT CONDUIT AND WIRING FROM
UNIT. EXISTING WIRE IS TO BE PULLED BACK TO THE PANEL. PULL EXISTING CONDUIT BACK TO
AN ACCESIBLE CEILING DURING CONSTRUCTION FOR REUSE.
D2 APPROXIMATE LOCATION OF EXISTING FREEZER CONDENSER. FREEZER CONDENSER TO
REMAIN.
D3 APPROXIMATE LOCATION OF EXISTING EXHAUST FAN. EXHAUST FAN TO REMAIN.
D4 DIV. 26 IS TO REMOVE & STORE EXISTING LIGHT FIXTURES AND FIRE ALARM DEVICE FROM
OFFICE 114 CEILING. REWORK ANY CONDUIT AND WIRING IN THE CEILING AS NECESSARY.
LIGHTING CONTROLS ARE TO REMAIN.
D6 DIV. 26 IS TO REMOVE & STORE EXISTING LIGHT FIXTURES AND FIRE ALARM DEVICES FROM
CEILING AS NECESSARY. COORDINATE WITH MECHANICAL CONTRACTOR. REWORK ANY
CONDUIT AND WIRING IN THE CEILING AS NECESSARY.
D7 EXISTING ROOF SERVICE GFCI. DIV. 26 IS TO DISCONNECT CONDUIT AND WIRING FROM GFCI.
EXISTING WIRE IS TO BE PULLED BACK TO THE PANEL. PULL EXISTING CONDUIT BACK TO AN
ACCESIBLE CEILING DURING CONSTRUCTION FOR REUSE.
E1 INDOOR UNIT TO BE POWERED UP BY OUTDOOR CONDENSING UNIT. DIV 26 IS TO COORDINATE
WIRING REQUIREMENTS WITH MECHANICAL PRIOR TO ROUGH IN
E2 EXISTING LIGHT FIXTURES AND CEILING FIRE ALARM DEVICE ARE TO BE REINSTALLED. ENSURE
ALL FIXTURES ARE TIED BACK TO THEIR PREVIOUS DESIGNATED CIRCUITING.
E3 CONNECT NEW MAU TO EXISTING CIRCUIT. EXTEND CONDUIT AS NEEDED. REFER TO PANEL
SCHEDULE FOR NEW WIRE SIZE. CIRCUITING IS FOR REFERENCE ONLY. DIV 26 IS TO VERIFY
BREAKER AVAILIBILITY. RESHUFFLE BREAKERS AS NEEDED TO ALLOW ROOM FOR NEW
BREAKER. ENSURE BREAKER IS COMPATIBLE WITH EXISTING WESTINGHOUSE POWER-R-LINE C
PANELBOARD.
E4 ROUTE NEW DATA LINE BACK TO DEMARK POINT IN ELECTRICAL ROOM 119.
E5 CONNECT NEW ROOF SERVICE GFCI TO EXISTING CIRCUIT. EXTEND CONDUIT AS NEEDED.
REFER TO PANEL SCHEDULE FOR NEW WIRE SIZE. CIRCUITING IS FOR REFERENCE ONLY. DIV 26 IS TO VERIFY BREAKER AVAILIBILITY. RESHUFFLE BREAKERS AS NEEDED TO ALLOW ROOM FOR
NEW BREAKER. ENSURE BREAKER IS COMPATIBLE WITH EXISTING WESTINGHOUSE
POWER-R-LINE C PANELBOARD.
F2 PROVIDE CONTROL MODULE WITH FAN SHUTDOWN RELAY FOR LOCAL CARBON-MONOXIDE
DETECTOR ACTIVATION. TIE TO FIRE ALARM SYSTEM AS REQUIRED
DEMOLITION GENERAL NOTES
1. DIVISION 26 SHALL CONFIRM EXACT LOCATION OF EXISTING AND NEW EQUIPMENT WITH
OWNERS. FIXTURE LOCATIONS ARE DIAGRAMMATICALLY SHOWN ON THE DRAWINGS.
EXISTING ELECTRICAL FIXTURES, DEVICES, EQUIPMENT, CIRCUITING AND/OR CIRCUITING
AND/OR CONDUITS ARE NOT SPECIFIED UNLESS NOTED ON DRAWINGS. FINAL ROUTING OF
THE CONDUITS, CIRCUITING AND CABLING SHALL BE DETERMINED BY THE CONTRACTOR AND
CLOSELY COORDINATED WITH OWNER. ALL EXISTING CONDITIONS MUST BE VERIFIED
WITHOUT EXCEPTION.
2. REFER TO ARCHITECTURAL, STRUCTURAL, MECHANICAL, PLUMBING DEMOLITION DRAWINGS
FOR ADDITIONAL DEMOLITION INFORMATION.
3. DURING DEMOLITION AND NEW CONSTRUCTION, THE CONTINUATION OF BUILDING SYSTEMS
MAY BE NECESSARY, TRACE AND IDENTIFY EXISTING ELECTRICAL SYSTEM (POWER,
LIGHTING, FIRE ALARM AND SECURITY) WIRING IN AREAS PRIOR TO DEMOLITION. ELECTRICAL
CONTRACTOR SHALL DISCONNECT ALL NECESSARY EQUIPMENT TO MAKE IT SAFE FOR
DEMOLITION, WHERE LIVE CIRCUITS OR FEEDERS PASS THROUGH A REMODEL AREA,
CONTRACTOR SHALL MAINTAIN ELECTRIC CONTINUITY TO AND PROTECT BRANCH CIRCUITS
AND/OR FEEDERS PASSING THROUGH. WHERE FEEDERS AND/OR BRANCH CIRCUITS FEED
BOTH LOADS IN A REMODELED AREA AND OUTSIDE OF A REMODELED AREA, CONTRACTOR
SHALL DISCONNECT AND REMOVE PORTIONS OF THE ELECTRICAL BRANCH CIRCUITS AND/OR
FEEDERS WITHIN THE REMODELED AREA AND…