1) CODES AND STANDARDS:
1A) GENERAL DESIGN
- INTERNATIONAL BUILDING CODE 2015
2) SEISMIC LOADS
- SEISMIC DESIGN CATEGORY = A
- RISK CATEGORY = II
- EARTHQUAKE IMPORTANCE FACTOR, le = 1.00
- MAPPED SPECTRAL RESPONSE ACCELERATION, Ss = 5.40 %g
- MAPPED SPECTRAL RESPONSE ACCELERATION, S1 = 2.00 %g
- DESIGN SPECTRAL RESPONSE COEFFICIENT, SDs = 0.057
- DESIGN SPECTRAL RESPONSE COEFFICIENT, SD1 = 0.032
- SOIL SITE CLASS = D
3) GRAVITY LOADS
3A) DEAD LOAD: SELF WEIGHT
3B) LIVE LOAD: 125 PSF AT FLOOR INFILLS (INCLUDING FLOORING)
1) GENERAL:
1A) ENGINEER: REFERENCES ON THE STRUCTURAL DRAWINGS TO ‘ENGINEER’ MEAN THE STRUCTURAL ENGINEER OF RECORD. OTHER ENTITIES ARE SPECIFICALLY NOTED AS “CONTRACTOR’S ENGINEER”, “MECHANICAL ENGINEER”, ETC.
2) EXISTING STRUCTURES:
2A) CONTRACT DOCUMENTS HAVE BEEN PREPARED USING AVAILABLE DRAWINGS AND SITE OBSERVATION
AS PERMITTED BY ACCESS RESTRICTIONS DURING DESIGN.
2B) DURING CONSTRUCTION, THE CONTRACTOR MAY ENCOUNTER EXISTING CONDITIONS WHICH ARE NOT
KNOWN OR ARE AT VARIANCE WITH PROJECT DOCUMENTATION. CONTRACTOR SHALL NOTIFY THE
ENGINEER OF ALL CONDITIONS NOT PER THE CONTRACT DOCUMENTS. EXAMPLES INCLUDE:
- SIZES OR DIMENSIONS OTHER THAN THOSE SHOWN
- DAMAGE OR DETERIORATION TO MATERIALS AND COMPONENTS
- CONDITIONS OF INSTABILITY OR LACK OF SUPPORT
- ITEMS NOTED AS EXISTING ON THE DRAWINGS BUT NOT FOUND IN THE FIELD
2C)CONTRACTOR SHALL FIELD VERIFY ALL EXISTING STRUCTURAL CONDITIONS PRIOR TO SUBMITTING
SHOP DRAWINGS.
2D)CONTRACTOR SHALL MAKE ALLOWANCE FOR THE RESOLUTION OF SUCH DISCOVERIES IN THE
CONSTRUCTION SCHEDULE.
3) USE OF DRAWINGS:
3A) DO NOT SCALE DRAWINGS.
3B) DETAILS ON DRAWINGS TAKE PRECEDENCE OVER GENERAL NOTES AND TYPICAL DETAILS.
3C)DETAILS NOTED TYPICAL APPLY TO ALL SIMILAR CONDITIONS. WHERE NO SPECIFIC DETAILS ARE
SHOWN, CONSTRUCTION SHALL CONFORM TO SIMILAR WORK ELSEWHERE ON THE PROJECT.
3D)WHERE DISCREPANCIES OCCUR BETWEEN PLANS, DETAILS, AND GENERAL NOTES THE MORE
STRINGENT REQUIREMENTS SHALL
4) SUBMITTALS AND SUBSTITUTIONS:
4A) SUBMITTALS:
- IF THE CONTRACTOR REQUESTS A CHANGE FROM THE STRUCTURAL DRAWINGS, IT SHALL BE
APPROVED AND DESIGNED BY MARTIN/MARTIN, INC. PRIOR TO SUBMITTING SHOP DRAWINGS. VARIATION SHALL BE INDICATED ON THE SHOP DRAWINGS. CONTRACTOR SHALL COMPENSATE MARTIN/MARTIN, INC.
FOR MAKING THE CHANGE.
- CONSTRUCTION DOCUMENTS SHALL NOT BE REPRODUCED FOR USE IN SUBMITTALS
- ALL SHOP DRAWINGS SHALL REFERENCE THE STRUCTURAL DRAWING NUMBER AND DETAIL USED TO
PREPARE THE SUBMITTAL
4B) SUBSTITUTIONS: ENGINEER’S APPROVAL SHALL BE SECURED FOR ALL SUBSTITUTIONS
4C)NONCONFORMANCE: NOTIFY ENGINEER OF CONDITIONS NOT CONSTRUCTED PER THE CONTRACT DOCUMENTS PRIOR TO PROCEEDING WITH CORRECTIVE WORK. SUBMIT PROPOSED REPAIR TO THE ENGINEER FOR ACCEPTANCE. CONTRACTOR SHALL COMPENSATE MARTIN/MARTIN, INC. FOR DESIGNING
THE REPAIR.
5) OSHA STANDARDS:
5A) THE STRUCTURE IS DESIGNED TO FUNCTION AS A UNIT UPON COMPLETION. NOTHING SHOWN ON THE STRUCTURAL DRAWINGS SHALL BE CONSTRUED AS ELIMINATING THE NEED FOR THE CONTRACTOR TO
COMPLY WITH ALL OSHA REQUIREMENTS.
6) CONSTRUCTION ENGINEERING:
6A) THE STRUCTURE DEFINED ON THE CONTRACT DOCUMENTS HAS BEEN DESIGNED ONLY FOR LOADS ANTICIPATED ON THE STRUCTURE DURING ITS SERVICE LIFE. PROVIDE ALL REQUIRED ENGINEERING AND OTHER MEASURES TO ACHIEVE THE MEANS, METHODS, AND SEQUENCES OF WORK. SUCH ENGINEERING
MAY INCLUDE, BUT IS NOT LIMITED TO:
- DESIGN OF CONCRETE MIXES
- WELD PROCEDURES
- SURVEYING TO VERIFY CONSTRUCTION TOLERANCES
- EVALUATION OF TEMPORARY CONSTRUCTION LOADS ON STRUCTURE DUE TO EQUIPMENT AND
MATERIALS
- STRUCTURAL ENGINEERING TO RESIST ANY OTHER LOADS NOT IDENTIFIED ON DESIGN DRAWINGS
1) GENERAL:
1A) ALL WORK SHALL CONFORM WITH ACI 301-10, UNLESS NOTED OTHERWISE IN DRAWINGS OR PROJECT
SPECIFICATIONS.
1B) DETAIL BARS IN ACCORDANCE WITH THE DRAWINGS, PROJECT SPECIFICATIONS, AND ACI PUBLICATION
SP-66 (2004): “ACI DETAILING MANUAL”
2) REINFORCING MATERIALS:
2A) ASTM A615 GRADE 60
3) REINFORCING FABRICATION:
3A) SPLICES:
- NO SPLICING OF REINFORCEMENT PERMITTED EXCEPT AS NOTED ON DRAWINGS. MAKE BARS
CONTINUOUS AROUND CORNERS WHERE DETAIL NOT PROVIDED. WHERE PERMITTED, SPLICES MAY BE
MADE BY CONTACT LAPS.
- SEE DETAILS HEREIN FOR LAP LENGTHS.
3B) MISCELLANEOUS REINFORCING REQUIREMENTS:
- PROVIDE ADDITIONAL BARS OR STIRRUPS REQUIRED TO SECURE REINFORCING IN PLACE DURING
CONCRETE PLACEMENT.
- MAKE ALL REINFORCING BAR BENDS IN THE FABRICATOR’S SHOP UNLESS NOTED.
- NO WELDING OF REINFORCING PERMITTED UNLESS NOTED ON DRAWINGS. WHERE PERMITTED,
PERFORM WELDING IN ACCORDANCE WITH AWS D1.4-2011.
4) STRUCTURAL CONCRETE MIX REQUIREMENTS:
4A) 28 DAY COMPRESSIVE STRENGTH, f’c = 4,000 PSI MIN
4B) MAX WATER/CEMENT RATIO = 0.4
4C) NORMAL WEIGHT CONCRETE
4D) MAX AGGREGATE SIZE = 3/4"
5) PLACING REINFORCEMENT:
5A) REINFORCEMENT PROTECTION:
- SEE DETAILS HEREIN FOR COVER REQUIREMENTS
- SEE ACI 117-10 FOR REINFORCEMENT PLACING TOLERANCES
5B) PROVIDE ACCESSORIES NECESSARY TO PROPERLY SUPPORT REINFORCING AND WELDED WIRE REINFORCEMENT AT POSITIONS SHOWN ON PLANS. ALL REINFORCING, DOWELS, BOLTS, AND EMBEDDED PLATES SHALL BE SET AND TIED IN PLACE BEFORE THE CONCRETE IS POURED. “STABBING” INTO
PREVIOUSLY PLACED CONCRETE IS NOT PERMITTED.
1) PERSONNEL REQUIREMENTS:
1A) THE CONTRACTOR SHALL ARRANGE AN ANCHOR MANUFACTURER’S REPRESENTATIVE TO PROVIDE ONSITE INSTALLATION TRAINING FOR ALL OF THEIR ANCHORING PRODUCTS SPECIFIED. SUBMIT DOCUMENTED CONFIRMATION THAT ALL OF THE CONTRACTOR’S PERSONNEL WHO INSTALL ANCHORS
HAVE PASSED THE TRAINING COURSE PRIOR TO THE COMMENCEMENT OF INSTALLING ANCHORS.
2) INSTALLATION REQUIREMENTS:
2A) ALL POST-INSTALLED ANCHORS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S PRINTED
INSTALLATION INSTRUCTIONS AND PER MANUFACTURER'S ON-SITE TRAINING.
2B) ALL ADHESIVE ANCHORS AND ADHESIVE ANCHORED REINFORCEMENT DESIGNS ARE FOR
INSTALLATION IN THE FOLLOWING CONDITIONS, UNLESS NOTED OTHERWISE. WRITTEN APPROVAL MUST
BE RECEIVED FROM ENGINEER PRIOR TO INSTALLATION IN ALTERNATE CONDITIONS.
- DRY CONCRETE, UNLESS NOTED OTHERWISE.
- CONCRETE TEMPERATURE AT TIME OF INSTALLATION THROUGH CURE TIME MUST BE WITHIN THE TEMPERATURE RANGE SPECIFIED IN MANUFACTURER'S PRINTED INSTALLATION INSTRUCTION FOR
ADHESIVE GEL AND CURE TIMES.
- ANCHOR HOLES TO BE HAMMER DRILLED AND CLEANED.
- CONCRETE MUST BE AT LEAST 21 DAYS OLD BEFORE INSTALLATION OF ANCHORS.
- HOLES TO BE CLEANED AND PREPARED IN STRICT ACCORDANCE WITH MANUFACTURER'S PRINTED
INSTALLATION INSTRUCTIONS AND EVALUATION REPORT PRIOR TO ADHESIVE INJECTION.
2C)THE POSITION OF EXISTING REINFORCING BARS IN THE CONCRETE STRUCTURE SHALL BE LOCATED PRIOR TO INSTALLING POST INSTALLED ANCHORS OR REINFORCEMENT. EXISTING REINFORCEMENT SHALL BE LOCATED USING A SCANNER, GPR, X-RAY, CHIPPING OR OTHER MEANS. DO NOT DAMAGE OR
CUT EXISTING REINFORCEMENT.
3) SUBSTITUTION REQUESTS:
3A) SUBSTITUTION REQUESTS FOR ALTERNATE PRODUCTS MUST BE APPROVED IN WRITING BY THE STRUCTURAL ENGINEER PRIOR TO USE. CONTRACTOR SHALL PROVIDE CALCULATIONS AND PRODUCT DATA DEMONSTRATING THAT THE SUBSTITUTED PRODUCT IS IN COMPLIANCE WITH THE RELEVANT BUILDING CODES, LOAD RESISTANCE, INSTALLATION CATEGORY, CREEP APPROVAL, IN-SERVICE
TEMPERATURE AND INSTALLATION TEMPERATURE OF THE SPECIFIED PRODUCT.
CONCRETE SLAB
FLOOR FINISH TO
MATCH EXISTING,
COORDINATE WITH
OWNER
EXISTING
ELEVATED
SLAB
#4 BARS @12"OC
EACH WAY, BOTTOM
MAT IN SHORT
DIRECTION
4" M
IN
EXISTING
EXTERIOR WALL
EXISTING STEEL
FRAMING
EXISTING LEDGER
SEE NOTE 1
APPLY BACKER
ROD AND SILICONE
SEALANT ALONG
FULL PERIMETER
OF INFILL 1/2"
1"
6'-0" ±
C O
V E
R 3/
4"
NOTES:
1. CLEAN EXISTING STEEL AT CONCRETE INFILL AND COAT WITH A RUST INHIBITIVE PRIMER
ROUGHEN
SURFACE TO ±
1/4" AMPLITUDE
AND SLOPE
INWARD 2:1,
TYPICAL, DO
NOT DAMAGE
REINFORCING
FLOOR FINISH TO MATCH
EXISTING, COORDINATE
WITH OWNER
EXISTING WAFFLE SLAB
ELEVATED CONCRETE
SLAB FINISH LEVEL
WITH EXISTING TOP
OF SLAB
#4 BARS @12"ON
CENTER EACH WAY,
LAP 24" MINIMUM
8" M
IN
EXISTING
WAFFLE SLAB
DRILL AND
EPOXY 4" MIN
INTO EXISTING
SLAB WITH HILTI
HIT-RE-500V3
ADHESIVE
C O
V E
R 1"
5'-4" ±
M a rt in
/M ar ti n
In c . c o n s id er s t h a t d e si g n d at a is o n ly i n it s fi n al f o rm o n p lo tt ed d ra w in g s w it h o ri g in a l s ig n a tu re s a n d p ro fe s s io n al c er ti fi ca ti o n b e in g v is ib ly p re se n t o n t h e d ra w in g s.
D at a s u p p li ed v ia c o m p u te r g en e ra te d f o rm a t d o es n o t c o n ta in t h is a p p ro va l o r c e rt if ic at io n . T h e re ce iv e r o f e le c tr o n ic al ly t ra n s m it te d d ra w in g s is r e s p o n s ib le f o r v er if yi n g t h e in fo rm a ti o n c o n ta in ed w it h in t h e e le ct ro n ic d a ta a g ai n s t th e re co rd e d o r a p p ro v ed d o cu m en ts
T h e u se o f el e ct ro ni ca lly t ra ns m itt e d d ra w in gs is c o n si d er e d to b e a t yo ur o w n r is k.
M ar tin /M ar tin
In c.
a ss u m es n o re sp on si b ili ty f o r an y cl a im s or d a m ag e s re su lti n g fr om y o ur u se o f th is in fo rm at io n . E le ct ro n ic in fo rm a tio n is p ro vi d ed f or th e co n ve n ie nc e o f th e r e ci p ie nt o n ly
T h e re ci p ie n t o f t h is f ile a g re e s th at t he in fo rm a tio n m a y n o t b e tr an sf er re d to a ny o th e r p ar ty
M M
J O
B
P
R
IN
C
IP
A L:
D E
S
IG
N E
R S
D
A T
E P
R
IN
T E
D
F
IL
E P
A T
H
E O
R
P R
O
JE
C T
M A
N A
G E
R
DENVER, COLORADO 80209
TELEPHONE: (303) 260-7277
482 S. BROADWAY
architecture
C O
P Y
R
IG
H T
D
E S
IG
N
E D
G E
P
.C
A L L R
IG
H
T S
R E
S E
R V
E D
A
N Y
C O
P Y
IN
G
O R
O T
H E
R R
E P
R O
D U
C T
IO
N
O F
T H
E S
E D
R A
W
IN
G S
W
IT
H O
U T
T H
E P
R
IO
R
W
IT
T
E N
A U
T H
O R
IZ
A
T
IO
N O
F D
E S
IG
N
E D
G E
P
.C
C O
N S
T
IT
U T
E S
A V
IO
L A
T
IO
N O
F C
O P
Y R
IG
H
T L
A W
A N
D W
IL
L B
E S
U B
J E
C T
T O
L E
G A
L A
C T
IO
N
REGISTRATION:
interior design
711 N. CASCADE AVENUE
TELEPHONE: (719) 667-1972
COLORADO SPRINGS, CO 80903
SUITE 100
D E S I G N EDGE
SHEET NO.
SHEET TITLE:
PROJECT NO.
DRAWN BY:
CHECKED BY:
PRINT DATE:
ISSUE DATES:
U.S. General Services Administration
PROPERTY OF THE UNITED STATES
GOVERNMENT.
FOR OFFICIAL USE ONLY.
DO NOT REMOVE THIS NOTICE.
PROPERLY DESTROY DOCUMENTS WHEN NO
LONGER NEEDED.
9/
/2
:5 6:
A
M G
:\P R
O
JE
C T
S \1
8.
.S
.0 1-
2n d
A ve
N or th , F ar go
, N D
G
S A
F lo or In fil l\B
IM
\1
8.
.S
.0 1-
G S
A F lo or
In fil l-S
.r vt
G S
A F
E D
E R
A L B
U
IL
D
IN
G /P
O S
T O
F F
IC
E
F L
O O
R I N
F
IL
L
N D
A V
E N
O R
T H
F A
R G
O N
D
18.0785.S.01
09-14-2018
C H
R
IS
B R
IG
H
T M
A T
T S
C H
N E
ID
E
R E
LI
Z
A B
E T
H J
O N
E S
.0
5.
S .0
E
LI
Z
A B
E T
H J
O N
E S
S0
NOTES AND DETAILS
AC
EJ
DESIGN CRITERIAGENERAL NOTES
CONCRETE NOTES
POST-INSTALLED ANCHOR NOTES
1" = 1'-0"1 FLOOR INFILL
3/4" = 1'-0"2 WAFFLE SLAB INFILL
NO. ISSUE DATE
0 100% FINAL CD'S 09-14-2018
RAMP
DN
RAMP
DN
DN
DNUP
DN
UP
UP
R A M P
DN
DN
DN
D O W N
DN
R A M P
D N
UP
ABCDEFI
S2
S2
LOADING DOCK
M a rt in
/M ar ti n
In c . c o n s id er s t h a t d e si g n d at a is o n ly i n it s fi n al f o rm o n p lo tt ed d ra w in g s w it h o ri g in a l s ig n a tu re s a n d p ro fe s s io n al c er ti fi ca ti o n b e in g v is ib ly p re se n t o n t h e d ra w in g s.
D at a s u p p li ed v ia c o m p u te r g en e ra te d f o rm a t d o es n o t c o n ta in t h is a p p ro va l o r c e rt if ic at io n . T h e re ce iv e r o f e le c tr o n ic al ly t ra n s m it te d d ra w in g s is r e s p o n s ib le f o r v er if yi n g t h e in fo rm a ti o n c o n ta in ed w it h in t h e e le ct ro n ic d a ta a g ai n s t th e re co rd e d o r a p p ro v ed d o cu m en ts
T h e u se o f el e ct ro ni ca lly t ra ns m itt e d d ra w in gs is c o n si d er e d to b e a t yo ur o w n r is k.
M ar tin /M ar tin
In c.
a ss u m es n o re sp on si b ili ty f o r an y cl a im s or d a m ag e s re su lti n g fr om y o ur u se o f th is in fo rm at io n . E le ct ro n ic in fo rm a tio n is p ro vi d ed f or th e co n ve n ie nc e o f th e r e ci p ie nt o n ly
T h e re ci p ie n t o f t h is f ile a g re e s th at t he in fo rm a tio n m a y n o t b e tr an sf er re d to a ny o th e r p ar ty
M M
J O
B
P
R
IN
C
IP
A L:
D E
S
IG
N E
R S
D
A T
E P
R
IN
T E
D
F
IL
E P
A T
H
E O
R
P R
O
JE
C T
M A
N A
G E
R
DENVER, COLORADO 80209
TELEPHONE: (303) 260-7277
482 S. BROADWAY
architecture
C O
P Y
R
IG
H T
D
E S
IG
N
E D
G E
P
.C
A L L R
IG
H
T S
R E
S E
R V
E D
A
N Y
C O
P Y
IN
G
O R
O T
H E
R R
E P
R O
D U
C T
IO
N
O F
T H
E S
E D
R A
W
IN
G S
W
IT
H O
U T
T H
E P
R
IT
T
E N
A U
T H
O R
IZ
A
T
IO
N O
F D
E S
IG
N
E D
G E
P
.C
C O
N S
T
IT
U T
E S
A V
IO
L A
T
IO
N O
F C
O P
Y R
IG
H
T L
A W
A N
D W
IL
L B
E S
U B
J E
C T
T O
L E
G A
L A
C T
IO
N
REGISTRATION:
interior design
711 N. CASCADE AVENUE
TELEPHONE: (719) 667-1972
COLORADO SPRINGS, CO 80903
SUITE 100
D E S I G N EDGE
SHEET NO.
SHEET TITLE:
PROJECT NO.
DRAWN BY:
CHECKED BY:
PRINT DATE:
ISSUE DATES:
U.S. General Services Administration
PROPERTY OF THE UNITED STATES
GOVERNMENT.
FOR OFFICIAL USE ONLY.
DO NOT REMOVE THIS NOTICE.
PROPERLY DESTROY DOCUMENTS WHEN NO
LONGER NEEDED.
9/
/2
:5 6:
A
M G
:\P R
O
JE
C T
S \1
8.
.S
.0 1-
2n d
A ve
N or th , F ar go
, N D
G
S A
F lo or In fil l\B
IM
\1
8.
.S
.0 1-
G S
A F lo or
In fil l-S
.r vt
G S
A F
E D
E R
A L B
U
IL
D
IN
G /P
O S
T O
F F
IC
E
F L
O O
R I N
F
IL
L
N D
A V
E N
O R
T H
F A
R G
O N
D
18.0785.S.01
09-14-2018
C H
R
IS
B R
IG
H
T M
A T
T S
C H
N E
ID
E
R E
LI
Z
A B
E T
H J
O N
E S
.0
5.
S .0
E
LI
Z
A B
E T
H J
O N
E S
S1
1ST FLOOR INFILL PLAN
AC
EJ
NORTH
1/16" = 1'-0"
GROUND FLOOR INFILL PLAN
UP
I
S0
F
S0
S0
M a rt in
/M ar ti n
In c . c o n s id er s t h a t d e si g n d at a is o n ly i n it s fi n al f o rm o n p lo tt ed d ra w in g s w it h o ri g in a l s ig n a tu re s a n d p ro fe s s io n al c er ti fi ca ti o n b e in g v is ib ly p re se n t o n t h e d ra w in g s.
D at a s u p p li ed v ia c o m p u te r g en e ra te d f o rm a t d o es n o t c o n ta in t h is a p p ro va l o r c e rt if ic at io n . T h e re ce iv e r o f e le c tr o n ic al ly t ra n s m it te d d ra w in g s is r e s p o n s ib le f o r v er if yi n g t h e in fo rm a ti o n c o n ta in ed w it h in t h e e le ct ro n ic d a ta a g ai n s t th e re co rd e d o r a p p ro v ed d o cu m en ts
T h e u se o f el e ct ro ni ca lly t ra ns m itt e d d ra w in gs is c o n si d er e d to b e a t yo ur o w n r is k.
M ar tin /M ar tin
In c.
a ss u m es n o re sp on si b ili ty f o r an y cl a im s or d a m ag e s re su lti n g fr om y o ur u se o f th is in fo rm at io n . E le ct ro n ic in fo rm a tio n is p ro vi d ed f or th e co n ve n ie nc e o f th e r e ci p ie nt o n ly
T h e re ci p ie n t o f t h is f ile a g re e s th at t he in fo rm a tio n m a y n o t b e tr an sf er re d to a ny o th e r p ar ty
M M
J O
B
P
R
IN
C
IP
A L:
D E
S
IG
N E
R S
D
A T
E P
R
IN
T E
D
F
IL
E P
A T
H
E O
R
P R
O
JE
C T
M A
N A
G E
R
DENVER, COLORADO 80209
TELEPHONE: (303) 260-7277
482 S. BROADWAY
architecture
C O
P Y
R
IG
H T
D
E S
IG
N
E D
G E
P
.C
A L L R
IG
H
T S
R E
S E
R V
E D
A
N Y
C O
P Y
IN
G
O R
O T
H E
R R
E P
R O
D U
C T
IO
N
O F
T H
E S
E D
R A
W
IN
G S
W
IT
H O
U T
T H
E P
R
IT
T
E N
A U
T H
O R
IZ
A
T
IO
N O
F D
E S
IG
N
E D
G E
P
.C
C O
N S
T
IT
U T
E S
A V
IO
L A
T
IO
N O
F C
O P
Y R
IG
H
T L
A W
A N
D W
IL
L B
E S
U B
J E
C T
T O
L E
G A
L A
C T
IO
N
REGISTRATION:
interior design
711 N. CASCADE AVENUE
TELEPHONE: (719) 667-1972
COLORADO SPRINGS, CO 80903
SUITE 100
D E S I G N EDGE
SHEET NO.
SHEET TITLE:
PROJECT NO.
DRAWN BY:
CHECKED BY:
PRINT DATE:
ISSUE DATES:
U.S. General Services Administration
PROPERTY OF THE UNITED STATES
GOVERNMENT.
FOR OFFICIAL USE ONLY.
DO NOT REMOVE THIS NOTICE.
PROPERLY DESTROY DOCUMENTS WHEN NO
LONGER NEEDED.
9/
/2
:5 6:
A
M G
:\P R
O
JE
C T
S \1
8.
.S
.0 1-
2n d
A ve
N or th , F ar go
, N D
G
S A
F lo or In fil l\B
IM
\1
8.
.S
.0 1-
G S
A F lo or
In fil l-S
.r vt
G S
A F
E D
E R
A L B
U
IL
D
IN
G /P
O S
T O
F F
IC
E
F L
O O
R I N
F
IL
L
N D
A V
E N
O R
T H
F A
R G
O N
D
18.0785.S.01
09-14-2018
C H
R
IS
B R
IG
H
T M
A T
T S
C H
N E
ID
E
R E
LI
Z
A B
E T
H J
O N
E S
.0
5.
S .0
E
LI
Z
A B
E T
H J
O N
E S
S2
PARTIAL PLANS
AC
EJ
1/8" = 1'-0"
GROUND FLOOR INFILL PLAN WEST
1/8" = 1'-0"
GROUND FLOOR INFILL PLAN EAST
NORTH
NORTH
| 18.0785.S.01-GSA Floor Infill-100% CDs 09-14-2018.pdf |
| Sheets |
| S0 - NOTES AND DETAILS |
| S1 - 1ST FLOOR INFILL PLAN |
| S2 - PARTIAL PLANS |