Midland_RFI_(1)_(2).docx

DOCX document 18 KB Posted

Attached to
Chiller Replacement Federal contract opportunity
Solicitation number
47PH1118R0010
Issued by
General Services Administration Public Buildings Service Region 7

About this file

Contractor request for information and Government responses

View the file

Other files for this federal contract opportunity

Other files attached to Chiller Replacement, newest first.
File Type Posted
Site_Visit_Record_.pdf PDF
SOW_Midland_Chillers_-091718_(1).docx DOCX document
Exhibit_A_-_Midland_SOO.docx DOCX document
Exhibit_B_-_DDC_Controls_vers_20170417_(1).pdf PDF
1442__Form_(1).pdf PDF
PBS_PPQ_Att_1.pdf PDF
TX0311.pdf PDF
C301_GC_Reps_&_Certs.pdf PDF
Exhibit_A_-_Midland_SOO_(1).pdf PDF
Exhibit_D_-_GSA_Proj_Haystack_Point_Naming_Conventions_(1).pdf PDF
GSA527-15b_Att_2.pdf PDF
Exhibit_E_-_LED_Fixture_(2).pdf PDF
C101_The_Agreement.docx DOCX document
Exhibit_C_-_Gauge_Setup_(1).pdf PDF
SOW_Midland_Chillers_-_Final_7-26-2017_(1).pdf PDF
Show all 15

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Midland Chiller Replacement

47PH1118R0010

Does the government have as-builts of the facility that they can provide to the contractors? As builts cannot be provided due to SBU requirement.

Please advise as to the make and model of the basis of design chiller?

Arctic Chill, Daiken, Multi Stack & Smardt are just a few manufactures were aware of that manufacture a chiller that meets or exceeds the specifications described in the solicitation.

We are having trouble locating a twin compressor 200 ton water cooled chiller. Our cursory review of multiple chiller manufacturer’s product offerings has shown that only large chillers (1200 tons and up) are equipped with dual compressors.

Arctic Chill, Daiken, Multi Stack & Smardt are just a few manufactures were aware of that manufacture a chiller that meets or exceeds the specifications described in the solicitation.

Can GSA provide contact information or a suggestion for the Niagra Certified Tech’s?

Chris Love from Contech in Lubbock Chris@contech-cti.com, chris.love@gsa.gov 806-379-8010 5710 40th St, Lubbock, TX 7940

Will single compressor chillers be acceptable? No Arctic Chill, Daiken, Multi Stack & Smardt are just a few manufactures were aware of that manufacture a chiller that meets or exceeds the specifications described in the solicitation.

Can CPARS reports be provided in lieu of Past Performance surveys? YES

We are a 40 year old company with a 40 year history of executing federal construction contracts. Furthermore, we are a verified SDVOSB and SBA HubZone small business who is active on multiple MACC contracts. Will we still need to provide a completed GSA Form 527? YES

Please confirm that all crane and rigging work shall be completed on the weekends. The delivery and removal of the chiller(s) shall occur on the weekend to reduce impact to the building’s occupants during crane operation. Any chilled water/condenser water outage required for this project shall be accomplished after hours or on the weekend.

Please advise if the government can post the site sign in sheet? Provided September 17th 2018 in Amendment 1

We have reviewed a few different manufacturer’s offerings and we are having trouble finding a chiller meets the government specs. Please provide the basis of design chiller make and model as well as and provide verification of the BOD chiller’s performance specifications.

Arctic Chill, Daiken, Multi Stack & Smardt are just a few manufactures were aware of that manufacture a chiller that meets or exceeds the specifications described in the solicitation.

Are purchases made for this project by the contractors sales tax exempt? Contractors need to check with the Texas Comptroller as these matters are determined case by case.