Midland_RFI_(1)_(2).docx
DOCX document 18 KB Posted
- Attached to
- Chiller Replacement Federal contract opportunity
- Solicitation number
- 47PH1118R0010
About this file
Contractor request for information and Government responses
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Site_Visit_Record_.pdf | ||
| SOW_Midland_Chillers_-091718_(1).docx | DOCX document | |
| Exhibit_A_-_Midland_SOO.docx | DOCX document | |
| Exhibit_B_-_DDC_Controls_vers_20170417_(1).pdf | ||
| 1442__Form_(1).pdf | ||
| PBS_PPQ_Att_1.pdf | ||
| TX0311.pdf | ||
| C301_GC_Reps_&_Certs.pdf | ||
| Exhibit_A_-_Midland_SOO_(1).pdf | ||
| Exhibit_D_-_GSA_Proj_Haystack_Point_Naming_Conventions_(1).pdf | ||
| GSA527-15b_Att_2.pdf | ||
| Exhibit_E_-_LED_Fixture_(2).pdf | ||
| C101_The_Agreement.docx | DOCX document | |
| Exhibit_C_-_Gauge_Setup_(1).pdf | ||
| SOW_Midland_Chillers_-_Final_7-26-2017_(1).pdf |
Show all 15
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Midland Chiller Replacement
47PH1118R0010
Does the government have as-builts of the facility that they can provide to the contractors? As builts cannot be provided due to SBU requirement.
Please advise as to the make and model of the basis of design chiller?
Arctic Chill, Daiken, Multi Stack & Smardt are just a few manufactures were aware of that manufacture a chiller that meets or exceeds the specifications described in the solicitation.
We are having trouble locating a twin compressor 200 ton water cooled chiller. Our cursory review of multiple chiller manufacturer’s product offerings has shown that only large chillers (1200 tons and up) are equipped with dual compressors.
Arctic Chill, Daiken, Multi Stack & Smardt are just a few manufactures were aware of that manufacture a chiller that meets or exceeds the specifications described in the solicitation.
Can GSA provide contact information or a suggestion for the Niagra Certified Tech’s?
Chris Love from Contech in Lubbock Chris@contech-cti.com, chris.love@gsa.gov 806-379-8010 5710 40th St, Lubbock, TX 7940
Will single compressor chillers be acceptable? No Arctic Chill, Daiken, Multi Stack & Smardt are just a few manufactures were aware of that manufacture a chiller that meets or exceeds the specifications described in the solicitation.
Can CPARS reports be provided in lieu of Past Performance surveys? YES
We are a 40 year old company with a 40 year history of executing federal construction contracts. Furthermore, we are a verified SDVOSB and SBA HubZone small business who is active on multiple MACC contracts. Will we still need to provide a completed GSA Form 527? YES
Please confirm that all crane and rigging work shall be completed on the weekends. The delivery and removal of the chiller(s) shall occur on the weekend to reduce impact to the building’s occupants during crane operation. Any chilled water/condenser water outage required for this project shall be accomplished after hours or on the weekend.
Please advise if the government can post the site sign in sheet? Provided September 17th 2018 in Amendment 1
We have reviewed a few different manufacturer’s offerings and we are having trouble finding a chiller meets the government specs. Please provide the basis of design chiller make and model as well as and provide verification of the BOD chiller’s performance specifications.
Arctic Chill, Daiken, Multi Stack & Smardt are just a few manufactures were aware of that manufacture a chiller that meets or exceeds the specifications described in the solicitation.
Are purchases made for this project by the contractors sales tax exempt? Contractors need to check with the Texas Comptroller as these matters are determined case by case.