FIRE ALARM INSPECTION REPORT
Performed in Accordance with Applicable National Fire Protection Association Standards
May 2017 Inspection
PREPARED FOR
Charles Sapp Sam Nunn Atlanta Federal Ctr
Kherimba 61 Forsyth St
Atlanta, GA 30303
07/05/2017
SimplexGrinnell
FIRE ALARM INSPECTION REPORT
SITE: Sam Nunn Atlanta Federal Ctr
TABLE OF CONTENTS
Test Summary 1
Special Provisions 3
Monitoring/Jurisdictional Agencies 4
Test Results - Control Panel/Central Processing Unit 5
Test Results - Alarm Initiating Devices 12
Test Results - Alarm Indicating Devices 37
Test Results - Control/Auxiliary Devices 49
Inspection Deficiencies Summary 56
Inspection Deficiencies 57
FIRE ALARM INSPECTION REPORT PAGE 1
Charles Sapp Sam Nunn Atlanta Federal Ctr Kherimba 61 Forsyth St Atlanta, GA 30303
Thank you for choosing SimplexGrinnell as the provider of your Fire Alarm Inspection services, which began on May 2, 2017, and were completed on July 5, 2017.
The following devices were found in this Simplex Fire Alarm System:
4903-9146 Audio / Visual's 2094-9001 Fire Phone Jacks 4902-9707 Speakers 2099-9761 Pull Stations 4098-9703 Analog Smoke Detector 4904-9137 Visual Only 2088-9582 Door Holder 4009-9001 Power Extender 4120-8601 Network Universal Transponder
*Note:The Elevator Recall was tested and operated as required .
*Note:Central station received the alarm signal went sent by the inspection team.
Note: During the Audio / Visual Test the following devices were found to be none operational.
Connector Building:
Connector Meeting Room Bathrooms @ Womens Room Visual only failure
Richs Building:
Parking Deck:
The following devices all had visual failures P8 Parking Space 335 P8 Parking Space 1270 P8 Parking Space 1248 P8 North Stair P8 South Elevator Lobby P7 Parking Space 1078 None of the Speakers worked from P5 thru P10 when the A/Vs were Tested.
The conduit and wiring will need to be replaced for the rise of the parking deck. The conduit and wiring is continuously wet due to the location. How muck wiring and conduit is needed is unknown, due to the
FIRE ALARM INSPECTION REPORT PAGE 2
Sam Nunn Atlanta Federal Ctr existing is in the slab of the building and to replace this will require conduit to be installed on the surface of the walls and may require core holes between floors.
High Rise:
24th Floor Corridor near Room 24T15 on the column A/V total failure 21st Floor Most of this floor is not working due to the issue with the 4009. From Around 21T55 to the end of the hallway.
Corridor near Ned Roberts Desk Landmark A/V total failure Freight Elevator Lobby A/V total failure 18th Floor Mens Bathroom A/V total failure
* The following Batteries failed a load test and were replaced by the customer during the inspection:
Tower 22nd Floor 4120 12 volt 35amp 21st Floor 4009 12 volt 7 amp 19th Floor 4009 Top Left 12 volt 7 amp 18th Floor 4009 12 voltt 7 amp 17th Floor 4009 12 volt 7 amp 15th Floor 4009 12 volt 7 amp 14th Floor 4009 12 volt 7 amp 11th Floor 4009 12 volt 7 amp 10th Floor 4009 Top 12 volt 7 amp 9th Floor 4009 Bottom 12 volt 7 amp 8th Floor 4009 Top 12 volt 7 amp 6th Floor 4009 12 volt 7 amp 5th Floor 4009 12 volt 7 amp
FIRE ALARM INSPECTION REPORT PAGE 3
SITE: Sam Nunn Atlanta Federal Ctr
SPECIAL PROVISIONS
Contract Coverage:
FIRE ALARM INSPECTION REPORT PAGE 4
SITE: Sam Nunn Atlanta Federal Ctr
Monitoring Agency:
Authority Having Jurisdiction: City of Atlanta Fire Department
Fire Marshal
Inspection Service: SimplexGrinnell 3980 Dekalb Technology Pk Suite 640 Atlanta, GA 30340 Phone: (678) 896-4090 Fax: (770) 452-7181
License No.:
Service Mgr: Brian Arnold Inspector: Jamey York
FIRE ALARM INSPECTION REPORT PAGE 5
SITE: Sam Nunn Atlanta Federal Ctr
CONTROL PANEL/CENTRAL PROCESSING UNIT
SimplexGrinnell 4004 Serial # Building: High Rise Comp Rm 4T Floor: 04 Area: Computer Room 4T20
Test Performed Result Value Notes
Voltage w/ Charger Passed Voltage w/o Charger Passed Battery % of Charge Passed Battery Age Check Passed Zone Trouble Passed Signal Trouble Passed Type Signal Circuit Passed AC Input Voltage Passed Earth Detection Passed Lamps/LED Test Passed Drill Switch Not Applicable Control Function(s) Passed
FIRE ALARM INSPECTION REPORT PAGE 6
SITE: Sam Nunn Atlanta Federal Ctr
CONTROL PANEL/CENTRAL PROCESSING UNIT
SimplexGrinnell 4004 Serial # Building: High Rise Comp Rm 8T Floor: 08 Area: Computer Room 8T74
Test Performed Result Value Notes
Voltage w/ Charger Passed Voltage w/o Charger Passed Battery % of Charge Passed Battery Age Check Passed Zone Trouble Passed Signal Trouble Passed Type Signal Circuit Passed AC Input Voltage Passed Earth Detection Passed Lamps/LED Test Passed Drill Switch Passed
FIRE ALARM INSPECTION REPORT PAGE 7
SITE: Sam Nunn Atlanta Federal Ctr
CONTROL PANEL/CENTRAL PROCESSING UNIT
SimplexGrinnell 4004 Serial # Building: High Rise Comp Rm 9T Floor: 09 Area: Computer Room 9TS
Test Performed Result Value Notes
Voltage w/ Charger Voltage w/o Charger Battery % of Charge Battery Age Check Zone Trouble Signal Trouble Type Signal Circuit AC Input Voltage Earth Detection Lamps/LED Test Drill Switch Control Function(s)
FIRE ALARM INSPECTION REPORT PAGE 8
SITE: Sam Nunn Atlanta Federal Ctr
CONTROL PANEL/CENTRAL PROCESSING UNIT
SimplexGrinnell 4004 Serial # Building: Mid Rise Comp Rm 5M Floor: 05 Area: Computer Room
Test Performed Result Value Notes
Voltage w/ Charger Not Applicable Voltage w/o Charger Not Applicable Battery % of Charge Not Applicable Battery Age Check Not Applicable Zone Trouble Not Applicable Signal Trouble Not Applicable Type Signal Circuit Not Applicable AC Input Voltage Not Applicable Earth Detection Not Applicable Lamps/LED Test Not Applicable
Control Function(s) Not Applicable Access could not be gained
FIRE ALARM INSPECTION REPORT PAGE 9
SITE: Sam Nunn Atlanta Federal Ctr
CONTROL PANEL/CENTRAL PROCESSING UNIT
SimplexGrinnell 4004 Serial # Building: Mid Rise Comp Rm 6M Floor: 06 Area: Computer Room
Test Performed Result Value Notes
Voltage w/ Charger Passed Voltage w/o Charger Passed Battery % of Charge Passed Battery Age Check Passed Zone Trouble Passed Signal Trouble Passed Type Signal Circuit Passed AC Input Voltage Passed Earth Detection Passed Lamps/LED Test Passed
FIRE ALARM INSPECTION REPORT PAGE 10
SITE: Sam Nunn Atlanta Federal Ctr
CONTROL PANEL/CENTRAL PROCESSING UNIT
SimplexGrinnell 4004 Serial # Building: Mid Rise Comp Rm 6M Floor: 10 Area: Computer Room
Test Performed Result Value Notes
Voltage w/ Charger Passed Voltage w/o Charger Passed Battery % of Charge Passed Battery Age Check Passed Zone Trouble Passed Signal Trouble Passed Type Signal Circuit Passed AC Input Voltage Passed Earth Detection Passed Lamps/LED Test Passed
FIRE ALARM INSPECTION REPORT PAGE 11
SITE: Sam Nunn Atlanta Federal Ctr
CONTROL PANEL/CENTRAL PROCESSING UNIT
SimplexGrinnell 4004 Serial # Building: Richs Building Comp Floor: 06 Area: Computer Room
Test Performed Result Value Notes
Voltage w/ Charger Passed Voltage w/o Charger Passed Battery % of Charge Passed Battery Age Check Passed Zone Trouble Passed Signal Trouble Passed Type Signal Circuit Passed AC Input Voltage Passed Earth Detection Passed Lamps/LED Test Passed
FIRE ALARM INSPECTION REPORT PAGE 12
SITE: Sam Nunn Atlanta Federal Ctr
ALARM INITIATING DEVICES
SUMMARY TEST RESULTS
Dev. Number Number Number Type Description Total Tested Failed Not Tested
ASD Analog Smoke Detector 345 345 0 0 BSD Beam Smoke Detector 1 1 0 0 PSD Photo Smoke Detector 68 38 1 30 PSDA Pull Station-Double Action 54 54 0 0
DETAIL TEST RESULTS
Dev Cust Cust Address/ Service Test Type Building Floor Area Zone Dev# Zone No. Performed Result
PSDA High Rise 02 Stair North 6:M2-085 Tested Passed ASD High Rise 03 AHU Room (F,5) 6:M2-095 Tested Cleaned/
Passed ASD High Rise 03 Electrical Room A (B,5) 6:M2-093 Tested Cleaned/
Passed ASD High Rise 03 Electrical Room B (F,4) thru Mechanical 6:M2-101 Tested Cleaned/
Passed ASD High Rise 03 Electrical Room C 6:M2-123 Tested Cleaned/
Passed ASD High Rise 03 Passenger Elevator Lobby 6:M2-106 Tested Cleaned/
Passed ASD High Rise 03 Passenger Elevator Lobby 6:M2-105 Tested Cleaned/
Passed ASD High Rise 03 Service Elevator Lobby 6:M2-102 Tested Cleaned/
Passed ASD High Rise 03 Stair North 6:M2-089 Tested Cleaned/
Passed PSDA High Rise 03 Stair North 6:M2-090 Tested Passed PSDA High Rise 03 Stair South 6:M2-107 Tested Passed ASD High Rise 03 Stair South 6:M2-109 Tested Cleaned/
Passed ASD High Rise 03 Telephone Room A (C,5) 6:M2-094 Tested Cleaned/
Passed ASD High Rise 03 Telephone Room B (G,5) 6:M2-103 Tested Cleaned/
Passed
FIRE ALARM INSPECTION REPORT PAGE 13
SITE: Sam Nunn Atlanta Federal Ctr
ALARM INITIATING DEVICES
DETAIL TEST RESULTS
Dev Cust Cust Address/ Service Test Type Building Floor Area Zone Dev# Zone No. Performed Result
ASD High Rise 03 Telephone Room C (J,4) On P-8 Parking 6:M2-104 Tested Cleaned/ Passed
ASD High Rise 04 AHU Room (E,5) 3:M1-008 Tested Cleaned/ Passed
ASD High Rise 04 Electrical Room A (B,5) 3:M1-006 Tested Cleaned/ Passed
ASD High Rise 04 Electrical Room B (G,4)thru Mechanical 3:M1-016 Tested Cleaned/ Passed
ASD High Rise 04 Electrical Room C (K,4) 3:M1-024 Tested Cleaned/ Passed
ASD High Rise 04 Passenger Elevator Lobby 3:M1-018 Tested Cleaned/ Passed
ASD High Rise 04 Passenger Elevator Lobby 3:M1-017 Tested Cleaned/ Passed
ASD High Rise 04 Service Elevator Lobby 3:M1-014 Tested Cleaned/ Passed
ASD High Rise 04 Stair North 3:M1-002 Tested Cleaned/ Passed
PSDA High Rise 04 Stair North 3:M1-003 Tested Passed ASD High Rise 04 Stair South 3:M1-020 Tested Cleaned/
Passed PSDA High Rise 04 Stair South 3:M1-021 Tested Passed ASD High Rise 04 Telephone Room A (C,5) 3:M1-007 Tested Cleaned/
Passed ASD High Rise 04 Telephone Room B (G,5) 3:M1-015 Tested Cleaned/
Passed ASD High Rise 04 Telephone Room C (J,4) On P-9 Parking 3:M1-019 Tested Cleaned/
Passed ASD High Rise 05 AHU Room (E,5) 3:M1-036 Tested Cleaned/
Passed ASD High Rise 05 Electrical Room A (B,5) 3:M1-034 Tested Cleaned/
Passed ASD High Rise 05 Electrical Room B (F,4)thru Mechanical 3:M1-037 Tested Cleaned/
Passed ASD High Rise 05 Electrical Room C (K,4) 3:M1-051 Tested Cleaned/
FIRE ALARM INSPECTION REPORT PAGE 14
SITE: Sam Nunn Atlanta Federal Ctr
ALARM INITIATING DEVICES
DETAIL TEST RESULTS
Dev Cust Cust Address/ Service Test Type Building Floor Area Zone Dev# Zone No. Performed Result
ASD High Rise 05 Passenger Elevator Lobby 3:M1-044 Tested Cleaned/ Passed
ASD High Rise 05 Passenger Elevator Lobby 3:M1-045 Tested Cleaned/ Passed
ASD High Rise 05 Service Elevator Lobby 3:M1-042 Tested Cleaned/ Passed
PSDA High Rise 05 Stair North 3:M1-031 Tested Passed ASD High Rise 05 Stair North 3:M1-030 Tested Cleaned/
Passed ASD High Rise 05 Stair South 3:M1-047 Tested Cleaned/
Passed PSDA High Rise 05 Stair South 3:M1-048 Tested Passed ASD High Rise 05 Telephone Room A (C,5) 3:M1-035 Tested Cleaned/
Passed ASD High Rise 05 Telephone Room B (G,5) 3:M1-043 Tested Cleaned/
Passed ASD High Rise 05 Telephone Room C (J,4) On P-10 Parking 3:M1-046 Tested Cleaned/
Passed ASD High Rise 06 AHU Room (E,4) 3:M1-060 Tested Cleaned/
Passed ASD High Rise 06 AHU Room (E,4) 3:M1-059 Tested Cleaned/
Passed ASD High Rise 06 Electrical Room A (B,5) 3:M1-057 Tested Cleaned/
Passed ASD High Rise 06 Electrical Room B (G,4) 3:M1-067 Tested Cleaned/
Passed ASD High Rise 06 Electrical Room C (K,4) 3:M1-071 Tested Cleaned/
Passed ASD High Rise 06 Elevator Machine Room (B,4) 3:M1-103 Tested Cleaned/
Passed ASD High Rise 06 Elevator Machine Room (K,4) 3:M1-099 Tested Cleaned/
Passed ASD High Rise 06 Passenger Elevator Lobby 3:M1-068 Tested Cleaned/
Passed ASD High Rise 06 Passenger Elevator Lobby 3:M1-069 Tested Cleaned/
FIRE ALARM INSPECTION REPORT PAGE 15
SITE: Sam Nunn Atlanta Federal Ctr
ALARM INITIATING DEVICES
DETAIL TEST RESULTS
Dev Cust Cust Address/ Service Test Type Building Floor Area Zone Dev# Zone No. Performed Result
ASD High Rise 06 Service Elevator Lobby 3:M1-065 Tested Cleaned/ Passed
ASD High Rise 06 South Stair 3:M1-072 Tested Cleaned/ Passed
PSDA High Rise 06 Stair North 3:M1-053 Tested Passed ASD High Rise 06 Stair North 3:M1-056 Tested Cleaned/
Passed PSDA High Rise 06 Stair South 3:M1-073 Tested Passed ASD High Rise 06 Telephone Room A (C,5) 3:M1-058 Tested Cleaned/
Passed ASD High Rise 06 Telephone Room B (G,5) 3:M1-066 Tested Cleaned/
Passed ASD High Rise 06 Telephone Room C (J,4) 3:M1-070 Tested Cleaned/
Passed ASD High Rise 07 AHU Room (E,4) 3:M1-083 Tested Cleaned/
Passed ASD High Rise 07 AHU Room (E,4) 3:M1-082 Tested Cleaned/
Passed ASD High Rise 07 Electrical Room A (B,5) 3:M1-080 Tested Cleaned/
Passed ASD High Rise 07 Electrical Room B (G,4) 3:M1-090 Tested Cleaned/
Passed ASD High Rise 07 Electrical Room C (K,4) 3:M1-094 Tested Cleaned/
Passed ASD High Rise 07 Passenger Elevator Lobby 3:M1-092 Tested Cleaned/
Passed ASD High Rise 07 Passenger Elevator Lobby 3:M1-091 Tested Cleaned/
Passed ASD High Rise 07 Service Elevator Lobby 3:M1-088 Tested Cleaned/
Passed ASD High Rise 07 Stair North 3:M1-079 Tested Cleaned/
Passed PSDA High Rise 07 Stair North 3:M1-076 Tested Passed PSDA High Rise 07 Stair South 3:M1-096 Tested Passed ASD High Rise 07 Stair South 3:M1-095 Tested Cleaned/
FIRE ALARM INSPECTION REPORT PAGE 16
SITE: Sam Nunn Atlanta Federal Ctr
ALARM INITIATING DEVICES
DETAIL TEST RESULTS
Dev Cust Cust Address/ Service Test Type Building Floor Area Zone Dev# Zone No. Performed Result
ASD High Rise 07 Telephone Room A (C,5) 3:M1-081 Tested Cleaned/ Passed
ASD High Rise 07 Telephone Room B (G,5) 3:M1-089 Tested Cleaned/ Passed
ASD High Rise 07 Telephone Room C (J,4) 3:M1-093 Tested Cleaned/ Passed
ASD High Rise 08 AHU Room 3:M2-031 Tested Cleaned/ Passed
ASD High Rise 08 AHU Room 3:M2-030 Tested Cleaned/ Passed
ASD High Rise 08 Electrical Room A (B,5) 3:M2-028 Tested Cleaned/ Passed
ASD High Rise 08 Electrical Room B (G,4) 3:M2-038 Tested Cleaned/ Passed
ASD High Rise 08 Electrical Room C (K,4) 3:M2-042 Tested Cleaned/ Passed
ASD High Rise 08 Passenger Elevator Lobby 3:M2-040 Tested Cleaned/ Passed
ASD High Rise 08 Passenger Elevator Lobby 3:M2-039 Tested Cleaned/ Passed
ASD High Rise 08 Service Elevator Lobby 3:M2-036 Tested Cleaned/ Passed
PSDA High Rise 08 Stair North 3:M2-024 Tested Passed ASD High Rise 08 Stair North 3:M2-027 Tested Cleaned/
Passed PSDA High Rise 08 Stair South 3:M2-044 Tested Passed ASD High Rise 08 Stair South 3:M2-043 Tested Cleaned/
Passed ASD High Rise 08 Telephone Room A (C,5) 3:M2-029 Tested Cleaned/
Passed ASD High Rise 08 Telephone Room B (G,5) 3:M2-037 Tested Cleaned/
Passed ASD High Rise 08 Telephone Room C (J,4) 3:M2-041 Tested Cleaned/
Passed ASD High Rise 09 AHU Room 3:M2-007 Tested Cleaned/
FIRE ALARM INSPECTION REPORT PAGE 17
SITE: Sam Nunn Atlanta Federal Ctr
ALARM INITIATING DEVICES
DETAIL TEST RESULTS
Dev Cust Cust Address/ Service Test Type Building Floor Area Zone Dev# Zone No. Performed Result
ASD High Rise 09 AHU Room 3:M2-008 Tested Cleaned/ Passed
ASD High Rise 09 East Corridor (H,5) 3:M2-109 Tested Cleaned/ Passed
ASD High Rise 09 East Corridor (H,5) 3:M2-110 Tested Cleaned/ Passed
ASD High Rise 09 Electrical Room A (B,5) 3:M2-005 Tested Cleaned/ Passed
ASD High Rise 09 Electrical Room B (G,4) 3:M2-015 Tested Cleaned/ Passed
ASD High Rise 09 Electrical Room C (K,4) 3:M2-019 Tested Cleaned/ Passed
ASD High Rise 09 Passenger Elevator Lobby 3:M2-017 Tested Cleaned/ Passed
ASD High Rise 09 Passenger Elevator Lobby 3:M2-016 Tested Cleaned/ Passed
ASD High Rise 09 Service Elevator Lobby 3:M2-013 Tested Cleaned/ Passed
PSDA High Rise 09 Stair North 3:M2-001 Tested Passed ASD High Rise 09 Stair North 3:M2-004 Tested Cleaned/
Passed PSDA High Rise 09 Stair South 3:M2-020 Tested Passed ASD High Rise 09 Stair South 3:M2-023 Tested Cleaned/
Passed ASD High Rise 09 Telephone Room A (C,5) 3:M2-006 Tested Cleaned/
Passed ASD High Rise 09 Telephone Room B (G,5) 3:M2-014 Tested Cleaned/
Passed ASD High Rise 09 Telephone Room C (J,4) 3:M2-018 Tested Cleaned/
Passed ASD High Rise 09 Toilet Exhaust North 3:M2-106 Tested Cleaned/
Passed ASD High Rise 09 West Corridor (D,4) 3:M2-104 Tested Cleaned/
Passed ASD High Rise 09 West Corridor (D,4) 3:M2-105 Tested Cleaned/
FIRE ALARM INSPECTION REPORT PAGE 18
SITE: Sam Nunn Atlanta Federal Ctr
ALARM INITIATING DEVICES
DETAIL TEST RESULTS
Dev Cust Cust Address/ Service Test Type Building Floor Area Zone Dev# Zone No. Performed Result
ASD High Rise 10 AHU Room (E,4) 4:M1-032 Tested Cleaned/ Passed
ASD High Rise 10 AHU Room (E,4) 4:M1-033 Tested Cleaned/ Passed
ASD High Rise 10 Electrical Room A (B,5) 4:M1-028 Tested Cleaned/ Passed
ASD High Rise 10 Electrical Room B (G,4) 4:M1-040 Tested Cleaned/ Passed
ASD High Rise 10 Electrical Room C (K,4) 4:M1-049 Tested Cleaned/ Passed
ASD High Rise 10 LR Elevator Equipment Room (H,5) 4:M1-041 Tested Cleaned/ Passed
ASD High Rise 10 LR Elevator Equipment Room (H,5) 4:M1-042 Tested Cleaned/ Passed
ASD High Rise 10 Passenger Elevator Lobby 4:M1-031 Tested Cleaned/ Passed
ASD High Rise 10 Passenger Elevator Lobby 4:M1-030 Tested Cleaned/ Passed
ASD High Rise 10 Service Elevator Lobby 4:M1-038 Tested Cleaned/ Passed
ASD High Rise 10 Stair North 4:M1-027 Tested Cleaned/ Passed
PSDA High Rise 10 Stair North 4:M1-024 Tested Passed ASD High Rise 10 Stair South 4:M1-045 Tested Cleaned/
Passed PSDA High Rise 10 Stair South 4:M1-046 Tested Passed ASD High Rise 10 Telephone Room A (C,5) 4:M1-029 Tested Cleaned/
Passed ASD High Rise 10 Telephone Room B (G,5) 4:M1-039 Tested Cleaned/
Passed ASD High Rise 10 Telephone Room C (J,4) 4:M1-127 Tested Cleaned/
Passed ASD High Rise 11 AHU Room 4:M1-058 Tested Cleaned/
Passed ASD High Rise 11 AHU Room 4:M1-059 Tested Cleaned/
FIRE ALARM INSPECTION REPORT PAGE 19
SITE: Sam Nunn Atlanta Federal Ctr
ALARM INITIATING DEVICES
DETAIL TEST RESULTS
Dev Cust Cust Address/ Service Test Type Building Floor Area Zone Dev# Zone No. Performed Result
ASD High Rise 11 Electrical Room A (B,5) 4:M1-054 Tested Cleaned/ Passed
ASD High Rise 11 Electrical Room B (G,4) 4:M1-066 Tested Cleaned/ Passed
ASD High Rise 11 Electrical Room C (K,4) 4:M1-072 Tested Cleaned/ Passed
ASD High Rise 11 Passenger Elevator Lobby 4:M1-057 Tested Cleaned/ Passed
ASD High Rise 11 Passenger Elevator Lobby 4:M1-056 Tested Cleaned/ Passed
ASD High Rise 11 Service Elevator Lobby 4:M1-064 Tested Cleaned/ Passed
PSDA High Rise 11 Stair North 4:M1-050 Tested Passed ASD High Rise 11 Stair North 4:M1-053 Tested Cleaned/
Passed PSDA High Rise 11 Stair South 4:M1-068 Tested Passed ASD High Rise 11 Stair South 4:M1-071 Tested Cleaned/
Passed ASD High Rise 11 Telephone Room A (C,5) 4:M1-055 Tested Cleaned/
Passed ASD High Rise 11 Telephone Room B (G,5) 4:M1-065 Tested Cleaned/
Passed ASD High Rise 11 Telephone Room C (H,4) 4:M1-067 Tested Cleaned/
Passed ASD High Rise 12 AHU Room 4:M1-082 Tested Cleaned/
Passed ASD High Rise 12 AHU Room 4:M1-081 Tested Cleaned/
Passed ASD High Rise 12 Electrical Room A (B,5) 4:M1-077 Tested Cleaned/
Passed ASD High Rise 12 Electrical Room B (G,4) 4:M1-089 Tested Cleaned/
Passed ASD High Rise 12 Electrical Room C (K,4) 4:M1-095 Tested Cleaned/
Passed ASD High Rise 12 Passenger Elevator Lobby 4:M1-080 Tested Cleaned/
FIRE ALARM INSPECTION REPORT PAGE 20
SITE: Sam Nunn Atlanta Federal Ctr
ALARM INITIATING DEVICES
DETAIL TEST RESULTS
Dev Cust Cust Address/ Service Test Type Building Floor Area Zone Dev# Zone No. Performed Result
ASD High Rise 12 Passenger Elevator Lobby 4:M1-079 Tested Cleaned/ Passed
ASD High Rise 12 Service Elevator Lobby 4:M1-087 Tested Cleaned/ Passed
PSDA High Rise 12 Stair North 4:M1-073 Tested Passed ASD High Rise 12 Stair North 4:M1-076 Tested Cleaned/
Passed PSDA High Rise 12 Stair South 4:M1-091 Tested Passed ASD High Rise 12 Stair South 4:M1-094 Tested Cleaned/
Passed ASD High Rise 12 Telephone Room A (C,5) 4:M1-078 Tested Cleaned/
Passed ASD High Rise 12 Telephone Room B (G,5) 4:M1-088 Tested Cleaned/
Passed ASD High Rise 12 Telephone Room C (J,4) 4:M1-090 Tested Cleaned/
Passed ASD High Rise 13 AHU Room 4:M1-104 Tested Cleaned/
Passed ASD High Rise 13 AHU Room 4:M1-105 Tested Cleaned/
Passed ASD High Rise 13 Electrical Room A (B,5) 4:M1-100 Tested Cleaned/
Passed ASD High Rise 13 Electrical Room B (G,4) 4:M1-112 Tested Cleaned/
Passed ASD High Rise 13 Electrical Room C (K,4) 4:M1-121 Tested Cleaned/
Passed ASD High Rise 13 Passenger Elevator Lobby 4:M1-103 Tested Cleaned/
Passed ASD High Rise 13 Passenger Elevator Lobby 4:M1-102 Tested Cleaned/
Passed ASD High Rise 13 Service Elevator Lobby 4:M1-110 Tested Cleaned/
Passed ASD High Rise 13 Stair North 4:M1-099 Tested Cleaned/
PSDA High Rise 13 Stair North 4:M1-120 Tested Passed
FIRE ALARM INSPECTION REPORT PAGE 21
SITE: Sam Nunn Atlanta Federal Ctr
ALARM INITIATING DEVICES
DETAIL TEST RESULTS
Dev Cust Cust Address/ Service Test Type Building Floor Area Zone Dev# Zone No. Performed Result
ASD High Rise 13 Stair South 4:M1-117 Tested Cleaned/ Passed
PSDA High Rise 13 Stair South 4:M1-114 Tested Passed ASD High Rise 13 Telephone Room A (C,5) 4:M1-101 Tested Cleaned/
Passed ASD High Rise 13 Telephone Room B (G,5) 4:M1-111 Tested Cleaned/
Passed ASD High Rise 13 Telephone Room C (J,4) 4:M1-113 Tested Cleaned/
Passed ASD High Rise 14 AHU Room 4:M2-009 Tested Cleaned/
Passed ASD High Rise 14 AHU Room 4:M2-010 Tested Cleaned/
Passed ASD High Rise 14 Electrical Room A (B,5) 4:M2-005 Tested Cleaned/
Passed ASD High Rise 14 Electrical Room B (G,4) 4:M2-017 Tested Cleaned/
Passed ASD High Rise 14 Electrical Room C (K,4) 4:M2-023 Tested Cleaned/
Passed ASD High Rise 14 Passenger Elevator Lobby 4:M2-007 Tested Cleaned/
Passed ASD High Rise 14 Passenger Elevator Lobby 4:M2-008 Tested Cleaned/
Passed ASD High Rise 14 Service Elevator Lobby 4:M2-015 Tested Cleaned/
Passed PSDA High Rise 14 Stair North 4:M2-001 Tested Passed ASD High Rise 14 Stair North 4:M2-004 Tested Cleaned/
Passed PSDA High Rise 14 Stair South 4:M2-019 Tested Passed ASD High Rise 14 Stair South 4:M2-022 Tested Cleaned/
Passed ASD High Rise 14 Telephone Room A (C,5) 4:M2-006 Tested Cleaned/
Passed ASD High Rise 14 Telephone Room B (G,5) 4:M2-016 Tested Cleaned/
FIRE ALARM INSPECTION REPORT PAGE 22
SITE: Sam Nunn Atlanta Federal Ctr
ALARM INITIATING DEVICES
DETAIL TEST RESULTS
Dev Cust Cust Address/ Service Test Type Building Floor Area Zone Dev# Zone No. Performed Result
ASD High Rise 14 Telephone Room C (J,4) 14T76 4:M2-018 Tested Cleaned/ Passed
ASD High Rise 15 AHU Room 4:M2-033 Tested Cleaned/ Passed
ASD High Rise 15 AHU Room 4:M2-032 Tested Cleaned/ Passed
ASD High Rise 15 Electrical Room A (B,5) 4:M2-028 Tested Cleaned/ Passed
ASD High Rise 15 Electrical Room B (G,4) 4:M2-040 Tested Cleaned/ Passed
ASD High Rise 15 Electrical Room C (K,4) 4:M2-046 Tested Cleaned/ Passed
ASD High Rise 15 Passenger Elevator Lobby 4:M2-031 Tested Cleaned/ Passed
ASD High Rise 15 Passenger Elevator Lobby 4:M2-030 Tested Cleaned/ Passed
ASD High Rise 15 Service Elevator Lobby 4:M2-038 Tested Cleaned/ Passed
ASD High Rise 15 Stair North 4:M2-027 Tested Cleaned/ Passed
PSDA High Rise 15 Stair North 4:M2-024 Tested Passed PSDA High Rise 15 Stair South 4:M2-042 Tested Passed ASD High Rise 15 Stair South 4:M2-045 Tested Cleaned/
Passed ASD High Rise 15 Telephone Room A (C,5) 4:M2-029 Tested Cleaned/
Passed ASD High Rise 15 Telephone Room B (G,5) 4:M2-039 Tested Cleaned/
Passed ASD High Rise 15 Telephone Room C (J,4) 4:M2-041 Tested Cleaned/
Passed ASD High Rise 16 9-14 Elevator Machine Room 4:M2-054 Tested Cleaned/
Passed ASD High Rise 16 9-14 Elevator Machine Room 4:M2-053 Tested Cleaned/
Passed ASD High Rise 16 AHU Room 4:M2-060 Tested Cleaned/
FIRE ALARM INSPECTION REPORT PAGE 23
SITE: Sam Nunn Atlanta Federal Ctr
ALARM INITIATING DEVICES
DETAIL TEST RESULTS
Dev Cust Cust Address/ Service Test Type Building Floor Area Zone Dev# Zone No. Performed Result
ASD High Rise 16 AHU Room 4:M2-059 Tested Cleaned/ Passed
ASD High Rise 16 Electrical Room A (B,5) 4:M2-051 Tested Cleaned/ Passed
ASD High Rise 16 Electrical Room B (G,4) 4:M2-067 Tested Cleaned/ Passed
ASD High Rise 16 Electrical Room C (K,4) 4:M2-073 Tested Cleaned/ Passed
ASD High Rise 16 Passenger Elevator Lobby 4:M2-058 Tested Cleaned/ Passed
ASD High Rise 16 Passenger Elevator Lobby 4:M2-057 Tested Cleaned/ Passed
ASD High Rise 16 Service Elevator Lobby 4:M2-065 Tested Cleaned/ Passed
PSDA High Rise 16 Stair North 4:M2-047 Tested Passed ASD High Rise 16 Stair North 4:M2-050 Tested Cleaned/
Passed PSDA High Rise 16 Stair South 4:M2-069 Tested Passed ASD High Rise 16 Stair South 4:M2-072 Tested Cleaned/
Passed ASD High Rise 16 Telephone Room A (C,5) 4:M2-052 Tested Cleaned/
Passed ASD High Rise 16 Telephone Room B (G,5) 4:M2-066 Tested Cleaned/
Passed ASD High Rise 16 Telephone Room C (J,4) 4:M2-068 Tested Cleaned/
Passed ASD High Rise 17 AHU Room 4:M2-083 Tested Cleaned/
Passed ASD High Rise 17 AHU Room 4:M2-082 Tested Cleaned/
Passed ASD High Rise 17 Electrical Room A (B,5) 4:M2-078 Tested Cleaned/
Passed ASD High Rise 17 Electrical Room B (G,4) 4:M2-090 Tested Cleaned/
Passed ASD High Rise 17 Electrical Room C (K,4) 4:M2-096 Tested Cleaned/
FIRE ALARM INSPECTION REPORT PAGE 24
SITE: Sam Nunn Atlanta Federal Ctr
ALARM INITIATING DEVICES
DETAIL TEST RESULTS
Dev Cust Cust Address/ Service Test Type Building Floor Area Zone Dev# Zone No. Performed Result
ASD High Rise 17 Passenger Elevator Lobby 4:M2-081 Tested Cleaned/ Passed
ASD High Rise 17 Passenger Elevator Lobby 4:M2-080 Tested Cleaned/ Passed
ASD High Rise 17 Service Elevator Lobby 4:M2-088 Tested Cleaned/ Passed
PSDA High Rise 17 Stair North 4:M2-074 Tested Passed ASD High Rise 17 Stair North 4:M2-077 Tested Cleaned/
Passed PSDA High Rise 17 Stair South 4:M2-092 Tested Passed ASD High Rise 17 Stair South 4:M2-095 Tested Cleaned/
Passed ASD High Rise 17 Telephone Room A (C,5) 4:M2-079 Tested Cleaned/
Passed ASD High Rise 17 Telephone Room B (G,5) 4:M2-089 Tested Cleaned/
Passed ASD High Rise 17 Telephone Room C (J,4) 4:M2-091 Tested Cleaned/
Passed ASD High Rise 18 AHU Room 5:M1-009 Tested Cleaned/
Passed ASD High Rise 18 AHU Room 5:M1-010 Tested Passed ASD High Rise 18 Electrical Room A (B,5) 5:M1-005 Tested Cleaned/
Passed ASD High Rise 18 Electrical Room B (G,4) 5:M1-017 Tested Cleaned/
Passed ASD High Rise 18 Electrical Room C (K,4) 5:M1-023 Tested Cleaned/
Passed ASD High Rise 18 Passenger Elevator Lobby 5:M1-008 Tested Cleaned/
Passed ASD High Rise 18 Passenger Elevator Lobby 5:M1-007 Tested Cleaned/
Passed ASD High Rise 18 Service Elevator Lobby 5:M1-015 Tested Cleaned/
Passed PSDA High Rise 18 Stair North 5:M1-001 Tested Passed ASD High Rise 18 Stair North 5:M1-004 Tested Cleaned/
FIRE ALARM INSPECTION REPORT PAGE 25
SITE: Sam Nunn Atlanta Federal Ctr
ALARM INITIATING DEVICES
DETAIL TEST RESULTS
Dev Cust Cust Address/ Service Test Type Building Floor Area Zone Dev# Zone No. Performed Result
PSDA High Rise 18 Stair South 5:M1-019 Tested Passed ASD High Rise 18 Stair South 5:M1-022 Tested Cleaned/
Passed ASD High Rise 18 Telephone Room A (C,5) 5:M1-006 Tested Cleaned/
Passed ASD High Rise 18 Telephone Room B (G,5) 5:M1-016 Tested Cleaned/
Passed ASD High Rise 18 Telephone Room C (J,4) 5:M1-018 Tested Cleaned/
Passed ASD High Rise 19 AHU Room 5:M1-033 Tested Cleaned/
Passed ASD High Rise 19 AHU Room 5:M1-032 Tested Cleaned/
Passed ASD High Rise 19 Electrical Room A (B,5) 5:M1-028 Tested Cleaned/
Passed ASD High Rise 19 Electrical Room B (G,4) 5:M1-040 Tested Cleaned/
Passed ASD High Rise 19 Electrical Room C (K,4) 5:M1-046 Tested Cleaned/
Passed ASD High Rise 19 Passenger Elevator Lobby 5:M1-031 Tested Cleaned/
Passed ASD High Rise 19 Passenger Elevator Lobby 5:M1-030 Tested Cleaned/
Passed ASD High Rise 19 Service Elevator Lobby 5:M1-038 Tested Cleaned/
Passed PSDA High Rise 19 Stair North 5:M1-024 Tested Passed ASD High Rise 19 Stair North 5:M1-027 Tested Cleaned/
Passed PSDA High Rise 19 Stair South 5:M1-042 Tested Passed ASD High Rise 19 Stair South 5:M1-045 Tested Cleaned/
Passed ASD High Rise 19 Telephone Room A (C,5) 5:M1-029 Tested Cleaned/
Passed ASD High Rise 19 Telephone Room B (G,5) 5:M1-039 Tested Cleaned/
FIRE ALARM INSPECTION REPORT PAGE 26
SITE: Sam Nunn Atlanta Federal Ctr
ALARM INITIATING DEVICES
DETAIL TEST RESULTS
Dev Cust Cust Address/ Service Test Type Building Floor Area Zone Dev# Zone No. Performed Result
ASD High Rise 19 Telephone Room C (J,4) 5:M1-041 Tested Cleaned/ Passed
ASD High Rise 20 AHU Room 5:M1-056 Tested Cleaned/ Passed
ASD High Rise 20 AHU Room 5:M1-055 Tested Cleaned/ Passed
ASD High Rise 20 Electrical Room A (B,5) 5:M1-051 Tested Cleaned/ Passed
ASD High Rise 20 Electrical Room B (G,4) 5:M1-063 Tested Cleaned/ Passed
ASD High Rise 20 Electrical Room C (K,4) 5:M1-071 Tested Cleaned/ Passed
ASD High Rise 20 Passenger Elevator Lobby 5:M1-065 Tested Cleaned/ Passed
ASD High Rise 20 Passenger Elevator Lobby 5:M1-064 Tested Cleaned/ Passed
ASD High Rise 20 Service Elevator Lobby 5:M1-061 Tested Cleaned/ Passed
PSDA High Rise 20 Stair North 5:M1-047 Tested Passed ASD High Rise 20 Stair North 5:M1-050 Tested Cleaned/
Passed PSDA High Rise 20 Stair South 5:M1-067 Tested Passed ASD High Rise 20 Stair South 5:M1-070 Tested Cleaned/
Passed ASD High Rise 20 Telephone Room A (C,5) 5:M1-052 Tested Cleaned/
Passed ASD High Rise 20 Telephone Room B (G,5) 5:M1-062 Tested Cleaned/
Passed ASD High Rise 20 Telephone Room C (J,4) 5:M1-066 Tested Cleaned/
Passed ASD High Rise 21 15-19 Elevator Machine Room 5:M1-079 Tested Cleaned/
Passed ASD High Rise 21 15-19 Elevator Machine Room 5:M1-078 Tested Cleaned/
Passed ASD High Rise 21 AHU Room 5:M1-083 Tested Cleaned/
FIRE ALARM INSPECTION REPORT PAGE 27
SITE: Sam Nunn Atlanta Federal Ctr
ALARM INITIATING DEVICES
DETAIL TEST RESULTS
Dev Cust Cust Address/ Service Test Type Building Floor Area Zone Dev# Zone No. Performed Result
ASD High Rise 21 AHU Room 5:M1-082 Tested Cleaned/ Passed
ASD High Rise 21 Electrical Room A (B,5) 5:M1-076 Tested Cleaned/ Passed
ASD High Rise 21 Electrical Room B (G,4) 5:M1-090 Tested Cleaned/ Passed
ASD High Rise 21 Electrical Room C (K,4) 5:M1-098 Tested Cleaned/ Passed
ASD High Rise 21 Passenger Elevator Lobby 5:M1-092 Tested Cleaned/ Passed
ASD High Rise 21 Passenger Elevator Lobby 5:M1-091 Tested Cleaned/ Passed
ASD High Rise 21 Service Elevator Lobby 5:M1-084 Tested Cleaned/ Passed
PSDA High Rise 21 Stair North 5:M1-072 Tested Passed ASD High Rise 21 Stair North 5:M1-075 Tested Cleaned/
Passed PSDA High Rise 21 Stair South 5:M1-099 Tested Passed ASD High Rise 21 Stair South 5:M1-097 Tested Cleaned/
Passed ASD High Rise 21 Telephone Room A (C,5) 5:M1-077 Tested Cleaned/
Passed ASD High Rise 21 Telephone Room B (G,5) 5:M1-089 Tested Cleaned/
Passed ASD High Rise 21 Telephone Room C (J,4) 5:M1-093 Tested Cleaned/
Passed ASD High Rise 22 AHU Room 5:M2-035 Tested Cleaned/
Passed ASD High Rise 22 AHU Room 5:M2-034 Tested Cleaned/
Passed ASD High Rise 22 Electrical Room A (B,5) 5:M2-032 Tested Cleaned/
Passed ASD High Rise 22 Electrical Room B (G,4) 5:M2-042 Tested Cleaned/
Passed ASD High Rise 22 Electrical Room C (K,4) 5:M2-050 Tested Cleaned/
FIRE ALARM INSPECTION REPORT PAGE 28
SITE: Sam Nunn Atlanta Federal Ctr
ALARM INITIATING DEVICES
DETAIL TEST RESULTS
Dev Cust Cust Address/ Service Test Type Building Floor Area Zone Dev# Zone No. Performed Result
ASD High Rise 22 Passenger Elevator Lobby 5:M2-044 Tested Cleaned/ Passed
ASD High Rise 22 Passenger Elevator Lobby 5:M2-043 Tested Cleaned/ Passed
ASD High Rise 22 Service Elevator Lobby 5:M2-040 Tested Cleaned/ Passed
PSDA High Rise 22 Stair North 5:M2-028 Tested Passed ASD High Rise 22 Stair North 5:M2-031 Tested Cleaned/
Passed PSDA High Rise 22 Stair South 5:M2-046 Tested Passed ASD High Rise 22 Stair South 5:M2-049 Tested Cleaned/
Passed ASD High Rise 22 Telephone Room A (C,5) 5:M2-033 Tested Cleaned/
Passed ASD High Rise 22 Telephone Room B (G,5) 5:M2-041 Tested Cleaned/
Passed ASD High Rise 22 Telephone Room C (J,4) 5:M2-045 Tested Cleaned/
Passed ASD High Rise 23 AHU Room 5:M2-058 Tested Cleaned/
Passed ASD High Rise 23 AHU Room 5:M2-057 Tested Cleaned/
Passed ASD High Rise 23 Electrical Room A (B,5) 5:M2-055 Tested Cleaned/
Passed ASD High Rise 23 Electrical Room B (G,4) 5:M2-065 Tested Cleaned/
Passed ASD High Rise 23 Electrical Room C (K,4) 5:M2-073 Tested Cleaned/
Passed ASD High Rise 23 Passenger Elevator Lobby 5:M2-067 Tested Cleaned/
Passed ASD High Rise 23 Passenger Elevator Lobby 5:M2-066 Tested Cleaned/
Passed ASD High Rise 23 Service Elevator Lobby 5:M2-063 Tested Cleaned/
PSDA High Rise 23 Stair North 5:M2-051 Tested Passed
FIRE ALARM INSPECTION REPORT PAGE 29
SITE: Sam Nunn Atlanta Federal Ctr
ALARM INITIATING DEVICES
DETAIL TEST RESULTS
Dev Cust Cust Address/ Service Test Type Building Floor Area Zone Dev# Zone No. Performed Result
ASD High Rise 23 Stair North 5:M2-054 Tested Cleaned/ Passed
PSDA High Rise 23 Stair South 5:M2-069 Tested Passed ASD High Rise 23 Stair South 5:M2-072 Tested Cleaned/
Passed ASD High Rise 23 Telephone Room A (C,5) 5:M2-056 Tested Cleaned/
Passed ASD High Rise 23 Telephone Room B (G,5) 5:M2-064 Tested Cleaned/
Passed ASD High Rise 23 Telephone Room C (J,4) 5:M2-068 Tested Cleaned/
Passed ASD High Rise 24 AHU Room 5:M2-105 Tested Cleaned/
Passed ASD High Rise 24 AHU Room 5:M2-104 Tested Cleaned/
Passed ASD High Rise 24 Electrical Room A (B,5) 5:M2-102 Tested Cleaned/
Passed ASD High Rise 24 Electrical Room B (G,4) 5:M2-112 Tested Cleaned/
Passed ASD High Rise 24 Electrical Room C (K,4) 5:M2-120 Tested Cleaned/
Passed ASD High Rise 24 Passenger Elevator Lobby 5:M2-114 Tested Cleaned/
Passed ASD High Rise 24 Passenger Elevator Lobby 5:M2-113 Tested Cleaned/
Passed ASD High Rise 24 Service Elevator Lobby 5:M2-110 Tested Cleaned/
Passed ASD High Rise 24 Stair North 5:M2-101 Tested Cleaned/
Passed PSDA High Rise 24 Stair North 5:M2-098 Tested Passed ASD High Rise 24 Stair South 5:M2-119 Tested Cleaned/
Passed PSDA High Rise 24 Stair South 5:M2-116 Tested Passed ASD High Rise 24 Telephone Room A (C,5) 5:M2-103 Tested Cleaned/
FIRE ALARM INSPECTION REPORT PAGE 30
SITE: Sam Nunn Atlanta Federal Ctr
ALARM INITIATING DEVICES
DETAIL TEST RESULTS
Dev Cust Cust Address/ Service Test Type Building Floor Area Zone Dev# Zone No. Performed Result
ASD High Rise 24 Telephone Room B (G,5) 5:M2-111 Tested Cleaned/ Passed
ASD High Rise 24 Telephone Room C (J,4) 5:M2-115 Tested Cleaned/ Passed
BSD High Rise GND Atrium Beam Detector 6:M2-117 Tested Passed ASD High Rise GND Conference Elevator Lobby 6:M2-077 Tested Cleaned/
Passed ASD High Rise GND Conference Elevator Lobby 6:M2-076 Tested Cleaned/
Passed ASD High Rise GND Conference Elevator Lobby 6:M2-075 Tested Cleaned/
Passed ASD High Rise GND Conference Elevator Lobby 6:M2-074 Tested Cleaned/
Passed ASD High Rise GND Connector Conference Duct Chase 7:M1-066 Tested Cleaned/
Passed ASD High Rise GND Electrical Room A (B,5) 6:M2-059 Tested Cleaned/
Passed ASD High Rise GND Electrical Room B 6:M2-115 Tested Cleaned/
Passed ASD High Rise GND Elevator 3-7 Lobby 6:M2-063 Tested Cleaned/
Passed ASD High Rise GND Elevator 3-7 Lobby 6:M2-062 Tested Cleaned/
Passed ASD High Rise GND Elevator 8-12 Lobby 6:M2-064 Tested Cleaned/
Passed ASD High Rise GND Elevator 8-12 Lobby 6:M2-065 Tested Cleaned/
Passed ASD High Rise GND Elevator 15-19 Lobby 6:M2-070 Tested Cleaned/
Passed ASD High Rise GND Elevator 15-19 Lobby 6:M2-069 Tested Cleaned/
Passed ASD High Rise GND Elevator 20-24 Lobby 6:M2-072 Tested Cleaned/
Passed ASD High Rise GND Elevator 20-24 Lobby 6:M2-071 Tested Cleaned/
FIRE ALARM INSPECTION REPORT PAGE 31
SITE: Sam Nunn Atlanta Federal Ctr
ALARM INITIATING DEVICES
DETAIL TEST RESULTS
Dev Cust Cust Address/ Service Test Type Building Floor Area Zone Dev# Zone No. Performed Result
ASD High Rise GND Fire Command Room 6:M2-111 Tested Cleaned/ Passed
ASD High Rise GND Fire Control Room 6:M2-114 Tested Cleaned/ Passed
ASD High Rise GND Kitchen AHU Room 6:M2-035 Tested Cleaned/ Passed
PSDA High Rise GND Kitchen Stair (L,4) 6:M2-083 Tested Passed ASD High Rise GND Kitchen Stair (L,4) 6:M2-084 Tested Cleaned/
Passed ASD High Rise GND Kitchen Storage (L,3) 6:M2-082 Tested Cleaned/
Passed ASD High Rise GND Kitchen Storage (L,3) 6:M2-081 Tested Cleaned/
Passed ASD High Rise GND Kitchen Storage (L,3) 6:M2-080 Tested Cleaned/
Passed PSDA High Rise GND Security Post 6:M1-057 Tested Passed PSDA High Rise GND Stair North 6:M2-054 Tested Passed ASD High Rise GND Stair North 6:M2-057 Tested Cleaned/
Passed PSDA High Rise GND Stair South 6:M2-073 Tested Passed ASD High Rise GND Telephone Room A 6:M2-061 Tested Cleaned/
Passed ASD High Rise GND Telephone Room B (G,5) 6:M2-068 Tested Cleaned/
Passed PSDA High Rise PH Penthouse AHU Room 5:M2-092 Tested Passed ASD High Rise PH Penthouse AHU Room 5:M2-097 Tested Cleaned/
Passed ASD High Rise PH Penthouse AHU Room 5:M2-096 Tested Cleaned/
Passed PSDA High Rise PH Penthouse MCC Room 1 5:M2-089 Tested Passed ASD High Rise PH Penthouse MCC 1 5:M2-090 Tested Cleaned/
Passed ASD High Rise PH Penthouse MCC 2 5:M2-091 Tested Cleaned/
Passed ASD High Rise PH Top of North Stair 5:M2-015 Tested Cleaned/
FIRE ALARM INSPECTION REPORT PAGE 32
SITE: Sam Nunn Atlanta Federal Ctr
ALARM INITIATING DEVICES
DETAIL TEST RESULTS
Dev Cust Cust Address/ Service Test Type Building Floor Area Zone Dev# Zone No. Performed Result
ASD High Rise PH Top of South Stair 5:M2-016 Tested Cleaned/ Passed
PSDA High Rise RF Antenna Room 5:M2-002 Tested Passed PSDA High Rise RF Antenna Room 5:M2-001 Tested Passed ASD High Rise RF Roof Antenna Room 5:M1-006 Tested Cleaned/
Passed ASD High Rise RF Roof Antenna Room 5:M1-005 Tested Cleaned/
Passed ASD High Rise RF Roof Antenna Room 5:M1-004 Tested Cleaned/
Passed ASD High Rise RF Roof Antenna Room 5:M2-003 Tested Cleaned/
Passed ASD High Rise RF Roof Mechanical / Elevator Machine Room 5:M2-076 Tested Cleaned/
Passed ASD High Rise RF Roof Mechanical / Elevator Machine Room 5:M2-075 Tested Cleaned/
Passed ASD High Rise RF Roof Mechanical / Elevator Machine Room 5:M2-074 Tested Cleaned/
Passed PSDA High Rise RF Roof Mechanical Room 5:M2-079 Tested Passed ASD High Rise Shf Elevator Shaft # 14 5:M2-081 Tested Cleaned/
Passed ASD High Rise Shf Elevator Shaft # 6 4:M2-123 Tested Cleaned/
Passed ASD High Rise Shf Elevator Shaft # 7 4:M2-124 Tested Cleaned/
Passed ASD High Rise Shf Elevator Shaft # 8 & 9 5:M1-094 Tested Cleaned/
Passed ASD High Rise Shf High Rise Elevator Shaft # 21 5:M1-095 Tested Cleaned/
Passed ASD High Rise Shf Low Elevator Shaft # 21 4:M1-118 Tested Cleaned/
Passed ASD High Rise Shf Low Elevator Shaft # 23 4:M1-119 Tested Cleaned/
Passed ASD High Rise Shf Low Mid Elevator Shaft # 4 4:M2-098 Tested Cleaned/
FIRE ALARM INSPECTION REPORT PAGE 33
SITE: Sam Nunn Atlanta Federal Ctr
ALARM INITIATING DEVICES
DETAIL TEST RESULTS
Dev Cust Cust Address/ Service Test Type Building Floor Area Zone Dev# Zone No. Performed Result
ASD High Rise Shf Roof Elevator Shaft # 13 5:M2-080 Tested Cleaned/ Passed
ASD High Rise Shf Shaft # 15, 16, 17 5:M2-007 Tested Cleaned/ Passed
ASD High Rise Shf Shaft # 18, 19 5:M2-008 Tested Cleaned/ Passed
PSD High Rise Comp Rm 4T 04 Ceiling 3:M1-009 Tested Cleaned/ Passed
PSD High Rise Comp Rm 4T 04 Ceiling 3:M1-009 Tested Cleaned/ Passed
PSD High Rise Comp Rm 4T 04 Ceiling 3:M1-009 Tested Cleaned/ Passed
PSD High Rise Comp Rm 4T 04 Ceiling 3:M1-009 Tested Cleaned/ Passed
PSD High Rise Comp Rm 4T 04 Ceiling 3:M1-009 Tested Cleaned/ Passed
PSD High Rise Comp Rm 4T 04 Under Floor 3:M1-009 Tested Cleaned/ Passed
PSD High Rise Comp Rm 4T 04 Under Floor 3:M1-009 Tested Cleaned/ Passed
PSD High Rise Comp Rm 4T 04 Under Floor 3:M1-009 Tested Cleaned/ Passed
PSD High Rise Comp Rm 4T 04 Under Floor 3:M1-009 Tested Cleaned/ Passed
PSD High Rise Comp Rm 4T 04 Under Floor 3:M1-009 Tested Cleaned/ Passed
PSD High Rise Comp Rm 8T 08 Ceiling 3:M2-118 Tested Cleaned/ Passed
PSD High Rise Comp Rm 8T 08 Ceiling 3:M2-118 Tested Cleaned/ Passed
PSD High Rise Comp Rm 8T 08 Ceiling 3:M2-118 Tested Cleaned/ Passed
PSD High Rise Comp Rm 8T 08 Ceiling 3:M2-118 Tested Cleaned/ Passed
PSD High Rise Comp Rm 8T 08 Under Floor 3:M2-118 Tested Cleaned/
FIRE ALARM INSPECTION REPORT PAGE 34
SITE: Sam Nunn Atlanta Federal Ctr
ALARM INITIATING DEVICES
DETAIL TEST RESULTS
Dev Cust Cust Address/ Service Test Type Building Floor Area Zone Dev# Zone No. Performed Result
PSD High Rise Comp Rm 8T 08 Under Floor 3:M2-118 Tested Cleaned/ Passed
PSD High Rise Comp Rm 8T 08 Under Floor 3:M2-118 Tested Cleaned/ Passed
PSD High Rise Comp Rm 8T 08 Under Floor @ Fire Alarm Panel 3:M2-118 Tested Failed No alarm when tested
PSD High Rise Comp Rm 9T 09 Main Room Ceiling 3M2-117 Not Tested PSD High Rise Comp Rm 9T 09 Main Room Ceiling 3M2-117 Not Tested PSD High Rise Comp Rm 9T 09 Main Room Ceiling 3M2-117 Not Tested PSD High Rise Comp Rm 9T 09 Main Room Ceiling 3M2-117 Not Tested PSD High Rise Comp Rm 9T 09 Main Room Ceiling 3M2-117 Not Tested PSD High Rise Comp Rm 9T 09 Main Room Under Floor 3M2-117 Not Tested PSD High Rise Comp Rm 9T 09 Main Room Under Floor 3M2-117 Not Tested PSD High Rise Comp Rm 9T 09 Main Room Under Floor 3M2-117 Not Tested PSD High Rise Comp Rm 9T 09 Main Room Under Floor 3M2-117 Not Tested PSD High Rise Comp Rm 9T 09 Main Room Under Floor 3M2-117 Not Tested PSD High Rise Comp Rm 9T 09 Panel Room Ceiling 3M2-117 Not Tested PSD High Rise Comp Rm 9T 09 Panel Room Under Floor 3M2-117 Not Tested PSD High Rise Comp Rm 9T 09 Rear Room Ceiling 3M2-117 Not Tested PSD High Rise Comp Rm 9T 09 Rear Room Ceiling 3M2-117 Not Tested PSD High Rise Comp Rm 9T 09 Rear Room Ceiling 3M2-117 Not Tested PSD High Rise Comp Rm 9T 09 Rear Room Under Floor 3M2-117 Not Tested PSD High Rise Comp Rm 9T 09 Rear Room Under Floor 3M2-117 Not Tested PSD High Rise Comp Rm 9T 09 Rear Room Under Floor 3M2-117 Not Tested PSD High Rise Comp Rm 9T 09 Small Room Ceiling 3M2-117 Not Tested PSD High Rise Comp Rm 9T 09 Small Room Under Floor 3M2-117 Not Tested PSD Mid Rise Comp Rm 5M 05 Ceiling 8:M2-093 Not Tested
Access could not be gained PSD Mid Rise Comp Rm 5M 05 Ceiling 8:M2-093 Not Tested
Access could not be gained PSD Mid Rise Comp Rm 5M 05 Ceiling 8:M2-093 Not Tested
Access could not be gained PSD Mid Rise Comp Rm 5M 05 Ceiling 8:M2-093 Not Tested
Access could not be gained PSD Mid Rise Comp Rm 5M 05 Ceiling 8:M2-093 Not Tested
FIRE ALARM INSPECTION REPORT PAGE 35
SITE: Sam Nunn Atlanta Federal Ctr
ALARM INITIATING DEVICES
DETAIL TEST RESULTS
Dev Cust Cust Address/ Service Test Type Building Floor Area Zone Dev# Zone No. Performed Result
PSD Mid Rise Comp Rm 5M 05 Ceiling 8:M2-093 ...continued...
Access could not be gained
PSD Mid Rise Comp Rm 5M 05 Under Floor 8:M2-010 Not Tested Access could not be gained
PSD Mid Rise Comp Rm 5M 05 Under Floor 8:M2-010 Not Tested Access could not be gained
PSD Mid Rise Comp Rm 5M 05 Under Floor 8:M2-010 Not Tested Access could not be gained
PSD Mid Rise Comp Rm 5M 05 Under Floor 8:M2-010 Not Tested Access could not be gained
PSD Mid Rise Comp Rm 5M 05 Under Floor 8:M2-010 Not Tested Access could not be gained
PSD Mid Rise Comp Rm 6M 06 Ceiling 8:M2-088 Tested Cleaned/ Passed
PSD Mid Rise Comp Rm 6M 06 Ceiling 8:M2-088 Tested Cleaned/ Passed
PSD Mid Rise Comp Rm 6M 06 Ceiling 8:M2-088 Tested Cleaned/ Passed
PSD Mid Rise Comp Rm 6M 06 Ceiling 8:M2-088 Tested Cleaned/ Passed
PSD Mid Rise Comp Rm 6M 06 Under Floor 8:M2-088 Tested Cleaned/ Passed
PSD Mid Rise Comp Rm 6M 06 Under Floor 8:M2-088 Tested Cleaned/ Passed
PSD Mid Rise Comp Rm 6M 06 Under Floor 8:M2-088 Tested Cleaned/ Passed
PSD Mid Rise Comp Rm 6M 06 Under Floor 8:M2-088 Tested Cleaned/ Passed
PSD Mid Rise Comp Rm 6M 10 Ceiling 9:M1-036 Tested Cleaned/ Passed
PSD Mid Rise Comp Rm 6M 10 Ceiling 9:M1-036 Tested Cleaned/ Passed
PSD Mid Rise Comp Rm 6M 10 Ceiling 9:M1-036 Tested Cleaned/ Passed
PSD Mid Rise Comp Rm 6M 10 Ceiling 9:M1-036 Tested Cleaned/
FIRE ALARM INSPECTION REPORT PAGE 36
SITE: Sam Nunn Atlanta Federal Ctr
ALARM INITIATING DEVICES
DETAIL TEST RESULTS
Dev Cust Cust Address/ Service Test Type Building Floor Area Zone Dev# Zone No. Performed Result
PSD Mid Rise Comp Rm 6M 10 Under Floor 9:M1-036 Tested Cleaned/ Passed
PSD Mid Rise Comp Rm 6M 10 Under Floor 9:M1-036 Tested Cleaned/ Passed
PSD Mid Rise Comp Rm 6M 10 Under Floor 9:M1-036 Tested Cleaned/ Passed
PSD Mid Rise Comp Rm 6M 10 Under Floor 9:M1-036 Tested Cleaned/ Passed
PSD Richs Building Comp 06 Ceiling 10:M2-022 Tested Cleaned/ Passed
PSD Richs Building Comp 06 Ceiling 10:M2-022 Tested Cleaned/ Passed
PSD Richs Building Comp 06 Under Floor 10:M2-022 Tested Cleaned/ Passed
PSD Richs Building Comp 06 Under Floor 10:M2-022 Tested Cleaned/
FIRE ALARM INSPECTION REPORT PAGE 37
SITE: Sam Nunn Atlanta Federal Ctr
ALARM INDICATING DEVICES
SUMMARY TEST RESULTS
Dev. Number Number Number Type Description Total Tested Failed Not Tested
A/V Audio/Visual Signal Device 96 93 17 3 ANNC Annunciator 1 1 0 0 SPKR Speaker 73 71 6 2 VSIG Visual Only Signal 201 198 6 3
DETAIL TEST RESULTS
Dev Cust Cust Address/ Service Test Type Building Floor Area Zone Dev# Zone No. Performed Result
A/V Connector 01 Gallery Audio / Visual Devices Tested Passed SPKR Connector 01 Gallery Speakers Tested Passed VSIG Connector 01 Gallery Visual Only Devices Tested Passed A/V Connector 02 Audio / Visual Devices Tested Passed VSIG Connector 02 Ladies Rest Room Tested Passed SPKR Connector 02 Speakers Tested Passed VSIG Connector 02 Visual Only Devices Tested Passed A/V Connector 03 Audio / Visual Devices Tested Passed VSIG Connector 03 Corridor @ Mens Rest Room Tested Passed VSIG Connector 03 Corridor @ Rm 3B50 Tested Passed VSIG Connector 03 Elevator Lobby Tested Passed VSIG Connector 03 In Room 3B10 Tested Passed SPKR Connector 03 Speakers Tested Passed VSIG Connector 03 Visual Only Devices Tested Passed A/V Connector 04 Audio / Visual Devices Tested Passed SPKR Connector 04 Speakers Tested Passed VSIG Connector 04 Visual Device @ Men's Restroom Tested Passed VSIG Connector 04 Visual Only Devices Tested Passed A/V Connector 05 Audio / Visual Devices Tested Passed VSIG Connector 05 Visual Only Devices Tested Passed VSIG Connector 05 Womens Rest Room Tested Passed A/V Connector 06 Audio / Visual Devices Tested Passed SPKR Connector 06 Speakers Tested Passed VSIG Connector 06 Visual Only Devices Tested Passed
FIRE ALARM INSPECTION REPORT PAGE 38
SITE: Sam Nunn Atlanta Federal Ctr
ALARM INDICATING DEVICES
DETAIL TEST RESULTS
Dev Cust Cust Address/ Service Test Type Building Floor Area Zone Dev# Zone No. Performed Result
A/V Connector 07 Audio / Visual Devices Tested Passed SPKR Connector 07 Speakers Tested Passed VSIG Connector 07 Visual Only Devices Tested Passed A/V Connector 08 Audio / Visual Devices Tested Passed VSIG Connector 08 By Elevator Tested Passed VSIG Connector 08 Corridor North @ Telephone Closet 0840 Tested Passed SPKR Connector 08 Speakers Tested Passed VSIG Connector 08 Visual Only Devices Tested Passed A/V Connector CL Audio / Visual Devices Tested Passed A/V Connector CL Corridor @ Post Office Tested Passed A/V Connector CL Kitchen @ Ice Machine Tested Passed VSIG Connector CL Kitchen Exit to Serving Line Tested Passed SPKR Connector CL Speakers Tested Passed VSIG Connector CL Visual Only Devices Tested Passed SPKR Connector P3 Speakers Tested Passed VSIG Connector P3 Visual Only Devices Tested Passed A/V Connector P4 Audio / Visual Devices Tested Passed SPKR Connector P4 Speakers Tested Passed VSIG Connector P4 Visual Only Devices Tested Passed A/V Connector RF Audio / Visual Devices Tested Passed SPKR Connector RF Speakers Tested Passed A/V High Rise 02 Audio / Visual Devices Tested Passed A/V High Rise 02 Corridor @ Conferance Room E Tested Passed SPKR High Rise 02 Speakers Tested Passed VSIG High Rise 02 Visual Only Devices Tested Passed A/V High Rise 03 Audio / Visual Devices Tested Passed VSIG High Rise 03 Columbus Conference Room Tested Passed A/V High Rise 03 Confrence Center Room 3B90 Tested Passed VSIG High Rise 03 Corridor @ 0136 Tested Passed VSIG High Rise 03 Corridor @ 3T14 Tested Passed VSIG High Rise 03 Corridor @ Savannah Conference Room Tested Passed VSIG High Rise 03 File Area @ Tele Room 0303 Tested Passed VSIG High Rise 03 Inside Room 3B90 Tested Passed VSIG High Rise 03 Macon Conference Room Tested Passed VSIG High Rise 03 Savannah Conference Room Tested Passed
FIRE ALARM INSPECTION REPORT PAGE 39
SITE: Sam Nunn Atlanta Federal Ctr
ALARM INDICATING DEVICES
DETAIL TEST RESULTS
Dev Cust Cust Address/ Service Test Type Building Floor Area Zone Dev# Zone No. Performed Result
SPKR High Rise 03 Speakers Tested Passed VSIG High Rise 03 Visual Only Devices Tested Passed A/V High Rise 04 Audio / Visual Devices Tested Passed VSIG High Rise 04 Corridor @ Rest Room 416 Tested Passed SPKR High Rise 04 Speakers Tested Passed VSIG High Rise 04 Visual Only Devices Tested Passed A/V High Rise 05 Audio / Visual Devices Tested Passed VSIG High Rise 05 Corridor @ Womens Restroom 5B95 Tested Passed SPKR High Rise 05 Speakers Tested Passed VSIG High Rise 05 Visual Only Devices Tested Passed A/V High Rise 06 Audio / Visual Devices Tested Passed VSIG High Rise 06 Corridor @ Womens Restroom 0612 Tested Passed VSIG High Rise 06 Men's Restroom Tested Passed VSIG High Rise 06 Room 6T95 SE Corner Tested Passed SPKR High Rise 06 Speakers Tested Passed VSIG High Rise 06 SW Corner Tested Passed VSIG High Rise 06 Visual Only Devices Tested Passed A/V High Rise 07 Audio / Visual Devices Tested Passed VSIG High Rise 07 Reception Suite 7T80 Tested Passed SPKR High Rise 07 Speakers Tested Passed VSIG High Rise 07 Suite 7T80 Tested Passed VSIG High Rise 07 Visual Only Devices Tested Passed VSIG High Rise 07 Women's Restroom Tested Passed VSIG High Rise 08 8T100 Left Corner Tested Passed A/V High Rise 08 Audio / Visual Devices Tested Passed VSIG High Rise 08 In Room 8T30 Tested Passed VSIG High Rise 08 Room 8T10 Tested Passed SPKR High Rise 08 Speakers Tested Passed VSIG High Rise 08 Visual Only Devices Tested Passed VSIG High Rise 08 Visual Only Devices @ 8T100 Tested Passed VSIG High Rise 08 Visual Only Devices @ 8T55 Tested Passed A/V High Rise 09 Audio / Visual Devices Tested Passed VSIG High Rise 09 Corridor @ Mens Restroom 0905 Tested Passed VSIG High Rise 09 Corridor @ Room 9T89 Tested Passed VSIG High Rise 09 Elevator Lobby Tested Passed
FIRE ALARM INSPECTION REPORT PAGE 40
SITE: Sam Nunn Atlanta Federal Ctr
ALARM INDICATING DEVICES
DETAIL TEST RESULTS
Dev Cust Cust Address/ Service Test Type Building Floor Area Zone Dev# Zone No. Performed Result
SPKR High Rise 09 Speakers Tested Passed VSIG High Rise 09 Visual Only Devices Tested Passed VSIG High Rise 10 @ East Recycling Tested Passed A/V High Rise 10 Audio / Visual Devices Tested Passed SPKR…