36E77618R0062-006.pdf
PDF 12 MB Posted
- Attached to
- Research Addition JP, Construction Federal contract opportunity
- Solicitation number
- 36E77618R0062
About this file
36E77618R0062 S02 Attachment 5 523-307 Research Addition JP - Bid Docs - Plans Vol 1- 2 of 2.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36E77619C0005_1.docx | DOCX document | |
| 36E77618R0062-0002000.docx | DOCX document | |
| 36E77618R0062-0001000.docx | DOCX document | |
| 36E77618R0062-012.docx | DOCX document | |
| 36E77618R0062-004.pdf | ||
| 36E77618R0062-009.pdf | ||
| 36E77618R0062-007.pdf | ||
| 36E77618R0062-002.pdf | ||
| 36E77618R0062-008.pdf | ||
| 36E77618R0062-011.docx | DOCX document | |
| 36E77618R0062-001.docx | DOCX document | |
| 36E77618R0062-003.pdf | ||
| 36E77618R0062-005.pdf | ||
| 36E77618R0062-010.pdf | ||
| 36E77618R0062-000.docx | DOCX document |
Show all 15
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1ST Floor 0"
Ground Floor -14' - 0"
2nd Floor 14' - 0"
3rd Floor 28' - 0"
4th FLOOR/ROOF 42' - 0"
B.5C
SUMP PIT
AS407
AS407
LADDER
CORRIDOR
CR-2-01
CORRIDOR
CR-G-02
ES6C6 ES6C8
CORRIDOR
CR-3-01
ELEV.
G-30
CORRIDOR
CR-1-01
CONTINUOUS
WATERPROOFING
AT ELEVATOR PIT
AS407
AS407
AS407
AS407
AS407
AS407
AS407
AS407
AS407
S4S-2
1/ 8"
1ST Floor 0"
Ground Floor -14' - 0"
2nd Floor 14' - 0"
3rd Floor 28' - 0"
4th FLOOR/ROOF 42' - 0"
ABC
STAIR TOWER
ROOF
39' - 6"
R
IS
ER
S
7'
0"
R
IS
ER
S
7'
0"
R
IS
ER
S
7'
0"
R
IS
ER
S
7'
0"
R
IS
ER
S
7'
0"
R
IS
ER
S
7'
0"
AS406
AS406
AS406
AS406
STAIR 1
3S-11
STAIR 1
2S-11
STAIR 1
1S-11
STAIR 1
GS-11
S4F
S4F
S4F
AS406
AS407
3SIM
AS407
SIM
AS407
SIM
1ST Floor 0"
Ground Floor -14' - 0"
2nd Floor 14' - 0"
3rd Floor 28' - 0"
4th FLOOR/ROOF 42' - 0"
2 3
ELEVATOR PIT
-19' - 0"
T.O. ELEV. SHAFT
58' - 6"
ROOF T.O. STEEL
41' - 5 1/2"
ES8C6
ELEV.
G-30
ELEVATOR
CONTROL
ROOM
4-02
PATIENT
TOILET
3-03
PATIENT
TOILET
2-02
PATIENT
TOILET
1-10
PATIENT
TLT
G-01
STAIR 1
3S-11
STAIR 1
2S-11
STAIR 1
1S-11
STAIR 1
GS-11
1.9
AS407
AS407
AS407
AS407
AS407
AS407
AS407
AS407
AS407
AS407
1.8
9' - 6" CLR
9' - 6"
9' - 6"
8' - 9 1/2" CLR
GENERAL SHEET NOTES
VERTICAL CIRCULATION:
1. All handrail and guardrail components shall be able to withstand a horizontal load of 250 pounds at any point.
2. Guardrails shall not allow the passage of a 4-inch sphere between members.
3. All ramp, stair, ladder, alternating tread device, handrail and guardrail components shall comply with the applicable provisions of the latest version(s) IBC, NFPA 101, and the ADA.
49 DARTMOUTH STREET
PORTLAND, ME 04101
207-775-1059 www.pdtarchs.com
ARCHITECTURE
INTERIOR DESIGN
PLANNING
Project Number
Building Number
Drawing NumberLocation
Project Title
Date Checked Drawn
Drawing Title
Approved: Project Director
Dwg:
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
1 2 3 4 5 6 7 8
A
B
C
D
E
VA FORM 08-6231, OCT 1978
on e e ig ht h in ch o ne fo ot on e q ua rte r i nc on e h al f th re e e ig hs th re e q ua rte rs i
6" on e i
6" on e a nd on e h a lf i nc he s f oo t 6"
Denis McLaughlin Telephone: 857-364-5149
1 2 3 4 5 6 7 8
Jamaica Plain, MA
A
B
C
D
E
M.E.P.:
Stantec 482 Payne Road Scarborough, ME 04074 T: (207) 883-3355 F: (207) 883-3376
SPECIFICATIONS:
Lowell Specifications, Inc.
34 Marc Avenue Topsham, ME 04086 T: (207) 406-4001
STRUCTURAL:
Becker Structural Engineers 75 York St Portland, ME 04101 T: (207) 879-1838 F: (207) 879-1822
CIVIL/LANDSCAPE:
Stantec Consulting 141 Portland St.
Boston, MA 02114 T: (617) 523-8103
AE Research Addition 523-307
0%
S
UB
MI
TT
AL
- B
ID
D
OC
UM
EN
TS
3-31-2016
Stair and Elevator Sections
AS403
PNDW
3/16" = 1'-0"1 Elevator Section 3/16" = 1'-0"3 Stair 1 Longitudinal Section
3/16" = 1'-0"2 Stair 1 and Elevator Cross Section
UP
UP
UP DN DN
AS203
AS404
AS404
U P
T
R
EA
D S
1"
9'
2"
4' - 4" 10" 4' - 4" 0"
/4
RETURN RAIL @ BASE
LEVEL BACK TO NOSING
EL. -7' - 7"
EL. -14' - 0"
CORRIDOR
CR-G-27
ELEC.
CLOSET
G-23
PLAN VIEW CUT PLANE IS
ADJUSTED TO SHOW
INTERMEDIATE LANDING
AND DOOR
STAIR 2
GS-22
CLR
9' - 6"
AS508
EXPANSION JOINT
TO
I N
SI
D
E F O
S
TR
I N G
ER
1'
5/ 8"
IN
SI
D E
FO
S
TR
IN
G
ER
ST
R
IN
G
ER
1/
2" F
O C
-W
AL
L
TO
6'
AS404
AS404
AS306
T
R
EA
D S
1"
" U
P
EL. 14' - 0"
EL. 7' - 0"
CORRIDOR
CR-2-10
ELEC.
ROOM
2-17
AS305
CLR
9' - 6"
AS508
45.00°
6'
1"
4' - 4"4' - 4"
AS404
AS404
AS306
T
R
EA
D S
1"
" D
N ELEC.
ROOM
3-18
CORRIDOR
CR-3-16
EL. 28' - 0"
EL. 21' - 0"
AS305
CLR
9' - 6 5/8"
AS508
45.00°
6'
1"
4' - 4"4' - 4"
1ST Floor 0"
E-6E-6.8
Ground Floor -14' - 0"
2nd Floor 14' - 0"
3rd Floor 28' - 0"
4th FLOOR/ROOF 42' - 0"
AS404
EFG
STAIR TOWER
ROOF
39' - 6"
R
IS
ER
S
7'
0"
R
IS
ER
S
7'
0"
R
IS
ER
S
7'
0"
R
IS
ER
S
7'
0"
AS406
AS406
AS406
AS406
EL. 21' - 0"
EL. 7' - 0"
AS407
SIM
AS407
SIM
AS407
SIM
AS406
1ST Floor 0"
Ground Floor -14' - 0"
2nd Floor 14' - 0"
3rd Floor 28' - 0"
4th FLOOR/ROOF 42' - 0"
AS404
3 1.8
AS407
3 OH
AS407
3 OH
AS407
3 OH
AS407
SIM
AS407
SIM
AS407
SIM
9' - 6" CLR
AS404
AS404
AS306
AS305
DASHED LINES INDICATE
LANDING ABOVE
ELEC.
CLOSET
1-30
CORRIDOR
CR-1-23
AS508
EL. 7' - 0"
T
R
EA
D S
1"
/4 " U
P
4' - 4" 10" 4' - 4"
D O
W N
T
R
EA
D S
AT
1"
CLR
9' - 6"
/4
UP DN
9' - 6" CLR
AS407
6'
1" 5'
1"
49 DARTMOUTH STREET
PORTLAND, ME 04101
207-775-1059 www.pdtarchs.com
ARCHITECTURE
INTERIOR DESIGN
PLANNING
Project Number
Building Number
Drawing NumberLocation
Project Title
Date Checked Drawn
Drawing Title
Approved: Project Director
Dwg:
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
1 2 3 4 5 6 7 8
A
B
C
D
E
VA FORM 08-6231, OCT 1978
on e e ig on e q ua rte r i on e h al f th re e e ig th re e q ua rte rs i
6" on e i
6" on e h a lf i nc f oo t 6"
Denis McLaughlin Telephone: 857-364-5149
1 2 3 4 5 6 7 8
Jamaica Plain, MA
A
B
C
D
E
M.E.P.:
Stantec 482 Payne Road Scarborough, ME 04074 T: (207) 883-3355 F: (207) 883-3376
SPECIFICATIONS:
Lowell Specifications, Inc.
34 Marc Avenue Topsham, ME 04086 T: (207) 406-4001
STRUCTURAL:
Becker Structural Engineers 75 York St Portland, ME 04101 T: (207) 879-1838 F: (207) 879-1822
CIVIL/LANDSCAPE:
Stantec Consulting 141 Portland St.
Boston, MA 02114 T: (617) 523-8103
AE Research Addition 523-307
0%
S
UB
MI
TT
AL
- B
ID
D
OC
UM
EN
TS
3-31-2016
Stair Plans & Sections
AS404
PNDW
1/4" = 1'-0"6 Stair 2 Plan - Ground Floor
1/4" = 1'-0"4 Stair 2 Plan - 2nd Floor 1/4" = 1'-0"3 Stair 2 Plan - 3rd Floor
1/4" = 1'-0"2 Stair 2 Longitudinal Section 1/4" = 1'-0"1 Stair 2 Cross Section
1/4" = 1'-0"5 Stair 2 Plan - 1st Floor
E-5.6
3.3 4
D.6
ST
AI
R O
PE
N
IN
G
4'
0" C
LR
10' - 10" FO SHAFT LINER
RETURN HANDRAIL
AROUND CORNER,
SAME BOTH SIDES
1'
1/
4" F
O S
H
AF
T
LI
N
ER
7'
1/
2" C
LR
7' - 7 3/8" CLR
1' - 1"
HOLD GWB COL
WRAP TIGHT TO
FIRE-PROOFING8"
1'
0"
11"
4'
0" C
LR3
AS405
AS405
AS405
5 TREADS @ 11"
MECHANICAL SHAFT
ALIGN GWB WITH
FURRING WALL ON
OPPOSITE SIDE OF STAIR
Existing 2nd Floor 12' - 6"
2nd Floor 14' - 0"
3.3
EQ
. R
IS
ER
S
1'
6"
AS405
1' - 1"
AS405
FIRESTOP SYSTEM
CLOSING SHAFT
WALL TO UNDERSIDE
OF DECK, TYP
STL PIPE HANDRAIL
2 HR FLOOR ASSEMBLY -
NEW CONNECTOR STAIR
LANDING AT EXISTING 2ND
FLOOR LEVEL
2HR FLOOR ASSEMBLY
LIGHT WT. CONC. FILL OVER
METAL STAIR PAN
2HR RATED 4" C-H STUD
SHAFT WALL ASSEMBLY
BETWEEN SLABS AT STAIR 4
NOTE: THIS DETAIL APPLIES TO
FLOOR 3 STAIR 4 AT THIS SAME
LOCATION, EXCEPT THERE ARE
6 EQ RISERS TOTALING 3'-0"
BETWEEN SLABS
11"
1' - 0"AF FLOOR 3 (STAIR 4)
THE LANDING IS DOWN
3' AND BEARS ON A
LOWER STEEL BEAM.
E-5.6
3.3 4
D.6
AS405
AS405
AS405
10' - 10" FO SHAFT LINER
4'
0" C
LR
7' - 7 3/8"
7'
1/
2" C
LR
1'
1/
4" F
O S
H
AF
T
LI
N
ER
8"
1'
0"
11"
1' - 1"
RETURN HANDRAIL
AROUND CORNER,
SAME BOTH SIDES
HOLD GWB COL
WRAP TIGHT TO
FIRE-PROOFING
2 TREADS @ 11"
ST
AI
R O
PE
N
IN
G
4'
0" C
LR
MECHANICAL SHAFT
ALIGN GWB WITH
FURRING WALL ON
OPPOSITE SIDE OF STAIR
Existing 2nd Floor 12' - 6"
2nd Floor 14' - 0"
D.6
2HR RATED SHAFT
WALL ASSEMBLY WITH
DEFLECTION TRACK
2HR RATED HORIZONTAL
SHAFT WALL ASSEMBLY
2 HR FLOOR ASSEMBLY -
NEW CONNECTOR STAIR
LANDING AT EXISTING 2ND
FLOOR LEVEL
" M
IN
" M
AX
H
AN
D
R
AI
L H
G T
NEW STAIR, STRINGER, AND
HANDRAIL ASSEMBLY
EXISTING WALL
BLOCKING AS REQ FOR
HANDRAIL INSTALLATION
MECHANICAL
SHAFT
NOTE: THIS DETAIL APPLIES TO
FLOOR 3 STAIR 4 AT THIS SAME
LOCATION, EXCEPT THERE IS NO
HORIZONTAL SHAFT WALL AND
THE VERTICAL SHAFT WALL/DUCT
CHASE ENCLOSURE CONTINUES
BELOW SLAB
FURRING CHANNEL ON
BEAM FOR SHAFT WALL
TRACK ANCHORAGE
5 1/2" 1' - 1"
2 HR FLOOR ASSEMBLY
Existing 2nd Floor 12' - 6"
2nd Floor 14' - 0"
D.6
LIGHT WT. CONC. FILL OVER
METAL STAIR PAN
STEEL PIPE HAND RAIL 1 1/4"
MIN TO 2" MAX O.D.
PROVIDE SHIM AS REQ FOR
GWB ATTACHMENT
FIRE SEALANT BETWEEN
GWB AND SLAB EDGE
FURRING WALL PER PLAN
5 1/2"4' - 8 1/2"
4' - 8"
ALIGN GWB
2HR RATED SHAFT WALL
ASSEMBLY BETWEEN SLABS
2 HR FLOOR ASSEMBLY - NEW
CONNECTOR STAIR LANDING AT
EXISTING 2ND FLOOR LEVEL
NEW STAIR, STRINGER, AND
HANDRAIL ASSEMBLY
2HR FLOOR ASSEMBLY
WALL PER PLAN
PROVIDE INTERMEDIATE
HANDRAIL SUPPORT AND
BLOCKING AS REQ
NOTE: THIS DETAIL APPLIES TO FLOOR 3 STAIR 4 AT
THIS SAME LOCATION, EXCEPT THERE ARE 6 EQ
RISERS TOTALING 3'-0" BETWEEN SLABS - ADJUST
HEIGHT OF WALLS BETWEEN SLABS ACCORDINGLY
FIRESTOP SYSTEM
CLOSING SHAFT WALL TO
UNDERSIDE OF DECK, TYP
2HR RATED SHAFT
WALL ASSEMBLY WITH
DEFLECTION TRACK
AF FLOOR 3 (STAIR 4) THE LANDING IS
DOWN 3' AND BEARS ON A LOWER STEEL
BEAM SIMILAR TO OPPOSITE SIDE OF THIS
DETAIL. AT STAIR 4 THIS INFILL FURRING
WALL IS TO BE A 2 HR RATED SHAFT WALL
ASSEMBLY TO MATCH THAT SHOWN AT
OPPOSITE SIDE OF THIS DETAIL
FURRING CHANNEL ON
BEAM FOR SHAFT WALL
TRACK ANCHORAGE
49 DARTMOUTH STREET
PORTLAND, ME 04101
207-775-1059 www.pdtarchs.com
ARCHITECTURE
INTERIOR DESIGN
PLANNING
Project Number
Building Number
Drawing NumberLocation
Project Title
Date Checked Drawn
Drawing Title
Approved: Project Director
Dwg:
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
1 2 3 4 5 6 7 8
A
B
C
D
E
VA FORM 08-6231, OCT 1978
on e e ig on e q ua rte r i on e h al f th re e e ig th re e q ua rte rs i
6" on e i
6" on e h a lf i nc f oo t 6"
Denis McLaughlin Telephone: 857-364-5149
1 2 3 4 5 6 7 8
Jamaica Plain, MA
A
B
C
D
E
M.E.P.:
Stantec 482 Payne Road Scarborough, ME 04074 T: (207) 883-3355 F: (207) 883-3376
SPECIFICATIONS:
Lowell Specifications, Inc.
34 Marc Avenue Topsham, ME 04086 T: (207) 406-4001
STRUCTURAL:
Becker Structural Engineers 75 York St Portland, ME 04101 T: (207) 879-1838 F: (207) 879-1822
CIVIL/LANDSCAPE:
Stantec Consulting 141 Portland St.
Boston, MA 02114 T: (617) 523-8103
AE Research Addition 523-307
0%
S
UB
MI
TT
AL
- B
ID
D
OC
UM
EN
TS
3-31-2016
Stair and Mech Shaft Plans and Details
AS405
PNDW
1/4" = 1'-0"2 Stair 4 - Mechanical Shaft
1 1/2" = 1'-0"3 Stair 3 Section (Stair 4 Similar)
1/4" = 1'-0"1 Stair 3 - Mechanical Shaft
1 1/2" = 1'-0"5 Stair 3 Cross Section at Landing (Stair 4 Similar) 1 1/2" = 1'-0"4 Stair 3 Cross Section (Stair 4 Similar)
" M
IN
. T
O
8" M
AX
G U
AR
D
R
AI
L
" T O
T .O
VERTICAL TRANSITION
@ CONTINUOUS
HANDRAIL RETURN
STEEL STRINGER BEYOND
GUARD RAIL BEYOND
GUARD RAIL BEYOND
STEEL CHANNEL @ LANDING
BY STAIR FABRICATOR
AS406
G U
AR
D
R
AI
L
" T O
T .O
" M
IN
T
O
8" M
AX
AS406
3/4" SQUARE SOLID
STEEL PICKETS -
4"O.C. MAX
1 1/2" O.D. STEEL
GUARDRAIL
STEEL HANDRAIL TO
MATCH WALL
MOUNTED HANDRAILS
3 1/4"
STEEL STRINGER BY
STAIR FABRICATOR
STAIR BEYOND
1 1/2" O.D. STEEL
GUARDRAIL -
BOTTOM RAIL
TYP.
4" O.C.
1 1/2" O.D. POST
" M
IN
. T
O
8" M
AX
EXTEND RAIL 1 TREAD
@ END OF RUN TYP.
STEEL STRINGER BY STAIR
FABRICATOR
LIGHT WT. CONC. FILL OVER
METAL STAIR PAN
11"
LIGHT WT. CONC. FILL OVER
MTL STAIR LANDING BY STAIR
FABRICATOR
HANDRAIL BRACKET BY HANDRAIL
FABRICATOR
RETURN NON-CONTINUOUS
HANDRAILS AT END
B
1ST Floor 0"
@ TOP OF RUN - TYP.
1' - 0"
" M
IN
. T
O
8" M
AX
2" M
AX
O
.D
1/
4" M
IN
T
O
EXTEND RAIL @ TOP OF
RUN TYP.
TY
P.
A
LL
7" M
AX
STEEL STRINGER BY STAIR
FABRICATOR
1"
LIGHT WT. CONC. FILL OVER
METAL STAIR PAN
COMPOSITE CONC.
DECK SEE STRUCT.
RETURN NON-CONTINUOUS
HANDRAILS AT END
HANDRAIL BRACKET BY
HANDRAIL FABRICATOR
Z-GIRT FURRING FOR FURRING
WALL ATTACHMENT,
ENCAPSULATE IN FIRE-PROOFING,
WITH BOTTOM FLANGE EXPOSED
SPRAY APPLIED FIRE-PROOFING
FILL FLUTE WITH SPRAY
APPLIED FIRE-PROOFING
FURRING AND LGMG AS REQ TO CARRY
FINISH TO BOTTOM OF STAIR PAN
GUARDRAIL WELDED TO
STRINGER
3/4" SQUARE SOLID STEEL
PICKETS
LIGHT WT. CONC. FILL OVER
METAL STAIR PAN
RISERS BEYOND
STEEL PIPE HAND RAIL 1
1/4" MIN TO 2" MAX O.D.
1 1/2" O.D. STEEL GUARDRAIL
1 1/2" O.D. STEEL GUARDRAIL -
BOTTOM RAIL
SEALANT
SEE EXTERIOR DETAILS
FOR FOUNDATION
COMPONENTS
SILL SEAL BELOW
CFMF, TYP
WALL AS SCHEDULED
1' - 0"
SELF-ADHERING BUTYL
FLASHING, EXTEND 4" UP
WALL
BLOCKING AS REQ TO
SUPPORT GWB, SEPARATE
FROM FND WITH MEMBRANE
STRINGER SUPPORT AS
REQ BY STAIR MFG
ALIGN STRINGER WITH FACE
OF RATED STAIR ENCLOSURE
LANDING AND STRINGER
CHANNEL BY STAIR MFG
1/
2"
GRADE PER CIVIL DWGS
1/
2"
CLEAR
2 1/4" MIN.
INTO STAIR
4 1/2" MAX PROJECTION
2" O.D. MAX
1 1/4" MIN TO
WALL AS SCHEDULED
SEE PLANS
STEEL PIPE HAND RAIL
RETURN AT ENDS OF NON-
CONTINUOUS HANDRAILS
PROVIDE BLOCKING OR
STEEL BACKING STRIPS
FOR HAND RAIL BRACKETS
4"
49 DARTMOUTH STREET
PORTLAND, ME 04101
207-775-1059 www.pdtarchs.com
ARCHITECTURE
INTERIOR DESIGN
PLANNING
Project Number
Building Number
Drawing NumberLocation
Project Title
Date Checked Drawn
Drawing Title
Approved: Project Director
Dwg:
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
1 2 3 4 5 6 7 8
A
B
C
D
E
VA FORM 08-6231, OCT 1978
on e e ig on e q ua rte r i on e h al f th re e e ig th re e q ua rte rs i
6" on e i
6" on e h a lf i nc f oo t 6"
Denis McLaughlin Telephone: 857-364-5149
1 2 3 4 5 6 7 8
Jamaica Plain, MA
A
B
C
D
E
M.E.P.:
Stantec 482 Payne Road Scarborough, ME 04074 T: (207) 883-3355 F: (207) 883-3376
SPECIFICATIONS:
Lowell Specifications, Inc.
34 Marc Avenue Topsham, ME 04086 T: (207) 406-4001
STRUCTURAL:
Becker Structural Engineers 75 York St Portland, ME 04101 T: (207) 879-1838 F: (207) 879-1822
CIVIL/LANDSCAPE:
Stantec Consulting 141 Portland St.
Boston, MA 02114 T: (617) 523-8103
AE Research Addition 523-307
0%
S
UB
MI
TT
AL
- B
ID
D
OC
UM
EN
TS
3-31-2016
Stair Details
AS406
PNDW
1 1/2" = 1'-0"1 Typical Stair @ landing 1 1/2" = 1'-0"2 Typical Guardrail
1 1/2" = 1'-0"4 Typical Wall Rail @ Bottom of run
1 1/2" = 1'-0"5 TOP OF STAIR RUN @ FLOOR
1 1/2" = 1'-0"6 GUARDRAIL SECTION
1 1/2" = 1'-0"7 DETAIL AT INTERMEDIATE STAIR LANDING
1 1/2" = 1'-0"3 Typical Wall Mounted Handrail
Ground Floor -14' - 0"
C 5
AS407
CLR
1' - 4"
4'
0" M
IN
Ground Floor -14' - 0"
ELEVATOR PIT
-19' - 0"
1'
0"
5'
0" 4'
0"
3 3/4" 1 1/2"
EXISTING ELEC.
ROOM LEVEL
59' - 0"
Ground Floor 61' - 0"
EXISTING
BASEMENT
62' - 0"
4"
Z-GIRT FURRING FOR SHAFT WALL
TRACK ATTACHMENT,
ENCAPSULATE IN FIRE-PROOFING,
WITH BOTTOM FLANGE EXPOSED
FIRE-RATED SHAFT WALL
DEFLECTION TRACK
SHAFT WALL TRACK
SOF
FILL FLUTE WITH SPRAY
APPLIED FIRE-PROOFING
ELEVATOR RAIL
ELEVATOR HOISTWAY
RAIL SUPPORT AS REQ, MAINTAIN
FIRE-PROOFING AT FULL DEPTH
NOTE: GC TO COORDINATE
FINAL GIRT SIZE WITH
REQUIRED DEPTH OF SOF - TYP
5"
Z-GIRT FURRING FOR GWB
ATTACHMENT
FIRE-RATED DEFLECTION
TRACK
SOF
RATED FL ASSEMBLY
FIRE SEALANT FROM GWB TO
RATED FL ASSEMBLY
FIRE SEALANT FROM GWB TO
RATED FL ASSEMBLY
ELEVATOR RAIL
ELEVATOR HOISTWAYSTAIR LANDING
RAIL SUPPORT BY ELEV
MFG, FIRE-SEAL ALL
PENETRATIONS OF RATED
ENCLOSURE, TYP
Z-GIRT FURRING FOR STUD
ATTACHMENT, ENCAPSULATE IN
FIRE-PROOFING, WITH BOTTOM
FLANGE EXPOSED
FILL FLUTE WITH SOF
NOTE: GC TO COORDINATE
FINAL GIRT SIZE WITH
REQUIRED DEPTH OF SOF - TYP
BEYOND
9" EO SLAB
FIRE-RATED DEFLECTION
TRACK
RATED FL ASSEMBLY
FIRE SEALANT FROM GWB TO
RATED FL ASSEMBLY
FIRE SEALANT FROM GWB TO
RATED FL ASSEMBLY
Z-GIRT FURRING FOR LGMF
ATTACHMENT, ENCAPSULATE IN SOF
WITH BOTTOM FLANGE EXPOSED
LGMF TO CARRY TWO LAYERS
GWB AND CLOSE RATED WALL
ASSEMBLY TO SOF
FILL FLUTES AT BEAM WITH SOF
ALIGN GWB WITH GWB ON
SHAFT WALL BEYOND
EDGE OF SLAB AT STAIR SHAFT
BEYOND
STAIR LANDING
NOTE: GC TO COORDINATE
FINAL GIRT SIZE WITH
REQUIRED DEPTH OF SOF - TYP
1"
Z-GIRT FURRING FOR LGMF
ATTACHMENT, ENCAPSULATE IN
FIRE-PROOFING, WITH BOTTOM
FLANGE EXPOSED
LGMF TO CARRY GWB AND
CLOSE RATED SHAFT WALL
ASSEMBLY TO SOF
1"9" EO SLAB
SHAFT WALL TRACK
SOF
FILL FLUTE WITH SPRAY
APPLIED FIRE-PROOFING
OUTER LAYER OF GWB TO RUN
BY SLAB EDGE
FIRE SEALANT FROM GWB TO
RATED FL ASSEMBLY
STAIR SHAFT
ALIGN STRINGER WITH FACE
OF RATED STAIR ENCLOSURE
ELEVATOR RAIL
ELEVATOR HOISTWAY
IF INTERMEDIATE RAIL
SUPPORT IS REQ, FIRE-SEAL
ALL PENETRATIONS OF
RATED ENCLOSURE, TYP
ALIGN STRINGER WITH FACE
OF RATED STAIR ENCLOSURE
RAIL SUPPORT AS REQ
STAIR SHAFT
TWO HOUR RATED WALL
5" EO SLAB/FO SHAFTWALL
ELEVATOR HOISTWAY
ELEVATOR DOOR
ELEVATOR JAMB
LEVELING BED
ELEVATOR
THRESHOLD
EXPANSION BOLT
STEEL ANGLE-
SPAN OPENING
SOF
C
Z-GIRT FURRING FOR SHAFT
WALL TRACK ATTACHMENT,
ENCAPSULATE IN SOF WITH
BOTTOM FLANGE EXPOSED
FIRE-RATED SHAFT WALL
DEFLECTION TRACK
NOTE: GC TO COORDINATE
FINAL GIRT SIZE WITH
REQUIRED DEPTH OF SOF - TYP
3/4" PANEL AS SCHEDULED
ELEVATOR DOOR
9 1/4"
MTL DUST PAN
AT HEAD ONLY
RATED SS ELEVATOR FRAME
(GRAY HATCH IS RATED
SEGMENT
SS ELEVATOR FRAME
EXTENSION BY ELEV MFG TO
MATCH RATED FRAME
HOISTWAY SHAFTWALL
FURRING PARTITION PER
PLANS, RETURN TO RATED
PARTITION AS SHOWN
C
1/2" LG FURRING FOR
PANEL ATTACHMENT
2" 1"
NOTE: AT ROOF TOP PENTHOUSE THERE IS
ONLY THE SHAFTWALL AND RATED FRAME
3/4" PANEL AS SCHEDULED
ELEVATOR DOOR
1/
4"
RATED SS ELEVATOR FRAME
(GRAY HATCH IS RATED
SEGMENT
SS ELEVATOR FRAME
EXTENSION BY ELEV MFG TO
MATCH RATED FRAME
HOISTWAY SHAFTWALL
FURRING PARTITION PER
PLANS, RETURN TO RATED
PARTITION AS SHOWN
C
1/2" LG FURRING FOR
PANEL ATTACHMENT
2" 1"
NOTE: AT ROOF TOP PENTHOUSE THERE IS
ONLY THE SHAFTWALL AND RATED FRAME
Z-GIRT FURRING FOR LGMF
ATTACHMENT, ENCAPSULATE IN
FIRE-PROOFING WITH BOTTOM
FLANGE EXPOSED
PROVIDE FURRING SUPPORT AS
REQ.TO CARRY GWB PAST BEAM
AND SLAB EDGE
SHAFT WALL PER PLAN
SOF
FILL FLUTE WITH SPRAY
APPLIED FIRE-PROOFING, TYP
OUTER LAYER OF GWB TO RUN
BY SLAB EDGE
FIRE SEALANT
1"
4" EO SLAB
STAIR SHAFT
FURRING WALL PER PLAN
RATED FLOOR ASSEMBLY
2 LAYERS TYPE X 5/8" GWB ON
1-5/8" LGMF HELD TIGHT TO SOF -
EXTEND FULL HEIGHT AND FIRE-
SEAL TO UNDERSIDE OF DECK
SHAFT WALL PER PLANS
2 LAYERS TYPE X 1/2"
GWB ON 2 1/2" LGMF
MINERAL WOOL FIRE SAFING
FULL HEIGHT OF BALLOON
FRAMED STUD CAVITY
EXTERIOR WALL
ASSEMBLIES PER PLANS
1.8
B
ALIGN FACE OF GWB IN
STAIR SHAFT
STAIR SHAFT 2 LAYERS TYPE X 5/8" GWB ON
1-5/8" LGMF HELD TIGHT TO SOF -
EXTEND FULL HEIGHT AND FIRE-
SEAL TO UNDERSIDE OF DECK
SHAFT WALL PER PLANS
FURRING AS REQ
EXTERIOR WALL
ASSEMBLIES PER PLANS
1.8
BALIGN FACE OF GWB IN
STAIR SHAFT
STAIR SHAFT
49 DARTMOUTH STREET
PORTLAND, ME 04101
207-775-1059 www.pdtarchs.com
ARCHITECTURE
INTERIOR DESIGN
PLANNING
Project Number
Building Number
Drawing NumberLocation
Project Title
Date Checked Drawn
Drawing Title
Approved: Project Director
Dwg:
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
1 2 3 4 5 6 7 8
A
B
C
D
E
VA FORM 08-6231, OCT 1978
on e e ig on e q ua rte r i on e h al f th re e e ig th re e q ua rte rs i
6" on e i
6" on e h a lf i nc f oo t 6"
Denis McLaughlin Telephone: 857-364-5149
1 2 3 4 5 6 7 8
Jamaica Plain, MA
A
B
C
D
E
M.E.P.:
Stantec 482 Payne Road Scarborough, ME 04074 T: (207) 883-3355 F: (207) 883-3376
SPECIFICATIONS:
Lowell Specifications, Inc.
34 Marc Avenue Topsham, ME 04086 T: (207) 406-4001
STRUCTURAL:
Becker Structural Engineers 75 York St Portland, ME 04101 T: (207) 879-1838 F: (207) 879-1822
CIVIL/LANDSCAPE:
Stantec Consulting 141 Portland St.
Boston, MA 02114 T: (617) 523-8103
AE Research Addition 523-307
0%
S
UB
MI
TT
AL
- B
ID
D
OC
UM
EN
TS
3-31-2016
Stair And Elevator Shaft Details
AS407
PNDW
1" = 1'-0"4 ELEVATOR PIT LADDER
1" = 1'-0"5 ELEVATOR PIT LADDER SECTION
VERIFY FINAL LADDER DETAILS WITH ELEVATOR
MANUFACTURER'S REQUIREMENTS AND LOCAL CODES
TURN UP ENDS OF SIDE RAIL
IN 3" AND ANCHOR WITH 3/8"
DIA BOLTS.
1-1/2"X1/4" BAR RAILS
W/ 1/2" DIA X 16" WIDE
RUNGS @ 12" O.C.
FIRST RUNG @ 12" AFF
4-1/2" MINIMUM CLEARANCE
FROM CENTERLINE OF RUNGS
TO FACE OF PIT WALL
ANGLE BRACKETS
2-1/2"X3-1/2"X4-1/2" LONG
@ 4'-0" O.C.
(NOT LESS THAN
2 TOP, CENTER, AND BOTTOM)
TWO BOLTS PER BRACKET.
ANCHORED TO WALL.
TOP RUNG AT FINISHED
FLOOR ELEVATION
1 1/2" = 1'-0"1 Slab Edge at Elevator Shaft 1 1/2" = 1'-0"2 Rated Wall Between Stair/Elevator at Stair Landing
1 1/2" = 1'-0"3 Floor Level Stair Landing
1 1/2" = 1'-0"8 Stair Opening Shaft Wall Detail 1 1/2" = 1'-0"7 Rated Wall Between Stair/Elevator
1 1/2" = 1'-0"6 Elevator Door Threshold
1 1/2" = 1'-0"13 Elevator Head 1 1/2" = 1'-0"12 Elevator Door Jamb
1 1/2" = 1'-0"11 Stair 2 Slab Edge Detail 1 1/2" = 1'-0"10 Stair Opening at Interior Corner Column
1 1/2" = 1'-0"9 Stair Opening at Interior Corner Column at Concrete Pier
ACM PANEL
CONTINUOUS 2" HORIZONTAL Z-
FURRING
CLOSURE TRIM BY ACM PANEL MFG
- SAME PROFILE AS PLAN DETAIL
CONTINUOUS 6 1/2"
HORIZONTAL Z-FURRING
WEEP IN ACM PANEL
ACM PANEL
CONTINUOUS 3" VERTICAL Z-FURRING -
EXTEND TO ACM PANEL SOFFIT AT
GROUND FLOOR C-WALL HEAD AND
FASTEN TO RELIEVING ANGLE
RELIEVEING ANGLE FOR
FURRING CHANNEL
ATTACHMENT, SEE STRUCT
MTL FURRING AS REQUIRED TO
RETURN SHEATHING TO
MASONRY FND WALL
RETURN INSULATION AND AVB TO
FND WALL AS SHOWN
ALIGN ACM PANEL
SOFFIT WITH M.O.
CANTILEVERED FL SLAB
VERTICAL CLOSURE TRIM BEYOND
SEE CURTAIN WALL
TYPES FOR HEAD DETAIL
3/ 4"
3/ 4"4
1/ 2"
TOP OF ACM PANEL TO ALIGN WITH
BOTTOM OF JOINT BEYOND TO ALLOW
3/4" VERTICAL LEG OF CLOSURE TRIM
TO MATCH JOINT BEYOND - SEE EXT
ELEVATIONS FOR JOINT ALIGNMENTS
COORDINATE F.O. ANGLE WITH
WITH MTL FURRING CHANNEL
WEEPS IN ACM PANEL
SILL SEAL PRODUCT AT
STUD ON SLAB, TYP
1/
2"
4 1/2"
3/4"
8"
1'
0"
1/
2"
3/4"ACM PANEL CLOSURE TRIM
DRAINAGE SHEET
2" RIGID INSULATION
DAMP-PROOFING TO
TOP OF WALL
GRADE
COMPOSITE DRAINAGE
MEDIA, FABRIC SIDE
TOWARD GROUT
PINS DRILLED/GROUTED
INTO FND
GROUT SOLID (NON-
SHRINK GROUT)
1" WIDE STRIPS OF HEAVY
DUTY COMPOSITE
DRAINAGE MEDIA, 24" OC
2" INSUL
SEAL ALL MEMBRANE
PENETRATIONS BY PRECAST
ANCHORS WITH LIQUID
MEMBRANE, TYP
DAMP-PROOFING TO
TOP OF WALL
F.O. STUD
1" - E.O. DECK TO
5 1/2" FASCIA
SYSTEM, TYP
6" CFMF ABOVE ROOF
DECK, PACK WITH
MINERAL WOOL
SEE ROOF PLAN FOR TOP
OF ROOF BLOCKING
CFMF AS REQ TO
CARRY SHEATHING
AND GWB PAST BEAM
LAP ROOF MEMBRANE
OVER AVB AND SEAL
BLOCKING/SHIMS AS REQ
EPDM TO EXTEND
OVER PARAPET
ONTO F.O. ROOF
BLOCKING
SLOPE TOP OF
PARAPET 1/2"/FT,
TYP.
1' - 0 1/2" STL PLATE
5 1/2" FASCIA SYSTEM, TYP
T.O. 2X BLOCKING
PER ROOF PLAN
HOLD PLYWD 1"
ABOVE BENT PLATE
LAP ROOF MEMBRANE
OVER AVB AND SEAL
5/8" PLYWD
FURRING FOR ACM PANEL
ATTACHMENT - SEAL ALL
PENETRATIONS OF AVB
SHIMS AS REQ
EPDM TO EXTEND OVER
PARAPET ONTO F.O.
ROOF BLOCKING
COMPLETELY FILL
PARAPET STUD
CAVITY WITH MINERAL
WOOL INSULATION
ADD CFMF TRACK TO
BALLOON-FRAMED
PARAPET TO HOLD
INSUL. IN PLACE
SLOPE TOP OF
PARAPET 1/2"/FT, TYP.
SEE STRL FOR BEAM,
DECK, AND BENT PLATE
1" MOVEMENT JOINT TYP
AT ALL BALLOON
FRAMED PARAPET
CONDITIONS - USE
ANGLED COMPRESSIBLE
FOAM CANT TO CARRY
EPDM ACROSS GAP
FILL JOINT WITH
MINERAL WOOL
2X10 2X10
SHEATHING AND AVB
AROUND KICKER
CFMF OUTRIGGER
8 3/4"
5"
B.
O
. P
AN
EL
1" FURRING/SHIM SPACE FOR ACM PANEL
1' - 0"
1/
2"
ENTRY SLAB
= -7' 0"
1' - 5"
SELF-ADHERING BUTYL FLASHING,
EXTEND 4" UP WALL
FILL STUD CAVITY WITH
MINERAL WOOL INSUL
6" CFMF
ALIGN FO INSUL WITH FO FNDWALL COMPONENTS
7 1/2" - TYP
AVB ONTO FND SHELF
SILL SEAL BELOW
CFMF, TYP
TOP OF PARAPET BEYOND
TRANSITION TO 6" CFMF
ABOVE ROOF STEEL
(MAINTAIN ALIGNMENT WITH
OUTSIDE F.O. 8" CFMF BELOW
FO PANEL
1' - 5" FO PANEL TO
STL CHANNEL SUPPORT PER STRUCT
WD BLOCKING FOR PARAPET
SUPPORT
CFMF SUPPORTED OFF
BEAM AS REQ. TO CARRY
SHEATHING AND INTERIOR
GWB PAST BEAM
FIRE-RATED 8" DEFLECTION TRACK
FURRING CHANNELS AS REQ FOR
ACM PANEL ATTACHMENT - SEAL ALL
MEMBRANE PENETRATIONS, TYP
DISCONTINUE THIS FASCIA 2"
BEFORE WALL OF ELEVATOR
PENTHOUSE AND SLOPE
BLOCKING AS REQ TO ALLOW
PARAPET TO DRAIN
COORDINATE PANEL
JOINTS WITH EXTERIOR
ELEVATIONS
COVER TOP OF PARAPET
BLOCKING WITH ROOF MEMBRANE
DEFLECTION TRACK
INSUL, AVB, SHEATHING PER
TYPICAL WALL SYSTEMS
EXTEND MEMBRANE DOWN
THIS WALL AND ADHERE TO
MEMBRANE ON MAIN ROOF
SEALANT
MINIMUM 8" OVERLAP
1/2" PLYWD SHEATHING
PARAPET BLOCKING ASSEMBLY
FROM 1/2" PLYWD AND BLOCKING
AS REQ TO SLOPE ASSEMBLY 1/4"
BACK TOWARD ELEVATOR
PENTHOUSE WALL
5 1/2" FASCIA SYSTEM, TYP
LAP MEMBRANE OVER AVB ON
FACE OF BLOCKING AND SEAL
FILL VOID WITH INSUL
1 HR SOF, TYP AT ROOF DECK
Z-GIRT FURRING FOR CFMF
ATTACHMENT, ENCAPSULATE IN
FIRE-PROOFING, WITH BOTTOM
FLANGE EXPOSED
CONTINUOUS 2" HORIZONTAL
Z-FURRING
CLOSURE TRIM BY ACM
PANEL MFG - SAME PROFILE
AS PLAN DETAIL
CONTINUOUS 6 1/2"
HORIZONTAL Z-FURRING
3/ 4"
3/ 4"
1/
2"
B.O. OF ACM PANEL TO ALIGN
WITH BOTTOM OF JOINT
BEYOND TO ALLOW 3/4"
VERTICAL LEG OF CLOSURE
TRIM TO MATCH JOINT BEYOND
- SEE EXT ELEVATIONS FOR
JOINT ALIGNMENTS
7"
1'
8" CFMF
.0
0°
DEFLECTION HEAD
AS501
PROVIDE SLOPED PLYWD
PARAPET BLOCKING
ASSEMBLY FOR ACM PANEL
ATTACHMENT - FILL VOID
WITH MINERAL WOOL INSUL
TYPICAL ACM PANEL
FURRING ELEMENTS
COORDINATE PANEL
JOINTS WITH EXTERIOR
ELEVATIONS
STEEL PER STRL
RETURN ACM PANEL TO
BACK OF BLOCKING
ASSEMBLY AND FASTEN
VERTICAL LEG
8"
ROOF MEMBRANE ON 3/4"
PLYWD SHEATHING
SEAL ROOF MEMBRANE
OVER TRANSITION STRIP
CONTINUOUS ROOF MEMBRANE
UNDER SCREEN WALL, TURN
DOWN ROOF EDGE ASSEMBLY
AND SEAL TO AVB
LIQUID MEMBRANE
COMPRESSIBLE FOAM TUBES TO
CARRY TRANSITION MEMBRANE
OVER 4" GAP BETWEEN BOTTOM OF
SCREEN WALL SHEATHING AND
PLYWD ROOF EDGE ASSEMBLY
ROOF MEMBRANE
TRANSITION STRIP
PLYWD BLOCKING ROOF EDGE
ASSEMBLY - ALIGN WITH FO INSUL
AND FILL WITH MINERAL WOOL
INSUL - MODIFY AS REQ AT
STRUCTURAL PENETRATIONS
SEE STRL FOR OUTRIGGER
AND OTHER STRUCTURAL
COMPONENTS
AVB ON GWB SHEATHING -
ALIGN SHEATHING AND
SCREEN WALL WITH MAIN
CFMF EXTERIOR WALL BELOW
WRAP ROOF MEMBRANE OVER
PLYWD PARAPET BLOCKING
ASSEMBLY - EXTEND DOWN FO
OF AVB 7" AND SEAL
8" CFMF
TYPICAL ACM PANEL
FURRING ELEMENTS
EXTEND AVB UP FO
ROOF EDGE ASSEMBLY
CONTINUOUS BLOCKING
TO CARRY SHEATHING
PAST STL STRUCTURE
BLOCKING AS REQ
SEAL MEMBRANE TO SCREEN
WALL STEEL COLUMN
PENETRATIONS - SEE STRUCT
DASHED LINES REPRESENT HSS
COLUMNS AT SCREEN WALL
CORNERS - COLUMN AT MIDPOINT
OF WALL IS A WIDE FLANGE
BUMP PLYWD AND MEMBRANE
ASSEMBLY OUT TO CAPTURE WIDE
FLANGE COL AT CENTER OF SCREEN
WALL (SEE STRUCT) - SUPPORT
COLUMN BUMP WITH CFMF AS REQ.
6"
6" CFMF
3/4" PLYWD
SEE ELEVATIONS FOR
PANEL JOINTS
PARAPET BEYOND
2-PIECE MTL
COUNTERFLASHING
C
1/
2"
1' - 0" FO STUD
ROOF MEMBRANE ON 3/4"
PLYWD SHEATHING
CONTINUOUS ROOF
INSULATION AND COVER
BOARD ON MTL DECKING
COMPRESSIBLE FOAM TUBE
- 4" GAP
2X4 AND PLYWD BLOCKING
ASSEMBLY
SAMF TO CONNECT
COUNTERFLASHING TO AVB
BLOCKING AS REQ TO
CARRY SHEATHING PAST
STL STRUCTURE
EXTEND MEMBRANE DOWN
FO OF AVB 7" AND SEAL
RETURN ACM PANEL TO
BACK OF BLOCKING
ASSEMBLY AND FASTEN
CONTINUOUS ROOF MEMBRANE
UNDER SCREEN WALL
LIQUID MEMBRANE
ROOF MEMBRANE
TRANSITION STRIP
AVB TO TOP OF BLOCKING
SEAL ROOF MEMBRANE
OVER TRANSITION STRIP
1' - 7 1/2" FO ACM
2X10 2X10
4"
CONTINUOUS 2"
HORIZONTAL Z-FURRING
ACM PANEL
CLOSURE TRIM
CONTINUOUS 6 1/2"
HORIZONTAL Z-FURRING
3/ 4"
3/ 4"
ACM PANEL JOINT
BEYOND
FACE OF ACM
PANEL BEYOND
3 5/8"
1 3/4"
1/
2"
3/
4"
TYPICAL PRECAST
MASONRY TOP
MTL FLASHING, EXTEND
ONTO SLOPED INSULATION
COMPOSITE DRAINAGE MEDIA,
FABRIC SIDE TOWARD GROUT
GROUT SOLID (NON-
SHRINK GROUT)
SEALANT
WEEPS AT VERTICAL JOINTS
BETWEEN PRECAST PANELS, TYP
TYP WALL COMPONENTS
SEE SYSTEMS SHEET FOR
PRECAST ANCHOR
SET IN GROUTED SLOT
SEAL ALL PENETRATIONS
OF AVB, TYP
SLOPED EXTRUDED
POLYSTYRENE INSULATION
(MINERAL WOOL INSUL
ABOVE AND BELOW)
SELF-ADHERING BUTYL
FLASHING, EXTEND FROM
WALL TO VERTICAL MTL
FLASHING LEG AS SHOWN
SEAL ALL FLASHING PENETRATIONS
BY PRECAST ANCHORS WITH
LIQUID MEMBRANE, TYP
49 DARTMOUTH STREET
PORTLAND, ME 04101
207-775-1059 www.pdtarchs.com
ARCHITECTURE
INTERIOR DESIGN
PLANNING
Project Number
Building Number
Drawing NumberLocation
Project Title
Date Checked Drawn
Drawing Title
Approved: Project Director
Dwg:
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
1 2 3 4 5 6 7 8
A
B
C
D
E
VA FORM 08-6231, OCT 1978
on e e ig on e q ua rte r i on e h al f th re e e ig th re e q ua rte rs i
6" on e i
6" on e h a lf i nc f oo t 6"
Denis McLaughlin Telephone: 857-364-5149
1 2 3 4 5 6 7 8
Jamaica Plain, MA
A
B
C
D
E
M.E.P.:
Stantec 482 Payne Road Scarborough, ME 04074 T: (207) 883-3355 F: (207) 883-3376
SPECIFICATIONS:
Lowell Specifications, Inc.
34 Marc Avenue Topsham, ME 04086 T: (207) 406-4001
STRUCTURAL:
Becker Structural Engineers 75 York St Portland, ME 04101 T: (207) 879-1838 F: (207) 879-1822
CIVIL/LANDSCAPE:
Stantec Consulting 141 Portland St.
Boston, MA 02114 T: (617) 523-8103
AE Research Addition 523-307
0%
S
UB
MI
TT
AL
- B
ID
D
OC
UM
EN
TS
3-31-2016
Exterior Details
AS501
PNDW
1 1/2" = 1'-0"1 SECTION DETAIL AT LOWER ACM PANEL TRANSITION
1 1/2" = 1'-0"12 PLAN DETAIL AT ACM PANEL TRANSITION
1 1/2" = 1'-0"7 FOUNDATION SHELF DETAIL AT CONNECTOR CORRIDOR
1 1/2" = 1'-0"10 PARAPET AT INNER MTL PANEL, BEAM WITHIN CFMF
1 1/2" = 1'-0"9 PARAPET AT OUTER MTL PANEL, BEAM OUTSIDE CFMF
1 1/2" = 1'-0"13 SECTION AT STAIR 1 EXTERIOR WALL PROJECTION
1 1/2" = 1'-0"2 HIGH PARAPET - STAIR 1
1 1/2" = 1'-0"5 SECTION DETAIL AT UPPER ACM PANEL TRANSITION
1 1/2" = 1'-0"4 SCREEN WALL
1 1/2" = 1'-0"3 SCREEN WALL RETURN
1 1/2" = 1'-0"6 ACM PANEL TRANSITION
3" = 1'-0"8 TYPICAL TOP OF PRECAST DETAIL
1 1/2" = 1'-0"11 PRECAST JOINT
ROOF DRAIN (TYP COMBINED
PRIMARY/SECONDARY U.N.O. ON ROOF PLAN)
ROOF MEMBRANE
MAINTAIN 2" BASE LAYER OF INSULATION AT
ROOF DRAIN - TYP
TAPERED INSULATION
ROOF OPENING FRAME
2' - 0"CL
MIN 1/2" SLOPE AT 4'X4' SUMPMIN
3"
MIN
3"
WATER CUT OFF MASTIC
STAINLESS STEEL
CLAMPING RING
PRE-FABRICATED
PIPE SEAL
CONTINUOUS LAP
SEALANT AND
SPLICING CEMENT
MEMBRANE
ROOFING SYSTEM
VENT THROUGH ROOF -
ANCHOR TO STRUCTURE
MIN
3"
MIN
3"
SEE PLAN FOR NO.
OF PIPES
STAINLESS STEEL
CLAMPING RING
PRE-FABRICATED
PIPE SEAL
CONTINUOUS LAP
SEALANT AND
SPLICING CEMENT
MEMBRANE
ROOFING SYSTEM
CHASE THROUGH ROOF -
ANCHOR TO STRUCTURE
INSULATION
3"
CURB W/ INTERGRAL CAP
FLASHING
CONTINUOUS BACKER ROD
AND SEALANT @ ALL
EDGES OF UNIT
ELASTROMERIC FLASHING SET
IN BONDING ADHESIVE - LOOP
FLASHING OVER BACKER ROD
CONTINUOUS LAP SEALANT @
ELASTOMERIC FLASHING SET
IN SPLICING CEMENT
MEMBRANE ROOFING SYSTEM
CONT. RUBBER NAILING STRIP
- ANCHOR TO P.T. BLOCKING
M
IN2"
T.O. BLOCKING
@ H.P. OF INSUL
PRE-FAB CURB UNIT
PT WD NAILER
RETURN FASCIA SYSTEM
FULL DEPTH OF WALL
BRAKE METAL SCUPPER W/
HOLD DOWN CLIP - TURN
UP SIDES OF OPENING
INSULATED WOOD BUILD-OUT
SLOPED 1/4"/FT
LAP ROOF MEMBRANE
OVER WALL AVB
LAP SCUPPER METAL
1" MIN OVER SIDING
LAP STRIP W/ SLACK
FOR MOVEMENT
RETURN SIDING MIN 3"
INTO OPENING
3/ 4"
NOTE: SEE SYSTEMS SHEET FOR
TYPICAL WALL COMPONENTS
ACM PANEL CLOSURE TRIM
THIS DIMENSION IS T.O. PRECAST TO B.O. ACM PANEL CLOSURE TRIM (WHERE THIS
DETAIL OCCURS ADJACENT TO GROUND FL WINDOWS THE INTENT IS FOR THE
BOTTOM OF THIS CLOSURE TRIM TO ALIGN WITH WINDOW CLOSURE TRIM AND THE
WINDOW RO - SEE WINDOW HEAD DETAILS IN MASONRY)
SEAL ALL PENETRATIONS OF AVB, TYP
SLOPED EXTRUDED POLYSTYRENE
INSULATION (TYPICAL MINERAL WOOL
INSUL ABOVE AND BELOW)
TYPICAL ACM PANEL FURRING
COMPONENTS, COPE END OF VERTICAL
GIRT AS REQ TO CLEAR FLASHING
ELEMENTS
AVB
SELF-ADHERING BUTYL FLASHING,
SEAL TO FACE OF PRECAST AND AVB
AS SHOWN
SEALANT
ACM PANEL CLOSURE TRIM
PRECAST ANCHOR
1/
2"
3"
SEAL ALL PENETRATIONS OF AVB, TYP
FASTEN SILL FLASHING TO PRECAST
THROUGH BED OF SEALANT
MTL SILL FLASHING IS A
CONTINUATION OF THE ADJACENT C-
WALL SILL FLASHING, EXTEND ONTO
SLOPED INSULATION
NOTE: SEE SYSTEMS SHEET FOR
TYPICAL WALL COMPONENTS
SLOPED EXTRUDED POLYSTYRENE
INSULATION (TYPICAL MINERAL WOOL
INSUL ABOVE AND BELOW)
TYPICAL ACM PANEL FURRING
COMPONENTS, COPE END OF VERTICAL GIRT
AS REQ TO CLEAR FLASHING ELEMENTS
AVB
SELF-ADHERING BUTYL FLASHING,
EXTEND FROM WALL TO FACE OF
PRECAST AS SHOWN
SEALANT
SELF-ADHERING BUTYL FLASHING
STRIP TO "TAPE-IN" MTL SILL FLASHING
PRECAST ANCHOR
COMPOSITE DRAINAGE MEDIA,
FABRIC SIDE TOWARD GROUT
GROUT SOLID (NON-SHRINK GROUT)
2" RIGID INSULATION
EXTEND WATERPROOFING
ONTO SHELF OVER WALL
WATERPROOFING
COMPOSITE DRAINAGE
MEDIA, FABRIC SIDE
TOWARD GROUT
PINS DRILLED/GROUTED
INTO FND
GROUT SOLID (NON-
SHRINK GROUT)
1" WIDE STRIPS OF HEAVY
DUTY COMPOSITE
DRAINAGE MEDIA, 24" OC
BITUTHENE WATERPROOFING
SET IN DECK PREP
BITUTHENE WATERPROOFING
- EXTEND ACROSS CMU
SHELF AND UP WALL ABOVE
GRADE AS SHOWN
LAP AVB OVER
WATERPROOFING AND SEAL
CMU INFILL WALL WITH FND
SHELF TO FACILITATE FUTURE
MRI REPLACEMENT - SEE STRUCT
1'
0"
GRAVEL BASE - HOLD 1' BELOW
RF SHIELDING FLOOR
CONTINUE WATERPROOFING AND
INSUL TO BOTTOM OF WALL
SEE STRUCT FOR SLAB
DEPRESSION AT MRI
VAPOR RETARDER
AND 2" INSUL
SEE SHIELDING DRAWINGS FOR
MRI SHIELDING ENCLOSURE
SEE CIVIL FOR
OVERBURDEN
SEAL ALL FLASHING PENETRATIONS
BY PRECAST ANCHORS WITH
LIQUID MEMBRANE, TYP
ACM CLOSURE TRIM,
FASTEN TO PRECAST
RF SHIELDING WALL, SEE
SHIELDING DRAWINGS
FND WALL, SEE STRUCT
UNGROUTED CMU INFILL
PARTITION FOR FUTURE MRI
REPLACEMENT, SEE STRUCT
SEE ASSEMBLY TYPES FOR
TYPICAL WALL COMPONENTS
JOINT IN SHIELDING WALL
FOR FUTURE MRI
REPLACEMENT, SEE
SHIELDING DRAWINGS
F
1' - 5 1/2"
PRECAST BELOW
TY
PI
C
AL
C O
M
PO
N
EN
TS
SE
E
AS
SE
M
BL
Y
SH
EE
T
FO
R
SEE ELEVATIONS FOR
PANEL JOINT LOCATIONS
49 DARTMOUTH STREET
PORTLAND, ME 04101
207-775-1059 www.pdtarchs.com
ARCHITECTURE
INTERIOR DESIGN
PLANNING
Project Number
Building Number
Drawing NumberLocation
Project Title
Date Checked Drawn
Drawing Title
Approved: Project Director
Dwg:
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
1 2 3 4 5 6 7 8
A
B
C
D
E
VA FORM 08-6231, OCT 1978
on e e ig on e q ua rte r i on e h al f th re e e ig th re e q ua rte rs i
6" on e i
6" on e h a lf i nc f oo t 6"
Denis McLaughlin Telephone: 857-364-5149
1 2 3 4 5 6 7 8
Jamaica Plain, MA
A
B
C
D
E
M.E.P.:
Stantec 482 Payne Road Scarborough, ME 04074 T: (207) 883-3355 F: (207) 883-3376
SPECIFICATIONS:
Lowell Specifications, Inc.
34 Marc Avenue Topsham, ME 04086 T: (207) 406-4001
STRUCTURAL:
Becker Structural Engineers 75 York St Portland, ME 04101 T: (207) 879-1838 F: (207) 879-1822
CIVIL/LANDSCAPE:
Stantec Consulting 141 Portland St.
Boston, MA 02114 T: (617) 523-8103
AE Research Addition 523-307
0%
S
UB
MI
TT
AL
- B
ID
D
OC
UM
EN
TS
3-31-2016
Exterior Details
AS502
PNDW
3" = 1'-0"6 TYP. MEMBRANE @ ROOF DRAIN
3" = 1'-0"8 DTL @ VENT / FLAT ROOF
3" = 1'-0"7 CHASE FOR MECHANICAL PENETRATION
3" = 1'-0"9 VERTICAL TERMINATION @ ROOF TOP AHU
1 1/2" = 1'-0"5 SECTION AT METAL SCUPPER
3" = 1'-0"4 OUTER ACM PANEL TO PRECAST TRANSITION
3" = 1'-0"1 INNER ACM PANEL TO PRECAST TRANSITION
1 1/2" = 1'-0"2 FOUNDATION SHELF AT AREAWAY
1 1/2" = 1'-0"3 Plan Detail at CMU Infill
8"
PROVIDE 2 FEET HIGH MINERAL WOOL INSUL
AROUND ENTIRE INTERFACE OF EXISTING
AND NEW CONSTRUCTION - FILL ENTIRE
WIDTH OF VOID AND INSTALL ON PUSH PINS
ADHERED TO EXISTING METAL PANEL.
4"1' - 0"
EA
DASHED LINES REPRESENT 4"
WALL EXPANSION JOINT BEYOND
NOTE: AT WALL FOR ROOF TOP ELEVATOR
ENCLOSURE THE ROOF EXPANSION JOINT SHIFTS
FROM ITS ALIGNMENT WITH FACE OF EXISTING MTL
PANEL TO ALIGN WITH THE NEW WALL AND THE
WALL EXPANSION JOINT BEYOND - SEE ROOF PLAN
DOUBLE DASHED LINE REPRESENTS
EXISTING METAL PANEL TO BE
REMOVED TO ALLOW INSTALLATION
OF BLDG EXPANSION JOINT -
EXISTING PANEL WRAPS TOP OF
WALL AS SHOWN TO FORM COPING
REMOVE EXISTING PANEL ABOVE THIS
JOINT, INCLUDING ANY FURRING
ELEMENTS THAT INTERFERE WITH
INSTALLATION OF EXPANSION JOINT
ADD NEW LAYER OF PLYWD TO TOP
OF EXISTING PARAPET
WD BLOCKING TO SUPPORT PLYWD
TERMINATION BAR
PROTECT UPPER EDGE OF TERMINATION
BAR WITH LAP SEALANT
PROVIDE 5X5 STL ANGLE WITH
BLOCKING/SHIM TO SUPPORT PLYWD
AS503
PLYWD SUPPORT BETWEEN DECK
FLUTES AS REQ.
SHAFT WALL PER PLANS
FACE OF BLOCKING AND PLYWD THAT FRAMES
THE EXPANSION JOINT ALIGNS WITH BLOCKING
IN WALL EXPANSION JOINT BEYOND TO ALLOW
BELLOWS TO CONTINUE VERTICALLY DOWN TO
NEW FOUNDATION WALL - SEE PLAN DETAILS
FILL BELLOWS WITH MINERAL WOOL INSUL, TYP
ROOF MEMBRANE FULLY ADHERED
TO EXISTING MEMBRANE - GC TO
CONFIRM COMPATIBLE ADHESIVE
FLANGED EXPANSION JOINT COVER -
"EXPAND-O-FLASH" IS BASIS OF DESIGN
BELLOWS IS TO DRAIN INTO THE VERTICAL
BELLOWS AT WALL EXPANSION JOINT BEYOND -
MAINTAIN CONTINUITY OF BELLOWS THROUGH
SHIFT OF EXPANSION JOINT TO NEW POSITION -
EXTEND ONTO NEW PLYWD (UNDER ROOF
MEMBRANE) AS SHOWN AND SEAL
PROVIDE 2 FEET HIGH MINERAL WOOL INSUL AROUND
ENTIRE INTERFACE OF EXISTING AND NEW CONSTRUCTION
- FILL ENTIRE WIDTH OF VOID AND INSTALL ON PUSH PINS
ADHERED TO EXISTING METAL PANEL.
4" JOINT
EA
1'
9"
DOUBLE DASHED LINE REPRESENTS
EXISTING METAL PANEL TO BE
REMOVED TO ALLOW INSTALLATION
OF BLDG EXPANSION JOINT -
EXISTING PANEL WRAPS TOP OF
WALL AS SHOWN TO FORM COPING
REMOVE EXISTING PANEL ABOVE THIS
JOINT, INCLUDING ANY FURRING
ELEMENTS THAT INTERFERE WITH
INSTALLATION OF EXPANSION JOINT
ADD NEW LAYER OF PLYWD TO TOP OF
EXISTING PARAPET
WD BLOCKING TO SUPPORT PLYWD
WRAP ROOF MEMBRANE DOWN
EXISTING PARAPET - SEAL TO
EXISTING CONSTRUCTION AND
SECURE WITH TERMINATION BAR
PROTECT UPPER EDGE OF TERMINATION
BAR WITH LAP SEALANT
EXTEND ROOF MEMBRANE
OVER JOINT AND DOWN BACK
FACE OF EXISTING PARAPET
DRAPE EPDM OR NEOPRENE BELLOWS INTO
EXPANSION JOINT. EXTEND ONTO NEW PLYWD
(UNDER ROOF MEMBRANE) AS SHOWN AND SEAL.
BELLOWS IS TO RUN CONTINUOUSLY THROUGH
BUILDING EXPANSION JOINT BOTH VERTICALLY
AND HORIZONTALLY (USE PRE-FORMED CORNERS)
SHAFT WALL PER PLANS
PLYWD FASTENED TO FACE OF 6" CFMF
WD BLOCKING AS REQ FOR
EDGE OF DECK SUPPORT, TYP
TYPICAL NEW ROOF CONSTRUCTION PER
ASSEMBLY SHEET
FILL BELLOWS WITH MINERAL WOOL
INSUL, TYP
NEW ROOF MEMBRANE FULLY ADHERED
TO EXISTING MEMBRANE - GC TO
CONFIRM COMPATIBLE ADHESIVE
FLANGED EXPANSION JOINT COVER -
"EXPAND-O-FLASH" IS BASIS OF DESIGN
SEE STRUCT FOR
DECK SUPPORT
NOTE: WHERE THE EJ ABUTS A WALL, THE "EXPAND-O-FLASH" FLANGES
SHIFT FROM HORIZONTAL TO VERTICAL. INSTALL "BUTTERFLY" STYLE
CLOSURES TO SEAL THE JOINT AT THESE TRANSITIONS
2' HIGH X 4' LONG EXISTING METAL PANELS
TO BE REMOVED, MODIFIED, AND
REINSTALLED TO ACCOMODATE
EXPANSION JOINT INSTALLATION. LOWER
SECTION SHOWN DASHED IS TO BE CUT
AND REMOVED AS REQ. - UPPER SECTION
TO BE REINSTALLED AS SHOWN
1'
1"
REAPPLY SILICONE SEALANT OVER BACKER
ROD TO ALL EFFECTED PANEL JOINTS
EXISTING 7/8" VERTICAL MTL
FURRING CHANNEL
EXISTING GYPSUM SHEATHING
EXISTING INSULATED STUD WALL
REMOVE SECTION OF EXISTING 7/8" MTL
FURRING AT EACH PANEL JOINT TO ALLOW
INSTALLATION OF EXPANSION JOINT
MATERIALS - RE-FASTEN CUT ENDS,
PROVIDING SEALANT BETWEEN
FASTENERS AND EXISTING SHEATHING
PROTECT UPPER EDGE OF TERMINATION
BAR WITH LAP SEALANT
FLANGED EXPANSION JOINT COVER -
"EXPAND-O-FLASH" IS BASIS OF DESIGN
ROOFING MEMBRANE
EXTEND ROOFING MEMBRANE 6" UP
EXISTING SHEATHING
METAL FLASHING
TERMINATION BAR SET IN BED OF SEALANT
SECURE LOWER CUT EDGE OF EXISTING PANEL BY
POP-RIVETING TO A CLEAT THAT HOOKS INTO
KICKED OUT MTL FLASHING LEG. FASTEN THROUGH
A MTL SPACER BETWEEN BACK OF PANEL AND
CLEAT THAT IS HIGH ENOUGH TO PREVENT
FLASHING FROM HITTING BACK OF PANEL.
WD BLOCKING CANT
TO SHEATHING +/-
3" F.O. EXISTING PANEL
DRAPE EPDM OR NEOPRENE BELLOWS INTO
EXPANSION JOINT AND FASTEN TO EXISTING
SHEATHING AS SHOWN, BELLOWS IS TO RUN
CONTINUOUSLY THROUGH BUILDING EXPANSION
JOINT BOTH VERTICALLY AND HORIZONTALLY
(USE PRE-FORMED CORNERS)
2X4 WD BLOCKING
BLOCKING AS REQ.
EXISTING METAL PANEL SYSTEM
AREA OF GRAY HATCH REPRESENTS
EXISTING CONSTRUCTION TO REMAIN, TYP
FILL BELLOWS WITH MINERAL WOOL
INSUL, TYP
EXTEND BELLOWS MEMBRANE UP WALL TO
CREATE 4" MINIMUM OVERLAP WITH ROOF
MEMBRANE
RE-FASTEN UPPER CUT EDGE AND SIDES
OF EXISTING PANEL BY POP-RIVETING TO Z-
CLIPS (FASTEN Z-CLIPS THROUGH BED OF
SEALANT INTO EXISTING STUD WALL)
SUPPORT WD CANT ON CFMF AND
FASTEN PLYWD TO FACE AS SHOWN
WD BLOCKING AS REQ AT
EDGE OF DECK TO PICK UP
ROOF ASSEMBLY, TYP
WALL AS SCHEDULED, SEE
ASSEMBLY TYPES FOR TOP OF
PARTITION DETAILS
FLANGED EXPANSION
JOINT COVER
ROOFING MEMBRANE
METAL FLASHING
MTL SPACER AT POP RIVETS
TO PREVENT MTL FLASHING
FROM CONTACTING BACK OF
EXISTING MTL PANEL AND
ALLOWING WALL DRAINAGE
CLEAT
POP-RIVET
EXISTING MTL
PANEL
DEMOLISHED PORTION
OF METAL PANEL
PROVIDE 2 FEET HIGH MINERAL WOOL INSUL AROUND ENTIRE INTERFACE
OF EXISTING AND NEW CONSTRUCTION - FILL ENTIRE WIDTH OF VOID AND
INSTALL ON PUSH PINS ADHERED TO EXISTING METAL PANEL.
WATER CUTOFF MASTIC TO BE USED
WHERE MEMBRANE IS SECURED WITH A
TERMINATION BAR, TYP
SEE STRUCT FOR MTL DECK
SUPPORT
2-PIECE MTL COUNTERFLASHING
EXTEND EPDM UNDER
COUNTERFLASHING AND
SEAL TO SAMF
LAP EPDM OVER 1" FOAM
TUBE AT TRANSITION TO
ALLOW MOVMENT - TYP
TAPERED OR SHIMMED WD
BLOCKING AS REQ. FOR
PLYWD SUPPORT
MIN - 1/4"/FT SLOPED 5/8" PLYWD
1/2" PLYWD, TYP
USE OUTER PLYWD FOR OUTER
METAL PANEL ALIGNMENT AS
SHOWN IN THIS DETAIL
USE INNER PLYWD FOR INNER
METAL PANEL ALIGNMENT
CONCRETE SLAB WHERE THIS DETAIL
OCCURS AT 4TH FL ELEV STOP -
INSTALL SILL SEAL BETWEEN MTL
STUD AND SLAB IN THESE LOCATIONS
MINERAL WOOL INSUL
EXTEND AVB TO ROOF DECK
SAMF - EXTEND UP FO WALL
OVER AVB AND DOWN FACE
PLYWD UNDER ROOF MEMBRANE
2x6 2x6
METAL DECK - PROVIDE PLYWD SUPPORT
BETWEEN DECK FLUTES FOR 2X BLOCKING
WHERE DECK SPANS IN OPPOSITE DIRECTION
TAPE-IN MTL FLASHING WITH SAMF
PROTECT UPPER EDGE OF
TERMINATION BAR WITH LAP SEALANT
TERMINATION BAR SET
IN BED OF SEALANT
WATER CUTOFF MASTIC TO BE
USED WHERE MEMBRANE IS
SECURED WITH A
TERMINATION BAR, TYP
CLOSURE BY MTL PANEL MFG
PARAPET BEYOND
1'
1/
2"
49 DARTMOUTH STREET
PORTLAND, ME 04101
207-775-1059 www.pdtarchs.com
ARCHITECTURE
INTERIOR DESIGN
PLANNING
Project Number
Building Number
Drawing NumberLocation
Project Title
Date Checked Drawn
Drawing Title
Approved: Project Director
Dwg:
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
1 2 3 4 5 6 7 8
A
B
C
D
E
VA FORM 08-6231, OCT 1978
on e e ig on e q ua rte r i on e h al f th re e e ig th re e q ua rte rs i
6" on e i
6" on e h a lf i nc f oo t 6"
Denis McLaughlin Telephone: 857-364-5149
1 2 3 4 5 6 7 8
Jamaica Plain, MA
A
B
C
D
E
M.E.P.:
Stantec 482 Payne Road Scarborough, ME 04074 T: (207) 883-3355 F: (207) 883-3376
SPECIFICATIONS:
Lowell Specifications, Inc.
34 Marc Avenue Topsham, ME 04086 T: (207) 406-4001
STRUCTURAL:
Becker Structural Engineers 75 York St Portland, ME 04101 T: (207) 879-1838 F: (207) 879-1822
CIVIL/LANDSCAPE:
Stantec Consulting 141 Portland St.
Boston, MA 02114 T: (617) 523-8103
AE Research Addition 523-307
0%
S
UB
MI
TT
AL
- B
ID
D
OC
UM
EN
TS
3-31-2016
Exterior Details
AS503
PNDW
3" = 1'-0"3 EXISTING ROOF TO WALL EXPANSION JOINT
3" = 1'-0"4 EXISTING ROOF TO NEW ROOF EXPANSION JOINT
3" = 1'-0"2 NEW ROOF TO EXISTING WALL EXPANSION JOINT
3" = 1'-0"1 ROOF TO WALL TRANSITION
EXISTING FND
G
E-6.8
E-AA
SHAFT WALL PER PLANS
FILL BELLOWS WITH MINERAL
WOOL INSUL, TYP
2X4 WD BLOCKING
DEMOLISH THIS DASHED LINE PORTION OF EXISTING
PANEL AND ASSOCIATED FURRING AS REQ
EXISTING 8' HIGH DOOR SYSTEM TO BE DEMOLISHED
6"
FILL VOID WITH MINERAL WOOL INSUL
EJ COVER PLATE
LIQUID MEMBRANE
EXTEND BELLOWS BEHIND
ENTIRE REINSTALLED MTL PANEL
WD BLOCKING AS REQ TO CARRY BELLOWS
REMOVE, MODIFY, AND REINSTALL EXISTING METAL PANEL TO ALLOW
INSTALLATION OF BLDG EXPANSION JOINT - FASTEN THROUGH NEW WD BLOCKING -
AT BOTTOM OF WALL RESEAL PANEL RETURN TO EXISTING CONCRETE FNDMTL CLOSURE TRIM BY C-WALL
MFG, WRAP BLOCKING AT EJ
COVER AND FASTEN
SEAL BELLOWS TO AVB
BED BOTH SIDES OF EJ COVER IN SEALANT, TYP
SHAPE BLOCKING AS REQ TO ALIGN WITH
EXISTING MTL PANEL RETURN
SEALANT AT ALL BLOCKING
FASTENED THROUGH BELLOWS, TYP
PROVIDE BENT CFMF AS
NECESSARY TO CARRY
SHEATHING
2HR RATED EXPANSION JOINT AND COVER - SHIM
ATTACHMENT SURFACES AS REQ TO FIT
NEW 7' HIGH DOOR SYSTEM AS SCHEDULED
SHIMMED GWB INFILL TO MATCH EXISTING -
PROTECT CORNER WITH METAL ANGLE
4"
AS504
EXISTING CAST IN PLACE COLUMN
EXISTING EXTERIOR SHEATHING
G
E-6.8
E-AA
WD BLOCKING AS REQ TO CARRY BELLOWS
REMOVE, MODIFY, AND REINSTALL EXISTING METAL PANEL TO
ALLOW INSTALLATION OF BLDG EXPANSION JOINT - FASTEN
THROUGH NEW WD BLOCKING
LIQUID MEMBRANE
MTL CLOSURE TRIM BY C-WALL MFG, RETURN
AT EJ COVER AND FASTEN TO BLOCKING
SEAL BELLOWS TO AVB
BED BOTH SIDES OF EJ COVER IN SEALANT, TYP
SHAFT WALL PER PLANS
FILL BELLOWS WITH MINERAL
WOOL INSUL, TYP
1'
1/
2"
2X4 WD BLOCKING
DEMOLISH THIS DASHED LINE
PORTION OF EXISTING PANEL
1'
3/
4"
FILL VOID BETWEEN EXISTING AND NEW CONSTRUCTION WITH MINERAL
WOOL INSUL FOR 2 FEET MINIMUM BEYOND EXPANSION JOINT, TYP
7"
SEE PLANS/SECTIONS FOR EXTERIOR WALL TYPES
AND ASSEMBLY SHEET FOR COMPONENTS
EJ COVER PLATE
SHAPE BLOCKING AS REQ TO ALIGN WITH
EXISTING MTL PANEL RETURN
EXTEND BELLOWS BEHIND
ENTIRE REINSTALLED MTL PANEL
SEALANT AT ALL BLOCKING
FASTENED THROUGH BELLOWS, TYP
4" TYP
PROVIDE BENT CFMF AS
REQ TO CARRY SHEATHING
4"
BELLOWS MEMBRANE - EXTEND
ACROSS TOP AND DOWN FACE OF FND
BEHIND MTL FLASHING AS SHOWN
SLOPED MTL FLASHING
SAMF TRANSITION STRIP
MEMBRANE STRIP TO ISOLATE
BLOCKING FROM CONCRETE - TYP
2X BLOCKING
SEAL ALL MEMBRANE
PENETRATIONS
RETURN METAL FLASHING AT
BLOCKING ON BOTH SIDES OF
EXPANSION JOINT AND ACROSS FACE
OF WALL FOR ENTIRE HORIZONTAL
EXTENT OF BELLOWS MEMBRANE
EXPANSION JOINT COVER PLATE,
CLOSURE AT BOTTOM
NEW FND, SEE STRUCT
G
E-6.8
E-AA
7"
SHAFT AND FURRING
PARTITIONS PER PLANS
FILL VOID BETWEEN EXISTING AND
NEW CONSTRUCTION WITH MINERAL
WOOL INSUL FOR 2 FEET MINIMUM
BEYOND EXPANSION JOINT, TYP
EXPANSION JOINT COVER ABOVE
EXISTING MTL PANEL ABOVE
NEW MTL PANEL ABOVE
AS504
NEW FND, SEE STRUCT
EXISTING FND
DASHED LINE = SLOPED
MTL SILL FLASHING ABOVE,
FORM A PAN AS SHOWN IN
SECTION DETAIL AND RUN
BEHIND ENTIRE EXTENT
OF BELLOWS MEMBRANE
SOLID HEAVY LINE =
BELLOWS MEMBRANE ABOVE,
SEE DETAILS THIS PAGE
49 DARTMOUTH STREET
PORTLAND, ME 04101
207-775-1059 www.pdtarchs.com
ARCHITECTURE
INTERIOR DESIGN
PLANNING
Project Number
Building Number
Drawing NumberLocation
Project Title
Date Checked Drawn
Drawing Title
Approved: Project Director
Dwg:
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
1 2 3 4 5 6 7 8
A
B
C
D
E
VA FORM 08-6231, OCT 1978
on e e ig on e q ua rte r i on e h al f th re e e ig th re e q ua rte rs i
6" on e i
6" on e h a lf i nc f oo t 6"
Denis McLaughlin Telephone: 857-364-5149
1 2 3 4 5 6 7 8
Jamaica Plain, MA
A
B
C
D
E
M.E.P.:
Stantec 482 Payne Road Scarborough, ME 04074 T: (207) 883-3355 F: (207) 883-3376
SPECIFICATIONS:
Lowell Specifications, Inc.
34 Marc Avenue Topsham, ME 04086 T: (207) 406-4001
STRUCTURAL:
Becker Structural Engineers 75 York St Portland, ME 04101 T: (207) 879-1838 F: (207) 879-1822
CIVIL/LANDSCAPE:
Stantec Consulting 141 Portland St.
Boston, MA 02114 T: (617) 523-8103
AE Research Addition 523-307
0%
S
UB
MI
TT
AL
- B
ID
D
OC
UM
EN
TS
3-31-2016
Exterior Details
AS504
PNDW
3" = 1'-0"3 DETAIL AT STAIR 2 DOOR JAMB EXPANSION JOINT
3" = 1'-0"5 DETAIL AT STAIR 2 EXPANSION JOINT
3" = 1'-0"1 EXPANSION JOINT AT TOP OF FOUNDATION WALL
3" = 1'-0"2 FOUNDATION BELOW EXPANSION JOINT
E-A
E-4
EXISTING CONCRETE
COLUMN
NOTE: EJ COVER, BELLOWS AND OTHER COMPONENTS TURN
HORIZONTAL BELOW AT LEVEL OF EXISTING SOFFIT
REMOVE EXISTING FURRING CHANNEL
AND REPLACE WITH WD BLOCKING TO
ALLOW REINSTALLATION OF METAL PANEL
REMOVE AND REINSTALL EXISTING
METAL PANEL TO INSTALL NEW
BLDG EXPANSION JOINT
SEAL BELLOWS TO DAMP-PROOFING ON
FACE OF COL WITH LIQUID MEMBRANE
BLOCKING AS REQ FOR FASTENING OF MTL
CLOSURE TRIM
MTL CLOSURE TRIM TO MATCH
COLOR OF EXISTING MTL PANEL
9" +/-
BLOCKING FOR CLOSURE TRIM
FASTENING
SEAL BELLOWS TO AVB
BED BOTH SIDES
IN SEALANT,TYP
FACE OF BLOCKING THAT FRAMES THE
EXPANSION JOINT ALIGNS WITH BLOCKING IN
ROOF EXPANSION JOINT ABOVE - FASTEN TO
PLYWD/STL ANGLE
REMOVE SECTION OF EXISTING
MTL PANEL BEGINNING AT JOINT
PROVIDE 5X5 STL ANGLE THAT ALIGNS WITH
ANGLE IN ROOF EXPANSION JOINT DETAIL AT
ELEVATOR WALL - MOUNT ON BLOCKING
FASTENED TO EXISTING CONSTRUCTION -
ANGLE AND BLOCKING ARE TO RETURN
BELOW TO ALLOW FRAMING OF HORIZONTAL
EXPANSION JOINT AT THE LEVEL OF THE
THIRD FLOOR EXTERIOR SOFFIT
EJ COVER
PLATE
RESEAL EXISTING PANEL TO NEW
CLOSURE TRIM
PLYWD
SEALANT BETWEEN BLOCKING
AND BELLOWS, TYP
SEAL EJ COVER TO BELLOWS
AT BOTH SIDES, TYP
MINERAL WOOL INSULATION IN
GAP
SEALANT AT ALL BLOCKING
FASTENED THROUGH BELLOWS, TYP
FILL BELLOWS WITH
MINERAL WOOL INSUL, TYP
SHAFT WALL AS SCHEDULED
BENT CFMF CLOSURE TO CARRY SHAFT
WALL RATING TO EXTERIOR SHEATHING.
FASTEN TO 6" MTL STUD AND SHAFT WALL
TRACK AS SHOWN - INSTALL SHEATHING
ON EXTERIOR FACE AND FILL TRIANGULAR
VOID WITH MINERAL WOOL INSULATION
GWB FOR FULL HEIGHT OF BENT
CFMF CLOSURE
4"
FILL VOID BETWEEN EXISTING AND NEW
CONSTRUCTION WITH MINERAL WOOL INSUL FOR 2
FEET MINIMUM BEYOND EXPANSION JOINT, TYP
C
4" BLDG EJ COVER - EJ STOPS AT
FND/C-WALL SILL BELOW AND DOES
NOT CONTINUE THROUGH PRECAST
F.O. PRECAST BELOW
2X BLOCKING FOR EXPANSION
JOINT COVER ATTACHMENT EXPANSION JOINT WALL COVER
EXPANSION JOINT CLG
COVER ABOVE
EXISTING EXTERIOR COLUMN
WRAP AVB ONTO EXPANSION JOINT
BLOCKING AS SHOWN AND SEAL
TYPICAL FURRING SYSTEM
FOR OUTER ACM PANEL
BED IN
SEALANT
EPDM OR NEOPRENE BELLOWS,
SEAL OVER AVB ON WD BLOCKING
AND FILL WITH MINERAL WOOL INSUL
C
2X42X4
2X4
2X8
SE
E
AS
SE
M
BL
Y
TY
PE
S
FO
R
W
AL
L C
O M
PO
N
EN
TS
4"
DO NOT FASTEN ACM PANEL
THROUGH BELLOWS MEMBRANE
EXISTING EXTERIOR
COLUMN
SHAFT WALL AS SCHEDULED
2X BLOCKING FOR EXPANSION
JOINT COVER ATTACHMENT
WRAP AVB ONTO EXPANSION JOINT
BLOCKING AS SHOWN AND SEAL
BENT CFMF CLOSURE TO CARRY SHAFT
WALL RATING TO EXTERIOR SHEATHING.
FASTEN TO 6" MTL STUD AND SHAFT WALL
TRACK - INSTALL SHEATHING ON EXTERIOR
FACE AND FILL TRIANGULAR VOID WITH
MINERAL WOOL INSULATION
DO NOT FASTEN ACM PANEL
THROUGH BELLOWS MEMBRANE
GWB FOR FULL HEIGHT OF BENT
CFMF CLOSURE
EXPANSION JOINT CLG
COVER BELOW
7"4"
2X42X4
2X4
2X8
4" BLDG EJ COVER
EPDM OR NEOPRENE BELLOWS,
SEAL OVER AVB ON WD BLOCKING
AND FILL WITH MINERAL WOOL INSUL
EDGE OF SLAB BELOW
C
SE
E
AS
SE
M
BL
Y
TY
PE
S
FO
R
W
AL
L C
O M
PO
N
EN
TS
49 DARTMOUTH STREET
PORTLAND, ME 04101
207-775-1059 www.pdtarchs.com
ARCHITECTURE
INTERIOR DESIGN
PLANNING
Project Number
Building Number
Drawing NumberLocation
Project Title
Date Checked Drawn
Drawing Title
Approved: Project Director
Dwg:
ARCHITECT/ENGINEERS:CONSULTANTS:
DateRevisions:
1 2 3 4 5 6 7 8
A
B
C
D
E
VA FORM 08-6231, OCT 1978
on e e ig on e q ua rte r i on e h al f th re e e ig th re e q ua rte rs i
6" on e i
6" on e h a lf i nc f oo t 6"
Denis McLaughlin Telephone: 857-364-5149
1 2 3 4 5 6 7 8
Jamaica Plain, MA
A
B
C
D
E
M.E.P.:
Stantec 482 Payne Road Scarborough, ME 04074 T: (207) 883-3355 F: (207) 883-3376
SPECIFICATIONS:
Lowell Specifications, Inc.
34 Marc Avenue Topsham, ME 04086 T: (207) 406-4001
STRUCTURAL:
Becker Structural Engineers 75 York St Portland, ME 04101 T: (207) 879-1838 F: (207) 879-1822
CIVIL/LANDSCAPE:
Stantec Consulting 141 Portland St.
Boston, MA 02114 T: (617) 523-8103
AE Research Addition 523-307
0%
S
UB
MI
TT
AL
- B
ID
D
OC
UM
EN
TS
3-31-2016
Exterior Details
AS505
PNDW
3" = 1'-0"2 INTERIOR CORNER EXPANSION JOINT - THIRD FLOOR
3" = 1'-0"1 INTERIOR CORNER EXPANSION JOINT - FIRST FLOOR
3" = 1'-0"3 INTERIOR CORNER EXPANSION JOINT - SECOND FLOOR
2' - 2 1/2" +/- 5" +/-
LOCATE DOOR JAMB AS CLOSE TO
EXISTING CONC COL AS POSSIBLE
WITHOUT INTERFERING WITH
HANDRAIL OF NEW STAIR
MODIFY AND REINSTALL
EXISTING HANDRAIL AT NEW
DOOR JAMB
EXISTING 10" CONC COL
NOTE: GRAY HATCH REPRESENTS APPROXIMATE AREA
OF EXISTING CONSTRUCTION TO REMAIN. SELECTIVELY
DEMOLISH EXISTING EXTERIOR WALL AS REQ FOR NEW
DOOR - NEW INFILL FINISHES TO MATCH EXISTING
EXISTING GWB ON LG FURRING
EXISTING 8" INSULATED MTL
STUD
EXISTING 1/2" SHEATHING TO
REMAIN
DEMOLISH EXISTING EXTERIOR MTL
PANEL AND FURRING AS REQUIRED
TO INSTALL NEW DOOR
PROVIDE NEW 1-HR FIRE RATED
8" MTL STUD INFILL AT NEW HM
DOOR OPENING
SHAFT WALL PER PLAN, RETURN TO
NEW DOOR OPENING WITH 2 1/2"
LGMF AND TWO LAYERS GWB
STAIR 3 HANDRAIL AND TREADS
NEW HM DOOR AND FRAME AS
SCHEDULED, SEE TYPICAL DOOR
DETAILS FOR ADDITIONAL NOTES
DEMOLISH EXISTING CORNER
WINDOW UNIT AND ASSOCIATED
SUPPORT STRUCTURE AS REQ
TO INSTALL NEW INFILL WALL
INFILL WALL OF 6" LGMF AND
ACOUSTIC INSUL - PNT TO MATCH
EXISTING - USE 1/2" NON-PAPER-
FACED GWB SHEATHING ON EXTERIOR
AND 5/8" GWB ON INTERIOR
EXISTING PLYWOOD WINDOW SILL BELOW
WITH FINNED TUBE HEAT AND GRILL
11"
NEW GWB AND FURRING AS REQ
DEMOLISH EXISTING CORNER
WINDOW UNIT AND ASSOCIATED
SUPPORT STRUCTURE AS REQ
TO INSTALL NEW INFILL WALL
4"
4'
8"
PATCH CONSTRUCTION AS REQ
TO MATCH EXISTING FINISHES
NOTE: AT EXISTING THIRD FLOOR THE WINDOW INFILL
WALL IS A DIFFERENT - SEE SECTION FOR CORRECT
DETAIL AT THIS LOCATION
AS306
7 1/2" +/-
4"
2 HR FIRE-RATED FLOOR
EXPANSION JOINT
NOTE: GRAY HATCH REPRESENTS APPROXIMATE AREA
OF EXISTING CONSTRUCTION TO REMAIN. SELECTIVELY
DEMOLISH EXISTING EXTERIOR WALL AS REQ FOR NEW
DOOR - NEW INFILL FINISHES TO MATCH EXISTING
EXISTING GWB ON LG FURRING
EXISTING 8" INSULATED MTL STUD
EXISTING 1/2" SHEATHING TO REMAIN
DEMOLISH EXISTING EXTERIOR MTL
PANEL, FURRING, AND MTL STUD
BACKUP WALL AS REQ TO INSTALL NEW
DOOR AND EXPANSION JOINT
PROVIDE NEW 1-HR FIRE
RATED 8" MTL STUD INFILL
AT NEW HM DOOR OPENING
SHAFT WALL PER PLAN, RETURN TO
NEW DOOR OPENING WITH 2 1/2"
LGMF AND TWO LAYERS GWB
NEW GWB AND FURRING AS REQ
2 HR FLOOR ASSEMBLY - NEW
CONNECTOR STAIR LANDING AT
EXISTING FLOOR LEVEL
NEW HM DOOR AND FRAME AS
SCHEDULED, SEE TYPICAL DOOR
DETAILS FOR ADDITIONAL NOTES
FURRING CHANNEL ON
BEAM FOR SHAFT WALL
TRACK ANCHORAGE
SHAFT WALL
7" +/- VIF
SHAFT WALL
EXISTING OPENING IN
CONCRETE WALL FOR
EXISTING 8' EXTERIOR DOOR
SHAFT WALL PER PLAN
MODIFY AND REPAIR EXISTING
FINISHES AS REQ
EXISTING 8' HIGH STEEL DOOR
SYSTEM TO BE DEMOLISHED
2HR RATED EXPANSION JOINT AND
COVER - SHIM ATTACHMENT
SURFACES AS REQ TO FIT
2HR RATED INFILL OF MTL STUDS
AND TWO LAYERS GWB
ALIGN NEW AND EXISTING FINISH,
PAINT NEW TO MATCH EXISTING
EXISTING MTL PANEL SYSTEM TO BE
REMOVED AS REQ FOR
INSTALLATION OF NEW DOOR
4"
TO
E
XI
ST
IN
G
1" N
EW
L
AN
D
IN
G
2HR RATED FLOOR
EXPANSION JOINT
EXISTING CONCRETE
STRUCTURE AND FLOOR
REMOVE EXISTING METAL
PANEL AND FURRING
SYSTEM AS REQ
EXISTING DOOR SYSTEM TO BE
DEMOLISHED
BLOCKING AS REQ TO FASTEN
FLOOR EXPANSION JOINT COVER
CLOSURE ANGLE
NEW 7' HIGH DOOR SYSTEM AS
SCHEDULED
FLOOR EXPANSION JOINT COVER
7" +/-
49…