Hot Springs VA EHRM Upgrade Amendment 2 of 2.pdf
PDF 17 MB Posted
- Attached to
- Y1DA--568A4-21-702 EHRM Infrastructure Construction - Hot Springs, SD Federal contract opportunity
- Solicitation number
- 36C77622B0032
About this file
This solicitation seeks a general contractor to upgrade data cable infrastructure at the Hot Springs VA Medical Center in South Dakota. The scope of work includes demolishing over 14,000 phone lines, upgrading electrical panels and generators, renovating HVAC and fire suppression systems, migrating from 50 telecommunications rooms to 29, upgrading the data center, installing new cabling and outlets, and integrating physical security and the campus fiber network. Technical complexities arise from maintaining existing critical systems, phasing to minimize downtime, and reintegrating disconnected security and life safety functions. The contractor must furnish all labor, materials, equipment and supervision to complete infrastructure improvements across 20 buildings on the medical center campus.
View the file
Other files for this federal contract opportunity
Show all 32
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Appendix D: Telephone System 1987.pdf (See attached separate file).
Appendix E: B65 main floor switch plan – network.pdf (See attached separate file).
Appendix F: 001_Full Set of Plans_3-19-2012.pdf (See attached separate file).
Appendix G: Electrical One Lines.pdf (See attached separate file).
Appendix H: Revised drawing responses to technical questions (See attached separate file).
1 5/8" (1)
2 1/2" (2)
3 5/8" (3)
6" (6)
A SERIES PARTITION (GWB BOTH SIDES)
A
1 1/2" (1)
2 1/2" (2)
3 1/2" (3)
5 1/2" (6)
1 5/8" (1)
2 1/2" (2)
3 5/8" (3)
6" (6)
1 1/2" (1)
2 1/2" (2)
3 1/2" (3)
5 1/2" (6)
1 5/8" (1)
2 1/2" (2)
3 5/8" (3)
6" (6)
1 1/2" (1)
2 1/2" (2)
3 1/2" (3)
5 1/2" (6)
9 5/8" (10)
A-6
FIN. FLOOR, TYP
UNDERSIDE OF DECK
OR BEAM ABOVE, TYP
CONT SEALANT BOTH SIDES, TYP
(FIRE RATED SEALANT AT RATED
WALLS)
SYMBOL:
CONT SEALANT
BOTH SIDES, TYP
STUD SIZE
(w/ INHERENT FIRE RATING, IF ANY)
WALL TYPE
METAL STUD w/
5/8" GWB EACH SIDE
SLIP TRACK
A-6
FIN. FLOOR, TYP
UNDERSIDE OF DECK
OR BEAM ABOVE, TYP
CONT SEALANT BOTH SIDES, TYP
(FIRE RATED SEALANT AT RATED
WALLS)
SYMBOL:
CONT SEALANT
BOTH SIDES, TYP
WALL TYPE
WOOD STUD w/
5/8" GWB EACH SIDE
TOP PLATE(S)
STUD SIZE
(w/ INHERENT FIRE RATING, IF ANY)
BATT INSULATION or SOUND
BATTS (WHERE REQ'D)
BATT INSULATION or SOUND
BATTS (WHERE REQ'D)
2A-6
FIN. FLOOR, TYP
UNDERSIDE OF DECK
OR BEAM ABOVE, TYP
FIRE RATED CONT SEALANT
BOTH SIDES, TYP
SYMBOL:
CONT SEALANT
BOTH SIDES, TYP
STUD SIZE
(w/ INHERENT FIRE RATING, IF ANY)
WALL TYPE
METAL STUD w/
5/8" GWB EACH SIDE
SLIP TRACK
2A-6
FIN. FLOOR, TYP
UNDERSIDE OF DECK
OR BEAM ABOVE, TYP
FIRE RATED CONT SEALANT
BOTH SIDES, TYP
SYMBOL:
CONT SEALANT
BOTH SIDES, TYP
WALL TYPE
WOOD STUD w/
5/8" GWB EACH SIDE
TOP PLATE(S)
STUD SIZE
(w/ INHERENT FIRE RATING, IF ANY)
BATT INSULATION or SOUND
BATTS (WHERE REQ'D)
BATT INSULATION or SOUND
BATTS (WHERE REQ'D)
3A-6
FIN. FLOOR, TYP
UNDERSIDE OF DECK
OR BEAM ABOVE, TYP
FIRE RATED CONT SEALANT
BOTH SIDES, TYP
SYMBOL:
FIRE RATED CONT SEALANT
BOTH SIDES, TYP
STUD SIZE
(w/ INHERENT FIRE RATING, IF ANY)
WALL TYPE
METAL STUD w/
5/8" GWB EACH SIDE
SLIP TRACK
3A-6
FIN. FLOOR, TYP
UNDERSIDE OF DECK
OR BEAM ABOVE, TYP
FIRE RATED CONT SEALANT
BOTH SIDES, TYP
SYMBOL:
CONT SEALANT
BOTH SIDES, TYP
WALL TYPE
WOOD STUD w/
5/8" GWB EACH SIDE
TOP PLATE(S)
STUD SIZE
(w/ INHERENT FIRE RATING, IF ANY)
BATT INSULATION or SOUND
BATTS (WHERE REQ'D)
BATT INSULATION or SOUND
BATTS (WHERE REQ'D)
1A-6 1A-6or or
B SERIES PARTITION (GWB 1-SIDE)
B
C SERIES PARTITION (CONC)
C
D SERIES PARTITION (SHAFT)
D
M SERIES PARTITION (CMU)
M
NOT-RATED or 1-HOUR RATING (MTL) 2-HOUR RATING (MTL) 3-HOUR RATING (MTL)NOT-RATED or 1-HOUR RATING (WD) 2-HOUR RATING (WD) 3-HOUR RATING (WD)
1 5/8" (1)
2 1/2" (2)
3 5/8" (3)
6" (6)
1 1/2" (1)
2 1/2" (2)
3 1/2" (3)
5 1/2" (6)
1 5/8" (1)
2 1/2" (2)
3 5/8" (3)
6" (6) B-6
FIN. FLOOR, TYP
UNDERSIDE OF DECK
OR BEAM ABOVE, TYP
CONT SEALANT,
TYP
SYMBOL:
CONT SEALANT,
TYP
STUD SIZE
WALL TYPE
METAL STUD w/
5/8" GWB 1-SIDE
SLIP TRACK
B-6
FIN. FLOOR, TYP
UNDERSIDE OF DECK
OR BEAM ABOVE, TYP
CONT SEALANT,
TYP
SYMBOL:
CONT SEALANT,
TYP
WALL TYPE
WOOD STUD w/
5/8" GWB 1-SIDE
TOP PLATE(S)
STUD SIZE
BATT INSULATION or SOUND
BATTS (WHERE REQ'D)
BATT INSULATION or SOUND
BATTS (WHERE REQ'D)
2D-6
FIN. FLOOR, TYP
UNDERSIDE OF DECK
OR BEAM ABOVE, TYP
FIRE RATED CONT SEALANT
BOTH SIDES, TYP
SYMBOL:
CONT SEALANT
BOTH SIDES, TYP
STUD SIZE
(w/ INHERENT FIRE RATING, IF ANY)
WALL TYPE
METAL CH-STUD
SLIP TRACK
BATT INSULATION or SOUND
BATTS (WHERE REQ'D)
NOT-RATED (MTL) 2-HOUR RATING (MTL)NOT-RATED (WD)
TOP OF
WALL
CAST IN
PLACE
CONC
TOP OF
WALL
CONCRETE MASONRY
UNITS (CMU)
12" (12)
7 5/8" (8)10" (10)
5 5/8" (6)8" (8)
3 5/8" (4)6" (6)
C-8
SYMBOL:
WALL TYPE
STUD SIZE
(w/ INHERENT FIRE RATING, IF ANY)
2A-6
SYMBOL:
STUD SIZE
(w/ INHERENT FIRE RATING, IF ANY)
WALL TYPE
1" GWB SHAFT LINER
(2) LAYERS 5/8" GWB
VERTICAL ASSEMBLIES
UL DES U465 UL DES U411
NOTE:
PARTITIONS ARE NOTED TO INDICATE POTENTIAL
AREAS TO BE ENCOUNTERED; NEW PARTITIONS
ARE NOTED WITH ASSEMBLY MARKS IN FLOOR
PLANS.
CONCRETE SLAB ON GRADE,
REF STRUCTURAL
15 MIL. VAPOR PERMEABLE AIR
BARRIER
UNDERSLAB GRAVEL PER
STRUCTURAL DETAIL
FLOOR ASSEMBLY
F1
FLOOR ASSEMBLY
F2
METAL DECK, REF STRUCTURAL
STEEL BEAM, REF STRUCTURAL
CAST IN PLACE CONCRETE
MECHANICALLY FASTENED EPDM
ROOFING SYSTEM
METAL DECK, REF STRUCTURAL
5/8" TYPE 'X' GYPSUM BOARD
STEEL BEAM, REF STRUCTURAL
(2) LAYERS POLYISOCYANURATE INSULATION
BOARD, STAGGER JOINTS, 6" MIN
1/2" COVER BOARD
ROOF ASSEMBLY
R1
HORIZONTAL ASSEMBLIES
10MM VAPOR BARRIER
MECHANICALLY FASTENED
EPDM ROOFING MEMBRANE
5/8" PLYWOOD SHEATHING
STEEL FRAMING, REF STRUCTURAL
(2) LAYERS POLYISOCYANURATE INSULATION
BOARD, STAGGER JOINTS, 6" MIN
1/2" COVER BOARD
ROOF ASSEMBLY
R3
10MM VAPOR BARRIER
FIRE PROOFING, SEE PROJECT
CODE SUMMARY FOR UL
DESIGN NUMBER
FULLY ADHERED EPDM ROOFING
SYSTEM
METAL DECK, REF STRUCTURAL
5/8" TYPE 'X' GYPSUM BOARD
STEEL BEAM, REF STRUCTURAL
(2) LAYERS POLYISOCYANURATE INSULATION
BOARD, STAGGER JOINTS, 6" MIN
1/2" COVER BOARD
ROOF ASSEMBLY
R2
10MM VAPOR BARRIER
FIRE PROOFING, SEE PROJECT
CODE SUMMARY FOR UL
DESIGN NUMBER
ROOF ASSEMBLY
R4
5/8" TYPE 'X' GYPSUM BOARD
5/8" PLYWOOD SHEATHING
STEEL FRAMING, REF STRUCTURAL
ICE AND WATER SHIELD
5/8" TYPE 'X' GYPSUM BOARD
ASPHALT SHINGLES TO MATCH EXISTING
2" Z-GIRTS, EQUAL TO SMART ci
2 IN 1 PERPENDICULAR
1x3 WOOD FURRING @ 16" O.C.
INSULATION BAFFLE
R-21 BATT INSULATION
R-10 RIGID INSULATION
EXAMPLE: = 2-HOUR FIRE RATING (PER U.L. DESCRIPTION)
TYPE 'A' WALL
WITH 6" STUDS
TILE BACKER BOARD ( T )
ADDITIONAL WALL COMPONENTS:
L - LOW WALL
P - PARTIAL HEIGHT
S - SOUND BATTS
T - TILE BACKER BOARD
V - VAPOR PERMEABLE AIR BARRIER
W - WET WALL
TYPE (A - Z)
STUD/MATERIAL WIDTH
2 A - 6 T
FIRE RATING
2A-6T
WALL TYPE TAG LEGEND
E SERIES EXTERIOR WALL ASSEMBLIESE
6" METAL STUDS AT 16" O.C.
2" CLOSED CELL SPRAY INSULATION, R-14
1/2" PLYWOOD SHEATHING, R-0.45
2" MINERAL WOOL RIGID INSULATION, R-9.2
5/8" TYPE 'X' GYPSUM BOARD, R-0.56
VERTICALLY INSTALLED 2" Z-GIRTS
SPACED AS PER CEMENTITOUS PANEL
COURSING REQUIREMENTS EQUAL TO
SMART ci 2 IN 1
CEMENTITIIOUS SHINGLE PANELS,
MECHANICALLY FASTENED TO GIRTS
AIR BARRIER
5/8" 6"
1/2"
1/4"
2"
1/4" PRIMED, STRAIGHT EDGE PANEL
SHINGLE SIDING BY HARDIE, FIELD PAINT
EXTERIORINTERIOR
R FACTOR = 24.21
U FACTOR = 0.041
6E-11
5/8" 6" 1/2" 2" 2" VARIES
6E-66
EXTERIORINTERIOR
5/8" TYPE 'X' GYPSUM BOARD
R-0.56
CONTINUOUS RIGID INSULATION
R-10
2" AIR GAP
R FACTOR = 29.16
U FACTOR = 0.034
EXTERIOR FACE OF
CONCRETE FOUNDATION
2" CLOSED CELL SPRAY
INSULATION R-14
1/2" PLYWOOD SHEATHING
R-0.45
AIR BARRIER
STONE VENEER TO MATCH EXISITNG
VENEER
STAINLESS STEEL ANCHORS EVERY
6TH COURSE VERTICALLY, 16" O.C.
HORIZONTALLY
VERTICALLY INSTALLED 2" Z-
GIRTS AT 24" O.C. EQUAL TO
SMART ci 2 IN 1
6" METAL STUDS AT 16" O.C.
2" CLOSED CELL SPRAY INSULATION, R-14
1/2" DENSE GLASS SHEATHING, R-0.45
3" MINERAL WOOL RIGID INSULATION, R-14.4
5/8" TYPE 'X' GYPSUM BOARD, R-0.56
HORRIZONTALLY INSTALLED 3"
Z-GIRTS SPACED AT 24" O.C.
AND AS EQUAL TO SMART ci 2 IN
CEMENTITIOUS BOARD CLIPS,
MECHANICALLY FASTENED TO GIRTS
AIR BARRIER
5/8" 6"
1/2"
1/4" 3"
1 5/8" 3/8"
1' - 0 3/8"
8MM OR 10MM FIBER CEMENT PANELS
EXTERIORINTERIOR
R FACTOR = 29.01
U FACTOR = 0.034
6E-01
6" METAL STUDS AT 16" O.C.
2" CLOSED CELL SPRAY INSULATION, R-14
(2) LAYERS 5/8" TYPE 'X' GYPSUM
BOARD EACH SIDE OF STUDS, R=
2.24
3" MINERAL WOOL RIGID INSULATION, R-14.4
HORRIZONTALLY INSTALLED 3"
Z-GIRTS SPACED AT 24" O.C.
AND AS EQUAL TO SMART ci 2 IN
AIR BARRIER
5/8" 6 5/8"
5/8"
1/4" 3"
1 5/8" 3/8"
1' - 1 1/8"
8MM OR 10MM FIBER CEMENT PANELS
EXTERIORINTERIOR
R FACTOR = 30.64
U FACTOR = 0.033
2-6E-01
7" E X
P O
S U
R
EC
E
M E
N T
IT
IO
U S
P A
N E
L
1' - 3 1/4"
3/4" FURRING AT ATTACHMENT LOCATIONS OVER
1/4" DRAINAGE SHIM
U.S. Department of Veterans Affairs
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED BY DRAWN BY
DRAWING TITLE
APPROVED:
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FLS
PROGRAM
CONTRACTING
ACTIVITY
CENTRAL (PCAC)
B
IM
/2
V A
M e d ic a l C e n te r
H o t S p ri n g s S
D /2
G
E N
E R
A L
I N
F O r2
.r v t
/1
/2
:0
:1
P
M
00-GI-005
PROJECT ASSEMBLY TYPES
GDM
1000 W STEUBEN ST. UNIT 3
BINGEN, WA 98605
541.436.4723
ADAM GOODIN, PE
A&E DESIGN
124 NORTH 29TH STREET, #100
BILLINGS, MONTANA 59101
406.248.2633
T. MARCELLO PIERROTTET, AIA
EHRM INFRASTRUCTURE
UPGRADES
HOT SPRINGS, SOUTH DAKOTA
568A4-21-702
Project Director
AHTMP02/23/2022
100% CD FINAL
SOLUTION
ARCHITECTA/E:
FULLY SPRINKLERED
Revisions: Date:
Clarification 7-15-22
CLOSET
9A
TR
ITEM DESCRIPTION
24 PORT WAP PATCH PANEL1
24 PORT COPPER PATCH PANEL2
48 PORT COPPER PATCH PANEL3
96 PORT COPPER PATCH PANEL4
NETWORK SWITCH5
JOHNSON CONTROL PATCH PANEL6
CHECK POINT TEMPERATURE SENSOR7
CHECK POINT REPEATER8
MULTIMODE FIBER HOUSING9
BLOW IN FIBER HOUSING10
EXISTING TELECOM ROOM SCHEDULE
TELEPHONE PUNCHDOWN BLOCK11
NOTE
PLAN
NORTH
SITE LEGEND
U.S. Department of Veterans Affairs
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED BY DRAWN BY
DRAWING TITLE
APPROVED:
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FLS
PROGRAM
CONTRACTING
ACTIVITY
CENTRAL (PCAC)
JEREMY A. MAXIE
7/13/22
EE-113847
C U s e rs \C a le b K o p p \D o c u m e n ts
\R E
V
IT
L O
C A
L S
\M
E
S E
R
IE
S
B L
D G r2 c k o p p Q
G E
T M
.r v t
/1
/2
:3
:0
P
M
003-TD-0B2
TELECOM DEMOLITION PLAN -
BUILDING 3 ENLARGED PLANSGDM
1000 W STEUBEN ST. UNIT 3
BINGEN, WA 98605
541.436.4723
ADAM GOODIN, PE
EHRM INFRASTRUCTURE
UPGRADES
HOT SPRINGS, SOUTH DAKOTA
568A4-21-702
Project Director
CSZJAM7/13/2022
100% CD FINAL SOLUTIONA/E:
FULLY SPRINKLERED
1/2" = 1'-0"1 ENLARGED ROOM - B9A TELECOM DEMOLITION
1/2" = 1'-0"2 ENLARGED ROOM -103 TELECOM DEMOLITION
1/2" = 1'-0"3 ENLARGED ROOM - 203 TELECOM DEMOLITION
DETAIL NOTES:
1. DEMOLISH EQUIPMENT AND ALL CABLING.
2. EQUIPMENT TO REMAIN.
3. EQUIPMENT TO BE SALVAGED/REMOVED BY VA.
4. EQUIPMENT TO BE DEMOLISHED IF ALL FIELD CABLING IS
REMOVED, OTHERWISE TO REMAIN.
GENERAL NOTES:
A. SEE 003-TD-0B1 FOR GENERAL NOTES.
SHEET NOTES:
1. EXISTING TELECOM SPACE. DEMOLISH NETWORK PATCH PANELS, RACKS, AND
FIBER HOUSING. LEAVE OTHER SYSTEMS (DDC, ACCESS CONTROL, ETC)
UNLESS OTHERWISE NOTED.
2. ALL TELECOM DEVICES SHALL BE DEMOLISHED FROM ROOMS INTENDED TO BE
TELECOM ROOMS.
PLAN
NORTH
PLAN
NORTH
PLAN
NORTH
CONTRACTOR Q&A
48-PORT COPPER CONDUCTOR PANEL SHEET
PROJECT #: M1121 ROOM #: B1C PANEL #: TB12 *LIF? = LOCATED IN FIELD?
NO LABEL
BUILDING #: 1 RACK #:
48-PORT COPPER PATCH PANNEL
X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 B09-01 X PORT 13 B11-11 PORT 25 B11-3 X PORT 37 B102-01 X
PORT 2 B09-02 X PORT 14 B11-12 PORT 26 B11-4 X PORT 38 B102-02 X
PORT 3 B09-03 X PORT 15 B11-13 PORT 27 B11-5 X PORT 39 B102-03 X
PORT 4 B09-04 X PORT 16 B11-14 PORT 28 B11-6 X PORT 40 B102-04 X
PORT 5 B10-01 X PORT 17 B11-15 X PORT 29 103-01 X PORT 41 B102-05 X
PORT 6 B10-02 X PORT 18 B11-16 X PORT 30 103-02 X PORT 42 B102-06 X
PORT 7 B10-03 X PORT 19 B11-9 X PORT 31 103-03 X PORT 43 B102-07 X
PORT 8 B10-04 X PORT 20 B11-10 X PORT 32 103-04 X PORT 44 B102-08 X
PORT 9 B09A-01 X PORT 21 B11-19 X PORT 33 100-01 X PORT 45 B11-1 X
PORT 10 B09A-02 X PORT 22 B11-20 X PORT 34 100-02 X PORT 46 B11-2 X
PORT 11 B09-05 X PORT 23 B11-7 X PORT 35 100-03 X PORT 47
PORT 12 B09-06 X PORT 24 B11-8 X PORT 36 100-04 X PORT 48
48-PORT COPPER CONDUCTOR PANEL SHEET
PROJECT #: M1121 ROOM #: B1C PANEL #: *LIF? = LOCATED IN FIELD?
NO LABEL
BUILDING #: 1 RACK #:
48-PORT COPPER PATCH PANNEL
X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 B11-21 X PORT 13 PORT 25 PORT 37
PORT 2 B11-17 X PORT 14 PORT 26 PORT 38
PORT 3 B11-18 X PORT 15 PORT 27 PORT 39
PORT 4 PORT 16 PORT 28 PORT 40
PORT 5 PORT 17 PORT 29 PORT 41
PORT 6 PORT 18 PORT 30 PORT 42
PORT 7 PORT 19 PORT 31 PORT 43
PORT 8 PORT 20 PORT 32 PORT 44
PORT 9 PORT 21 PORT 33 PORT 45
PORT 10 PORT 22 PORT 34 PORT 46
PORT 11 PORT 23 PORT 35 PORT 47
PORT 12 PORT 24 PORT 36 PORT 48
48-PORT COPPER CONDUCTOR PANEL SHEET
PROJECT #: M1121 ROOM #: B1E PANEL #: TB12A *LIF? = LOCATED IN FIELD?
NO LABEL
BUILDING #: 001 RACK #:
48-PORT COPPER PATCH PANNEL
X X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 B1B-01 X PORT 13 B03-11 X PORT 25 B7-01 X PORT 37 107-3 X
PORT 2 B1B-02 X PORT 14 B03-12 X PORT 26 B7-02 X PORT 38 107-4 X
PORT 3 B03-01 X PORT 15 B5-3 X PORT 27 B7-03 X PORT 39 107-5 X
PORT 4 B03-02 X PORT 16 B5-4 X PORT 28 B7-04 X PORT 40 107-6 X
PORT 5 B03-03 X PORT 17 B4-01 X PORT 29 PORT 41 107-7 X
PORT 6 B03-04 X PORT 18 B4-02 X PORT 30 PORT 42 107-8 X
PORT 7 B03-05 X PORT 19 B5-01 X PORT 31 B1A-01 X PORT 43
PORT 8 B03-06 X PORT 20 B5-02 X PORT 32 B1A-02 X PORT 44
PORT 9 B03-07 X PORT 21 B6-01 X PORT 33 PORT 45
PORT 10 B03-08 X PORT 22 B6-02 X PORT 34 PORT 46
PORT 11 B03-09 X PORT 23 B6-03 X PORT 35 PORT 47
PORT 12 B03-10 X PORT 24 B6-04 X PORT 36 PORT 48
48-PORT COPPER CONDUCTOR PANEL SHEET
PROJECT #: M1121 ROOM #: B26 PANEL #: 1 *LIF? = LOCATED IN FIELD?
NO LABEL
BUILDING #: 1 RACK #:
48-PORT COPPER PATCH PANNEL
X X X X X X X X X X X X X X X X X X X X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 B20-01 X PORT 13 B22-05 X PORT 25 PORT 37
PORT 2 B20-02 X PORT 14 B22-06 X PORT 26 PORT 38
PORT 3 B20-03 X PORT 15 B22-07 X PORT 27 PORT 39
PORT 4 B20-04 X PORT 16 B22-08 X PORT 28 PORT 40
PORT 5 B19-01 X PORT 17 B21-01 X PORT 29 PORT 41
PORT 6 B19-02 X PORT 18 B21-02 X PORT 30 PORT 42
PORT 7 B19-03 X PORT 19 B24-01 X PORT 31 PORT 43
PORT 8 B19-04 X PORT 20 B24-02 X PORT 32 PORT 44
PORT 9 B22-01 X PORT 21 B24-03 X PORT 33 PORT 45
PORT 10 B22-02 X PORT 22 B24-04 X PORT 34 PORT 46
PORT 11 B22-03 X PORT 23 PORT 35 PORT 47
PORT 12 B22-04 X PORT 24 PORT 36 PORT 48
24-PORT COPPER CONDUCTOR PANEL SHEET
PROJECT #: M1121 ROOM #: 104B PANEL #: TB18A *LIF? = LOCATED IN FIELD?
BUILDING #: 1 RACK #:
24-PORT COPPER PATCH PANNEL
X X X X X X X X X X X X X X X X X X X X X X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 102A-1 PORT 7 104A-5 X PORT 13 104-05 X PORT 19 102-11 X
PORT 2 102A-2 PORT 8 104A-6 X PORT 14 104-06 X PORT 20 102-12 X
PORT 3 104A-1 X PORT 9 104-01 X PORT 15 103-05 X PORT 21 102-13 X
PORT 4 104A-2 X PORT 10 104-02 X PORT 16 103-06 X PORT 22 102-14 X
PORT 5 104A-3 X PORT 11 104-03 X PORT 17 102-09 X PORT 23 102A-3
PORT 6 104A-4 X PORT 12 104-04 X PORT 18 102-10 X PORT 24 102-15 X
24-PORT WIRELESS ACCESS POINT PANEL SHEET
PROJECT #: M1121 ROOM #: 104B PANEL #: *LIF? = LOCATED IN FIELD?
BUILDING #: 1 RACK #:
24-PORT WAP PANEL
X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 AP02 X PORT 7 PORT 13 PORT 19
PORT 2 AP03 X PORT 8 PORT 14 PORT 20
PORT 3 AP04 X PORT 9 PORT 15 PORT 21
PORT 4 PORT 10 PORT 16 PORT 22
PORT 5 PORT 11 PORT 17 PORT 23
PORT 6 PORT 12 PORT 18 PORT 24
U.S. Department of Veterans Affairs
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED BY DRAWN BY
DRAWING TITLE
APPROVED:
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FLS
PROGRAM
CONTRACTING
ACTIVITY
CENTRAL (PCAC)
JEREMY A. MAXIE
7/13/22
EE-113847
C U s e rs \C a le b K o p p \D o c u m e n ts
\R E
V
IT
L O
C A
L S
\M
E
S E
R
IE
S
B L
D G r2 c k o p p Q
G E
T M
.r v t
/1
/2
:3
:2
P
M
TK-108
PATCH PANEL SCHEDULES
GDM
1000 W STEUBEN STR, UNIT 3
BINGEN,WA 98605
541.436.4723
ADAM GOODIN, PE
EHRM INFRASTRUCTURE
UPGRADES
HOT SPRINGS, SOUTH DAKOTA
568A4-21-702
N/A
Project Director
CKJAM07/13/2022
100% CD FINAL SOLUTIONA/E:
FULLY SPRINKLERED
PROJECT #: M1121 ROOM #: BASEMENT PANEL #: *LIF? = LOCATED IN FIELD?
NO LABEL
BUILDING #: 6 RACK #: TB26A ILLEGIBLE
48-PORT COPPER PATCH PANNEL
X X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 07-01 X PORT 13 06-01 X PORT 25 10-03 X PORT 37 103-01 X
PORT 2 07-02 X PORT 14 06-02 X PORT 26 10-04 X PORT 38 103-02 X
PORT 3 07-03 PORT 15 06-03 X PORT 27 5A-01 PORT 39 201-01 X
PORT 4 07-04 PORT 16 06-04 X PORT 28 5A-02 PORT 40 201-02 X
PORT 5 08-01 X PORT 17 06-05 X PORT 29 107-01? PORT 41 2XX-01?
PORT 6 08-02 X PORT 18 06-06 X PORT 30 107-02? PORT 42
PORT 7 08-03 X PORT 19 06-07 X PORT 31 101-01 PORT 43 203-01
PORT 8 08-04 X PORT 20 06-08 X PORT 32 101-02 PORT 44 203-02
PORT 9 08-05 ? PORT 21 06-09? X PORT 33 101-03? X PORT 45
PORT 10 08-06 ? PORT 22 06-10? X PORT 34 101-04? X PORT 46 104-01? X
PORT 11 08-07 ? PORT 23 10-01 X PORT 35 102-01 X PORT 47 104-02 X
PORT 12 08-08 ? PORT 24 10-02 X PORT 36 102-02 X PORT 48
24-PORT COPPER CONDUCTOR PANEL SHEET
PROJECT #: M1121 ROOM #: BASEMENT PANEL #: *LIF? = LOCATED IN FIELD?
NO LABEL
BUILDING #: 6 RACK #: ILLEGIBLE
24-PORT COPPER PATCH PANEL
X X X X X X X X X X X X X X X X X X X X X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 210-1 X PORT 7 211-3 X PORT 13 212-5 X PORT 19 05-D1B? X
PORT 2 210-2 X PORT 8 211-4 X PORT 14 212-6 X PORT 20 05-D1C? X
PORT 3 210-3 X PORT 9 212-1 X PORT 15 212A-1 X PORT 21 05-D2A? X
PORT 4 210-4 X PORT 10 212-2 X PORT 16 212A-2 X PORT 22 05-D2B X
PORT 5 211-1 X PORT 11 212-3 X PORT 17 05-DXX(1?) PORT 23 05-D2C? X
PORT 6 211-2 X PORT 12 212-4 X PORT 18 05-D1A X PORT 24
24-PORT WIRELESS ACCESS POINT PANEL SHEET
PROJECT #: M1121 ROOM #: BASEMENT PANEL #: *LIF? = LOCATED IN FIELD?
NO LABEL
BUILDING #: 6 RACK #: ILLEGIBLE
24-PORT WAP PANEL
X X X X X X X X X X X X X X X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 B6-FB1-AP01? PORT 7 B6-FB1-AP07 PORT 13 PORT 19
PORT 2 B6-FB1-AP02? X PORT 8 B6-FB1-AP08? X PORT 14 PORT 20
PORT 3 B6-FB1-AP03? X PORT 9 B6-FB1-AP09? X PORT 15 PORT 21 05-D4 X
PORT 4 B6-FB1-AP04? PORT 10 B6-FB1-AP10? X PORT 16 PORT 22 05-D5 X
PORT 5 B6-FB1-AP05? X PORT 11 B6-FB1-AP11? X PORT 17 PORT 23 05-D6? X
PORT 6 B6-FB1-AP06? X PORT 12 PORT 18 PORT 24 05-D7? X
48-PORT COPPER CONDUCTOR PANEL SHEET
PROJECT #: M1121 ROOM #: Basement 13 PANEL #: *LIF? = LOCATED IN FIELD?
NO LABEL
BUILDING #: 8 RACK #: TC28A
48-PORT COPPER PATCH PANNEL
X X X X X X X X X X X X X X X X X X
X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 01-01 X PORT 13 107-01 PORT 25 B5-1 PORT 37
PORT 2 01-02 X PORT 14 107-02 PORT 26 B5-2 PORT 38
PORT 3 11-01 PORT 15 108-01 X PORT 27 PORT 39
PORT 4 11-02 PORT 16 108-02 X PORT 28 PORT 40
PORT 5 12-01 X PORT 17 209-01 X PORT 29 PORT 41
PORT 6 12-02 X PORT 18 209-02 X PORT 30 PORT 42
PORT 7 12-03 X PORT 19 PORT 31 PORT 43
PORT 8 12-04 X PORT 20 PORT 32 PORT 44
PORT 9 12-05 PORT 21 PORT 33 PORT 45
PORT 10 12-06 PORT 22 PORT 34 PORT 46
PORT 11 12-07 X PORT 23 PORT 35 PORT 47
PORT 12 12-08 X PORT 24 PORT 36 PORT 48
24-PORT COPPER CONDUCTOR PANEL SHEET
PROJECT #: M1121 ROOM #: BASEMENT 13 PANEL #: *LIF? = LOCATED IN FIELD?
BUILDING #: 8 RACK #:
24-PORT COPPER PATCH PANEL
X X X X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 106D1 X PORT 7 PORT 13 PORT 19
PORT 2 106D2 X PORT 8 PORT 14 PORT 20
PORT 3 207D1 X PORT 9 PORT 15 PORT 21
PORT 4 207D2 X PORT 10 PORT 16 PORT 22
PORT 5 208D1 PORT 11 PORT 17 PORT 23
PORT 6 208D2 PORT 12 PORT 18 PORT 24
24-PORT WIRELESS ACCESS POINT PANEL SHEET
PROJECT #: M1121 ROOM #: BASEMENT 13 PANEL #: *LIF? = LOCATED IN FIELD?
BUILDING #: 8 RACK #:
24-PORT WAP PANEL
X X X X X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 B8-FB1 AP01 X PORT 7 B8-FB1 AP07 X PORT 13 PORT 19
PORT 2 B8-FB1 AP02 PORT 8 PORT 14 PORT 20
PORT 3 B8-FB1 AP03 PORT 9 PORT 15 PORT 21
PORT 4 B8-FB1 AP04 X PORT 10 PORT 16 PORT 22
PORT 5 B8-FB1 AP05 PORT 11 PORT 17 PORT 23
PORT 6 B8-FB1 AP06 X PORT 12 PORT 18 PORT 24
U.S. Department of Veterans Affairs
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED BY DRAWN BY
DRAWING TITLE
APPROVED:
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FLS
PROGRAM
CONTRACTING
ACTIVITY
CENTRAL (PCAC)
JEREMY A. MAXIE
7/13/22
EE-113847
C U s e rs \C a le b K o p p \D o c u m e n ts
\R E
V
IT
L O
C A
L S
\M
E
S E
R
IE
S
B L
D G r2 c k o p p Q
G E
T M
.r v t
/1
/2
:3
:2
P
M
TK-113
PATCH PANEL SCHEDULES
GDM
1000 W STEUBEN STR, UNIT 3
BINGEN,WA 98605
541.436.4723
ADAM GOODIN, PE
EHRM INFRASTRUCTURE
UPGRADES
HOT SPRINGS, SOUTH DAKOTA
568A4-21-702
N/A
Project Director
CKJAM07/13/2022
100% CD FINAL SOLUTIONA/E:
FULLY SPRINKLERED
96-PORT COPPER CONDUCTOR PANEL SHEET
PROJECT #: M1121 ROOM #: B08C PANEL #: *LIF? = LOCATED IN FIELD?
NO LABEL
BUILDING #: 12 RACK #:
96-PORT COPPER PATCH PANNEL
X X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 AB08-1 PORT 25 AB08-25 PORT 49 AB08-49 PORT 73 AB8A-5
PORT 2 AB08-2 PORT 26 AB08-26 PORT 50 AB08-50 PORT 74 AB8A-6
PORT 3 AB08-3 PORT 27 AB08-27 PORT 51 AB08-51 PORT 75 AB8A-7
PORT 4 AB08-4 PORT 28 AB08-28 PORT 52 AB08-52 PORT 76 AB8A-8
PORT 5 AB08-5 PORT 29 AB08-29 PORT 53 AB08-53 PORT 77 AB8-69
PORT 6 AB08-6 PORT 30 AB08-30 PORT 54 AB08-54 PORT 78 AB8-70
PORT 7 AB08-7 PORT 31 AB08-31 PORT 55 AB08-55 PORT 79 AB8-71
PORT 8 AB08-8 PORT 32 AB08-32 PORT 56 AB08-56 PORT 80 AB8-72
PORT 9 AB08-9 PORT 33 AB08-33 PORT 57 AB08-57 PORT 81 AB8B-1
PORT 10 AB08-10 PORT 34 AB08-34 PORT 58 AB08-58 PORT 82 AB8B-2
PORT 11 AB08-11 PORT 35 AB08-35 PORT 59 AB08-59 PORT 83 AB8B-3
PORT 12 AB08-12 PORT 36 AB08-36 PORT 60 AB08-60 PORT 84 AB8B-4
PORT 13 AB08-13 PORT 37 AB08-37 PORT 61 AB08-61 PORT 85 AB8B-5
PORT 14 AB08-14 PORT 38 AB08-38 PORT 62 AB08-62 PORT 86 AB8B-6
PORT 15 AB08-15 PORT 39 AB08-39 PORT 63 AB08-63 PORT 87 AB12A-1
PORT 16 AB08-16 PORT 40 AB08-40 PORT 64 AB08-64 PORT 88 AB12A-2
PORT 17 AB08-17 PORT 41 AB08-41 PORT 65 AB08-65 PORT 89 AB12A-3
PORT 18 AB08-18 PORT 42 AB08-42 PORT 66 AB08-66 PORT 90 AB12A-4
PORT 19 AB08-19 PORT 43 AB08-43 PORT 67 AB08-67 PORT 91 A014-5
PORT 20 AB08-20 PORT 44 AB08-44 PORT 68 AB08-68 PORT 92 A014-6
PORT 21 AB08-21 PORT 45 AB08-45 PORT 69 AB8A-1 PORT 93 A014-7
PORT 22 AB08-22 PORT 46 AB08-46 PORT 70 AB8A-2 PORT 94 A014-8
PORT 23 AB08-23 PORT 47 AB08-47 PORT 71 AB8A-3 PORT 95 A014-9
PORT 24 AB08-24 PORT 48 AB08-48 PORT 72 AB8A-4 PORT 96 A014-10
48-PORT COPPER CONDUCTOR PANEL SHEET
PROJECT #: M1121 ROOM #: B08C PANEL #: *LIF? = LOCATED IN FIELD?
NO LABEL
BUILDING #: 12 RACK #: ILLEGIBLE
48-PORT COPPER PATCH PANNEL
X X X X X X X X X X X X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 A14-11 PORT 13 A14-23 PORT 25 PORT 37
PORT 2 A14-12 PORT 14 A14-24 PORT 26 PORT 38
PORT 3 A14-13 PORT 15 PORT 27 PORT 39
PORT 4 A14-14 PORT 16 PORT 28 PORT 40
PORT 5 A14-15 PORT 17 PORT 29 PORT 41
PORT 6 A14-16 PORT 18 PORT 30 PORT 42
PORT 7 A14-17 PORT 19 PORT 31 PORT 43
PORT 8 A14-18 PORT 20 PORT 32 PORT 44
PORT 9 A14-19 PORT 21 PORT 33 PORT 45
PORT 10 A14-20 PORT 22 PORT 34 PORT 46
PORT 11 A14-21 PORT 23 PORT 35 PORT 47
PORT 12 A14-22 PORT 24 PORT 36 PORT 48
24-PORT WIRELESS ACCESS POINT SHEET
PROJECT #: M1121 ROOM #: B08C PANEL #: *LIF? = LOCATED IN FIELD?
NO LABEL
BUILDING #: 12 RACK #: ILLEGIBLE
24-PORT WAP PANEL
X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 B12-FB1-AP19 PORT 7 PORT 13 PORT 19
PORT 2 B12-FB1-AP20 PORT 8 PORT 14 PORT 20
PORT 3 B12-FB1-AP21 PORT 9 PORT 15 PORT 21
PORT 4 PORT 10 PORT 16 PORT 22
PORT 5 PORT 11 PORT 17 PORT 23
PORT 6 PORT 12 PORT 18 PORT 24
48-PORT COPPER CONDUCTOR PANEL SHEET
PROJECT #: M1121 ROOM #: B10B PANEL #: *LIF? = LOCATED IN FIELD?
NO LABEL
BUILDING #: 12 RACK #: ILLEGIBLE
48-PORT COPPER PATCH PANNEL
X X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 AB05-1 PORT 13 AB14-5 PORT 25 AB14A-5 PORT 37 AB16-1
PORT 2 AB05-2 PORT 14 AB14-6 PORT 26 AB14A-6 PORT 38 AB16-2
PORT 3 AB07-1 PORT 15 AB14-7 PORT 27 AB14B-1 PORT 39 AB16-3
PORT 4 AB07-2 PORT 16 AB14-8 PORT 28 AB14B-2 PORT 40 AB16-4
PORT 5 AB07-3 PORT 17 AB14-1 PORT 29 AB14B-4 PORT 41 AB16-5
PORT 6 AB07-4 PORT 18 AB14-2 PORT 30 AB14B-3 PORT 42 AB16-6
PORT 7 AB10-1 PORT 19 AB14-3 PORT 31 AB14B-5 PORT 43 AB16A-1
PORT 8 AB10-2 PORT 20 AB14-4 PORT 32 AB14B-8 PORT 44 AB16A-2
PORT 9 AB13-1 PORT 21 AB14A-1 PORT 33 AB14B-7 PORT 45 AB16A-3
PORT 10 AB13-2 PORT 22 AB14A-2 PORT 34 AB14B-6 PORT 46 AB16A-4
PORT 11 AB13-3 PORT 23 AB14A-3 PORT 35 AB15-1 PORT 47 AB16A-5
PORT 12 AB13-4 PORT 24 AB14A-4 PORT 36 AB15-2 PORT 48 AB16A-6
24-PORT COPPER CONDUCTOR PANEL SHEET
PROJECT #: M1121 ROOM #: 10B PANEL #: *LIF? = LOCATED IN FIELD?
BUILDING #: 12 RACK #:
24-PORT COPPER PATCH PANEL
X X X X X X X X X X X X X X X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 AB16B-1 PORT 7 AB18A-1 PORT 13 A006-6 PORT 19
PORT 2 AB16B-2 PORT 8 AB18A-2 PORT 14 AB12B-1 PORT 20
PORT 3 AB18B-3 PORT 9 AB18B-1 PORT 15 AB12B-2 PORT 21
PORT 4 AB18B-4 PORT 10 AB18B-2 PORT 16 AB12B-3 PORT 22
PORT 5 AB18B-5 PORT 11 A006-4 PORT 17 AB12B-4 PORT 23
PORT 6 AB18-6 PORT 12 A006-5 PORT 18 PORT 24
24-PORT WIRELESS ACCESS POINT PANEL SHEET
PROJECT #: M1121 ROOM #: 105 PANEL #: F01 *LIF? = LOCATED IN FIELD?
NO LABEL
BUILDING #: 65 RACK #: ILLEGIBLE
24-PORT WAP PANEL
X X X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 AP-1 PORT 7 PORT 13 PORT 19
PORT 2 AP-2 PORT 8 PORT 14 PORT 20
PORT 3 AP-3 PORT 9 PORT 15 PORT 21
PORT 4 AP-4 PORT 10 PORT 16 PORT 22
PORT 5 AP-5 PORT 11 PORT 17 PORT 23
PORT 6 PORT 12 PORT 18 PORT 24
U.S. Department of Veterans Affairs
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED BY DRAWN BY
DRAWING TITLE
APPROVED:
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FLS
PROGRAM
CONTRACTING
ACTIVITY
CENTRAL (PCAC)
JEREMY A. MAXIE
7/13/22
EE-113847
C U s e rs \C a le b K o p p \D o c u m e n ts
\R E
V
IT
L O
C A
L S
\M
E
S E
R
IE
S
B L
D G r2 c k o p p Q
G E
T M
.r v t
/1
/2
:3
:3
P
M
TK-117
PATCH PANEL SCHEDULES
GDM
1000 W STEUBEN STR, UNIT 3
BINGEN,WA 98605
541.436.4723
ADAM GOODIN, PE
EHRM INFRASTRUCTURE
UPGRADES
HOT SPRINGS, SOUTH DAKOTA
568A4-21-702
N/A
Project Director
CKJAM07/13/2022
100% CD FINAL SOLUTIONA/E:
FULLY SPRINKLERED
24-PORT COPPER CONDUCTOR PANEL SHEET
PROJECT #: M1121 ROOM #: 10B PANEL #: *LIF? = LOCATED IN FIELD?
BUILDING #: 12 RACK #:
24-PORT COPPER PATCH PANEL
X X X X X X X X X X X X X X X X X X X X X X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 AB14-1 PORT 7 AB16-3 PORT 13 AB15-1 PORT 19 AB05-3
PORT 2 AB14-2 PORT 8 AB16-4 PORT 14 AB15-2 PORT 20 AB05-4
PORT 3 AB14-3 PORT 9 AB20-1 PORT 15 AB15-3 PORT 21 AB05-5
PORT 4 AB14-4 PORT 10 AB20-2 PORT 16 AB15-04 PORT 22 AB05-6
PORT 5 AB16-1 PORT 11 AB20-3 PORT 17 AB05-1 PORT 23 AB05-7
PORT 6 AB16-2 PORT 12 AB20-4 PORT 18 AB05-2 PORT 24 AB05-8
48-PORT COPPER CONDUCTOR PANEL SHEET
PROJECT #: M1121 ROOM #: 10B PANEL #: *LIF? = LOCATED IN FIELD?
NO LABEL
BUILDING #: 12 RACK #: ILLEGIBLE
48-PORT COPPER PATCH PANNEL
X X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 AB03-1 PORT 13 AB02-1 PORT 25 AB21-1 PORT 37
PORT 2 AB03-2 PORT 14 AB02-2 PORT 26 AB06-5 PORT 38
PORT 3 AB03-3 PORT 15 AB04-1 PORT 27 AB06-6 PORT 39
PORT 4 AB03-4 PORT 16 AB04-2 PORT 28 AB06-7 PORT 40
PORT 5 AB03-5 PORT 17 AB04-3 PORT 29 AB06-8 PORT 41
PORT 6 AB03-6 PORT 18 AB04-4 PORT 30 AB06-9 PORT 42
PORT 7 AB3A-1 PORT 19 AB04-5 PORT 31 AB10-1 PORT 43
PORT 8 AB3A-2 PORT 20 AB04-6 PORT 32 AB10-2 PORT 44
PORT 9 AB3A-3 PORT 21 AB06-1 PORT 33 PORT 45
PORT 10 AB3A-4 PORT 22 AB06-2 PORT 34 PORT 46
PORT 11 AB12-1 PORT 23 AB06-3 PORT 35 PORT 47
PORT 12 AB12-2 PORT 24 AB06-4 PORT 36 PORT 48
24-PORT WIRELESS ACCESS POINT PANEL SHEET
PROJECT #: M1121 ROOM #: 10B PANEL #: *LIF? = LOCATED IN FIELD?
NO LABEL
BUILDING #: 12 RACK #: ILLEGIBLE
24-PORT WAP PANEL
X X X X X X X X X X X X X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 B12-FB1-11 PORT 7 B12-FB1-AP17 PORT 13 B12-FB1-AP28 PORT 19
PORT 2 B12-FB1-12 PORT 8 B12-FB1-AP18 PORT 14 B12-FB1-AP29 PORT 20
PORT 3 B12-FB1-13 PORT 9 B12-FB1-AP23 PORT 15 B12-FB1-AP30 PORT 21
PORT 4 B12-FB1-14 PORT 10 B12-FB1-AP24 PORT 16 PORT 22
PORT 5 B12-FB1-15 PORT 11 B12-FB1-AP25 PORT 17 PORT 23
PORT 6 B12-FB1-16 PORT 12 B12-FB1-AP26 PORT 18 PORT 24
48-PORT COPPER CONDUCTOR PANEL SHEET
PROJECT #: M1121 ROOM #: C006 PANEL #: *LIF? = LOCATED IN FIELD?
NO LABEL
BUILDING #: 12 RACK #: ILLEGIBLE
48-PORT COPPER PATCH PANNEL
X X X X X
X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 D018-1 PORT 13 PORT 25 C012-1 PORT 37 D007-1
PORT 2 C004-1 PORT 14 PORT 26 PORT 38
PORT 3 A002-1 PORT 15 PORT 27 PORT 39
PORT 4 PORT 16 PORT 28 PORT 40
PORT 5 PORT 17 PORT 29 PORT 41
PORT 6 A002-4 PORT 18 PORT 30 PORT 42
PORT 7 PORT 19 PORT 31 D015-1 PORT 43
PORT 8 PORT 20 PORT 32 PORT 44
PORT 9 PORT 21 PORT 33 PORT 45
PORT 10 D016-3 PORT 22 PORT 34 PORT 46
PORT 11 PORT 23 PORT 35 PORT 47
PORT 12 PORT 24 PORT 36 PORT 48
48-PORT COPPER CONDUCTOR PANEL SHEET
PROJECT #: M1121 ROOM #: C006 PANEL #: *LIF? = LOCATED IN FIELD?
NO LABEL
BUILDING #: 12 RACK #: ILLEGIBLE
48-PORT COPPER PATCH PANNEL
X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 BA103-1 PORT 13 PORT 25 B011-5 PORT 37 B007-1
PORT 2 BA103-2 PORT 14 PORT 26 B011-6 PORT 38 B007-2
PORT 3 PORT 15 B011A-1 PORT 27 B011-7 PORT 39 B007-3
PORT 4 PORT 16 B011A-2 PORT 28 B011-8 PORT 40 B007-4
PORT 5 PORT 17 B011A-3 PORT 29 B011B-1 PORT 41 B007-5
PORT 6 PORT 18 B011A-4 PORT 30 B011B-2 PORT 42 B007-6
PORT 7 PORT 19 B011A-5 PORT 31 B011B-3 PORT 43 B007-7
PORT 8 PORT 20 B011A-6 PORT 32 B011B-4 PORT 44 B007-8
PORT 9 PORT 21 B011-1 PORT 33 B011B-5 PORT 45 B009A-1
PORT 10 PORT 22 B011-2 PORT 34 B011B-6 PORT 46 B009A-2
PORT 11 PORT 23 B011-3 PORT 35 B005A-1 PORT 47 B009A-3
PORT 12 PORT 24 B011-4 PORT 36 B005A-2 PORT 48 B009A-4
U.S. Department of Veterans Affairs
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED BY DRAWN BY
DRAWING TITLE
APPROVED:
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FLS
PROGRAM
CONTRACTING
ACTIVITY
CENTRAL (PCAC)
JEREMY A. MAXIE
7/13/22
EE-113847
C U s e rs \C a le b K o p p \D o c u m e n ts
\R E
V
IT
L O
C A
L S
\M
E
S E
R
IE
S
B L
D G r2 c k o p p Q
G E
T M
.r v t
/1
/2
:3
:3
P
M
TK-118
PATCH PANEL SCHEDULES
GDM
1000 W STEUBEN STR, UNIT 3
BINGEN,WA 98605
541.436.4723
ADAM GOODIN, PE
EHRM INFRASTRUCTURE
UPGRADES
HOT SPRINGS, SOUTH DAKOTA
568A4-21-702
N/A
Project Director
CKJAM07/13/2022
100% CD FINAL SOLUTIONA/E:
FULLY SPRINKLERED
PROJECT #: M1121 ROOM #: C006 PANEL #: *LIF? = LOCATED IN FIELD?
NO LABEL
BUILDING #: 12 RACK #:
96-PORT COPPER PATCH PANNEL
X X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 B001-1 PORT 25 B11A-3 PORT 49 B010-3 PORT 73 C004-3
PORT 2 B001-2 PORT 26 B11A-4 PORT 50 B010-4 PORT 74 C004-4
PORT 3 B001-3 PORT 27 B011-1 PORT 51 B08B-1 PORT 75 C004-5
PORT 4 B001-4 PORT 28 B011-2 PORT 52 B08B-2 PORT 76 C004-6
PORT 5 B001-5 PORT 29 B011-3 PORT 53 B08B-3 PORT 77 C007-1
PORT 6 B001-6 PORT 30 B011-4 PORT 54 B08B-4 PORT 78 C007-2
PORT 7 B05A-1 PORT 31 B11B-1 PORT 55 B08B-5 PORT 79 C007-3
PORT 8 B05A-2 PORT 32 B11B-2 PORT 56 B08B-6 PORT 80 C007-4
PORT 9 B05A-3 PORT 33 B11B-3 PORT 57 B008-1 PORT 81 C007-5
PORT 10 B05A-4 PORT 34 B11B-4 PORT 58 B008-2 PORT 82 C008-5
PORT 11 B007-1 PORT 35 B017-1 PORT 59 B008-3 PORT 83 C008-6
PORT 12 B007-2 PORT 36 B017-2 PORT 60 B008-4 PORT 84 C010-1
PORT 13 B007-3 PORT 37 B017-3 PORT 61 B008-5 PORT 85 C010-2
PORT 14 B007-4 PORT 38 B017-4 PORT 62 B008-6 PORT 86 C011-1
PORT 15 B007-5 PORT 39 B014-1 PORT 63 B006-1 PORT 87 C011-2
PORT 16 B007-6 PORT 40 B014-2 PORT 64 B006-2 PORT 88 C012-1
PORT 17 B007-7 PORT 41 B10B-1 PORT 65 B004-1 PORT 89 C012-2
PORT 18 B007-8 PORT 42 B10B-2 PORT 66 B004-2 PORT 90 C012-3
PORT 19 B09A-1 PORT 43 B10B-3 PORT 67 B004-3 PORT 91 C012-4
PORT 20 B09A-2 PORT 44 B10B-4 PORT 68 B004-4 PORT 92 C012-5
PORT 21 B11A-1 PORT 45 B10A-1 PORT 69 B002-1 PORT 93 C012-6
PORT 22 B11A-2 PORT 46 B10A-2 PORT 70 B002-2 PORT 94
PORT 23 B09-1 PORT 47 B010-1 PORT 71 C004-1 PORT 95
PORT 24 B09-2 PORT 48 B010-2 PORT 72 C004-2 PORT 96
48-PORT COPPER CONDUCTOR PANEL SHEET
PROJECT #: M1121 ROOM #: C006 PANEL #: *LIF? = LOCATED IN FIELD?
NO LABEL
BUILDING #: 12 RACK #: ILLEGIBLE
48-PORT COPPER PATCH PANNEL
X X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 C01A-3 PORT 13 C002-1 PORT 25 B004-05 PORT 37 B006-3
PORT 2 C01A-4 PORT 14 C002-2 PORT 26 B004-06 PORT 38 B006-4
PORT 3 C01A-5 PORT 15 C002-3 PORT 27 B004-07 PORT 39 B004-D1
PORT 4 C01A-6 PORT 16 C002-4 PORT 28 B004-08 PORT 40 B004-D2
PORT 5 C001-1 PORT 17 C003-1 PORT 29 B004-09 PORT 41 B007-9
PORT 6 C001-2 PORT 18 C003-2 PORT 30 B004-10 PORT 42 B007-10
PORT 7 C001-3 PORT 19 C007-3 PORT 31 B004-11 PORT 43 B007-9
PORT 8 C001-4 PORT 20 B010A-1 PORT 32 B004-12 PORT 44 B007-10
PORT 9 C01B-1 PORT 21 B010A-2 PORT 33 B004-13 PORT 45 B007-11
PORT 10 C01B-2 PORT 22 PORT 34 B004-14 PORT 46 B007-12
PORT 11 C01B-3 PORT 23 PORT 35 B004-15 PORT 47
PORT 12 C01B-4 PORT 24 PORT 36 B004-16 PORT 48
24-PORT COPPER CONDUCTOR PANEL SHEET
PROJECT #: M1121 ROOM #: C006 PANEL #: *LIF? = LOCATED IN FIELD?
BUILDING #: 12 RACK #:
24-PORT COPPER PATCH PANEL
X X X X X X X X X X X X X X X X X X X X X X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 B010-1 PORT 7 B004-5 PORT 13 B004-11 PORT 19 B12-FG1-AP14
PORT 2 B010-2 PORT 8 B004-6 PORT 14 B12-FG1-AP09 PORT 20 B12-FG1-AP15
PORT 3 B010-3 PORT 9 B004-7 PORT 15 B12-FG1-AP10 PORT 21 B12-FG1-AP16
PORT 4 B010-4 PORT 10 B004-8 PORT 16 B12-FG1-AP11 PORT 22 B12-FG1-AP17
PORT 5 B010-5 PORT 11 B004-9 PORT 17 B12-FG1-AP12 PORT 23 B12-FG1-AP18
PORT 6 B010-6 PORT 12 B004-10 PORT 18 B12-FG1-AP13 PORT 24 B12-FG1-AP19
96-PORT COPPER CONDUCTOR PANEL SHEET
PROJECT #: M1121 ROOM #: D011 PANEL #: *LIF? = LOCATED IN FIELD?
NO LABEL
BUILDING #: 12 RACK #:
96-PORT COPPER PATCH PANNEL
X X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 D009-1 PORT 25 D002-1 PORT 49 D12A-1 PORT 73 D16-19
PORT 2 D009-2 PORT 26 D002-2 PORT 50 D12A-2 PORT 74 D16-20
PORT 3 D009-3 PORT 27 D004-1 PORT 51 D12A-3 PORT 75 D16-21
PORT 4 D009-4 PORT 28 D004-2 PORT 52 D12A-4 PORT 76 D16-22
PORT 5 D009-5 PORT 29 D004-3 PORT 53 D016-5 PORT 77 D16-23
PORT 6 D009-6 PORT 30 D004-4 PORT 54 D016-6 PORT 78 D16-24
PORT 7 D007-1 PORT 31 D008-1 PORT 55 D016-7 PORT 79 D16-25
PORT 8 D007-2 PORT 32 D008-2 PORT 56 D016-8 PORT 80 D16-26
PORT 9 D005-1 PORT 33 D008-3 PORT 57 D016-9 PORT 81 D16-27
PORT 10 D005-2 PORT 34 D008-4 PORT 58 D016-10 PORT 82 D16-28
PORT 11 D005-3 PORT 35 D008-5 PORT 59 D16B-1 PORT 83 D16-29
PORT 12 D005-4 PORT 36 D008-6 PORT 60 D16B-2 PORT 84 D16-30
PORT 13 D03A-1 PORT 37 D008-7 PORT 61 D16B-3 PORT 85 D16-31
PORT 14 D03A-2 PORT 38 D008-8 PORT 62 D16B-4 PORT 86 D16-32
PORT 15 D03A-3 PORT 39 D010-1 PORT 63 D016-11 PORT 87 D16-33
PORT 16 D03A-4 PORT 40 D010-2 PORT 64 D016-12 PORT 88 D16-34
PORT 17 D001-1 PORT 41 D012-1 PORT 65 D016-13 PORT 89 D16-35
PORT 18 D001-2 PORT 42 D012-2 PORT 66 D016-14 PORT 90 D16-36
PORT 19 D001-3 PORT 43 D012-3 PORT 67 D016-15 PORT 91 D16-37
PORT 20 D001-4 PORT 44 D012-4 PORT 68 D016-16 PORT 92 D16-38
PORT 21 D001-5 PORT 45 D016-1 PORT 69 D016-17 PORT 93 D16-39
PORT 22 D001-6 PORT 46 D016-2 PORT 70 D016-18 PORT 94 D16-40
PORT 23 D001-7 PORT 47 D016-3 PORT 71 D16A-1 PORT 95 D16-41
PORT 24 D00001-8 PORT 48 D016-4 PORT 72 D16A-2 PORT 96 D16-42
96-PORT COPPER CONDUCTOR PANEL SHEET
PROJECT #: M1121 ROOM #: D011 PANEL #: *LIF? = LOCATED IN FIELD?
NO LABEL
BUILDING #: 12 RACK #:
96-PORT COPPER PATCH PANNEL
X X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 D016-47 PORT 25 D019-1 PORT 49 D16-61 PORT 73
PORT 2 D016-48 PORT 26 D019-2 PORT 50 D16-62 PORT 74
PORT 3 D016-49 PORT 27 D019-3 PORT 51 D16-57 PORT 75
PORT 4 D016-50 PORT 28 D019-4 PORT 52 D16-58 PORT 76
PORT 5 D016-51 PORT 29 D019-5 PORT 53 D16-59 PORT 77
PORT 6 D016-52 PORT 30 D019-6 PORT 54 D16-60 PORT 78
PORT 7 D016-53 PORT 31 D019-7 PORT 55 D16-35 PORT 79
PORT 8 D016-54 PORT 32 D019-8 PORT 56 D003B-1 PORT 80
PORT 9 D016-55 PORT 33 D019-9 PORT 57 D003B-2 PORT 81
PORT 10 D016-56 PORT 34 D019-10 PORT 58 D018-97 PORT 82
PORT 11 D018-1 PORT 35 D019-11 PORT 59 D018-98 PORT 83
PORT 12 D018-2 PORT 36 D019-12 PORT 60 D018-99 PORT 84
PORT 13 D018-3 PORT 37 D17-1 PORT 61 D013B PORT 85
PORT 14 D018-4 PORT 38 D17-2 PORT 62 PORT 86
PORT 15 D018-5 PORT 39 D17-3 PORT 63 D013A PORT 87
PORT 16 D018-6 PORT 40 D17-4 PORT 64 PORT 88
PORT 17 D018-7 PORT 41 D17-5 PORT 65 PORT 89
PORT 18 D018-8 PORT 42 D17-6 PORT 66 PORT 90
PORT 19 D018-9 PORT 43 D015-1 PORT 67 PORT 91
PORT 20 D018-10 PORT 44 D015-2 PORT 68 PORT 92
PORT 21 D018-11 PORT 45 D015-3 PORT 69 PORT 93
PORT 22 D018-12 PORT 46 D015-4 PORT 70 PORT 94
PORT 23 D018-13 PORT 47 D013-1 PORT 71 PORT 95
PORT 24 D018-14 PORT 48 D013-2 PORT 72 PORT 96
U.S. Department of Veterans Affairs
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED BY DRAWN BY
DRAWING TITLE
APPROVED:
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FLS
PROGRAM
CONTRACTING
ACTIVITY
CENTRAL (PCAC)
JEREMY A. MAXIE
7/13/22
EE-113847
C U s e rs \C a le b K o p p \D o c u m e n ts
\R E
V
IT
L O
C A
L S
\M
E
S E
R
IE
S
B L
D G r2 c k o p p Q
G E
T M
.r v t
/1
/2
:3
:3
P
M
TK-119
PATCH PANEL SCHEDULES
GDM
1000 W STEUBEN STR, UNIT 3
BINGEN,WA 98605
541.436.4723
ADAM GOODIN, PE
EHRM INFRASTRUCTURE
UPGRADES
HOT SPRINGS, SOUTH DAKOTA
568A4-21-702
N/A
Project Director
CKJAM07/13/2022
100% CD FINAL SOLUTIONA/E:
FULLY SPRINKLERED
24-PORT WIRELESS ACCESS POINT PANEL SHEET
PROJECT #: M1121 ROOM #: D011 PANEL #: *LIF? = LOCATED IN FIELD?
NO LABEL
BUILDING #: 12 RACK #: ILLEGIBLE
24-PORT WAP PANEL
X X X X X X X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 B12-FG1-AP17 PORT 7 B12-FG1-B23 PORT 13 PORT 19
PORT 2 B12-FG1-B18 PORT 8 B12-FG1-B24 PORT 14 PORT 20
PORT 3 B12-FG1-B19 PORT 9 B12-FG1-B25 PORT 15 PORT 21
PORT 4 B12-FG1-B20 PORT 10 PORT 16 PORT 22
PORT 5 B12-FG1-B21 PORT 11 PORT 17 PORT 23
PORT 6 B12-FG1-B22 PORT 12 PORT 18 PORT 24
24-PORT COPPER CONDUCTOR PANEL SHEET
PROJECT #: M1121 ROOM #: D011 PANEL #: *LIF? = LOCATED IN FIELD?
BUILDING #: 12 RACK #:
24-PORT COPPER PATCH PANEL
X X X X X X X X X X X X X X X X X X X X X X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 D012-1 PORT 7 D012-7 PORT 13 D16E-5 PORT 19 D16D-3
PORT 2 D012-2 PORT 8 D012-8 PORT 14 D16E-6 PORT 20 D16D-4
PORT 3 D012-3 PORT 9 D16E-1 PORT 15 D16E-7 PORT 21 D16C-1
PORT 4 D012-4 PORT 10 D16E-2 PORT 16 D16E-8 PORT 22 D16C-2
PORT 5 D012-5 PORT 11 D16E-3 PORT 17 D16D-1 PORT 23 D16C-3
PORT 6 D012-6 PORT 12 D16E-4 PORT 18 D16D-2 PORT 24 D16C-4
24-PORT COPPER CONDUCTOR PANEL SHEET
PROJECT #: M1121 ROOM #: D011 PANEL #: *LIF? = LOCATED IN FIELD?
BUILDING #: 12 RACK #:
24-PORT COPPER PATCH PANEL
X X X X X X X X X X X X X X X X X X X X X X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 D16B-1 PORT 7 D16B-7 PORT 13 D16A-1 PORT 19 D16F-7
PORT 2 D16B-2 PORT 8 D16B-8 PORT 14 D16A-2 PORT 20 D16F-8
PORT 3 D16B-3 PORT 9 D16F-1 PORT 15 D16A-3 PORT 21 D16F-9
PORT 4 D16B-4 PORT 10 D16F-2 PORT 16 D16A-4 PORT 22 D16F-10
PORT 5 D16B-5 PORT 11 D16F-3 PORT 17 D16F-5 PORT 23 D16F-11
PORT 6 D16B-6 PORT 12 D16F-4 PORT 18 D16F-6 PORT 24 D16F-12
24-PORT COPPER CONDUCTOR PANEL SHEET
PROJECT #: M1121 ROOM #: D011 PANEL #: *LIF? = LOCATED IN FIELD?
BUILDING #: 12 RACK #:
24-PORT COPPER PATCH PANEL
X X X X X X X X X X X X X X X X X X X X X X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 D16F13 PORT 7 D16F19 PORT 13 D16F25 PORT 19 D16G-3
PORT 2 D16F14 PORT 8 D16F20 PORT 14 D16F26 PORT 20 D16G-4
PORT 3 D16F15 PORT 9 D16F21 PORT 15 D16F27 PORT 21 D16H-1
PORT 4 D16F16 PORT 10 D16F22 PORT 16 D16F28 PORT 22 D16H-2
PORT 5 D16F17 PORT 11 D16F23 PORT 17 D16G-1 PORT 23 D16H-3
PORT 6 D16F18 PORT 12 D16F24 PORT 18 D16G-2 PORT 24 D16H-4
24-PORT COPPER CONDUCTOR PANEL SHEET
PROJECT #: M1121 ROOM #: D011 PANEL #: *LIF? = LOCATED IN FIELD?
BUILDING #: 12 RACK #:
24-PORT COPPER PATCH PANEL
X X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 D16I-1 PORT 7 PORT 13 PORT 19
PORT 2 D16I-2 PORT 8 PORT 14 PORT 20
PORT 3 D16I-3 PORT 9 PORT 15 PORT 21
PORT 4 D16I-4 PORT 10 PORT 16 PORT 22
PORT 5 PORT 11 PORT 17 PORT 23
PORT 6 PORT 12 PORT 18 PORT 24
96-PORT COPPER CONDUCTOR PANEL SHEET
PROJECT #: M1121 ROOM #: A119 PANEL #: *LIF? = LOCATED IN FIELD?
NO LABEL
BUILDING #: 12 RACK #:
96-PORT COPPER PATCH PANNEL
X X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 A135-1 PORT 25 A128-9 PORT 49 A123-1 PORT 73 A101-1
PORT 2 A135-2 PORT 26 A128-10 PORT 50 A123-2 PORT 74 A101-2
PORT 3 A135-3 PORT 27 A128-11 PORT 51 A123-3 PORT 75 A116-1
PORT 4 A135-4 PORT 28 A128-12 PORT 52 A123-4 PORT 76 A116-2
PORT 5 A135-5 PORT 29 A128-13 PORT 53 A122-1 PORT 77 A116-3
PORT 6 A135-6 PORT 30 A128-14 PORT 54 A122-2 PORT 78 A116-4
PORT 7 A135-7 PORT 31 A128-17 PORT 55 A122-3 PORT 79 A116-5
PORT 8 A135-8 PORT 32 A128-18 PORT 56 A122-4 PORT 80 A116-6
PORT 9 A135-9 PORT 33 A128-19 PORT 57 A121-1 PORT 81 A116-7
PORT 10 A135-10 PORT 34 A128-20 PORT 58 A121-2 PORT 82 A116-8
PORT 11 A135-11 PORT 35 A128-21 PORT 59 A121-3 PORT 83 A115-1
PORT 12 A135-12 PORT 36 A128-22 PORT 60 A121-4 PORT 84 A115-2
PORT 13 A128-1 PORT 37 A126-1 PORT 61 A121-5 PORT 85 A115-3
PORT 14 A128-2 PORT 38 A126-2 PORT 62 A121-6 PORT 86 A115-4
PORT 15 A128-3 PORT 39 A126-3 PORT 63 A121-7 PORT 87 A112A-1
PORT 16 A128-4 PORT 40 A126-4 PORT 64 A121-8 PORT 88 A112A-2
PORT 17 A128-5 PORT 41 A125-1 PORT 65 A120-1 PORT 89 A111-1
PORT 18 A128-6 PORT 42 A125-2 PORT 66 A120-2 PORT 90 A111-2
PORT 19 A128-7 PORT 43 A125-3 PORT 67 A120-3 PORT 91 A111-3
PORT 20 A128-8 PORT 44 A125-4 PORT 68 A120-4 PORT 92 A111-4
PORT 21 A129-1 PORT 45 A126-1 PORT 69 A120-5 PORT 93 A111-5
PORT 22 A129-2 PORT 46 A126-2 PORT 70 A120-6 PORT 94 A111-6
PORT 23 A128-15 PORT 47 A126-3 PORT 71 A120-7 PORT 95 A111-7
PORT 24 A128-16 PORT 48 A126-4 PORT 72 A120-7 PORT 96 A111-8
48-PORT COPPER CONDUCTOR PANEL SHEET
PROJECT #: M1121 ROOM #: A119 PANEL #: *LIF? = LOCATED IN FIELD?
NO LABEL
BUILDING #: 12 RACK #: ILLEGIBLE
48-PORT COPPER PATCH PANNEL
X X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 A110-1 PORT 13 PORT 25 A102A-1 PORT 37
PORT 2 A110-2 PORT 14 PORT 26 A102A-2 PORT 38
PORT 3 A110-3 PORT 15 A101-1 PORT 27 A102A-3 PORT 39 A125-5
PORT 4 A110-4 PORT 16 A101-2 PORT 28 A102A-4 PORT 40 A125-6
PORT 5 A109-1 PORT 17 A127-1 PORT 29 A102A-5 PORT 41 A131-1
PORT 6 A109-2 PORT 18 OPEN PORT 30 A102A-6 PORT 42 A131-2
PORT 7 A109-3 PORT 19 A127-3 PORT 31 A104-2 PORT 43
PORT 8 A109-4 PORT 20 A127-4 PORT 32 A105 HALL- PORT 44
PORT 9 A109-5 PORT 21 A103-1 PORT 33 PORT 45
PORT 10 A109-6 PORT 22 A103-2 PORT 34 PORT 46 TELEMETRY
PORT 11 A108-1 PORT 23 A102-1 PORT 35 PORT 47 TELEMETRY
PORT 12 A108-2 PORT 24 A102-2 PORT 36 PORT 48 TELEMETRY
24-PORT WIRELESS ACCESS POINT PANEL SHEET
PROJECT #: M1121 ROOM #: A119 PANEL #: *LIF? = LOCATED IN FIELD?
NO LABEL
BUILDING #: 12 RACK #: ILLEGIBLE
24-PORT WAP PANEL
X X X X X X X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 B12-F01-AP01 PORT 7 B12-F01-AP07 PORT 13 PORT 19
PORT 2 B12-F01-AP02 PORT 8 B12-F01-AP08 PORT 14 PORT 20
PORT 3 B12-F01-AP03 PORT 9 B12-F01-AP09 PORT 15 PORT 21
PORT 4 B12-F01-AP04 PORT 10 PORT 16 PORT 22
PORT 5 B12-F01-AP05 PORT 11 PORT 17 PORT 23
PORT 6 B12-F01-AP06 PORT 12 PORT 18 PORT 24
U.S. Department of Veterans Affairs
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED BY DRAWN BY
DRAWING TITLE
APPROVED:
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FLS
PROGRAM
CONTRACTING
ACTIVITY
CENTRAL (PCAC)
JEREMY A. MAXIE
7/13/22
EE-113847
C U s e rs \C a le b K o p p \D o c u m e n ts
\R E
V
IT
L O
C A
L S
\M
E
S E
R
IE
S
B L
D G r2 c k o p p Q
G E
T M
.r v t
/1
/2
:3
:3
P
M
TK-120
PATCH PANEL SCHEDULES
GDM
1000 W STEUBEN STR, UNIT 3
BINGEN,WA 98605
541.436.4723
ADAM GOODIN, PE
EHRM INFRASTRUCTURE
UPGRADES
HOT SPRINGS, SOUTH DAKOTA
568A4-21-702
N/A
Project Director
CKJAM07/13/2022
100% CD FINAL SOLUTIONA/E:
FULLY SPRINKLERED
PROJECT #: M1121 ROOM #: TB5 PANEL #: *LIF? = LOCATED IN FIELD?
NO LABEL
BUILDING #: 12 RACK #:
96-PORT COPPER PATCH PANNEL
X X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 B105-1 PORT 25 B119-3 PORT 49 B118-1 PORT 73 106A-1
PORT 2 B105-2 PORT 26 B119-4 PORT 50 B118-2 PORT 74 106A-2
PORT 3 B105-3 PORT 27 B121-1 PORT 51 B116-1 PORT 75 B104-1
PORT 4 B105-4 PORT 28 B121-2 PORT 52 B116-2 PORT 76 B104-2
PORT 5 B105-5 PORT 29 B121-3 PORT 53 B116-3 PORT 77 B104-3
PORT 6 B105-6 PORT 30 B121-4 PORT 54 B116-4 PORT 78 B104-4
PORT 7 B107-1 PORT 31 B123-1 PORT 55 B112A-1 PORT 79 C105-1
PORT 8 B107-2 PORT 32 B123-2 PORT 56 B112A-2 PORT 80 C105-2
PORT 9 B107-3 PORT 33 B123-3 PORT 57 B110A-1 PORT 81 C105-3
PORT 10 B107-4 PORT 34 B123-4 PORT 58 B110A-2 PORT 82 C105-4
PORT 11 B107-5 PORT 35 B127-1 PORT 59 B108-1 PORT 83 C106-1
PORT 12 B107-6 PORT 36 B127-2 PORT 60 B108-2 PORT 84 C106-2
PORT 13 B109-1 PORT 37 B127-3 PORT 61 B108A-1 PORT 85 C106-3
PORT 14 B109-2 PORT 38 PORT 62 B108A-2 PORT 86 C106-4
PORT 15 B111-1 PORT 39 B126-1 PORT 63 B106-1 PORT 87 C106-5
PORT 16 B111-2 PORT 40 B126-2 PORT 64 B106-2 PORT 88 C106-6
PORT 17 B115-1 PORT 41 B126-3 PORT 65 B106-3 PORT 89 C106-7
PORT 18 B115-2 PORT 42 B126-4 PORT 66 B106-4 PORT 90 C106-8
PORT 19 B117-1 PORT 43 B124-1 PORT 67 B106-5 PORT 91 C107-1
PORT 20 B117-2 PORT 44 B124-2 PORT 68 B106-6 PORT 92 C107-2
PORT 21 B117-3 PORT 45 B120-1 PORT 69 B106-7 PORT 93 C107-3
PORT 22 B117-4 PORT 46 B120-2 PORT 70 B106-8 PORT 94 C107-4
PORT 23 B119-1 PORT 47 B120-3 PORT 71 B106-9 PORT 95 C108-1
PORT 24 B119-2 PORT 48 B120-4 PORT 72 B106-10 PORT 96 C108-2
96-PORT COPPER CONDUCTOR PANEL SHEET
PROJECT #: M1121 ROOM #: TB5 PANEL #: *LIF? = LOCATED IN FIELD?
NO LABEL
BUILDING #: 12 RACK #:
96-PORT COPPER PATCH PANNEL
X X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 C108-3 PORT 25 D115-1 PORT 49 PORT 73
PORT 2 C108-4 PORT 26 D115-2 PORT 50 PORT 74
PORT 3 D102-1 PORT 27 D115-3 PORT 51 PORT 75
PORT 4 D102-2 PORT 28 D115-4 PORT 52 PORT 76
PORT 5 D102-3 PORT 29 PORT 53 PORT 77
PORT 6 D102-4 PORT 30 PORT 54 PORT 78
PORT 7 D104A-1 PORT 31 PORT 55 PORT 79
PORT 8 D104A-2 PORT 32 PORT 56 PORT 80
PORT 9 D106-1 PORT 33 PORT 57 PORT 81
PORT 10 D106-2 PORT 34 PORT 58 PORT 82
PORT 11 D106-3 PORT 35 PORT 59 PORT 83
PORT 12 D106-4 PORT 36 PORT 60 PORT 84
PORT 13 D112A1 PORT 37 PORT 61 PORT 85
PORT 14 D112A2 PORT 38 PORT 62 PORT 86
PORT 15 D112A3 PORT 39 PORT 63 PORT 87
PORT 16 D112A4 PORT 40 PORT 64 PORT 88
PORT 17 D112B1 PORT 41 PORT 65 PORT 89
PORT 18 D112B2 PORT 42 PORT 66 PORT 90
PORT 19 D112B3 PORT 43 PORT 67 PORT 91
PORT 20 D112B4 PORT 44 PORT 68 PORT 92
PORT 21 D112-1 PORT 45 PORT 69 PORT 93
PORT 22 D112-2 PORT 46 PORT 70 PORT 94
PORT 23 D112-3 PORT 47 PORT 71 PORT 95
PORT 24 D112-4 PORT 48 PORT 72 PORT 96
24-PORT WIRELESS ACCESS POINT PANEL SHEET
PROJECT #: M1121 ROOM #: TB5 PANEL #: *LIF? = LOCATED IN FIELD?
NO LABEL
BUILDING #: 12 RACK #: ILLEGIBLE
24-PORT WAP PANEL
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 PORT 7 PORT 13 PORT 19
PORT 2 PORT 8 PORT 14 PORT 20
PORT 3 PORT 9 PORT 15 PORT 21
PORT 4 PORT 10 PORT 16 PORT 22
PORT 5 PORT 11 PORT 17 PORT 23
PORT 6 PORT 12 PORT 18 PORT 24
U.S. Department of Veterans Affairs
PROJECT NUMBER
BUILDING NUMBER
DRAWING NUMBER
PROJECT TITLE
LOCATION
ISSUE DATE CHECKED BY DRAWN BY
DRAWING TITLE
APPROVED:
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHASE
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
FLS
PROGRAM
CONTRACTING
ACTIVITY
CENTRAL (PCAC)
JEREMY A. MAXIE
7/13/22
EE-113847
C U s e rs \C a le b K o p p \D o c u m e n ts
\R E
V
IT
L O
C A
L S
\M
E
S E
R
IE
S
B L
D G r2 c k o p p Q
G E
T M
.r v t
/1
/2
:3
:3
P
M
TK-121
PATCH PANEL SCHEDULES
GDM
1000 W STEUBEN STR, UNIT 3
BINGEN,WA 98605
541.436.4723
ADAM GOODIN, PE
EHRM INFRASTRUCTURE
UPGRADES
HOT SPRINGS, SOUTH DAKOTA
568A4-21-702
N/A
Project Director
CKJAM07/13/2022
100% CD FINAL SOLUTIONA/E:
FULLY SPRINKLERED
PROJECT #: M1121 ROOM #: C212 PANEL #: *LIF? = LOCATED IN FIELD?
NO LABEL
BUILDING #: 12 RACK #: ILLEGIBLE
48-PORT COPPER PATCH PANNEL
X X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X
PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF? PORT # ROOM # CAT LIF?
PORT 1 B201-D1 PORT 13 B203-D11 PORT 25 B203-D23 PORT 37
PORT 2 B201-D2 PORT 14 B203-D12 PORT 26 B203-D24 PORT 38
PORT 3 B203-D1 PORT 15 B203-D13 PORT 27 B204-D1 PORT 39
PORT 4 B203-D2 PORT 16 B203-D14 PORT 28…