36C26118R0306-009.pdf

PDF 686 KB Posted

Attached to
Activation Warehouse San Jose Federal contract opportunity
Solicitation number
36C26118R0306
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 21

About this file

36C26118R0306 S02 G1-10 LIFE SAFETY SITE PLAN.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Activation Warehouse San Jose, newest first.
File Type Posted
36C26118R0306-0006000.docx DOCX document
36C26118R0306-0006001.pdf PDF
36C26118R0306-0005000.docx DOCX document
36C26118R0306-00004000.docx DOCX document
36C26118R0306-00004001.pdf PDF
36C26118R0306-00003006.pdf PDF
36C26118R0306-00003008.pdf PDF
36C26118R0306-00003013.pdf PDF
36C26118R0306-00003001.pdf PDF
36C26118R0306-00003000.docx DOCX document
36C26118R0306-00003005.pdf PDF
36C26118R0306-00003011.xlsx XLSX spreadsheet
36C26118R0306-00003012.pdf PDF
36C26118R0306-00003003.pdf PDF
36C26118R0306-00003007.pdf PDF
36C26118R0306-00003009.pdf PDF
36C26118R0306-00003002.xlsx XLSX spreadsheet
36C26118R0306-00003004.pdf PDF
36C26118R0306-00003010.xlsx XLSX spreadsheet
36C26118R0306-00002000.docx DOCX document
36C26118R0306-00001000.docx DOCX document
36C26118R0306-012.pdf PDF
36C26118R0306-007.pdf PDF
36C26118R0306-001.docx DOCX document
36C26118R0306-005.docx DOCX document
36C26118R0306-003.docx DOCX document
36C26118R0306-002.xlsx XLSX spreadsheet
36C26118R0306-004.docx DOCX document
36C26118R0306-006.pdf PDF
36C26118R0306-008.pdf PDF
36C26118R0306-010.pdf PDF
36C26118R0306-011.pdf PDF
36C26118R0306-000.docx DOCX document
Show all 33

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

T

R

R

R

T R

T R

R

T R

T R

FH

FH

FH

FH

FH

FH

FH

ELECTRICAL

N O

P A

R K

IN

G

N O

P A

R K

IN

G

NO

PARKING

SITE LIFE SAFETY LEGEND

PROPERTY LINE

FIRE TRUCK ROUTE THROUGH

SITE

FIRE DEPARTMENT CONNECTION

KNOX BOX

MINIMUM STAND OFF

DISTANCE OF 25'-0"

EXISTING FIRE HYDRANT

NEW FIRE HYDRANT

K.B.

FIRE LANE - CURB TO BE PAINTED

RED PER S.J.F.D. REGUALTIONS

DIRECTION OF

VEHICLE TRAFFIC

MINIMUM STAND OFF

DISTANCE OF 25'-0"

PROPERTY LINE

PROPERTY LINE

LOADING

DOCK

SILVER CREEK VALLEY PLACE

S H

A R

E D

E N

T R

Y R

O A

D

SERVICE

ENTRANCE

FUTURE DEVELOPMENT

10 10

VAN

VAN

VAN

VAN

14 14

HIGHWAY 101

FH

FH

FH

FH

FH

FH

SAN JOSE FIRE TRUCK

TURNING RADIUS (TYP.)

K.B. K.B.

FIRE ACCESS

150' - 0"

FIRE ACCESS

150' - 0"

GRASS PAVER SYSTEM

75,000 CAPACITY

RE: CIVIL

SAN JOSE FIRE TRUCK

TURNING RADIUS (TYP.)

ROOF HATCH FOR

FIRE ACCESS

ROOF HATCH FOR

FIRE ACCESS

SPEED BUMP

RE: CIVIL

SPEED BUMP

RE: CIVIL

SPEED BUMP

RE: CIVIL

SPEED BUMP

RE: CIVIL

FUTURE DEVELOPMENT

N.I.C.

FH

K.B.

125' - 0" TYP.

STANDPIPE STANDPIPE

FALL PROTECTION

RAILING

FALL PROTECTION

RAILING

DURESS PHONE

LOCATION RE: ELEC

DURESS PHONE

LOCATION

RE: ELEC

PROFESSIONAL SEAL

C O

P Y

R

IG

H T

C

B

Y H

O E

F E

R W

Y S

O C

K I

A R

C H

IT

E

C T

S L

L C

Drawn:Checked:

Location:

Date:

Project Title:

Dwg. of

Drawing Number:

Project Number:

Building Number:

Approved: Andy Lamendola

Drawing Title:

ARCHITECT/ENGINEERS:CONSULTANTS:

A

B

C

D

E

F

986543 7 o n e an d o n e h al f in ch es o n e fo o t th re e in ch es o n e fo o t

A

B o n e in ch o n e fo o t

C o n e h al f in ch o n e fo o t

E

D th re e q u ar te rs i n ch o n e fo o t o n e q u ar te r in ch o n e fo o t

F

VA FORM 08-6231

o n e ei g h th i n ch o n e fo o t th re e ei g h th s in ch o n e fo o t

Department of Veterans Affairs

Office of Construction and Facilities Management

Project Status:

PLAN

NORTH

PROJECT

NORTH

/2

/2

:0 :0

P

M LIFE SAFETY SITE PLAN VA SAN JOSE COMMUNITY BASED

OUTPATIENT CLINIC

OCTOBER 7, 2016

VA-101-13-R-0077

5855 SILVER CREEK VALLEY PLACE,

SAN JOSE, CA 95138

ISSUED FOR CONSTRUCTION

G1.10

1" = 30'-0"F9 LIFE SAFETY SITE PLAN

Applicable Codes per California State and the City of San Jose::

• 2013 Building Standards Codes (Locally amended 2013 California Building

Code)

• 2013 Fire Code (Locally amended 2013 California Fire Code)

• 2013 California Green Building Standards Code (Title 24, Part 11)

Applicable Codes per VA as specified in the SFO:

• Fire Protection Design Manual (VA) - 2011 edition

• NFPA 101 Life Safety Code - 2009 edition

• NFPA 99 Health Care Facilities Code - 2012 edition

• International Building Code (IBC) Except for Chapter 10 - 2009 edition

• Occupational Safety and Health Administration (OSHA) Standards (Healthcare) -

2004 edition

• Safety Code for Elevators and Escalators, American Society of Mechanical

Engineers (ASME) A 17.1 - 2007 edition

• NFPA 99 Health Care Facilities Code – 2012 edition

• International Energy Conservation Code (IECC) - 2009 edition

• International Fuel Gas Code (IFGC) - 2009 edition

• International Mechanical Code (IMC) - 2006 edition

• International Plumbing Code (IPC) - 2009 edition

Code Summary

Type of Construction: Type II-B Construction per Building Standards Codes, CBC & IBC

Type II (000) Construction per NFPA 101 0-hour, non combustible construction

Height Limitations and Allowable Floor Area (calculated based on Building Standards Codes, CBC & IBC Chapter 5):

Occupancy Classifications:

B (Business) (offices, treatment areas, waiting areas and conference rooms less than 750 ft2) A-3 Cafe & Terrace S-1 Moderate-hazard storage

Incidental Use: n/a

Actual Area Per Story:

First Story 31,412 ft2 Second Story 32,100 ft2 Third Story 32,264 ft2 Total 95,756 ft2

Mixed Use Approach: Separated use of S-1 on the first story only (Section 508.4)

Building Height/Number of Stories:

Allowable Height: 75 feet and 4 stories (Section 504) Actual Height: 47'-8" feet and 3 stories

Passive Fire Resistive Requirements:

Construction materials Noncombustible (Section 602.2) Structural frame 0 hour construction (Table 601) except where required for supporting construction Interior/exterior bearing walls 0 hour construction (Table 601) Roof construction 0 hour construction (Table 601)

Floor construction 0 hour construction (Table 601) Occupancy separations Required for S-1 on first floor only Specific room ratings

Pharmacy Smoke partition separation Storage rooms Greater than 50SF; smoke partition per

Medical record storage 1 hour per SFO 4.2.10 (A) Smoke compartments Not required

Shafts 1 hour fire barrier shaft enclosure Building Standards Codes and CBC Section 713.4 IBC, Section 708.4 NFPA 101, Section 8.6.5

Soiled linen & trash rooms Smoke partitions Medical gas storage 1 hour (NFPA 99 Section 5.1.3.3.2(4))

Exiting:

Number of exits required Three exits per floor are required where the occupant load exceeds 500; else two exits per floor are required

Spaces with one means of egress 49 occupants or less and common path of travel is not exceeded Exit width factors Doors 0.2 inch per person

Stairs 0.3 inch per person Travel distance to an exit From any point not greater than 300 feet

Common path of travel 100 feet in Business and Storage 75 feet in Assembly less than 50 occupants 20 feet in Assembly more than 50 occupants

Dead end corridors 50 feet in Business

LIFE SAFETY CODE NARRATIVE

NO. Description Date tstrong Highlight