36C26118R0306-009.pdf
PDF 686 KB Posted
- Attached to
- Activation Warehouse San Jose Federal contract opportunity
- Solicitation number
- 36C26118R0306
About this file
36C26118R0306 S02 G1-10 LIFE SAFETY SITE PLAN.pdf
View the file
Other files for this federal contract opportunity
Show all 33
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T
R
R
R
T R
T R
R
T R
T R
FH
FH
FH
FH
FH
FH
FH
ELECTRICAL
N O
P A
R K
IN
G
N O
P A
R K
IN
G
NO
PARKING
SITE LIFE SAFETY LEGEND
PROPERTY LINE
FIRE TRUCK ROUTE THROUGH
SITE
FIRE DEPARTMENT CONNECTION
KNOX BOX
MINIMUM STAND OFF
DISTANCE OF 25'-0"
EXISTING FIRE HYDRANT
NEW FIRE HYDRANT
K.B.
FIRE LANE - CURB TO BE PAINTED
RED PER S.J.F.D. REGUALTIONS
DIRECTION OF
VEHICLE TRAFFIC
MINIMUM STAND OFF
DISTANCE OF 25'-0"
PROPERTY LINE
PROPERTY LINE
LOADING
DOCK
SILVER CREEK VALLEY PLACE
S H
A R
E D
E N
T R
Y R
O A
D
SERVICE
ENTRANCE
FUTURE DEVELOPMENT
10 10
VAN
VAN
VAN
VAN
14 14
HIGHWAY 101
FH
FH
FH
FH
FH
FH
SAN JOSE FIRE TRUCK
TURNING RADIUS (TYP.)
K.B. K.B.
FIRE ACCESS
150' - 0"
FIRE ACCESS
150' - 0"
GRASS PAVER SYSTEM
75,000 CAPACITY
RE: CIVIL
SAN JOSE FIRE TRUCK
TURNING RADIUS (TYP.)
ROOF HATCH FOR
FIRE ACCESS
ROOF HATCH FOR
FIRE ACCESS
SPEED BUMP
RE: CIVIL
SPEED BUMP
RE: CIVIL
SPEED BUMP
RE: CIVIL
SPEED BUMP
RE: CIVIL
FUTURE DEVELOPMENT
N.I.C.
FH
K.B.
125' - 0" TYP.
STANDPIPE STANDPIPE
FALL PROTECTION
RAILING
FALL PROTECTION
RAILING
DURESS PHONE
LOCATION RE: ELEC
DURESS PHONE
LOCATION
RE: ELEC
PROFESSIONAL SEAL
C O
P Y
R
IG
H T
C
B
Y H
O E
F E
R W
Y S
O C
K I
A R
C H
IT
E
C T
S L
L C
Drawn:Checked:
Location:
Date:
Project Title:
Dwg. of
Drawing Number:
Project Number:
Building Number:
Approved: Andy Lamendola
Drawing Title:
ARCHITECT/ENGINEERS:CONSULTANTS:
A
B
C
D
E
F
986543 7 o n e an d o n e h al f in ch es o n e fo o t th re e in ch es o n e fo o t
A
B o n e in ch o n e fo o t
C o n e h al f in ch o n e fo o t
E
D th re e q u ar te rs i n ch o n e fo o t o n e q u ar te r in ch o n e fo o t
F
VA FORM 08-6231
o n e ei g h th i n ch o n e fo o t th re e ei g h th s in ch o n e fo o t
Department of Veterans Affairs
Office of Construction and Facilities Management
Project Status:
PLAN
NORTH
PROJECT
NORTH
/2
/2
:0 :0
P
M LIFE SAFETY SITE PLAN VA SAN JOSE COMMUNITY BASED
OUTPATIENT CLINIC
OCTOBER 7, 2016
VA-101-13-R-0077
5855 SILVER CREEK VALLEY PLACE,
SAN JOSE, CA 95138
ISSUED FOR CONSTRUCTION
G1.10
1" = 30'-0"F9 LIFE SAFETY SITE PLAN
Applicable Codes per California State and the City of San Jose::
• 2013 Building Standards Codes (Locally amended 2013 California Building
Code)
• 2013 Fire Code (Locally amended 2013 California Fire Code)
• 2013 California Green Building Standards Code (Title 24, Part 11)
Applicable Codes per VA as specified in the SFO:
• Fire Protection Design Manual (VA) - 2011 edition
• NFPA 101 Life Safety Code - 2009 edition
• NFPA 99 Health Care Facilities Code - 2012 edition
• International Building Code (IBC) Except for Chapter 10 - 2009 edition
• Occupational Safety and Health Administration (OSHA) Standards (Healthcare) -
2004 edition
• Safety Code for Elevators and Escalators, American Society of Mechanical
Engineers (ASME) A 17.1 - 2007 edition
• NFPA 99 Health Care Facilities Code – 2012 edition
• International Energy Conservation Code (IECC) - 2009 edition
• International Fuel Gas Code (IFGC) - 2009 edition
• International Mechanical Code (IMC) - 2006 edition
• International Plumbing Code (IPC) - 2009 edition
Code Summary
Type of Construction: Type II-B Construction per Building Standards Codes, CBC & IBC
Type II (000) Construction per NFPA 101 0-hour, non combustible construction
Height Limitations and Allowable Floor Area (calculated based on Building Standards Codes, CBC & IBC Chapter 5):
Occupancy Classifications:
B (Business) (offices, treatment areas, waiting areas and conference rooms less than 750 ft2) A-3 Cafe & Terrace S-1 Moderate-hazard storage
Incidental Use: n/a
Actual Area Per Story:
First Story 31,412 ft2 Second Story 32,100 ft2 Third Story 32,264 ft2 Total 95,756 ft2
Mixed Use Approach: Separated use of S-1 on the first story only (Section 508.4)
Building Height/Number of Stories:
Allowable Height: 75 feet and 4 stories (Section 504) Actual Height: 47'-8" feet and 3 stories
Passive Fire Resistive Requirements:
Construction materials Noncombustible (Section 602.2) Structural frame 0 hour construction (Table 601) except where required for supporting construction Interior/exterior bearing walls 0 hour construction (Table 601) Roof construction 0 hour construction (Table 601)
Floor construction 0 hour construction (Table 601) Occupancy separations Required for S-1 on first floor only Specific room ratings
Pharmacy Smoke partition separation Storage rooms Greater than 50SF; smoke partition per
Medical record storage 1 hour per SFO 4.2.10 (A) Smoke compartments Not required
Shafts 1 hour fire barrier shaft enclosure Building Standards Codes and CBC Section 713.4 IBC, Section 708.4 NFPA 101, Section 8.6.5
Soiled linen & trash rooms Smoke partitions Medical gas storage 1 hour (NFPA 99 Section 5.1.3.3.2(4))
Exiting:
Number of exits required Three exits per floor are required where the occupant load exceeds 500; else two exits per floor are required
Spaces with one means of egress 49 occupants or less and common path of travel is not exceeded Exit width factors Doors 0.2 inch per person
Stairs 0.3 inch per person Travel distance to an exit From any point not greater than 300 feet
Common path of travel 100 feet in Business and Storage 75 feet in Assembly less than 50 occupants 20 feet in Assembly more than 50 occupants
Dead end corridors 50 feet in Business
LIFE SAFETY CODE NARRATIVE
NO. Description Date tstrong Highlight
File details come from the government source that posted it.