1. REMOVE ALL ELECTRICAL EQUIPMENT, CABLE AND CONDUITS INDICATED BY
DASHED LINES.
2. REMOVE EXISTING CABLE FROM CONDUIT AND RETURN TO VA. CONDUIT TO BE
RE-USED.
SHEET DEMOLITION KEYNOTES
1. PROVIDE NEW 400 AMP 3 PHASE MAIN CIRCUIT BREAKER. SEE ONE-LINE.
2. RE-USE 2 EACH 4" CONDUIT. PROVIDE 2 EACH 4-600 MCM, #2/0 GROUND.
LENGTH OF RUN IS APPROXIMATELY 500 FEET.
SHEET NEW WORK KEYNOTES
C1
PARTIAL POWER RISER ONE-LINE DIAGRAM
BUILDING #01 - MAIN BUILDING DISTRIBUTION - NEW WORK
SCALE: 1/8" = 1'-0"
F1
PARTIAL POWER RISER ONE-LINE DIAGRAM
BUILDING #01 - MAIN BUILDING DISTRIBUTION - DEMOLITION
SCALE: 1/8" = 1'-0"
MRI SWITCHBOARD "1-G-D-C-D3"
277/480V 3Ø, 4W 1200A "MX"
225/3 400/3 100/3 150/3 200/3125/3
PEDSCAN
COMP
RM
"PDU-MBP"
RADIOLOGY
ANGIO
ELECTRICAL
GD04
800/3800/3
800/3800/3
800/3
MBP
ELECTRICAL
1D36
DISTRIBUTION "1-G-D-C-D2"
277/480V 3Ø, 4W 800A
UPS SYSTEM
500 KVA
SWITCHBOARD
"1-G-D-C-D1"
277/480V 3Ø, 4W 800A
ELECTRICAL
GD04
ELECTRICAL
GD04
400/3
"1-2-E-C-D1"
"1C2E2"
250/3
"1-G-D-C-T1"
112.5 KVA
480-208/120V
3Ø, 4W
DRY TYPE
DISTRIBUTION PANEL "1-G-D-C-D4"
120/208V 3Ø, 4W 400A "MDP"
ELECTRICAL
GD04
"MCCA"
"1-1-D-C-D1"
"XR1-1"
ELECTRICAL
1D04A
SWITCHGEAR "42-1-A-E-S1"
2000A MLO, 277/480V, 3∅, 4W "42EDP"
800AF
800AT
DRAW-OUT SWITCHGEAR "42-1-A-N-S2"
2000A MLO, 277/480V, 3∅, 4W "42GMSB"
800AF
800AT
ATS5
(RADIOLOGY)
BUILDING #42
"1-G-A-C-ATS2"
300/3225/3
400/3
225/3
"RPP" "RPP"
GD13
"1-G-D-C-PDU1"
300/3
"RPP"
GA02
225/3
225/3
"RPP2" "RPP2"
GD13
"1-G-D-C-PDU2"
MRI SWITCHBOARD "1-G-D-C-D3"
277/480V 3Ø, 4W 1200A "MX"
225/3 400/3 100/3 150/3 200/3125/3
PEDSCAN
COMP
RM
"PDU-MBP"
RADIOLOGY
ANGIO
ELECTRICAL
GD04
600/3600/3
800/3800/3
800/3
MBP
ELECTRICAL
1D36
DISTRIBUTION "1-G-D-C-D2"
277/480V 3Ø, 4W 800A
"MBPBBL2XX"
UPS SYSTEM
400A
SWITCHBOARD
"1-G-D-C-D1"
277/480V 3Ø, 4W 600A
"MBPBBL"
ELECTRICAL
GD04
ELECTRICAL
GD04
400/3
"1-2-E-C-D1"
"1C2E2"
150/3
45 KVA
4-250 MCM
DISTRIBUTION PANEL "1-G-D-C-D4"
120/208V 3Ø, 4W 400A "MDP"
ELECTRICAL
GD04
"MCCA"
"1-1-D-C-D1"
"XR1-1"
ELECTRICAL
1D04A
SWITCHGEAR "42-1-A-E-S1"
2000A MLO, 277/480V, 3∅, 4W "42EDP"
800AF
800AT
DRAW-OUT SWITCHGEAR "42-1-A-N-S2"
2000A MLO, 277/480V, 3∅, 4W "42GMSB"
800AF
800AT
ATS5
(RADIOLOGY)
BUILDING #42
"1-G-A-C-ATS2"
300/3225/3
300/3
225/3
"RPP" "RPP"
GD13
300/3
"RPP"
GA02
Y
GENERAL SHEET NOTES
1. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT LOCATED OUTDOORS.
REFER TO PLANS FOR EQUIPMENT LOCATIONS.
2. REFER TO PLANS FOR CONSTRAINTS ON PHYSICAL DIMENSIONS AND
CLEARANCE REQUIREMENTS OF EQUIPMENT. PROVIDE EQUIPMENT
DIMENSIONS THAT FALL WITHIN THE CONSTRAINTS OF EACH SPECIFIC
LOCATION.
3. ALL EQUIPMENT SHALL BE CONSTRUCTED AND BRACED FOR THE SEISMIC
CONDITIONS OF THE PROJECT. REFER TO ELECTRICAL SPECIFICATIONS FOR
REQUIREMENTS.
4. PROVIDE PERFORMANCE TESTING FOR GROUND-FAULT PROTECTION
SYSTEMS ON SITE WITH A WRITTEN RECORD OF THIS TEST SUBMITTED TO THE
AUTHORITY HAVING JURISDICTION PER 2011 NEC 230.95(C).
5. ALL SHUT DOWNS MUST BE COORDINATED OFF HOURS ONLY AND MUST BE
COORDINATED W/ VA 3 WEEKS IN ADVANCE.
1 20 .75 2 12 12 12 8 2
2 20 .75 3 12 12 12 8 2,3
3 20 .75 4 12 12 12 8 2,3
4 30 .75 2 10 10 10 8 2
5 30 .75 3 10 10 10 8 2
6 30 .75 4 10 10 10 8 2
7 40 1 2 8 10 8 6 2
8 40 1 3 8 10 8 6 2
9 40 1 4 8 10 8 6 2
10 55 1 2 6 10 8 4 2
11 55 1 3 6 10 8 4 2
12 55 1.25 4 6 10 8 4 2
13 70 1 2 4 8 4 2 2
14 70 1.25 3 4 8 4 2 2
15 70 1.25 4 4 8 4 2 2
16 85 1.25 2 3 8 3 2 2
17 85 1.25 3 3 8 3 2 2
18 85 1.25 4 3 8 3 2 2
19 95 1.25 3 2 8 2 2 2
20 95 1.50 4 2 8 2 2 2
21 130 1.50 3 1 6 2 2 2
22 130 1.50 4 1 6 2 2 2
23 150 2 3 1/0 6 2 1/0 2
24 150 2 4 1/0 6 2 1/0 2
25 175 2 3 2/0 6 2 2/0 2
26 175 2 4 2/0 6 2 2/0 2
27 200 2 3 3/0 6 2 2/0 2
28 200 2.50 4 3/0 6 2 2/0 2
29 230 2.50 3 4/0 4 2 2/0 2
30 230 2.50 4 4/0 4 2 2/0 2
31 255 2.50 3 250 4 1 2/0 2
32 255 2.50 4 250 4 1 2/0 2
33 310 3 3 350 3 1/0 3/0 2
34 310 3 4 350 3 1/0 3/0 2
35 380 3.50 3 500 3 3/0 3/0 2
36 380 4 4 500 3 3/0 3/0 2
37 400 2 EA 2 3 3/0 3 3/0 3/0 2
38 400 2 EA 2.50 4 3/0 3 3/0 3/0 2
39 510 2 EA 2.50 3 250 1 4/0 3/0 2
40 510 2 EA 3 4 250 1 4/0 3/0 2
41 620 2 EA 3 3 350 1/0 4/0 3/0 2,4
42 620 2 EA 3 4 350 1/0 4/0 3/0 2,4
43 760 2 EA 3.50 3 500 1/0 4/0 3/0 2,4
44 760 2 EA 4 4 500 1/0 4/0 3/0 2,4
45 855 3 EA 3 3 300 2/0 4/0 3/0 2,4
46 855 3 EA 3 4 300 2/0 4/0 3/0 2,4
47 1000 3 EA 3.50 3 400 2/0 4/0 3/0 4
48 1000 3 EA 3.50 4 400 2/0 4/0 3/0 4
49 1140 3 EA 4 3 500 3/0 4/0 3/0 4
50 1140 3 EA 4 4 500 3/0 4/0 3/0 4
51 1240 4 EA 3 3 350 3/0 4/0 3/0 4
52 1240 4 EA 3 4 350 3/0 4/0 3/0 4
53 1675 5 EA 4 4 400 4/0 4/0 4/0 4
54 2010 6 EA 4 4 400 250 250 250 4
55 2660 7 EA 4 4 500 350 350 350 4
56 3040 8 EA 4 4 500 500 500 500 4
57 4180 11 EA 4 4 500 500 500 500 4
58 5 EA 4 6
59 5 6
60 10 EA 4 6
CONDUCTOR AND CONDUIT SCHEDULE NOTES
1. CONDUCTORS SHOWN ARE SHOWN FOR EACH CONDUIT WITH
MODIFICATIONS AS NOTED IN NOTE 5. ALL CONDUCTORS SHOWN ARE
THWN UNLESS OTHERWISE NOTED.
2. PROVIDE EQUIPMENT GROUND CONDUCTORS PER TABLE 250-122 WHEN
CIRCUIT BREAKERS ARE SIZED GREATER THAN AMPERE RATING SHOWN
IN TABLE.
3. PROVIDE #10 NEUTRALS FOR MULTIWIRE BRANCH CIRCUITS SERVING
COMPUTERS.
4. GROUND CONDUCTOR SHALL BE OMITTED BETWEEN THE UTILITY
TRANSFORMER AND THE FIRST OVERCURRENT PROTECTIVE DEVICE.
5. SYMBOL SUBSCRIPTS:
"2N": INCLUDE TWO NEUTRAL CONDUCTORS, SIZED AS SCHEDULED
FOR PHASED AND NEUTRAL CONDUCTORS.
"FG": FULL SIZE GROUND, SIZE EQUIPMENT GROUNDING CONDUCTOR
TO BE THE SAME SIZE AS THE PHASE CONDUCTORS.
"HH": NEUTRAL CURRENTS EXIST DUE TO HIGH HARMONIC
"NONLINEAR" LOADS. CURRENT CARRYING CONDUCTORS DERATED
ACCORDINGLY. PROVIDE THE IG/HH SIZE FOR THE EQUIPMENT
GROUNDING CONDUCTOR.
"IG": INCLUDE IG (INSULATED/ISOLATED GROUND CONDUCTOR)
SCHEDULED ALONG WITH GROUND OF EQUIPMENT GROUND
CONDUCTOR.
"SBJ": SUBSTITUTE "SBJ" CONDUCTOR FOR "G" CONDUCTOR SHOWN,
WHICH IS SIZED FOR THE SYSTEM BONDING JUMPER OF THE
SEPARATELY DERIVED SYSTEM.
6. RACEWAY ONLY. CONDUCTORS PROVIDED BY UTILITY.
IG
(E.G.)
SBJIG/HH
GSIZEQTY
CONDUCTOR(NOTE 1)
NOTES
SYM AMP
COPPER CONDUCTOR AND
SUBSCRIPT (NOTE 5)
SCHEDULE NUMBER
CONDUIT SIZE
CONDUIT SCHEDULE
SE
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS:
RPP SCHEMATIC
VAMC, SALT LAKE CITY, UT 84148
ARCHITECT/ENGINEERS: VAMC B.1 UPS AND 660-18-239
2018-05-10
B.01
Office of Construction and Facilities Management
N. FELT
No.7690241-2202
WILLIAM
L
I C
E N
S
E
D
P
R
O
F
E
SS
I O
N
A
L
N
G
I N
E E
R
S
T
A
T
O F
U
T
A
H
324 S. State St., Suite 444
Salt Lake City, UT 84111
385-549-8799 www.rdcea.com
F i l e
N a m e
P
R
D C
D r a w i n g s S h e e t E
E d w g
L a s t
P l o t t e d
P
M
B y p s s
SC
HE
MA
TI
C
DE
SI
GN
EE601
PARTIAL ONE-LINE
DIAGRAMS
WNF PSS
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
File details come from the government source that posted it.