36C25818B0352 600-18-110_HR Lobby_Automatic Door Operators_Section 08 71 13.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25818B0352-0006001.pdf | ||
| 36C25818B0352-0006000.docx | DOCX document | |
| 36C25818B0352-0005000.docx | DOCX document | |
| 36C25818B0352-0004003.pdf | ||
| 36C25818B0352-0004002.pdf | ||
| 36C25818B0352-0004001.pdf | ||
| 36C25818B0352-0004000.docx | DOCX document | |
| 36C25818B0352-0003000.docx | DOCX document | |
| 36C25818B0352-0002000.docx | DOCX document | |
| 36C25818B0352-0002001.docx | DOCX document | |
| 36C25818B0352-0001001.pdf | ||
| 36C25818B0352-0001000.docx | DOCX document | |
| 36C25818B0352-001.docx | DOCX document | |
| 36C25818B0352-002.pdf | ||
| 36C25818B0352-006.pdf | ||
| 36C25818B0352-005.pdf | ||
| 36C25818B0352-003.pdf | ||
| 36C25818B0352-000.docx | DOCX document |
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VA Long Beach Healthcare Center Long Beach, California
VA Project Project 600-18-110 Reconfigure HR Lobby
AUTOMATIC DOOR OPERATORS
08 71 13 - 1
SECTION 08 71 13
AUTOMATIC DOOR OPERATORS
PART 1 - GENERAL
1.1 DESCRIPTION
A. This section specifies equipment, controls and accessories for automatic operation of swing and sliding doors.
1.2 RELATED WORK
A. Aluminum frames entrance work; Section 08 41 13, ALUMINUM-FRAMED ENTRANCES
AND STOREFRONTS.
B. Door hardware; Section 08 71 00, DOOR HARDWARE.
C. Section 28 13 16, ACCESS CONTROL. N/A
D. Glass and glazing of doors and frames; Section 08 80 00, GLAZING.
E. Electric general wiring, connections and equipment requirements; Division 26, ELECTRICAL.
F. Section 28 31 00, FIRE DETECTION AND ALARM.
1.3 QUALITY ASSURANCE
A. Automatic door operators, controls and other equipment shall be products of a manufacturer regularly engaged in manufacturing such equipment for a minimum of three years.
B. One type of automatic door equipment shall be used throughout the building.
C. Equipment installer shall have specialized experience and shall be approved by the manufacturer.
1.4 WARRANTY
A. Automatic door operators shall be subject to the terms of the Manufacturer’s Warranty, except that the Warranty period shall be two years in lieu of one year.
1.5 MAINTENANCE MANUALS
A. In accordance with Section 01 00 00, GENERAL REQUIREMENTS Article titled
"INSTRUCTIONS", furnish maintenance manuals and instructions on automatic door operators.
1.6 SUBMITTALS
A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
B. Manufacturer's literature and data describing operators, power units, controls, door hardware and safety devices.
C. Shop Drawings:
1. Showing location of controls and safety devices in relationship to each automatically operated door.
08 71 13 - 2
2. Showing layout, profiles, product components, including anchorage, accessories, as applicable.
3. Submit templates, wiring diagrams, fabrication details and other information to coordinate the proper installation of the automatic door operators.
D. Submit in writing to Project Engineer that items listed in Article 1.3 are in compliance.
1.7 DESIGN CRITERIA
A. As a minimum automatic door equipment shall comply with the requirements of BHMA
156.10. Except as otherwise noted on drawings, provide operators which will move the doors from the fully closed to fully opened position in three seconds maximum time interval, when speed adjustment is at maximum setting.
B. Equipment: Conforming to UL 325. Provide key operated power disconnect wall switch for each door installation.
C. Electrical Wiring, Connections and Equipment: Provide all motor, starter, controls, associated devices, and interconnecting wiring required for the installation. Equipment and wiring shall be as specified in Division 26, ELECTRICAL.
1.8 APPLICABLE PUBLICATIONS
A. The publications listed below form a part of this specification to the extent referenced.
The publications are referenced in the text by the basic designation only.
B. Builders Hardware Manufacturers Association, Inc. (BHMA):
A156.10-05 ................................. Power Operated Pedestrian Doors (BHMA 1601)
C. National Fire Protection Association (NFPA):
101-09 ........................................ Life Safety Code
D. Underwriters Laboratory (UL):
325-10 ........................................ Door, Drapery, Gate, Louver, and Window Operators and Systems
1.9 DELIVERY AND STORAGE
A. Delivery shall be in factory’s original, unopened, undamaged container with identification labels attached.
PART 2 - PRODUCTS
2.1 SWING DOOR OPERATORS
A. General: Swing door operators shall be of institutional type, door panel size 600 mm to
1250 mm (2'-0" to 5'-0") width, weight not to exceed 300 kg (600 pounds), electric operated for overhead mounting within the header or transom. Furnish metal mounting supports, brackets and other accessories necessary for the installation of operators at the head of the door frames. The motor on automatic door operator shall be provided with an interlock so that the motor will not operate when doors are electrically locked from opening.
08 71 13 - 3
B. Operators shall have checking mechanism providing cushioning action at last part of door travel, in both opening and closing cycle. Operators shall be capable of recycling doors instantaneously to full open position from any point in the closing cycle when control switch is activated. Operators shall, when automatic power is interrupted or shut-off, permit doors to easily open manually without damage to automatic operator system.
C. Operator, enclosed in housing, shall open door by energizing motor and shall stop by electrically reducing voltage and stalling motor against mechanical stop. Door shall close by means of spring energy, and close force shall be controlled by gear system and motor being used as dynamic break without power, or controlled by hydraulic closer in electro-hydraulic operators. System shall operate as manual door control in event of power failure. Opening and closing speeds shall be adjustable:
1. Operator Housing: Housing shall be a minimum of 112 mm (4-1/2 inches) wide by 140 mm (5.5 inches) high aluminum extrusions with enclosed end caps for application to 100 mm (4 inches) and larger frame systems. All structural sections shall have a minimum thickness of 3.2 mm (0.125 inch) and be fabricated of a minimum of 6063-T5 aluminum alloy.
2. Power Operator: Completely assembled and sealed unit which shall include gear drive transmission, mechanical spring and bearings, all located in aluminum case and filled with special lubricant for extreme temperature conditions. Complete unit shall be rubber mounted with provisions for easy maintenance and replacement, without removing door from pivots or frame.
3. Connecting hardware shall have drive arm attached to door with a pin linkage rotating in a self-lubricating bearing. Door shall not pivot on shaft of operator.
4. Electrical Control: Operator shall have a self contained electrical control unit, including necessary transformers, relays, rectifiers, and other electronic components for proper operation and switching of power operator. All connecting harnesses shall have interlocking plugs.
2.2 MICROPRCESSOR CONTROLS
A. The system shall include a multi-function microprocessor control providing adjustable hold open time (1–30 seconds), LED indications for sensor input signals and operator status and power assist close options. Control shall be capable of receiving activation signals from any device with normally open dry contact output. All activation modes shall provide fully adjustable opening speed:
B. The door shall be held open by low voltage applied to the continuous duty motor. The control shall include an adjustable safety circuit that monitors door operation and stops the opening direction of the door if an obstruction is sensed. The motor shall include a recycle feature that reopens the door if an obstruction is sensed at any point during the
08 71 13 - 4 closing cycle. The control shall include a standard three position key switch with functions for ON, OFF, and HOLD OPEN, mounted on operator enclosure, door frame, or wall, as indicated in the architectural drawings.
2.3 SLIDING DOOR OPERATORS
A. General: Sliding doors shall have electric operators, conforming to BHMA A156.10 and the following requirements as applicable. Assembly shall be single or bi-parting sliding doors as shown on drawings.
B. Door Operation: Doors shall be opened by electric motor pulling door from closed to open position and shall stop door by electrically reducing voltage and stalling door against mechanical stop. System shall permit manual control of door in event of power failure.
Opening and closing speeds shall be adjustable. In compliance with NFPA-101, all door panels shall allow "breakout" to the full open position to provide instant egress at any point in the door’s movement.
C. Operators: Completely assembled and sealed electromechanical operating unit, all located in cast aluminum housing and filled with special lubricant for extreme conditions.
Attached to transmission system shall be a minimum 1/8 Hp "DC" shunt-wound permanent magnet motor with sealed ball bearings. Complete unit shall be rubber mounted with provisions for easy maintenance and replacement. Operators shall have adjustable opening and closing cycle. Housing shall be minimum 6063T-5 alloy aluminum not less than .005 mm (125 inch) minimum thickness, 150 mm by 200 mm (6 inch wide by 8 inch high).
D. Sliding Door Hardware Guide Rollers, Door Carrier: Top door carriers shall ride on steel or delrin rollers incorporating sealed bearings with each door having two support rollers and one anti-rise roller. Each roller shall have a minimum of 9 mm (3/8-inch) of vertical adjustment with positive mechanical locks. Each door shall also include two urethane covered oil impregnated bearing bottom rollers attached with 5 mm (3/16-inch) thick formed steel guide brackets. Each door carrier supporting a door leaf shall include a vertical steel reinforcing member to prevent sagging when door is swung under breakaway conditions. All carbon steel brackets and fittings shall be plated for corrosion resistance.
E. Locking Hardware: Do not provide any locking hardware at interior doors not requiring physical security. Provide doors with flush concealed vertical rod panic hardware integrated into the doors where physical security is required and free egress is required at all times. Provide doors with manufacturers’ standard hookbolt lock (keyed both sides) where physical security is required and free egress is not required at all times. At doors with access control devices (card readers, etc.), provide doors with electronic deadbolt locking to prevent the doors from manually sliding open.
08 71 13 - 5
F. Door Closers: Provide all breakout or swing-out panels with door closers concealed in the top rail of the door.
2.4 POWER UNITS
A. Each power unit shall be self-contained, electric operated and independent of the door operator. Capacity and size of power circuits shall be in accordance with automatic door operator manufacturer's specifications and Division 26 – ELECTRICAL.
2.5 DOOR CONTROLS
A. Opening and closing actions of doors shall be actuated by controls and safety devices specified, and conform to ANSI 156.10. Controls shall cause doors to open instantly when control device is actuated; hold doors in open positions; then, cause doors to close, unless safety device or reactivated control interrupts operation.
B. Manual Controls:
1. Push Plate Wall Switch: Recess type, stainless steel push plate minimum 100 mm by 100 mm (four-inch by four-inch), with 13 mm (l/2-inch) high letters "To
Operate Door--Push" engraved on face of plate.
C. Motion Detector: The motion detector may be surface mounted or concealed, to provide a signal to actuate the door operator, and monitor the immediate zone, to detect intrusion by persons, carts or similar objects. The zone which the detector monitors shall be 1500 mm (five feet) deep and 1500 mm (five feet) across, plus or minus 150 mm (six inches) on all dimensions. The maximum response time shall be no less than 25 milliseconds.
Unit shall be designed to operate on 24 volts AC. The control shall not be affected by cleaning material, solvents, dust, dirt and outdoor weather conditions.
2.6 SAFETY DEVICES
A. General: Area over which doors swing or slide shall be a safety section and anyone standing in path of door's movement shall be protected by a safety device.
B. At sliding doors, provide two photoelectric beams mounted at heights of 600 mm (24 inches) and 1200 mm (48 inches) in the door frame on sliding doors. Provide overhead safety presence sensors at door head on each side of the opening. Beams shall parallel door openings to prevent doors from closing when anyone is in the center of the door or doors. When beams are activated, doors shall recycle to full open position. Actuation shall include a motion detector mounted on each side of the door for detection of traffic in each direction.
C. Each swing door shall have installed on the pull side a presence sensor to detect any person standing in the door swing path and prevent the door from opening.
D. Time delay switches shall be adjustable between 3 to 60 seconds and shall control closing cycle of doors.
08 71 13 - 6
E. Decals with sign "In" or "Do Not Enter" shall be installed on both faces of each door where shown.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Coordinate installation of equipment with other related work. Manual controls and power disconnect switches shall be recessed or semi-flush mounted in partitions. Secure operator components to adjacent construction with suitable fastenings. Conceal conduits, piping, and electric equipment, in finish work.
B. Install power units in locations shown. Where units are to be mounted on walls, provide metal supports or shelves for the units. All equipment, including time delay switches, shall be accessible for maintenance and adjustment.
C. Operators shall be adjusted and must function properly for the type o£ traffic
(pedestrians, carts, stretchers and wheelchairs) expected to pass through doors. Each door leaf of pairs of doors shall open and close in synchronization. On pairs of doors, operators shall allow either door to be opened manually without the other door opening.
D. Install controls at positions shown and make them convenient for particular traffic expected to pass through openings. Maximum height of push plate wall switches from finished floors shall be 40 inches unless otherwise approved by the Project Engineer.
3.2 INSTRUCTIONS
A. Following the installation and final adjustments of the door operators, the installer shall fully instruct VA personnel 2 hours on the operating, servicing and safety requirements for the swing and sliding automatic door operators.
B. Coordinate instruction to VA personnel with Project Engineer.
- - - E N D - - -