Technical Questions_36C25725Q0410.docx

DOCX document 18 KB Posted

Attached to
Chilled Water Pump Replacement (7-9 VFD)
Solicitation number
36C25725Q0410
Issued by

About this file

The document is a Technical Questions file for Solicitation 36C25725Q0410, a Chilled Water Pump Replacement project for the Department of Veterans Affairs Veterans Health Administration. The solicitation involves replacing Variable-Frequency Drive (VFD) units for Pumps 7, 8, and 9, as the current Cutler-Hammer HV9000 system is becoming obsolete. The project is a new contract with the contractor responsible for all costs associated with equipment removal and replacement.

Key details include: no badging is required (contractors sign in at the Energy Center), electrical outlets are available on-site, and contractors can park behind the Energy Center or inside the chill plant. The installation will begin once parts are delivered, and system commissioning can be performed during regular work hours. The specific equipment replacement involves an ACH580-BCR-156A-4+F267 drive, and no additional BACnet or LON card is needed to connect to the existing Siemens Apogee System. The project is not tax-exempt, and any contract modifications will require a firm fixed price quote from the vendor before work commences.

View the file

Other files

File Type Posted
SF30 RFQ 36C25725Q0410 0001.docx DOCX document
Site Visit.pdf PDF
Service Contract Act WD 2015-522_12-23-2024.pdf PDF
S02 RFQ 36C25725Q0410.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Technical Questions | 36C25725Q0410 NTX Chilled Water Pump Replacement (7-9 VFD)

1. Is this a brand-new contract?

Answer: Yes

2. Is there a cost estimate, budget, or ballpark figure for the project listed?

Answer: N/A

3. Is there an actual start date for the project?

Answer: Installation will begin once all parts are delivered onsite.

4. Are their more numbers after the +F2 in the Equipment Required Section of your document.

5. Answer: ACH580-BCR-156A-4+F267

6. Is the "+F2" part at the end actually "+F253or F267"?

Answer: F267

7. Would a BACnet or LON card would be needed with the new drives to connect to the existing Siemens Apogee System?

Answer: No

8. Please provide a copy of the Site Visit Attendance Sheet.

Answer: Attached.

9. Please confirm this is not a tax-exempt project.

Answer: No, not tax exempt.

10. In the event of contract modifications, should bond premiums be applied to the individual modification or wait until the end of the job, when a final modification is issued, to reimburse the contractor for all bond overruns for all mods? We ask this because there is a particular clause that states bond premium overruns are to be invoiced at the end of the project for all modifications.

Answer: Any modifications to the contract will require a firm fixed price quote from the vendor before any work is performed.

11. Is badging required for the project?

Answer: No, sign in at the Energy Center.

12. Is any scope of work for this project required to be performed outside of regular work hours?

Answer: No

a. If so, what trades or scopes will be required to be performed outside of regular work hours?

Answer: N/A

b. If so, what will the work hours and days be for scopes required to be performed outside of regular work hours?

Answer: N/A

13. Are electrical outlets available for contractors to connect to in the construction area?

Answer: Yes

a. If not, where are electrical outlets available for contractors to connect to?

Answer: N/A.

14. Where are the designated contractors' and subcontractors' parking area?

Answer: Contractor can park behind the Energy Center, or inside the chill plant during work if no other work is being conducted.

15. Can system commissioning activities be performed during regular hours?

Answer: Yes