This document is a comprehensive Joint Commission fire and life safety inspection report for the Overton Brooks outbuildings, conducted by Johnson Controls on August 12-17, 2024. The inspection covered multiple buildings and systems, including water flow switches, tamper switches, main drain tests, fire department water supply connections, and various sprinkler system components across seven different buildings. The inspection was performed by William "Andy" Rolen, who systematically tested and documented the condition of fire protection equipment, with all tested devices passing inspection and no deficiencies noted.
The report utilized NFPA 25 (2011 edition) standards and included detailed assessments of wet systems, easy riser or shotgun systems, control valves, check valves, gauges, hose valve outlets, and low point drains. Key findings indicate that all systems were functional, with proper water pressures, no external damages, and recent internal pipe inspections completed between February and March 2021. The water supply is a pressure fire pump and tank system, and all sprinkler systems appear to be in good condition, with appropriate clearances, no corrosion, and all necessary extra sprinkler heads and wrenches available on-site.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25625Q1231 0002_1.docx | DOCX document | |
| Att 3.pdf | ||
| SF-30 Amendment 2.pdf | ||
| Att 1 - Antifreeze.pdf | ||
| Att 2 Water Storage Reservoir.pdf | ||
| SF-30 Amendment.pdf | ||
| 36C25625Q1231 0001.docx | DOCX document | |
| 36C25625Q1231_1.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Johnson Controls is committed to serving our customers with the best-in-class services and technologies. Xaap is an advanced inspection reporting application that has been used by Johnson Controls on your inspections.
Xaap is a software-as-a-service (SaaS) solution that provides a streamlined and digitized approach for performing fire and life safety inspections and managing compliance reports in a single, centralized platform.
The application allows inspectors to capture data for fire and life safety systems and devices while generating the required compliance reports directly from their phones. It also provides facility managers, building managers and key stakeholders with a centralized view of all building systems and deficiency data. Users can easily access, download and share historical inspection reports through Xaap.
See how your organization can leverage this smart technology for your internal inspections Visit info.jci.com/xaap-tjc To Learn More
This report is powered by Xaap, the Building Compliance Reporting Platform used by Johnson Controls.
This page is informational only and not part of The Joint Commission Report
This report is powered by https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc
[This Page Intentionally Left Blank]
Inspection Summary
Customer Information
Name Overton Brooks
Building Information
Name Overton Brooks - Outbuildngs
Address 510 E Stoner Ave, Shreveport, LA, 71101
Contact Information
Name Paul Celli
Role Supervisor
E-Mail paul.celli@va.gov
Phone 3182726117
Account Information
Service Provider
Johnson Controls North America
Office Address
3691 Old Shed Road, Bossier City, LA 71111
Office Phone 318-655-9114
Office License
F186
Inspector Name
William “Andy” Rolen
Inspector License
LA - E25457 / Backflow - 20240991
Inspection Information
Start Date 08/12/2024
Date 08/17/2024
Inspection Type
Joint Commission
Work Order# 57425096, 57425098, 57425100, 57425102, 57425104, 57425106
Timezone GMT-05:00
Inspection Summary
The following Tests and Inspections have been covered in this inspection
EP 2 - Tamper Switches and Water Flow Devices
EP 9 - Sprinkler Systems Main Drain
EP 10 - Fire Department Water Supply Connections
NFPA 25
General Inspection Notes
1. Annual Fire Sprinkler Inspection - Green Tagged www.xaapbuildings.com
DEVICE DEFICIENCIES
No device deficiencies in this inspection.
INSPECTION RESULTS SUMMARY
CURRENT INSPECTION RESULTS PREVIOUS INSPECTION RESULTS
TEST PERFORMED DEVICE TYPE TOTAL PASSED FAILED CANNOT INSPECT % INSPECTED TOTAL
EP2 High Pressure Water Alarm Switch 1 1 0 0 100 1
EP2 Tamper Switch 7 7 0 0 100 7
EP2 Water Flow Switch 7 7 0 0 100 7
EP2 Water Motor Gong 2 2 0 0 100 2
EP9 Main Drain - Easy Riser or Shotgun Valve 6 6 0 0 100 6
EP9 Main Drain - Wet Pipe Valve 2 2 0 0 100 2
EP10 Fire Dept. Connection 7 7 0 0 100 7
NFPA 25 Antifreeze System 1 1 0 0 100 1
NFPA 25 Check Valve 9 9 0 0 100 9
NFPA 25 Control Valve 9 9 0 0 100 9
NFPA 25 Easy Riser or Shotgun System 6 6 0 0 100 6
NFPA 25 Gauge 16 16 0 0 100 16
NFPA 25 Hose Valve Outlet 7 7 0 0 100 7
NFPA 25 Inspectors Test Valve 7 7 0 0 100 7
NFPA 25 Low Point Drain 2 2 0 0 100 2
NFPA 25 Pressure Regulating Valve 1 1 0 0 100 1
NFPA 25 Standpipe System 1 1 0 0 100 1
NFPA 25 Wet System 3 3 0 0 100 3
TOTAL 94 94 0 0 100 94
TAMPER SWITCHES AND WATER FLOW DEVICES
CUSTOMER NAME: Overton Brooks
BUILDING NAME: Overton Brooks - Outbuildngs
BUILDING ADDRESS: 510 E Stoner Ave, Shreveport, LA, 71101
CONTACT NAME: Paul Celli
CONTACT E-MAIL: paul.celli@va.gov
CONTACT ROLE: Supervisor
CONTACT PHONE: 3182726117
SERVICE PROVIDER: Johnson Controls North America
OFFICE ADDRESS: 3691 Old Shed Road, Bossier City, LA 71111
OFFICE PHONE: 318-655-9114
OFFICE LICENSE: F186
INSPECTOR: William “Andy” Rolen
INSPECTOR LICENSE: LA - E25457 / Backflow - 20240991
INSPECTION START DATE: 08/12/2024
INSPECTION END DATE: 08/17/2024
WORK ORDER: 57425096, 57425098, 57425100, 57425102, 57425104, 57425106
TIMEZONE: GMT-05:00
INSPECTION RESULTS SUMMARY
CURRENT INSPECTION RESULTS PREVIOUS INSPECTION RESULTS
DEVICE TYPE INVENTORY COUNT PASSED FAILED CANNOT INSPECT % INSPECTED INVENTORY COUNT
Water Flow Switch 7 7 0 0 100 7
High Pressure Water Alarm Switch 1 1 0 0 100 1
Water Motor Gong 2 2 0 0 100 2
Tamper Switch 7 7 0 0 100 7
DEVICE DEFICIENCIES
No device deficiencies in this inspection.
RETIRED DEVICES
No retired devices in this inspection.
Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2
Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2
9ee2a713-2681-49ec-aa72-7093a816ae41 | Tamper Switches and Water Flow Devices | 08/17/2024
Customer: Overton Brooks | Building: Overton Brooks - Outbuildngs
Elements of Performance #2
At least semi-annually, the facility tests water-flow devices and at least semi-annually the facility tests supervisory valve tamper switches. The completion date of the tests is documented.
Valve Tamper Switches and Water Flow devices
For additional guidance on performing tests, see NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2
Device Test Method
Control Valve Tamper Switch:
14.4.2.2-14.(i).(1)
Valve shall be operated and signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacture's specifications
Mechanical, Electro-sonic, or Pressure-Type Water flow Device:
14.4.2.2-14.(j)
Water shall be flowed through an inspector's test connection indicating the flow of water equal to that from a single sprinkler of the smallest orifice size in the system for wet-pipe systems, or an alarm test bypass connection for dry-pipe, pre-action, or deluge systems in accordance with NFPA 25.
A.1.1.1.2 There are times when a single inspection or test can meet the requirements of both NFPA 25 and NFPA 72 (e.g., operation of a tamper switch). This standard does not necessarily require that two separate inspections or tests be conducted on the same component, provided the inspection or test meets the requirements of both standards and the individual performing the inspection or test is qualified to perform the inspection or test required by both standards.
Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2
Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2
9ee2a713-2681-49ec-aa72-7093a816ae41 | Tamper Switches and Water Flow Devices | 08/17/2024
WATER FLOW SWITCH
# LOCATION DESCRIPTION MAKE DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 Building 55 Elevator shaft top sprinkler flow switch (above ceiling)
Water flow switch Water Flow Switch 287005580 Andy Rolen 08/16/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 15
Open test connection/bypass. Did water flow activate the alarm? Yes
2 Building 57 Wet system water flow switch Water flow switch Water Flow Switch 287006206 Andy Rolen 08/16/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 20
Open test connection/bypass. Did water flow activate the alarm? Yes
3 Building 6 Wet system water flow switch Water flow switch Water Flow Switch 287006213 Ethan Williamson 08/16/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 31
Open test connection/bypass. Did water flow activate the alarm? Yes
4 Building 16 Wet system water flow switch Water flow switch Water Flow Switch 287006222 Andy Rolen 08/16/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 15
Open test connection/bypass. Did water flow activate the alarm? Yes
5 Building 42 Wet system water flow switch Water flow switch Water Flow Switch 287013410 Andy Rolen 08/16/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 15
Open test connection/bypass. Did water flow activate the alarm? Yes
6 Building 4 Wet system water flow switch (room
4-17) Water flow switch Water Flow Switch 287005553 Andy Rolen 08/16/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 20
Open test connection/bypass. Did water flow activate the alarm? Yes
7 Building 33 Wet system water flow switch (room
111) Water flow switch Water Flow Switch 287005561 Andy Rolen 08/16/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 15
Open test connection/bypass. Did water flow activate the alarm? Yes
TAMPER SWITCH
# LOCATION DESCRIPTION MAKE DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 Building 55
Elevator shaft top sprinkler valve tamper switch (above ceiling)
Tamper switch Tamper Switch 287005581 Andy Rolen 08/16/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
2 Building 55 Supply test valve tamper switch Tamper switch Tamper Switch 287005576 Andy Rolen 08/16/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2
Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2
9ee2a713-2681-49ec-aa72-7093a816ae41 | Tamper Switches and Water Flow Devices | 08/17/2024
TAMPER SWITCH
3 Building 2 Wet system control valve tamper switch
Snap switch Tamper Switch 287005544 Andy Rolen 08/16/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
4 Building 55 Wet system control valve tamper switch
Tamper switch Tamper Switch 287005574 Andy Rolen 08/16/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
5 Building 57 Wet system control valve tamper switch
Tamper switch Tamper Switch 287005582 Andy Rolen 08/16/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
6 Building 42 Wet system control valve tamper switch
Tamper switch Tamper Switch 287006230 Andy Rolen 08/16/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
7 Building 33 Wet system control valve tamper switch
(room 111) Tamper switch Tamper Switch 287005560 Andy Rolen 08/16/2024 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
WATER MOTOR GONG
# LOCATION DESCRIPTION MAKE DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 Building 55 Water motor alarm Water motor alarm Water Motor Gong 287005572 Andy Rolen 08/16/2024 Passed
Water Motor Alarm Test Valve Closed? Yes
Water Motor Alarm Leak Tight? Yes
Visual Inspection – Is Water Motor Alarm Free of Damage? Yes
Open test connection/bypass. Did water flow activate the alarm? Yes
Is exterior alarm operational? Yes
2 Building 33 Wet system water motor alarm (room 111)
Water motor alarm Water Motor Gong 287005565 Andy Rolen 08/16/2024 Passed
Water Motor Alarm Test Valve Closed? Yes
Water Motor Alarm Leak Tight? Yes
Visual Inspection – Is Water Motor Alarm Free of Damage? Yes
Open test connection/bypass. Did water flow activate the alarm? Yes
HIGH PRESSURE WATER ALARM SWITCH
# LOCATION DESCRIPTION MAKE DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 Building 55 Wet system water flow pressure switch Water pressure switch High Pressure Water
Alarm Switch 287005569 Andy Rolen 08/16/2024 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
Inspector Signature
Inspector Name William “Andy” Rolen Date 08/17/2024
Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2
Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2
9ee2a713-2681-49ec-aa72-7093a816ae41 | Tamper Switches and Water Flow Devices | 08/17/2024
SPRINKLER SYSTEMS MAIN DRAIN
BUILDING NAME: Overton Brooks - Outbuildngs
BUILDING ADDRESS: 510 E Stoner Ave, Shreveport, LA, 71101
CONTACT NAME: Paul Celli
CONTACT E-MAIL: paul.celli@va.gov
CONTACT ROLE: Supervisor
CONTACT PHONE: 3182726117
SERVICE PROVIDER: Johnson Controls North America
OFFICE ADDRESS: 3691 Old Shed Road, Bossier City, LA 71111
OFFICE PHONE: 318-655-9114
OFFICE LICENSE: F186
INSPECTOR: William “Andy” Rolen
INSPECTOR LICENSE: LA - E25457 / Backflow - 20240991
INSPECTION START DATE: 08/12/2024
INSPECTION END DATE: 08/17/2024
WORK ORDER: 57425096, 57425098, 57425100, 57425102, 57425104, 57425106
TIMEZONE: GMT-05:00
INSPECTION RESULTS SUMMARY
CURRENT INSPECTION RESULTS PREVIOUS INSPECTION RESULTS
DEVICE TYPE INVENTORY COUNT PASSED FAILED CANNOT INSPECT % INSPECTED INVENTORY COUNT
Main Drain - Wet Pipe Valve 2 2 0 0 100 2
Main Drain - Easy Riser or Shotgun Valve 6 6 0 0 100 6
DEVICE DEFICIENCIES
No device deficiencies in this inspection.
RETIRED DEVICES
No retired devices in this inspection.
Element of Performance - EP-9 NFPA 25-2011: 13.2.5; 13.3.3.4; Table 13.1.1.2; Table 13.8.1
Joint Commission Standard EC.02.03.05 Element of Performance 9 EP -9
9ee2a713-2681-49ec-aa72-7093a816ae41 | Sprinkler Systems Main Drain | 08/17/2024
Elements of Performance #9
Every 12 months the facility tests the main drains at the system low point or at all system risers. A main drain test shall be conducted annually at each system riser and any time the valve is closed at each system riser or feed main after the control valve has been closed to determine whether there has been a change in the condition of the water supply piping and control valves. The completion date of the tests is documented.
Main Drain
For additional guidance on performing the annual / quarterly tests, see NFPA 25-2011: 13.2.5; 13.3.3.4; Table 13.1.1.2; Table 13.8.1
Device Test Method
Main Drain 1. Record the pressure indicated by the supply water gauge.
2. Close the alarm control valve on alarm valves.
3. Fully open the main drain valve.
4. After the flow has stabilized, record the residual (flowing) pressure indicated by the water supply gauge.
5. Close the main drain valve slowly.
6. Record the time taken for the supply water pressure to return to the original static (non-flowing) pressure.
7. Open the alarm control valve.
** 13.2.5.1 In systems where the sole water supply is through a backflow preventer and/or pressure reducing valves, the main drain test of at least one system downstream of the device shall be conducted on a quarterly basis.
Element of Performance - EP-9 NFPA 25-2011: 13.2.5; 13.3.3.4; Table 13.1.1.2; Table 13.8.1
Joint Commission Standard EC.02.03.05 Element of Performance 9 EP -9
9ee2a713-2681-49ec-aa72-7093a816ae41 | Sprinkler Systems Main Drain | 08/17/2024
MAIN DRAIN - WET PIPE VALVE
1 Building 2 Main drain test Gate valve Main Drain - Wet
Pipe Valve 287005545 Andy Rolen 08/16/2024 Passed
Test Pipe Located? Riser
Size of Test Pipe? 2”
Previous Main Drain Test Date 08/25/2023
Previous Main Drain Static Pressure 175
Previous Main Drain Residual Pressure 168
Static Supply Pressure? 160
Residual Pressure? 150
Time to return to Normal System Pressure? 1 second
Static Pressure after completion of test? 160
Main Drain-PSI Comparable Yes
Main drain opened & free of obstruction discoloration? Yes
2 Building 55 Main drain test Gate valve Main Drain - Wet
Pipe Valve 287005577 Andy Rolen 08/16/2024 Passed
Test Pipe Located? Riser
Size of Test Pipe? 1.25
Previous Main Drain Test Date 08/25/2023
Previous Main Drain Static Pressure 175
Previous Main Drain Residual Pressure 167
Static Supply Pressure? 190
Residual Pressure? 175
Time to return to Normal System Pressure? 1 second
Static Pressure after completion of test? 190
Main Drain-PSI Comparable Yes
Main drain opened & free of obstruction discoloration? Yes
MAIN DRAIN - EASY RISER OR SHOTGUN VALVE
# LOCATION DESCRIPTION MAKE DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 Building 57 Main drain test Gate valve Main Drain - Easy Riser or Shotgun
Valve 287006209 Andy Rolen 08/16/2024 Passed
Test Pipe Located? Riser
Size of Test Pipe? 1.5
Previous Main Drain Test Date 08/25/2023
Previous Main Drain Static Pressure 150
Previous Main Drain Residual Pressure 140
Static Supply Pressure? 160
Residual Pressure? 150
Time to return to Normal System Pressure? 1 second
Static Pressure after completion of test? 150
Element of Performance - EP-9 NFPA 25-2011: 13.2.5; 13.3.3.4; Table 13.1.1.2; Table 13.8.1
Joint Commission Standard EC.02.03.05 Element of Performance 9 EP -9
9ee2a713-2681-49ec-aa72-7093a816ae41 | Sprinkler Systems Main Drain | 08/17/2024
MAIN DRAIN - EASY RISER OR SHOTGUN VALVE
2 Building 6 Main drain test Gate Main Drain - Easy Riser or Shotgun
Valve 287006216 Ethan Williamson 08/16/2024 Passed
Test Pipe Located? Riser
Size of Test Pipe? 1.25
Previous Main Drain Test Date 11/15/2022
Previous Main Drain Static Pressure 176
Previous Main Drain Residual Pressure 167
Static Supply Pressure? 175
Residual Pressure? 162
Time to return to Normal System Pressure? 1 second
Static Pressure after completion of test? 175
3 Building 16 Main drain test Gate valve Main Drain - Easy Riser or Shotgun
Valve 287006225 Andy Rolen 08/16/2024 Passed
Test Pipe Located? Riser
Size of Test Pipe? 1.25
Previous Main Drain Test Date 08/25/2023
Previous Main Drain Static Pressure 174
Previous Main Drain Residual Pressure 169
Static Supply Pressure? 170
Residual Pressure? 160
Time to return to Normal System Pressure? 1 second
Static Pressure after completion of test? 170
Main Drain-PSI Comparable Yes
Main drain opened & free of obstruction discoloration? Yes
4 Building 42 Main drain test Gate valve Main Drain - Easy Riser or Shotgun
Valve 287006231 Andy Rolen 08/16/2024 Passed
Test Pipe Located? Riser
Size of Test Pipe? 1”
Previous Main Drain Test Date 08/25/2023
Previous Main Drain Static Pressure 177
Previous Main Drain Residual Pressure 167
Static Supply Pressure? 175
Residual Pressure? 169
Time to return to Normal System Pressure? 1 second
Static Pressure after completion of test? 174
Main Drain-PSI Comparable Yes
Element of Performance - EP-9 NFPA 25-2011: 13.2.5; 13.3.3.4; Table 13.1.1.2; Table 13.8.1
Joint Commission Standard EC.02.03.05 Element of Performance 9 EP -9
9ee2a713-2681-49ec-aa72-7093a816ae41 | Sprinkler Systems Main Drain | 08/17/2024
MAIN DRAIN - EASY RISER OR SHOTGUN VALVE
5 Building 4 Main drain test
(room 4-17) Angle gate valve
Main Drain - Easy Riser or Shotgun
Valve 287005555 Andy Rolen 08/16/2024 Passed
Test Pipe Located? Riser
Size of Test Pipe? 1.5
Previous Main Drain Test Date 08/25/2023
Previous Main Drain Static Pressure 176
Previous Main Drain Residual Pressure 167
Static Supply Pressure? 175
Residual Pressure? 168
Time to return to Normal System Pressure? 1 second
Static Pressure after completion of test? 176
Main Drain-PSI Comparable Yes
Main drain opened & free of obstruction discoloration? Yes
6 Building 33 Wet system main drain Gate valve
Main Drain - Easy Riser or Shotgun
Valve 287005563 Andy Rolen 08/16/2024 Passed
Test Pipe Located? Building 33
Size of Test Pipe? 2”
Previous Main Drain Test Date 08/25/2023
Inspector Signature
Inspector Name William “Andy” Rolen Date 08/17/2024
Element of Performance - EP-9 NFPA 25-2011: 13.2.5; 13.3.3.4; Table 13.1.1.2; Table 13.8.1
Joint Commission Standard EC.02.03.05 Element of Performance 9 EP -9
9ee2a713-2681-49ec-aa72-7093a816ae41 | Sprinkler Systems Main Drain | 08/17/2024
FIRE DEPARTMENT WATER SUPPLY CONNECTIONS
BUILDING NAME: Overton Brooks - Outbuildngs
BUILDING ADDRESS: 510 E Stoner Ave, Shreveport, LA, 71101
CONTACT NAME: Paul Celli
CONTACT E-MAIL: paul.celli@va.gov
CONTACT ROLE: Supervisor
CONTACT PHONE: 3182726117
SERVICE PROVIDER: Johnson Controls North America
OFFICE ADDRESS: 3691 Old Shed Road, Bossier City, LA 71111
OFFICE PHONE: 318-655-9114
OFFICE LICENSE: F186
INSPECTOR: William “Andy” Rolen
INSPECTOR LICENSE: LA - E25457 / Backflow - 20240991
INSPECTION START DATE: 08/12/2024
INSPECTION END DATE: 08/17/2024
WORK ORDER: 57425096, 57425098, 57425100, 57425102, 57425104, 57425106
TIMEZONE: GMT-05:00
INSPECTION RESULTS SUMMARY
CURRENT INSPECTION RESULTS PREVIOUS INSPECTION RESULTS
DEVICE TYPE INVENTORY COUNT PASSED FAILED CANNOT INSPECT % INSPECTED INVENTORY COUNT
Fire Dept. Connection 7 7 0 0 100 7
DEVICE DEFICIENCIES
No device deficiencies in this inspection.
RETIRED DEVICES
No retired devices in this inspection.
Element of Performance - EP-10 NFPA 25-2011: 13.7; Table 13.1.1.2
Joint Commission Standard EC.02.03.05 Element of Performance 10 EP -1
9ee2a713-2681-49ec-aa72-7093a816ae41 | Fire Department Water Supply Connections | 08/17/2024
Elements of Performance #10
Every quarter the facility inspects all fire department water supply connections. The completion date of the tests is documented.
Fire Department Connections
For additional guidance on performing the tests, see NFPA 25-2011: 13.7; Table 13.1.1.2
Device Test Method
Fire Department Connections
1. The fire department connections are visible and accessible.
2. Couplings or swivels are not damaged and rotate smoothly.
3. Plugs or caps are in place and undamaged.
4. Gaskets are in place and in good condition.
5. Identification signs are in place.
6. The check valve is not leaking.
7. The automatic drain valve is in place and operating properly.
8. The fire department connection clapper(s) is in place and operating properly.
Element of Performance - EP-10 NFPA 25-2011: 13.7; Table 13.1.1.2
Joint Commission Standard EC.02.03.05 Element of Performance 10 EP -1
9ee2a713-2681-49ec-aa72-7093a816ae41 | Fire Department Water Supply Connections | 08/17/2024
FIRE DEPT. CONNECTION
1 Parking garage FDC Standpipe FDC Fire Dept.
Connection 287006200 Andy Rolen 08/16/2024 Passed
FDC Quarterly Questions
Is FDC Visible / Accessible? Yes
Are Couplings / Swivels / Plugs / Caps in place? Yes
Identification Signs In Place? Yes
Check Valve Not Leaking / Gaskets In Good Condition / Ball Drip and Clapper in Place and Operating Properly Yes
FDC Hydrostatic Test Date 07/14/2023
FDC Check Valves Internal Inspection Date 07/14/2023
2 Building 4 FDC wet system FDC Fire Dept.
Connection 287005551 Andy Rolen 08/16/2024 Passed
FDC Quarterly Questions
Is FDC Visible / Accessible? Yes
Are Couplings / Swivels / Plugs / Caps in place? Yes
Identification Signs In Place? Yes
Check Valve Not Leaking / Gaskets In Good Condition / Ball Drip and Clapper in Place and Operating Properly Yes
FDC Hydrostatic Test Date 03/08/2021
FDC Check Valves Internal Inspection Date 03/23/2021
3 Building 55 FDC wet system FDC Fire Dept.
Connection 287005566 Andy Rolen 08/16/2024 Passed
FDC Quarterly Questions
Is FDC Visible / Accessible? Yes
Are Couplings / Swivels / Plugs / Caps in place? Yes
Identification Signs In Place? Yes
Check Valve Not Leaking / Gaskets In Good Condition / Ball Drip and Clapper in Place and Operating Properly Yes
FDC Hydrostatic Test Date 03/12/2021
FDC Check Valves Internal Inspection Date 03/12/2021
4 Building 57 FDC wet system FDC Fire Dept.
Connection 287005585 Andy Rolen 08/16/2024 Passed
FDC Quarterly Questions
Is FDC Visible / Accessible? Yes
Are Couplings / Swivels / Plugs / Caps in place? Yes
Identification Signs In Place? Yes
Check Valve Not Leaking / Gaskets In Good Condition / Ball Drip and Clapper in Place and Operating Properly Yes
FDC Hydrostatic Test Date 02/11/2021
FDC Check Valves Internal Inspection Date 02/11/2021
5 Building 6 FDC wet system FDC Fire Dept.
Connection 287006210 Ethan Williamson 08/16/2024 Passed
FDC Quarterly Questions
Is FDC Visible / Accessible? Yes
Are Couplings / Swivels / Plugs / Caps in place? Yes
Identification Signs In Place? Yes
Check Valve Not Leaking / Gaskets In Good Condition / Ball Drip and Clapper in Place and Operating Properly Yes
FDC Hydrostatic Test Date 02/11/2021
FDC Check Valves Internal Inspection Date 02/11/2021
Element of Performance - EP-10 NFPA 25-2011: 13.7; Table 13.1.1.2
Joint Commission Standard EC.02.03.05 Element of Performance 10 EP -1
9ee2a713-2681-49ec-aa72-7093a816ae41 | Fire Department Water Supply Connections | 08/17/2024
FIRE DEPT. CONNECTION
6 Building 16 FDC wet system FDC Fire Dept.
Connection 287006224 Andy Rolen 08/16/2024 Passed
FDC Quarterly Questions
Is FDC Visible / Accessible? Yes
Are Couplings / Swivels / Plugs / Caps in place? Yes
Identification Signs In Place? Yes
Check Valve Not Leaking / Gaskets In Good Condition / Ball Drip and Clapper in Place and Operating Properly Yes
FDC Hydrostatic Test Date 02/10/2021
FDC Check Valves Internal Inspection Date 02/10/2021
7 Building 2 FDC wet system
(Room 09-2)
FDC
Fire Dept.
Connection
287005548 Andy Rolen 08/16/2024 Passed
FDC Quarterly Questions
Is FDC Visible / Accessible? Yes
Are Couplings / Swivels / Plugs / Caps in place? Yes
Identification Signs In Place? Yes
Check Valve Not Leaking / Gaskets In Good Condition / Ball Drip and Clapper in Place and Operating Properly Yes
FDC Hydrostatic Test Date 03/12/2021
FDC Check Valves Internal Inspection Date 03/12/2021
Inspector Signature
Inspector Name William “Andy” Rolen Date 08/17/2024
Element of Performance - EP-10 NFPA 25-2011: 13.7; Table 13.1.1.2
Joint Commission Standard EC.02.03.05 Element of Performance 10 EP -1
9ee2a713-2681-49ec-aa72-7093a816ae41 | Fire Department Water Supply Connections | 08/17/2024
NFPA 25
BUILDING NAME: Overton Brooks - Outbuildngs
BUILDING ADDRESS: 510 E Stoner Ave, Shreveport, LA, 71101
CONTACT NAME: Paul Celli
CONTACT E-MAIL: paul.celli@va.gov
CONTACT ROLE: Supervisor
CONTACT PHONE: 3182726117
SERVICE PROVIDER: Johnson Controls North America
OFFICE ADDRESS: 3691 Old Shed Road, Bossier City, LA 71111
OFFICE PHONE: 318-655-9114
OFFICE LICENSE: F186
INSPECTOR: William “Andy” Rolen
INSPECTOR LICENSE: LA - E25457 / Backflow - 20240991
INSPECTION START DATE: 08/12/2024
INSPECTION END DATE: 08/17/2024
WORK ORDER: 57425096, 57425098, 57425100, 57425102, 57425104, 57425106
TIMEZONE: GMT-05:00
INSPECTION RESULTS SUMMARY
CURRENT INSPECTION RESULTS PREVIOUS INSPECTION RESULTS
DEVICE TYPE INVENTORY COUNT PASSED FAILED CANNOT INSPECT % INSPECTED INVENTORY COUNT
Antifreeze System 1 1 0 0 100 1
Check Valve 9 9 0 0 100 9
Control Valve 9 9 0 0 100 9
Easy Riser or Shotgun System 6 6 0 0 100 6
Gauge 16 16 0 0 100 16
Hose Valve Outlet 7 7 0 0 100 7
Inspectors Test Valve 7 7 0 0 100 7
Low Point Drain 2 2 0 0 100 2
Pressure Regulating Valve 1 1 0 0 100 1
Standpipe System 1 1 0 0 100 1
Wet System 3 3 0 0 100 3
DEVICE DEFICIENCIES
No device deficiencies in this inspection.
RETIRED DEVICES
No retired devices in this inspection.
NFPA 25, Edition 2011
N
FP
A
9ee2a713-2681-49ec-aa72-7093a816ae41 | NFPA 25 | 08/17/2024
CHECK VALVE
1 Building 6 Antifreeze loop check valve (room A-10)
Swing check Check Valve 287005999 Ethan Williamson 08/16/2024 Passed
What is the Size of this Check Valve 1.25
Annual Visual Inspection Pass
Date of 5 Year Internal Check Valve Inspection 02/11/2021
2 Building 55 FDC check valve Swing check Check Valve 287005567 Andy Rolen 08/16/2024 Passed
What is the Size of this Check Valve 4”
Annual Visual Inspection Pass
Was the 5 Year Internal Check Valve Inspection Completed During This Inspection No
Date of 5 Year Internal Check Valve Inspection 03/12/2021
3 Building 57 FDC check valve Swing check Check Valve 287005584 Andy Rolen 08/16/2024 Passed
What is the Size of this Check Valve 4”
Annual Visual Inspection Pass
Was the 5 Year Internal Check Valve Inspection Completed During This Inspection No
Date of 5 Year Internal Check Valve Inspection 02/11/2021
4 Building 6 FDC check valve Swing check Check Valve 287006212 Ethan Williamson 08/16/2024 Passed
What is the Size of this Check Valve 4”
Annual Visual Inspection Pass
Date of 5 Year Internal Check Valve Inspection 02/11/2021
5 Building 16 FDC check valve Wafer Check Check Valve 287006221 Andy Rolen 08/16/2024 Passed
What is the Size of this Check Valve 4”
Annual Visual Inspection Pass
Was the 5 Year Internal Check Valve Inspection Completed During This Inspection No
Date of 5 Year Internal Check Valve Inspection 02/10/2021
6 Building 4 FDC check valve
(room 4-17) Swing check Check Valve 287005552 Andy Rolen 08/16/2024 Passed
What is the Size of this Check Valve 4”
Annual Visual Inspection Pass
Was the 5 Year Internal Check Valve Inspection Completed During This Inspection No
Date of 5 Year Internal Check Valve Inspection 03/08/2021
7 Building 2 FDC check valve
(Room 09-2) Swing check Check Valve 287005549 Andy Rolen 08/16/2024 Passed
What is the Size of this Check Valve 4”
Annual Visual Inspection Pass
Was the 5 Year Internal Check Valve Inspection Completed During This Inspection No
Date of 5 Year Internal Check Valve Inspection 03/12/2021
8 Parking garage Standpipe FDC
Check Valve Swing check Check Valve 287006201 Andy Rolen 08/16/2024 Passed
What is the Size of this Check Valve 4”
Annual Visual Inspection Pass
Was the 5 Year Internal Check Valve Inspection Completed During This Inspection No
Date of 5 Year Internal Check Valve Inspection 12/31/2017
NFPA 25, Edition 2011
N
FP
A
9ee2a713-2681-49ec-aa72-7093a816ae41 | NFPA 25 | 08/17/2024
CHECK VALVE
9 Building 16 Wet system supply check valve Wafer Check Check Valve 287006220 Andy Rolen 08/16/2024 Passed
What is the Size of this Check Valve 4”
Annual Visual Inspection Pass
Was the 5 Year Internal Check Valve Inspection Completed During This Inspection No
Date of 5 Year Internal Check Valve Inspection 02/10/2021
ANTIFREEZE SYSTEM
# LOCATION DESCRIPTION MAKE DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 Building 6 Antifreeze loop (room
A-10) PG Antifreeze System 287005969 Andy Rolen 08/16/2024 Passed
Size (In Gallons) 18
Antifreeze Information Sign Located on Antifreeze System Main Valve Yes
What Type of Antifreeze Solution is in the System PG
Is the antifreeze solution the correct type for the system piping? Yes
What is the antifreeze protection level (In Degrees) -26
Antifreeze Inspected and Tested Per NFPA 25 Yes
GAUGE
# LOCATION DESCRIPTION MAKE DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 Building 6 Antifreeze loop supply gauge (room A-10)
Water gauge Gauge 287005967 Ethan Williamson 08/16/2024 Passed
Type of Gauge Water
Gauge Date 02/11/2021
2 Building 6 Antifreeze loop system gauge
(room A-10) Water gauge Gauge 287005968 Ethan Williamson 08/16/2024 Passed
Type of Gauge Water
Gauge Date 02/11/2021
3 Building 2 Wet system supply water gauge Water gauge Gauge 287005540 Andy Rolen 08/16/2024 Passed
Type of Gauge Water
Gauge Date 03/22/2021
4 Building 55 Wet system supply water gauge Water gauge Gauge 287005570 Andy Rolen 08/16/2024 Passed
Type of Gauge Water
Gauge Date 03/12/2021
5 Building 16 Wet system supply water gauge Water gauge Gauge 287006218 Andy Rolen 08/16/2024 Passed
Type of Gauge Water
Gauge Date 03/10/2021
6 Building 42 Wet system supply water gauge Water gauge Gauge 287006226 Andy Rolen 08/16/2024 Passed
Type of Gauge Water
Gauge Date 03/12/2021
NFPA 25, Edition 2011
N
FP
A
9ee2a713-2681-49ec-aa72-7093a816ae41 | NFPA 25 | 08/17/2024
GAUGE
7 Building 2 Wet system water gauge Water gauge Gauge 287005541 Andy Rolen 08/16/2024 Passed
Type of Gauge Water
Gauge Date 03/22/2021
8 Building 55 Wet system water gauge Water gauge Gauge 287005571 Andy Rolen 08/16/2024 Passed
Type of Gauge Water
Gauge Date 03/12/2021
9 Building 57 Wet system water gauge Water gauge Gauge 287006208 Andy Rolen 08/16/2024 Passed
Type of Gauge Water
Gauge Date 02/11/2021
10 Building 6 Wet system water gauge Water gauge Gauge 287006211 Ethan Williamson 08/16/2024 Passed
Type of Gauge Water
Gauge Date 02/11/2021
11 Building 16 Wet system water gauge Water gauge Gauge 287006219 Andy Rolen 08/16/2024 Passed
Type of Gauge Water
Gauge Date 02/10/2021
12 Building 42 Wet system water gauge Water gauge Gauge 287006227 Andy Rolen 08/16/2024 Passed
Type of Gauge Water
Gauge Date 03/12/2021
13 Building 4 Wet system water gauge (room 4-17)
Water gauge Gauge 287005554 Andy Rolen 08/16/2024 Passed
Type of Gauge Water
Gauge Date 03/08/2021
14 Building 3 Wet system water gauge (Room 09-2) Water gauge Gauge 287005072 Andy Rolen 08/16/2024 Passed
Type of Gauge Water
Gauge Date 03/12/2021
15 Building 33 Wet system water gauge (room 111)
Water gauge Gauge 287005558 Andy Rolen 08/16/2024 Passed
Type of Gauge Water
Gauge Date 02/10/2021
16 Building 33 Wet system water gauge (room 111)
Water gauge Gauge 287005559 Andy Rolen 08/16/2024 Passed
Type of Gauge Water
Gauge Date 02/10/2021
NFPA 25, Edition 2011
N
FP
A
9ee2a713-2681-49ec-aa72-7093a816ae41 | NFPA 25 | 08/17/2024
STANDPIPE SYSTEM
1 Parking garage Dry standpipe system.
Class 1 Standpipe System 287006202 Andy Rolen 08/16/2024 Passed
Is This a Wet or Dry Standpipe? Dry Standpipe
Define Type Of Standpipe Class 1 (2.5")
What Size Is This Valve? 2.5
Drains Leak Tight Yes
Building Free Of Conditions Exposing Pipe To Freezing Yes
Date of Last Standpipe System Flow Test 07/14/2023
Date of Check Valves Internal Inspection 07/14/2023
Date of Internal Inspection of Standpipe Valve Strainers, Filters, And Restriction Orifices. 07/14/2023
Date of Dry Pipe And Dry Portions Hydro Test 07/14/2023
Date of Gauges Replacement 07/14/2023
Date the internal pipe inspection was performed? 07/14/2023
* Due for a 5 year internal inspection
CONTROL VALVE
# LOCATION DESCRIPTION MAKE DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 Building 55
Elevator shaft top sprinkler control valve (above ceiling)
Butterball Control Valve 287005579 Andy Rolen 08/16/2024 Passed
Is This A Main System, Sub System, Or Auxiliary Control Valve? Sub System
What Size Is This Control Valve? 1”
Easily Accessible? Yes
Signs? Yes
Valve in the Appropriate Open or Closed Position? Yes
Sealed, Locked, and/or Supervised Supervised
Free from External Leaks Yes
2 Building 2 Storage isolation control valve Osy Control Valve 287005547 Andy Rolen 08/16/2024 Passed
Is This A Main System, Sub System, Or Auxiliary Control Valve? Sectional
What Size Is This Control Valve? 2”
Easily Accessible? Yes
Signs? Yes
Valve in the Appropriate Open or Closed Position? Yes
Sealed, Locked, and/or Supervised Locked
Free from External Leaks Yes
Control Valve - Annual Questions
Control Valve Fully Exercised? Yes
NFPA 25, Edition 2011
N
FP
A
9ee2a713-2681-49ec-aa72-7093a816ae41 | NFPA 25 | 08/17/2024
CONTROL VALVE
3 Building 55 Supply test control valve Butterfly Control Valve 287005575 Andy Rolen 08/16/2024 Passed
Is This A Main System, Sub System, Or Auxiliary Control Valve? Main
What Size Is This Control Valve? 2.5”
Easily Accessible? Yes
Signs? Yes
Valve in the Appropriate Open or Closed Position? Yes
Sealed, Locked, and/or Supervised Supervised
Free from External Leaks Yes
4 Building 2 Wet system control valve Osy Control Valve 287005543 Andy Rolen 08/16/2024 Passed
Is This A Main System, Sub System, Or Auxiliary Control Valve? Main
What Size Is This Control Valve? 4”
Easily Accessible? Yes
Signs? Yes
Valve in the Appropriate Open or Closed Position? Yes
Sealed, Locked, and/or Supervised Locked
Free from External Leaks Yes
Control Valve - Annual Questions
Control Valve Fully Exercised? Yes
5 Building 55 Wet system control valve Osy Control Valve 287005573 Andy Rolen 08/16/2024 Passed
Is This A Main System, Sub System, Or Auxiliary Control Valve? Main
What Size Is This Control Valve? 2.5
Easily Accessible? Yes
Signs? Yes
Valve in the Appropriate Open or Closed Position? Yes
Sealed, Locked, and/or Supervised Supervised
Free from External Leaks Yes
6 Building 57 Wet system control valve Butterfly Control Valve 287005583 Andy Rolen 08/16/2024 Passed
Is This A Main System, Sub System, Or Auxiliary Control Valve? Main
What Size Is This Control Valve? 2.5”
Easily Accessible? Yes
Signs? Yes
Valve in the Appropriate Open or Closed Position? Yes
Sealed, Locked, and/or Supervised Supervised
Free from External Leaks Yes
Control Valve - Annual Questions
Control Valve Fully Exercised? Yes
NFPA 25, Edition 2011
N
FP
A
9ee2a713-2681-49ec-aa72-7093a816ae41 | NFPA 25 | 08/17/2024
CONTROL VALVE
7 Building 42 Wet system control valve Butterball Control Valve 287006229 Andy Rolen 08/16/2024 Passed
Is This A Main System, Sub System, Or Auxiliary Control Valve? Main
What Size Is This Control Valve? 2”
Easily Accessible? Yes
Signs? Yes
Valve in the Appropriate Open or Closed Position? Yes
Sealed, Locked, and/or Supervised Supervised
Free from External Leaks Yes
8 Building 3 Wet system control valve (Room 09-2)
Osy Control Valve 287005073 Andy Rolen 08/16/2024 Passed
Is This A Main System, Sub System, Or Auxiliary Control Valve? Sub System
What Size Is This Control Valve? 2.5
Easily Accessible? Yes
Signs? Yes
Valve in the Appropriate Open or Closed Position? Yes
Sealed, Locked, and/or Supervised Supervised
Free from External Leaks Yes
9 Building 33 Wet system control valve (room 111)
Osy Control Valve 287005562 Andy Rolen 08/16/2024 Passed
Is This A Main System, Sub System, Or Auxiliary Control Valve? Main
What Size Is This Control Valve? 4”
Easily Accessible? Yes
Signs? Yes
Valve in the Appropriate Open or Closed Position? Yes
Sealed, Locked, and/or Supervised Supervised
Free from External Leaks Yes
Control Valve - Annual Questions
Control Valve Fully Exercised? Yes
INSPECTORS TEST VALVE
# LOCATION DESCRIPTION MAKE DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 Building 2 ITV wet system Gate valve Inspectors Test Valve 287005550 Andy Rolen 08/16/2024 Passed
Inspectors Test Valve Functional Test Yes
2 Building 55 ITV wet system Gate valve Inspectors Test Valve 287005568 Andy Rolen 08/16/2024 Passed
Inspectors Test Valve Functional Test Yes
3 Building 57 ITV wet system ITV Inspectors Test Valve 287006207 Andy Rolen 08/16/2024 Passed
Inspectors Test Valve Functional Test Yes
4 Building 6 ITV wet system Gate valve Inspectors Test Valve 287005998 Ethan Williamson 08/16/2024 Passed
Inspectors Test Valve Functional Test Yes
5 Building 16 ITV wet system Gate valve Inspectors Test Valve 287006217 Andy Rolen 08/16/2024 Passed
Inspectors Test Valve Functional Test Yes
6 Building 42 ITV wet system Ball valve Inspectors Test Valve 287006233 Andy Rolen 08/16/2024 Passed
Inspectors Test Valve Functional Test Yes
NFPA 25, Edition 2011
N
FP
A
9ee2a713-2681-49ec-aa72-7093a816ae41 | NFPA 25 | 08/17/2024
INSPECTORS TEST VALVE
7 Building 4 ITV wet system
(room 4-9) Gate valve Inspectors Test Valve 287005557 Andy Rolen 08/16/2024 Passed
Inspectors Test Valve Functional Test Yes
HOSE VALVE OUTLET
# LOCATION DESCRIPTION MAKE DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 Parking garage Level B East entry Hose valve Hose Valve Outlet 287006204 Andy Rolen 08/16/2024 Passed
Define Type Of Hose Valve Class 1 (2.5")
What Is The Size Of This Hose Valve? 2.5"
Quarterly - Hose Valve Questions
Hose caps are in place and not damaged. Yes
Hose threads are not damaged. Yes
Valve handles are present and not damaged. Yes
Gaskets are not damaged or showing signs of deterioration. Yes
No leaks are present. Yes
Valves are not obstructed or otherwise not capable of normal operation. Yes
Annual - Hose Valve Questions
Hose Valve Exercised? Yes
2 Parking garage Level B north elevator stairwell Hose valve Hose Valve Outlet 287006203 Andy Rolen 08/16/2024 Passed
Define Type Of Hose Valve Class 1 (2.5")
What Is The Size Of This Hose Valve? 2.5"
Quarterly - Hose Valve Questions
Hose caps are in place and not damaged. Yes
Hose threads are not damaged. Yes
Valve handles are present and not damaged. Yes
Gaskets are not damaged or showing signs of deterioration. Yes
No leaks are present. Yes
Valves are not obstructed or otherwise not capable of normal operation. Yes
Annual - Hose Valve Questions
Hose Valve Exercised? Yes
3 Parking garage Middle of garage level SB Hose connection Hose Valve Outlet 287005595 Andy Rolen 08/16/2024 Passed
Define Type Of Hose Valve Class 1 (2.5")
What Is The Size Of This Hose Valve? 2.5"
Quarterly - Hose Valve Questions
Hose caps are in place and not damaged. Yes
Hose threads are not damaged. Yes
Valve handles are present and not damaged. Yes
Gaskets are not damaged or showing signs of deterioration. Yes
No leaks are present. Yes
Valves are not obstructed or otherwise not capable of normal operation. Yes
Annual - Hose Valve Questions
Hose Valve Exercised? Yes
NFPA 25, Edition 2011
N
FP
A
9ee2a713-2681-49ec-aa72-7093a816ae41 | NFPA 25 | 08/17/2024
HOSE VALVE OUTLET
4 Parking garage North stairs level
SB
Hose connection Hose Valve Outlet 287005597 Andy Rolen 08/16/2024 Passed
Define Type Of Hose Valve Class 1 (2.5")
What Is The Size Of This Hose Valve? 2.5"
Quarterly - Hose Valve Questions
Hose caps are in place and not damaged. Yes
Hose threads are not damaged. Yes
Valve handles are present and not damaged. Yes
Gaskets are not damaged or showing signs of deterioration. Yes
No leaks are present. Yes
Valves are not obstructed or otherwise not capable of normal operation. Yes
Annual - Hose Valve Questions
Hose Valve Exercised? Yes
5 Parking garage West stairs level B Hose connection Hose Valve Outlet 287005593 Andy Rolen 08/16/2024 Passed
Define Type Of Hose Valve Class 1 (2.5")
What Is The Size Of This Hose Valve? 2.5"
Quarterly - Hose Valve Questions
Hose caps are in place and not damaged. Yes
Hose threads are not damaged. Yes
Valve handles are present and not damaged. Yes
Gaskets are not damaged or showing signs of deterioration. Yes
No leaks are present. Yes
Valves are not obstructed or otherwise not capable of normal operation. Yes
Annual - Hose Valve Questions
Hose Valve Exercised? Yes
6 Parking garage West stairs level
SB
Hose connection Hose Valve Outlet 287005599 Andy Rolen 08/16/2024 Passed
Define Type Of Hose Valve Class 1 (2.5")
What Is The Size Of This Hose Valve? 2.5"
Quarterly - Hose Valve Questions
Hose caps are in place and not damaged. Yes
Hose threads are not damaged. Yes
Valve handles are present and not damaged. Yes
Gaskets are not damaged or showing signs of deterioration. Yes
No leaks are present. Yes
Valves are not obstructed or otherwise not capable of normal operation. Yes
Annual - Hose Valve Questions
Hose Valve Exercised? Yes
NFPA 25, Edition 2011
N
FP
A
9ee2a713-2681-49ec-aa72-7093a816ae41 | NFPA 25 | 08/17/2024
HOSE VALVE OUTLET
7 Parking garage West stairs top floor Hose connection Hose Valve Outlet 287005592 Andy Rolen 08/16/2024 Passed
Define Type Of Hose Valve Class 1 (2.5")
What Is The Size Of This Hose Valve? 2.5"
Quarterly - Hose Valve Questions
Hose caps are in place and not damaged. Yes
Hose threads are not damaged. Yes
Valve handles are present and not damaged. Yes
Gaskets are not damaged or showing signs of deterioration. Yes
No leaks are present. Yes
Valves are not obstructed or otherwise not capable of normal operation. Yes
Annual - Hose Valve Questions
Hose Valve Exercised? Yes
LOW POINT DRAIN
# LOCATION DESCRIPTION MAKE DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 Parking garage North stairs level
SB
Low point drain Low Point Drain 287005596 Andy Rolen 08/16/2024 Passed
Monthly Low Point Drain Questions
Has this been drained? Yes
2 Parking garage West stairs level
SB
Low point drain Low Point Drain 287005598 Andy Rolen 08/16/2024 Passed
Monthly Low Point Drain Questions
Has this been drained? Yes
NFPA 25, Edition 2011
N
FP
A
9ee2a713-2681-49ec-aa72-7093a816ae41 | NFPA 25 | 08/17/2024
EASY RISER OR SHOTGUN SYSTEM
# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 Building 57 Wet system Easy Riser or Shotgun
System 287006205 Andy Rolen 08/16/2024 Passed
Make and Model Site built
What Size is This Easy Riser valve? 2.5”
Hydraulic Name Plate Present Yes
Record The Coverage Area Defined On The Hydraulic Plate 1000
Record The GPM On The Hydraulic Plate 377.49
Record The PSI On The Hydraulic Plate 100.67
Easy Riser or Shotgun Systems Weekly - Monthly - Questions
Inspect Check Valve For Exterior Damage Yes
Drains Leak Tight Yes
Trim Piping Leak Tight Yes
Trim Valves In Normal Position Yes
Gauges Reading Normal PSI Yes
Record The Pressure (PSI) Shown On The System Side Pressure Gauge. 150
Date the internal pipe inspection was performed? 02/11/2021
Date of Check Valves Internal Inspection 02/11/2021
Date of Gauges Replacement 02/11/2021
Date of Internal Inspection of Easy Riser or Shotgun Valve Strainers, Filters, And Restriction Orifices. 02/11/2021
Easy Riser or Shotgun Systems 5 Year Questions
All Gauges over 5 Years Replaced Yes
2 Building 6 Wet system Easy Riser or Shotgun
System 287006215 Ethan Williamson 08/16/2024 Passed
Make and Model Reliable Model C
What Size is This Easy Riser valve? 3”
Easy Riser or Shotgun Systems Weekly - Monthly - Questions
Inspect Check Valve For Exterior Damage Yes
Drains Leak Tight Yes
Trim Piping Leak Tight Yes
Trim Valves In Normal Position Yes
Gauges Reading Normal PSI Yes
Record The Pressure (PSI) Shown On The System Side Pressure Gauge. 175
Date the internal pipe inspection was performed? 02/11/2021
Date of Check Valves Internal Inspection 02/11/2021
Date of Gauges Replacement 02/11/2021
Date of Internal Inspection of Easy Riser or Shotgun Valve Strainers, Filters, And Restriction Orifices. 02/11/2021
Easy Riser or Shotgun Systems Quarterly - Semi Annual - Annual - Questions
Did Water Flow Alarm Devices, And Retards Test Satisfactorily? Yes
Inspector Test Opened & Free Of Obstruction / Discoloration Yes
NFPA 25, Edition 2011
N
FP
A
9ee2a713-2681-49ec-aa72-7093a816ae41 | NFPA 25 | 08/17/2024
3 Building 16 Wet system Easy Riser or Shotgun
System 287006223 Andy Rolen 08/16/2024 Passed
Make and Model Tyco CV-1F
What Size is This Easy Riser valve? 2.5”
Easy Riser or Shotgun Systems Weekly - Monthly - Questions
Inspect Check Valve For Exterior Damage Yes
Drains Leak Tight Yes
Trim Piping Leak Tight Yes
Trim Valves In Normal Position Yes
Gauges Reading Normal PSI Yes
Record The Pressure (PSI) Shown On The Water Supply Pressure Gauge. 175
Record The Pressure (PSI) Shown On The System Side Pressure Gauge. 175
Date the internal pipe inspection was performed? 02/10/2021
Date of Check Valves Internal Inspection 02/10/2021
Date of Gauges Replacement 02/10/2021
Date of Internal Inspection of Easy Riser or Shotgun Valve Strainers, Filters, And Restriction Orifices. 02/10/2021
Easy Riser or Shotgun Systems Quarterly - Semi Annual - Annual - Questions
Did Water Flow Alarm Devices, And Retards Test Satisfactorily? Yes
Inspector Test Opened & Free Of Obstruction / Discoloration Yes
Easy Riser or Shotgun Systems 5 Year Questions
All Gauges over 5 Years Replaced Yes
4 Building 42 Wet system Easy Riser or Shotgun
System 287006228 Andy Rolen 08/16/2024 Passed
Make and Model Tyco CV-1F
What Size is This Easy Riser valve? 2”
Easy Riser or Shotgun Systems Weekly - Monthly - Questions
Inspect Check Valve For Exterior Damage Yes
Drains Leak Tight Yes
Trim Piping Leak Tight Yes
Trim Valves In Normal Position Yes
Gauges Reading Normal PSI Yes
Record The Pressure (PSI) Shown On The Water Supply Pressure Gauge. 175
Record The Pressure (PSI) Shown On The System Side Pressure Gauge. 175
Retard Chamber Leak Tight And In Good Condition Yes
Date the internal pipe inspection was performed? 03/12/2021
Date of Check Valves Internal Inspection 03/12/2021
Date of Gauges Replacement 03/12/2021
Date of Internal Inspection of Easy Riser or Shotgun Valve Strainers, Filters, And Restriction Orifices. 03/12/2021
Easy Riser or Shotgun Systems 5 Year Questions
All Gauges over 5 Years Replaced Yes
NFPA 25, Edition 2011
N
FP
A
9ee2a713-2681-49ec-aa72-7093a816ae41 | NFPA 25 | 08/17/2024
5 Building 4 Wet system (room
4-17) Easy Riser or Shotgun
System 287005556 Andy Rolen 08/16/2024 Passed
Make and Model 2000 site built
What Size is This Easy Riser valve? 2.5”
Easy Riser or Shotgun Systems Weekly - Monthly - Questions
Inspect Check Valve For Exterior Damage Yes
Drains Leak Tight Yes
Trim Piping Leak Tight Yes
Trim Valves In Normal Position Yes
Gauges Reading Normal PSI Yes
Record The Pressure (PSI) Shown On The System Side Pressure Gauge. 167
Date the internal pipe inspection was performed? 03/08/2021
Date of Check Valves Internal Inspection 03/08/2021
Date of Gauges Replacement 03/08/2021
Date of Internal Inspection of Easy Riser or Shotgun Valve Strainers, Filters, And Restriction Orifices. 03/08/2021
Easy Riser or Shotgun Systems Quarterly - Semi Annual - Annual - Questions
Did Water Flow Alarm Devices, And Retards Test Satisfactorily? Yes
Inspector Test Opened & Free Of Obstruction / Discoloration Yes
Easy Riser or Shotgun Systems 5 Year Questions
All Gauges over 5 Years Replaced Yes
6 Building 3 Wet system (Room
09-2) Easy Riser or Shotgun
System 287005074 Andy Rolen 08/16/2024 Passed
Make and Model Site built. Stick system
What Size is This Easy Riser valve? 2.5
Easy Riser or Shotgun Systems Weekly - Monthly - Questions
Inspect Check Valve For Exterior Damage Yes
Drains Leak Tight Yes
Trim Piping Leak Tight Yes
Trim Valves In Normal Position Yes
Gauges Reading Normal PSI Yes
Record The Pressure (PSI) Shown On The System Side Pressure Gauge. 165
Date the internal pipe inspection was performed? 03/12/2021
Date of Check Valves Internal Inspection 03/12/2021
Date of Gauges Replacement 03/12/2021
Date of Internal Inspection of Easy Riser or Shotgun Valve Strainers, Filters, And Restriction Orifices. 03/12/2021
Easy Riser or Shotgun Systems Quarterly - Semi Annual - Annual - Questions
Did Water Flow Alarm Devices, And Retards Test Satisfactorily? Yes
Inspector Test Opened & Free Of Obstruction / Discoloration Yes
Easy Riser or Shotgun Systems 5 Year Questions
All Gauges over 5 Years Replaced Yes
NFPA 25, Edition 2011
N
FP
A
9ee2a713-2681-49ec-aa72-7093a816ae41 | NFPA 25 | 08/17/2024
WET SYSTEM
1 Building 2 Wet system Wet alarm valve Wet System 287005546 Andy Rolen 08/16/2024 Passed
Wet Systems - Weekly - Monthly Questions
Make and Model Firematic 4-AV
What Size Is This Wet Pipe Valve 4
Inspect Alarm Valve For Exterior Damage Yes
Drai…